0% found this document useful (0 votes)
165 views40 pages

Electrical Installation Project Overview

The document provides lighting calculations and equipment selection for various rooms in a house plan. It includes calculations of the lumen output needed, number of luminaires required, and lamp selection for the living room, two bedrooms, bathroom, kitchen, and other spaces. It also lists the electrical equipment for the installation and provides panel diagrams, installation diagrams, circuit diagrams, and a grounding diagram. Power consumption and costs are summarized.

Uploaded by

Olga Oktaviani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
165 views40 pages

Electrical Installation Project Overview

The document provides lighting calculations and equipment selection for various rooms in a house plan. It includes calculations of the lumen output needed, number of luminaires required, and lamp selection for the living room, two bedrooms, bathroom, kitchen, and other spaces. It also lists the electrical equipment for the installation and provides panel diagrams, installation diagrams, circuit diagrams, and a grounding diagram. Power consumption and costs are summarized.

Uploaded by

Olga Oktaviani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

FINAL PROJECT

ELECTRICAL INSTALLATION

Written By:
AQMALDINA INAY SAFWINA
STATE POLYTECHNIC OF MALANG
1941150008
TABLE OF CONTENT

TABLE OF CONTENT ....................................................................................................................... 1


I. HOUSE PLAN................................................................................................................................ 2
II. LIGHTING CALCULATION ........................................................................................................ 3
i. Living Room ..................................................................................................................... 3
ii. Bedroom 1 ......................................................................................................................... 3
iii. Bedroom 2 ......................................................................................................................... 4
iv. Bathroom ........................................................................................................................... 5
v. Kitchen .............................................................................................................................. 6
vi. N space .............................................................................................................................. 6
vii. A space .............................................................................................................................. 7
viii. Terrace .............................................................................................................................. 8
III. LIST OF EQUIPMENT .............................................................................................................. 12
IV. PANEL DIAGRAM..................................................................................................................... 22
V. ELECTRICAL EQUIPMENT ...................................................................................................... 23
VI. CABLE SELECTION:LINE, NEUTRAL, PE ............................................................................ 24
i. Group 1 ........................................................................................................................... 24
ii. Group 2 ........................................................................................................................... 25
VII. INSTALLATION DIAGRAM .................................................................................................. 28
VIII. CIRCUIT DIAGRAM ............................................................................................................... 29
i. All Group ........................................................................................................................ 29
ii. Group 1 ........................................................................................................................... 30
iii. Group 2 ........................................................................................................................... 31
IX. GROUNDING DIAGRAM ........................................................................................................ 32
X. SINGLE LINE DIAGRAM .......................................................................................................... 34
XI. POWER RECAPITULATION .................................................................................................... 35
i. Recapitulation At Home.................................................................................................. 35
ii. Tariff Group per Day And Month .................................................................................. 35
XII. BILL OF QUANTITY ................................................................................................................ 38
XIII. REFERENCE ............................................................................................................................. 39

1
I. HOUSE PLAN
With Using AutoCAD 2018 Applications:

30 30

TERRACE

30
N SPACE
35

BEDROOM 2
BEDROOM 1

60
A SPACE
LIVING ROOM

30,01
TERRACE
25
15

KITCHEN BATHROOM

25 25 20

2
II. Lighting Calculation

1. Living Room

 Dimension = 2m X 3m
= 6m²
𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 6
=
0.5 × 0.8

1500
=
0.4
= 3750 Lumen
𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

3750
=
2500 × 1

= 1.5 Luminaire ̴ 1 lamp

 Type of Lamp
ND 23.5-150W E27 827 A80 “ CorePro LED bulbs – 120W-150W

 Color Rendering Index : 80 (Good)


 Color Temperature : 2700K (Warm White)
 Power : 1 × 22.5 = 22.5 W

2. Bedroom 1
 Dimension = 3m × 3.5m
= 10.5 m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 10.5
=
0.5 × 0.8

= 6562.5 Lumen (Lumentation needed)

3
𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

6562.5
=
2500 × 2

= 1.3 Luminaire ̴ 2 (lamps needed)

 Type of Lamp
Ultra Efficiency 1200mm UE 14.5W 840 T8 “Master LEDtube T8 Ultra Output”

 Color Rendering Index : 83 (Good)


 Color Temperature : 4000K (Natural White)
 Power : 2×14.5 = 29 W

3. Bedroom 2

 Dimension = 3m × 3m
= 9m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 9
=
0.5 × 0.8
= 5625 𝐿𝑢𝑚𝑒𝑛 (Lumentation needed)
𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

5625
=
2500 × 2
= 1.1Luminaire ̴ 2 (Lamps Needed)

4
 Type Of lamp
Ultra Efficiency 1200mm UE 14.5W 840 T8 “Master LEDtube T8 Ultra Output”

 Color Rendering Index : 83 (Good)


 Color Temperature : 4000K (Natural White)
 Power : 2×14.5 = 29 W

4. Bathroom

 Dimension = 2.5m × 1.5m


= 3.75 m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 3.75
=
0.5 × 0.8

= 2343.75 Lumen (Lumentation needed)

𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

2343.75
=
1521 × 1
= 1.5 Luminaire ̴ 1 (Lamps Needed)

 Type Of Lamp
12.5-100W A60 E27 840 “CorePro LED bulbs – 75/100W”

 Color Rendering Index : 80 (Good)


 Color Temperature : 4000K (Natural White)
 Power : 1 × 12.5 = 12.5 W

5
5. Kitchen

 E = 250 lux
 Dimension = 2.5m × 2.5m
= 6.25m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 6.25
=
0.5 × 0.8

= 3906.25 lumen (Lumentation needed)


𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

3906.25
=
2500 × 1

= 1.5 luminaire ̴ 1 (Lamps needed)

 Type Of Lamp
ND 23.5-150W E27 827 A80 “CorePro LED bulbs – 120W – 150W”

 Color Rendering Index : 80 (Good)


 Color Temperature : 2700K (Warm White)
 Power : 1 × 22.5 = 22.5 W

6. N Space

 Dimension = 3m × 1m
= 3m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 ×3
= = 1875 lumen (lumentation needed)
0.5 ×0.8

𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

1875
=
1521 × 1

= 1.2 luminaire ̴ 1 (Lamp needed)

6
 Type Of Lamp
ND 13-100W A60 E27 827 “CorePro LED bulb”

 Color Rendering Index : 80 (Good)


 Color Temperature : 2700K (Warm White)
 Power : 1 × 13 = 13 W

7. A Space

 Dimension = 2.5m × 1.5m


= 3.75m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 3.75
=
0.5 × 0.8

= 2343.75 lumen (lumentation needed)

𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

2343.75
=
1521 × 1

= 1.5 luminaire ̴ 1 (Lamp needed)

 Type Of Lamp
ND 13-100W A60 E27 827 “CorePro LED bulb”

 Color Rendering Index : 80 (Good)


 Color Temperature : 2700K (Warm White)
 Power : 1 × 13 = 13 W

7
8. Terrace

 Dimension = 6m × 1m
= 6m²

𝐸 ×𝐴
 𝐹 𝑡𝑜𝑡𝑎𝑙 = 𝐾𝑝 ×𝐾𝑑

250 × 6
=
0.5 × 0.8

= 3750 lumen (lumentation needed)

𝐹𝑡𝑜𝑡
 𝑁 𝑡𝑜𝑡𝑎𝑙 = 𝐹1×𝑁

3750
=
1521 × 2

= 1.2 luminaire ̴ 2 (Lamps needed)

 Type Of Lamp
12.5-100W A60 E27 840 “CorePro LED bulb-75/100W”

 Color Rendering Index : 80 (Good)


 Color Temperature : 4000K (Natural White)
 Power : 2 × 12.5 = 25 W

8
Table 1: Minimum lighting levels and recommended color rendering

MINIMUM LIGHTING LEVELS AND RECOMMENDED COLOR RENDERING

COLOR
LIGHTING
ROOM FUNCTION RENDERATION EXPLANATION
LEVELS (lux)
GROUP
RESIDENTIAL
HOUSE
Terrace 60 1 or 2
Living Room 120 ~ 250 1 or 2
Dining Room 120 ~ 250 1 or 2
Workspace 120 ~ 250 1
Bed Room 120 ~ 250 1 or 2
Bathroom 250 1 or 2
Kitchen 250 1 or 2
Garage 60 3 or 4
Warehouse 100 3

For places that require


Prayer Room 200 1 or 2 higher lighting levels, local
lighting can be used.

Table 2: Coefficient of utilization

TYPE OF LIGHT
ESTIMATED USAGE
DISTRIBUTION (TYPE OF
COEFFICIENT
LIGHTING)
Direct Lighting 0,60 until 0,45
Semi Direct 0,55 until 0,40
Diffused 0,50 until 0,35
Semi Indirect 0,45 until 0,35
Indirect 0,35 until 0,20
Indirect (decorative lighting on the
0,20 until 0,10
wall)

9
Table 3: Color Rendering

COLOR
COLOR RENDERING COLOR
RENDERING QUALITY
INDEX RANGE LOOKS
GROUP
Cool
1 Ra > 85 Neutral Very Good
Warm
Cool
2 70 < Ra < 85 Neutral Good
Warm
3 40 < Ra < 70 Medium
4 Ra < 40 Poor

10
Table 4: Color Temperature

11
III. LIST OF EQUIPMENT

1. CABLES
 Types : - NYA
Cross Section = 1.5 mm²
= 4 mm²
- NYM
Cross section = 2.5 mm²
4 mm²
 Cross Section NYA :
i. Tube lamp

 Power = 29 Watt (2Lamps)


 V = 220 V
 PF = 0.7
 P = V × I × PF
29= 220 × I × 0.7
I = 29 / 154
= 0.18 A
 CCC = 125% × I
CCC = 1.25 × 0.18
= 0.225 A

 Temperature = 30°C
CCC Cable = 0.225 / 1
= 0.225 A

 Cross Section Based on Table on PUIL 2011


Cross Section = 1.5 𝑚𝑚2

12
ii. LED Bulb

 Power = 108.5 Watt


 V = 220 V
 PF = 0.9
 P = V × I × PF
108.5= 220 × I × 0.9
I = 108.5 / 198
= 0.55 A
 CCC = 125% × I
CCC = 1.25 × 0.55
= 0.6875 A

13
 Temperature = 30°C
CCC Cable = 0.6875 / 1
= 0.6875 A

Cross Section Based on Table on PUIL 2011


Cross Section = 1,5 𝑚𝑚2

 Cross Section NYM : 2.5 𝑚𝑚2

 Colors
- Blue : Phase
- Black : Neutral
- Yellow-Green : Grounding

14
 Length
NYA Cable = 50 M

 Drop Voltage NYA Cable


Tube Lamp
 ΔV = I × Xa
ΔV = 0.18 × (1.15 × 0.05)
ΔV = 0.18 × 0.0575
ΔV = 0.01035 V
ΔV (%) = 0.01035 / 220X100
ΔV (%) = 4.70 ~ Less Than 5%

Led bulb
 ΔV = I × Xa
ΔV = 0.55 × (3.08 × 0.05)
ΔV = 0.55 × 0.154
ΔV = 0.0847 V
ΔV (%) = 0.0847 / 220X100
ΔV (%) = 3.85 ~ Less Than 5%

15
2. LAMPS AND FIXTURES

I. Fixtures
Type:
 Fluorescent High Bay Luminaires
 Quantity: 2

 LED bulb
Quantity: 7

II. Lamps
 Type :

1) ND 23.5-150W E27 827 A80 “ CorePro LED bulbs – 120W-150W

16
2) Ultra Efficiency 1200mm UE 14.5W 840 T8 “Master LEDtube T8 Ultra Output”

3) 12.5-100W A60 E27 840 “CorePro LED bulbs – 75/100W”

4) ND 13-100W A60 E27 827 “CorePro LED bulb”

3. SOCKET OUTLET

 Type F
Rating: 16 A 250V~
Quantity: 4

4. CONDUIT

 Type : PVC Conduit


 Size : 50 mm
 Length : 20mm

17
5. CLAMPS

 Size : 20mm
 Quantity : 10 pack

20 mm PVC
6. MCB

 Type : MCB Type C


 Rating : 4A / 220V
10A / 220V
 Quantity : 2

 Type : MCB Type C


 Rating : 16A /220V
 Quantity : 1

18
7. TERMINALS
- Type : 12 pole
Rating: 25A / 600V
Quantity: 2 pcs

8. JUNCTION BOX

- Type T – Junction
Quantity: 8

- Type:
Quantity: 3

9. SWITCHES
- Type :
 Single Pole Switch
Quantity: 5

19
 Double Pole Switch
Quantity: 2

10. WIRE NUT


Quantity : 20 pcs

11. PANEL BOX


Quantity: 1

20
12. GROUNDING ROD
Quantity: 1
Type: Copper
Dimension: ¾ inch
Length: 2 meters
Quantity: 1

21
IV. PANEL DIAGRAM : GROUPING
This Panel Use 1 Main MCB and 2 Group for the House
1. Group 1 used for the Lamp
2. Group 2 used for the Switch and Socket
3. Group 3 used for Emergency

L N L N PE L N
G1 G1 G2 G2 G2 G3 G3

N PE

G1 G2 G3

APP

L N PE

SCALE 1 : 1
PANEL DIAGRAM
D : INAY C : [Link] A4 02
POLINEMA DT : DT : D-IV SKL 1A

22
V. ELECTRICAL EQUIPMENT

30 30

30
35

60
30,01
25
15

25 25 20

23
VI. CABLE SELECTION : LINE, NEUTRAL,PE
1. Group 1 (For Lamp)
Group 1
Voltage Total Total
Loads Power (W) Current (A) Quantity
(V) Power (W) Current (A)
Lamps 1 22.5 W 1,136 A 220 V 2 44 W 2.272 A
Lamps 2 14.5 W 0.18 A 220 V 4 58 W 0.36 A
Lamps 3 12.5 W 0.063 A 220 V 3 37.5 W 0.189 A
Lamps 4 13 W 0.065 A 220 V 2 26 W 0.13 A
TOTAL 165.5 W 2.951 A

 Current Carrying Capacity


CCC = 1,25 × 2.951
= 3.7 A
 Derating Factor
 Temperature 40° = 0.87
3.7 A / 0.87 = 4.25 A
 Installation Method
Method E = 23
Cross Section = 2.5 mm²

 Type of Cable : NYA


 Selected Cross Section : 1,5 mm²
 Color :

24
- Black : Phase
- Blue : Neutral
- Yellow- Green: Grounding

 Length : 50m
 Drop Voltage
ΔV = I × Xa
ΔV = 2.951×(1.15 × 0.05)
ΔV = 0.168 V

2. Group 2 (For Socket)


Group 2
Total Total
Power Current Voltage
Load Quantity Power Current
(VA) (A) (V)
(VA) (A)
Socket 200 VA 0.9 A 220 V 4 800 VA 3.6 A

 Current Carrying Capacity


CCC = 1,25 × 3.6
= 4.5 A
 Derating Factor
o Temperature 40° = 0.87
4.5 A / 0.87 = 5.17 A
o Installation Method
Method E = 23
Cross Section = 2.5 mm²

25
 Type of Cable : NYM
 Selected Cross Section : 2,5 mm²
 Color :

- Black : Phase
- Blue : Neutral
- Yellow- Green: Grounding

 Length : 50 m
 Drop Voltage
ΔV = I × Xa
ΔV = 3.6 ×(1.15 × 0.05)
ΔV = 0.207 V

26
Cable Selection Based on PUIL 2011

The selected cable and MCB


 Main Circuit
1) NYA 4mm²
o Phase (red) 1m
o Neutral (blue) 1m
o Ground (yellow stripe green) 9m
2) MCB 10A type C
 Branch Circuit
1) NYA 4mm²
o Phase (red) 1m
o Neutral (blue) 1m
o Ground (yellow stripe green) 1m
 End circuit
o Group 1
 NYA 1,5mm²
 Phase (red) 55m
 Neutral (blue) 55m
 Ground (yellow stripe green) 55m
 MCB 4A type C
o Group 2
 NYM 2,5mm²
 Phase (red) 55m
 Neutral (blue) 55m
 MCB 10A type C

27
VII. INSTALLATION DIAGRAM

I
C B
A

B
C D
A

E
D
I
H

F
G
G

H
F

28
VIII. CIRCUIT DIAGRAM

This is circuit diagram for all group

29
CIRCUIT DIAGRAM FOR GROUP 1

30
CIRCUIT DIAGRAM FOR GROUP 2

31
IX. GROUNDING DIAGRAM
Grounding (Earthing) is a series / network starting from the poles earthing / electrode, connecting
conductor to the terminal earthing which serves to channel more current to the earth so that it can provide
protection against humans from electric shock, and secure installation components so that they can avoid
danger foreign currents and voltages, as well as devices can operate in accordance with proper technical
provisions.

32
Type of grounding:
TN-S (TERRE NEUTRAL - SEPARATE)
TNC-S (TERRE NEUTRAL - COMBINED - SEPARATE)
TT (DOUBLE TERRE)
TN-C (TERRE NEUTRAL – COMBINED)
IT (ISOLATED TERRE)
For this installation, using TT (Double Terre) for this grounding system
TT (DOUBLE TERRE)
In TT systems, the neutral part of the power source is not directly connected with neutral earthing on
the consumer side (equipment installation). On TT system, the consumer must provide their own connection
to the earth that is with install earth electrodes suitable for the installation.

33
X. SINGLE LINE DIAGRAM

34
XI. POWER RECAPITULATION

1. Power Recapitulation At Home

POWER RECAPITULATION
TOTAL
POWER TOTAL USAGE
NO PLACE EQUIPMENTS QUANTITY ENERGY
(W) (Wh) (h)
(Wh)
Living
1. Lamp LED 1 22.5 22.5 12 270
Room
Lamp TL 2 14.5 29 12 174
Bed
2. Fan 1 45 45 6 270
Room 1
Television 1 50 50 6 300
Lamp TL 2 14.5 29 12 348
Bed
3. Fan 1 45 45 6 270
Room 2
Television 1 50 50 7 350
4 Bathroom Lamp LED 1 12.5 12.5 12 150
Lamp LED 1 22.5 22.5 12 270
5. Kitchen Refrigerator 1 50 50 24 1200
Rice Cooker 1 95 95 24 2280
6. N Space Lamp LED 1 13 13 12 156
7. A Space Lamp LED 1 13 13 12 156
8. Terrace Lamp LED 2 12.5 25 12 300
TOTAL 17 760 801.5 169 6494

2. Tariff Group per Day and Month

ELECTRICITY TARIFF GROUP


TARIFF/kWh ENERGY (kWh) COST
3500VA

Per Day Rp.1.467 6.494 Rp.9.529,632


Per Month Rp.1.467 194.82 Rp285.800,94

35
This Electricity Tariff Groups based on PLN data.

ELECTRICITY
POWER LIMIT BILL
TARIFF GROUP
Rp
R-1/TR 1.300 VA
1.467,28/kWh
Rp
R-1/TR 2.200 VA
1.467,28/kWh
3.500 VA – 5.500 Rp
R-2/TR
VA 1.467,28/kWh
Rp
R-3/TR > 6.600 VA
1.467,28/kWh
6.600 VA – 200 Rp
B-2/TR
kVA 1.467,28/kWh
B-3/TM > 200 kVA Rp 1.115/kWh
I-3/TM > 200 kVA Rp 1.115/kWh
I-4/TT > 30.000 kVA Rp 997/kWh
6.600 VA – 200
P-1/TR Rp 1.467/kWh
kVA
P-2/TM > 200 kVA Rp 1.115/kWh
Rp
P-3/TR
1.467,28/kWh
Rp
L/TR, TM, TT
1.644,52/kWh

36
37
XII. BILL OF QUANTITY

BILL OF QUANTITY
SPECIFIC
NO EQUIPMENT TYPE CAPACITY QUANTITY COST TOTAL COST
INFORMATION
LED 2500 lm 22.5 W 2 Rp.75.435.4 Rp.150.870.8
LED 1521 lm 12.5 W 3 Rp.77.848.8 Rp.233.546.4
1 Lamp
LED 1521 lm 13 W 2 Rp.91.121.4 Rp.182.242.8
TL LED 2500 lm 14.5 W 4 Rp.324.131.2 Rp.[Link]
Edison light bulb LED 7 Rp.20.000 Rp.140.000
2 Fixture Fluorescent High Bay
Luminaires TL lamp 2 Rp.1.069.500 Rp.2.139.000

Single Switch 10A/250V 5 Rp.15.000 Rp.75.000


3 Switch
Double Switch 10A/250V 2 Rp.40.000 Rp.80.000
Socket 16 A
4 Type F 4 Rp.15.000 Rp.60.000
Outlet 250V~
Junction Type T – Junction 8 Rp.8.841.2 Rp.70.729,6
5
box 4 way 3 Rp.4.420.6 Rp.13.261,8
Terminal
6 12 pole 25A/600V 2 Rp.10.000 Rp.20.000
Block
7 Panel Box Metal plate 30cm x 20cm 1 Rp.83.000 Rp.83.000
8 Conduit PVC 50mm 20 Rp.1.426 Rp.28.520
9 Clamps PVC 50mm 100 Rp.1.426 Rp.28.520
4A 1 Rp.25.000 Rp.25.000
10 MCB C 16A 1 Rp.50.000 Rp.50.000
10A 1 Rp.45.000 Rp.45.000
11 Wire Nut 1 Rp.45.000 Rp.45.000
Grounding
12 Cooper 50mm² 1 Rp.205.000 Rp.205.000
Road
NYA Phase 20A 1,5mm² 2 Rp.339.000 Rp.678.000
NYA Neutral 20A 1,5mm² 1 Rp.339.000 Rp.339.000
13 Cables
NYM Phase, Neutral,
22A 2,5mm² 2 Rp.1.470.000 Rp.2.940.000
Ground
TOTAL Rp.[Link]

38
XIII. REFERENCE

- Keselamatan dan Pemasangan Instalasi Listrik Voltase Rendah untuk Rumah Tangga
- PUIL 2011
- SNI
- IEC
- Philips LED Lighting Catalog 2018
- Schneider Electric Sedna 2018
- PLN
- Group Presentation Lighting Calculation
- Group Presentation Grounding
- Image from Google
- [Link]

39