0% found this document useful (0 votes)
233 views48 pages

Fire Alarm System Limitations Guide

This document provides information and limitations about fire alarm systems. It discusses how smoke detectors, heat detectors, and audible alarms have sensing limitations and may not detect or warn about all types of fires. It emphasizes that fire alarm systems are not a substitute for fire insurance and do not guarantee protection against property damage or loss of life. Regular inspection and maintenance of the fire alarm system is necessary to ensure proper operation.

Uploaded by

Said Romero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
233 views48 pages

Fire Alarm System Limitations Guide

This document provides information and limitations about fire alarm systems. It discusses how smoke detectors, heat detectors, and audible alarms have sensing limitations and may not detect or warn about all types of fires. It emphasizes that fire alarm systems are not a substitute for fire insurance and do not guarantee protection against property damage or loss of life. Regular inspection and maintenance of the fire alarm system is necessary to ensure proper operation.

Uploaded by

Said Romero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

G

PN 50362:C0 ECN 01-155

Control Relay Module


ACM-8RF
Instruction Manual

Document 50362
03/21/2001 Rev: C
While a fire alarm system may lower insurance
Fire Alarm System Limitations rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up Heat detectors do not sense particles of combustion
of smoke detectors, heat detectors, manual pull and alarm only when heat on their sensors increases
stations, audible warning devices, and a fire alarm at a predetermined rate or reaches a predetermined
control with remote notification capability–can provide level. Rate-of-rise heat detectors may be subject to
early warning of a developing fire. Such a system, reduced sensitivity over time. For this reason, the
however, does not assure protection against property rate-of-rise feature of each detector should be tested
damage or loss of life resulting from a fire. at least once per year by a qualified fire protection
specialist. Heat detectors are designed to protect
The Manufacturer recommends that smoke and/or
property, not life.
heat detectors be located throughout a protected
premise following the recommendations of the current IMPORTANT! Smoke detectors must be installed in
edition of the National Fire Protection Association the same room as the control panel and in rooms
Standard 72 (NFPA 72), manufacturer's recommenda- used by the system for the connection of alarm
tions, State and local codes, and the recommenda- transmission wiring, communications, signaling, and/or
tions contained in the Guide for Proper Use of System power. If detectors are not so located, a developing
Smoke Detectors, which is made available at no fire may damage the alarm system, crippling its ability
charge to all installing dealers. A study by the to report a fire.
Federal Emergency Management Agency (an agency
of the United States government) indicated that Audible warning devices such as bells may not alert
smoke detectors may not go off in as many as 35% of people if these devices are located on the other side
all fires. While fire alarm systems are designed to of closed or partly open doors or are located on
provide early warning against fire, they do not guaran- another floor of a building. Any warning device may
tee warning or protection against fire. A fire alarm fail to alert people with a disability or those who have
system may not provide timely or adequate warning, or recently consumed drugs, alcohol or medication.
simply may not function, for a variety of reasons: Please note that:
Smoke detectors may not sense fire where smoke • Strobes can, under certain circumstances, cause
cannot reach the detectors such as in chimneys, in or seizures in people with conditions such as
behind walls, on roofs, or on the other side of closed epilepsy.
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor • Studies have shown that certain people, even
detector, for example, may not sense a first-floor or when they hear a fire alarm signal, do not respond
basement fire. or
comprehend the meaning of the signal. It is the
Particles of combustion or "smoke" from a develop- property owner's responsibility to conduct fire drills
ing fire may not reach the sensing chambers of smoke and other training exercise to make people aware
detectors because: of fire alarm signals and instruct them on the
• Barriers such as closed or partially closed doors, proper reaction to alarm signals.
walls, or chimneys may inhibit particle or smoke
flow. • In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
• Smoke particles may become "cold," stratify, and
not reach the ceiling or upper walls where detec- A fire alarm system will not operate without any
tors are located. electrical power. If AC power fails, the system will
operate from standby batteries only for a specified
• Smoke particles may be blown away from detec-
time and only if the batteries have been properly
tors by air outlets.
maintained and replaced regularly.
• Smoke particles may be drawn into air returns
before reaching the detector. Equipment used in the system may not be
technically compatible with the control. It is essential
The amount of "smoke" present may be insufficient to
to use only equipment listed for service with your
alarm smoke detectors. Smoke detectors are
control panel.
designed to alarm at various levels of smoke density.
If such density levels are not created by a developing Telephone lines needed to transmit alarm signals
fire at the location of detectors, the detectors will not from a premise to a central monitoring station may be
go into alarm. out of service or temporarily disabled. For added
Smoke detectors, even when working properly, have protection against telephone line failure, backup radio
sensing limitations. Detectors that have photoelec- transmission systems are recommended.
tronic sensing chambers tend to detect smoldering
fires better than flaming fires, which have little visible The most common cause of fire alarm malfunction is
smoke. inadequate maintenance. To keep the entire fire
Detectors that have ionizing-type sensing chambers alarm system in excellent working order, ongoing
tend to detect fast-flaming fires better than smoldering maintenance is required per the manufacturer's
fires. Because fires develop in different ways and are recommendations, and UL and NFPA standards. At a
often unpredictable in their growth, neither type of minimum, the requirements of Chapter 7 of NFPA 72
detector is necessarily best and a given type of shall be followed. Environments with large amounts
detector may not provide adequate warning of a fire. of dust, dirt or high air velocity require more frequent
maintenance. A maintenance agreement should be
Smoke detectors cannot be expected to provide arranged through the local manufacturer's representa-
adequate warning of fires caused by arson, children tive. Maintenance should be scheduled monthly or as
playing with matches (especially in bedrooms), required by National and/or local fire codes and
smoking in bed, and violent explosions (caused by should be performed by authorized professional fire
escaping gas, improper storage of flammable alarm installers only. Adequate written records of all
materials, etc.). inspections should be kept.

LimWarSm.p65 01/10/2000
Adherence to the following will aid in problem-free
Installation Precautions
installation with long-term reliability:
WARNING - Several different sources of power can Like all solid state electronic devices, this system
be connected to the fire alarm control panel. may operate erratically or can be damaged when
Disconnect all sources of power before servicing. subjected to lightning-induced transients. Although no
Control unit and associated equipment may be dam- system is completely immune from lightning transients
aged by removing and/or inserting cards, modules, or and interferences, proper grounding will reduce sus-
interconnecting cables while the unit is energized. Do ceptibility. Overhead or outside aerial wiring is not
not attempt to install, service, or operate this unit until recommended, due to an increased susceptibility to
this manual is read and understood. nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated
CAUTION - System Reacceptance Test after Soft- or encountered.
ware Changes. To ensure proper system operation,
this product must be tested in accordance with NFPA Disconnect AC power and batteries prior to
72 Chapter 7 after any programming operation or removing or inserting circuit boards. Failure to do so
change in site-specific software. Reacceptance test- can damage circuits.
ing is required after any change, addition or deletion
of system components, or after any modification, Remove all electronic assemblies prior to any
repair or adjustment to system hardware or wiring. drilling, filing, reaming, or punching of the enclosure.
When possible, make all cable entries from the sides
All components, circuits, system operations, or soft- or rear. Before making modifications, verify that they
ware functions known to be affected by a change must will not interfere with battery, transformer, and printed
be 100% tested. In addition, to ensure that other circuit board location.
operations are not inadvertently affected, at least 10%
Do not tighten screw terminals more than 9 in-lbs.
of initiating devices that are not directly affected by
Over-tightening may damage threads, resulting in
the change, up to a maximum of 50 devices, must
reduced terminal contact pressure and difficulty with
also be tested and proper system operation verified.
screw terminal removal.
This system meets NFPA requirements for operation
Though designed to last many years, system com-
at 0-49° C/32-120° F and at a relative humidity of
ponents can fail at any time. This system contains
85% RH (non-condensing) at 30° C/86° F. However,
static-sensitive components. Always ground yourself
the useful life of the system's standby batteries and
with a proper wrist strap before handling any circuits
the electronic components may be adversely affected
so that static charges are removed from the body.
by extreme temperature ranges and humidity. There-
Use static-suppressive packaging to protect electronic
fore, it is recommended that this system and all
assemblies removed from the unit.
peripherals be installed in an environment with a
nominal room temperature of 15-27° C/60-80° F. Follow the instructions in the installation, operating,
Verify that wire sizes are adequate for all initiating and programming manuals. These instructions must
be followed to avoid damage to the control panel and
and indicating device loops. Most devices cannot
tolerate more than a 10% I.R. drop from the specified associated equipment. FACP operation and reliability
device voltage. depend upon proper installation by authorized
personnel.

FCC Warning
WARNING: This equipment generates, uses, and Canadian Requirements
can radiate radio frequency energy and if not This digital apparatus does not exceed the Class
installed and used in accordance with the instruc- A limits for radiation noise emissions from digital
tion manual, may cause interference to radio apparatus set out in the Radio Interference
communications. It has been tested and found to Regulations of the Canadian Department of
comply with the limits for class A computing de- Communications.
vice pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de
protection against such interference when operat- bruits radioelectriques depassant les limites
ed in a commercial environment. Operation of this applicables aux appareils numeriques de la
equipment in a residential area is likely to cause classe A prescrites dans le Reglement sur le
interference, in which case the user will be re- brouillage radioelectrique edicte par le ministere
quired to correct the interference at his own des Communications du Canada.
expense.

LimWarSm.p65 01/10/2000
This page intentionally left blank

4 ACM-8RF PN 50362:C 03/21/01


Table of Contents
Table of Contents
1. Introduction
General................................................................................................... 7
Mounting ............................................................................................... 7
Features ................................................................................................. 8
Relays ................................................................................................. 8
24 VDC Power and Earth Ground...................................................... 8
EIA-485 Communications.................................................................. 9
Address Switches ............................................................................... 9
Relay Function Selection.................................................................... 9
Mode Selection................................................................................... 9
Related Documentation ........................................................................ 9

2. Installation
Mounting the Enclosure. .................................................................... 11
Wiring the Power Terminal Blocks................................................... 11
Wiring the Relay Terminal Blocks.................................................... 12
Wiring the EIA-485 Terminal Blocks ............................................... 13
Wiring Specifications ....................................................................... 13
EIA-485 Shield in Conduit .......................................................... 13
EIA-485 Shield Not in Conduit ................................................... 14
EIA-485 - TB2 Terminals ................................................................ 14
Configuring the ACM-8RF................................................................ 15
Address Switches - SW1 and SW2 .................................................. 15
Relay Assignment DIP Switch - SW3.............................................. 15
Mode Select Switch - SW4 .............................................................. 16
Mounting in the ABS-8RF Enclosure ............................................... 16
UL Power-limited Wiring Requirements ......................................... 17

3. Electrical Ratings
24 VDC................................................................................................. 19
Relay Contacts .................................................................................... 19
Data Communications Port ............................................................... 19
Power Requirements .......................................................................... 19

Appendix A: MS-5210UD
Capabilities.......................................................................................... 21
FACP Activations ............................................................................... 22
Alarm Only Activation..................................................................... 22
Alarm and Trouble Activation ......................................................... 23
Application Example #1 ..................................................................... 24
Application Example #2 ..................................................................... 25
Application Example #3 ..................................................................... 26
Application Example #4 ..................................................................... 28
Table of Contents
Appendix B: MS-9200
Capabilities ..........................................................................................31
Testing..................................................................................................31
Wiring ..................................................................................................31
FACP Activations ...............................................................................32
Alarm Only Activation .....................................................................32
Alarm and Trouble Activation..........................................................33

Appendix C: MS-9600
Capabilities ..........................................................................................37
Testing..................................................................................................37
Wiring ..................................................................................................37
Configuration ......................................................................................38
Setting Rotary Switches ...................................................................38
Mode Select ......................................................................................39
Alarm Only or Alarm/Trouble Mode ...........................................39
Receive Only or Receive/Transmit Mode....................................39
Setting the DIP Switches ..................................................................40
Alarm Only Activation.................................................................40
Alarm and Trouble Activation .....................................................41
Multiple ACM-8RFs ....................................................................42
1. Introduction

General
The ACM-8RF Relay Control Module contains eight high current (5 amps)
Form-C relays. The module interfaces to host Fire•Lite control panels which
employ an EIA-485 communications bus and may be connected to the bus up
to 6,000 feet away from the host control panel.
Typically, each relay is assigned to a zone on the
host fire alarm control panel. The relays may be
triggered by either a zone alarm (activation) or
zone trouble. The relays may also take on
special functions depending upon the host
panel. Refer to the Appendices for additional FF O

information.
1 2 O 1 2 3 4 5 6 7 8
F
F

The ACM-8RF Relay Control Module may be

[Link]
used in combination with the following
products on the same EIA-485 bus circuit:
• AFM/ACM Series LED annunciators
• LDM Series graphic annunciators
• UDACT-F (Universal Digital Alarm Communicator/Transmitter)
• LED-10 Annunciator
EIA-485 bus compatible accessories are designed to provide maximum
flexibility to system configurations. Examples include multiple remote LED
annunciators with customized labels per corresponding area or function,
multiple remote graphic annunciators that illustrate building layout and floor
plans, remote DACTs for strategic mounting location near telephone
equipment plus remote high current switching relays for such purposes as fan
and damper control, elevator recall and door releasing.

Mounting
The ACM-8RF module will mount to an ABS-8RF backbox.
A blank faceplate is provided with the backbox.
The CAB-3F Series cabinets, with CHS-4L or CHS-4F
chassis, may also be used to house several ACM-8RFs.
[Link]

ABS-8RF

ACM-8RF PN 50362:C 03/21/01 7


1. Introduction Features
Features

SW3 - Relay Assignment


DIP Switches

K4 K5
Relays Relays

K3 K6

K2 K7

[Link]
K1 K8
FF O
1 2 O 1 2 3 4 5 6 7 8
F
F

SW4 - Mode
TB2 - EIA-485
Select
Terminal Block
Switch

SW1-SW2
Address
TB1 - 24 VDC
Select Rotary
Terminal Block
Switches

Figure 1 ACM-8RF Features

Relays
The Relay Control Module provides eight Form-C relays with 5 amp contacts
@ 125 VAC (resistive) or 30 VDC (resistive) and 2 amps at 125 VAC
inductive). The relay contacts are gold plated silver alloy for medium duty
switching and are not intended for motor control or pilot duty. Wiring to the
relays is via sturdy removable terminal blocks.

24 VDC Power and Earth Ground


Wiring to removable terminal block TB1 is for 24 VDC power-limited,
regulated, nonresettable power from the host FACP or a compatible UL listed
battery backed power supply such as the Fire•Lite FCPS-24F. This terminal
block may be used to daisy chain the 24 VDC to other ACM-8RFs or EIA-485
Fire•Lite compatible devices.

8 ACM-8RF PN 50362:C 03/21/01


Related Documentation 1. Introduction
EIA-485 Communications
Wiring to removable terminal block TB2 is for communications over the EIA-
485 bus. The bus carries commands and data sent between the host FACP and
ACM-8RFs. The EIA-485 circuit is power-limited. The host FACP supervises
devices wired to the EIA-485 bus.
A maximum of 32 ACM-8RFs may be connected to the FACPs EIA-485 bus,
but if other types of devices are also connected to the bus, the maximum
number of ACM-8RFs must be reduced by the total of such devices.

Address Switches
Two rotary BCD (Binary Coded Decimal) switches, located on the lower right
of the module, are used to set the ACM-8RF system address. SW1 represents
the 'tens' position and SW2 represents the 'ones' position of the address setting.

Relay Function Selection


DIP switch SW3 is used to program the assignment of each ACM-8RF relay
to either a zone function (such as zone alarm or zone trouble triggering) or to
a system function (such as system alarm, system trouble, system supervisory,
signal silence, pre-alarm or AC fail). Be certain to review the Appendices for
information on SW3 switch settings for specific FACPs and the operation and
options available to each host FACP.

Mode Selection
DIP switch SW4 is used to set the mode of operation for the ACM-8RF as
follows:
• #1 sets Alarm activation or Alarm/Trouble activation mode.
• #2 sets Receive or Receive/Transmit mode.

Related Documentation
Further details about products referenced in this document can be found in the
manuals for the particular fire alarm control panel and components.

Part
Product
Number

MS-5210UD Fire Alarm Control Panel Instruction Manual 50193


MS-9200 Fire Alarm Control Panel Instruction Manual 51003
MS-9600 Fire Control Panel Instruction Manual 51335
LED-10 Remote Fire Annunciator 50400
FCPS-24F Instruction Manual 50079
UDACT-F Instruction Manual 50049
CAB-3F Series Cabinets 15391

Table 1 Related Documentation


ACM-8RF PN 50362:C 03/21/01 9
1. Introduction Related Documentation
NOTES

10 ACM-8RF PN 50362:C 03/21/01


2. Installation

Mounting the Enclosure.


Select and remove the appropriate knockout(s) on the ABS-8RF enclosure.
Securely mount the enclosure.
Ground the enclosure to a solid electrical ground per NEC Article 250.
Pull all wiring into the enclosure (refer to "UL Power-limited Wiring
Requirements" on page 17).

Wiring the Power Terminal Blocks


24 VDC power supplied by the host control panel or external power supply
must be regulated and power-limited. This power is inherently supervised (loss
of power also results in a communication failure at the control panel).
• Limit the total wire resistance to 10 ohms.
• Connect 24 VDC power from FACP or Power Supply to TB1-3 (+)
and TB1-4 (–).
• Connect earth ground (TB1-1 EARTH) to a mounting screw on the
backbox or cabinet.

TB1
24 VDC
5 S Y S C O M (– )
Power
4 S Y S C O M (– )
[Link]

3 24 V (+ )
2 24 V (+)
1 EARTH

Figure 2 24 VDC Power & Earth Ground Terminals - TB1

Wiring of multiple modules.


Host FACP or Remote First ACM-8RF -- -- -- -- -- -- Last ACM-8RF
Power Supply TB1 TB1
5 5
– 24 V D C
4 4
[Link]

3 3
+ 24 V D C
2 2
1 1

Figure 3 Multiple Module Wiring

ACM-8RF PN 50362:C 03/21/01 11


2. Installation Wiring the Relay Terminal Blocks
Wiring the Relay Terminal Blocks
The ACM-8RF provides eight relays with Form-C contacts rated for 5 amps.
Note: Wiring from these relays is not supervised.

The terminal assignments are illustrated below. For information on wiring


limitations, refer to "UL Power-limited Wiring Requirements" on page 17.

Relay 4 Relay 5
Normally Open Normally Open
Common Common
Normally Closed Normally Closed

Relay 3 Relay 6

Relay 2
Relay 7

[Link]
Relay 1 Relay 8

FF O
1 2 O 1 2 3 4 5 6 7 8
F
F

Note: All Relays have the same terminal


assignment position as those on relay #4 & #5

Figure 4 Relay Terminal Assignments

12 ACM-8RF PN 50362:C 03/21/01


Wiring the EIA-485 Terminal Blocks 2. Installation
Wiring the EIA-485 Terminal Blocks
Communications between the Fire Alarm Control Panel and the ACM-8RF is
accomplished over a two-wire EIA-485 serial communications bus which must
be power-limited. Communications between the host FACP and ACM-8RFs
is supervised by the fire alarm control panel.

Wiring Specifications
• The EIA-485 circuit cannot be T-tapped; it must be wired in a
continuous fashion from the control panel to the ACM-8RFs.
• The maximum wiring distance between the panel and ACM-8RFs is
6,000 feet.
• The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable
having a characteristic impedance of 120 ohms, +/- 20%.
• Limit the total wire resistance to 100 ohms.
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC
service, noisy electrical circuits that are powering mechanical bells or
horns, audio circuits above 25 VRMS, motor control circuits, or SCR
power circuits.
Note: Never use the EIA-485 shield for grounding purposes. Terminate the EIA-485
shield at the Fire Alarm Control Panel only.

Standard Annealed Copper Wire

Wire Size Diameter Cross Section Ohms per 1000 feet Pounds per
A.W.G in Mils Circ. Mils Sq. Inch @ 77°F. @ 149°F. 1000 feet

14 64 4110 0.00323 2.85 2.97 12.4


16 51 2580 0.00203 4.09 4.73 7.82
18 40 1620 0.00128 6.51 7.51 4.92

Table 2 Wire Specifications

EIA-485 Shield in Conduit


When the EIA-485 wiring is in conduit, connect the shield to system common.
The shield can enter the cabinet, but must be insulated from the cabinet (no
electrical contact). Between ACM-8RFs, wire-nut multiple shields together
(which can be inside of the respective ACM-8RF enclosure but ensure that the
shield does not contact earth ground).
[Link]

TB2
4 IN (– )
3 O U T (– )
2 O U T (+ )
1 IN (+ )

Figure 5 Terminating the Shield in Conduit

ACM-8RF PN 50362:C 03/21/01 13


2. Installation Wiring the EIA-485 Terminal Blocks
EIA-485 Shield Not in Conduit
When the EIA-485 wiring is not in conduit, terminate the shield at the outside
of the FACP cabinet. Do not allow the shield to enter or even touch the cabinet
housing the ACM-8RFs. Between ACM-8RFs, wire-nut multiple shields
together outside of the respective enclosures. Ensure that the shield does not
touch earth ground at any junction points.

TB 2
4 IN (– )

[Link]
3 O U T (– )
2 O U T (+ )
1 IN (+ )

Figure 6 Terminating the Shield with No Conduit

EIA-485 - TB2 Terminals


Wire as shown below:
Note: Leave a 120 ohm ELR installed across the EIA-485 Out terminals at the last
ACM-8RF on the circuit (see below). All other ACM-8RFs should not have a resistor
installed.

TB2
4 IN (–)
3 O U T (– )
[Link]

2 O U T (+ )
1 IN (+)

Figure 7 EIA-485 Terminal Block - TB2

Multiple wiring of EIA-485 circuits


First ACM-8RF -- -- -- -- -- -- Last ACM-8RF
Host FACP
TB2 TB2

E IA -4 8 5 (– ) 4 4
3 3
[Link]

2 2
E IA -4 8 5 (+ ) 1 1

Figure 8 Wiring Multiple ACM-8RFs - EIA-485

14 ACM-8RF PN 50362:C 03/21/01


Configuring the ACM-8RF 2. Installation
Configuring the ACM-8RF

Address Switches - SW1 and SW2


It is critical to the operation of the relays that the address switches be set
correctly.
To set the relay module for address ‘01’, position the arrow on SW1 (tens) so
it points to 0 and position the arrow on SW2 (ones) so it points to 1.

[Link]
TENS SW 2 ONES
SW 1
Figure 9 Address Switches SW1 & SW2

Relay Assignment DIP Switch - SW3


Check the Appendices for information on SW3 switch settings for specific
FACPs and the operation and options available to each host FACP. The
following illustration provides details on DIP switch placement in the On and
OFF position.
Side View of Switch
Shown in the OFF
Position
FF O
O 1 2 3 4 5 6 7 8
F
[Link]

Figure 10 Relay Assignment Switch

ACM-8RF PN 50362:C 03/21/01 15


2. Installation Mounting in the ABS-8RF Enclosure
Mode Select Switch - SW4
Set the mode of operation as follows:
ALM RCV
O N LY O N LY

1 2

[Link]
M O DE SELE CT
Figure 11 Mode Select Switch
• Switch #1 set to the ON position will cause the ACM-8RF relays to
trigger only for FACP zone alarm activation.
• Switch #1 set to the OFF position will cause the ACM-8RF relays to
trigger for FACP zone alarm and zone trouble activation.
• Switch #2 set to the ON position places the ACM-8RF in 'Receive
only' mode. In this mode, the ACM-8RF does not transmit
information back to the host FACP.
• Switch #2 set to the OFF position places the ACM-8RF in 'Receive/
Transmit' mode. In this mode, the ACM-8RF will transmit
supervisory data back to the FACP. The FACP will use this data to
acknowledge that the ACM-8RF is properly communicating.
Note: It is essential that ACM-8RFs and any other devices wired to the EIA-485 bus
and set to the same address not be programmed for receive/transmit mode. Only one
EIA-485 device per address may be set for receive/transmit.

Mounting in the ABS-8RF Enclosure


Place the ACM-8RF in the ABS-8RF backbox. Align the two captive screws
on the top of the relay module and the two mounting holes on the bottom of
the relay module with the standoffs on the backbox.
Note: A solid earth ground connection must be made to one of the top mounting
screws in order to provide transient and lightning protection.

Secure with captive screws at top and with two loose screws at bottom. Plug
all terminal blocks into their respective sockets. Place and secure faceplate to
backbox.
16 ACM-8RF PN 50362:C 03/21/01
UL Power-limited Wiring Requirements 2. Installation
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25" away
from any nonpower-limited circuit wiring. Furthermore, all power-limited
circuit wiring and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram
for the ACM-8RF is shown below. In this diagram, relays K1 through K4 are
being used for power-limited circuits and relays K5 through K8 for nonpower-
limited circuits. Different applications may require different conduit
knockouts to be used. Any conduit knockouts may be used provided that the
nonpower-limited wiring remain separated from the power-limited wiring.

K4 K5

K3 K6

K2 K7

K1 K8
FF O
1 2 O 1 2 3 4 5 6 7 8
F
F
[Link]

Figure 12 Typical Wiring Diagram


Requirements for power-limited and nonpower-limited circuits on the same
ACM-8RF module are as follows:
1. If a mix of power-limited and nonpower- limited circuits are connected
to relays, skip a set of dry contacts to maintain 0.25" spacing between
power-limited and nonpower-limited circuits.
2. If only power-limited or nonpower-limited circuits are being employed,
all relays may be used without skipping any for spacing purposes.
3. Relays K1 through K4 may be used to run all power-limited circuits
while K5 through K8 are being used to run all non-power-limited
circuits.
4. Refer to the Power-limited label located on the FACP door. Make a
notation on the label for each circuit being employed as a Nonpower-
limited circuit. (Refer to the example on the label).
ACM-8RF PN 50362:C 03/21/01 17
2. Installation UL Power-limited Wiring Requirements
NOTES

18 ACM-8RF PN 50362:C 03/21/01


3. Electrical Ratings

24 VDC
Must be power-limited.
Current Draw from 24 VDC Input @ Normal Standby: 0.030 amps
Maximum current with all output relays activated: 158 mA.

Relay Contacts
UL contact ratings are 5 amps @ 125 VAC (resistive) or 30 VDC (resistive)
and 2 amps @ 125 VAC (inductive).

Data Communications Port


Must be power-limited.
EIA-485 operating at: 20 Kbaud

Power Requirements
Each ACM-8RF relay module must be accounted for in the power calculations
outlined in the respective FACP installation manual. The ACM-8RF draws its
power from the control panel and must be considered when calculating the
primary and secondary power supply requirements for the system. However,
if the current draw dedicated to the ACM-8RF must be calculated as a separate
figure (in cases where a separate UL listed power source is used), use the
equations below:

Standby Current

Number of ACM-8RF modules [ ] X 0.030 =[ ] amps

Alarm Current

1.) Number of ACM-8RF modules [ ] X 0.030 =[ ] amps

2.) Maximum number of relays which [ ] X 0.016 =[ ] amps


can be activated simultaneously1

Total Alarm Current (sum of 1 & 2) =[ ] amps

1. The maximum number of simultaneously activated relays depends on system


configuration and programming.

Table 3 Power Requirement Calculations

ACM-8RF PN 50362:C 03/21/01 19


3. Electrical Ratings Power Requirements
NOTES

20 ACM-8RF PN 50362:C 03/21/01


Appendix A: MS-5210UD

Capabilities
When installed with an MS-5210UD Fire Alarm Control Panel (FACP), the
ACM-8RF Relay Control Modules provide relay activation for each of the ten
FACP zones plus special functions. Options exist to allow for alarm only or
alarm and trouble activations per zone. Output activation for General Alarm,
general trouble, general Supervisory, NAC Fault, AC Fail, System Off Normal,
Walktest start and Battery Trouble are also available. Up to 32 ACM-8RF
Relay Control Modules may be placed onto the EIA-485 communication bus
(if no other devices are installed on the bus).
CAUTION: It is vitally important that, following relay programming, all
relays be tested for correct activation by triggering zones and/or special
functions at the FACP. It should also be noted:
• ACM-8RF Relays will activate during the Alarm Pre-signal
Sequence and for Process Monitoring.
• ACM-8RF Relays will not activate during the Alarm Verification
Retard and Reset periods.
• ACM-8RF Relays will return to normal if a zone is set for
autoresettable operation.
Power Out + + -–+ - EIA-485
+ – LED-10IM
TB2 TB3 TB4 TB5

J10
J6J6

120 ohm ELR


Part #71244
[Link]

FF O
1 2 O 1 2 3 4 5 6 7 8
F
F

Figure 13 Wiring the ACM-8RF to an MS-5210UD

ACM-8RF PN 50362:C 03/21/01 21


Appendix A: MS-5210UD FACP Activations
FACP Activations
DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the Relay Control Module.
When installed with an MS-5210UD Fire Alarm Control Panel, use the
following tables to set SW3 switches. Note that two tables are provided; one
table for alarm only operation (SW4-1 = ON) and one table for alarm and
trouble operation (SW4-1 = OFF).
Alarm Only Activation
Table 4 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm activation only. Note that a
maximum of three ACM-8RFs are required if one relay is to be designated to
trigger on any FACP alarm. If a general system alarm relay is not required, two
ACM-8RFs may be used to allow individual relay triggering for activation of
FACP zones 1 through 10. When using only two ACM-8RFs, be sure to use
the switch settings for the 2nd and 3rd ACM-8RF in Table 4. Refer to "Relay
Assignment DIP Switch - SW3" on page 15 for information on setting DIP
switch SW3.
MS-5210UD Zone ACM-8RF Relay SW3 Settings
System Alarm Relay 1
Not Used Relay 2 (not used)
Not Used Relay 3 (not used) 1st ACM-8RF
Not Used Relay 4 (not used) SW3-1 = ON
Not Used Relay 5 (not used) SW3-5 = ON
Not Used Relay 6 (not used) All others = OFF
Not Used Relay 7 (not used)
Not Used Relay 8 (not used)
Z1 Relay 1
Z2 Relay 2
Z3 Relay 3 2nd ACM-8RF
Z4 Relay 4 SW3-2 = ON
Z5 Relay 5 SW3-5 = ON
Z6 Relay 6 All others = OFF
Z7 Relay 7
Z8 Relay 8
Z9 Relay 1
Z10 Relay 2
n/a Relay 3 (not used) 3rd ACM-8RF
n/a Relay 4 (not used) SW3-3 = ON
n/a Relay 5 (not used) SW3-5 = ON
n/a Relay 6 (not used) All others = OFF
n/a Relay 7 (not used)
n/a Relay 8 (not used)

Table 4 SW3 Settings for Alarm Only

22 ACM-8RF PN 50362:C 03/21/01


FACP Activations Appendix A: MS-5210UD
Alarm and Trouble Activation
Table 5 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm and trouble activation. Note that a
maximum of five ACM-8RFs are required if relays are to be designated to
trigger on any FACP status change. If system status relays are not required,
three ACM-8RFs may be used to allow individual relay triggering for alarm
and trouble activation of FACP zones 1 through 10. When using only three
ACM-8RFs, be sure to use the switch settings for the 3rd, 4th and 5th
ACM-8RF in Table 5.
MS-5210UD ACM-8RF ACM-8RF Trouble
SW3 Settings
Zone Alarm Relay Relay
System Status 1=System Alarm 5=System Trouble 1st ACM-8RF
System Status Relay 2 (not used) Relay 6 (not used) SW3-1 = ON
System Status Relay 3 (not used) 7=System Off Normal SW3-5 = ON
System Status Relay 4 (not used) 8=System Supervisory All others = OFF
System Status Relay 1 (not used) 5=NAC(s) Fault 2nd ACM-8RF
System Status Relay 2 (not used) 6=Walktest Start SW3-2 = ON
System Status Relay 3 (not used) 7=Battery Fail SW3-5 = ON
System Status Relay 4 (not used) 8=AC Fail All others = OFF
Z1 Relay 1 Relay 5 3rd ACM-8RF
Z2 Relay 2 Relay 6 SW3-3 = ON
Z3 Relay 3 Relay 7 SW3-5 = ON
Z4 Relay 4 Relay 8 All others = OFF
Z5 Relay 1 Relay 5 4th ACM-8RF
Z6 Relay 2 Relay 6 SW3-4 = ON
Z7 Relay 3 Relay 7 SW3-5 = ON
Z8 Relay 4 Relay 8 All others = OFF
Z9 Relay 1 Relay 5 5th ACM-8RF
Z10 Relay 2 Relay 6 SW3-1 = ON
n/a Relay 3 (not used) Relay 7 (not used) SW3-6 = ON
n/a Relay 4 (not used) Relay 8 (not used) All others = OFF

Table 5 SW3 Settings for Alarm and Trouble

ACM-8RF PN 50362:C 03/21/01 23


Appendix A: MS-5210UD Application Example #1
Application Example #1
Zone Alarm Only Activation (no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, only one relay per zone is required and the ACM-8RFs are
the only devices on the EIA-485 bus. Since only ACM-8RFs occupy the bus,
the address setting for them should be switch SW1 = 0 and switch SW2 = 1.
Enter this address into the MS-5210UD Level 3 addresses 02 - 03.
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones. Refer to the following chart for switch settings:
MS-5210UD ACM-8RF
Switch Settings
Zone Relay
Z1 Relay 1
Z2 Relay 2
Z3 Relay 3 1st ACM-8RF
SW1=0; SW2=1 (Address ‘01’)
Z4 Relay 4
SW3-2 = ON; SW3-5 = ON
Z5 Relay 5 All other SW3s = OFF
Z6 Relay 6 SW4-1=ON; SW4-2=ON
Z7 Relay 7
Z8 Relay 8
Z9 Relay 1
Z10 Relay 2
n/a Relay 3 2nd ACM-8RF
SW1=0, SW2=1 (Address ‘01’)
n/a Relay 4
SW3-3 = ON; SW3-5 = ON
n/a Relay 5 All other SW3s = OFF
n/a Relay 6 SW4-1=ON; SW4-2=OFF
n/a Relay 7
n/a Relay 8

Table 6 Settings for Zone Alarm Activation

24 ACM-8RF PN 50362:C 03/21/01


Application Example #2 Appendix A: MS-5210UD
Application Example #2
Zone Alarm and Trouble Activation (no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, two relays per zone are required for alarm and trouble,
therefore, three ACM-8RFs are necessary. In this example, the ACM-8RFs are
the only devices on the EIA-485 bus. Set the ACM-8RF address switches so
that SW1 = 0 and SW2 = 1 on each of the three ACM-8RFs. Enter this address
into the MS-5210UD Level 3 addresses 02 - 03. Refer to the following chart
for switch settings:
MS-5210UD ACM-8RF ACM-8RF
Switch Settings
Zone Alarm Relay Trouble Relay
Z1 Relay 1 Relay 5 1st ACM-8RF
Z2 Relay 2 Relay 6 SW1=0; SW2=1 (Address ‘01’)
Z3 Relay 3 Relay 7 SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
Z4 Relay 4 Relay 8
SW4-1=OFF; SW4-2=ON
Z5 Relay 1 Relay 5 2nd ACM-8RF
Z6 Relay 2 Relay 6 SW1=0; SW2=1 (Address ‘01’)
SW3-4 = ON; SW3-5 = ON
Z7 Relay 3 Relay 7
All other SW3s = OFF
Z8 Relay 4 Relay 8 SW4-1=OFF; SW4-2=ON
Z9 Relay 1 Relay 5 3rd ACM-8RF
Z10 Relay 2 Relay 6 SW1=0; SW2=1 (Address ‘01’)
SW3-1 = ON; SW3-6 = ON
n/a Relay 3 Relay 7
All other SW3s = OFF
n/a Relay 4 Relay 8 SW4-1=OFF; SW4-2=OFF

Table 7 Settings for Zone Alarm and Trouble Activation

ACM-8RF PN 50362:C 03/21/01 25


Appendix A: MS-5210UD Application Example #3
Application Example #3
Two LED-10 Annunciators and 10 Alarm Only Relays
(no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, only one relay per MS-5210UD zone is required and the
ACM-8RFs are sharing the EIA-485 bus with two LED-10s. Since ACM-8RFs
are sharing the bus with two other devices, the address setting for the ACM-
8RFs should be switches SW1 = 0 and SW2 = 3. Enter this address into the
MS-5210UD Level 3 addresses 02 - 03.
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones. Refer to the following chart for switch settings:
MS-5210UD ACM-8RF
Switch Settings
Zone Relay
Z1 Relay 1
Z2 Relay 2
Z3 Relay 3 1st ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
Z4 Relay 4
SW3-2 = ON; SW3-5 = ON
Z5 Relay 5 All other SW3s = OFF
Z6 Relay 6 SW4-1=ON; SW4-2=ON
Z7 Relay 7
Z8 Relay 8
Z9 Relay 1
Z10 Relay 2
n/a Relay 3 2nd ACM-8RF
SW1=0, SW2=3 (Address ‘03’)
n/a Relay 4
SW3-3 = ON; SW3-5 = ON
n/a Relay 5 All other SW3s = OFF
n/a Relay 6 SW4-1=ON; SW4-2=OFF
n/a Relay 7
n/a Relay 8

Table 8 Settings for Zone Alarm Activation with LED-10s

26 ACM-8RF PN 50362:C 03/21/01


Application Example #3 Appendix A: MS-5210UD
The figure below is provided as an application example of using two LED-10s
and two ACM-8RFs. It is not intended to be used as a wiring diagram.
Refer to Figure 13 on page 21, or the appropriate instruction manuals, for
detailed wiring information.

-
LED-10IM ++-- + -

J 6J6
LED-10 Address ‘01’

MS-5210UD

FIRE ANNUNCIATOR

FACP Program Level 3


Address 02 = ‘0’ Receive/Transmit
Address 03 = ‘3’ LED-10 Address ‘02’

[Link]
FIRE ANNUNCIATOR

Receive/Transmit

ACM-8RF ACM-8RF
Address ‘03’ Address ‘03’

FF O
1 2 O 1 2 3 4 5 6 7 8
FFO
1 2 O 1 2 3 4 5 6 7 8
F F
F F

Receive Only Receive/Transmit

Figure 14 Two LED-10s and Two ACM-8RFs

ACM-8RF PN 50362:C 03/21/01 27


Appendix A: MS-5210UD Application Example #4
Application Example #4
Two LED-10 Annunciators, 10 Alarm Only Relays and 20
Alarm/Trouble Relays (no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, only one relay per MS-5210UD zone is required for the first
set of Alarm Only Relays, two relays per MS-5210UD zone is required for the
second set of Alarm and Trouble Relays and the ACM-8RFs are sharing the
EIA-485 bus with two LED-10s. Since ACM-8RFs are sharing the bus with
two other devices, the address setting for the first set of ACM-8RFs should be
switches SW1 = 0 and SW2 = 3 for address '03'. The address setting for the
second set of ACM-8RFs should be switches SW1 = 0 and SW2 = 4 for address
'04'. Enter this highest address into the MS-5210UD Level 3 addresses 02 - 03.
Continued on the next page...

28 ACM-8RF PN 50362:C 03/21/01


Application Example #4 Appendix A: MS-5210UD
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones of Alarm Only Relays and three ACM-8RF modules
are required for 10 zones of Alarm and Trouble Relays (20 relays required).
MS-5210UD ACM-8RF ACM-8RF
Switch Settings
Zone Alarm Relay Trouble Relay
Z1 Relay 1
Z2 Relay 2
Z3 Relay 3 1st ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
Z4 Relay 4
SW3-2 = ON; SW3-5 = ON
Z5 Relay 5
All other SW3s = OFF
Z6 Relay 6 SW4-1=ON; SW4-2=ON
Z7 Relay 7
Z8 Relay 8
Z9 Relay 1
Z10 Relay 2
n/a Relay 3 2nd ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
n/a Relay 4
SW3-3 = ON; SW3-5 = ON
n/a Relay 5
All other SW3s = OFF
n/a Relay 6 SW4-1=ON; SW4-2=OFF
n/a Relay 7
n/a Relay 8
Z1 Relay 1 Relay 5 3rd ACM-8RF
Z2 Relay 2 Relay 6 SW1=0; SW2=4 (Address ‘04’)
Z3 Relay 3 Relay 7 SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
Z4 Relay 4 Relay 8
SW4-1=OFF; SW4-2=ON
Z5 Relay 1 Relay 5 4th ACM-8RF
Z6 Relay 2 Relay 6 SW1=0; SW2=4 (Address ‘04’)
SW3-4 = ON; SW3-5 = ON
Z7 Relay 3 Relay 7
All other SW3s = OFF
Z8 Relay 4 Relay 8 SW4-1=OFF; SW4-2=ON
Z9 Relay 1 Relay 5 5th ACM-8RF
Z10 Relay 2 Relay 6 SW1=0; SW2=4 (Address ‘04’)
SW3-1 = ON; SW3-6 = ON
n/a Relay 3 Relay 7
All other SW3s = OFF
n/a Relay 4 Relay 8 SW4-1=OFF; SW4-2=OFF

Table 9 Settings for Zone Alarm and Trouble Activation with LED-10s

ACM-8RF PN 50362:C 03/21/01 29


Appendix A: MS-5210UD Application Example #4
The figure below is provided as an application example of using two LED-10s
and two ACM-8RFs. It is not intended to be used as a wiring diagram.
Refer to Figure 13 on page 21, or the appropriate instruction manuals, for
detailed wiring information.
LED-10IM
++--
- + -

J6J 6
LED-1 Address ‘01’

FIRE ANNUNCIATOR

FACP Program Level 3


Address 02 = ‘0’ Receive/Transmit
Address 03 = ‘3’ LED-1 Address ‘02’

FIRE ANNUNCIATOR

Receive/Transmit

ACM-8RFs set to Address ‘03’ (Alarm Only)

[Link]
F FO FF O
1 2 O 1 2 3 4 5 6 7 8 1 2 O1 2 3 4 5 6 7 8
F F
F F

Receive Only
Receive/Transmit

ACM-8RFs set to Address ‘04’ (Alarm and Trouble)

FF O FF O FFO
1 2 O 1 2 3 4 5 6 7 8 1 2 O 1 2 3 4 5 6 7 8 1 2 O 1 2 3 4 5 6 7 8
F F F
F F F

Receive Only Receive Only Receive/Transmit

Figure 15 Two LED-10s and Five ACM-8RFs

30 ACM-8RF PN 50362:C 03/21/01


Appendix B: MS-9200

Capabilities
When installed with an MS-9200 Fire Alarm Control Panel (FACP), the ACM-
8RF Relay Control Modules provide relay activation (alarm only or alarm/
trouble) for each of the 56 FACP zones. Output activation for System Alarm,
System Trouble, Alarm Silence, Walktest, Supervisory, NAC Fault, Battery
Trouble and AC Fail are also available. Up to 32 ACM-8RF Relay Control
Modules may be placed onto the EIA-485 communication bus (if no other
devices are installed on the bus).

Testing
It is vitally important that, following relay programming, all relays be tested
for correct activation by triggering zones and/or special functions at the FACP.
It should also be noted:
• ACM-8RF relays will activate during the Alarm Pre-signal Sequence.
• ACM-8RF relays will not activate during the Alarm Verification
Retard and Reset periods.

Wiring
Wire the AMC-8RF to the MS-9200 control panel as shown below.

ACM-8RF

120 ohm ELR


Part #71244
FF O
1 2 O 1 2 3 4 5 6 7 8
F
F
[Link]

Nonresettable
24 VDC EIA-485
Power Out TB5 (+) & (–)
TB4(+) & (–)
24 V UN R EG 24 V NON R S 24 V RST BE LL 2 PO WER BE LL 1 PO WER SU P V AL AR M TR OUB LE PC /PR INTER SH IEL D SL C SL C
AC S

T
+ - + - + - B+ A + A- B- B+ A + A- B- NO C NO NC C NO NC C
T
TER M C O MM 1 C O MM 2 A B B+ A+ B- A -
T T O U T+ IN+ O UT- IN -
T T
B B B B T B B
4 2 1 3 B 5 6
7

MS-9200 Terminal Blocks

Figure 16 Wiring ACM-8RF to MS-9200


ACM-8RF PN 50362:C 03/21/01 31
Appendix B: MS-9200 FACP Activations
FACP Activations
DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the ACM-8RF. Use the following
tables to set SW3 switches. The Address Select Rotary Switches on all ACM-
8RFs must be set to address ‘01’ (SW1 = 0, SW2 = 1).
Two tables are provided, one table for alarm only operation (SW4-1 = ON) and
one table for alarm and trouble operation (SW4-1 = OFF).
Alarm Only Activation
Table 10 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm activation only. A
maximum of eight ACM-8RFs are required if one relay is to be designated to
trigger on any FACP zone alarm. If a general system alarm relay is not required,
seven ACM-8RFs may be used to allow individual relay triggering for alarm
activation of FACP zones 1 through 56. When using seven ACM-8RFs, be sure
to use the switch settings for the 2nd through the eighth ACM-8RF in Table 10.
ACM-8RF ACM-8RF MS-9200 ACM-8RF
MS-9200 Zone SW3 Settings
Relay SW3 Settings Zone Relay
System Alarm Relay 1 Z25 Relay 1
Not Used Relay 2 Z26 Relay 2
Not Used Relay 3 1st ACM-8RF Z27 Relay 3 5th ACM-8RF
Not Used Relay 4 SW3-1 = ON Z28 Relay 4 SW3-1 = ON
SW3-5 = ON SW3-6 = ON
Not Used Relay 5 All others = Z29 Relay 5 All others =
Not Used Relay 6 OFF Z30 Relay 6 OFF
Not Used Relay 7 Z31 Relay 7
Not Used Relay 8 Z32 Relay 8
Z1 Relay 1 Z33 Relay 1
Z2 Relay 2 Z34 Relay 2
Z3 Relay 3 2nd ACM-8RF Z35 Relay 3 6th ACM-8RF
Z4 Relay 4 SW3-2 = ON Z36 Relay 4 SW3-2 = ON
SW3-5 = ON SW3-6 = ON
Z5 Relay 5 All others = Z37 Relay 5 All others =
Z6 Relay 6 OFF Z38 Relay 6 OFF
Z7 Relay 7 Z39 Relay 7
Z8 Relay 8 Z40 Relay 8
Z9 Relay 1 Z41 Relay 1
Z10 Relay 2 Z42 Relay 2
Z11 Relay 3 3rd ACM-8RF Z43 Relay 3 7th ACM-8RF
Z12 Relay 4 SW3-3 = ON Z44 Relay 4 SW3-3 = ON
SW3-5 = ON SW3-6 = ON
Z13 Relay 5 All others = Z45 Relay 5 All others =
Z14 Relay 6 OFF Z46 Relay 6 OFF
Z15 Relay 7 Z47 Relay 7
Z16 Relay 8 Z48 Relay 8
Z17 Relay 1 Z49 Relay 1
Z18 Relay 2 Z50 Relay 2
Z19 Relay 3 4th ACM-8RF Z51 Relay 3 8th ACM-8RF
Z20 Relay 4 SW3-4 = ON Z52 Relay 4 SW3-4 = ON
SW3-5 = ON SW3-6 = ON
Z21 Relay 5 All others = Z53 Relay 5 All others =
Z22 Relay 6 OFF Z54 Relay 6 OFF
Z23 Relay 7 Z55 Relay 7
Z24 Relay 8 Z56 Relay 8

Table 10 SW3 Settings for Alarm Only

32 ACM-8RF PN 50362:C 03/21/01


FACP Activations Appendix B: MS-9200
Alarm and Trouble Activation
Table 11 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm and trouble activation. A
maximum of 16 ACM-8RFs are required if relays are to be designated to trigger
on any FACP status change. If system status relays are not required, 14 ACM-
8RFs may be used to allow individual relay triggering for alarm and trouble
activation of FACP zones 1 through 56. When using 14 ACM-8RFs, be sure
to use the switch settings for the 3rd through the 16th ACM-8RF in Table 11.
When the MS-9200 is programmed for an annunciator without a UDACT-F,
the first 16 relays will be assigned to the status functions listed in the table
below.
If the MS-9200 is programmed for an annunciator and a UDACT-F, the first
16 relays will be assigned to the status functions listed in Table 12 on page 35.
MS-9200 ACM-8RF ACM-8RF
Switch Settings
Zone Alarm Trouble
System Status 1=System Alarm 5=System Trouble
1st ACM-8RF
System Status Relay 2 (not used) 6=Alarm Silence SW3-1 = ON;
System Status Relay 3 (not used) Relay 7 (not used) SW3-5 = ON
All other SW3s = OFF
System Status Relay 4 (not used) Relay 8 (not used)
System Status Relay 1 (not used) 5= Supervisory
2nd ACM-8RF
System Status Relay 2 (not used) Relay 6 (not used) SW3-2 = ON;
System Status Relay 3 (not used) Relay 7 (not used) SW3-5 = ON
All other SW3s = OFF
System Status Relay 4 (not used) 8= Panel Trouble
Z1 Relay 1 Relay 5
3rd ACM-8RF
Z2 Relay 2 Relay 6 SW3-3 = ON;
Z3 Relay 3 Relay 7 SW3-5 = ON
All other SW3s = OFF
Z4 Relay 4 Relay 8
Z5 Relay 1 Relay 5
4th ACM-8RF
Z6 Relay 2 Relay 6 SW3-4 = ON;
Z7 Relay 3 Relay 7 SW3-5 = ON
All other SW3s = OFF
Z8 Relay 4 Relay 8
Z9 Relay 1 Relay 5
5th ACM-8RF
Z10 Relay 2 Relay 6 SW3-1 = ON;
Z11 Relay 3 Relay 7 SW3-6 = ON
All other SW3s = OFF
Z12 Relay 4 Relay 8
Z13 Relay 1 Relay 5
6th ACM-8RF
Z14 Relay 2 Relay 6 SW3-2 = ON;
Z15 Relay 3 Relay 7 SW3-6 = ON
All other SW3s = OFF
Z16 Relay 4 Relay 8
Z17 Relay 1 Relay 5
7th ACM-8RF
Z18 Relay 2 Relay 6 SW3-3 = ON;
Z19 Relay 3 Relay 7 SW3-6 = ON
All other SW3s = OFF
Z20 Relay 4 Relay 8

Table 11 SW3 Settings for Alarm and Trouble

ACM-8RF PN 50362:C 03/21/01 33


Appendix B: MS-9200 FACP Activations
MS-9200 ACM-8RF ACM-8RF
Switch Settings
Zone Alarm Trouble
Z21 Relay 1 Relay 5
8th ACM-8RF
Z22 Relay 2 Relay 6 SW3-4 = ON;
Z23 Relay 3 Relay 7 SW3-6 = ON
All other SW3s = OFF
Z24 Relay 4 Relay 8
Z25 Relay 1 Relay 5
9th ACM-8RF
Z26 Relay 2 Relay 6 SW3-1 = ON;
Z27 Relay 3 Relay 7 SW3-7 = ON
All other SW3s = OFF
Z28 Relay 4 Relay 8
Z29 Relay 1 Relay 5
10th ACM-8RF
Z30 Relay 2 Relay 6 SW3-2 = ON;
Z31 Relay 3 Relay 7 SW3-7 = ON
All other SW3s = OFF
Z32 Relay 4 Relay 8
Z33 Relay 1 Relay 5
11th ACM-8RF
Z34 Relay 2 Relay 6 SW3-3 = ON;
Z35 Relay 3 Relay 7 SW3-7 = ON
All other SW3s = OFF
Z36 Relay 4 Relay 8
Z37 Relay 1 Relay 5
12th ACM-8RF
Z38 Relay 2 Relay 6 SW3-4 = ON;
Z39 Relay 3 Relay 7 SW3-7 = ON
All other SW3s = OFF
Z40 Relay 4 Relay 8
Z41 Relay 1 Relay 5
13th ACM-8RF
Z42 Relay 2 Relay 6 SW3-1 = ON;
Z43 Relay 3 Relay 7 SW3-8 = ON
All other SW3s = OFF
Z44 Relay 4 Relay 8
Z45 Relay 1 Relay 5
14th ACM-8RF
Z46 Relay 2 Relay 6 SW3-2 = ON;
Z47 Relay 3 Relay 7 SW3-8 = ON
All other SW3s = OFF
Z48 Relay 4 Relay 8
Z49 Relay 1 Relay 5
15th ACM-8RF
Z50 Relay 2 Relay 6 SW3-3 = ON;
Z51 Relay 3 Relay 7 SW3-8 = ON
All other SW3s = OFF
Z52 Relay 4 Relay 8
Z53 Relay 1 Relay 5
16th ACM-8RF
Z54 Relay 2 Relay 6 SW3-4 = ON;
Z55 Relay 3 Relay 7 SW3-8 = ON
All other SW3s = OFF
Z56 Relay 4 Relay 8

Table 11 SW3 Settings for Alarm and Trouble

34 ACM-8RF PN 50362:C 03/21/01


FACP Activations Appendix B: MS-9200
Status functions of first 16 relays if the FACP has a UDACT-F installed.
ACM-8RF ACM-8RF Trouble
MS-9200 Zone SW3 Settings
Alarm Relay Relay
System Status 1 System Alarm 5= System Trouble 1st ACM-8RF
System Status Relay 2 (not used) 6=Alarm Silence SW3-1 = ON
System Status Relay 3 (not used) 7=Walk Test SW3-5 = ON
System Status Relay 4 (not used) 8=Supervisory All others = OFF
System Status Relay 1 (not used) 5=NAC Fail 2nd ACM-8RF
System Status Relay 2 (not used) Relay 6 (not used) SW3-2 = ON
System Status Relay 3 (not used) 7=Battery Trouble SW3-5 = ON
System Status Relay 4 (not used) 8=AC Fail All others = OFF

Table 12 Status Relays (with UDACT-F)

ACM-8RF PN 50362:C 03/21/01 35


Appendix B: MS-9200 FACP Activations
NOTES

36 ACM-8RF PN 50362:C 03/21/01


Appendix C: MS-9600

Capabilities
When installed with an MS-9600 Fire Alarm Control Panel (FACP), the ACM-
8RF Relay Control Modules provide relay activation (alarm only or alarm/
trouble) for: each of the 99 FACP zones; the two NACs; each of the 159
modules and 159 detectors on both SLC loops. Output activation for System
Alarm, System Trouble, Alarm Silence, Walktest, Supervisory, NAC Fault,
Battery Trouble and AC Fail are also available. Up to 32 ACM-8RF Relay
Control Modules may be placed onto the EIA-485 communication bus (if no
other devices are installed on the bus).

Testing
It is vitally important that, following relay programming, all relays be tested
for correct activations by triggering zones, points and special functions at the
FACP. It should also be noted:
• ACM-8RF relays will activate during the Alarm Pre-signal Sequence.
• ACM-8RF relays will not activate during the Alarm Verification
Retard and Reset periods

Wiring
Wire the ACM-8RF to the MS-9600 control panel as shown below.

ACM-8RF

120 ohm ELR


Part #17244 1 2
FF O
O 1
F
F
2 3 4 5 6 7 8

Nonresettable
24 VDC
[Link]

Power Out EIA-485


TB3(+) & (–) TB6 (+) & (–)

TB 3 TB 4 TB 5 TB 6 TB 7 TB 8

MS-9600 Terminal Blocks

Figure 17 Wiring ACM-8RF to MS-9600


ACM-8RF PN 50362:C 03/21/01 37
Appendix C: MS-9600 Configuration
Configuration
Setting Rotary Switches
The Address Select Rotary Switches (SW1 & SW2) are used to determine
which FACP annunciator address will trigger relays on the ACM-8RF. Use the
following table to set these switches. Refer to "Address Switches - SW1 and
SW2" on page 15 for information on setting these switches.
M = Module D = Detector
FACP
SW1 SW2 Relay Activation for:
Address
1 0 1 8 System Points & Zones 1-56
2 0 2 Zones 57-99 & 2 NACs
3 0 3 Loop 1, Address M1 - M64
4 0 4 Loop 2, Address M1 - M64
5 0 5 Loop 1, Address M65 - M128
6 0 6 Loop 2, Address M65 - M128
Loop 1, Address M129 - M159 &
7 0 7
Loop 2, Address M129 - M159
8 0 8 Loop 1, Address D1 - D64
9 0 9 Loop 2, Address D1 - D64
10 1 0 Loop 1, Address D65 - D128
11 1 1 Loop 2, Address D65 - D128
Loop 1, Address D129 - D159 &
12 1 2
Loop 2, Address D129 - D159
13 - 19 Not Used
20 2 0 8 System Points & Zones 1-56
21 2 1 Zones 57-99 & 2 NACs
22 2 2 Loop 1, Address M1 - M64
23 2 3 Loop 2, Address M1 - M64
24 2 4 Loop 1, Address M65 - M128
25 2 5 Loop 2, Address M65 - M128
Loop 1, Address M129 - M159 &
26 2 6
Loop 2, Address M129 - M159
27 2 7 Loop 1, Address D1 - D64
28 2 8 Loop 2, Address D1 - D64
29 2 9 Loop 1, Address D65 - D128
30 3 0 Loop 2, Address D65 - D128
Loop 1, Address D129 - D159 &
31 3 1
Loop 2, Address D129 - D159
Table 13 SW1 & SW2 Switch Settings
Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of
these addresses.

38 ACM-8RF PN 50362:C 03/21/01


Configuration Appendix C: MS-9600
Mode Select

Alarm Only or Alarm/Trouble Mode


Determine if “alarm only” mode or “alarm/trouble” mode is to be used and set
the Mode Select switch SW4-1 as described in "Mode Select Switch - SW4"
on page 16 and below.
If “alarm only” is selected, relays 1 to 8 will activate when an alarm signal is
received from a zone or point.
Alarm
Zone or Point
Signal
1, 9, 17 etc. or 65, 73, 81 etc. Relay 1
2, 10, 18 etc. or 66, 74, 82 etc. Relay 2
3, 11, 19 etc. or 67, 75, 83 etc. Relay 3
4, 12, 20 etc. or 68, 76, 84 etc. Relay 4
5, 13, 21 etc. or 69, 77, 85 etc. Relay 5
6, 14, 22 etc. or 70, 78, 86 etc. Relay 6
7, 15, 23 etc. or 71, 79, 87 etc. Relay 7
8, 16, 24 etc. or 72, 80, 88 etc. Relay 8

Table 14 Alarm Only Setup


If “alarm/trouble” is selected, then relays 1 to 4 will activate when an alarm
signal is received from a zone or point and relays 5 to 8 will activate when a
trouble signal is received from a zone or point.
Alarm Trouble
Zone or Point Zone or Point
Signal Signal
1, 9, 17 etc. or 65, 73, 81 etc. Relay 1 5, 13, 21 etc. or 69, 77, 85 etc. Relay 5
2, 10, 18 etc. or 66, 74, 82 etc. Relay 2 6, 14, 22 etc. or 70, 78, 86 etc. Relay 6
3, 11, 19 etc. or 67, 75, 83 etc. Relay 3 7, 15, 23 etc. or 71, 79, 87 etc. Relay 7
4, 12, 20 etc. or 68, 76, 84 etc. Relay 4 8, 16, 24 etc. or 72, 80, 88 etc. Relay 8

Table 15 Alarm and Trouble Setup

Receive Only or Receive/Transmit Mode


Determine if “receive only” mode or “receive/transmit” mode is to be used and
set the Mode Select switch SW4-2 as described in "Mode Select Switch - SW4"
on page 16.
Note: Only one EIA-485 device per address may be set for receive/transmit.

ACM-8RF PN 50362:C 03/21/01 39


Appendix C: MS-9600 Configuration
Setting the DIP Switches
The DIP switch (SW3), in combination with the Rotary Switches, is used to
determine which FACP activations will trigger relays on the ACM-8RF.
As described previously, the selection of “Alarm Only” or “Alarm/Trouble”
will determine how each module controls its relays. The difference between
these two settings is described below.

Alarm Only Activation


When “Alarm Only” is selected all relays respond to alarm signals.
The following table displays a dual example (zones & modules) of how to set
the DIP switches on two (2) ACM-8RFs to annunciate the zones or points of
an annunciator address. Although this table shows System Points & Zones 1
to 8 (address 01) and Loop 1, Points M65 to M80 (address 05), by referring to
Table 13 on page 38 it can be determined which ACM-8RF will activate what
zone or point, depending on the address that is set on the rotary switches.
ACM-8RF
Relay MS-9600 Zone1 or Point2

Relay 1 System Alarm or Loop 1, Address M65


Relay 2 Not Used or Loop 1, Address M66
Relay 3 Not Used or Loop 1, Address M67
1st ACM-8RF
SW3-1 = ON Relay 4 Not Used or Loop 1, Address M68
SW3-5 = ON Relay 5 Not Used or Loop 1, Address M69
All others = OFF
Relay 6 Not Used or Loop 1, Address M70
Relay 7 Not Used or Loop 1, Address M71
Relay 8 Not Used or Loop 1, Address M72
Relay 1 Zone 1 or Loop 1, Address M73
Relay 2 Zone 2 or Loop 1, Address M74
Relay 3 Zone 3 or Loop 1, Address M75
2nd ACM-8RF
SW3-2 = ON Relay 4 Zone 4 or Loop 1, Address M76
SW3-5 = ON Relay 5 Zone 5 or Loop 1, Address M77
All others = OFF
Relay 6 Zone 6 or Loop 1, Address M78
Relay 7 Zone 7 or Loop 1, Address M79
Relay 8 Zone 8 or Loop 1, Address M80

1. As per Table 13 the Rotary Switches (SW1 & SW2) are set to address ‘01’ for
System Points and Zones 1 to 56.
2. As per Table 13 the Rotary Switches (SW1 & SW2) are set to address ‘05’ for
Loop 1, Address M65 to M128.

Table 16 SW3 Settings for Alarm Only


Note: If the System Points (system alarm) is not required, up to seven (7) ACM-8RFs
may be used to allow activation of FACP zones 1 through 56. When using this
configuration do not use the DIP Switch settings for the 1st ACM-8RF.

40 ACM-8RF PN 50362:C 03/21/01


Configuration Appendix C: MS-9600
Alarm and Trouble Activation
When “Alarm/Trouble” is selected, relays 1 - 4 respond to alarm signals and
relays 5 - 8 respond to trouble signals.
The following table displays an example of how to set the DIP switches on four
(4) ACM-8RFs to annunciate the zones of an annunciator address. Although
this table shows System Points & Zones 1 to 8 (address 01), by referring to Table
13 on page 38 it can be determined which ACM-8RF will activate what zone
or point, depending on the address that is set on the rotary switches.

ACM-8RF ACM-8RF
MS-9600 Zone MS-9600 Zone
Alarm Relay Trouble Relay

1st ACM-8RF 1=System Alarm System Point 5=System Trouble System Point
SW3-1 = ON 2 (not used) System Point Relay 6 (not used) System Point
SW3-5 = ON 3 (not used) System Point 7=System Off Normal System Point
All others = OFF 4 (not used) System Point 8=System Supervisory System Point

2nd ACM-8RF 1 (not used) System Point 5=NAC Fault System Point
SW3-2 = ON 2 (not used) System Point 6=Walktest Start System Point
SW3-5 = ON 3 (not used) System Point 7=Battery Fail System Point
All others = OFF 4 (not used) System Point 8=AC Fail System Point

3rd ACM-8RF Relay 1 Zone 1 Relay 5 Zone 1


SW3-3 = ON Relay 2 Zone 2 Relay 6 Zone 2
SW3-5 = ON Relay 3 Zone 3 Relay 7 Zone 3
All others = OFF Relay 4 Zone 4 Relay 8 Zone 4

4th ACM-8RF Relay 1 Zone 5 Relay 5 Zone 5


SW3-4 = ON Relay 2 Zone 6 Relay 6 Zone 6
SW3-5 = ON Relay 3 Zone 7 Relay 7 Zone 7
All others = OFF Relay 4 Zone 8 Relay 8 Zone 8

Table 17 SW3 Settings for Alarm/Trouble - Zones


Note: If the System Points (system alarm, trouble or silence etc.) is not required, up to
fourteen (14) ACM-8RFs may be used to allow activation of FACP zones 1 through 56.
When using this configuration do not use the DIP Switch settings for the 1st ACM-8RF.

ACM-8RF PN 50362:C 03/21/01 41


Appendix C: MS-9600 Configuration
The following table displays an example of how to set the DIP switches on four
(4) ACM-8RFs to annunciate the points of an annunciator address. Although
this table shows Points M65 to M80 (address 05), by referring to Table 13 on
page 38 it can be determined which ACM-8RF will activate what zone or point,
depending on the address that is set on the rotary switches.

ACM-8RF ACM-8RF
MS-9600 Point MS-9600 Point
Alarm Relay Trouble Relay

1st ACM-8RF Relay 1 Loop1-Address M65 Relay 5 Loop1-Address M65


SW3-1 = ON Relay 2 Loop1-Address M66 Relay 6 Loop1-Address M66
SW3-5 = ON Relay 3 Loop1-Address M67 Relay 7 Loop1-Address M67
All others = OFF Relay 4 Loop1-Address M68 Relay 8 Loop1-Address M68

2nd ACM-8RF Relay 1 Loop1-Address M69 Relay 5 Loop1-Address M69


SW3-2 = ON Relay 2 Loop1-Address M70 Relay 6 Loop1-Address M70
SW3-5 = ON Relay 3 Loop1-Address M71 Relay 7 Loop1-Address M71
All others = OFF Relay 4 Loop1-Address M72 Relay 8 Loop1-Address M72

3rd ACM-8RF Relay 1 Loop1-Address M73 Relay 5 Loop1-Address M73


SW3-3 = ON Relay 2 Loop1-Address M74 Relay 6 Loop1-Address M74
SW3-5 = ON Relay 3 Loop1-Address M75 Relay 7 Loop1-Address M75
All others = OFF Relay 4 Loop1-Address M76 Relay 8 Loop1-Address M76

4th ACM-8RF Relay 1 Loop1-Address M77 Relay 5 Loop1-Address M77


SW3-4 = ON Relay 2 Loop1-Address M78 Relay 6 Loop1-Address M78
SW3-5 = ON Relay 3 Loop1-Address M79 Relay 7 Loop1-Address M79
All others = OFF Relay 4 Loop1-Address M80 Relay 8 Loop1-Address M80

Table 18 SW3 Settings for Alarm/Trouble - Points

Multiple ACM-8RFs
The table below provides DIP switch (SW3) settings for the use of multiple
ACM-8RFs. Only those switches listed in the ON column are placed in the
‘ON’ position. All other switches are to be in the ‘Off’ position.
ON ON
1st ACM-8RF 1&5 9th ACM-8RF 1&7
2nd ACM-8RF 2&5 10th ACM-8RF 2&7
3rd ACM-8RF 3&5 11th ACM-8RF 3&7
4th ACM-8RF 4&5 12th ACM-8RF 4&7
5th ACM-8RF 1&6 13th ACM-8RF 1&8
6th ACM-8RF 2&6 14th ACM-8RF 2&8
7th ACM-8RF 3&6 15th ACM-8RF 3&8
8th ACM-8RF 4&6 16th ACM-8RF 4&8

Table 19 DIP Switch Settings for Multiple ACM-8RFs

42 ACM-8RF PN 50362:C 03/21/01


Index
Index

Numerics current draw 19


120 ohm ELR 14, 21, 31, 37
120 volts AC 13 D
24 VDC 8, 11, 19 daisy chain 8
Detector 38
A DIP switch 9, 15, 22, 23, 32, 33,
ABS-8RF 7, 11, 16 40, 41, 42
AC Fail 21, 31, 37
activations 22, 32, 37, 40 E
address 16, 40 earth ground 11, 13, 14, 16
Address Select Rotary Switches 32, EIA-485 39
38 EIA-485 bus 9, 13, 16, 21, 31, 37
address setting 9 enclosure 11, 13, 14
address switches 15 external power supply 11
alarm 21
alarm activation 16
F
Alarm Pre-signal Sequence 31, 37
faceplate 7, 16
alarm signal 39, 40, 41
FCPS-24F 8
Alarm Silence 31, 37
Form-C contacts 12
Alarm Verification Retard 21, 31, 37
Form-C relays 7, 8
Alarm/Trouble activation 9
function 9
annunciator address 38, 40, 41, 42
autoresettable operation 21
I
B impedance 13
backbox 7, 16
Battery Trouble 21, 31, 37 K
knockout 11, 17
C
CAB-3F Series 7 L
cabinet 7, 13, 14 LDM Series annunciators 7
cable 13 LED annunciators 7
chassis 7 LED-10 27, 30
CHS-4F chassis 7 LED-10 Annunciators 26, 28
CHS-4L chassis 7 lightning protection 16
circuit wiring 17 Loop 40
communication failure 11
compatible devices 8 M
conduit 13, 14, 17 mode of operation 9, 16
contact ratings 19 Mode Select Switch 16
contacts 8 Module 38
Copper Wire 13 multiple ACM-8RFs 42
ACM-8RF PN 50362:C 03/21/01 43
Index
multiple modules 11 SW1 9, 15, 32, 38
multiple shields 13 SW2 9, 15, 32, 38
multiple wiring 14 SW3 9, 15, 22, 23, 32, 33, 40, 42
SW4 9, 16, 22, 32, 39
N switch settings 15, 22
NAC Fault 21, 31, 37 system address 9
NEC Article 250 11 System Alarm 31, 37
no conduit 14 system alarm 40
nonpower-limited 17 system alarm, trouble or silence 41
system common 13
system function 9
O System Trouble 31, 37
other devices 16
T
P TB1 8, 11
point 39 TB2 9, 14
points 37, 40, 42 terminal assignments 12
power calculations 19 terminal blocks 8, 16
power supply 11 tested 21, 31, 37
power supply requirements 19 transient protection 16
power-limited 9, 11, 13, 17, 19 trouble 21
Power-limited label 17 trouble activation 16
Pre-signal Sequence 21 trouble signal 39
Process Monitoring 21 trouble signals 41
protection 16 T-tapped 13

R U
Receive mode 16 UDACT-F 7, 33, 35, 38
Receive/Transmit mode 9, 16
regulated 11
relay assignment 15 W
relay triggering 22, 23, 32, 33 Walktest 21, 31, 37
relays 39, 40 wire-nut 13
Reset 21 wiring diagram 17
Reset periods 31, 37 wiring distance 13
resistance 11, 13
resistor 14 Z
rotary switches 9, 32, 38, 40 zone 7, 39
zone function 9
S zones 21, 31, 37, 40, 41
shield 13, 14
special functions 7, 21, 37
status functions 33
supervised 11
Supervisory 21, 31, 37
supervisory data 16
44 ACM-8RF PN 50362:C 03/21/01
ACM-8RF PN 50362:C 03/21/01 45
46 ACM-8RF PN 50362:C 03/21/01
Limited Warranty

The manufacturer warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under normal
use and service. Products are date-stamped at time of manufacture. The sole and
exclusive obligation of the manufacturer is to repair or replace, at its option, free of
charge for parts and labor, any part which is defective in materials or workmanship
under normal use and service. For products not under the manufacturer's date-
stamp control, the warranty is eighteen (18) months from date of original purchase
by the manufacturer's distributor unless the installation instructions or catalog sets
forth a shorter period, in which case the shorter period shall apply. This warranty is
void if the product is altered, repaired, or serviced by anyone other than the
manufacturer or its authorized distributors, or if there is a failure to maintain the
products and systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our customer
service department. Return product, transportation prepaid, to the manufacturer.

This writing constitutes the only warranty made by this manufacturer with respect
to its products. The manufacturer does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that the
manufacturer is not an insurer and assumes no risk for loss or damages or the cost
of any inconvenience, transportation, damage, misuse, abuse, accident, or similar
incident.

THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED,


OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT,
INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR
INABILITY TO USE THE MANUFACTURER'S PRODUCTS.
FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF,
OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE
OF ITS PRODUCTS.

This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized.

LimWarSm.p65 01/10/2000
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
[Link]

Common questions

Powered by AI

The ACM-8RF module interfaces with Fire•Lite control panels through an EIA-485 communications bus, which facilitates communication up to 6,000 feet from the host panel. It supports multiple ACM-8RF modules on the same bus and uses removable terminal blocks for connections. Each module can be configured using address switches SW1 and SW2 for system addressing, and DIP switches SW3 and SW4 for relay assignment and mode selection (e.g., Alarm activation or Alarm/Trouble activation mode). This ensures compatibility and proper communication with various control panels .

Using a single ACM-8RF for multiple zones can reduce costs and simplify system architecture by consolidating control functions, particularly suitable for smaller buildings or systems requiring fewer relay actions. However, the primary drawbacks include potential bottlenecks in relay processing and limited flexibility in independent zone control, which might affect troubleshooting and system maintenance. Conversely, dedicated modules for each zone improve granular control and system resilience but at increased complexity and cost, necessitating careful consideration of the building's specific needs and alarm response strategies .

The design strategy significantly benefits from the ACM-8RF's flexibility in connecting up to 32 modules per FACP, as well as its capacity to interface with LED and graphic annunciators, remote DACTs, and other signaling devices on the EIA-485 bus. This scalability allows system designers to consider both physical layout and functional requirements, optimizing for strategic relay placement to handle specific building fire protection areas and control needs such as fan/damper controls and elevator recalls, which could impact holistic system design .

The SW3 Relay Assignment DIP switch configures each relay on the ACM-8RF for zone or system functions, including zone alarm, zone trouble, system alarms, or supervisory functions, adapting to the specific requirements of the host FACP. The SW4 Mode Select switch sets the ACM-8RF to either Alarm or Alarm/Trouble activation mode and toggles between Receive or Receive/Transmit modes. For instance, in Application Example #2 with MS-5210UD, SW3 is set for Zone Alarm and Trouble Activation using two relays per zone. In Example #3, SW4 settings adjust between Receive/Transmit modes to integrate with LED-10 Annunciators without interference .

Integration involves addressing ACM-8RF modules using SW1 and SW2 to manage their positioning on the EIA-485 bus, ensuring optimal relay deployment for system needs. For varying scenarios, like zone alarm and trouble activations, specific relay configurations are set using the SW3 DIP switch for dedicated zone actions or combining system status relays when multiple modules work together, as seen in MS-9200 setups. When more complex set-ups are needed, multiple modules can align relays with specific supervisory or activation roles, thereby allowing a single FACP to manage varied situation responses effectively .

To securely mount the ACM-8RF, first, select and remove appropriate knockouts on the ABS-8RF enclosure for wire routing. Then firmly affix the enclosure and ground it to a solid electrical ground per NEC Article 250 standards. This grounding and secure installation are crucial to prevent electrical interference, ensuring the integrity and reliability of data communication and power supply via the closely regulated wiring pathways .

Using the MS-5210UD, the zone-specific control is achieved by programming the ACM-8RF relays with address and relay configurations tailored to each zone's requirements. Application Example #1 programs a single relay per zone for simple alarm activations, with SW3 controlling relay assignments for individual zone coverage and SW4 managing activation modes. The sequential deployment of multiple ACM-8RFs, each handling specific zone alarms and troubles, enables a detailed and efficient management of zone-specific fire alarm controls in a given setup .

The wiring requirements for the EIA-485 bus demand a continuous wiring pattern without T-tapping, using 18 AWG to 14 AWG twisted shielded pair cables with a characteristic impedance of 120 ohms (+/- 20%). The total wire resistance must not exceed 100 ohms. These requirements are critical because they ensure reliable data transmission and proper supervision by the host FACP, minimizing the risk of communication failures that could compromise the fire alarm system's operations .

The UDACT-F within an ACM-8RF network serves as a digital communicator that interfaces directly with the EIA-485 bus, allowing for remote dialer functions and transmission of alarm and trouble signals to external monitoring systems. This not only enhances system communication by providing a link to off-site monitoring but also adds a layer of redundancy and reliability to fire alarm reporting, supporting high-level operational assurances and quicker response times across the network .

The wiring for the ACM-8RF requires a total wire resistance limited to 10 ohms for the power terminal blocks and 100 ohms for EIA-485 communications to ensure effective and reliable circuit performance. To mitigate potential issues, it is advisable to use appropriate gauge twisted-pair cables (18-14 AWG), ensure correct impedance specifications, and check all connections diligently to maintain resistance within specified limits .

You might also like