LiBr Absorption Chiller Principles

The document describes the working principle of a LiBr absorption chiller. It uses two working fluids: a refrigerant and an absorbent, lithium bromide (LiBr) solution. The refrigerant absorbs heat from chilled water in the evaporator, becoming a vapor. The LiBr solution absorbs the refrigerant vapor in the absorber, becoming weak. It is then heated to release the refrigerant vapor and regenerate in the generator. The chilled water cools spaces through fan coils while the heat source drives the process.

Uploaded by

wilber Banda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views43 pages

LiBr Absorption Chiller Principles

The document describes the working principle of a LiBr absorption chiller. It uses two working fluids: a refrigerant and an absorbent, lithium bromide (LiBr) solution. The refrigerant absorbs heat from chilled water in the evaporator, becoming a vapor. The LiBr solution absorbs the refrigerant vapor in the absorber, becoming weak. It is then heated to release the refrigerant vapor and regenerate in the generator. The chilled water cools spaces through fan coils while the heat source drives the process.

Uploaded by

wilber Banda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Brief on Working Principle of

LiBr Absorption Chiller


Central Air-conditioning System

Cooling tower

Machine Room Fan Coil

Chiller
Chilled water

Fan coil
WORKING PRINCIPLE

WORKING PRINCIPLE
There are two kinds of medium in the chiller. One is refrigerant.

Inside the chiller, the refrigerant will absorb the heat of the chilled
water. So, the temperature of the chilled water will decrease, and this
(low temperature) chilled water can be supplied to the places where it is
needed (for example, to cool down the rooms). The refrigerant will
convert into vapor after it absorbs the heat of the chilled water.
WORKING PRINCIPLE

WORKING PRINCIPLE
Pressure
Temperature
101 kPa (760mmHg) 100 ℃
84 kPa (634mmHg) 95 ℃
6.9 kPa (52.4mmHg) 39 ℃
1 kPa (7.51mmHg) 7℃
0.87 kPa (6.54mmHg) 5℃
0.75 kPa (5.68mmHg) 3℃
WORKING PRINCIPLE

WORKING PRINCIPLE
The other medium is absorbent (LiBr solution).

Inside the chiller, the absorbent will absorb the vapor of the refrigerant.
The concentration of absorbent will decrease after it absorbs the vapor
of the refrigerant. (We call it weak solution.) After the concentration
decreases to a degree, the absorbent will have no ability to absorb the
vapor of the refrigerant, then it will be needed to be reconcentrated. It
will be heated to a high temperature in other parts of the chiller, to
separate the refrigerant from the absorbent and to make the weak
solution become strong solution. Again, the strong solution can absorb
the vapor of the refrigerant, and the refrigerant can absorb the heat of
the chilled water.
The heat source can be hot water, steam, gas, oil, or waste flue.
THE CHARACTERISTICS OF LiBr SOLUTION

SATURATION WATER VAPOR PRESSURE OF


LiBr SOLUTION
Saturation water vapor pressure of LiBr solution is closely
related to the temperature and concentration of LiBr solution.
When the temperature is kept constant, the higher the
concentration, the lower the saturation water vapor pressure.
When the concentration is kept constant, the lower the
temperature, the lower the saturation water vapor pressure.

39℃ 57% 6.4 mmHg


50℃ 63% 6.2 mmHg
94℃ 63% 55 mmHg
87℃ 60% 53 mmHg
THE CHARACTERISTICS OF LiBr SOLUTION

SATURATION WATER VAPOR PRESSURE


1 water 2 LiBr solution

5℃ 6.54 mmHg (Evaporator) 39℃ 57% 6.4 mmHg (absorber)


10℃ 9.20 mmHg 50℃ 63% 6.2 mmHg
39℃ 52.4 mmHg (Condenser) 94℃ 63% 55 mmHg
87℃ 60% 53 mmHg (LPG or HS
Generator)

157℃ 63% 650 mmHg


HPG Double Effect
THE CHARACTERISTICS OF LiBr SOLUTION

SATURATION WATER VAPOR PRESSURE


1 water 2 LiBr solution

5℃ 6.54 mmHg 39℃ 57% 6.4 mmHg


WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
WORKING PRINCIPLE (Single Effect)
Hot water fired Single stage chiller
Steam fired Single Effect chiller
Hot water fired Two stage chiller
WORKING PRINCIPLE (Double Effect)
DFH3 refrigerating principle
DFH2 refrigerating principle
Steam Operated Chiller working principle
直燃型溴化锂吸收式冷热水机组
Direct-fired LiBr Absorption chiller/heater
冷凝器 低压发生器 LP generator
Condenser

高压发生器

蒸发器 HP generator

Evaporator

吸收器
Absorber

燃烧器
Burner

热交换器
Heat
exchange
r
直燃型机组高压发生器 HP Generator
汽包 Refrigerant vapor box 挡液板 Eliminator

防爆门 进液盒
Rupture Solution
disk inlet

排烟口 布液管

Flue Distribution
gas tube
outlet
传热管
Heat transfer
tube

燃烧器 炉膛
Burner furnace
蒸发-吸收器 Evaporator - Absorber
吸收器 挡液板 蒸发器 挡液板 吸收器 冷剂水管
Absorber Eliminator Evaporator Eliminator Absorber
Refrigerant tube
溶液管 Solution 溶液管 Solution
spraying tube spraying tube

吸收器淋板 吸收器淋板
Distribution Distribution plate
plate 蒸发器淋板
Distribution plate
抽气管 Purging
抽气管 tube
Purging tube
吸收器传热管
Heat transfer tube
吸收器传热管
heat transfer tube 冷剂水水盘 Refrigerant
water pan

蒸发器传热管 Heat 闪发蒸汽管 Flashed


transfer tube vapor tube

吸收腔 冷剂水液囊 Refrigerant


water chamber
Absorption
chamber
低发-冷凝器 LP generator - condenser
支撑板Supporting plate 冷凝器
Condenser

低压发生器
LP generator
低发-冷凝器 LP generator - condenser
低压发生器 挡液板 冷凝器 冷凝器传热管
LP generator Eliminator Condenser Heat transfer tube

抽气管
Purging
tube

进液管
Solution inlet
tube
储气室
Non-
低压传热管 condensable
Heat transfer gas box
tube
热交换器 Heat Exchanger

B out 传热管 Heat transfer tube

A in
A out

B in
溴化锂吸收式冷水机组
LiBr Absorption chiller

抽气系统
Purging
system

真空泵
Vacuum
pump 溶液泵 冷剂泵
Solution pump Refrigerant pump
蒸汽双效型溴化锂吸收式冷水机组
Steam operated double effect LiBr absorption chiller
低压发生器
高压发生器 冷凝器
LP Generator
HP Generator Condenser

蒸发器
Evaporator

吸收器
Absorber
热交换器
Heat
exchanger
蒸汽双效型溴化锂吸收式冷水机组
Steam operated double effect LiBr absorption chiller
高压发生器 HP Generator 低压发生器 LP Generator 冷凝器 Condenser

蒸发器
Evaporator

吸收器
Absorber

热交换器
Heat
exchanger
蒸汽双效型机组高压发生器
HP generator of Steam Operated
Double Effect Chiller
高发辅助发生器
汽包 Refrigerant vapor box
Auxiliary generator

蒸汽进口
Steam inlet

浓溶液液囊 液位箱 高发传热管 凝水出口


Strong solution chamber Level indicator Heat exchanger Condensate outlet
YX ---Flue Gas Operated Double Effect Chiller Flow Chart
------Exhaust outlet temperature 170℃
YBX ---Flue Gas Operated Chiller With Burner Flow Chart
------Exhaust outlet temperature 170℃ <40% after burning
YSX—Flue Gas /Steam Operated Chiller Flow Chart
------Exhaust outlet temperature 170℃, steam 0-100%
YRX--Flue Gas /Hot water Operated Chiller Flow Chart
------Exhaust outlet temperature 170 ℃, hot water >88℃
YRBX—Flue Gas /Hot Water Operated Chiller with after Burning
------Exhaust outlet temperature 170℃
THE CHARACTERISTICS OF LiBr SOLUTION

PREPARING OF LiBr
SOLUTION
HBr + LiOH  LiBr + H2O
2HBr + Li2CO3  2LiBr + H2O + CO2

REQUIREMENTS TO LiBr SOLUTION


Elements Contents
LiBr 50%±0.5%
Li2CrO4 0.1%~0.3%
Alkalinity pH = 9.0~10.5
NH3 < 0.0001%
Ca < 0.001%
Mg < 0.001%
SO42- < 0.02%
Cl- < 0.05%
Ba < 0.001%
Fe < 0.0001%
Cu < 0.0001%
BrO3- No reaction
THE CHARACTERISTICS OF LiBr SOLUTION

REQUIREMENTS TO LiBr SOLUTION


LiBr solution has no non-condensable gases, such as CO2, can
contained, and the water, which is used to prepare LiBr solution,
had to be distilled water, or treated by ion exchanger.

2LiOH + CO2  Li2CO3 + H2O

Poor quality LiBr solution will tends to decrease the cooling


capacity of chiller, deviate the crystallization conditions, increase
the corrosive attacks of chiller material and reduce the operation
life of it.
THE CHARACTERISTICS OF LiBr SOLUTION

CORROSION OF METALS BY LiBr SOLUTION


Fe + H2O + 0.5O2  Fe(OH)2
Fe(OH)2 + 0.5H2O + 0.25O2  Fe(OH)3
4Fe(OH)2  Fe3O4 + Fe + 4H2O
2Cu + 0.5O2  Cu2O
Cu2O + 0.5O2 + 2H2O  2Cu(OH)2

Influence of Corrosion to The Performance of Chiller


1. Corrodes the metals of chiller, and reduces its operation life
2. Corrosion of metals produces non-condensable gas-hydrogen,
which deteriorates the absorption and condensation processes,
leads to decrease the cooling capacity of chiller.
3. The scale and other corrosion products will block spray nozzles
(or holes in the dripping plates) and filter to impair the normal
operation of chiller.
THE CHARACTERISTICS OF LiBr SOLUTION

THE MEANS AGAINST CORROSION


1. Isolation of Oxygen - The Fundamental Measure against
Corrosion
2. Keep the solution with pH in the limits of 9.0~10.5
3. Add the inhibitor, such as Li2CrO4, Li2MoO4.
4. Keep the solution temperature not higher than 165 ℃
THE CHARACTERISTICS OF LiBr SOLUTION

CONCENTRATION OF
LiBr SOLUTION

The solubility is usually


expressed by the mass in gram
solved in 100g of solvent.
Concentration of LiBr solution
means the quantity percentage
of LiBr in the solution.

The solubility of a matter is


dependent to the temperature
conditions.

You might also like