TITANUS PRO·SENS®
Product information
Fire detection
Universal air sampling smoke
detection system for a broad
range of applications
EG1905001
202064
EN 54-20
TITANUS PRO·SENS®
The universal air sampling
smoke detection system
TITANUS PRO·SENS® is a universal air sampling
device for a broad range of applications. The high
degree of modularity of the device makes it possible
to achieve a cost-effective solution – customised to
suit the specific needs of the customer.
An additional price advantage comes with the optional
equipping of the device with a second detector
module. This means that one air sampling device can
monitor two separate monitored areas. Alternatively,
double-knock detection can be set up for both room
and equipment monitoring purposes.
TITANUS PRO·SENS® is available with 1 to 3 alarm
levels, with a network option, in the cold storage
version or in the silent version, which operates at
noise levels as low as 23 dB (A).
The coverage of the detector is in accordance with
EN 54-20: a single TITANUS PRO·SENS® 2
system can replace up to 64 point-type smoke
detectors. Thanks to a powerful fan operating at up to
560 Pa, a pipe length of up to 560 m can be achieved
fullfilling EN 54-20 Class A to C requirement.
EG1905001
202064
Applications Advantages
The robust TITANUS PRO·SENS® offers a compre Early fire detection thanks to innovative, highly
hensive product range complete with accessories sensitive HPLS light source technology
approved to EN 54-20. This allows the device to be High degree of false alarm immunity through
used in areas where other smoke detectors and air LOGIC·SENS fire pattern recognition
sampling smoke detection systems have long reached Up to 3 alarm thresholds for a tiered alarm concept
their limits. These include: A broad range of accessories, approved to EN 54-20
High degree of modularity for a customised, cost
IT areas and clean rooms effective solution
General warehouses, high bay storage areas and Reliable project design with just 5 mouse clicks
cold storage areas Time saving commissioning through Plug & Play
Production and assembly lines Double-knock detection to enable separate room
Wind farms and equipment monitoring
Libraries, museums and archives Available as silent option from 23 dB (A)
Hospitals, hotel rooms and saunas
Recycling areas
Rail vehicles and tunnels
2
TITANUS PRO·SENS®
Technical data
Basic equipment TITANUS PRO·SENS® (/net) TITANUS PRO·SENS® 2 (/net)
Number of detector modules 1 2
max. number of sampling orifices 32 64
max. pipe length (with max. number of sampling holes) 300 m 560 m
Monitored area per sampling hole Corresponds to one point-type smoke detector in accordance with VDE 0833-2
Monitoring of pipe systems for breakage and obstruction Optional adjustment for individual hole monitoring **
Double-knock detection Possible using detector box Yes (separate room and equipment protection)
Sensitivity detector module DM-Tx-01 Info-alarm: 0.005 % LT/m*
(Sampling holes in accordance with EN 54-20: Class A max. 2 x Pre-alarm: 0.010 % LT/m*
32, Class B max. 2 x 32, Class C max. 2 x 32 ) Main alarm: 0.015 % LT/m
Sensitivity detector module DM-Tx-10 Info-alarm: 0.03 % LT/m*
(Sampling holes in accordance with EN 54-20: Class A max. 2 x Pre-alarm: 0.06 % LT/m*
9, Class B max. 2 x 32, Class C max. 2 x 32) Main alarm: 0.1 % LT/m
Sensitivity detector module DM-Tx-50 Info-alarm: 0.17 % LT/m*
(Sampling holes in accordance with EN 54-20: Class A max. 2 x Pre-alarm: 0.3 % LT/m*
4, Class B max. 2 x 12, Class C max. 2 x 32 ) Main alarm: 0.5 % LT/m
Alarms (potential free change-over contacts) Up to 3 alarms per detector module (info-alarm, pre-alarm and main alarm)
Fault alarms Common alarm
(1 potential free contact per detector module, NC or NO)
Alarm and fault relay power rating 1 A, 30 V DC, max. 24 W
Clamped connections max. 1.5 mm²
Displays on device
- Main alarm (Types TP-1/a, TP-3, TP-4, TP-5) 1 red alarm indicator per detector module
- Pre-alarm (Types TP-4, TP-5) 1 red alarm indicator per detector module*
- Info-alarm (Type TP-5) 1 red alarm indicator per detector module*
- Fault Yellow collective fault
- Operation Green operation display
Operating voltage 24 V DC (14 - 30 V DC)
Max. quiescent current (at 24 V DC)*** 200 (210) mA* 220 (240) mA*
Max. alarm current (at 24 V DC)*** 210 (220) mA* 240 (250) mA*
Starting current limited to 300 (390) mA 320 (400) mA
SL version:
Max. quiescent current (at 24 V DC)*** 150 (140) mA* 180 (170) mA*
Max. current consumption alarm (at 24 V DC)*** 160 (150) mA* 190 (180) mA*
Starting current limited to 300 (230) mA 330 (260) mA
Noise level from 23 dB (A)
Dimensions (W x H x D) 200 x 292 x 113 mm3
Weight 1460 g 1560 g
Protection category IP 20 (optional IP 52)
Temperature range -20 °C bis + 60 °C
- Cold storage option (no SL version) -40 °C bis + 60 °C
Humidity (permanent) 10 % bis 95 % relative humidity
Event log Built-in, additional external data storage possible
Connection of external alarm notifications Parallel display optional
Network capability optional ethernet network version****
Approved in accordance with EN 54-20, Classes A, B, C:
VdS-No. G 202064
BPRI-No. 0786-CPD-20685
* Depending on type of device ** Depending on project design *** At standard 6.9 V fan voltage **** Version TITANUS PRO·SENS® /net
4
Other TITANUS® air sampling smoke detection systems
TITANUS MICRO·SENS® Solution for monitoring up to 5
small to medium sized rooms,
optional with localisation of the
fire source e.g. hotel room,
hospital, prison cell
TITANUS TOP·SENS® Complete solution with smoke
level visualisation for up to 560 m
pipe length for monitoring large
areas, from IT rooms up to
recycling areas
TITANUS SUPER·SENS® A High-End solution for the most
demanding detection needs, a
WAGNER®, TITANUS®, RACK·SENS®, MICRO·SENS®, SUPER·SENS®, PRO·SENS®, TOP·SENS®, OxyReduct®, FirExting®,
© WAGNER Group GmbH, Technical modifications reserved without prior notification. Part no. 68-30-1141, Issue 02/10
thousand times more sensitive
than conventional smoke detec
tors, e.g. for clean rooms and IT
areas with high levels of air con
ditioning
TITANUS RACK·SENS® Intelligent solution for the protec
tion of open and closed server
and switch cabinets
VisuLAN® are registered trademarks of WAGNER Group GmbH.
FIRE DETECTION Very early fire detection with TITANUS® provides critical
additional time to assess the risk and take counter measures.
FIRE PREVENTION Actively prevents fires.
OxyReduct® is the innovative way in fire protection.
FIRE EXTINGUISHING Fixed fire extinguishing systems with various gaseous
extinguishing agents.
RISK MANAGEMENT Visualisation and control of important system data combined with multiple diagnostic
and messaging functions integrated into a powerful building management system.
WAGNER Group GmbH
Schleswigstraße 1 - 5
30853 Langenhagen, Germany
Phone +49 (0)511-97383-0
Fax +49 (0)511-97383-140
[email protected]www.wagner.eu