0 ratings0% found this document useful (0 votes) 2K views11 pagesCESSNA Citation Bravo-Electrical
Electrical Systems for Citation Bravo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
AIRPLANE AND SYSTEMS MODEL 550
ELECTRICAL
GENERAL
Electrical power is normally supplied by two 28-volt direct current (DC), 400-ampere,
[engine-driven starter/generators. A 24-volt, 44-ampere hour (or optional 43-ampere hour),
nickel-cadmium battery is located in the tailcone compartment to supply power for starting
and emergency requirements. A receptacle below the left engine pylon is provided for
‘connection of an external power unit.
ALTERNATING CURRENT (AC) POWER
Alternating current (AC) is provided by two 250 VA static inverters that convert 28 volt DC
into 115 and 26 volt, 400 Hz, AC power. The AC system is a dual split bus system in which
the number one 115 and 26-volt AC buses, and the number two 115 and 26-volt buses are
Powered by the number one and number two inverters respectively (NORM position on the
(INV /NORM/INV 2 AVIONIC POWER switch). If an inverter fails, the respective amber
INVTR FAIL (1 or 2), annunciator will illuminate, and the pilot must select the remaining
inverter to power the complete system, by selecting the inverter opposite to the one indicating
failure (INV 1/NORM/INV 2 switch to the operating inverter).
DIRECT CURRENT (DC) POWER
The direct current (DC) power distribution system consists of the starter/generators,
battery indicators, switches and bus networks. Normally, the left generator powers the left
main DC bus and the right main DC bus receives power from the right generator. Both
Operate in parallel, but in the event either generator is off the line, the battery bus acts as a
ross tie so that the remaining generator will power both main DC buses. The DC buses
‘supply power for all DC functions except engine starting.
The avionics DC buses (and the 26-volt and 115-volt AC busses) are in two separate
sections controlled by two power relays, so that the failure of one relay or the loss of one
section of the bus will result in the loss of only approximately one-half the items of equipment
on that particular bus. The circuit breakers in Figure 2-20 (Sheet 2) are coded to indicate the
equipment items powered by each section of the main bus and its relay.
GENERATORS
A generator control unit provides starter regulation, overvoltage, feeder fault and ground
fault protection for each generator. Three-position L and R generator switches are marked
GEN, OFF and RESET. In the GEN position, generator control is automatic for regulation,
Protection and load bus connection. This is the normal switch position for battery starting and
all flight modes. Placing the switch to OFF isolates the generator from its load bus. The
momentary RESET position resets a generator that has been tripped as a result of an
overvoltage, feeder fault or engine fire switch actuation.
I Each starter/generator is capable of a 50 percent overload for two minutes. A single
generator is capable of supporting the entire electrical system; however, if the optional Freon
air conditioning system is installed and in operation, it must be shut down.
2-44 55BOM-01MODEL 550 AIRPLANE AND SYSTEMS
BATTERY
‘The battery is a secondary source of direct current (DC) power available to supply the
distribution system prior to start, or in the event of generator failure. The three-position
control switch is labeled BATT, OFF and EMER. Placing the switch to the BATT position
closes the battery and emergency relays and powers the battery bus, emergency bus and
both main DC buses. This position also enables external power to supply the entire system.
In the OFF position, battery or external power is isolated from all but the hot battery bus.
The hot battery bus is energized any time the battery is installed or external power is,
connected. It powers the emergency exit lights, tailcone light, nose baggage compartment
light and an aft baggage compartment light. A battery disconnect relay between the battery
and ground is located below the battery.
During each engine start using external power, the battery disconnect relay will
automatically open interrupting battery power to the hot battery bus. The relay will close
automatically at the end of the start cycle.
The EMER (emergency) position of the battery switch will provide at least 30 minutes
operation for selected instruments and systems. The following are powered from the
emergency bus.
LH & RH Fan Speed Inds.
Cockpit Flood Lights
COMM 1
NAV 1
Gi and Standby HSI
Voltmeter
Standby Pitot-Static Heaters/standby altimeter vibrator
Copilot's Audio Panel
Pilot's Audio Panel *
* The pilot's audio panel is switched to the emergency bus when the battery
switch is placed to EMER position.
Additionally, the standby gyro battery provides at least 30 minutes lighting for the
following: dual fan tachometers, standby gyro indicator, standby HSI, and standby
altimeter/airspeed indicator. In some cases, it may be prudent to select OFF on the
unneeded systems, such as lighting and pitot-static heat in order to conserve battery life. The
cockpit speakers will remain operational and selection of EMER COMM is not necessary.
The battery temperature monitor gage provides a continuous indication of battery
temperature from 0 to 180°F (-18° to + 82°C).
Battery temperature should remain below 63°C (145°F). A battery temperature
exceeding 63°C (145°F) is annunciated by a steady illumination of the red BATT O'TEMP
light on the annunciator panel. A battery temperature exceeding 71°C (160°F) is shown by a
flashing annunciator light.
The battery must be serviced per the Maintenance Manual when the battery temperature
exceeds 63°C (145°F).
55BOM-00 245ARPLANE AND SYSTEMS MODEL 550
EXTERNAL POWER
External direct current (DC) power can be connected to the airplane through a
receptacle located on the left side of the fuselage. When external power is connected, the
external power relay energizes and connects the power source to the hot battery bus.
Positioning the battery switch to BATT energizes the battery and emergency relays allowing
external power to be connected to the entire DC system. Ground power requirements dictate
a 28-volt unit, with a maximum capability of 1000 amperes current. If an adjustable power unit
is used, it should be adjusted to provide a maximum of 1000 amperes. A ground power uni
with a soft start capability is preferable. The battery should be disconnected if the airplane is
to be on a ground power unit for a prolonged period of time.
CAUTION
CURRENT IN EXCESS OF 1000 AMPERES MAY DAMAGE THE STARTERS.
DIRECT CURRENT (DC) POWER INDICATORS
The indicators consist of two ammeters, a voltmeter and two amber generator failure
lights (GEN OFF, L and R). The ammeters function as loadmeters indicating the load being
carried by each generator.
The voltmeter is wired through the battery switch and will indicate the voltage of the hot
battery bus any time the battery switch is in the BATT or EMER position. The voltmeter
selector switch can be rotated to the LH or RH GEN positions to check generator voltage
‘output. Since the voltmeter reads the highest voltage on the bus, an accurate check of one
generator is obtained only with the opposite one off the line.
Should either generator fail, the associated power relay will open, removing the generator
from the system and illuminating the appropriate L or R GEN OFF annunciator panel light.
‘Should both generators fail, the master warning light will also illuminate. This is the only
condition under which illumination of an amber annunciator light will trigger the master
warning,
EMERGENCY BATTERY
Placing the battery switch in the EMER position opens the battery relay; the emergency
bus relay will remain closed. This disconnects the main direct current (DC) busses and the
battery bus from the battery and connects the battery directly to the emergency bus. With
both generators off, all electrical equipment will be inoperative except COMM 1, NAV 1, the
standby airspeed indicator/altimeter vibrator, the standby horizontal situation indicator (HSI),
directional gyro number one, the N; tachometers, the standby pitot-static system heaters, the
voltmeter and the cockpit floodlights, and the pilot's and copilot's audio amplifiers (the pilot's
audio is switched to the emergency bus when the BATT switch is placed to EMER).
Emergency lighting which will be available, in addition to the cockpit flood lights, are the
instrument lights for the standby gyro, the N;/ITT indicators, the standby HSI, and the standby
airspeed indicator/attimeter.
NOTE
The pilot should be aware that with both generators off the line and the
battery switch in the EMER position some of the more inportant items such
as annunciator lights, gear indicator lights, main pitot/static and angle-of=
attack system heat, fire warming and fire bottle discharge will be inoperative.
2-46 55BOM-00SECTION
MODEL 550 AIRPLANE AND SYSTEMS
Going to emergency (EMER) with either or both generators on the line will have no affect
except that the battery will not charge. As long as at least one generator is on the line,
turning off the battery switch will not cause any equipment on the emergency bus to cease
functioning,
CIRCUIT BREAKERS
Push-to-reset, pull-off type circuit breakers with the amperage rating marked on each
breaker, are stalled in panels located on both sides of the cockpit. The panels are readily
accessible to the flight crew during flight. Panel configurations may vary from airplane to
irplane due to differences in installed equipment; therefore, the panels shown are typical
installations.
Additional circuit breakers to which flight crew access is not essential, are located in the
tailcone junction boxes.
55BOM-00 2-47‘SECTION
AIRPLANE AND SYSTEMS
MODEL 550
DIRECT CURRENT ELECTRICAL SYSTEM SCHEMATIC
LEFT CIRCUIT BREAKER PANEL
GENERATOR
CONTROL
‘SWITCH
BATTERY,
DISCONNECT
RELAY
2-48
RIGHT CROSSOVER BUS_
Figure 2-18
LEFT CROSSOVER BUS
GENERATOR]
GENERATOR =
EXTERNAL POWER
DISABLE RELAYS RIGHT
TO GENERATOR
CONTROL
SWITCH
55BOM-00MODEL 550 AIRPLANE AND SYSTEMS
ENGINE STARTING
Depressing either engine start button closes the respective start relay and provides DC
power to the engine starter. Power to close the solenoid start relays and energize ignition
comes from the battery bus requiring the battery switch to be in the BATT position. Automatic
ignition sequencing takes place with both engine ignition switches in the NORM position.
A white light in each starter button indicates power on the contacts of the respective start
relay. The starter operation is terminated when the speed sensor in the generator control unit
[removes power from the start relay at approximately 39 percent Nz RPM. The automatic start
‘sequence can be terminated at any time by pushing the cockpit STARTER DISENGAGE
switch located between the start buttons which will open the start relay and halt the start
sequence. During engine start, when the generator output exceeds battery voltage and/or is
in parallel with the other generator (within 40 amperes), the starter/generator reverts to
generator operation. The power relay closes and supplies power to the respective DC bus.
Current will then flow from either main DC bus through the battery bus, battery relay and hot
battery bus, providing battery charging.
The airplane is equipped with a cross start capability which utilizes the generator of an
‘operating engine to assist starting the second. This is accomplished by both start relays
closing when the second start is initiated routing power through the hot battery bus to the
other engine. On all cross starts, the operating engine should be set at 52 to 53 percent No
to ensure proper torque on the generator shaft. Cross generator start capability is disabled
with weight off the left main gear squat switch in order to prevent cross starts in flight.
Starts being made on external power may be accomplished with the generator switches
in either the ON or OFF position; however, it is recommended that they be turned OFF during
the start. If the generator switch is placed in the ON position the generator control unit will
automatically initiate the generator mode after engine start. If the generator switch is placed
in the OFF position, the generator mode will be initiated by manually placing the generator
switch to the ON position. External power is automatically disconnected when either
generator is supplying power to the bus. In order to start the second engine by auxiliary
power unit, the generator supplying voltage to the bus must be disconnected by placing the
generator switch to the OFF position.
An overvoltage protection system is provided during use of an auxiliary power unit. The
control unit monitors the external power unit voltage and will deenergize the external power
relay if the voltage rises above 32.5 volts. During an engine start using the external power
unit, a voltage signal is applied to the control unit. If the output of the power cart exceeds
32.5 volts the control unit will deenergize the external power relay and terminate the start
External power cannot be reapplied to the airplane until the voltage has been interrupted after
the start termination. Simply reducing the voltage to below 32.5 volts will not enable the
external power to be reapplied.
For battery starts and under all normal flight conditions, the generators are left in the
GEN position.
55BOM-01 2-49AIRPLANE AND SYSTEMS MODEL 550
ALTERNATING CURRENT ELECTRICAL SCHEMATIC
TO A
pL Fa
INV 1 FAIL
115 VAC COMMON
FAULT MONITOR
|28 VDC IN
SYNC INPUT
28 VDC COMMON
INVERTER #2
118 VAC COMMON]
[7] FAULT MONITOR
128 VDC IN
VG 4
115 VAC
Figure 2-19 (Sheet 1 of 2) es77C7008 1)
2-50 8500M-00MODEL 550 AIRPLANE AND SYSTEMS
ALTERNATING CURRENT ELECTRICAL SCHEMATIC
© 26 VAC BUS 1 O
Figure 2-19 (Sheet 2 of 2) __ e5r7ETON8
5500M-00 _AIRPLANE AND SYSTEMS MODEL 550
ALTERNATING CURRENT (AC) POWER
‘The AC power distribution system consists of a 2-position AVIONIG POWER switch
(ON/OFF), a 3-position INV 1/NORM/NV 2 switch (both on the left meter panel), two 26
VAG/115 VAG, 400 Hz static inverters, four AC buses (two 26-volt and two 115-volt) and two
annunciator panel lights. Each inverter converts 28 volts DC into AC power, with a maximum
output of 250 VA each. Both AC and DC power to the avionics equipment is controlled by the
AVIONIC POWER ON/OFF switch, which serves as an avionics master switch. The AC
system functions normally with the left AVIONICS POWER switch in the NORM position; in this
Position the number 1 inverter powers the number one 26 VAC bus and the number one 115
VAG bus, and the number two inverter powers the respective number two AC busses. In the
case of the failure of an inverter, the pilot must select the opposite inverter by positioning the
‘switch to INV 1 or INV 2, which will result in the remaining (selected) inverter powering both
busses.
‘The AC system powers avionics and navigation equipment. Equipment on the number
‘one 26-volt AC (VAC) bus includes: NAV 1 (AC REF 1 circuit breaker), vertical gyro number
‘one (VG 1), and the optional flight data recorder (FDR). The number one 115 VAC bus
powers the the pilot's'vertical gyro (VG 1). The number two 26 VAC bus powers NAV 2 (AC
REF 2), the pilot's directional gyro (DG REF 1), the standby horizontal situation indicator (HSI),
the weather radar, and the optional traffic warning and collision avoidance system (TCAS).
The number two 115 VAC bus provides power for the number two (copilot's) vertical gyro.
When the battery switch is placed to EMER position AC power for the standby HSI is provided
by an internal static inverter in the pilot's C-14D directional gyro. In this case the DG static
inverter also provides its own AC power.
In the event of failure of one inverter the respective amber INVTR FAIL (1 or 2) light and
the MASTER CAUTION will flash. Selecting the opposite inverter will correct the AC power
failure situation by switching the busses having the failed inverter to the remaining (opposite)
inverter, which will then power all four AC busses, thereby cancelling the failure light.
Resetting the MASTER CAUTION will not cancel the INVTR FAIL light unless the failure
situation has been cleared. One inverter provides adequate power for the AC system;
however, both inverters must be operational for takeoff. An operational check of both
inverters, according to the procedure stated in Section Four of this manual, must be
accomplished before takeoff.
In the unlikely event of a dual inverter failure the amber INVATR FAIL 1 and 2
annunciator lights, the red AC FAIL warning light, the MASTER CAUTION, and the MASTER
WARNING lights will flash. In this case the pilots DG and the standby HSI can be used for
heading reference; the NAV bearing pointers will be inoperative.
AC inverter protection is provided by two 10-amp circuit breakers (AC INVERTER NO.1,
left circuit breaker pane! and AC INVERTER No. 2, right circuit breaker panel). Since the
circuit breakers are located between the DC bus and the inverters which can power the
respective AG bus, the AC bus cannot receive power if the circuit breaker is disengaged. itis
possible that a disengaged circuit breaker was caused by a bus short; therefore, re-
engagement should be carefully considered before an attempt is made. System damage
could possibly result.
252 ‘55BOM-00SECTION N
AIRPLANE AND SYSTEMS
MODEL 550
LEFT CIRCUIT BREAKER PANEL
Cc
a
a@
2@
PLUG BUTTON
LEFT MAIN OC BUS
e
oO
EMERGENCY DC 8US
RIGHT MAIN DC BUS
sor2e7a-4
Figure 2-20. Circuit Breaker Panels (Sheet 1 of 2)
2-53
56B0M-00AIRPLANE AND SYSTEMS
MODEL 550
RIGHT CIRCUIT BREAKER PANEL
i
@+ @:
@- el
@f OF
@* Os
@- ©
e:
@:
@:
@:
a FF
>
be POWER
@ encraency 0c aus
RIGHT AVIONICS BUS #1 - SWITCHES TO EMERGENCY
DC BUS WHEN BATT SWITCH TO EMER
COrict avionics Bus #1
@ nisi AvioNes aus #2
@ rien maw 0c aus
‘AC POWER
@ 25 vac Bus 1
@ 2 vac aus #2
© 115 vac Bus #1
© 1s vac eus #2
Figure 2-20. Circuit Breaker Panels (Sheet 2 of 2)
85B0M-00