AVX-B & ACHX-B Performance
AVX-B & ACHX-B Performance
PRICE SUMMARY
Physical Specifications
Compressors (Qty) MSC1220(1) Shipping weight (lb) 8,765
Length (in) 206.00 Operating weight (lb) 8,968
Width (in) 88.00 Approx. refrigerant charge (lb) 276
Height (in) 88.00 Refrigerant R-134a
Conditions of service
Percent of full load 100% Compressor power (kW) 137.6
Capacity (Tons) 108.3 Total Fan Power (kW) 17.64
Unit power (kW) 155.3 Cooling Efficiency (EER, Btu /[Link]) 8.369
[Link] (EER, Btu /[Link]) 15.64
Evaporator
Model (Qty) 1CR(1) Leaving fluid temp. (°F) 44.60
Fluid Water Fouling factor (h·ft²·°F/Btu) 0.000100
Fluid flow rate (USgpm) 288.9 Pressure drop (psi/ft.H2O) 9.75/22.5
Entering fluid temp. (°F) 53.61 Fluid freezing point (°F) 32.00
Condenser
Design ambient (°F) 113.0 Altitude (ft) 0.000
Fan Motor Power (kW) (Qty) 2.520 (7)
Electrical characteristics
Unit power supply 400V/3ph/50.0Hz Unit min. circuit ampacity (A) 322
Unit max. fuse size (A) 500 Comp. rated load amps (A) 228
Unit rated load amps 265 Comp. locked rotor amps (A) 949
Notes
- Refrigerant charge may vary. Unit nameplate will show final - Certified in accordance with the AHRI Air Cooled Water-
factory charge. Chilling Packages Using the Vapor Compression Cycle
- Meets ASHRAE 90.1-2016 Path B chiller minimum efficiency Certification Program, which is based on AHRI Standard-
guidelines 550/590(I-P) and AHRI Standard 551/591(SI). Certified units
- ETL listed for US and Canada region, optional for 50Hz series may be found in the AHRI Directory at [Link].
and other 60Hz.
[Link] Points
% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F)
100% 108.3 155.3 137.6 17.64 8.369 113.0
75% 81.23 80.22 62.58 17.64 12.15 91.3
50% 54.15 36.83 29.27 7.560 17.65 69.5
25% 27.08 15.51 11.56 3.950 20.95 55.0
Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 32.80 ft 45 53 57 58 63 53 44 38 66
*Sound Pressure Level (free field) ± 2 dB(A) Tolerance
Standard Equipment
Unit Construction Code Compliance
▪ Unit shall be constructed of heavy gauge G90 galvanized steel ▪ Units conform to NEC,NEMA and ASHRAE 15 safety code for
▪ All sheet metal parts are painted with oven baked epoxy / mechanical refrigeration
polyester powder paint, sustaining 1000 hour salt spray test in ▪ Rated in accordance with AHRI 550/590 std.
accordance with ASTM B-117 ▪ IEEE
▪ Rigid Structural base to prevent unit deformation and damage
during hoisting
▪ Bolted construction for easy semi knockdown at site in case
hoisting problem
▪ Control panel IP54
Compressor
▪ Compartmentalized to reduce noise ▪ Compressor oil sump heater(s)
▪ MSC rotary screw ▪ Relief valve if required
▪ Cast iron housing ▪ Optical oil level sensor
▪ IP21 Terminal box ▪ Integral Oil separator
▪ Slide valve unloading ▪ Integral lubration system using pressure differential
▪ Suction check valve and discharge service valve ▪ One (1) year warranty
▪ Full hermetic design ▪ Compressor liquid injection, and vapour injection (only available
in selected models)
▪ VFD
Air Cooled condenser
▪ Inner ridged copper tubes ▪ Close blade tip clearance with the fan venturis to assure smooth,
▪ 450 psig test pressure for condenser coils quiet operation
▪ Low noise direct driven propeller and axial fans ▪ 6 pole fan motor, IP55, class F insulation with class B
▪ Galvanized steel tubesheet temperature rise
▪ Hydrophilic Coated Fins
Evaporator
▪ Flooded design for higher capacity and easy maintenance ▪ 150 psig on water side design pressure
▪ Cleanable integral fin copper tubes for easy serviceability ▪ Drain and vent plugs
▪ Removable water heads ▪ Relief valve
▪ Optional Flanged water connection for quick installation and/or ▪ 1" thick PE foam closed cell evaporator insulation,thermal
service conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F.)
▪ Full pump-down capacity in condenser, therefore, pump out unit ▪ 1" thick PE foam closed cell suction line insulation/thermal
not required conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F)
▪ 200 psig on refrigerant side design pressure ▪ Carbon steel header, shell and tube sheet
Refrigerant Specialties
▪ Economizer usage to boost capacity(Only available for selected ▪ Charging and gauge connections
models) ▪ Pressure relief valve
▪ Sight glass with moisture indicator ▪ Refrigerant charge
▪ Electronic Expansion Valve ▪ Oil Charge
▪ Replaceable core filter drier ▪ Discharge check valves on multiple compressor units
Standard Electrical Components
▪ Compressor cirucit breaker and contactors ▪ Fan control contactors
▪ Compressor overloads ▪ Control circuit transformer
▪ Low voltage/phase failure/phase reversal relay ▪ Current transformer
▪ On-off in the unit control circuit and each compressor control ▪ Optional Ambient temperature sensor
circuit
Warranty and Testing Analog readouts
▪ Standard one year warranty on unit and on compressors ▪ Evaporator and condenser refrigerant pressure
▪ Factory run tested ▪ Compressor amps (each compressor)
▪ Water sensor: Evaporator leaving - Standard sensor to provide
temperature readout for water leaving the evaporator.
Controllers
▪ Vision 2020i Advanced microprocessor based DDC controller ▪ Fluid temperature reset value
with 132x64 pixels DBG1 semi-graphic display panel with ▪ Water flow switch status
menu driven software digital readout, pushbutton keyboard ▪ External stop/start command status
▪ Selection on English (Imperial) or metric display units ▪ Condenser fan cycling
▪ Remote monitoring via RS-485 port ▪ Low ambient lockout
▪ Leaving chilled fluid temperature ▪ Identification of up to 99 most recent alarms with critical data
▪ Evaporator and condenser pressure stamping
▪ Single phase amp draw, each compressor ▪ OPTIONAL (BMS Communication option)
▪ No. of compressor starts ▪ Optional Ambient temperature sensor
▪ Elapsed run time, each compressor ▪ Optional Return water temperature sensor
▪ Oil level status ▪ Optional Remote and stop signal
Digital readouts Capacity control Setpoints
▪ Compressor contactor ▪ Elapsed compressor run ▪ Leaving water temperature ▪ Amp limit
status time ▪ Freeze up temperature ▪ Ramp up
▪ Flow switch status ▪ External enable/disable ▪ High and low pressure
▪ Oil level status status
▪ Number of compressor ▪ Liquid injection solenoid
starts state
Unit Protection
▪ High and low pressures
Physical Specifications
Compressors (Qty) MSC1220(1) Shipping weight (lb) 8,765
Length (in) 206.00 Operating weight (lb) 8,968
Width (in) 88.00 Approx. refrigerant charge (lb) 276
Height (in) 88.00 Refrigerant R-134a
Conditions of service
Percent of full load 100% Compressor power (kW) 116.6
Capacity (Tons) 111.6 Total Fan Power (kW) 17.64
Unit power (kW) 134.3 Cooling Efficiency (EER, Btu /[Link]) 9.973
[Link] (EER, Btu /[Link]) 16.42
Evaporator
Model (Qty) 1CR(1) Leaving fluid temp. (°F) 44.60
Fluid Water Fouling factor (h·ft²·°F/Btu) 0.000100
Fluid flow rate (USgpm) 297.6 Pressure drop (psi/ft.H2O) 10.3/23.7
Entering fluid temp. (°F) 53.61 Fluid freezing point (°F) 32.00
Condenser
Design ambient (°F) 104.0 Altitude (ft) 0.000
Fan Motor Power (kW) (Qty) 2.520 (7)
Electrical characteristics
Unit power supply 400V/3ph/50.0Hz Unit min. circuit ampacity (A) 278
Unit max. fuse size (A) 450 Comp. rated load amps (A) 193
Unit rated load amps 231 Comp. locked rotor amps (A) 949
Notes
- Refrigerant charge may vary. Unit nameplate will show final - Certified in accordance with the AHRI Air Cooled Water-
factory charge. Chilling Packages Using the Vapor Compression Cycle
- Meets ASHRAE 90.1-2016 Path B chiller minimum efficiency Certification Program, which is based on AHRI Standard-
guidelines 550/590(I-P) and AHRI Standard 551/591(SI). Certified units
- ETL listed for US and Canada region, optional for 50Hz series may be found in the AHRI Directory at [Link].
and other 60Hz.
[Link] Points
% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F)
100% 111.6 134.3 116.6 17.64 9.973 104.0
75% 83.69 75.84 58.20 17.64 13.24 85.6
50% 55.79 36.58 29.02 7.560 18.30 67.3
25% 27.90 15.95 11.91 4.040 20.98 55.0
Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 32.80 ft 45 53 57 58 63 53 44 38 66
*Sound Pressure Level (free field) ± 2 dB(A) Tolerance
Standard Equipment
Unit Construction Code Compliance
▪ Unit shall be constructed of heavy gauge G90 galvanized steel ▪ Units conform to NEC,NEMA and ASHRAE 15 safety code for
▪ All sheet metal parts are painted with oven baked epoxy / mechanical refrigeration
polyester powder paint, sustaining 1000 hour salt spray test in ▪ Rated in accordance with AHRI 550/590 std.
accordance with ASTM B-117 ▪ IEEE
▪ Rigid Structural base to prevent unit deformation and damage
during hoisting
▪ Bolted construction for easy semi knockdown at site in case
hoisting problem
▪ Control panel IP54
Compressor
▪ Compartmentalized to reduce noise ▪ Compressor oil sump heater(s)
▪ MSC rotary screw ▪ Relief valve if required
▪ Cast iron housing ▪ Optical oil level sensor
▪ IP21 Terminal box ▪ Integral Oil separator
▪ Slide valve unloading ▪ Integral lubration system using pressure differential
▪ Suction check valve and discharge service valve ▪ One (1) year warranty
▪ Full hermetic design ▪ Compressor liquid injection, and vapour injection (only available
in selected models)
▪ VFD
Air Cooled condenser
▪ Inner ridged copper tubes ▪ Close blade tip clearance with the fan venturis to assure smooth,
▪ 450 psig test pressure for condenser coils quiet operation
▪ Low noise direct driven propeller and axial fans ▪ 6 pole fan motor, IP55, class F insulation with class B
▪ Galvanized steel tubesheet temperature rise
▪ Hydrophilic Coated Fins
Evaporator
▪ Flooded design for higher capacity and easy maintenance ▪ 150 psig on water side design pressure
▪ Cleanable integral fin copper tubes for easy serviceability ▪ Drain and vent plugs
▪ Removable water heads ▪ Relief valve
▪ Optional Flanged water connection for quick installation and/or ▪ 1" thick PE foam closed cell evaporator insulation,thermal
service conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F.)
▪ Full pump-down capacity in condenser, therefore, pump out unit ▪ 1" thick PE foam closed cell suction line insulation/thermal
not required conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F)
▪ 200 psig on refrigerant side design pressure ▪ Carbon steel header, shell and tube sheet
Refrigerant Specialties
▪ Economizer usage to boost capacity(Only available for selected ▪ Charging and gauge connections
models) ▪ Pressure relief valve
▪ Sight glass with moisture indicator ▪ Refrigerant charge
▪ Electronic Expansion Valve ▪ Oil Charge
▪ Replaceable core filter drier ▪ Discharge check valves on multiple compressor units
Standard Electrical Components
▪ Compressor cirucit breaker and contactors ▪ Fan control contactors
▪ Compressor overloads ▪ Control circuit transformer
▪ Low voltage/phase failure/phase reversal relay ▪ Current transformer
▪ On-off in the unit control circuit and each compressor control ▪ Optional Ambient temperature sensor
circuit
Warranty and Testing Analog readouts
▪ Standard one year warranty on unit and on compressors ▪ Evaporator and condenser refrigerant pressure
▪ Factory run tested ▪ Compressor amps (each compressor)
▪ Water sensor: Evaporator leaving - Standard sensor to provide
temperature readout for water leaving the evaporator.
Controllers
▪ Vision 2020i Advanced microprocessor based DDC controller ▪ Fluid temperature reset value
with 132x64 pixels DBG1 semi-graphic display panel with ▪ Water flow switch status
menu driven software digital readout, pushbutton keyboard ▪ External stop/start command status
▪ Selection on English (Imperial) or metric display units ▪ Condenser fan cycling
▪ Remote monitoring via RS-485 port ▪ Low ambient lockout
▪ Leaving chilled fluid temperature ▪ Identification of up to 99 most recent alarms with critical data
▪ Evaporator and condenser pressure stamping
▪ Single phase amp draw, each compressor ▪ OPTIONAL (BMS Communication option)
▪ No. of compressor starts ▪ Optional Ambient temperature sensor
▪ Elapsed run time, each compressor ▪ Optional Return water temperature sensor
▪ Oil level status ▪ Optional Remote and stop signal
Digital readouts Capacity control Setpoints
▪ Compressor contactor ▪ Elapsed compressor run ▪ Leaving water temperature ▪ Amp limit
status time ▪ Freeze up temperature ▪ Ramp up
▪ Flow switch status ▪ External enable/disable ▪ High and low pressure
▪ Oil level status status
▪ Number of compressor ▪ Liquid injection solenoid
starts state
Unit Protection
▪ High and low pressures
Physical Specifications
Compressors (Qty) HSC 1616HHL6V6K(1) Shipping weight (lb) 7,329
Length (in) 152.00 Operating weight (lb) 7,535
Width (in) 89.00 Approx. refrigerant charge (lb) 287
Height (in) 89.00 Refrigerant R-134a
Conditions of service
Percent of full load 100% Compressor power (kW) 120.1
Capacity (Tons) 111.4 Total Fan Power (kW) 15.12
Unit power (kW) 135.2 Cooling Efficiency (EER, Btu /[Link]) 9.889
[Link] (EER, Btu /[Link]) 13.35
Evaporator
Model (Qty) C5R Leaving fluid temp. (°F) 44.60
Fluid Water Fouling factor (h·ft²·°F/Btu) 0.000100
Fluid flow rate (USgpm) 296.9 Pressure drop (psi/ft.H2O) 4.97/11.5
Entering fluid temp. (°F) 53.61 Fluid freezing point (°F) 32.00
Condenser
Design ambient (°F) 107.0 Altitude (ft) 0.000
Fan Motor Power (kW) (Qty) 2.520 (6)
Electrical characteristics
Unit power supply 400V/3ph/50.0Hz Unit rated load amps 231
Unit max. fuse size (A) 450 Unit min. circuit ampacity (A) 281
Total Comp. RLA (A) 199
Notes
- Refrigerant charge may vary. Unit nameplate will show final - Certified in accordance with the AHRI Air Cooled Water-
factory charge. Chilling Packages Using the Vapor Compression Cycle
Certification Program, which is based on AHRI Standard-
550/590(I-P) and AHRI Standard 551/591(SI). Certified units
may be found in the AHRI Directory at [Link].
[Link] Points
% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F)
100% 111.4 135.2 120.1 15.12 9.889 107.0
75% 83.58 88.80 78.72 10.08 11.29 87.5
50% 55.72 41.89 34.33 7.560 15.96 68.0
25% 27.86 30.28 25.59 4.690 11.04 55.0
Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 32.80 ft 46 53 57 57 57 55 50 37 63
*Sound Pressure Level (free field) ± 2 dB(A) Tolerance
Standard Equipment
Cabinet Construction Unit Construction
▪ (Cabinet construction information not available) ▪ Unit shall be constructed of heavy gauge G90 galvanized steel
▪ All sheet metal parts are painted with oven baked epoxy /
polyester powder paint, sustaining 1000 hour salt spray test in
accordance with ASTM B-117
▪ Rigid Structural base to prevent unit deformation and damage
during hoisting
▪ Bolted construction for easy semi knockdown at site in case
hoisting problem
▪ Compressor contactor ▪ Elapsed compressor run ▪ Leaving water temperature ▪ Amp limit
status time ▪ Freeze up temperature ▪ Ramp up
▪ Flow switch status ▪ External enable/disable ▪ High and low pressure
▪ Oil level status status
▪ Number of compressor ▪ Liquid injection solenoid
starts state
Unit Protection
▪ High and low pressures
▪ High discharge temperature
▪ Freeze protection
▪ Low pressure differential
▪ Low oil level
▪ Compressor run error and over current
▪ Power loss
▪ Chilled water flow loss
▪ High/Low System voltage
▪ Sensor error
▪ Compressor anti-recycle