Fire Sprinkler Monitoring Training Manual
Fire Sprinkler Monitoring Training Manual
2
Foreword
The purpose of this manual is to provide general information to persons responsible for the design, installation
and operation of sprinkler system monitoring.
The manual covers terminology, basic theory of operation, basic system design, and installation information. As
with any installation, the manufacturers instructions should be followed.
It does not contain information regarding when or how a particular type of system should be installed in a
specific location. That should be performed by a qualified engineer or designer using information from the
NFPA codes and standards, any local or national building codes and the authority having jurisdiction.
Information in this manual was obtained from:
Potter Electric
National Fire Protection Association [NFPA]
3
Introduction
When properly installed, supervised, and maintained, automatic fire sprinkler systems are the most effective
method of controlling damage and providing life safety in the event of a fire. In most cases they will detect
and control a fire before hazardous flames and toxic gasses destroy a building or cause loss of life. Although
a sprinkler system may extinguish a fire, it’s primary purpose is to contain the spread of the fire until the fire
department arrives.
In an untended fully sprinklered building, if one or more sprinkler heads activate to extinguish a fire, water will
continue to flow until the system is shut down. Unless the head is one of the “on-off” types that reset when the
temperature returns to normal. Also, if the heat source should fail in the winter, sprinkler pipes containing water
could freeze and rupture. Water discharging through an open sprinkler head or broken pipe for several hours can
cause considerable damage. Monitoring for water flow and building temperature will alert the proper personnel
to those property damaging situations.
Sprinkler systems may sit idle for years or even decades, however, when needed they must work to perfection.
Even though they have an excellent performance record, the occasional failure can be catastrophic. Most of
these failures are the result of the sprinkler system not being fully operational at the time of the fire. Monitoring
for water flow, valve position, low building temperature, etc. along with regular testing according to NFPA
standards will help to ensure proper operation.
4
Glossary/Definitions
Addressable Device - A fire alarm system component with discreet identification that can have its status
individually identified, or that is used to individually control other functions.
Air Sampling-Type Detector - A detector that consists of a piping or tubing distribution network from the
detector to the areas being protected. A fan in the detector housing draws air from the protected area back to the
detector. The air is analyzed for products of combustion.
Alarm Signal - A signal indicating an condition that requires immediate response, such as a signal indicative of a
fire.
Alarm Verification - A feature of some automatic fire detection and alarm systems to reduce unwanted alarms.
Smoke detectors must report alarm conditions for a minimum period of time, or confirm alarm conditions within
a given time period after being reset, to be accepted as a valid alarm initiating signal.
Analog Initiating Device - An initiating device that transmits a signal indicating varying degrees of condition,
such as smoke obscuration levels. As contrasted with a conventional initiating device which can only indicate
an “on/off” condition.
Annunciator - A unit containing two or more indicator lamps, alpha-numeric displays, or other equivalent
means in which each indication provides status information about a circuit, condition, or location.
Approved - Acceptable to the “authority having jurisdiction”. Note: The National Fire Protection Association
does not approve, inspect or certify any installations, procedures, equipment, or materials, nor does it approve
or evaluate testing laboratories.
Authority Having Jurisdiction (AHJ) - An organization, office, or individual responsible for enforcing the
requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
Automatic Extinguishing System Operation Detector - A device that detects the operation of an extinguishing
system by means appropriate to the system employed. Including but not limited to water flow devices.
Automatic Extinguishing System Supervision - Devices that respond to abnormal conditions that could affect
the proper operation of an automatic sprinkler system or other fire extinguishing system. Including but not
limited to control valves, pressure levels, room temperature, etc.
Automatic Fire Detectors - A device designed to detect the presence of fire or the products of combustion.
Including but not limited to heat detectors, flame detectors, smoke detectors.
Auxiliary Fire Alarm System - A system connected to a municipal fire alarm system for transmitting an alarm
of fire to the public fire service communication center. Fire alarms from an auxiliary system are received at the
public fire service communication center on the same equipment and by the same methods as alarms transmitted
manually from municipal fire alarm boxes located on streets.
Branch Line - A piping system, generally in a horizontal plane, connecting not more than one hose connection
with a standpipe.
Breakglass Fire Alarm Box - A fire alarm box in which it is necessary to break a special element in order to
operate the box.
Ceiling - The upper surface of a space, regardless of height. Areas with a suspended ceiling would have two
ceilings, one visible from the floor and one above the suspended ceiling.
Ceiling Height - The height from the continuous floor of a room to the continuous ceiling of a room or space.
5
Ceiling Surfaces - Ceiling surfaces referred to in conjunction with the locations of initiating devices are as follows:
A) Beam Construction - Ceilings having solid nonstructural members projecting down from the ceiling surface
more than 4 in. and spaced more than 3 ft., center to center.
B) Girders - Girders support beams or joists and run at right angles to the beams or joists. When the top of girders
are within 4 in. of the ceiling, they are a factor in determining the number of detectors and are to be considered as
beams. When the top of the girder is more than 4 in. from the ceiling, it is not a factor in detector location. Check
Valve - A self-operating valve that is used to prevent reverse flow through any portion of the system.
Central Station - A supervising station that is listed for central station service.
Central Station Fire Alarm System - A system or group of systems in which the operations of circuits and
devices are transmitted automatically to, recorded in, maintained by, and supervised from a listed central station.
Class A Circuit - Class A refers to an arrangement of monitored initiating device, signaling line, or notification
appliance circuits, which would permit a single open or ground on the installation wiring of these circuits from
causing loss of the systems intended function.
Class B Circuit - Class B refers to an arrangement of monitored initiating device, signaling line, or notification
appliance circuits, which would permit a single open or ground on the installation wiring of these circuits to
cause loss of the systems intended function.
Combination Detector - A device that either responds to more than one fire phenomenon or employes more
than one operating principle to sense one of these phenomenon. Typical examples are combination smoke/heat
detectors or a combination rate of rise and fixed temperature heat detector.
Compatibility Listed - A specific listing process that applies only to two wire devices [such as smoke
detectors] designed to operate with certain control equipment.
Control Valve - A valve controlling flow to water-based fire protection systems. Control valves do not include
hose valves, inspector’s test valves, drain valves, trim valves for dry pipe, pre-action and deluge valves, check
valves, or relief valves.
Digital Alarm Communicator Receiver [DACR] - A system component that will accept and display signals
from digital alarm communicator transmitters [DACT] sent over public switched telephone network.
Digital Alarm Communicator System [DACS] - A system in which signals are transmitted from a digital
alarm communicator transmitter [DACT] located at the protected premises through the public switched
telephone network to a DACR.
Digital Alarm Communicator Transmitter [DACT] - A system component at the protected premises to
which initiating devices are connected. The DACT will seize the connected telephone line, dial a pre-selected
telephone number to connect to a DACR, and transmit signals indicating a status change of the initiating device.
Display - The visual representation of output data other than printed copy.
Dry Pipe Sprinkler System - A sprinkler system employing automatic sprinklers that are attached to a piping
system containing air or nitrogen under pressure, the release of which (as from the opening of a sprinkler)
permits the water pressure to open a valve known as a dry pipe valve, and the water then flows into the piping
system and out the opened sprinklers.
End Of Line Device - A device such as a resistor or diode placed at the end of a class B circuit to maintain supervision
End Of Line Relay - A device used to supervise power [usually for 4-wire smoke detectors] and installed
within or near the last device on an initiating circuit.
6
Evacuation - The withdrawal of occupants from a building. Note: Evacuation does not include relocation of
occupants within a building.
Evacuation Signal - Distinctive signal intended to be recognized by the occupants as requiring evacuation of
the building.
Fire Alarm Control Unit [Panel] - A system component that receives inputs from automatic and manual fire
alarm devices and may supply power to detection devices and transponders or off-premises transmitters. The
control unit may also provide transfer of power to the notification appliances and transfer condition of relays or
devices connected to the control unit. The fire alarm control unit can be a local unit or a master control unit.
Fire Rating - The classification indicating in time [hours] the ability of a structure or component to withstand
fire conditions.
Fire Safety Functions - Building and fire control functions that are intended to increase the level of life safety
for occupants or to control the spread of harmful effects of fire.
Flame Detector - A device that detects the infrared, ultraviolet, or visible radiation caused by fire.
Four Wire Smoke Detector - A smoke detector which initiates an alarm condition on two separate wires
[initiating circuit] separate from the two power leads.
Heat Detector - A device that detects abnormally high temperature or rate of temperature rise.
Initiating Device - A system component that originates transmission of a change of state condition, such as a
smoke detector, water flow switch, etc.
Initiating Device Circuit - A circuit to which automatic or manual initiating devices are connected.
Ionization Smoke Detector - A smoke detector that has a small amount of radioactive material which ionizes
the air in the sensing chamber, thus rendering it conductive and permitting a current to flow between two
charged electrodes. This gives the sensing chamber an effective electrical conductance. When smoke particles
enter the sensing chamber they decrease the conductance of the air by attaching themselves to the ions, causing
a reduction in mobility. When conductance is reduced to less than a predetermined level, the detector responds.
Level Ceilings - Those ceilings that are actually level or have a slope of less than 1½ in. per foot.
Light Scattering - The action of light being reflected and/or refracted off particles of combustion for detection
by a photoelectric smoke detector.
Line Type Detector - A device in which detection is continuous along a path. Examples include projected beam
smoke detectors and heat sensitive cable.
Listed - Equipment or materials included in a list published by an organization acceptable to the “authority
having jurisdiction” and concerned with product evaluation, that maintains periodic inspection of production of
listed equipment or materials and whose listing states either that the equipment or material meets appropriate
standards or has been tested and found suitable for use in a specific manner. Note: The means for identifying
listed equipment may vary for each organization concerned with product evaluation, some of which do not
recognize as listed unless it is also labeled. The “authority having jurisdiction” should utilize the system
employed by the listing organization to identify a listed product.
Local Fire Alarm System - A local system sounding an alarm at the protected premises as the result of the
operation of automatic or manual initiating devices.
Manual Station [pull station] - A manually operated device used to initiate an alarm signal.
7
National Electrical Manufacturers Association [NEMA] - is a U.S. trade organization representing
manufacturers of products used in the generation, transmission, distribution, control, and end-use of electricity. Many
of NEMA’s standards have been approved as American National Standards or adopted by the federal government.
National Fire Protection Association [NFPA] - Administers the development of and publishes codes,
standards, and other materials concerning all phases of fire safety.
Non Restorable Initiating Device - A device whose sensing element is designed to be destroyed in the process
of operation.
Notification Appliance - A fire alarm system component such as a bell, horn, speaker, strobe, etc., that provides
an audible or visible output or both.
Obscuration - A reduction in the atmospheric transparency caused by smoke. Usually expressed in percent per foot.
Photoelectric Smoke Detector - A smoke detector utilizing a light source and a photosensitive sensor so
arranged that the rays from the light do not normally shine on the photosensitive sensor. When smoke enters the
light path, some of the light reflects off the smoke onto the sensor, causing the detector to respond.
Proprietary Fire Alarm System - An installation of fire alarm systems that serve contiguous and noncontiguous
properties under one ownership from a proprietary supervising station located at the protected property.
Rate Of Rise Heat Detector - A device which will respond when the temperature rises at a rate exceeding a
predetermined amount [usually about 15 degrees per minute].
Remote Station Fire Alarm System - A system installed in accordance with NFPA 72 to transmit alarm, trouble
and supervisory from one or more protected premises to a remote location at which appropriate action is taken.
Residual Pressure - Potential pressure remaining in the system while the system is flowing.
Restorable Initiating Device - A device whose sensing element is not ordinarily destroyed in the process of
operation. Restoration may be manual or automatic.
Should - In NFPA literature indicates a recommendation or that which is requested but not required.
Sloping Ceiling - Ceilings having a slope of more than 1½ in. per foot.
A) Sloping - Peaked Type, Ceilings in which the slope is in two directions from the highest point. Curved or
domed ceilings may be considered peaked.
B) Sloping - Shed Type, Ceilings in which the high point is at one side with the slope extending toward the opposite side.
Smooth Ceiling - A surface uninterrupted by continuous projections such as solid joists, beams or ducts,
extending more than 4 in. below the ceiling surface.
Solid Joist Construction - Ceilings having solid structural or nonstructural members projecting down from the
ceiling surface a distance of more than 4 in. and spaced at intervals 3 ft. or less, center to center.
Spot Type Detector - A device whose detecting element is concentrated at a particular location. Examples
include, certain smoke and heat detectors.
8
Static Pressure - Pressure acting on a point in the system with no flow from the system.
Story - The portion of a building included between the upper surface of a floor and the upper surface of a floor
or roof next above.
Stratification - An effect that occurs when air containing smoke particles or products of combustion is heated by burning
material, rises until it reaches a level where there is no longer a temperature difference between it and the surrounding air.
Supervision - A visual and audible alarm signal given at the central safety station to indicate when the system is
in operation or when a condition that would impair the satisfactory operation of the system exists. Supervisory
alarms shall give a distinct indication for each individual system component that is monitored.
Supervisory Signal - A signal indicating an “off normal” condition on the fire suppression system. Examples
include, tamper indication, low air pressure and low building temperature.
Thermal Lag - The difference between the operating temperature of a thermal detector and the actual air temperature.
Two Wire Smoke Detector - A smoke detector which initiates an alarm condition on the same pair of wires that
supply power to the detector.
Wet Pipe Sprinkler System - A sprinkler system employing automatic sprinklers attached to a piping system
containing water and connected to a water supply so that water discharges immediately from sprinklers opened
by heat from a fire.
9
Fire Alarm and Emergency Communication Symbols
Signal Initiating Devices
Referent (Synonym) Symbol Comments
telephone station
(telephone call point)
duct detector
gas detector
flow detector/switch
level detector/switch*
10
Audible Type Alerting Devices (Sounder)/Visual Type/
Emergency Illumination/Control and Supervisory
Referent (Synonym) Symbol Comments
bell (gong)
control panel
door holder
11
Water Supply and Distribution Symbols
Mains/Pipe/Valves
Referent (Synonym) Symbol Comments
non-indicating valve
(non-rising stem valve)
12
Organizations, Codes and Standards
Codes and Standards
The following NFPA codes and standards may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269-7471
Ph: 617-770-3000
Fx: 617-770-0700
[Link]
Standard
Standards detail how the protection required by the code is to be achieved.
Examples of Standards:
NFPA 13 Standard for the installation of sprinkler systems
NFPA 72 National Fire Alarm Code (This is actually a standard even though it is called a code)
The terms “Shall” and “Should” are often used. Shall indicates a mandatory requirement, Should indicates
a recommendation.
13
Determine Fire Alarm Requirements
NFPA 101 Life Safety Code determines the fire alarm requirements based on the occupancy classification of the
building.
Within each occupancy chapter, section 3.4 will specify the fire alarm requirements for that occupancy class.
NFPA 101 Section 3.4 is “Detection, Alarms & Communication”. Section 3.5 is “Extinguishing Requirements”.
Chapter 9 of the IBC and IFC determine the fire alarm and sprinkler requirements based on building classification.
The IFC then references the applicable NFPA standard for installation. Detection and notification requirements are
stated in the IBC and IFC as well.
Water supply control valves shall be supervised to obtain a distinctive signal when in an off normal position,
within 2 revolutions of the handwheel, or when the valve has moved one fifth from its normal position.
14
The switch shall not restore to a normal condition throughout the entire travel of the valve, until it is restored to a
fully open position.
A Supervisory signal must be visually or audibly distinctive from both Alarm and Trouble signals.
Water flow and supervisory devices cannot be connected on the same initiating circuit so that the closing of a valve
is annunciated as a “trouble” condition.
C. Trouble: A signal indicating a problem with the fire control panel or associated wiring which may
render the system inoperable.
1. Loss of primary power (120VAC)
2. Loss of secondary power (battery)
3. A defect in the supervised wiring to an initiating device, indicating appliance or extinguishing agent
release device.
4. Disabled circuit or function
5. Failure to communicate with central station
6. Fault
15
Basic Sprinkler Systems and Water Flow Alarm Devices
Wet Pipe Sprinkler Systems
There are three basic types of wet systems
16
Straight Pipe Riser Waterflow And Supervisory Switch Installation
(Main Riser Flow Switch)
Fig. 1
VSR
24” MIN.
SYSTEM PRESSURE
SUPPLY PRESSURE
DRAIN
PCVS
FEED MAIN
UNION WITH
RESTRICTED DRAIN VALVE (CLOSED)
OPENING
SAME SIZE AS
SPRINKLER
HEAD
TEST VALVE (CLOSED)
TO DRAIN
17
Note: All water control valves shall be supervised per NFPA13 2016 [Link].2.1.
#2. Wet System With An Alarm Check Valve:
This type of system has an alarm check valve, the valve is basically a check valve with an alarm port. The main
purpose of the alarm check valve is to ring a mechanical bell called a water motor gong. The valve should, (if
properly maintained), help hold the system pressure steady and reduce the possibility of false alarms. Under
normal circumstances, the clapper of the valve is closed, blocking the alarm port, maintaining the system
pressure, and preventing the sprinkler system water from leaking back into the city supply. When a sprinkler
opens due to fire, or there is a large surge in the city pressure, the clapper of the valve opens. The alarm port is
now exposed to the incoming water supply. When the pressure at the switch reaches 6 psi, the pressure switch
trips, or the retard time starts on the pressure switch with built in retard. This alarm port may be piped to the
outside of the building through a water motor gong.
These systems can use a vane type flow switch with a retard or they can use a pressure type flow switch. The
pressure type flow switch would be installed on the alarm port, in line with a water motor gong if one is being
used. The pressure switch must either be installed on top of a retard chamber, (see Fig. 3), or a pressure switch
with a built in retard, (see Fig. 4), must be used to prevent false alarms due to water surges. There must be an
automatic drain on this line to allow the water to drain and the pressure to drop back to zero so the pressure
switch can reset after a surge or activation of the alarm valve.
Pressure type flow switches can be installed without disabling the sprinkler system. Since they are installed on
the alarm port, there is no pressure or water present under normal circumstances. The sprinkler system does not
have to be drained, they can be installed without shutting off the water supply. Therefore the sprinkler system is
never out of service.
Retard chambers are metal containers that fill with water when there is a surge in city pressure. They absorb
the pressure increase thereby allowing the pressure switch to only operate in an actual alarm condition. There
is an automatic drain at the bottom of the chamber to allow the surge to drain out. Retard chambers require
maintenance to make sure that the drain stays clear and doesn’t get clogged with rust or corrosion. If a surge
does not drain from the retard chamber before another surge happens, the retard chamber may fill causing the
pressure switch to send a false alarm.
A pressure switch with a built in retard allows the system to remain operational at all times, and eliminates the
maintenance required on the retard chamber. An automatic drain is still required to relieve the pressure on the line.
Note: All water control valves shall be supervised per NFPA13 2016 [Link].2.1 and IFC 903.4. Pressure type
flow switches must be installed before any shut-off valve, or such valve must be electronically supervised.
18
Pressure Type Flow Switch Installed On Top Of Retard Chamber
Fig. 3 RISER TO
SPRINKLER HEADS
TO WATER
MOTOR
GONG
WATERFLOW
SWITCH
PS10-1
PS10-2
WATER
PRESSURE
GAUGE
(SYSTEM
PRESSURE) ANY SHUT-OFF VALVE IN
LINE WITH A PRESSURE
(OPEN) SWITCH IS REQUIRED TO BE
SUPERVISED PER NFPA 72
DRAIN
TAMPER
WATER BY-PASS RBVS
DEVICE
OSYSU TEST VALVE
(CLOSED) DRIP
STRAINER CUP
CHECK
VALVE
DRAIN
WATER PRESSURE FROM PIPE
CITY MAINS
Note:
Unless excess pressure is pumped into system, the waterflow device should have a retard per NFPA 72 2016
17.12. There shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-off is
electrically supervised. The Potter Model RBVS is designed to electrically supervise ball valves.
19
This is the same type of system except this one uses a pressure switch with a built-in retard instead of installing
the pressure switch on top of the retard chamber. In this case, the retard chamber is only being used to delay the
water motor gong. If there is no water motor gong, the retard chamber can be eliminated.
The retard time will start when the pressure at the WFSR-F reaches 6 psi. The pressure must remain there for
the length of time the retard is set in order for the device to trip.
Pressure type flow switches can be installed without disabling the sprinkler system. Since they are installed on
the alarm port, there is no pressure or water present under normal conditions. The sprinkler system does not
have to be drained, they can be installed without shutting off the water supply. Therefore, the sprinkler system is
never out of service.
A pressure switch with a built-in retard allows the system to remain operational at all times, and eliminates the
maintenance required on the retard chamber. An automatic drain is still required to relieve the pressure on the line.
20
Pressure Type Flow Switch With Built-in Retard
Fig. 4 RISER TO
SPRINKLER HEADS
WFSR-F
WATERFLOW DEVICE
WITH BUILT-IN
RETARD
TO WATER
MOTOR GONG
(OPEN)
RBVS
BY-PASS LINE
TAMPER
DEVICE WATER BY-PASS TEST
VALVE (CLOSED) STRAINER
OSYSU DRIP
CUP
DRAIN
WATER PRESSURE FROM PIPE
CITY MAINS
Note:
Unless excess pressure is pumped into system, the waterflow device should have a retard per NFPA 72 2016
17.12. There shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-off is
electrically supervised. The Potter Model RBVS is designed to electrically supervise ball valves.
21
#3. Wet System With Maintained Excess Pressure
This type of system has a jockey or excess pressure pump that is maintaining a higher pressure on the system
side of the check valve than the supply pressure can be expected to reach. This excess pressure holds the clapper
of the valve down even when the city pressure fluctuates. This eliminates false alarms caused by water surges.
Two different methods utilizing two different waterflow devices can be used to monitor these types of systems.
Excess pressure systems do not require retards on the flow switches.
On both systems the excess pressure pump should be monitored with a supervisory pressure switch. This switch
should be set to trip when the pressure drops 10 psi below normal, this will prevent false alarms due to a drop in
pressure from a pump failure. A typical excess pressure system may maintain a system pressure of 120 psi. The
low pressure supervisory switch would be set to trip at 110 psi. High pressure should be monitored to prevent
damage to sprinkler system and long delay of a waterflow alarm.
A pressure drop type waterflow device is connected to the system side of the check valve. Activation of a
sprinkler head in the system results in a loss of excess pressure, the pressure will drop down to whatever the
supply pressure is. The waterflow switch detects this drop in pressure and sends an alarm signal.
The low pressure supervisory switch is set to trip approximately 10 psi below the normal excess pressure.
The waterflow switch would be set to trip 10 psi below the supervisory switch. The trip point of the waterflow
switch must be higher than the water supply pressure can be expected to reach.
Note: All water control valves should be supervised per NFPA 13 2016, [Link].2.1.
22
Wet System With Excess Pressure (Pressure Drop)
Waterflow Alarm Installation
Fig. 5
RISER TO
SPRINKLER HEADS
PS100-2 BVL
WATERFLOW SWITCH BLEEDER VALVE
OPERATES ON (OPEN)
PRESSURE DROP
CLAMP TYPE
FITTING
PS120-2
EXCESS PRESSURE
SUPERVISORY SWITCH
DRAIN VALVE
(CLOSED)
JOCKEY DRAIN
PUMP PIPE
WATER
OSY CONTROL CHECK
VALVES (OPEN) VALVE
TAMPER TAMPER
DEVICE DEVICE
OSYSU OSYSU
FIRE DEPT.
BALL DRIP VALVE CONNECTION
(SIAMESE)
23
B. Wet System With Alarm Check Valve And Maintained Excess Pressure
A pressure type flow switch is connected to the alarm port of the alarm check valve.
Activation of a sprinkler head in the system results in a loss of excess pressure, this allows the alarm check valve to
open. When the valve opens, the alarm port is exposed to the incoming water supply. The waterflow pressure switch
detects this increase in pressure and sends an alarm signal when the pressure in the alarm line reaches 6 psi.
Note: All water control valves shall be supervised per NFPA 13 2016, [Link].2.1.
24
Wet System With Excess Pressure
(Waterflow With Pressure Supervision)
Fig. 6
RISER TO
SPRINKLER
EXCESS HEADS
PRESSURE
SUPERVISION
WATERFLOW SWITCH
PS120-1 (NO RETARD)
TO EXCESS PS120-2 PS10-1
PRESSURE
PS10-2
PUMP
BVL
BLEEDER
VALVE
CHECK
(OPEN) TO WATER
WATER BY-PASS
MOTOR GONG
TEST VALVE
(CLOSED)
DRAIN
VALVE
RBVS
(CLOSED)
CITY WATER
PRESSURE CHECK RBVS
GAUGE
CHECK
OSY CONTROL VALVE
VALVE (OPEN)
DRAIN
PIPE
Unless excess pressure is pumped into system, the waterflow device should have a retard per NFPA 72 2016
17.12. There shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-off is electri-
cally supervised. Per NFPA 72 2016 [Link].4, the Potter Model RBVS is designed to electrically supervise
ball valves.
25
Dry Pipe Systems
Dry pipe systems are usually installed in unheated buildings or where there is the danger of sprinkler pipes
freezing. They have pressurized air in the sprinkler piping, this allows for supervision of the system and
prevents water from entering the pipes. The dry pipe valve and associated equipment Shall be protected in
accordance with NFPA 13 2016, 7.2.5.
This type of system uses a dry pipe valve which has an intermediate chamber or alarm port. Under normal
conditions, this section of piping has no water or air pressure in it. A pressure type flow switch would be
installed on the alarm port, this could also be connected to a water motor gong on the outside of the building.
Waterflow switches on dry systems do not need retards as there should not be any water surges.
When a sprinkler head opens due to fire, the air pressure is released from the system, this allows the water
supply to open the dry pipe valve and enter the system piping. When the clapper of the dry pipe valve opens,
it exposes the alarm port to the incoming water supply. The pressure type flow switch senses this increase in
pressure and sends an alarm signal.
Dry pipe systems should also have a supervisory pressure switch installed to monitor the system air pressure.
This switch should be adjusted to send a low air signal when the system pressure drops 10 psi below normal.
This will prevent accidental tripping of the dry pipe valve due to low air pressure from a compressor failure.
They should also be monitored for high air pressure as too much pressure will delay the time it takes to bleed
enough pressure off the system to allow the water pressure to open the dry pipe valve.
Notes: All water control valves shall be supervised per NFPA 13 2016 [Link].2.1.
The room temperature where the dry pipe valve is located should be monitored to Prevent the valve
from freezing.
A bleeder valve and pressure gauge should be installed in line with the air supervisory switch for
test purposes.
A WCS (Water Column Switch) can be used to comply with NFPA13 2016, [Link].1
26
Dry Pipe Valve System
Waterflow Alarm Installation
Fig. 7
RISER TO
TO WATER SPRINKLER HEADS
MOTOR GONG
AIR SUPPLY
AIR PRESSURE
SUPERVISORY
PS40-1
PS40-2
WATERFLOW
SWITCH
PS10-1 CHECK
PS10-2
BVL BLEEDER
TEST VALVE
(OPEN)
PRIMING
CHAMBER
AIR
PRESSURE
BALL INTERMEDIATE
DRIP CHAMBER
VALVE
DRAIN VALVE (CLOSED)
WATER BY-PASS WATER TAMPER
TEST VALVE PRESSURE DEVICE
(CLOSED) GAUGE OSYSU
DRIP OS & Y
CUP CONTROL
VALVE
(OPEN)
CHECK
Note:
Per NFPA 72 2016 [Link].4, there shall
be no shut-off valve in line to a pressure type
waterflow switch, unless the shut-off ball DWG# 8704200-4A
27
Typical Wet System
Waterflow Switch Selection Guide
Fig. 8
IS THERE AN ALARM VALVE?
NO YES
WFSR-F PS10-1
INSTALLED SINGLE CONTACT
IN LINE WITH PS10-2
WATER MOTOR DOUBLE CONTACTS
GONG, BEFORE INSTALLED ON TOP
ANY SHUT-OFF OF RETARD
CHAMBER
WFSR-F TO WATER
WATERFLOW MOTOR
DEVICE GONG
PS10
SHUT-OFF
(OPEN)
ALARM LINE
(OPEN) SHUT-OFF VALVE,
SUPERVISED
PETCOCK
ALARM (OPEN)
(OPEN)
VALVE
RETARD
CHAMBER
CHECK
(OPEN)
TAMPER
DEVICE RBVS
OSYSU DRIP
CUP
OS & Y CONTROL
VALVE (OPEN)
DWG# 3003509-H1
FROM WATER
SUPPLY
28
Dry Pipe System Waterflow And Air Supervisory Switch
Selection Guide
Fig. 9 AIR PRESSURE SUPERVISION
PS40-1
LOW PRESSURE (SET AT 30 PSI)
PS40-2
LOW AND HIGH PRESSURE
(SET AT 30 AND 50 PSI)
RISER TO
SPRINKLER HEADS
WATERFLOW
SWITCH
PS40
TO AIR SUPPLY
AIR
PRESSURE
ALARM LINE
SHUT-OFF VALVE, WATER LEVEL SHUT-OFF VALVE
SUPERVISED (CLOSED)
(OPEN)
DRIP
CUP
OS & Y
CONTROL VALVE
(OPEN)
CHECK
Note: Unless excess pressure is pumped into the system, the waterflow device should have a retard. Per NFPA
72 2016 [Link].4, there shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-
off is electrically supervised. Potter Model RBVS can electrically supervise shut-off ball valves.
29
Valve Supervision (Tamper Switch)
Selection Guide
Fig. 10
TYPE OF VALVE
WALL
30
Installation of Waterflow Switches
Read and follow the manufacturers instructions.
Vane (Paddle) type: For use in wet pipe systems only!
Vane type water flow switches can be installed in either vertical or horizontal sections of pipe. If they are
installed in a horizontal section, they must be installed on the top half of the pipe. This is to prevent any debris
in the pipe from falling into the throat area of the flow switch and affecting the paddle movement. They should
never be installed on the bottom half of the pipe.
After shutting off the water to the system and draining it, drill the correct size hole for the flow switch. The hole
should be de-burred and the inside of the pipe should be cleaned of any rust, scale or corrosion. Do not trim the
paddle. The most likely area for a paddle to hang up is the area immediately upstream of the hole in the pipe,
on the same side of the pipe as the hole. When water flows through the system, the paddle is pressed against the
inside of the pipe.
The flow switch should be centered in the pipe and the “U” bolt should be tightened evenly according to the
manufacturer’s specifications. This will prevent the paddle from dragging on the inside of the pipe and prevent
the flow switch from leaking.
Fig. 11
COVER TAMPER SWITCH
TIGHTEN NUTS
ALTERNATELY
MOUNT ON PIPE SO
ARROW ON SADDLE
POINTS IN DIRECTION
OF WATERFLOW
ROLL PADDLE IN
OPPOSITE DIRECTION
OF WATERFLOW
DIRECTION OF
WATERFLOW
DWG. #1146-1E
31
When filling the system, first open any valves at the end of the system or branch lines. Slowly open the water
supply valve, let the water flow out of the valves until it is flowing smoothly. This will prevent air from entering
the system and help bleed any trapped air out of the system.
When installing the smaller flow switches that screw into a tee fitting, the proper size tee must be used. Never
use a reducing bushing to make the switch fit the tee. Bushings prevent the paddle from being in the proper
location in the tee. Also make certain that the correct paddle for the size and type of piping is being used and
that the paddle is on the stem tight. The flow switch must be screwed into the tee the proper depth.
After the installation is complete, slowly open the water control valve and open the inspector’s test valve. This
will help prevent air from being trapped in the system.
Fig. 12 Fig. 13
COVER TAMPER SWITCH Screw the device into the TEE fitting as shown. Care
must be taken to properly orient the device for the
direction of the waterflow.
4,3MM
APPROX.
(1 11/16”)
MOUNT SO
ARROW ON
BUSHING POINTS
IN DIRECTION OF
WATERFLOW DEPTH
1” NPT
THREADED
FITTING ON DWG# 735-33
ALL SIZES
DIRECTION OF
WATERFLOW
DWG# 802-30A
32
Pressure Type
Pressure type flow switches can be installed on wet systems that have an alarm check valve. They must be
installed on dry sprinkler systems. Pressure switches should only be installed with the threaded connection down.
On wet systems, the flow switch should have a retard. This can be accomplished one of two ways:
One is to install a pressure switch on top of a retard chamber. A retard chamber is a metal container capable
of holding a few gallons of water. When a water surge happens, the chamber fills with water and absorbs the
pressure before the pressure switch trips. There is a small drip valve at the bottom of the chamber to allow the
water to drain out before the next surge. Retard chambers require periodic maintenance to prevent the drip valve
from becoming clogged with rust or scale and causing false alarms. The time delay also varies depending on
how fast the water fills the chamber.
The other way is to install a pressure switch that has a retard built into it. It is installed in place of the retard
chamber. This eliminates the cost of the retard chamber and the time consuming maintenance associated with it.
This type of switch also provides a much more accurate retard time.
Dry sprinkler systems must use a pressure type flow switch. Vane type flow switches are not permitted on dry
systems per NFPA 13 2016, [Link]. Since dry systems are not subject to water surges, they do not require the
use of a retard. A pressure type flow switch would be installed in the alarm port of the dry pipe valve.
Since pressure type flow switches are installed on the alarm port of the valves, where there is no water or air
pressure under normal conditions, they can be installed or replaced without disabling the sprinkler system.
Low pressure switches should be installed in line with a bleeder valve and a pressure gauge. A bleeder valve
is a valve with a small orifice in it. The purpose of the valve is to exhaust the pressure between the bleeder
valve and the pressure switch. This allows testing of the switch without any possibility of an accidental tripping
of the dry pipe valve. It also speeds up the testing process since such a small amount of air is being released.
33
Installation of Valve Supervisory Switches
The main reason for sprinkler system failure is due to the water control valves being closed. Therefore, every
water control valve that can disable any portion of a sprinkler system should be electrically supervised in the
open position.
The main types of valves used are, outside screw and yoke [OS&Y], butterfly and wall or post indicator
[PIV] valves.
OS&Y valves have a large handwheel with a threaded shaft through the center of the handwheel. There is also
a bracket or “yoke” that runs on both sides of the threaded shaft, from the body of the valve to the handwheel.
When the valve is open, the shaft protrudes through the handwheel. As the valve is closed, the shaft is being
screwed into the body of the valve. Most tamper switches for these valves mount on the yoke of the valve using
either “J” hooks or carriage bolts and a mounting bracket. The switches have a “trip rod” that rests in a groove
on the threaded shaft of the valve. Some valve manufacturers put the groove on the stem, with other valves the
installer must file a 1/8” deep groove using a 3/8” rat tail, (round not tapered), file. As the valve is closed, the
trip rod rises out of the groove and trips the switch. The switch must stay tripped throughout the entire travel of
the valve. It must not alternate between “tripped” and “normal” as the trip rod is rolling across the threads of the
stem. The switch must also trip if the switch is removed from the valve.
Post Indicator Valves use a different switch than OS&Y valves. For PIV valves, the switch screws into a 1/2”
NPT fitting on the side of the valve. The switch has a trip rod that rides on the target of the valve. The target is
the portion of the valve that shows “open” or “shut”. When the valve is fully open, the target should be pushing
the trip rod against the spring force of the rod. As the valve is closed, the spring force causes the rod to follow
the target of the valve, tripping the switch.
Butterfly Valves use the same switch as PIV valves. It also screws into a 1/2” NPT fitting on the valve. The
trip rod is operated by a cam inside of the valve that rotates as the valve is closed. Partially close the valve,
remove the nipple from the switch and screw it into the valve. Loosen the set screw that holds the trip rod in the
housing and extend the trip rod. Slide the PCVS over the nipple, observing which direction the rod will move
when the valve is closed. Orient the device so the cam of the valve is pushing against the spring force of the
PCVS when the valve is open. As the trip rod touches the cam, it will push the trip rod back into the housing.
If the trip rod is too long, remove the rod from the switch housing, note that there is a groove cut into the rod
1” from the end of the rod that was in the housing, this can be broken off with a pair of pliers. After the cam of
the valve pushes the trip rod back into the housing, remove the PCVS and slide the trip rod 1/32” farther into
the housing before tightening the set screw. This will prevent any imperfections on the cam from affecting the
operation of the PCVS. Slide the PCVS over the nipple and tighten the set screw.
Ball Valves. The Potter Model RBVS can be used to supervise ball valves.
Special Valves. For non-rising stem valves a “plug type switch” can be used. These are switches that are UL
listed for special applications and are subject to the approval of the authority having jurisdiction. A receptacle is
mounted on a wall or section of pipe, a plug with a length of cable is plugged into the receptacle. The other end
of the cable is looped through the handwheel of the valve or through a hole drilled into the handle of the valve,
then hard wired back into the receptacle. When the valve is closed it unplugs the plug from the receptacle and
trips a switch. If the cable is cut it also opens the circuit. The cable must be stretched tight enough so operation
of the valve will cause the plug to pull out of the receptacle.
Note: Valve supervisory switches shall trip within 2 revolutions of the handwheel, or 1/5 of the travel of the
valve, per NFPA 72 2016, [Link].
34
Other Types of Supervision
Low Water Supply Pressure
Loss of water supply pressure in the sprinkler supply mains can be monitored with a supervisory pressure
switch. Care must be taken to adjust the pressure switch below the lowest pressure available during peak
demand periods to avoid nuisance alarms.
Fire Pumps
Fire pumps are automatically started in the event of water flow in a sprinkler system in order to supply more
water pressure to the system. Power to an electric pump should be supervised for loss of phase or phase reversal.
A pump running signal can be obtained by installing a pressure switch in the discharge line of the pump.
Pressure Tanks
These tanks are pressurized waster reservoirs used to supply a limited amount of water for sprinkler systems.
The tanks are usually located above the highest sprinkler heads under the main roof, or in a heated room on the
roof. Each tank is kept 2/3 full of water with a maintained pressure of approximately 75 psi in the tank.
Supervision includes: Water level, low and high pressure, low temperature, and water control valves.
Building Temperature
It is recommended that premises protected by wet sprinkler systems, or the room that a dry pipe valve is
located in, be monitored for low temperature of 40° F. This will prevent sprinkler pipes or dry pipe valves from
freezing should the building heating equipment fail.
35
Test Procedures
Waterflow Switches - Wet Pipe Systems
Vane Type
There should be a valve downstream of the flow switch, preferably at the far end of the system, but it may
be immediately after the flow switch. The valve should be marked Inspectors Test Valve per NFPA 13 2016,
[Link]. The alarm test connection shall comply with NFPA 2016, [Link].1. The output of the valve should be
piped to a spot where it will not cause any water damage.
Open the valve and allow the water to flow, after the retard time expires, the switch will trip. If the device does
not operate check to make sure 10 gpm is flowing out of the test valve. If possible, place a 5 gallon bucket under
the output of the valve. If the bucket can be filled in 30 seconds then the valve is flowing 10 gpm.
If a hose needs to be connected to the test valve to prevent water damage, the hose should be 5/8” ID, and as
short as possible to reduce friction loss.
If the device still does not trip it may be installed too close to a valve or change in direction of pipe which is
causing turbulence or back pressure in the water, or paddle may have been trimmed. Never trim the paddle.
Pressure Type
The preferred method is to open the inspectors test valve at the end of the system similar to the method for
testing vane type flow switches. This test also causes the clapper of the alarm valve to open.
Another test method is to open the normally closed alarm by-pass valve that connects the supply water directly
to the pressure switch. This is usually a 1/2” or 3/4” ball valve. On most systems there will be two ball valves
between the pressure switch and the alarm valve. One of these is the normally closed by-pass valve that is
only opened for testing. The other valve is a normally open alarm shut off valve. It is used to either silence the
pressure switch in an actual alarm or to disable it if water must be flowed into the system.
The pressure switch should be installed on top of a retard chamber or a pressure switch with a built-in retard
should be used. If the switch is installed on top of the retard chamber, it will activate as soon as the retard
chamber fills. The time delay provided by a retard chamber will vary depending on the water supply pressure at
the time. The time delay provided by a pressure switch with a built-in retard will remain constant. As long as the
pressure at the switch is at least 6 psi, the switch will trip after the retard times expires.
36
Fig. 14
RBVS
STRAINER
DWG# 8704200-5A
37
Dry Pipe Systems
Waterflow Switch - Pressure Type
Unless an annual trip test is being done, open the alarm by-pass valve. This will allow water to flow from the water
supply directly to the pressure type flow switch, as soon as the pressure reaches 6 psi, the flow switch should trip. This
is usually a 1/2” or 3/4” ball valve. On most systems there will be two ball valves between the pressure switch and
the alarm valve. One of these is the normally closed by-pass valve that is only opened for testing. The other valve is a
normally open alarm shut-off valve. It is used to either silence the pressure switch in an actual alarm or to disable it if
water must be flowed into the system.
If a bleeder valve is not installed: Shut off the water supply to the system. Shut off the air compressor. Slowly bleed air
off the system while observing the the pressure gauge so it can be determined at what pressure the low air switch trips
at. To bleed air off, a pipe union may need to be loosened or the inspector’s test valve partially opened. After the switch
trips, close the inspector’s test valve or tighten the pipe union, turn on the air compressor. After the air pressure returns to
normal, very slowly open the water supply valve.
38
Fig. 15
PRESSURE TYPE
WATERFLOW SWITCH
BLEEDER VALVE
FOR TESTING
LOW AIR SWITCH
DWG# 8704200-6A
39
Sprinkler System Supervision Includes:
Water Pressures
Water Flow
Water Supply Control Valves
Fire Pump Status
Water Tank, Levels, Pressures and Temperatures
Air Pressure on Dry Pipe Systems
Building Temperature
Water supply control valves shall be supervised to obtain a distinctive signal when in an off normal position,
within 2 revolutions of the handwheel, or when the valve has moved 1/5 from its normal position.
The switch shall not restore to a normal condition throughout the entire travel of the valve, until it is restored to
a fully open position.
When connected to a fire alarm panel, a Supervisory signal must be visually or audibly distinctive from both
Alarm and Trouble signals.
Water flow and supervisory devices cannot be connected on the same initiating circuit so that the closing of a
valve is annunciated as a “trouble” condition.
Inspection testing and maintenance of water based fire protection systems shall be conducted in accordance
with applicable NFPA codes and standards such as NFPA 25 and/or the Authority Having Jurisdiction. Please
refer to NFPA 25.2017 Annex B for forms and reports.
40
Visual Inspections Inspections are required at various frequencies as noted below.
Weekly
All Sprinkler Systems:
Inspect control valves (if sealed).
Water supply valves, including post indicator and roadway valves,
should be checked weekly if sealed and monthly if locked or supervised to
assure that they are open.
Inspect condition of sprinkler heads.
Heads should be checked to make sure they are not damaged or
blocked by storage and have not been painted or otherwise impaired.
Note: An 18 inch (457-mm) clear space must be maintained below the
sprinklers to assure an adequate discharge pattern. Attachment of 18-inch-
long paper or plastic streamers to the sprinkler piping helps remind people
working in storage areas of the minimum clear space requirement.
Dry Pipe Sprinkler Systems:
Inspect air pressure and water pressure gauges. Be sure that air
and water pressures are within the normal range for that
particular system.
Record pressure readings. It is recommended that the normal
pressure be noted on the gauge or a tag attached to it. A loss of
pressure of more than 10 percent should be investigated.
Monthly
All Sprinkler Systems:
Inspect fire department connections. Connections should be accessible and
visible at all times. Caps or plugs should be in place and threads clean,
undamaged and lightly lubricated with graphite.
The connection should be drained through the ball drip from the check valve
to assure it will not freeze.
Inspect control valves (if locked), including post indicator and roadway
valves to assure they are open
Water supply valves, including post indicator and roadway valves, should be
checked to assure that they are open.
Quarterly Determine dry pipe system priming water level, if required by manufacturer
by slowly opening the priming water level test valve. If only air escapes,
close the test valve and add priming water. This is done by closing the lower
priming valve, opening the upper priming valve, and adding approximately
1 quart of water through the priming funnel. The upper priming valve is
then closed and the lower priming valve opened, which allows the water to
run into the dry pipe valve. Again, check the test valve. If water does not
run out, repeat the procedure. When sufficient water has been added so that
water drains from the test valve, allow it to drain until air begins to escape,
then close the valve securely. Also be sure the upper and lower priming
valves are closed securely.
41
Semi-annually Check cold weather valves (if provided) in the Fall, before freezing weather.
The valves should be closed and that portion of the system drained. In the
Spring, as soon as freezing weather has passed, the cold weather valve should
be reopened.
Note: Cold weather valves are sometimes used to isolate a portion of a
sprinkler system that might be subject to freezing temperatures. During
cold weather, the valve is closed and that portion of the system is drained.
However, cold weather valves are not desirable, as protection is not provided
during cold weather or if valve is inadvertently left closed. Also, NFPA 13
does not recognize cold weather valves. A preferred arrangement would be
to provide a dry pipe system in the unheated area, or an antifreeze loop in a
small area.
1
Where historical data indicate, NFPA 25 permits longer intervals between testing.
2
Testing of a representative sample (minimum of 1% and no less than 4 sprinklers) must be done by a
recognized testing laboratory acceptable to the AHJ.
3
For example, testing or replacement is required at 50, 60, 70, 75, 80 (and every 5 years beyond).
4
For guidance on examples of harsh environments, see annex section A.[Link].2 of the 2014 edition of
NFPA 25.
Please refer to NFPA 25 2017, Chapter 5 for additional information on testing intervals for sprinkler
components and piping inspection
42
Sprinkler Testing: Testing is required at various frequencies as noted below.
43
Annually
Wet Pipe Sprinkler Systems:
Test the freezing point of antifreeze solutions if used. This is done by
measuring the specific gravity with a hydrometer. Adjust the solution as
necessary to maintain the freezing point of the solution below the estimated
minimum temperature and within concentrations permitted
Dry Pipe Sprinkler Systems:
Trip test the dry pipe valve at partial flow.
Before the trip test, the main drain valve should be fully opened and
the water supply flushed out until the water flows clean. If a hydrant is
located on the system supply, it should be flushed before the main drain
is flushed. This flushing will help to reduce the amount of debris getting
into the dry pipe system. Each dry pipe valve, including
quick opening devices if provided, should be trip tested. This test should
be done in the Spring after freezing weather, with the water supply control
valve only partially open. Once the valve trips, the water control valve can
be quickly closed so that the system is not filled with water. (Caution: Some
dry pipe valves will not operate properly without an adequate flow of water
to fully lift the clapper valve.) The valve is tripped by opening the inspector’s
test valve which releases air pressure within the system.
After the test, open the 2-inch main drain valve to drain the system. Remove
the valve cover and thoroughly clean the valve interior. Renew worn or
damaged parts as required, reset the valve, and replace the cover.
Add priming water and open the air supply to fill the system with air.
When the air pressure has reached its proper level, open the 2-inch main
drain to reduce the chance of a water hammer tripping the system,
then slowly open the water supply valve. When the water supply valve is
fully open, slowly close the 2-inch main drain.
Every 3 years Trip test the dry pipe valve at full flow.
The dry pipe valve should be trip tested with the water supply valve fully
open. The test should be terminated when clean water flows from the
inspector’s test connection.
A full trip test should also be conducted whenever the sprinkler system
undergoes a major alteration or extension.
Every 10 years Dry sprinklers that have been in service for 10 years shall be replaced or
representative samples shall be tested and then retested at 10-year intervals.
44
Every 20 years Sprinklers made with a fast response element and have been in service for 20
years shall be replaced or shall have a representative sample tested, and then new
samples shall be tested every 10 years
Every 50 years Remove a representative sample of standard response sprinklers from service
and provide new sprinklers in their place. Send the removed sprinklers to a
testing lab for operational testing in accordance with NFPA 13. If the sprinklers
fail to perform satisfactorily during the operational tests, all of them should be
replaced with new sprinklers of similar rating. After the 50-year operational test,
the test should be repeated every 10 years.
Note: A representative sample consists of the larger of 1% or no less than
four sprinklers per sampling area
Every 75 years Sprinklers piping shall be replaced or representative samples from one or
more sample areas shall be submitted to a recognized testing laboratory
acceptable to the authority having jurisdiction for field service testing and
repeated at 5-year intervals.
45
Smoke/Heat Detector Replacement See NFPA 72
Detector placement is critical to early warning functions. In order to provide an effective early warning of a developing
fire situation, smoke detectors should be installed in all areas of the protected premises. Local codes or ordinances may
not be adequate for early detection. The location, quantity and zoning of detectors should be engineered to provide
maximum life safety, as opposed to meeting minimum requirements of local codes.
For Areas With Smooth And Flat Ceilings Ten Feet In Height
All points on the ceiling shall have a detector within a distance equal to .7 times the listed spacing.
Spot type detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12” down form the ceiling
to the top of the detector.
The distance between detectors shall not exceed their listed spacing. There shall be detectors within one-half the listed
spacing, measured at right angles, from all side walls.
Detectors shall not be recessed mounted unless specifically listed for recess mounting.
Spot type smoke detectors must be a minimum 36” from air diffusers, and may not be in a direct airflow exceeding their
air velocity, regardless of distance.
Detectors shall be supported independently of their attachment to circuit conductors.
Spot type detectors should be mounted at least 6’ from florescent lights.
Except in cases where “stratification” is expected, detectors shall never be mounted more than 12” below ceiling level.
Detectors must be wired to ensure supervision of the detector head. Removal of the detector head must cause a trouble
condition on the panel.
Ceilings
Smooth Ceiling Spacing - Spot Type Smoke Detectors
In the absence of specific performance-based design criteria, smoke detectors shall be permitted to be located using
9.1 m (30 ft) spacing. NFPA 72, 2016, [Link].3.1
Solid Joist and Beam Construction
Solid joists shall be considered equivalent to beams for smoke detector spacing guidelines. NFPA 72, 2016, [Link].4.1
Level Ceilings
1. For ceilings with beam depths of less than 10 percent of the ceiling height (0.1 H), smooth ceiling spacing shall be permitted.
Spot-type smoke detectors shall be permitted to be located on ceilings or on the bottom of beams.
2. For ceilings with beam depths equal to or greater than 10 percent of the ceiling height (0.1 H), the following shall apply:
a. Where beam spacing is equal to or greater than 40 percent of the ceiling height (0.4 H), spot-type detectors shall be
located on the ceiling in each beam pocket.
b. Where beam spacing is less than 40 percent of the ceiling height (0.4 H), the following shall be permitted for
spot detectors:
i. Smooth ceiling spacing in the direction parallel to the beams and at one-half smooth ceiling spacing in the
direction perpendicular to the beams.
ii. Location of detectors either on the ceiling or on the bottom of the beams
3. For beam pockets formed by intersecting beams, including waffle or pan-type ceilings, the following shall apply:
a. For beam depths less than 10 percent of the ceiling height (0.1 H), spacing shall be in accordance with
[Link].4.2
46
b. For beam depths greater than or equal to 10 percent of the ceiling height (0.1 H), spacing shall be in
accordance with [Link].4.2
4. For corridors 15 ft (4.6 m) in width or less having ceiling beams or solid joists perpendicular to the corridor
length, the following shall apply:
a. Smooth ceiling spacing shall be permitted.
b. Location of spot-type smoke detectors on ceilings, sidewalls, or the bottom of beams or solid joists
5. For rooms of 900 ft2 (84 m2) or less, the following shall be permitted:
a. Use of smooth ceiling spacing
b. Location of spot-type smoke detectors on ceilings or on the bottom of beams
Sloped/Peaked Ceilings
Sloped Ceiling - Having a slope of more than 1.5 inches per foot
Peaked Ceiling - Having a slope of more than 1.5 inches per foot in two directions from its highest point. May
include domed or curved ceilings.
To determine if a ceiling is sloped or peaked:
Divide the difference between the height of the low wall and the highest point of the ceiling in inches by the
width of the building in feet. If the answer is 1.5 or less, the ceiling is considered flat. (Highest point of ceiling
in inches) minus (top of low wall in inches) divided by (width of building in feet).
0 10 100% 20 22 58%
47
Temperature Classification for Heat-Sensing Fire Detectors NFPA 72, 2016 Table [Link]
Note: The difference between the detectors rated temperature and the maximum ambient ceiling temperature
should be as small as possible to minimize response time.
48
section of piping. When water flows into the system, it also flows into this port. The flow switch will operate
when the pressure reaches 6 psi. These devices do not need a retard as there should be no water surges. This
device does not need adjusting.
The waterflow switch will not trip until after the release panel goes into alarm and operates the release circuit
which opens the valve and allows water to flow into the system.
49
WATER
SPRINKLER SPRINKLER SPRINKLER
MOTOR
ALARM
TO DRAIN
SMOKE SMOKE
DETECTOR DETECTOR
PS10
PRESSURE
SUPERVISORY
ALARM SWITCH
HORN
SUPERVISORY
BELL
PS10
PRESSURE
BVL
ALARM
BLEEDER
SWITCH
VALVE
TO AIR
SUPPLY
TO PFC-4410RC
MANUAL
STATION
24 VDC
SOLENOID
WATERFLOW
BELL
OSYSU
TAMPER
SWITCH
Single Interlock
DWG# 8704200-L
50
Pre-Action (Double-Interlock) Systems
The double interlock system is designed for applications such as refrigerated areas, requiring maximum
protection against inadvertent operation.
Double interlock systems use closed sprinklers attached to a piping system containing supervisory air pressure.
The water is held back by an electrically operated valve. The valve is connected to a compatible releasing panel.
The panel is monitoring initiating devices such as smoke or heat detectors, and manual stations that are located in
the same area as the sprinkler heads. These devices are connected to the releasing panels alarm initiating zones.
The supervisory air pressure in the piping system is also monitored. A low air switch on a double interlock
system may perform two functions. One is to send a supervisory signal if the air pressure drops to a certain
point such as if an air compressor failed. This would be connected to a supervisory zone on the release panel.
The other would be an alarm condition if the air pressure dropped farther such as from a sprinkler opening due
to fire. This would be connected to an alarm initiating zone on the release panel and is one of the two events
necessary for the panel to operate the release circuit. The other event is a smoke or heat detector going into
alarm. On some release panels the low air switch may only cause a supervisory condition not an actual alarm
condition even though it is still one of the two events necessary to operate the release circuit.
In order to trip the release circuit, two independent events must occur. The sprinkler system piping must lose
air pressure due to the operation of one or more heads which causes the low air pressure switch to trip, and the
release panel must detect an alarm from an initiating device such as a smoke or heat detector.
If the system pressure drops due to an open sprinkler, damaged pipe, or compressor failure, the pressure switch
will cause a supervisory and/or an alarm condition on the release panel. If a smoke or heat detector or manual
station has not operated, the release circuit will not trip because only one event has happened
If a smoke or heat detector operates or a manual station is activated, the release panel will go into alarm. If the low
air switch has not tripped, the release circuit on the panel will not operate because only one event has happened.
Initiating (inputs)
Zone #1 - Conventional Alarm Zone - Smoke or Heat detectors
Zone #2 - Conventional Alarm Zone - Low Air Alarm switch
Zone #3 - Waterflow Zone - Pressure type waterflow switch
Zone #4 - Manual Station Zone - Pull Stations
Sup #1 - Supervisory Zone - Valve tamper and low air supervisory switch
Sup #2 - Supervisory Zone - Valve tamper and low air supervisory switch
Indicating (outputs)
#1 - Alarm - General alarm. Bell, horn, strobe, etc.
#2 - Alarm - Waterflow bell
#3 - Release - Solenoid on valve
#4 - Supervisory - Bell or horn to indicate supervisory condition
Theory of Operation
When both zones 1 and 2 are in alarm at the same time or if the manual station zone is
activated, the release circuit and the general alarm outputs, will operate.
Activation of zone 1 or zone 2 will operate the general alarm output.
Activation of the waterflow zone will operate the waterflow output.
Activation of the supervisory zone will operate the supervisory output.
51
SPRINKLER SPRINKLER SPRINKLER
WATER
MOTOR
ALARM
TO DRAIN
SMOKE DETECTOR SMOKE DETECTOR
PS10
PRESSURE
SUPERVISORY
ALARM SWITCH
HORN
BELL
SUPERVISORY
PS10
BVL
PRESSURE
BLEEDER
ALARM
VALVE
SWITCH
TO AIR
SUPPLY
TO PFC-4410RC
MANUAL
STATION
SOLENOID
BELL
FIRE ALARM
OSYSU
TAMPER
SWITCH
52
Deluge Systems
The purpose of a deluge system is to deliver water immediately to the protected area. It wets down an entire
area by dispensing water through sprinklers or spray nozzles that are normally open. Since the operation of a
deluge system does not rely on the opening of sprinkler heads, they are suitable for extra hazard occupancies in
which flammable liquids are handled or stored.
The water for a deluge system is held back by an electrically operated valve. The valve is connected to a
compatible release panel. The panel is monitoring initiating devices such as smoke or heat detectors, and pull
stations. When the panel detects an alarm condition, the release circuit is energized. This allows the valve to
open and water to flow into the system piping and out of the normally open sprinklers or spray nozzles.
In order to prevent an accidental discharge of water, deluge systems are sometimes crosszoned. This requires two
initiating zones with one device in each zone to be in alarm before the panel will energize the release circuit. A
manual station zone will override the cross zoning feature and cause the release circuit to be energized immediately.
Typical Configuration
Initiating (inputs)
Zone #1 - Conventional Alarm Zone - Smoke or Heat detectors
Zone #2 - Conventional Alarm Zone - Smoke or Heat detectors
Zone #3 - Waterflow Zone - Pressure type waterflow switch
Zone #4 - Manual Station Zone - Pull Stations
Sup #1 - Supervisory Zone - Valve tamper
Sup #2 - Supervisory Zone - Valve tamper
Note: If the panel is programmed for cross zone operation, both zones 1 and 2 would have to be in alarm before
the release circuit would become energized. The manual station zone would override the cross zoning feature.
Indicating (outputs)
#1 - Alarm - General alarm. Bell, horn, strobe, etc.
#2 - Alarm - Waterflow bell
#3 - Release - Solenoid on valve
#4 - Supervisory - Bell or horn to indicate supervisory condition
53
WATER
OPEN SPRINKLER OPEN SPRINKLER OPEN SPRINKLER MOTOR
ALARM
TO DRAIN
SMOKE SMOKE
DETECTOR DETECTOR
ALARM
HORN
ZONE 1
ALARM
BELL
ZONE 2
PS10
PRESSURE
ALARM
SWITCH
TO PFC-4410RC
MANUAL
STATION
24 VDC
SOLENOID
WATERFLOW
BELL
OSYSU
TAMPER
SWITCH
DELUGE VALVE
SYSTEM DWG# 8704200-K
54
System Installation
• Read and Understand All Instructions Before Proceeding
• Follow the manufacturers instructions
• Never connect or disconnect wiring or circuit boards with any power applied!
• Test release panel completely before bringing it to the job site. This will eliminate the possibility of installing
a defective panel
• Perform power calculations to determine if system power supply and wiring are sufficient
• Perform battery calculations to determine proper battery size
• Fire circuits cannot be run in the same raceway, cable or conduit as high voltage circuits
• When not in conduit, fire circuits should not be strapped to high voltage conduit, as electrical “noise” can
interfere with the fire circuits
• Prepare a carefully laid out drawing of the complete system, including wiring hookup. A copy of this drawing
should be secured in the panel cabinet
• Locate the panel for convenience and serviceability
• Carefully remove the panel and any associated modules from the cabinet
• Mount the cabinet and complete all conduit connections
• Pull all system wiring through conduit, tag and mark wires
• Install panel and any associated modules in cabinet
• Check integrity of field wiring
3. List in column #3 the standby current of each device (exclude all signal indicating devices).
5. For each line, multiply the figure in column #2 by the figure in column #3 and enter the product in column
#4. Then multiply the figure in column #2 by the figure in column #5 and enter the product in column #6.
6. Add the figures in columns #3 and #6, enter the sums in the appropriate Total mA box.
7. Convert these figures from mill amperes to amperes by multiplying by 0.001, enter the product in the
appropriate Total A box.
8. Multiply the standby total amperes by required time in hours from table 2.
10. Add the standby AH and the alarm AH and divide this sum by 0.85 (efficiency factor). Select a battery that
has an AH rating above this figure but not less than 6.5AH.
55
Battery Size Requirements and Maintenance
These panels require a 24 volt gel-cell battery for proper operation. 24 hours of standby power is required for
Local Systems and Central Station (NFPA-72).
The chart below will assist you in selecting the proper size battery: (Does not include LED Annunciator)
Number Number of
Auxiliary Power Standby Hours Battery Size Part/Stock
of Smoke Bells
Requirements Required (2 Required) Number
Detectors (100mA each)
0-100 0-10 0-25mA 24 8AH BT-80/5130084
0-100 0-10 0-30mA 90 18AH BT-180/5130086
Note: Maximum allowed battery size for UL Listings is 12AH. FM and others may require more than 24 hours
of standby time and may use larger batteries (Potter stock model 1000015). Mark the purchase date on the bat-
teries. Test the batteries at least semi annually according to the battery test methods in NFPA72 or the battery
manufacturers instructions. Replace the batteries if they either fail the test or after four years of use.
56
Table 1 Current Requirements
Module/Device Standby mA* Alarm mA*
PFC-4410RC 121 274
RA-4410RC 11 13
*Add 23 mA plus current requirement of all devices connected for each output programmed as Trouble Bell
**Includes one zone short circuit current.
NFPA 72
• Central Station (PPU) 24 hrs. 5 mins.
• Local 24 hrs. 5 mins.
FMRC 1011 and 1012, Deluge and Pre-action Systems 90 hrs. 10 mins.
Where requested by FM or others.
90 Hours is not a UL requirement.
Calculation Table
1 2 3 4 5 6
Module/Device Quantity Standby mA Per Unit Total Standby Current Alarm mA Per Unit Total Alarm Current
Total mA Total mA
Convert to A x 0.001 Convert to A x 0.001
Total A Total A
Multiply by hours from table 2 x ___ 5 min/12 or 10 min/6 ÷ ___
Total Standby AH Total Alarm AH
+ Total Standby AH
Total AH
Efficiency Factor ÷ 0.80
Required AH
Use a battery with a higher AH rating than Required AH
57
This page intentionally left blank.
58
PFC-4410RC
Releasing Control Panel
Features
• Multi-Hazard Operation
• Programmable Cross Zoning
• Supervised Microprocessor
• Custom Banner Message and Zone Description text
• Releasing Circuits Protected From False Activation
• Continuous or Timed Discharge
• 40 Event History Buffer
• Walktest with Automatic Time-out
• Alarm, Trouble Supervisory, and Waterflow relays
• Optional Class A Initiating Zone and output module
• 24 Standard Programs in Panel Memory
• Suitable for agent or water-based extinguishing
• Programmable pre-discharge timers*
• One Class B Abort circuit* (Defaults to additional supervisory zone
in water based mode.)
• Four Abort modes*
* Available in Chemical mode only
** One zone programmable as abort in chemical mode.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 59 OF 118
PFC-4410RC
Releasing Control Panel
Architects/Engineers Specifications The control shall have one fully supervised class B (style B) Abort circuit
with 4 different operating modes, ULI, IRI, and NYC, and 30 second.
The control panel for the extinguishing agent releasing system shall be a
microprocessor based control capable of protecting multiple hazards in The control shall have four fully supervised Class B (Style Y) output
one control panel. It shall be Underwriters Laboratories Inc. listed under circuits. These circuits shall be selectable through the programming
Standard 864 Ninth Edition and Underwriters Laboratories of Canada sequence to operate as one of the following: Alarm Notification
for Local Control Units for Releasing Service. The control shall also be Appliance, Supervisory Notification Appliance, Trouble Notification
approved by Factory Mutual Research Corporation and be compliant with Appliance or Releasing. The optional CAM module may be added to
the requirements of NFPA-72 (Local: A, M, SS service types; DAC and convert the outputs to Class A.
NC signaling type) and NFPA12, NFPA12A, NFPA-13, NFPA-15, NFPA- The panel shall have an RS-485 output and auxiliary power outputs for
16, NFPA-17, NFPA-17A, NFPA-750, and NFPA-2001. connection and supervision of up to 4 remote annunciators or an ARM-44
The control shall be housed in an 18 gauge steel cabinet that has a hinged, Relay Module and 3 annunciators.
removable door with a key lock. The finish shall be baked enamel and The releasing circuits shall be supervised for short circuit conditions and
available in red or off-white with contrasting trim and logo. An optional shall be programmable for cross zoning operation when required. The
matching bezel should be available for semi-flush mounting. The cabinet discharge timer for these releasing circuits shall be programmable for
shall have adequate space to house 18 AH standby batteries capable of times of 7, 8, 9, 10, 20 minutes or continuous. All initiating and
operating the system for at least 90 hours. output circuits shall be capable of being individually disabled or enabled.
The control shall include a fully supervised integral power In addition, when in the agent extinguishing mode there shall be a pre-
supply/battery charger capable of providing 200mA to the auxiliary power discharge timer adjustable from 0-60 seconds from an alarm zone or 0-30
circuit. It shall also be capable of providing 2.5 Amps to all releasing seconds from a manual release zone.
and notification appliance circuits combined. All initiating, output and The control shall have a test mode that will automatically disable all
auxiliary power circuits shall be power limited. releasing circuits. The test mode shall operate in such a manner as to
The control shall have a 32 character (16 characters, 2 lines) backlit LCD automatically reset the initiating circuit and indicating circuits after
display and a 34 LED supplemental display. All diagnostic and alarm detecting each alarm condition initiated by the test. All testing shall be
event information shall be viewable in text form on this display. A field recorded in the 40 event history buffer. The test mode will automatically
programmable custom banner message with the current date and time terminate after twenty minutes of inactivity.
shall be displayed when no current alarm or diagnostic information exists. The control shall have four integral relay contacts rated 3 Amps at 30 VDC
All operational features of the control panel shall be field programmable for connection to external auxiliary equipment. One relay shall operate
using menu driven selections on the alpha-numeric display and on board when an alarm condition occurs, another when a trouble signal occurs,
controls. No special programmer will be required and jumpers or switches the third when a supervisory condition occurs, and the fourth during a
to configure operational features shall not be permitted. Alarm and trouble waterflow condition.
indications shall resound when required.
The control panel shall be equipped with 24 programs built into the panel
memory, 15 for water based extinguishing and 9 for agent extinguishing.
In addition, the panel shall have the ability to add custom programs. All
programming functions shall be password protected.
The control shall have four fully supervised Class B (Style B) initiating
circuits capable of supporting the operation of 25 compatible 2-wire
smoke detectors on each circuit.
The individual circuits shall be selectable through the programming
sequence to operate in one of the following modes: Conventional,
Waterflow, Linear Heat Detection (up to 700 ohms per zone), Manual
Release, Low Air Alarm, Supervisory, Tamper, Low Air or High Air.
Optional Class A modules, CA2Z, may be added for Class A operation.
The panel shall have a Low Air Zone that creates a supervisory condition
and can be mapped to a release output.
The control shall have two fully supervised Class B (Style B) supervisory
circuits. These circuits shall be selectable through the programming
sequence to operate in one of the following modes: Supervisory, Tamper,
Low Air or High Air.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 60 OF 118
PFC-4410RC
Releasing Control Panel
Ordering Information
Model Description Stock No.
PFC-
4 Zone Releasing Control (White Cabinet) 3992360
4410RC
PFC-
4 Zone Releasing Control (Red Cabinet)
4410RC
PFC-
4410RC- Replacement Motherboard
PCA
PFC-TW Bezel for Semi-Flush Mounting (White)
PFC-TR Bezel for Semi-Flush Mounting (Red)
Battery, 12V 8AH for 24 hour standby (2
BT-80
Req’d)
Battery, 12V 12AH for 24 hour standby
BT-120
(2 Req’d)
Battery, 12V, 18AH for 90 hour standby
BT-180
(2 Req’d)
CA2Z 2 Zone Class A Initiating Circuit Module
CAM Class A Indicating Circuit Module
ARM-44 Relay Module for PFC-4410RC
ARM-2 Auxiliary Relay Module
RA-
Remote Annunciator
4410RC
BB-RA- Surface Mount Back Box for RA-4410RC
44R (Red)
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 61 OF 118
BELLS
PBA-AC & MBA-DC
Features
• Listed for indoor and outdoor use
• Outdoor use requires BBK-1 or HC-BB weatherproof back box
• Indoor use mounts directly to standard 4” box
• Low current draw
• High dB output
• AC and DC models
• DC models are motor driven, polarized, and have built in transient
protection for supervised alarm circuits
• Available in 6”, 8” and 10” sizes
Size inches Voltage Model Stock Current Typical dB at Minimum dB at *Specifications subject to change without notice.
(mm) Number Number (Max.) 10 ft. (3m) (2) 10 ft. (3m) (1)
All DC bells are polarized and have built-in transient protection. * Does not have ULC listing.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 62 OF 118
BELLS
PBA-AC & MBA-DC
Installation
The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90” AFF and not less than 6” below the
ceiling.
1. Remove the gong.
2. Connect wiring (see Fig. 3).
3. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down).
4. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong).
5. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority hav-
ing jurisdiction).
5 3/4” 3 3/8” 5”
(146 mm) (86 mm) (127 mm)
10”
(250 mm)
8”
(200 mm) 6” 3 3/8”
1 5/8” (86 mm)
(150 mm) (41 mm)
4 1/4”
(108 mm)
DWG# 776-2
2 11/16”
(68 mm)
DWG# 776-1
1. POLARITY
OBSERVE POLARITY TO RING D.C. BELLS. 1. WHEN1. USING
WHEN A.C.
USING A.C. BELLS,
BELLS, TERMINATE
TERMINATE EACH EXTRA
EACH EXTRA WIRE SEPERATELY
WIRE SEPERATELY
1. OBSERVE TO RING D.C. BELLS.
2. RED WIRES (+).
POSITIVE (+). AFTER
AFTER LAST LAST BELL.
BELL.
2. RED WIRES POSITIVE
3. BLACK WIRES NEGATIVE (-). 2. END-OF-LINE
2. END-OF-LINE RESISTORRESISTOR
IS NOT IS NOT REQUIRED
REQUIRED ON AC ON AC BELLS
BELLS . .
3. BLACK WIRES NEGATIVE (-).
4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL.
4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 63 OF 118
BVL
Lever Type Bleeder Valve
Installation PS40
Wiring Instructions
The Model BVL, lever type bleeder valve, is for use as a test valve for
pressure operated devices on wet pipe sprinkler systems that have excess
pressure, or dry pipe sprinkler systems. BVL
The BVL should be installed in-line with the pressure device. It provides
a convenient means for removal or testing the pressure actuated device
without affecting the pressure in the system. Closing the valve (moving
the valve handle perpendicular to the 1/2” pipeline) shuts off the water
or air from the supply and opens a small orifice (pin-hole) to exhaust the
pressure between the valve and the pressure device. This should provide a
low pressure actuation of the pressure device, testing its operation.
Technical Specifications
Exhaust Orifice .125” (3mm) RISER TO SPRINKLERS
DWG# 799-1
Valve Body: Bronze
Material
Handle: Zinc Plated Steel
Connection 1/2” NPT male
Maximum System
CAUTION
300 PSI (20,68 BAR)
Pressure
*Specifications subject to change without notice. The BVL should be installed so the exhaust orifice is pointed in a safe
direction.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 64 OF 118
OSYSU Series
Outside Screw and Yoke Valve
Supervisory Switch
Features
• NEMA 4X* (IP 65) and 6P (IP 67)
*Enclosure is 4X. For additional corrosion protection of
mounting hardware, use model OSYSU-2 CRH
• -40º to 140º (-40ºC to 60ºC) operating temperature range
• Visual switch indicators
• Two conduit entrances
• Adjustable length trip rod
• Accomodates up to 12AWG wire
• Three position switch detects tampering and valve closure
• Knurled mounting bracket prevents slipping
• Fine adjustment feature for fast, easy installation
• RoHS compliant
• One or two SPDT contact models (-1,-2)
Before any work is done on the fire sprinkler or fire alarm system, the
building owner or their authorized representative shall be notified.
Before opening any closed valve, ensure that opening the valve will not
cause any damage from water flow due to open or missing sprinklers,
piping, etc.
Important: This document contains important information on the installation and operation of OS&Y valve supervisory switches. Please read all instructions
carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Technical Specifications
Description Dimensions See Fig 8
The OSYSU is used to monitor the open position of an OS&Y (outside Weight 1.6 lbs (0,73 kg)
screw and yoke) type gate valve. This device is available in two models;
the OSYSU-1, containing one set of SPDT (Form C) contacts and the Cover: Die Cast Finish: Red Powder Coat
OSYSU-2, containing two sets of SPDT (Form C) contacts. These Enclosure Base: Die Cast Finish: Black Powder Coat
switches mount conveniently to most OS&Y valves ranging in size from All parts have corrosion resistant finishes
2” to 12” (50mm to 300mm). They will mount on some valves as small
as ½” (12,5mm). Tamper Resistant Screws
Cover Tamper Optional Cover Tamper Switch Available
The cover is held in place by two tamper resistant screws that require a
special tool to remove. The tool is furnished with each device.
OSYSU-1: One Set of SPDT (Form C)
Testing OSYSU-2: Two Sets of SPDT (Form C)
Contact Ratings 10.0 Amps at 125/250 VAC
The operation of the OSYSU and its associated protective monitoring 2.0 Amps at 30VDC Resistive
system shall be inspected, tested, and maintained in accordance with all 10 mAmps minimum at 24 VDC
applicable local and national codes and standards and/or the Authority
Having Jurisdiction (manufacturer recommends quarterly or more -40º F to 140ºF (-40ºC to 60ºC)
frequently). A minimum test shall consist of turning the valve wheel NEMA 4X (IP 65) and NEMA 6P (IP 67) Enclosure
towards the closed position. The OSYSU shall operate within the first two Environmental (Use suitably rated conduit and connector)
revolutions of the wheel. Fully close the valve and ensure that the OSYSU Limitations Indoor or Outdoor Use (See OSYSU-EX Bulletin
does not restore. Fully open the valve and ensure that the OSYSU restores 5400705 for Hazardous locations)
to normal only when the valve is fully opened.
Conduit En- Two Knockouts for 1/2” conduit provided
trances (See Notice on Page 6 and Fig. 9 on Page 5)
CAUTION Service Use NFPA 13, 13D, 13R, 72
Close the valve fully to determine that the stem threads do not Specifications subject to change without notice
activate the switch. The switch being activated by the stem threads
could result in a false valve open indication.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 65 OF 118
OSYSU Series
Outside Screw and Yoke Valve
Supervisory Switch
Theory of Operation
The OSYSU is a 3 position switch. The center position is the normal installation position. Normal is when the switch is installed on the OS&Y valve, the valve
is fully open and the trip rod of the OSYSU is in the groove of the valve stem. Closing the valve causes the trip rod to ride up out of the groove and activates the
switches. Removing the OSYSU from the valve causes the spring to pull the trip rod in the other direction and activates the switches.
Micro-Adjustment
Feature
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 66 OF 118
DETAIL A
SCALE 1 : 1
OSYSU Series
Outside Screw and Yoke Valve
Supervisory Switch
B
Small Valve Installation - 1/2” Through 2 1/2” Sizes
Fig 6
SLOTTED MOUNTING
HOLES MAY BE USED
FOR FINE ADJUSTMENT
OF SWITCH ASSEMBLY
TO MOUNTING BRACKET
Slotted mounting holes and micro-adjustment
feature may be used for fine adjustment of switch
assembly to mounting bracket.
Re-tighten screws to 20 in-lbs minimum.
Small Valve Installation rod of the OSYSU pulled against the valve stem and centered in CEN
the groove of the stem. If possible, position the OSYSU with the
MOUNTING BRACKET
NOTE: If the valve stem is pre-grooved at 1/8” minimum
depth; proceed to step 7.
flat side of the bracket toward the hand wheel, as shown in Fig.
6, to help avoid creating a pinch point between the wheel and
1. Remove and discard "E" ring and roller from the trip rod. OSYSU. When in this preferred mounting position, it is usually
2. With the valve in the FULL OPEN position, locate the OSYSU best to use the white indicator visible through the window, as
across the valve yoke as far as possible from the valve gland so illustrated in Fig. 3, to aid in initially locating the OSYSU in
that the spring loaded trip rod of the OSYSU is pulled against the
non threaded portion of the valve stem. Position the OSYSU with
ROLLER
the correct position on the yoke. If the unit must be installed
inverted with the white indicator no longer easily visible, use the
the bracket near the handwheel as shown in Fig. 6 if possible to visual indicators of the actuator buttons on the micro-switches,
avoid creating a pinch point between the wheel and the OSYSU. as illustrated in Fig. 1, or the trip rod alignment mark on the
bracket, as illustrated in Fig. 2 , to aid in initially locating the
3. Loosen the locking screw that holds the trip rod in place and OSYSU.
adjust the rod length (see Fig. 5). When adjusted properly, the
rod should extend past the valve screw, but not so far that it 8. Final adjustment can be made by slightly loosening the two
contacts the clamp bar. Tighten the locking screw to 5 in-lbs screws on the bracket and using the fine adjustment feature
minimum to hold the trip rod in place and properly seal the (see Fig. 5). The adjustment is correct when the plungers on the
enclosure. switches are depressed by the actuator and there is no continuity
between the COM and NO terminals on the switches.
NOTE: If trip rod length is excessive, loosen the locking
screw and remove the trip rod from the trip lever. Using 9. Tighten the adjustment screws and all mounting hardware
pliers, break off the one (1) inch long notched section (see securely (20 in-lbs minimum). Check to insure that the rod
Fig. 10). Reinstall trip rod and repeat Step 3 procedure. moves out of the groove easily and that the switches activate
within two turns when the valve is operated from the FULL
4. Mount the OSYSU loosely with the carriage bolts and clamp bar OPEN towards the CLOSED position.
supplied. On valves with limited clearance use J-hooks supplied
instead of the carriage bolts and clamp bar to mount the OSYSU. 10. Reinstall the cover and tighten the cover screws to 15 in-lbs
minimum to properly seal the enclosure.
5. Mark the valve stem at the center of the trip rod.
6.
CAUTION
Remove the OSYSU. Utilizing a 3/16” or 1/4” diameter straight
file, file a 1/8” minimum depth groove centered on the mark on
the valve stem. Deburr and smooth the edges of the groove to Close the valve fully to determine that the stem threads do not
prevent damage to the valve packing and to allow the trip rod to
activate the switch. The switch being activated by the stem threads
move easily in and out of the groove as the valve is operated.
could result in a false valve open indication.
NOTE: A groove depth of up to approximately 3/16” can
make it easier to install the OSYSU so that it does not restore
as it rolls over by the threads of the valve stem.
7. Mount the OSYSU on the valve yoke with the spring loaded trip
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 67 OF 118
DETAIL A
SCALE 1 : 1
OSYSU Series
Outside Screw and Yoke Valve
Supervisory Switch
B
Large Valve Installation - 3” Through 12” Sizes
Fig 7
SLOTTED MOUNTING
HOLES MAY BE USED
FOR FINE ADJUSTMENT
OF SWITCH ASSEMBLY
TO MOUNTING BRACKET
Slotted mounting holes and micro-adjust-
ment feature may be used for fine adjust-
ment of switch assembly to mounting
bracket. Re-tighten screws to 20 in-lbs
minimum.
Large Valve Installation flat side of the bracket toward the hand wheel, as shown in Fig.
7, to help avoid creating a pinch point between the wheel and
CEN
MOUNTING BRACKET
NOTE: If the valve stem is pre-grooved at 1/8” minimum
depth; proceed to step 6.
OSYSU. When in this preferred mounting position, it is usually
best to use the white indicator visible through the window, as
1. With the valve in the FULL OPEN position, locate the OSYSU illustrated in Fig. 3, to aid in initially locating the OSYSU in
across the valve yoke as far from the valve gland as possible so the correct position on the yoke. If the unit must be installed
that the spring loaded trip rod of the OSYSU is pulled against the inverted with the white indicator no longer easily visible, use the
non threaded portion of the valve stem. Position the OSYSU with visual indicators of the actuator buttons on the micro-switches,
the bracket near the handwheel as shown in Fig. 7 if possible to ROLLER
as illustrated in Fig. 1, or the trip rod alignment mark on the
avoid creating a pinch point between the wheel and the OSYSU. bracket, as illustrated in Fig. 2 , to aid in initially locating the
2. Mount the OSYSU loosely with the carriage bolts and clamp bar OSYSU.
supplied. 7. Final adjustment can be made by slightly loosening the two
3. Loosen the locking screw that holds the trip rod in place and screws on the bracket and using the fine adjustment feature
adjust the rod length (see Fig. 5). When adjusted properly, the (see Fig. 5). The adjustment is correct when the plungers on the
rod should extend past the valve screw, but not so far that it switches are depressed by the actuator and there is no continuity
contacts the clamp bar. Tighten the locking screw to 5 in-lbs between the COM and NO terminals on the switches.
minimum to hold the trip rod in place and properly seal the 8. Tighten the adjustment screws and mounting hardware securely
enclosure. (minimum 20 in-lbs). Check to insure that the rod moves out of
NOTE: If trip rod length is excessive, loosen the locking the groove easily and that the switches activate within two turns
screw and remove the trip rod from the trip lever. Using when the valve is operated from the FULL OPEN towards the
pliers, break off the one (1) inch long notched section (see CLOSED position.
Fig. 10). Reinstall trip rod and repeat Step 3 procedure. 9. Reinstall the cover and tighten the cover screws to 15 in-lbs
4. Mark the valve stem at the center of the trip rod. minimum to properly seal the enclosure.
5. Remove the OSYSU. Utilizing a 3/8” or ½” diameter straight
CAUTION
file, file a 1/8” minimum depth groove centered on the mark on
the valve stem. Deburr and smooth the edges of the groove to
prevent damage to the valve packing and to allow the trip rod to Close the valve fully to determine that the stem threads do not
move easily in and out of the groove as the valve is operated. activate the switch. The switch being activated by the stem threads
NOTE: A groove depth of up to approximately 3/16” can could result in a false valve open indication.
make it easier to install the OSYSU so that it does not restore
as it rolls over by the threads of the valve stem.
6. Mount the OSYSU on the valve yoke with the spring loaded trip
rod of the OSYSU pulled against the valve stem and centered in
the groove of the stem. If possible, position the OSYSU with the
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 68 OF 118
OSYSU Series
Outside Screw and Yoke Valve
8 7 6
Supervisory Switch 5 4
8 7 6 5 4
Dimensions
F
6.19
Fig 8 157.23
4.00
3.20 3.05
2.25
101.60 81.26 77.47 57.13
3.20 2.25
81.26 57.13
2.79
E 70.87
2.79
70.87
5.69
5.69 144.42
144.42
4 3 2 1
3.67
2.10 F
93.26 3.67
53.34 2.10
93.26
53.34
C
Rod fully extended
Cover Tamper Switch
(Optional)
Knockout Removal
Fig 9
(2) ø.886 To remove knockouts: Place screwdriver at inside edge of knockouts, not in
Knockouts For 1/2” Cover Removed the center. E
BElectrical Conduit
Connections
.XX = ENGLISH
[[Link]] = METRIC
D
1/4”-20 Mounting
8 Hardware 7 6 5 4 3
8 7 6 5 4
NOTE: Do not drill into the base as this creates metal shavings which
can create electrical hazards and damage theC device. Drilling voids the
warranty.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 69 OF 118
B
OSYSU Series
Outside Screw and Yoke Valve
Supervisory Switch
EOLR
COM NC NO NO NC COM
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 70 OF 118
PCVS Series
Control Valve Supervisory Switch
Features
• NEMA 4X* (IP 65) and 6P (IP 67)
*Enclosure is 4X. For additional corrosion protection of
mounting hardware, use model PCVS-2 CRH
• -40º to 140º (-40ºC to 60ºC) operating temperature range
• Visual Switch Indicators
• Two conduit entrances
• Adjustable length trip rod
• Accomodates up to 12AWG wire
• Switch detects tampering and valve closure
• RoHS compliant
• Two SPDT contacts
Before any work is done on the fire sprinkler or fire alarm system, the
building owner or their authorized representative shall be notified. Be-
fore opening any closed valve, ensure that opening the valve will not
cause any damage from water flow due to open or missing sprinklers,
piping, etc.
Important: This document contains important information on the installation and operation of PCVS valve supervisory switches. Please read all instructions
carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Description Technical Specifications
The Model PCVS is a weather proof and tamper resistant switch for Dimensions See Fig 10
monitoring the open position of fire sprinkler control valves of the wall Weight 1.0 lbs (0,45 kg)
and yard post indicator and butterfly types. Two SPDT (Form C) contacts
Cover: Die Cast Finish: Red Powder Coat
are provided which will operate when the valve position is altered from an
Enclosure Base: Die Cast Finish: Black Powder Coat
open state.
All parts have corrosion resistant finishes
The unit mounts in a 1/2” NPT tapped hole in the post indicator or butterfly
valve housing. The device is engaged by the indicating assembly of the Tamper Resistant Screws
post indicator or the operating mechanism of the butterfly valve, actuating Cover Tamper Optional Cover Tamper Switch Available
switches when the valve is fully open. The unit should be installed where
it is accessible for service. PCVS-2: Two Sets of SPDT (Form C)
The cover is held in place by two tamper resistant screws that require a Contact Rat- 10.0 Amps at 125/250 VAC
special tool to remove. The tool is furnished with each device. ings 2.0 Amps at 30VDC Resistive
10 mAmps minimum at 24 VDC
Testing -40º F to 140ºF (-40ºC to 60ºC)
NEMA 4X (IP 65) and NEMA 6P Enclosure
The operation of the PCVS and its associated protective monitoring
Environmental
(IP67)(Use suitably rated conduit and connector)
system shall be tested upon completion of the installation and inspected, Limitations
Indoor or Outdoor Use (See PIVSU-EX Bulletin
tested and maintained in accordance with all applicable local and national 5400694 for Hazardous locations)
codes and standards and/or the Authority Having Jurisdiction, (manufac-
Conduit En- Two Knockouts for 1/2” conduit provided
turer recommends quarterly or more frequently). A minimum test shall (See Notice on Page 7 and Fig. 11 on Page 6)
trances
consist of turning the valve operating mechanism towards the closed posi-
tion. The PCVS shall operate within the first two revolutions of the op- Service Use NFPA 13, 13D, 13R, 72
erating mechanism. Fully close the valve and ensure the PCVS does not
Specifications subject to change without notice
restore. Fully open the valve and ensure that the PCVS restores to normal.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 71 OF 118
PCVS Series
Control Valve Supervisory Switch
Theory Of Operation
The PCVS is a spring loaded switch. It is in normal position when the trip rod is pulling against the spring force. Normal is when the switch is installed on the
valve and the valve is fully open. As the valve closes, the valve actuator moves away from the trip rod of the PCVS and the spring on the PCVS pulls the trip
rod over and trips the switch.
Subject to the approval of the “authority having jurisdiction” the alternate If the target is stationary and a hood arrangement is used, such as is
method of installation shown in Fig. 1 may be used. In this method, shown in Fig. 2, the hood must be drilled with a 23/32” drill and tapped
one of the glass windows of the housing is replaced with a 1/4” thick with a 1/2” NPT. The center line of this hole should be 1/8” below the
metal plate that is cut to fit in place of the glass and drilled and tapped to portion of target assembly that strikes the PCVS trip rod. The 11 3/8”
recieve 1/2” NPT pipe nipple. In some cases it may be necessary to attach
dimension shown is for a Clow Valve. Flexible conduit must be used for
an angle bracket to the target assembly to engage the PCVS trip rod.
this type of installation. (More on pg. 3).
Locknut
11 3/8”
(28,9 cm)
Shut Marker
Target Assembly
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 72 OF 118
PCVS Series
Control Valve Supervisory Switch
NOTE: Before any work is done on the fire sprinkler or NOTE: In some cases, it may be necessary to attach an
fire alarm system, the building owner or their
TARGET MOVESauthorized
UP TARGET
angle bracket
MOVES DOWN
to the target assembly to engage the PCVS trip
AS VALVE IS SHUT
representative shall be notified. Before opening any closed rod.
AS VALVE IS SHUT
valve, ensure that opening the valve will not cause any 10. Using the special tool provided, loosen the two cover screws and
damage from water flow due to open or missing sprinklers, remove the cover from the PCVS.
piping, etc.
11. Loosen the locking screw that holds the trip rod in place and
1. osition the valve to fully open (“OPEN” should appear in the
P adjust the rod length, from the end of the collar to the end of
window of the housing). Partially close the valve while observing the rod, using the dimension determined in Step 9. Tighten the
the direction that the target assembly moves. Reopen the valve. locking screw to 5 in-lbs minimum to hold the rod in place and
If the valve housing is predrilled with a 1/2” NPT for installation properly seal the enclosure.
of a monitoring switch, remove the 1/2” plug and fully open the
valve. Make sure that “OPEN” appears in the window of the 12. Partially close the valve to move the target assembly away (3 to 4
housing. GO TO STEP NO. 6. revolutions of the handle/hand wheel).
2. If the valve is not pre-drilled for 1/2” NPT, remove the head 13. With the PCVS positioned so the spring will pull the trip rod to
and target assembly (consultation with valve manufacturer is follow the target as the valve is closing, slide the PCVS over the
recommended). nipple. Tighten the socket head screw in the collar.
3. If the target assembly moved up as the valve was closed, measure 14. Carefully open the valve to the fully open position. As the target
the distance from the bottom of the head to the lower part of moves to the open position it should engage the trip rod and
the target assembly that will contact the trip rod of the PCVS actuate the switch(es). There should be a minimum overtravel
(see Fig. 3). This is usually a plate or bar on the target assembly, of 1/2 revolution of the handle/hand wheel after the switch(es)
on a side adjacent to the “OPEN/SHUT” plates. Subtract 1/8” actuate (a continuity meter connected to each set of contacts is
from the measurement. If the target moved down as the valve one method that could be used to determine this).
was closed, measure the distance from the bottom of the head 15. Slowly close the valve. The switch must operate during the first
to the upper portion of the target assembly that will contact two revolutions of the handle/hand wheel or during 1/5 of the
the trip rod of the PCVS (see Fig. 4). Add 1/8” (3,2mm) to this travel distance of the valve control apparatus from its normal
measurement. condition.
4. Mark the housing at the proper location. Using a 23/32” NOTE: Small adjustments of the target position may
(18,2mm) drill bit, drill and then tap a 1/2” NPT in the housing be necessary (consultation with valve manufacturer is
on the side that coincides with the portion of the target assembly recommended).
that will engage the trip rod of the PCVS. 16. Complete the required electrical wiring, connections and tests.
5. Replace the head and target assembly. The valve should be operated through the entire cycle of fully
6. Loosen the socket head screw that holds the nipple in the PCVS closed and fully open to determine the integrity of the PCVS
and remove the nipple. installation and the signaling system. Check that all electrical and
mechanical connections are secure.
7. Screw the locknut that is provided onto the nipple.
17. Reinstall the cover and tighten the cover screws to 15 in-lbs
8. Screw the nipple into the 1/2” NPT hole in the valve housing minimum to properly seal the enclosure.
hand tighten. Tighten the locknut against the valve housing to
secure the nipple firmly in place. 18. When the installation and testing are complete, return valve to its
proper position.
9. Insert a scale or probe thru the nipple to measure the distance
from the open end of the nipple to the target assembly. Subtract 19. Alternative installation for other post indicator valve housing
1/2” (12,5mm) from this measurement. shown in Fig. 1 and 2.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 73 OF 118
PCVS Series
Control Valve Supervisory Switch
1/32”
(0,8mm)
DWG# 980-6
1/2”
(13mm) DWG# 980-7
1. Remove the 1/2” NPT plug from the gear operator case. gear box cover to ensure correct operation (consultation with
2. Loosen the set screw that holds the nipple in the PCVS and remove the valve manufacturer is recommended).
the nipple. 9. Carefully open the valve to its full open position, as the boss on
the gear hub moves to the open position it must engage the PCVS
3. Screw the locknut that is provided onto the nipple. trip rod and actuate the switch(es). There should be a minimum
4. Screw the nipple into the 1/2” NPT hole in the gear operator-hand overtravel or revolution of the crank or hand wheel after the
tighten. Tighten the locknut against the case, to secure the nipple firmly switch(es) actuate (a continuity meter connected to each set of
in place contacts is one method that could be used to determine this).
5. Partially close the valve to move the boss on the gear hub out of the way NOTE: Slight adjustment of gear stops may be necessary to
(3 or 4 revolutions of the hand wheel or crank). prevent overtravel of the trip rod (consultation with valve manufacture
is recommended).
6. Using the special tool provided, loosen the two cover screws and
remove the cover from the PCVS. 10. Carefully close the valve. The switch(es) must operate during the
7. Orient the PCVS so the spring will pull up the trip rod to follow the first two revolutions of the crank or hand wheel or during 1/5 of
actuating cam inside the valve. the travel distance of the valve control apparatus from its normal
condition.
NOTE: If trip rod length is excessive, loosen the locking screw
and remove the trip rod from the trip lever. Using pliers, break 11. Complete the required electrical wiring, connections and tests. The
off the one (1) inch long notched section (see Fig. 12). Reinstall valve should be operated through the entire cycle of fully closed and
the trip rod, tightening the screw to 5 in-lbs minimum, and fully open to determine the integrity of the PCVS installation and
repeat Step 7 procedure. signaling system.
8. Remove device from nipple and shorten the trip rod 1/32” (0,80mm) 12. Reinstall the cover and tighten the screws to 15 in-lbs minimum to
(this is to prevent the trip rod from dragging on the gear hub inside properly seal the enclosure.
the valve). Tighten the locking screw to hold the rod in place. 13. When the installation and testing are complete, return valve to its
Re-install the device on the nipple. Tighten the screw in the collar proper position.
against the nipple.
NOTE: In some cases it may be necessary to remove the
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 74 OF 118
PCVS Series
Control Valve Supervisory Switch
Typical Pressure Reducer Type Valve PVK - Pratt PIVA Post Indicator Valve
Installation Kit
Fig 7 Fig 9
COLLAR
LOCKNUT
NIPPLE
MACHINE
SCREW #8-32
PCVS
1/16” (1,6mm)
MIN. GAP
DWG# 980-10
This figure shows the Model PCVS mounted on the valve yoke, with
a bracket supplied by the valve manufacturer, to supervise a pressure
reducer type valve.
DWG# 980-9
NOTE: This application is subject to the approval of the authority having Pratt Valve Kit as used to mount a PCVS on a Pratt Model PIVA Valve.
jurisdiction. Kit contains: Instructions, template, screw and nut.
NOTE: This application is subject to the approval of the authority having
jurisdiction.
PBK - Butterfly Valve Kit for Valves
with Internal Supervisory Switches
Fig 8
Locknuts Both Sides
Pratt Butterfly Valve Kit as used to mount a PCVS on a Pratt Model IBV
Valve.
Kits contain: Bracket, nuts and instructions
NOTE: Due to changes in valves, brackets may need to be modified by
installer. This application is subject to the approval of the authority hav-
ing jurisdiction.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 75 OF 118
7 7 6 6 5 5
PCVS Series 4
Dimensions
Fig 10
4.00 3.05
4.00 3.05
101.60 77.47
101.60 77.47
3.20 2.25
3.20 2.25
81.26 57.13
81.26 57.13
2.79
2.79 70.87
70.87
COVER TAMPER
SWITCH (OPTIONAL)
Knockout Removal E
Fig 11
(2) .886 KNOCKOUTS FOR
1/2" ELECTRICAL CONDUIT
(2) To remove knockouts: Place screwdriver at inside edge of knockouts, not
.886 KNOCKOUTS FOR 1/2" ELECTRICAL CONDUIT CONNECTIONS
CONNECTIONS (2) inCONNECTIONS
.886 KNOCKOUTS FOR 1/2" ELECTRICAL CONDUIT the center.
D
.XX = ENGLISH
[[Link]] = METRIC
.XX = ENGLISH
DIMENSIONS APPEARING
[[Link]] = METRICIN PARENTHESIS [ ]
GROUND SCREW REPRESENTS EQUVALENT IN MILLIMETERS
DIMENSIONS APPEARING D
ALL DIMENSIONS FORIN PARENTHESIS
REFERENCE ONLY[]
REPRESENTS EQUVALENT IN MILLIMETERS
LOCK NUT
TRIP ROD
NOTE: Do not drill into the base as this creates metal shavings which
7 6
can create electrical
5 hazards and damage the device.
C 4 Drilling voids the
6
warranty.
7 5 4
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 76 OF 118
PCVS Series
Control Valve Supervisory Switch
An uninsulated section of a single conductor should not be looped around Engineering Specifications: Post
the terminal and serve as two separate connections. The wire must be Indicator & Butterfly Valves
severed, thereby providing supervision of the connection in the event that
the wire become dislodged from under the terminal. Failure to sever the UL, CUL Listed / FM Approved and CE Marked valve supervisory
wire may render the device inoperable risking severe property damage switches shall be furnished and installed on all post Indicator and But-
and loss of life. Do not strip wire beyond 3/8" of length or expose an terfly valves that can be used to shut off the flow of water to any portion
uninsulated conductor beyond the edge of the terminal block. When using of the fire sprinkler system, where indicated on the drawings and plans
stranded wire, capture all strands under the clamping plate. and as required by applicable local and national codes and standards. The
supervisory switch shall be NEMA 4X and 6P rated and capable of being
mounted in any position indoors or out and be completely submerged
without allowing water to enter the enclosure. The enclosure shall be held
All conduit and connectors selected for the installation of this product captive by tamper resistant screws. The device shall contain two conduit
shall be suitable for the environment for which it is to be used and entrances and two Single Pole Double Throw (SPDT) switches. The
shall be installed to the manufacturer’s installation instructions. For device shall contain a removable 1/2” NPT nipple and adjustable trip rod,
NEMA 4, 4X, 6, 6P installations, the cover screws are recommended the trip rod shall be held captive by a set screw accessible upon removal
to be tightened to 15 in-lbs minimum and the trip rod locking screw of the cover. The switch contacts shall be rated at 10A, 125/250VAC and
tightened to 5 in-lbs minimum to properly seal the enclosure. 2A, 30VDC. Post Indicator and Butterfly Valve supervisory switch shall
be model PCVS-2 manufactured by Potter Electric Signal Company LLC
EOLR
COM NC NO NO NC COM Supervisory switches have a normal service life of 10-15 years. How-
ever, the service life may be significantly reduced by local environ-
mental conditions.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 77 OF 118
PS-10
Pressure Switch
Features
• One and two switch models available.
• Independent switch adjustment, no tools needed.
• Two conduit / cable entrances.
• Separate isolated wiring chambers.
• Non-corrosive pressure connection.
• Solid metal enclosure.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 78 OF 118
PS-10
Pressure Switch
Testing
The operation of the pressure alarm switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA
codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Wet System
Method 1: When using PS10 and control unit with retard - connect PS10 into alarm port piping on the input side of retard chamber and electrically connect
PS10 to control unit that provides a retard to compensate for surges. Insure that no unsupervised shut-off valves are present between the alarm check valve
and PS10.
Method 2: When using the PS10 for local bell application or with a control that does not provide a retard feature - the PS10 must be installed on the alarm
outlet side of the retard chamber of the sprinkler system.
Testing: Accomplished by opening the inspector’s end-of-line test valve. Allow time to compensate for system or control retard.
NOTE: Method 2 is not applicable for remote station service use, if there is an unsupervised shut-off valve between the alarm check valve and the PS10.
Wet System With Excess Pressure
Connect PS10 into alarm port piping extending from alarm check valve. Retard provisions are not required. Insure that no unsupervised shut-off valves are
present between the alarm check valve and the PS10.
Testing: Accomplished by opening the water by-pass test valve or the inspector’s end-of-line test valve. When using end-of-line test, allow time for excess
pressure to bleed off.
Dry System
Connect PS10 into alarm port piping that extends from the intermediate chamber of the alarm check valve. Install on the outlet side of the in-line check valve
of the alarm port piping. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10.
Testing: Accomplished by opening the water by-pass test valve.
NOTE: The above tests may also activate any other circuit closer or water motor gongs that are present on the system.
1/2" NPT
NG
OI DWG# 923-3
TG
2.48 OU
1.60
[62.87] [40.64]
3.78 3.20
[95.89] [81.28]
An uninsulated section of a single conductor should not be looped around the
NOTE: To prevent leakage, apply Teflon tape sealant to male threads only. terminal and serve as two separate connections. The wire must be severed,
DWG# 930-1
thereby providing supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 79 OF 118
PS-10
Pressure Switch
PS10
PS10 PS10
WATER WATER WATER
MOTOR MOTOR MOTOR
GONG GONG GONG
RBVS CHECK
WET RBVS DRY VALVE RBVS
SYSTEM WET SYSTEM
ALARM SYSTEM ALARM
CHECK ALARM CHECK
CHECK RETARD VALVE
VALVE
VALVE
WATER WATER WATER
OS & Y BY-PASS BY-PASS OS & Y BY-PASS
OS & Y
VALVE VALVE VALVE VALVE VALVE
VALVE
DWG. #923-2AA
CAUTION
Closing of any shutoff valves between the alarm check valve and the PS10 will render the PS10 inoperative. To comply with NFPA-72 any such valve shall be
electrically supervised with a supervisory switch such as Potter Model RBVS.
Low Pressure Signal Connection Waterflow Signal Connection Local Bell For Waterflow Connection
Fig 4 Fig 5 Fig 6
TO FIRE ALARM PANEL NEGATIVE DC
TO FIRE ALARM PANEL OR NEUTRAL AC
EOLR EOLR BELL
LINE LOAD
POSITIVE DC
OR HOT AC
DWG# 928-1
DWG# 928-2 DWG# 928-3
low pressure
supervision
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 80 OF 118
PS-10
Pressure Switch
Removing Knockouts
Fig 9
•Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances.
•Shock hazard. Disconnect power source before servicing.
Serious injury or death could result.
•Read all instructions carefully and understand them before
starting installation. Save instructions for future use. Failure to
read and understand instructions could result in improper
operation of device resulting in serious injury or death.
•Risk of explosion. Not for use is hazardous locations. Serious
injury or death could result.
CAUTION
•Do not tighten by grasping the switch enclosure. Use wrenching
flats on the bushing only. Failure to install properly could damage
DWG#928-5 the switch and cause improper operation resulting in damage to
equipment and property.
•To seal threads, apply Teflon tape to male threads only. Using
joint compounds or cement can obstruct the pressure port inlet
Engineer/Architect Specifications and result in improper device operation and damage to equipment.
Pressure Type Waterflow Switch •Do not over tighten the device, standard piping practices apply.
Pressure type waterflow switches; shall be a Model PS10 as manufactured
by Potter Electric Signal Company, St Louis MO., and shall be installed
on the fire sprinkler system as shown and or specified herein.
Switches shall be provided with a ½” NPT male pressure connection and
shall be connected to the alarm port outlet of; Wet Pipe Alarm Valves,
Dry Pipe Valves, Pre-Action Valves, or Deluge Valves. The pressure
switch shall be actuated when the alarm line pressure reaches 4 - 8 PSI
(0,27 - 0,55 BAR).
Pressure type waterflow switches shall have a maximum service pressure
rating of 300 PSI (20,68 BAR) and shall be factory adjusted to operate on
a pressure increase of 4 - 8 PSI (0,27 - 0,55 BAR)
Pressure switch shall have one or two form C contacts, switch contact
rating 10.1 Amps at 125/250 VAC, 2.0 Amps at 30 VDC.
Pressure type waterflow switches shall have two conduit entrances one
for each individual switch compartment to facilitate the use of dissimilar
voltages for each individual switch.
The cover of the pressure type waterflow switch shall be Zinc die-
cast with rain lip and shall attach with one tamper resistant screw. The
Pressure type waterflow switch shall be suitable for indoor or outdoor
service with a NEMA 4/IP66 rating. Ordering Information
The pressure type waterflow switch shall be UL Ulc and CSFM listed,
Model Description Part Number
FM and LPC approved and NYMEA accepted.
Tamper Pressure switch with one set SPDT
PS10-1 1144402
contacts
Cover incorporates tamper resistant fastener that requires a special key for Pressure switch with two sets SPDT
removal. One key is supplied with each device. For optional cover tamper PS10-2 1144425
contacts
switch kit, order Stock No. 0090200. See bulletin #5401200 PSCTSK.
Hex Key 5250062
Cover Tamper
0090200
Switch Kit
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 81 OF 118
PS40 Series
Supervisory Pressure Switch
Features
• One and two switch models available.
• Independent switch adjustment, no tools needed.
• Two conduit / cable entrances.
• Separate isolated wiring chambers.
• Non-corrosive pressure connection.
• Solid metal enclosure.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 82 OF 118
PS40 Series
Supervisory Pressure Switch
Fig 1
2.87
GROUND
SCREWS CAUTION
ADJUSTMENT [72.97] Closing of any shutoff valves between the alarm check valve and the
KNOB 4.22 PS40 will render the PS40 inoperative. To comply with IBC, IFC, and
[107.19]
NFPA-13, any such valve shall be electrically supervised with a supervi-
1/2" NPT sory switch such as Potter Model RBVS.
2.48 1.60
[62.87] [40.64]
3.78 3.20
[95.89] [81.28]
NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.
DWG# 930-1
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 83 OF 118
PS40 Series
Supervisory Pressure Switch
HIGH
AIR
2 1 COM
COM 1 2
LOW
AIR
EOLR
With normal system pressure applied high - Terminal 1 will close on pressure release. LOW PRESSURE SWITCH
DWG# 928-4
C
With normal system pressure applied low -Terminal 2 will close on pressure drop.
Fig 5 Fig 8
EOLR C C
C 1 2 C 1 2
DWG# 930-3
Terminal Terminal
C: Common
HIGH PRESSURE SWITCH 1. Open when installed under
1. Closed when installed normal system pressure.
C
under normal system Closes on increase in
Pressure. pressure. Use for high air
DWG# 928-1
2. Open when installed under signal.
C 1 2
normal system pressure. 2. Closed under normal
High Pressure Signal Connection Closes on DWG#
pressure drop. system pressure.
930-3
DWG# 928-2
DWG#928-5
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 84 OF 118
PS40 Series
Supervisory Pressure Switch
The switch unit shall contain SPDT (Form C) switch(es). One switch Optional Cover Tamper Switch Kit 0090200
shall be set to operate at 30 psi (2,1 BAR) on a pressure decrease. If two
switches are provided, the second switch shall be set to operate at a 50 psi
(3,5 BAR) on a pressure increase.
Switch contacts shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps •Installation must be performed by qualified personnel and in
at 30VDC. The units shall have a maximum pressure rating of 300 PSI accordance with all national and local codes and ordinances.
(20,68 BAR) and shall be adjustable from 10 to 60 PSI (0,7 to 4,1 BAR). •Shock hazard. Disconnect power source before servicing.
Pressure switches shall have two conduit entrances, one for each indi- Serious injury or death could result.
vidual switch compartment to facilitate the use of dissimilar voltages for •Read all instructions carefully and understand them before
each individual switch. starting installation. Save instructions for future use. Failure to
read and understand instructions could result in improper
The cover of the pressure switch shall be zinc die-cast with rain lip and operation of device resulting in serious injury or death.
shall attach with one tamper resistant screw. The pressure switch shall be •Risk of explosion. Not for use is hazardous locations. Serious
suitable for indoor or outdoor service with a NEMA-4/IP66 rating. injury or death could result.
The pressure switch shall be UL, ULC, and CSFM listed, FM and LPC
approved and NYMEA accepted.
CAUTION
•Do not tighten by grasping the switch enclosure. Use wrenching
flats on the bushing only. Failure to install properly could damage
the switch and cause improper operation resulting in damage to
equipment and property.
•To seal threads, apply Teflon tape to male threads only. Using joint
compounds or cement can obstruct the pressure port inlet and result in
improper device operation and damage to equipment.
•Do not over tighten the device, standard piping practices apply.
•Do not apply any lubricant to any component of the pressure switch.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 85 OF 118
PS-120
Supervisory Pressure Switch
Features
• One and two switch models available.
• Independent switch adjustment, no tools needed.
• Two conduit / cable entrances.
• Separate isolated wiring chambers.
• Non-corrosive pressure connection.
• Solid metal enclosure.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 86 OF 118
PS-120
Supervisory Pressure Switch
Testing
The operation of the pressure alarm switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA
codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Wet System
NOTE: Testing the PS120 may activate other system connected devices. The use of a Potter BVL (see product bulletin 8900067 for details) is recommended
to facilitate setting and testing of the PS120 pressure switch. When a BVL (bleeder valve) is used, the pressure to the switch can be isolated and bled from the
exhaust port on the BVL without effecting the supervisory pressure of the entire system. See Fig. 3
The operation point of the PS120 Pressure Switch can be adjusted to any point between 25 and 175 PSI (1,7 - 12,1 BAR) by turning the adjustment knob(s)
clockwise to raise the actuation point and counter clockwise to lower the actuation point. In the case of the PS120-2, both switches operate independent of each
other. Each switch may be independently adjusted to actuate at any point acrosss the switch adjustment range. Initial adjustment can be made with a visual
reference from the top of the adjustment knob across to the printed scale on the switch bracket. Final adjustments should be verified with a pressure gauge.
1/2" NPT G
IN DWG# 923-3
TGO
2.48 OU
1.60
[62.87] [40.64]
3.78 3.20
[95.89] [81.28]
NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.
An uninsulated section of a single conductor should not be looped around
the terminal and serve as two separate connections. The wire must be
DWG# 930-1 severed, thereby providing supervision of the connection in the event that
the wire becomes dislodged from under the terminal.
CHECK
VALVE RBVS
EXCESS
PRESSURE
PUMP WATER
OS & Y
BY-PASS
VALVE
TEST VALVE
RBVS DWG #926-1A
CAUTION
Closing of any shutoff valves between the alarm check valve and the PS120 will render the PS120 inoperative. To comply with NFPA-72 any such valve
shall be electrically supervised with a supervisory switch such as Potter Model RBVS.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 87 OF 118
PS-120
Supervisory Pressure Switch
Typical Connections
Fig 4
PS120-1 PS120-2
DWG# 933-1
DWG# 928-1
DWG# 928-2
DWG# 928-4
pressure, closes
on pressure
increase. Use for
high pressure signal. C 1 2
2: Closed under
DWG# 930-3
normal system
pressure.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 88 OF 118
PS-120
Supervisory Pressure Switch
Removing Knockouts
Fig 9
•Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances. •Shock
hazard. Disconnect power source before servicing.
Serious injury or death could result.
•Read all instructions carefully and understand them before
starting installation. Save instructions for future use. Failure to
read and understand instructions could result in improper
operation of device resulting in serious injury or death.
•Risk of explosion. Not for use in hazardous locations. Serious
injury or death could result.
CAUTION
•Do not tighten by grasping the switch enclosure. Use wrenching
flats on the bushing only. Failure to install properly could damage
DWG#928-5 the switch and cause improper operation resulting in damage to
equipment and property.
•To seal threads, apply Teflon tape to male threads only. Using
joint compounds or cement can obstruct the pressure port inlet
Engineer/Architect Specifications and result in improper device operation and damage to equipment.
Pressure Type Waterflow Switch •Do not over tighten the device, standard piping practices apply.
Pressure type supervisory switches; shall be a Model PS120 as manufactured
by Potter Electric Signal Company, St. Louis, MO., and shall be installed on the
fire sprinkler system as shown and or specified herein.
Switches shall be provided with a ½” NPT male pressure connection to be
connected into the air supply line on the system side of any shut-off valve.
A Model BVL bleeder valve as supplied by Potter Electric Signal Company of St.
Louis, MO., or equivalent shall be connected in line with the PS120 to provide a
means of testing the operation of the supervisory switch. (See Fig. 3)
The switch unit shall contain SPDT (Form C) switch(es). One switch shall be
set to operate at a pressure decrease of 10 PSI (0,7 BAR) from normal. If two
switches are provided, the second switch shall be set to operate at a pressure
increase of 10 PSI (0,7 BAR) from normal.
Switch contact shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps at
30VDC. The units shall have a maximum pressure rating of 300 PSI (20,68
BAR) and shall be adjustable from 25 to 175 PSI (1,7 to 12,1 BAR).
Tamper
Cover incorporates tamper resistant fastener that requires a special key for
removal. One key is supplied with each device. For optional cover tamper
switch kit, order Stock No. 0090200. See bulletin #5401200 PSCTSK. Ordering Information
Model Description Part Number
Pressure switch with one set SPDT
PS120-1 1341203
contacts
Pressure switch with two sets SPDT
PS120-2 1341204
contacts
Hex Key 5250062
Cover Tamper
0090200
Switch Kit
BVL Bleeder valve 1000018
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 89 OF 118
RBVS
Retrofit Ball Valve Switch
Features
• Small and large clamp models available
• Non-corrosive composite housing
• Built-in housing cover tamper switch
• Assembled in the USA
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 90 OF 118
RBVS
Retrofit Ball Valve Switch
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 91 OF 118
RBVS
Retrofit Ball Valve Switch
DWG# 1086-6
Tamper Switch Connections
NG
MI
CO
IN
NG
G OI DWG# 923-3
OUT
Ordering Information
An uninsulated section of a single conductor should not be looped Model Description Part Number
around the terminal and serve as two separate connections. The wire Retrofit ball valve switch (w/o Cover
must be severed, thereby providing supervision of the connection in RBVS 1000040
the event that the wire become dislodged from under the terminal. Tamper)
Failure to sever the wire may render the device inoperable risking Retrofit ball valve switch (w/ Cover
severe property damage and loss of life. RBVS-T 1000035
Do not strip wire beyond 3/8” of length or expose an uninsulated Tamper)
conductor beyond the edge of the terminal block. When using stranded
wire, capture all strands under the clamping plate. Optional Cover Tamper Kit 0090201
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 92 OF 118
VSR
Vane Type Waterflow Alarm
Switch With Retard
Features
• Assembled in USA
• Visual and audible switch activation
• 0-90 second field replaceable electronic retard
• Two SPDT (form C) contacts
• Weatherproof
• Works on Schedule 5-40 pipe
• Easy to read wire terminal designations
• Easy to read retard time delay adjustment knob
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall
not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterflow switches used for this
application may result in unintended discharges caused by surges, trapped
air, or short retard times.
Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all instructions carefully
before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 93 OF 118
VSR
Vane Type Waterflow Alarm
Switch With Retard
Installation
These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be acces-
sible. The device should not be installed within 6” (15 cm) of a fitting which changes the direction of the waterflow or within 24” (60 cm) of a valve or drain.
NOTE: Do not leave cover off for an extended period of time.
Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a dis-
tance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that
the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside
the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1). The vane must not rub the inside of the pipe
or bind in any way.
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent
the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified
technician should disable the alarm system.
CAUTION
TIGHTEN NUTS
ALTERNATELY
Hole must be drilled perpendicular to the pipe and vertically centered. Refer to the
Compatible Pipe/Installation Requirements chart for size.
Correct Incorrect
MOUNT ON PIPE SO
ARROW ON SADDLE
POINTS IN DIRECTION
OF WATERFLOW
inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m
VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3
1.25 + .125/-
VSR-2 1/2 2.5 - 2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 - - - - 33.0 ± 2.0
.062
VSR-2 1/2 - DN65 3.000 76.1 - - - - - - 0.142 3.6 0.102 2.6
VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9
VSR-3 1/2 3.5 - 4.000 101.6 - - 0.120 3.05 0.226 5.74 - - - - 20 27
VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2
2.00 ± .125 50.8 ± 2.0
VSR-5 5 - 5.563 141.3 - - 0.134 3.40 0.258 6.55 - - - -
VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0
VSR-8 8 DN200 8.625 219.1 - - 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 94 OF 118
VSR
Vane Type Waterflow Alarm
Switch With Retard
NG
G OI DWG# 923-3
O UT
NOTE:
When connecting to a UL Listed
control panel, use the panel’s
resistor value for circuit supervision.
NOTES:
1. The Model VSR has two switches, one can be used to operate a central
station, proprietary or remote signaling unit, while the other contact is
used to operate a local audible or visual annunciator.
2. For supervised circuits, see “Switch Terminal Connections” drawing
and warning note (Fig. 4).
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 95 OF 118
VSR
Vane Type Waterflow Alarm
Switch With Retard
Testing
The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA
Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on
the system, application of the VSR is not recommended or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing
instructions.
Maintenance
Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch
assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly
stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection. Vane type watearflow switches have a normal service life
of 10-15 years. However, the service life may be significantly reduced by local environmental conditions.
Mounting Dimensions
Fig 6 Fig 7
GREEN GROUND
5.56 in SCREWS
3.50 in (141.2 mm)
2.00 in
(89.0 mm) (50.8 mm)
2.34 in
(59.4 mm)
PIPE DIA.
U-BOLT NUT + 5.25 in
(+ 133.4 mm)
U-BOLT WASHER
PIPE SADDLE
PIPE
PLASTIC PADDLE DWG. 1146-14
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 96 OF 118
VSR
Vane Type Waterflow Alarm
Switch With Retard
BASE
DWG# 1146-10
Ordering Information
Ordering Information Nominal Pipe Size Model Part Number
Nominal Pipe Size Model Part Number 4" DN100 VSR-4 1144404
2" DN50 VSR-2 1144402 5" - VSR-5 1144405
2 1/2" DN65 VSR-2 1/2 1144425 6" DN150 VSR-6 1144406
3" DN80 VSR-3 1144403 8" DN200 VSR-8 1144408
3 1/2" - VSR-3 1/2 1144435 Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 97 OF 118
VSR-S
Vane Type Waterflow Alarm
Switch With Retard
Features
• Assembled in USA
• 0-90 second field replaceable electronic retard
• Fits 1” to 2” CPVC, copper, or iron TEE’s
• Comes with all necessary paddles
• Two SPDT (form C) contacts
• Weatherproof
• Easy to read wire terminal designations
• Easy to read time delay adjustment knob
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall
not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterflow switches used for this
application may result in unintended discharges caused by surges, trapped
air, or short retard times.
Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all instructions carefully
before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Enclosure Enclosure
Die-cast, red enamel finish
Cover held in place with tamper resistant screws
The VSR-S switches and retard device are enclosed in a general purpose, Two sets of SPDT (Form C)
die-cast housing. The cover is held in place with two tamper resistant Contact Ratings 10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
screws which require a special key for removal. A field installable cover
tamper switch is available as an option which may be used to indicate Two knockouts provided for 1/2” conduit. Individual switch
Conduit Entrances
compartments suitable for dissimilar voltages.
unauthorized removal of the cover. See bulletin number 5401103 for
installation instructions of this switch. Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - 1” (25mm), 1 1/4” (32mm), 1 1/2” (38mm)
and 2” (50mm)
Usage NOTE: 12 paddles are furnished with each unit, one for each
pipe size of threaded and sweat TEE, one for 1” (25mm)
CPVC, one for 1” (25mm) CPVC (Central), one for 1” threaded
• Installation must be performed by qualified personnel and in ac- Nibco CPVC, and one for 1 1/2” (38mm) threaded (Japan).
cordance with all national and local codes and ordinances.
• Shock hazard. Disconnect power source before servicing. Serious NEMA-4/IP65 Rated enclosure suitable for indoor or
injury or death could result. Environmental outdoor use with factory installed gasket and die-cast
• Risk of explosion. Not for use in hazardous locations. Serious Specifications housing when used with appropriate conduit fitting.
injury or death could result. Temperature range: 40° F to 120° F, (4,5° C to 49° C) UL
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Service Use
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 98 OF 118
VSR-S
Vane Type Waterflow Alarm
Switch With Retard
Installation
These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be acces-
sible. The units should not be installed within 6” (15cm) of a valve, drain or fitting which changes the direction of the waterflow. Select the proper paddle for
the pipe size and type of TEE used see Fig. 1 for instructions on changing paddle. The unit has a 1” NPT bushing for threading into a non-corrosive TEE. See
Fig. 2 for proper TEE size, type and installation. Use no more than three wraps of teflon tape.
Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterflow.
The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand.
Note: Do not leave cover off for an extended period of time.
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent
the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified
technician should disable the alarm system.
Fig 1
COVER TAMPER SWITCH Retard Adjustment
The delay can be adjusted by rotating the retard adjustment knob from 0
to the max setting (60-90 seconds). The time delay should be set at the
minimum required to prevent false alarms.
Screw the device into the tee fitting as shown. Care must be taken to
properly orient the device for the direction of waterflow. On sweat tees,
no threaded bushings, inserts, or adapters are permitted, unless they com-
ply with the dimensions listed in the chart below.
Important - The depth to the inside bottom of the tee should have the
following dimensions:
MOUNT SO
ARROW ON
BUSHING POINTS Approximate Depth Requirement
IN DIRECTION OF
WATERFLOW Tee Size Threaded Sweat CPVC DIRECTION OF
WATER FLOW
1" x 1" x 1" 2 1/16" 1 3/4" 2 7/16"
1” NPT 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A
THREADED
FITTING ON 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" N/A
ALL SIZES 2" x 2" x 1" 3 3/16" 2 3/4" N/A
DWG# 737-31
RUN OF THE TEE
MAY BE
THREADED OR
SWEAT PIPE
DIRECTION OF There are 12 paddles furnished with each unit. One for each size of
WATERFLOW threaded, sweat or plastic TEE as described in Fig. 2. These paddles
have raised lettering that shows the pipe size and type of TEE that they
DWG# 802-30A
are to be used with. The proper paddle must be used. The paddle must
be properly attached (see drawing) and the screw that holds the paddle
must be securely tightened.
Shown with optional Cover Tamper Switch Kit.
Fig 2
Use only factory TEE’s with a 1” NPT boll. Reducing bushings, 4,3MM
APPROX.
mechanical TEE’s and weld-o-lets are not allowed. (1 11/16”)
* Do not use more than three wraps of teflon tape.
DEPTH
DWG# 735-33
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
PAGE 99 OF 118
VSR-S
Vane Type Waterflow Alarm
Switch With Retard
G
O IN DWG# 923-3
TG
OU
DWG 1146-4
LOAD TO BELL
BREAKER
NOTE:
When connecting to a UL Listed
control panel, use the panel’s
resistor value for circuit supervision.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Testing
The frequency of inspection and testing for the Model VSR-S and its associated protective monitoring system should be in accordance with applicable NFPA
Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently.)
An inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system,
application of the VSR-S is not recommended or advisable.
A minimum flow of 10 gpm (38 Lpm) is required to activate this device.
Important Notice
Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.
Maintenance
Inspect detectors monthly for leaks. If leaks are found, replace the detector. The VSR-S waterflow switch should provide years of trouble-free service. The
retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement
retard switch assembly stock #1029030. There is no maintenance required, only periodic testing and inspection. Vane type watearflow switches have a normal
service life of 10-15 years. However, the service life may be significantly reduced by local environmental conditions.
Removal
• To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or
replaced.
• Turn off electrical power to the detector, then disconnect wiring.
• Use a wrench on the flats of the bushing. Turn the switch counterclockwise to disengage the pipe threads.
• Gently lift with your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector.
• Lift detector clear of pipe.
Mounting Dimensions
Fig 8
3.50" 5.56"
(89.0 mm) (141.2 mm)
GROUND SCREWS
2.00"
(50.8 mm)
2.34"
(59.4 mm)
4.89"
(52.3 mm)
DWG# 1206-5
Ordering Information
Model Description Stock No.
Vane Type Waterflow Alarm Switch with
VSR-S 1144440
Retard
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Features
• Assembled in USA
• 0-90 second field replaceable electronic retard
• Fits 1’ to 2” CPVC
• Comes with all necessary paddles
• Easy to read wire terminal designations
• Easy to read retard time delay adjustment knob
• Union coupling for installations in confined locations
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as
the sole initiating device to discharge AFFF, deluge, or chemical suppression systems.
Waterflow switches used for this application may result in unintended discharges caused
by surges, trapped air, or short retard times.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Installation
These switches may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be acces-
sible. The switch should not be installed within 6” (15 cm) of a fitting which changes the direction of the waterflow or within 24” (60 cm) of a valve or drain.
The unit has a 1” male fitting for gluing into a CPVC plastic tee.
Note: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the 1” male fitting from the VSR-SG. Glue the 1” male fitting into the TEE following the TEE manufacturer’s instructions
for preparation and gluing of CPVC piping systems. (Note: The 1” male fitting must bottom out on the stop of the TEE for proper operation of the VSR-SG.
See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1” male fitting. Select the proper paddle for the pipe size and type of
TEE used. See Fig. 3 for instructions on how to change paddle. Verify that the o-ring is properly positioned in its groove. Hand tighten the nut on the union
after orienting the switch in the appropriate direction to detect waterflow as shown in Fig. 5 & Fig. 7.
The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand.
CAUTION CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent Do not over-tighten the union nut, hand tighten only. Use of a wrench may
the switch from operating and will void the warranty. damage the union nut.
Fig 1 Retard Adjustment
OPTIONAL COVER TAMPER SWITCH The delay can be adjusted by rotating the retard adjustment knob from 0
Do not leave cover off for extended period of time to the max setting (60-90 seconds). The time delay should be set at the
minimum required to prevent false alarms
RETARD
ADJUSTMENT
KNOB
MOUNT SO ARROW ON
BASE POINTS IN DIRECTION
OF WATERFLOW
11 paddles are furnished with each unit to accommodate the various sizes
and manufacturers of TEES. The paddles have raised lettering that show the
1" MALE FITTING ON pipe size and the TEE manufacturer they are to be used with. The proper
ALL SIZES
paddle must be used. The paddle must be properly attached (see Fig. 3) and
the screw that holds the paddle must be securely tightened.
Fig 2
DWG# 1205-1A
Glue the 1” male fitting into the TEE following the TEE manufacturer’s
instructions for preparation and gluing of CPVC piping systems. Wait 2
to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1”
male fitting.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Break out thin section of cover when wiring both switches from one Switch Terminal Connections
conduit entrance.
Clamping Plate Terminal
Fig 3
Fig 5
DWG# 1205-4
Typical Electrical Connections An uninsulated section of a single conductor should not be looped
around the terminal and serve as two separate connections. The wire
Fig 4 must be severed, thereby providing supervision of the connection in
the event that the wire become dislodged from under the terminal.
Failure to sever the wire may render the device inoperable risking
CONNECTOR
BELL
NEUTRAL FROM severe property damage and loss of life.
BREAKER NEUTRAL FROM BELL
Do not strip wire beyond 3/8” of length or expose an uninsulated
conductor beyond the edge of the terminal block. When using stranded
wire, capture all strands under the clamping plate.
LOAD TO BELL
BREAKER
Testing
The frequency of inspection and testing for the Model VSR-SG and its
associated protective monitoring system shall be in accordance with ap-
plicable NFPA Codes and Standards and/or the authority having jurisdic-
NOTE: tion (manufacturer recommends quarterly or more frequently).
When connecting to a UL Listed
control panel, use the panel’s A method of testing the VSR-SG must be provided. The valve used for
resistor value for circuit supervision.
testing shall be easily reached and shall produce a minimum flow of 10
GPM to activate the switch. The discharge orifice shall be equal to the
smallest sprinkler used in the system.
Notes:
1. The Model VSR-SG has two switches, one can be used to operate a central
station, proprietary or remote signaling unit, while the other contact is
used to operate a local audible or visual annunciator. Advise the person responsible for testing of the fire protection
2. For supervised circuits, see “Switch Terminal Connections” drawing and system that this system must be tested in accordance with the
warning note (Fig. 6). testing instructions.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Mounting Dimensions
Fig 6
5.56 in 90°
(141.2 mm)
3.50 in 2.00 in
(89.0 mm) (50.8 mm)
3.91 in
(99.33 mm)
CAUTION
Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. Improper orientation could delay or prevent notification of
waterflow.
Maintenance
Inspect the waterflow switch monthly. If leaks are found, replace the waterflow switch. The VSR-SG waterflow switch should provide years of trouble-
free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order
replacement retard switch assembly stock #1029030 (see Fig. 9). There is no maintenance required, only periodic testing and inspection.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe.
1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identify and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re-install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.
Fig 2
(2) ORIGINAL MOUNTING
REMOVE (2) ORIGINAL MOUNTING SCREWS
SCREWS HOLDING RETARD/SWITCH
ASSEMBLY TO BASE BREAK OUT THIN SECTION OF COVER
WHEN WIRING BOTH SWITCHES
FROM ONE CONDUIT ENTRANCE.
RETARD/SWITCH ASSEMBLY
DO NOT REMOVE
(2) RETARD HOUSING (2) LOCATING PIN
SCREWS BOSSES IN BASE
BASE
DWG# 1190-2
Ordering Information
Model Description Stock No. Optional: Cover Tamper Switch Kit, Stock No. 0090148
(See Fig. 4 for terminations)
Vane Type Waterflow Alarm Switch with Replaceable Components: Retard/Switch Assembly, stock no. 1029030
VSR-SG 1144460
Retard and Glue-In Union
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Features
• Assembled in USA
• 0-90 second field replaceable electronic retard
• Comes with all necessary paddles
• Easy to read wire terminal designations
• Easy to read retard time delay adjustment knob
WARNING
Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances.
Shock hazard. Disconnect power source before servicing. Serious
injury or death could result.
Risk of explosion. Not for use in hazardous locations. Serious injury
or death could result.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
N G
O MI
I NC
G
IN DWG# 923-3
T GO
OU
WARNING WARNING
There are 12 paddles furnished with each unit. One for each size of An uninsulated section of a single conductor should not be looped around
threaded, sweat or plastic TEE as described in Fig. 1. The paddles have the terminal and serve as two separate connections. The wire must be
raised lettering that show the pipe size and type of TEE that they are severed, thereby providing supervision of the connection in the event that
to be used with. The proper paddle must be used. The paddle must be the wire become dislodged from under the terminal. Failure to sever the
properly attached (see Fig. 3) and the screw that holds the paddle must wire may render the device inoperable risking severe property damage
be securely tightened. and loss of life.
Do not strip wire beyond 3/8” of length or expose an uninsulated
conductor beyond the edge of the terminal block. When using stranded
wire, capture all strands under the clamping plate.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
NEUTRAL AC
NC
Maintenance
COM
POSITIVE DC
OR HOT AC
Inspect detectors monthly for leaks. If leaks are found, replace the detector.
The VSR-ST waterflow switch should provide years of trouble-free service.
COM
WATERFLOW ZONE The retard and switch assembly are easily field replaceable. In the unlikely
NC
EOLR
ON FIRE PANEL
event that either component does not perform properly, please order
NO
Ordering Information
Model Description Stock No.
Vane Type Waterflow Alarm Switch with
VSR-ST 1144465
DWG# 1205-4 Retard
Vane Type Waterflow Alarm Switch with
VSR-ST 1144466
Retard w/TSK
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Features
• Assembled in USA
• Automatically resets when water in the system is lowered below
probe location
CAUTION
Not for use in hazardous locations.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
CAUTION CAUTION
Make sure that water entering the system during test does not enter in to the An insulated section of a single conductor should not be looped around
system piping that is exposed to current freezing conditions. the terminal and serve as two seperate connections. The wire must be
severed, thereby providing supervision of the connection in the event
that the wire becomes dislodged from under the terminal. Use 18 AWG
(min.), or as required by local code. Wire insulation rating must be at
least 167°F (75°C).
Dimensions
3.66
1.83
.79
2.60
5.53
.75
1.31
3/4" or 1/2" NPT FITTING
DWG. #1158-4
Ø.188
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
+ 24VDC -
SUPERVISORY +
SUPERVISORY -
ALARM
ALARM
LINE (HOT)
LINE (HOT)
NEUTRAL
NEUTRAL
LINE (HOT)
NEUTRAL
JUMPER
EOL
1/4" MIN.
MOUNTING
SCREW
MOUNTING
SCREW
1/4"
DWG. #1158-1
MIN.
PROBE
DWG. #1158-2
MOUNTING SCREWS DWG. #1158-3
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
DWG #1108-8
Ordering Information
Model Description Stock No.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
Features
• Adjustable instant recycling pneumatic retard
• Independent switch adjustment, no tools needed.
• Two conduit / cable entrances.
• Separate isolated wiring chambers.
• Non-corrosive pressure connection.
• Solid metal enclosure.
CAUTION
This device is not intended for applications in explosive environments.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
COM NO NC COM NO NC
RETARD
CHAMBER
COM NO NC COM NO NC
RBVS
Fig. 4
N G
O MI
INC
Retard Adjustment:
To change time turn knob (either
direction) for desired time delay. Use
the minimum amount of retard neces-
sary to prevent false alarms, a “B” G
IN DWG# 923-3
setting is usually adequate for this. T GO
Factory set at “B”. OU
DWG# 987-30
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
WARNING HEADS
operation. OSYSU
TAMPER WATER BY-PASS
DEVICE TEST VALVE STRAINER
(CLOSED) DRIP
Ordering Information
Model Description Stock No.
WFSR-F Waterflow Alarm Switch with Retard 1010080
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • [Link]
The OSYSU valve supervisory switch can be installed on small valves as small as ½” (12.5mm) and must be positioned carefully to ensure the trip rod operates correctly. Installation involves mounting the OSYSU across the valve yoke with the spring-loaded trip rod pulled against the valve stem, centering it in a ⅛” minimum depth groove on the stem. The groove allows smooth operation of the trip rod as the valve opens and closes, preventing false alarms due to stem threads . Precautions include ensuring that the enclosure is properly sealed with cover screws tightened to 15 in-lbs and the trip rod locking screw to 5 in-lbs to prevent water ingress . It's crucial to ensure valve operations do not cause damage, such as from water flow through open or missing components, and to notify authorities before any fire system work . Use suitable conduit and connectors for environmental conditions, and avoid metal shavings from drilling into the enclosure, as this voids the warranty .
A wet pipe sprinkler system contains water in the pipes at all times, allowing for immediate discharge upon activation of a sprinkler head due to fire . These systems are typically used in heated environments to prevent pipe freezing . In contrast, a dry pipe sprinkler system contains air under pressure, which is released when a sprinkler head opens, allowing the dry pipe valve to open and water to flow into the system. These systems are used in unheated locations or areas at risk of freezing . Overall, wet systems are more common and reliable in heated spaces, while dry systems prevent freezing in cold environments ."}
When choosing and installing a waterflow detector in a wet pipe sprinkler system, it's crucial to ensure the device is suited for the specific pipe size and type, such as CPVC or metal piping, and that it is mounted correctly based on the system layout. The detector should be mounted on the top side of horizontal pipes for accessibility and should not be within 6 inches of any valves, drains, or fittings that change the water flow direction to avoid false activations . It is important to select the appropriate vane or paddle based on the pipe specifications and ensure that it does not rub or bind within the pipe or tee fitting . Ensuring correct orientation concerning the waterflow direction is critical to avoid operational issues . Additionally, the retard time delay of the waterflow switch should be set to the minimum necessary to prevent false alarms caused by water pressure fluctuations, adjusting within the range of 0 to 90 seconds . Installation must be in accordance with all applicable national and local codes, like NFPA 72, and performed by qualified personnel . It is also advisable to conduct periodic testing and maintenance of the switch to ensure its proper functionality, replacing any defective components as needed . Monitoring systems should not solely rely on the waterflow switch for system activation to prevent unintended discharges ."
Supervisory switches in sprinkler systems play a critical role by providing notifications of any off-normal condition, such as when a control valve is not in the fully open position, which could impair the operation of the sprinkler system during a fire . These switches ensure that valves remain in the correct position to allow water flow throughout the system, thereby preventing system failure due to closed water control valves, which are often the main reason for sprinkler system failure . Supervisory switches must activate within two revolutions of the handwheel or one-fifth of the valve's travel . If these switches are not installed properly, there's a risk of failure which could lead to severe property damage and loss of life as water flow to the sprinkler system could be inadvertently shut off or not resumed automatically after maintenance . Proper installation and maintenance are crucial as failures to do so could result in serious injury or death due to improper operation .
Not incorporating a pressure gauge with sprinkler system components can lead to unawareness of potential water supply issues, such as a drop in pressure, which may indicate a closed valve or blocked pipe . A tamper-evident mechanism, or valve supervision, is crucial as it helps detect unauthorized or accidental changes in valve positions, ensuring the sprinkler system remains operational . Without these mechanisms, there is a risk of the system not functioning correctly during a fire, potentially leading to property damage or loss of life . Additionally, tamper-evident mechanisms can provide immediate alerts of off-normal conditions, which assists in maintaining the system's integrity and prompt attention to any malfunctions ."}
The presence of an alarm check valve in a wet pipe sprinkler system helps prevent false alarms by maintaining system pressure and isolating the system from water supply fluctuations. The alarm check valve acts as a check valve with an alarm port, holding a steady system pressure and preventing pressure surges from triggering alarms when no actual discharge occurs . This is done by keeping the clapper closed under normal circumstances, which blocks the alarm port and maintains the system's internal pressure . Additionally, the alarm check valve is part of a designed system that incorporates retard chambers, ensuring that momentary fluctuations in pressure do not lead to false alarm activations ."}
The integration of a retard chamber in waterflow switches enhances performance by preventing false alarms caused by surges or trapped air. When water surges occur, the retard chamber fills with water, absorbing the pressure and delaying the signal activation until a genuine and sustained flow is detected . The retard time delay can be adjusted to the minimum required to prevent false alarms . This delay ensures that temporary water pressure changes do not trigger unnecessary alarms, thus enhancing the reliability of the system . Additionally, retard chambers require periodic maintenance to prevent the drip valve from clogging, ensuring consistent operation ."}
Vane-type waterflow switches with retard, such as the VSR-S, are designed to handle variable flow conditions without causing false alarms by incorporating an adjustable pneumatic retard mechanism. This retard can be set from 0 to 90 seconds to delay alarm activation, ensuring that transient flows or water surges do not trigger false alarms . The switch is actuated only when a flow of at least 10 gallons per minute is sustained for the duration set by the retard. This feature allows the switch to filter out short durations of flow that are not indicative of actual sprinkler discharge . The unit contains two single-pole, double-throw snap action switches, providing flexibility in signaling while maintaining accurate alarm responses to true waterflow conditions .
Maintaining appropriate air temperature around dry pipe valves is critical to prevent freezing, which can immobilize the valve and compromise system readiness during a fire. Ensuring that the valve room remains heated prevents ice formation that could obstruct valve operation when air is released during a fire. Failure to regulate temperature can result in the dry pipe valve failing to open, delaying or preventing water from reaching the fire, and potentially leading to significant property damage or loss of life .
Excessive air pressure in a dry pipe sprinkler system can delay the time it takes to bleed off enough air pressure to allow the water supply to open the dry pipe valve, which is critical during a fire incident. This delay can hinder timely water discharge. Therefore, the system should be monitored for high air pressure, and adjustments should be made to ensure that air pressure does not exceed recommended levels to ensure the optimal responsiveness of the system .