16 Samss 503
16 Samss 503
1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 Information Required with Quotation.............. 4
5 Definitions....................................................... 5
6 General........................................................... 7
7 Service Conditions......................................... 8
8 Rating............................................................. 8
9 Enclosure....................................................... 9
10 Conductors................................................... 15
11 Grounding (Earthing).................................... 20
12 Switching Devices........................................ 20
13 Interlocks...................................................... 27
14 Protection, Control and Metering................. 27
15 Motor Space Heating System...................... 36
16 Accessories................................................. 36
17 Nameplates and Marking............................. 36
18 Testing and Inspection................................. 37
19 Shipping....................................................... 39
Previous Issue: 21 May 2012 Next Planned Update: 30 October 2017 Page 1 of 42
1 Scope
This Specification defines the mandatory requirements for indoor low voltage controlgear
built to either the International Electrotechnical Commission (IEC) or North American
(NA) based Standards.
2.1 If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.
2.2 Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.
3 References
The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.
Page 2 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Underwriters Laboratories
UL 198C High-Interrupting-Capacity Fuses, Current-Limiting
Types
UL 198D Class K Fuses
UL 198E Class R Fuses
UL 363 Knife Switches
UL 489 Molded-Case Circuit Breakers and Circuit-Breaker
Enclosures
UL 508 Industrial Control Equipment
UL 845 Motor Control Centers
UL 1087 Molded-Case Switches
Page 3 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
The following is a list of the information which shall be supplied with the Quotation:
4.1 A detailed listing of all deviations from this standard with an explanation against
each item. In addition, written certification shall be provided that the proposed
equipment shall fully comply with all other items within this Standard.
Page 4 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
5 Definitions
Definitions of terms within this Specification, not covered below, shall be as per
IEC 60050.
Compression connectors: Are connectors which are compressed onto the conductor
using a die and high mechanical force. The process is not reversible and the connector
becomes a permanent part of the conductor. The connector can only be removed from
the conductor by either cutting the conductor or cutting the connector.
Conductor: Applies to all material, devices and parts which are expected to carry
current as part of their normal function (e.g., cable, bus, relay contacts, terminal block
studs, etc.).
Discrete: Device which only performs one function. For example, a discrete voltmeter
only displays voltage.
IntC: Intelligent Control. All switching assemblies contain intelligent devices which
are networked together. This network is connected directly to the plant process control
computer system. All necessary two-way communication to control the switching
assemblies are performed over this network. The result is that one control circuit can
control all the switching assemblies in multiple controlgear.
Main Circuit: All the conductive parts of an assembly included in a circuit which is
intended to transmit electrical energy to the connected load.
Main Controlgear Disconnector: A device to isolate the controlgear from the main
incoming circuit.
Page 5 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Mechanical connectors: Connectors which are attached onto the conductor using,
generally, a standard tool. The process is reversible and the connector can be removed
from the conductor without cutting the conductor or the connector.
Raceways: Enclosed channels for housing and protecting electric wires and cable.
This term includes rigid and flexible conduit.
Space: Switching assembly locations which are not be equipped with a switching device
but shall be developed to accept, with no modifications other than the installation of
devices within the compartment door, a switching device suitable for a 19 kW (25 H.P.)
induction motor.
Specification: The main body (i.e., sections 1 to 19) and applicable Supplement and
does not, for example, include the information contained within the Data Schedules.
Switching assembly: The assembly of switching devices and associated control and
auxiliary equipment which controls or distributes power to a single load or via a single
circuit (e.g., a motor starter is a switching assembly).
Page 6 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Wireway: Troughs with hinged or removable covers for housing and protecting
electric wires and cable.
6 General
6.2 The controlgear shall also fully comply with either the “NA Supplement” or the
“IEC Supplement”.
6.5 This Specification shall take precedence over any referenced third party
document.
6.6 The main circuit bus systems of controlgear and switchgear shall not be
connected together.
6.10 All temperatures expressed within this specification are in Celsius units.
(NA Supplement)
6.NA1 Clearance and creepage distances and spacing shall meet the
requirements of NEMA ICS 1.
(IEC Supplement)
6.IEC1 Clearance and creepage distances and spacing shall meet the
requirements of IEC 60947-1.
Page 7 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
7 Service Conditions
7.3 Altitude is less than 1000 meters, unless a higher altitude is specified within
Data Schedule 1.
8 Rating
8.1 The rating of the controlgear shall not be dependent on forced-air systems.
Page 8 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
8.4 All short circuit ratings shall be based upon not having a short circuit protective
device within the main circuit of the controlgear; either integrated into the
controlgear or as a separate unit during testing. (i.e., ratings are not
“conditional”).
(NA Supplement)
8.NA1 Rated Operational Voltage: 480 V
8.NA2 Rated maximum voltage: 575 V
8.NA3 Rated Short-Circuit Withstand Current: 25 kA rms for 3 cycles
8.NA4 Dielectric Voltage Withstand rating: 2.15 kV for 1 minute
(IEC Supplement)
87.IEC1 Rated Operational Voltage: 600 V
8.IEC2 Rated Insulation Voltage: 660 V
8.IEC3 Rated Prospective Short- Circuit
Withstand Current: 25 kA rms for 3 cycles
8.IEC4 Dielectric Test Voltage: 2.5 kV for 1 minute
9 Enclosure
9.1 General
Vertical wireways are not required in the vertical portions of the vertical
section containing fixed mounted switching assemblies. (e.g., large
breakers/starters, AFDss, etc.)
Page 9 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Exception:
This does not apply to main controlgear disconnectors since these are
not considered switching devices. Refer to Section 12 for the
requirements for main controlgear disconnectors.
9.1.6 Controlgear shall be provided with a minimum of one space for every
three vertical sections.
9.2 Compartments
Page 10 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Page 11 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(NA Supplement)
Page 12 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(IEC Supplement)
9.3 Wireways
9.3.2 All wireways shall be accessible from the front of each vertical section
via compartment doors.
9.3.3 The controlgear shall have a horizontal wireway at the top and bottom
transversing the entire width of the controlgear. This wireway shall
have the following characteristics:
a) The horizontal wireway into/from which the field cables do not
enter/exit:
i) Shall have a minimum internal height of 150 mm.
ii) Shall have a minimum cross-sectional area of 29,000 mm²
except at the vertical wireway transition point noted below.
iii) Shall have a minimum cross-sectional area of 15,000 mm² at
the transition point between vertical sections.
b) For the horizontal wireways into/from which the field cables
enter/exit:
i) Shall have a minimum internal height of 150 mm.
ii) Shall have a minimum cross-sectional area of 50,000 mm².
If the cables are entering/exiting both the top and bottom
wireways, this minimum cross-sectional area shall apply to
Page 13 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
9.3.4 Each vertical section shall have a vertical wireway. This wireway and
shall have the following characteristics:
a) Shall have a minimum internal width of 200 mm.
b) Shall have a minimum cross-sectional area of 40,000 mm².
c) Shall have a minimum cross-sectional area of 20,000 mm² at the
transition point between the vertical and horizontal wireways or at
the barriers that are used protect the terminal blocks.
d) With the compartment door open, width of the access opening shall
be a minimum of 75% of the wireway width and a minimum of
90% of the wireway height (this height does not include the top
and bottom horizontal wireway).
e) The wireway adjacent to withdrawable switching assemblies shall
interconnect the top and bottom horizontal wireways.
Power and control terminal blocks directly associated with the switching
assemblies (refer to paragraph 10.3.11) may be installed within the
vertical wireway immediately adjacent to the switching assembly.
Page 14 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
9.4.2 The exterior of the controlgear shall be of a uniform color. The color
shall be the manufacturers standard except that the colors red, green,
yellow, orange or blue shall not be used.
10 Conductors
10.1 General
10.1.4 Each vertical section shall include a main circuit vertical bus system
to accept withdrawable switching assemblies. This bus shall have the
following characteristics:
a) Shall transverse the entire height of the controlgear.
Exception:
Page 15 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
10.1.5 The controlgear shall be equipped with a main circuit horizontal bus
and ground bus extending the full width of the assembly. All
connections shall be via bolted connections and all necessary hardware
to interconnect the bus between shipping splits shall be supplied.
10.1.6 The main circuit horizontal bus system and ground bus system serving
multiple vertical sections shall each have the same ampacity rating
throughout.
10.1.7 If vertical ground busses are specified within Data Schedule 1, each
vertical section shall be equipped with a vertical ground bus to allow
the termination of load cable ground conductors within or immediately
adjacent to the switching assembly. This bus may be either in the
vertical wireway or with the main circuit vertical busses.
a) If located within the wireway, the bus shall be pre-drilled by the
Supplier to accommodate a field installed, single hole connector
for each of the maximum possible number of switching
assemblies within the vertical section.
b) If located with the main circuit vertical busses, the switching
assembly shall include a terminal, which is in direct electrical
contact with the ground bus when the switching assembly is in
the connected position. This terminal shall accommodate a field
installed, single hole connector.
10.2 Material
10.2.1 All conductors shall be copper, silver or alloys of these materials with
the following exceptions:
Exceptions 10.2.1:
Page 16 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
10.2.2 The main circuit horizontal bus, main circuit vertical bus and ground
bus shall be of rigid material. Cable shall not be used as a substitute
for rigid bus material including transition circuits to other controlgear
(e.g., to interconnect main circuit bus between back-to-back
controlgear assemblies; refer to paragraph 10.1.3).
Commentary Note 10.2.2:
Cable is allowed for taps off the main bus system (e.g., connection to
the primary of PTs or control transformers, connection to fixed mounted
switching assemblies, etc.)
10.2.4 Mating surfaces, within the main circuit, between the stationary and
movable stab assemblies of the withdrawable main controlgear
disconnector shall be silver plated.
Page 17 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(NA Supplement)
(IEC Supplement)
10.3 Terminations
10.3.1 Whether the Supplier supplies the main circuit bus or ground bus
connectors or whether they are field supplied shall be as indicated on
Data Schedule 1.
10.3.4 The size and number of main circuit supply conductors shall be as
indicated within Data Schedule 1.
Page 18 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
10.3.6 Shorting type terminal blocks shall be provided for current transformer
circuits.
10.3.7 Low voltage circuit terminal blocks used to terminate the field cables
to the controlgear shall have the following characteristics:
a) Operational voltage rating shall be a minimum of 250 V.
b) Continuous current rating shall be a minimum of 10A.
c) Be either panel, rail or open mounted.
d) Be rated for 75°.
Exception:
10.3.8 There shall be a maximum of two (2) connectors per termination point
and only if the termination point is approved for two (2) connectors by
the manufacturer.
10.3.11 Termination of the field main load circuit and control/auxiliary cables
to the switching assemblies shall be as follows:
a) Main circuit cables
To terminal blocks or directly to the switching device terminals.
Page 19 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
b) Control/auxiliary cables
To terminal blocks.
(NA Supplement)
(IEC Supplement)
11 Grounding (Earthing)
Refer to Section 10 for the requirements of the controlgear ground conductor system.
12 Switching Devices
12.1 General
12.1.2 All main circuit switches and main circuit circuit breakers shall have
the following characteristics:
a) If the switching assembly has an exterior door, be manually
operable only with the door in the closed, secured position. Note
that this is conditional upon the mechanical interlocking
described within Section 13.
b) The center of the grip of the operating handle shall be a
maximum of 2000 mm from the base of the controlgear or the
working surface.
c) The operating handle shall be directly mechanically connected to
the switch/circuit breaker irrespective of the position of any
compartment doors/covers.
Page 20 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Page 21 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
d) For the purposes of testing (refer to Section 17), shall not be, or
considered to be, a short circuit protective device.
e) The switch or circuit breaker and supporting structure shall be
constructed so that it can be moved to either the main circuit
connected or disconnected position without the necessity of
removing connections or mounting supports.
f) If a circuit breaker is used, it shall not be equipped with
instantaneous ground fault protection.
Page 22 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
12.2.3 Circuit breakers within switching assemblies shall have a short circuit
rating not less than that of the complete controlgear with the following
exception:
Exception 12.2.3:
(NA Supplement)
Page 23 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(IEC Supplement)
Page 24 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
12.3 Contactors
Page 25 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
12.3.3 The contactor drop-out voltage shall not be greater than 75% of the
rated voltage of the contactor coil which is holding the main contacts
closed.
12.3.4 The contactor coil shall withstand 110% of rated voltage continuously,
without damage to operating coils, and close successfully at 85% of
rated voltage.
(NA Supplement)
(IEC Supplement)
Page 26 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
13 Interlocks
13.2 The switch-disconnector or circuit breaker operating handle from being closed
unless the compartment door is in the closed, secured position. This interlock
shall be defeatable with two separate operations.
14.1 General
Page 27 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
14.1.2 All control, metering and protection devices, with manual features
which are operable with the compartment doors closed, (e.g., selector
Page 28 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Page 29 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
14.1.5 Control schemes which are designed to keep the main circuit
contactor poles closed for a time period during a main circuit voltage
dip/loss, shall not be used.
Note that Paragraph 12.2.3 accepts the use of non-rated magnetic only
breakers under certain conditions.
(NA Supplement)
14.2 Fuses
14.2.1 Fuses shall not be used in the main circuit with the following
exceptions:
Page 30 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Exceptions:
(NA Supplement)
(IEC Supplement)
Page 31 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
a) All motors:
i) Overload.
ii) Instantaneous Overcurrent
Commentary Note 14.3.1a)i):
14.3.3 Devices which provide the overload function shall have the following
characteristics:
a) An overload on any of the three phase conductors shall open the
main circuit to the motor.
b) Trip characteristics shall be automatically ambient compensated.
c) Class 20 trip class. If specified for specialized applications (e.g.,
submersible motors, hermetic motors, etc.) or where specifically
recommended by the motor manufacturer, Class 10 or 30 trip
class is acceptable.
d) Be manually resettable with the switching assembly
compartment door closed.
e) Trip setting be either:
i) Adjustable over a minimum range of 90% to 110%. The
overload device shall be selected so the required setting
shall be at the midpoint of the operating range (i.e., 100%
± 10%).
ii) Have interchangeable heating elements.
f) For manually controlled motors 0.75 kW (1.0 HP) or less, it is
acceptable that the overload function be provided by a thermal-
magnetic circuit breaker.
g) Be trip free.
Page 32 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(NA Supplement)
(IEC Supplement)
Page 33 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
14.4.3 All phase current transformers within each switching assembly shall
be identical in all characteristics.
14.4.4 The rated burden of all instrument, control and voltage transformers
shall be a minimum of 125% of the load burden.
(NA Supplement)
14.7 Meters
14.7.2 Main incoming amperage and voltage metering shall be provided for
each controlgear assembly or for each back-to-back controlgear
assembly. This metering shall have the following requirements:
Page 34 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(NA Supplement)
14.8.NA1 All relays which interface with the field cabling shall meet
the requirements of NEMA ICS 5, Part 2 for Control Relays
and contact ratings shall be a minimum of A600/P600.
(IEC Supplement)
14.8.IEC1 All electrical relays which interface with the Buyer's field
cabling shall have the following characteristics:
Page 35 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Within switching assemblies for all motors 75 kW (100 HP) and larger, and all other
motors where the engineering documents indicate motor space heaters are installed, a
contact shall be wired to a terminal block in the low voltage compartment for the buyer
connection to the 24 VAC control circuit of a remotely mounted motor space heater
contactor. Contact shall be closed when the main circuit contactor is deenergized.
16 Accessories
A complete set of special tools, which is required for controlgear maintenance, shall be
provided for each group of assemblies within a substation.
17.1 White nameplates with black lettering shall be provided to identify the
controlgear with the tag number indicated within Data Schedule 1.
17.2 The controlgear manufacturer's shop order number, date, and catalog
designation shall be indicated on the controlgear nameplate in addition to the
nameplate information required by the Standards indicated within the
Supplement.
Page 36 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(NA Supplement)
(IEC Supplement)
(NA Supplement)
18.NA1 The controlgear shall meet all the requirements of the following:
a) “Design Tests” (i.e., performed on representative assemblies):
Page 37 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
(IEC Supplement)
Page 38 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
the equipment.
19 Shipping
Revision Summary
30 October 2012 Major revision to remove unnecessary limitation to source small VFD from the RVL list.
Removing this restriction enables a wider list of supplier to participate in bidding and that will
optimize cost.
Page 39 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Data Schedule 1
16-SAMSS-503, Indoor Controlgear - Low Voltage
(Information to be supplied to Supplier)
Line #
17 Details:
__________________________________________________________________________
Service Information:
31 No./phase and size of main circuit supply conductors: _____ /ph., ______ AWG, MCM, mm²
(2)
32 Cabling Entrance/Exit Location : Top ( ), Bottom ( )
(1)
35 Control Method : IntC ( ) , ConC ( ).
(6)
37 If IntC: Communication protocol type __________________
(4)
39 Communication Topology : Redundant Loop ( ), Radial ( ), Vendor's Std ( )
(1)
45 Main Controlgear Disconnector: YES ( ), NO ( ).
50 Main circuit supply conductor connectors (if applicable): Supplied by Supplier: YES ( ), NO ( )
Page 40 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Notes to Buyer:
(1) Refer to SAES-P-116 for requirements.
(2) SAES-P-119 requires top entry for equipment in new substations.
(3) Per SAES-P-116, communication protocol shall match what is available at DCS I/O in substation.
(4) Selecting “Vendor's Standard” preferred since manufacturers use different topologies
Page 41 of 42
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-503
Issue Date: 30 October 2012
Next Planned Update: 30 October 2017 Indoor Controlgear - Low Voltage
Data Schedule 2
16-SAMSS-503, Indoor Controlgear - Low Voltage
(Information to be Supplied by Vendor with the Quotation Request)
Note: This is one of several documents which is required to be submitted with the
Quotation. Refer to Section 4 of this Specification.
Line #
Proposed
Required By Supplier
If built to NA Supplement......
Page 42 of 42