100% found this document useful (1 vote)
1K views72 pages

Intelligent Control Panel: Wiring Manual

Uploaded by

Robel MT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views72 pages

Intelligent Control Panel: Wiring Manual

Uploaded by

Robel MT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Introduction
  • Wiring Requirements
  • Shielded Wire Termination
  • SLC Circuits without Isolators
  • SLC Circuits with Isolators
  • Monitor Modules
  • Control Modules
  • Relay Module
  • Intelligent Detector Bases
  • Addressable Manual Pull Station
  • Appendix A: Power Considerations
  • Appendix B: SLC Surge Suppression
  • Appendix C: Terminal Conversion Charts
  • Appendix D: Canadian Versions of SLC Devices

Intelligent Control Panel

SLC
Wiring Manual

Document 51870
04/23/2009
P/N 51870:G • ECN 08-704
G
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guides for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which are made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. These documents can be found at http:// pling its ability to report a fire.
www.systemsensor.com/html/applicat.html. A study by the Audible warning devices such as bells may not alert people
Federal Emergency Management Agency (an agency of the if these devices are located on the other side of closed or
United States government) indicated that smoke detectors partly open doors or are located on another floor of a building.
may not go off in as many as 35% of all fires. While fire alarm Any warning device may fail to alert people with a disability or
systems are designed to provide early warning against fire, those who have recently consumed drugs, alcohol or medica-
they do not guarantee warning or protection against fire. A fire tion. Please note that:
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons: • Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on • Studies have shown that certain people, even when they
roofs, or on the other side of closed doors. Smoke detectors hear a fire alarm signal, do not respond or comprehend the
also may not sense a fire on another level or floor of a building. meaning of the signal. It is the property owner's responsi-
A second-floor detector, for example, may not sense a first- bility to conduct fire drills and other training exercise to
floor or basement fire. make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors • In rare instances, the sounding of a warning device can
because: cause temporary or permanent hearing loss.

• Barriers such as closed or partially closed doors, walls, or A fire alarm system will not operate without any electrical
chimneys may inhibit particle or smoke flow. power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
• Smoke particles may become “cold,” stratify, and not reach been properly maintained and replaced regularly.
the ceiling or upper walls where detectors are located.
Equipment used in the system may not be technically com-
• Smoke particles may be blown away from detectors by air patible with the control panel. It is essential to use only equip-
outlets. ment listed for service with your control panel.
• Smoke particles may be drawn into air returns before Telephone lines needed to transmit alarm signals from a
reaching the detector. premise to a central monitoring station may be out of service
The amount of “smoke” present may be insufficient to alarm or temporarily disabled. For added protection against tele-
smoke detectors. Smoke detectors are designed to alarm at phone line failure, backup radio transmission systems are rec-
various levels of smoke density. If such density levels are not ommended.
created by a developing fire at the location of detectors, the The most common cause of fire alarm malfunction is inade-
detectors will not go into alarm. quate maintenance. To keep the entire fire alarm system in
Smoke detectors, even when working properly, have sensing excellent working order, ongoing maintenance is required per
limitations. Detectors that have photoelectronic sensing the manufacturer's recommendations, and UL and NFPA stan-
chambers tend to detect smoldering fires better than flaming dards. At a minimum, the requirements of NFPA 72 shall be
fires, which have little visible smoke. Detectors that have ion- followed. Environments with large amounts of dust, dirt or
izing-type sensing chambers tend to detect fast-flaming fires high air velocity require more frequent maintenance. A main-
better than smoldering fires. Because fires develop in different tenance agreement should be arranged through the local man-
ways and are often unpredictable in their growth, neither type ufacturer's representative. Maintenance should be scheduled
of detector is necessarily best and a given type of detector monthly or as required by National and/or local fire codes and
may not provide adequate warning of a fire. should be performed by authorized professional fire alarm
Smoke detectors cannot be expected to provide adequate installers only. Adequate written records of all inspections
warning of fires caused by arson, children playing with should be kept.
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of Limit-C1-2-2007

flammable materials, etc.).


2 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interference, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside aerial
energized. Do not attempt to install, service, or operate this wiring is not recommended, due to an increased susceptibility
unit until manuals are read and understood. to nearby lightning strikes. Consult with the Technical Ser-
CAUTION - System Re-acceptance Test after Software vices Department if any problems are anticipated or encoun-
Changes: To ensure proper system operation, this product tered.
must be tested in accordance with NFPA 72 after any pro- Disconnect AC power and batteries prior to removing or
gramming operation or change in site-specific software. Re- inserting circuit boards. Failure to do so can damage circuits.
acceptance testing is required after any change, addition or Remove all electronic assemblies prior to any drilling, filing,
deletion of system components, or after any modification, reaming, or punching of the enclosure. When possible, make
repair or adjustment to system hardware or wiring. All compo- all cable entries from the sides or rear. Before making modifi-
nents, circuits, system operations, or software functions known cations, verify that they will not interfere with battery, trans-
to be affected by a change must be 100% tested. In addition, former, or printed circuit board location.
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected Do not tighten screw terminals more than 9 in-lbs. Over-
by the change, up to a maximum of 50 devices, must also be tightening may damage threads, resulting in reduced terminal
tested and proper system operation verified. contact pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.

HARSH™, NIS™, Notifier Integrated Systems™, and NOTI•FIRE•NET™, are all trademarks; and FlashScan®, NION®, NOTIFIER®, ONYX®,
ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 3


Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we
make frequent upgrades to the embedded software in our products. To ensure that you are installing and
programming the latest features, we strongly recommend that you download the most current version of software for
each product prior to commissioning any system. Contact Technical Support with any questions about software and
the appropriate version for a specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions
about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

4 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Table of Contents

Table of Contents
Section 1: Introduction............................................................................................................. 8
1.1: About This Manual ........................................................................................................................................8
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Reference Documentation ............................................................................................................................9
1.4: SLC Overview .............................................................................................................................................11
1.5: Polling Protocols .........................................................................................................................................11
1.6: Devices .......................................................................................................................................................12
1.6.1: Monitor/Zone Interface Modules.......................................................................................................12
1.6.2: Control Modules ................................................................................................................................12
1.6.3: Isolator Modules ................................................................................................................................12
1.6.4: Relay Modules...................................................................................................................................13
1.6.5: Transponders .....................................................................................................................................13
1.6.6: Plug-in Detector Bases ......................................................................................................................13
1.6.7: Intelligent Detectors .........................................................................................................................13
1.6.8: Addressable Manual Pull Stations.....................................................................................................14
1.6.9: RFX Wireless Interface .....................................................................................................................14
1.6.10: ACPS-610/E Addressable Charger/Power Supply ..........................................................................14
1.6.11: ACPS-2406 Addressable Charger/Power Supply............................................................................15
1.6.12: AMPS-24/E Addressable Power Supply .........................................................................................15
1.7: SLC Capacity...............................................................................................................................................15
1.8: SLC Performance.........................................................................................................................................15
1.9: LED Operation.............................................................................................................................................16
Section 2: Wiring Requirements............................................................................................ 17
2.1: Recommended SLC Wiring.........................................................................................................................17
2.2: Two-Wire SLC - Style 4 (Class B) ..............................................................................................................18
2.2.1: Measuring Loop Resistance...............................................................................................................18
2.2.2: Measuring Total Wire Length ...........................................................................................................19
2.3: Four-Wire SLC Style 6 & 7 (Class A).........................................................................................................19
2.3.1: Measuring Loop Resistance...............................................................................................................19
2.3.2: Measuring Total Wire Length ...........................................................................................................20
2.4: Control Panel Terminal Blocks....................................................................................................................20
2.4.1: IFC2-3030 and IFC-3030 with LCM-320, LEM-320 ......................................................................20
2.4.2: IFC2-640 with Loop Expander Modules, IFC-320 ...........................................................................21
2.4.3: IFC-640 with Loop Expander Modules.............................................................................................21
2.4.4: IFC-200..............................................................................................................................................21
2.4.5: IFC-300/IFC-400 ...............................................................................................................................22
2.4.6: IFC-1010/IFC-2020 with JLIB-200A or JLIB-400 ...........................................................................22
Section 3: Shielded Wire Termination .................................................................................. 23
3.1: Overview......................................................................................................................................................23
3.2: No Conduit...................................................................................................................................................23
3.3: Full Conduit .................................................................................................................................................24
3.4: Partial Conduit .............................................................................................................................................24
3.5: Floating Shield ............................................................................................................................................25
Section 4: SLC Circuits without Isolators ............................................................................ 26
4.1: Overview......................................................................................................................................................26
4.2: NFPA Style 4 SLC .......................................................................................................................................26
4.3: NFPA Style 6 SLC .......................................................................................................................................27
Section 5: SLC Circuits with Isolators .................................................................................. 28
5.1: Overview......................................................................................................................................................28
5.2: Fault Isolator Module ..................................................................................................................................28
5.2.1: Wiring an Isolator Module ................................................................................................................28

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 5


Table of Contents

5.3: Isolator Detector Bases ................................................................................................................................29


5.3.1: How an Isolator Base Works .............................................................................................................29
5.4: NFPA Style 4 SLC Using Isolator Modules ................................................................................................30
5.5: NFPA Style 6 SLC Using Isolator Modules ................................................................................................31
5.6: NFPA Style 7 SLC Using an Isolating Device.............................................................................................32
Section 6: Monitor Modules................................................................................................... 33
6.1: Description ...................................................................................................................................................33
6.1.1: Addressable Monitor Module ............................................................................................................33
6.1.2: Zone Interface Module ......................................................................................................................33
6.1.3: Dual Monitor Module ........................................................................................................................34
6.1.4: Miniature Monitor Module ................................................................................................................34
6.1.5: M300MJ-4-20 4-20mA Monitor Module ..........................................................................................34
6.2: Setting an SLC Address for a Module .........................................................................................................35
6.3: NFPA Style B IDC Using Monitor Modules ...............................................................................................36
6.4: NFPA Style D IDC Using Monitor Modules ...............................................................................................37
6.5: NFPA Style B IDC Using Dual Monitor Modules.......................................................................................38
6.6: NFPA Style B IDC Using Zone Interface Modules .....................................................................................39
6.7: NFPA Style D IDC Using Zone Interface Modules.....................................................................................40
Section 7: Control Modules ................................................................................................... 41
7.1: Description ...................................................................................................................................................41
7.2: Wiring a NAC with Addressable Control Modules .....................................................................................41
7.2.1: Wiring a Solenoid with the M300CJ-REL ........................................................................................42
7.3: Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules ....................................................43
7.4: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules ....................................................44
7.5: Connecting a Releasing Device to the Addressable Control Module..........................................................45
Section 8: Relay Module ........................................................................................................ 47
8.1: Description ...................................................................................................................................................47
8.2: Wiring the Addressable Relay Module (Form-C Relay) .............................................................................47
Section 9: Intelligent Detector Bases ................................................................................... 48
9.1: Description ...................................................................................................................................................48
9.2: Wiring a Detector Base ................................................................................................................................48
9.3: Wiring an Isolator Base................................................................................................................................50
9.4: Wiring a Relay Base.....................................................................................................................................50
9.5: Wiring a Sounder Base.................................................................................................................................51
Section 10: Addressable Manual Pull Station...................................................................... 52
10.1: Description .................................................................................................................................................52
10.2: Wiring a Manual Pull Station.....................................................................................................................52
Appendix A: Power Considerations...................................................................................... 53
A.1: Supplying Power to 24 VDC Detectors and NACs ....................................................................................53
A.2: Supervising 24 VDC Power ........................................................................................................................54
A.2.1: Using Type Codes with Built-In Power Supervision on IFC-3030 .................................................54
A.2.2: Power Supervision Relay..................................................................................................................54
A.2.3: Using the Addressable Control Module Without Relay ...................................................................56
Appendix B: SLC Surge Suppression .................................................................................. 58
B.1: Introduction .................................................................................................................................................58
B.2: Installation ...................................................................................................................................................59
B.2.1: IFC-200 .............................................................................................................................................59
B.2.2: IFC-300, IFC-400..............................................................................................................................60
B.2.3: IFC-1010 & IFC-2020 (JLIB-200A or JLIB-400) ............................................................................61
B.2.4: IFC-640/E, IFC-3030/IFC2-3030 .....................................................................................................62
Appendix C: Terminal Conversion Charts for V-type and H-type Devices ....................... 63
C.1: M300RJ .......................................................................................................................................................63

6 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Table of Contents

C.2: M300CJ and M302MJ ................................................................................................................................64


C.3: M300MJ ......................................................................................................................................................65
Appendix D: Canadian Versions of SLC Devices ................................................................ 66

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 7


Section 1: Introduction

1.1 About This Manual


This document covers the installation and wiring of various Signaling Line Circuit (SLC) devices,
when used with the following Fire Alarm Control Panels (FACPs):
• IFC-200
• IFC-300/IFC-400
• IFC-1010/IFC-2020
• IFC-640/E, IFC2-640/E, IFC-320/E/C
• IFC-3030/IFC2-3030
• JNCA and JNCA-2
This document also provides basic information that applies to Johnson Controls SLC loops in
general, such as the branch resistance measurements.
See Section 2.4, “Control Panel Terminal Blocks”, on page 20 for basic panel-end SLC
connections. Additional information about each control panel and the modules and detectors
referenced in this document, and the part numbers for their manuals, can be found in the respective
installation manual as listed in Section 1.3, “Reference Documentation” below.
modules are changing to a new format. Several models are now available in this new format and
have replaced the old format illustrations in this manual. While the old format is no longer
manufactured for these models, Appendix C has been provided for those who need that wiring
information: it contains terminal conversion charts between the old and new formats. In this
appendix, the modules are referred to as “h-type” (the new format, which has horizontal rotary
dials) and “v-type” (the old format, which has vertical rotary dials). This naming convention is a
convenient way to avoid confusion when referring to a particular model, as the name of the model
does not indicate the format. Refer to Figure 1.1

Vertical rotary dials.


Old-format.

Horizontal rotary
dials. New-format.

Figure 1.1 Example of Old and New Module Formats

1.2 UL 864 Compliance


1.2.1 Products Subject to AHJ Approval
This SLC Wiring Manual accompanies installation, operation, and programming manuals for
various fire alarm control panels (FACPs). IFC2-3030, IFC2-640 and IFC-320/C have been
certified to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864 9th Edition.

8 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Reference Documentation Introduction

The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the SLC with products not tested for UL 864 9th Edition has not
been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These
applications will require the approval of the local Authority Having Jurisdiction (AHJ).

• IFC-200 • IFC-3030 with JCPU-3030


• IFC-300/400 • IFC-640/E
• IFC-1010/IFC-2020 • XP Series (XPP-1, XPC-8, XPM-8 &
• CMX-1 XPR-8)
• M510CJ • XP5-C
• FFT-7/FFT-7S • XP5-M
• M500MJ • ACPS-2406
• M501MJ • B224RB
• M502MJ • B501BH
• MPS-24A/E • B501BHT
• MPS-24B/E • FCPS-24/E
• JNCA

1.3 Reference Documentation


The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-JCI) provides the current
document revision. A copy of this document is included in every shipment. See Appendix D,
“Canadian Versions of SLC Devices” for Canadian part numbers.

Compatible Conventional Devices (Non-addressable) Document Number

Device Compatibility Document 51922


Device Compatibility Technical Bulletin LIT-445180

Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number

IFC-200 Instruction Manual Technical Manual 444

IFC-300/400 Installation, Operations and Programming Manual Technical Manual 443

IFC-640 Installation, Operations, and Programming Manuals 51864, 51865, 51866

IFC2-640 Installation, Operations, and Programming Manuals 52835, 52836, 52837


IFC-320 Installation, Operations, and Programming Manuals 52858, 52859, 52860
IFC-320C Canadian Applications Addendum 52858CDN

IFC2-3030E Installation, Operations, and Programming Manuals 52563, 52565, 52564


IFC-3030E Installation, Operations, and Programming Manuals 52024, 52026, 52025

JDVC Digital Voice Command Manual 52567

JDAA Digital Audio Amplifier Manual 52569

Johnson Controls Voice Alarm System Manual 51869

AA-series Audio Amplifier Manual 52526

IFC-1010/IFC-2020 Installation Manual Technical Manual 448

Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number

ACPS-610/E Installation Manual 53018

ACPS-2406 Installation Manual 51304

AMPS-24/E Power Supply Manual 51907

FCPS-24 Field Charger/Power Supply Manual 50059


Field Charger/Power Supply FCPS-24 Technical Bulletin LIT-445111

Table 1.1 Reference Documentation (1 of 3)

Continued on next page...

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 9


Introduction Reference Documentation

FCPS-24S6/FCPS-24S8 Field Charger/Power Supply 51977

System Components Document Number

RA400Z Remote LED Annunciator Installation Document I56-508


RFX Wireless Interface Manual 51012

XP Transponder Manual 15888


XP Transponder Technical Bulletin LIT-448180
XP10-M Installation Document I56-1803

XP5 Series Manual 50786


LIT-445230
XP6-C Installation Document I56-1805

XP6-MA Installation Document I56-1806

XP6-R Installation Document I56-1804


XPIQ Audio Transponder Manual 51013
XPIQ Quad Intelligent Audio Transponder Technical Bulletin LIT-445235

SLC Loop Devices Document Number


B224BI Isolator Base Installation Document (FlashScan/CLIP) I56-725

B224RB Relay Base Installation Document I56-659

B501J Standard Base Installation Document I56-1433

B501BH Sounder Base Installation Document I56-0491


B501BHT Temporal Sounder Base Installation Document I56-1367

B501B-FTXJ HARSH™ Base Installation Document I56-1486

B210LPJ Flanged Base Installation Document I56-727

2351TMJ Acclimate™ Multi-Sensor Detector Installation Document I56-1860

2951TMJ: See document for 2951J, 2951TJ and 2951TMJ

M300CJ Control Module Installation Document I56-1210


M300CJ-REL Control Module Installation Document I56-XXXX

M300DJ Dual Monitor Module Installation Document I56-0016

M300MJ Monitor Module Installation Document I56-1211


M300MJ-4-20 Monitor Module Installation Document I56-XXXX

M301MJ Mini Monitor Module Installation Document I56-1214

M300RJ Relay Module Installation Document I56-1213


FSB-200, FSB-200S Single-ended Reflected Type Projected Beam Smoke Detector I56-2424

2951J-COPTIR Intelligent Photoelectric Multi-Criteria Smoke Sensor I56-XXXX

DH300PL Low-flow Duct Detector I56-2198


DH300RPL Low-flow Duct Detector with Relay I56-2199

DH300P Duct Detector Installation Document I56-0018

DH300RP Duct Detector Installation Document I56-0048

FTX-P2J HARSH™ Installation Document I56-1863

1351J Ion Detector Installation Document I56-1362

1951J Ion Detector Installation Document I56-1929

7351J VIEW® Laser Detector Installation Document I56-1898

2351J & 2351TJ Photo Installation Document I56-1366

Table 1.1 Reference Documentation (2 of 3)

10 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


SLC Overview Introduction

2951J, 2951TJ and 2951TMJ (Acclimate™) Photoelectric Detectors Installation Document I56-1930

5351J Thermal Detector Installation Document I56-1363

5351RJ Rate of Rise Sensor Installation Document I56-1634


5951J, 5951RJ, and 5951HJ Thermal Detectors Installation Document I56-1931

M500FPJ Firephone Control Module I56-2550

M302MJ Zone Interface Module Installation Document I56-1212

FTX-P1J HARSH™ (CLIP mode) Installation Document I56-1485

M500XJ Isolator Module Installation Document I56-1384

JBG-12LX Addressable Pull Station Installation Document 51242

Note: Refer to the Device Compatibility Document for compatible conventional devices.

Table 1.1 Reference Documentation (3 of 3)

1.4 SLC Overview


Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC
wiring runs outside the building. For detailed information refer to Appendix B, “SLC Surge
Suppression”, on page 58.

1.5 Polling Protocols


FlashScan® is a patented system (US Patent Number 5,539,389) that greatly enhances the speed of
communication between analog intelligent devices. Communication is in a grouped fashion. If one
of the devices within the group has new information, the panel CPU stops the group poll and
concentrates on single points. Not all panels are FlashScan® capable; see “Protocol Use” below.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. Many but not all
FlashScan-capable devices can be set to run in CLIP mode; see installation sheet shipped with the
device.
Protocol Use: LCM-320/LEM-320 loops on IFC2-640, IFC-640/E and IFC-3030/IFC2-3030, and
SLC loops on IFC-320 can run in FlashScan mode or CLIP mode. IFC-200, IFC-300/IFC-400,
IFC-1010 and IFC-2020 run in CLIP mode only.
Many FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Use one of
the following three options with SLC loops:
1. Program all modules and detectors on an SLC as FlashScan.
2. Program all modules and detectors on an SLC as CLIP.

CAUTION:
! Do not program more than 99 addresses on a CLIP-mode SLC loop, because this will slow the
system down and compromise the response time of the panel to display off-normal events.

3. Program all detectors as CLIP and all modules as FlashScan on an SLC.

CAUTION:
! Do not program modules as CLIP and detectors as FlashScan on the same SLC. This combination
does not work.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 11


Introduction Devices

1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
• M300MJ Monitor Module; FlashScan or CLIP mode. (An earlier module named M500MJ
was CLIP mode only.)
• M300DJ Dual Monitor Module; FlashScan or CLIP mode.
• M301MJ Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module
named M501MJ was CLIP mode only.)
• M300MJ-4-20 Four-to-Twenty Milli-Amp Monitor Module; FlashScan mode only. CLIP
mode operation will generate a trouble message at the panel. This module is only compatible
with the IFC2-3030.
• M302MJ Zone Interface Module; FlashScan or CLIP mode. (An earlier module named
M502MJ was CLIP mode only).
• XP5-M Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. Supports FlashScan or CLIP mode. This module is
capable of participating in degraded mode where supported by the FACP. (See the XP5 Series
Manual)
• XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire
detectors; FlashScan or CLIP mode.
• XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of
participating in degraded mode where supported by the FACP.

1.6.2 Control Modules


Through these addressable modules, the control panel can selectively activate Notification
Appliance Circuits (NAC).
• M300CJ Control Module; FlashScan or CLIP mode. (Earlier monitor modules named CMX-1
and M510CJ were CLIP mode only.)
• M300CJ-REL Control Module; FlashScan mode only. CLIP mode operation will generate a
trouble message at the panel.
• XP5-C Acts as a NAC or a speaker/telephone circuit (Class B only) or a Form-C relay.
FlashScan capable. (See the XP5 Series Manual.)
• XP6-C Controls six NAC or speaker/telephone circuits; FlashScan or CLIP mode.
• M500FPJ Firefighter’s Telephone Module; FlashScan-only device for use with Fire Fighters
Telephone on IFC-320, IFC2-640, IFC-640, IFC-3030, and IFC2-3030. (See the Voice Alarm
System Manual, the DVC Manual, or the DAA Manual.)

1.6.3 Isolator Modules


Isolator Modules permit a short-circuited section of the SLC to be fault isolated from the remainder
of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
modules are required to meet the requirements of an NFPA Style 7 circuit.
• M500XJ Loop Fault Isolator Module; FlashScan or CLIP mode.

12 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Devices Introduction

1.6.4 Relay Modules


This addressable module provides the control panel with a dry-contact output for activating a
variety of auxiliary devices.
• M300RJ Relay Module; FlashScan or CLIP mode.
• XP6-R Controls six Form-C relays; FlashScan or CLIP mode.

1.6.5 Transponders
• XPIQ An integrated, multiple channel audio amplification and distribution subsystem
remotely controlled by the FACP. It can direct up to four low level audio signals from risers to
up to four audio amplifiers, which are then directed to up to four integrated, continuously
supervised speaker circuits. The XPIQ is FlashScan capable (only).
• XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with an efficient multiplex
subsystem capability. It communicates with the FACP and functions as a data-gathering panel
for alarm Initiating Device Circuits and as a remote switching center for Notification
Appliance Circuits (NAC), telephone circuits or relays. Not FlashScan capable.
For information on connecting these transponders to the SLC, refer to the XP Transponder Manual
or the XPIQ Manual.

1.6.6 Plug-in Detector Bases


Plug-in detector bases provide a connection between the SLC and a variety of intelligent detectors
which are snapped into place. Standard and isolator bases are used depending upon which NFPA
SLC style is required. Sounder and relay bases are similar to standard bases, but have sound or
relay capabilities.
• Standard Base - Models B501J (4 inch standard small diameter base, commonly used in
European installations) and B210LPJ (6 inch standard large diameter base, commonly used in
US installations)
• HARSH™ Base - Model B501B-FTXJ
• Isolator Base - Model B224BI isolator base.
• Sounder Base - Models B501BH (standard sounder base), and B501BHT(base with temporal
sounder)
• Relay Base - Model B224RB relay base

1.6.7 Intelligent Detectors


FSB-200S Addressable, intelligent, single-ended beam smoke detector with built-in sensitivity
testing. The FSB-200 is the same except that it does not provide sensitivity testing. Both models
support FlashScan and CLIP mode.
2951TMJ (Acclimate ™) Addressable, intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection (135°F / 57.2°C). FlashScan capable. (An earlier
version named 2351TMJ was also FlashScan capable. The model named 3251J was discontinued
as of December 1, 2001.)
2951J-COPTIR Intelligent Photoelectric Multi-Criteria Smoke Sensor. Plug-in type smoke sensor
that is a photoelectric sensing chamber combined with Carbon Monoxide (CO), thermal, and infra-
red (IR) sensors to help reduce false alarms. The 2951J-COPTIR adds thermal sensors that will
alarm at a fixed temperature of 135° F (57.2° C) and alarm sensitivity options with built-in alarm
and pre-alarm time delay. JCI panels offer different feature sets across different models. Certain
features of the 2951J-COPTIR may not be available on some panels. The 2951J-COPTIR
supports both FlashScan and CLIP modes. Read Status limitations may apply in CLIP mode.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 13


Introduction Devices

1951J Addressable, intelligent smoke detector that incorporates an ionization sensing chamber.
Designed to provide open area protection. FlashScan- and CLIP-mode capable. (An earlier model
named 1351J was also FlashScan capable. Earlier models named 1251J and 1551J were CLIP
mode only.)
2951J Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber.
Listed for use in ducts. Designed to provide open area protection. The 2951TJ adds thermal sensors
that will alarm at a fixed temperature of 135° F (57.2°C). Both models support FlashScan or CLIP
mode. (Earlier versions named 2351J and 2351TJ also supported FlashScan or CLIP mode, but
were not listed for use in ducts. Earlier models named2551J, 2251J and 2251THJ were CLIP mode
only.)
5951J Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot spacing capability. A fixed temperature sensor with 135°F (57.2°C) fixed
temperature alarm. The 5951RJ incorporates a thermal rate of rise of 15°F (8.3°C). The 5951HJ is
a high temperature sensor with 190°F (87.8°C) fixed temperature alarm. Both models support
FlashScan or CLIP mode. (Earlier versions named 5351J and 5351RJ also supported FlashScan or
CLIP mode. Earlier models named 5551J and 5551JR were CLIP mode only.)
DH300P Photoelectric Duct Detector. The DH300RP includes an alarm relay. Both models
support FlashScan or CLIP mode.
DH300PL Low-flow Photoelectric Duct Detector, with extended speed range of 100–4000 FPM
(0.5 m/s to 20.3 m/s). DH300RPL adds a relay. Both models support FlashScan or CLIP mode.
FTX-P2J (HARSH™) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. Supports FlashScan or
CLIP mode. (An earlier model named FTX-P1J was CLIP mode only.)
7351J VIEW® An advanced intelligent photoelectric detector that uses a laser diode, special
optics, and signal processing to obtain extremely high sensitivity. Supports FlashScan and CLIP
mode; compatible with IFC-300/IFC-400, IFC-320, IFC2-640, IFC-640, and IFC-3030/IFC2-3030
only. LPX-751L is compatible with IFC-200 and IFC-1010/IFC-2020; CLIP mode only. (An
earlier version named 7251J was CLIP mode only and compatible with IFC-300/IFC-400.)

1.6.8 Addressable Manual Pull Stations


The JBG-12LX is a dual-action pull station that, when activated, provides an addressable
identification and its location to the control panel. An addressable monitor module is mounted
inside the pull station to facilitate servicing and replacement. Supports FlashScan or CLIP mode.
An earlier model named BGX-101L was CLIP mode only.

1.6.9 RFX Wireless Interface


The RFX Wireless Interface allows communication between an intelligent addressable fire alarm
control panel and up to 80 wireless smoke detectors. The RFX Interface, which includes a wireless
receiver, monitors the status of each wireless detector and forwards this information to the control
panel through the SLC. This system uses the SDRF-751 Wireless Photo-Thermal Smoke Detector,
which is battery-powered and designed to operate with the RFX Wireless Interface. FlashScan
capable. Not suitable for Canadian applications. The RFX and associated devices were
discontinued as of December 31, 2005.

1.6.10 ACPS-610/E Addressable Charger/Power Supply


The ACPS-610/E is an addressable power supply and battery charger with 24 VDC outputs. It
operates in FlashScan or CLIP mode and has built-in strobe synchronization. Its four outputs may
be independently configured to drive Notification Appliance Circuits (NACs) or to provide
auxiliary power.

14 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


SLC Capacity Introduction

1.6.11 ACPS-2406 Addressable Charger/Power Supply


The ACPS-2406 is an auxiliary power supply and battery charger. Each of its four Notification
Appliance Circuits (NAC) is individually addressable, eliminating the need for control modules. In
addition, each circuit can provide notification appliance synchronization. FlashScan and CLIP
capable.

1.6.12 AMPS-24/E Addressable Power Supply


The AMPS-24/E is a primary power supply and battery charger. Depending on its configuration, it
can occupy either one or four addresses on an SLC. FlashScan capable.

1.7 SLC Capacity


The protocol selected for an SLC loop determines the maximum number of devices that can be
handled by the loop (see Section 1.5, “Polling Protocols”, on page 11). Within those limits, the
individual control panel may have additional restrictions. See the specific installation manual for
this information.

1.8 SLC Performance


SLC performance (Style 4, Style 6, or Style 7) depends on the configuration of the circuit and the
components on the circuit (see Table 1.2). SLC operation meeting Style 7 requirements isolates
each addressable device on the SLC from faults that may occur on the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-2002) lists the
trouble conditions that result when a fault exists on an SLC. Additional information is broken out in
Section 2, “Wiring Requirements”, on page 17, and Section 3, “Shielded Wire Termination”, on
page 17.

Type of Fault Style 4 Style 6 Style 7


Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 15


Introduction LED Operation

1.9 LED Operation


The table below lists the LED operation on the various devices of an SLC in CLIP (Classic Loop
Interface Protocol) Mode and FlashScan® Mode. When switching from FlashScan® to CLIP
mode, the loop circuit must be powered down for at least 30 seconds to reset devices to CLIP mode
LED operation.

CLIP Mode FlashScan® Mode

Control Panel Device Standby Activated Standby Activated

IFC-1010 Monitor Module Blinks RED RED continuous N/A N/A


IFC-2020 Control Module Blinks GREEN 2 sec. GREEN, then N/A N/A
Detector Blinks RED OFF N/A N/A
RED continuous

IFC-300/IFC-400 Monitor Module Blinks RED RED continuous N/A N/A


Control Module Blinks GREEN GREEN continous N/A N/A
Detector Blinks RED RED continuous N/A N/A

IFC-200 Monitor Module Blinks RED RED continuous N/A N/A


Control Module Blinks GREEN OFF N/A N/A
Detector Blinks RED RED continuous N/A N/A

IFC-320/E/C, IFC2- Monitor Module Blinks RED RED continuous Blinks GREEN RED continuous
640/E, IFC-640/E, Control Module Blinks GREEN GREEN continuous Blinks GREEN GREEN continuous
IFC-3030, Detector Blinks RED RED continuous Blinks GREEN RED continuous
IFC2-3030

NOTE: In CLIP mode, the 7251J and FTX-P1J blink GREEN in standby and stay RED when
activated.

16 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Section 2: Wiring Requirements

2.1 Recommended SLC Wiring


• Twisted-unshielded pair is recommended for IFC-320, IFC2-640, IFC-640, IFC2-3030,
IFC-3030, LCM-320, LEM-320, JLIB-200A, and JLIB-400;
Maximum resistance is 50 ohms per branch. See Table 2.1.
• Twisted-shielded pair: IFC-200, IFC-300/400, JLIB-200
Maximum resistance 40 ohms per branch. See Table 2.2.
To maximize distance on the SLC loop, use the recommended type of wire. Using other wiring
types makes the SLC circuit more susceptible to electrical interference and thus reduces its
maximum loop length.

FACP: Recommended
Wire Gauge†
Wire Type and Limitations* Max. Distance

JLIB-200A or JLIB-400 on IFC-1010/IFC-2020 (See Table 2.2 for JLIB-200.)

RECOMMENDED: Twisted unshielded 12,500 ft. (3,810 m) 12 AWG/3.31 mm²


pair, 12 to 18 AWG (3.31 mm² to 0.82 9,500 ft. (2,895.6 m) 14 AWG/2.08 mm²
mm²†). 50 ohms max per length of 6,000 ft. (1,828.8 m) 16 AWG/1.31 mm²
Style 6 and 7 loops. 50 ohms per 3,700 ft. (1,127.76 m) 18 AWG/0.82 mm²
branch max for Style 4 loops

NOTE: Twisted-shielded pair or untwisted unshielded wire is not recommended for use with JLIB-200A or JLIB-400.

IFC-640 and LEM-320 on IFC-640

RECOMMENDED: Twisted-unshielded 12,500 ft. (3,810 m) 12 AWG (3.31 mm²)


pair, 12 to 18 AWG (3.31 mm² to 0.82 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm²)
mm²). 50 ohms maximum per length of 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm²)
Style 6 & 7 loops. 50 ohms per branch 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm²)
maximum for Style 4 loop.

Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit.

Note: Twisted-shielded pair is not recommended for use with this panel.
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5
microfarads.

IFC-320, IFC2-640, LEM-320 on IFC2-640, LCM-320, LEM-320 on IFC-3030 or IFC2-3030

RECOMMENDED: Twisted-unshielded 12,500 ft. (3,810 m) 12 AWG (3.31 mm²)


pair, 12 to 18 AWG (3.31 mm² to 0.82 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm²)
mm²). 50 ohms, maximum per length of 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm²)
Style 6 & 7 loops. 50 ohms per branch 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm²)
maximum for Style 4 loop.

Untwisted, unshielded wire, in conduit 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 mm² to 1.31 mm²)
or outside of conduit. 3,700 ft. (1,127.76m) 18 AWG (0.82 mm²)

Twisted, shielded pair 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 mm² to 1.31 mm²)
Note: 3,700 ft. (1,127.76m) 18 AWG (0.82 mm²)
• Shields must be isolated from ground.
• Shields should be broken at each device.

Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not
exceed 0.5 microfarads.

Table 2.1 Wiring Recommendations: IFC-320, IFC2-640, IFC-640, IFC2-3030, IFC-3030, JLIB-200A,
JLIB-400, LEM-320, and LCM-320

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 17


Wiring Requirements Two-Wire SLC - Style 4 (Class B)

* XPIQ-SLI is an SLC device that provides an additional local SLC loop. This local SLC loop should use the same type of
wire recommended for the FACP controlling the main SLC loop. Maximum resistance of the local SLC (from any device
to FACP): 50 ohms. Maximum resistance of the local SLC (from any device to XPIQ-SLI): 20 ohms. (Maximum number
of detectors and modules = 64) Maximum SLC local branch current degraded mode: 20 mA. Maximum distance of local
loop: 2,000 ft. (600 m). Recommended wire: 12 AWG (3.31 mm²)
† Notifier brand cable is recommended; see the product catalog available from Paige Electric.

FACP: Recommended
Wire Gauge
Wire Type and Limitations Max. Distance

IFC-200

Twisted-shielded pair. 40 ohms 10,000 ft. (3,048 m) 12 AWG (3.31 mm²)


maximum per length of Style 6 and 7 8,000 ft. (2,438.4 m) 14 AWG (2.08 mm²)
loops. 40 ohms per branch maximum 4,875 ft. (1,485.9 m) 16 AWG (1.31 mm²)
for Style 4 loops 3,225 ft. (982.98 m) 18 AWG (0.82 mm²)

Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit

Note: Twisted-unshielded pair wire is not recommended for use with this panel.
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to earth) should not exceed
0.5 microfarads.

IFC-300/IFC-400

Twisted-shielded pair, 12 to 18 AWG. 10,000 ft. (3,048 m) 12 AWG (3.31 mm²)


40 ohms, maximum per length of Style 8,000 ft. (2,438.4 m) 14 AWG (2.08 mm²)
6 and 7 loops. 40 ohms per branch 4,875 ft. (1,485.9 m) 16 AWG (1.31 mm²)
maximum for Style 4 loops. 3,225 ft. (982.98 m) 18 AWG (0.82 mm²)

Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit.

Note: Twisted-unshielded pair wire is not recommended for use with this panel.

JLIB-200 on IFC-1010/IFC-2020 (See Table 2.1 for JLIB-200A or JLIB-400.)

Twisted-shielded pair. Maximum loop 10,000 ft. (3,048 m) 12 AWG (3.31 mm²)
resistance is 40 ohms. Maximum 8,000 ft. (2,438.4 m) 14 AWG (2.08 mm²)
length is 10,000 ft. per channel (NFPA 4,875 ft. (1,485.9 m) 16 AWG (1.31 mm²)
Style 4) or 10,000 ft. total twisted pair 3,225 ft. (982.98 m) 18 AWG (0.82 mm²)
length (NFPA Style 6 and 7). Maximum
loop current is 200 mA (short circuit) or *If the wiring connected to the JLIB-200 leaves the building it must be in conduit. It can
100 mA (normal). not exceed 1000 m (1093 yards), must not cross any power lines, and must not be in the
vicinity of any high voltage. These outdoor wiring restrictions do not apply to the JLIB-
200A or the JLIB-400.

Table 2.2 Wiring: IFC-200, IFC-300/400, JLIB-200

2.2 Two-Wire SLC - Style 4 (Class B)


2.2.1 Measuring Loop Resistance
T-tapping of the SLC wiring is permitted for two-wire Style 4 configurations. The total DC
resistance from the control panel to each branch end cannot exceed50 ohms.
• 50 ohms for IFC-320, IFC2-640, IFC-640, LCM-320, LEM-320, JLIB-200A and JLIB-400.
• 40 ohms for IFC-200, IFC-300/400, and JLIB-200
Measure DC resistance as detailed and shown below:
1. With power removed, short the termination point of one branch at a time and measure the DC
resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.

18 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Four-Wire SLC Style 6 & 7 (Class A) Wiring Requirements

In Figure 2.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is
T-tapped.

Branch A Branch B Branch C

SLC Out
SLC-meas5.cdr

Branch

Short Point SLC Terminal


Block
B+ B–

Figure 2.1 Measuring DC Resistance of a Two-Wire SLC

2.2.2 Measuring Total Wire Length


The total wire length of all combined branches of one SLC cannot exceed the limits set forth in
each system’s instruction manual. Determine the total length in each SLC by summing all wire
segments. In Figure 2.1 above, the picture on the right shows an SLC with 3 branches. Figure 2.2
below shows the same SLC divided into segments. The total length of the SLC is determined by
adding the lengths of Segment 1 + Segment 2 + Segment 3 + Segment 4 + Segment 5. No segment
should be summed twice.

Branch A Branch B Branch C

Segment
Segment
Five
Four

Segment

SLC-meas2.cdr
Segment Segment Three
One Two

SLC Terminal Block

Figure 2.2 Measuring the Total Wire Length of a Two-wire SLC

2.3 Four-Wire SLC Style 6 & 7 (Class A)


2.3.1 Measuring Loop Resistance
The total DC resistance of the SLC pair exceed 50 ohms.
• 50 ohms for IFC-320, IFC2-640, IFC-640, LCM-320, LEM-320, JLIB-200A and JLIB-400.
• 40 ohms for IFC-200, IFC-300/400, and JLIB-200
Measure DC resistance as detailed and shown below:
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the SLC at the last device and measure the resistance at SLC Out. Record resistance and
remove the short.
3. Short the SLC at the first device and measure the resistance at SLC return. Record resistance
and remove the short.
The maximum DC resistance of the SLC is the higher of 2 and 3.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 19


Wiring Requirements Control Panel Terminal Blocks

SLC Out First Device

STEP 2

Last Device
SLC Return

Short Point

SLC Out

SLC-meas5.cdr
First Device
STEP 3
SLC Return

Last Device

Figure 2.3 Measuring DC Resistance of a Four-Wire SLC

2.3.2 Measuring Total Wire Length


The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s
instruction manual. The figure below identifies the output and return loops from SLC terminal on
the control panel:

SLC channel B SLC channel A


(output loop) (return loop)

SLC Terminal Block


B+ A+ B– A–

Figure 2.4 Measuring the Wire Length of a Four-Wire SLC

2.4 Control Panel Terminal Blocks


2.4.1 IFC2-3030 and IFC-3030 with LCM-320, LEM-320
The IFC-3030/IFC2-3030 supports up to five pairs of loop control and expander modules,
providing from one to ten SLC loops. Loops can be either CLIP mode or FlashScan mode. SLC
loops connect to TB1 on the LCM-320 or LEM-320.
LEM320-SLC-TB.cdr

SLC Loop Connections SLC Loop Connections


on Loop Control Modules on Loop Expander Module

Figure 2.5 IFC2-3030, IFC-3030 SLC Loop Connections and Wiring

20 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Control Panel Terminal Blocks Wiring Requirements

2.4.2 IFC2-640 with Loop Expander Modules, IFC-320


The IFC2-640 provides one SLC loop and supports a second using optional expander module
LEM-320.The IFC-320 provides one SLC loop on the FACP’s main circuit board. Terminal block
designations are the same on the circuit board for both FACPs. Loops can be either CLIP mode or
FlashScan mode. SLC loop #1 connects to TB13 on the control panel; SLC loop #2 connects to
TB1 on the LEM-320.

NFS2640-SLC-TB.wmf,
LEM320-SC-tb.wmf
SLC Loop #1 Connections SLC Loop #2 Connections
on FACP’s main circuit board on Loop Expander Module

Figure 2.6 SLC Loop Connections and Wiring

2.4.3 IFC-640 with Loop Expander Modules


The IFC-640 provides one SLC loop and supports a second using optional expander module
LEM-320. Loops can be either CLIP mode or FlashScan mode. SLC loop #1 connects to TB16 on
the control panel; SLC loop #2 connects to TB1 on the LEM-320.

nfs640-slc-tb.cdr, LEM320-slc-tb.cdr
SLC1
B+ A+ B- A-
B+ A+ B- A- TB1

TB16
SLC Loop #1 Connections SLC Loop #2 Connections
on FACP’s main circuit board on Loop Expander Module

Figure 2.7 SLC Loop Connections and Wiring

2.4.4 IFC-200
IFC-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5.

slc-200.wmf

SLC Loop #1 Connections


on FACP’s main circuit board

Figure 2.8 SLC Connections for IFC-200

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 21


Wiring Requirements Control Panel Terminal Blocks

2.4.5 IFC-300/IFC-400
IFC-300 supports one SLC loop; IFC-400 supports two SLC loops. The loops are CLIP mode only.
SLC loops connect to TB6 on IFC-300; SLC loops connect to TB5 and TB6 on IFC-400.

slc-300.wmf, slc-400.wmf
SLC Loop #1 Connections SLC Loop Connections
on’s main circuit board on’s main circuit board

Figure 2.9 IFC-300/IFC-400.

2.4.6 IFC-1010/IFC-2020 with JLIB-200A or JLIB-400

slc-400.wmf
SLC Loop #1 Connections
on FACP’s main circuit board

IFC-1010/IFC-2020 supports up to ten SLC loops using JLIB-200A (one SLC loop per board)
and/or JLIB-400 (one or two SLC loops per board). The loops are CLIP mode only. SLC loops
connect to TB1 and TB2 on JLIB-400, and TB1 on JLIB-200A.

Pin 1 SLC Loop Port A+

Pin 3 SLC Loop Port A-

Pin 5 SLC Loop Port B+

Pin 7 SLC Loop Port B-


Pin 8 Earth Ground

Pin 1 SLC Loop Port A+ Pin 1 SLC Loop Port A+


slc-lib-200a.wmf,slc-lib-400.wmf

Pin 3 SLC Loop Port A- Pin 3 SLC Loop Port A-

Pin 5 SLC Loop Port B+ Pin 5 SLC Loop Port B+

Pin 7 SLC Loop Port B- Pin 7 SLC Loop Port B-


Pin 8 Earth Ground Pin 8 Earth Ground

JLIB-200A JLIB-400

NOTE: JLIB-200 has been replaced by JLIB-200A.

Figure 2.10 SLC Connections for JLIB-200A & JLIB-400

22 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Section 3: Shielded Wire Termination

3.1 Overview
This section shows the proper termination of the shield, if used.
Shielding of the SLC is recommended for use with IFC-200, IFC-300/400, JLIB-200. Proper
termination of the shield depends on the type of conduit used:
• Section 3.2, “No Conduit”.
• Section 3.3, “Full Conduit” (Canadian requirement).
• Section 3.4, “Partial Conduit”.
Shielding of the SLC is not recommended for use with IFC-320/E/C, IFC2-640/E, IFC-640/E,
IFC2-3030, IFC-3030, LCM-320, LEM-320, JLIB-200A or JLIB-400. If twisted-shielded wire is
used in one of these installations, use a floating shield to terminate the wire as shown in
Section 3.5, “Floating Shield”, on page 25.
Use of good wiring practice consistent with local electrical codes is expected.

3.2 No Conduit
„ For use with IFC-200, IFC-300/400, and JLIB-200 only
Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Fold the foil
and drain wire back over the cable jacket. Slide the cable into the connector clamp and secure. The
drain wire should be connected to the connector screw. Do not allow the shield drain wire or foil to
enter the system cabinet.
Connector Screw
Shield Drain Wire
Cabinet

Foil

SLC-swterm1.cdr

Figure 3.1 Shield Termination – No Conduit

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 23


Shielded Wire Termination Full Conduit

3.3 Full Conduit


„ For use with IFC-200, IFC-300/400, and JLIB-200only
Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire
through the conduit, into the control box. The shield drain wire must be connected to the
“reference” or “shield” terminal on the SLC terminal block, or connected to the negative side of the
loop if there is no “reference” or “shield” terminal on the SLC terminal block. Do not let the shield
drain wire or the shield foil touch the system cabinet or be connected to earth ground at any point.

Shield Drain Wire


Example at right illustrates Cabinet
shield drain wire connection Foil
to an SLC terminal block with
a “reference” connection.

Conduit

Shield2.wmf, SLC-swterm2a.wmf
Tape over foil.

Cabinet Foil
Shield Drain Wire
Example at right illustrates –
shield drain wire connection
to an SLC terminal block Conduit
without a “reference” or
“shield” connection. +

NOTE: For Style 6 or Style 7 SLC wiring, connect one end of the shield to the
reference/negative side of the respective channel

Figure 3.2 Shield Termination – Full Conduit

3.4 Partial Conduit


„ For use with IFC-200, IFC-300/400, and JLIB-200
If the length of conduit from the control panel cabinet is less than 20 ft. (6.1 m), terminate the
shield as shown. If using a metal box, you must use a metal conduit.
Connect the shielded wire to the junction box by using a proper connector. Scrape the paint on the
cabinet to bare metal to provide a good electrical connection. Connect the metal conduit between
the junction box and the cabinet by using the proper connectors.
Feed the twisted-pair wire into the junction box, through the conduit, into the cabinet box. Within
the junction box, connect the appropriate wires together using wire nuts. Connect the shield drain
wire to the junction box, at the end of the conduit run, as shown below.
Do not allow the shield drain wire to enter the system cabinet or the conduit.

Foil Shield Drain Wire

Cabinet
SLC-swterm3.cdr

Conduit

Figure 3.3 Shield Termination – Partial Conduit

24 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Floating Shield Shielded Wire Termination

3.5 Floating Shield


„ If using shielded wire with IFC-320, IFC2-640/E, IFC-640/E, IFC2-3030, IFC-3030,
LCM-320, LEM-320, JLIB-200A and JLIB-400
Twisted-unshielded wire is recommended for IFC-320/E/C, IFC2-640/E, IFC-640/E, IFC2-3030,
IFC-3030, LCM-320, LEM-320, JLIB-200A and JLIB-400. If twisted-shielded pair wire is used in
these installations, use a floating shield to terminate the wire. The following precautions must be
met:
• If the SLC is more than 3000 ft. (914.4 m), divide the shield into floating segments of less than
1000 ft. (304.8 m).
• To divide the shield wire into floating segments, cut shield even with jacket and tape as shown:

Tape

SLC-swterm4.cdr
NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum
SLC length. If shielded wire must be used where not recommended, failing to float the ends will
reduce the maximum SLC length even further.

Figure 3.4 Floating the Shield

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 25


Section 4: SLC Circuits without Isolators

4.1 Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:
• NFPA 72 Style 4
• NFPA 72 Style 6

4.2 NFPA Style 4 SLC


NFPA Style 4 requirements can be met by using the diagram below.
• T-tapping of the SLC wiring is allowed for Style 4 configuration.

Two-wire Addressable Detector

Addressable Module

T-tapped Circuits

B+ B–
SLC-style4.cdr
Control Panel
SLC

Figure 4.1 Basic NFPA Style 4 SLC

26 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


NFPA Style 6 SLC SLC Circuits without Isolators

4.3 NFPA Style 6 SLC


NFPA Style 6 requirements can be met by using the diagram below.

Two-wire Addressable Detector

SLC Out

Addressable Module

SLC Return

B+ B– A– A+

SLC-style6.cdr
Control Panel
SLC

NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.

Figure 4.2 Basic NFPA Style 6 SLC

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 27


Section 5: SLC Circuits with Isolators

5.1 Overview
There are two isolator devices used to protect critical elements of the FlashScan-mode or CLIP-
mode SLC loop from faults on other SLC branches or segments.
• Fault Isolator Module M500XJ
• Isolator Detector Base B224BI
A Fault Isolator Module on both sides of a device, or the combination of an Isolator Base and
Isolator Module are required to comply with NFPA Style 7 requirements.

CAUTION:
! If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected
between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum
number of addressable devices that can be connected between Isolators is reduced to seven.
Isolator modules will not function properly when these limits are exceeded. IFC-300 or IFC-400 The
address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of
200 when the Isolator Modules and/or Isolator Bases are connected to the SLC loop from the IFC-
320/E/C, IFC2-640/E, IFC-640/E, IFC2-3030, IFC-3030, or IFC-200.

5.2 Fault Isolator Module


The M500XJ module continuously monitors the circuit connected to terminals 3(–) and 4(+). Upon
powerup, an integral relay is latched on. The module periodically pulses the coil of this relay. A
short circuit on the SLC resets the relay. The module detects the short and disconnects the faulted
SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the
faulted branch from the remainder of the loop preventing a communication problem with all other
addressable devices on the remaining branches (labeled “Continuation of the SLC” in the figure
belowFigure 5.1). During a fault condition, the control panel registers a trouble condition for each
addressable device which is isolated on the SLC segment or branch. Once the fault is removed, the
module automatically reapplies power to the SLC branch or segment.

5.2.1 Wiring an Isolator Module


Figure 5.1 shows a Style 4 example for wiring of an Isolator Module.
Continuation
of the SLC

IN
IN

OUT
OUT
SLC-isowire.cdr

SLC Isolated branch


of the SLC

Figure 5.1 Wiring the M500XJ Module

28 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Isolator Detector Bases SLC Circuits with Isolators

5.3 Isolator Detector Bases


Isolator detector bases prevent an entire communications loop from being disabled when a short
circuit occurs. This is accomplished by isolating that part of the loop containing the short from the
remainder of the circuit. These bases also automatically restore the entire loop when the cause of
the short circuit is corrected.
B224BI is an intelligent isolator base used with FlashScan® detectors and most CLIP mode
detectors.

5.3.1 How an Isolator Base Works


If a short circuit fault occurs at point “X”, devices A, B, C & detector 2 will cease to function and
display a trouble warning at the control panel. Devices D, E, F & detectors 1, 3, 4, and 5 will
remain normal as they are served by ‘SLC Return’.
If a short circuit fault occurs at point “Y”, all devices will continue to function.
If a short circuit fault occurs at point “Z”, only detector 4 will cease to function.

Detector 1 X Detector 2

Y
Detector 5 Z

Detector 4 Detector 3
SLC Out SLC Return

SLC-isowork.wmf
Control Panel
Isolator Base Non-Isolating Device Short-circuit path

NOTE: For information on wiring an isolator base, refer to Figure 9.3, “Wiring an Isolator Base”
on page 50.

Figure 5.2 Isolator Base Circuit: Sample Style 6 Wiring

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 29


SLC Circuits with Isolators NFPA Style 4 SLC Using Isolator Modules

5.4 NFPA Style 4 SLC Using Isolator Modules


A variation of a Style 4 operation using isolator modules to protect each branch of the SLC. Refer
to Figure 5.1 on page 28 for M500XJ wiring and to Section 5.1, “Overview” for limitations.

Isolator Module
Two-wire Addressable Detector
Isolated Branch

Isolator Module

Isolated Branch

Addressable Pull Station

Isolator Module

Isolated Branch

B– B+

SLC-style4iso.cdr
Control Panel
SLC

Figure 5.3 NFPA Style 4 SLC Using M500XJ Modules

30 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


NFPA Style 6 SLC Using Isolator Modules SLC Circuits with Isolators

5.5 NFPA Style 6 SLC Using Isolator Modules


A variation of Style 6 operation using isolator modules to protect a section of the SLC. By flanking
each group of devices with M500XJ fault isolator modules each group is protected from faults that
may occur in the other groups. For example, a fault in Section B will not affect Sections A & C.
The isolator modules on either side of Section B will open the loop. Section A will still operate
from power on the SLC Out side and Section C will operate from the SLC Return side.
• A combination of isolator modules and isolator bases may be used.
• T-tapping is NOT allowed within the Style 6 configuration.
• Isolator modules shall be within 20 ft. (6.1 m) of device and the wire must be enclosed in metal
conduit.

Isolator Isolator
Module Module

Section B

Two-wire
Addressable Section C
Detector

Addressable
Pull Station

Section A

Additional isolator module required when first device in the


section is more than 20 feet from the control panel.
Isolator Isolator
Module Module

The first isolator module on SLC Out and SLC Return is


Isolator optional for IFC-320, IFC2-640/E, IFC-640/E, IFC-300, IFC- Isolator
Module 400 and IFC-3030/IFC2-3030 because the panels provide Module
the functionality.

SLC Out SLC Return

IFC-200, IFC-1010/IFC-2020: The first


SLC-style6iso.cdr

isolator module on SLC Out and SLC


Return must be contained within the same
enclosure as the FACP, or these isolator Control Panel
modules must be connected within 20 ft.
(6.1 m) of the FACP enclosure in conduit.

Figure 5.4 NFPA Style 6 SLC Using Isolator Modules

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 31


SLC Circuits with Isolators NFPA Style 7 SLC Using an Isolating Device

5.6 NFPA Style 7 SLC Using an Isolating Device


Style 7 operation requires using a combination of isolator detector bases and isolator modules or
isolator modules before and after a non-isolator device. Flanking each device with an isolator
provides fault protection to all other devices on the loop.
• T-tapping is NOT allowed within the Style 7 wiring configuration.
• When a non-isolator base or pull station is used, install isolator modules on both sides of
devices.
• When an isolator base is used in conjunction with an isolator module, install the isolator
module as shown in Figure 9.3.
• There must be a close-nipple connection between a device and the isolator bases or modules
that protect it.

Isolator
Module

Two-wire Isolator
Detector Base

Isolator Isolator
Module Module

Addressable
Pull Station
Addressable
Detector

Isolator Isolator
Module Module

The first isolator module on SLC Out and SLC Return is


optional for IFC-320, IFC2-640/E, IFC-640/E, IFC-300,
Isolator IFC-400 and IFC-3030/IFC2-3030 because the panels Isolator
Module provide the functionality. Module
SLC Out SLC Return

IFC-200, IFC-2020/IFC-1010: The first


isolator module on SLC Out and SLC
Return must be contained within the
same enclosure as the FACP, or these
isolator modules must be connected
SLC-style7iso.cdr

within 20 ft. (6.1 m) of the FACP


enclosure in conduit.
Control Panel

NOTE: See Figure 9.3, “Wiring an Isolator Base” on page 50.

Figure 5.5 NFPA Style 7 SLC

32 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Section 6: Monitor Modules

6.1 Description
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as NFPA Style B (Class B) or Style D (Class A) Initiating Device
Circuits (IDC). There is no limit to the number of contact-type devices installed on a monitor
module IDC.
For more information on the individual module specifications refer to the Installation Instructions
that are provided with this device. For information on transponders, refer to the specific
transponder manual.

6.1.1 Addressable Monitor Module


M300MJ is an addressable modules that monitors either a Style B (Class B) or Style D (Class A)
IDC of dry-contact input devices. This module is capable of participating in degraded mode where
supported by the FACP.

SLC–
IDC Return – Rotary
SLC+
Switches
IDC Return +
IDC Out +
IDC Out –

FMMtpH.wmf
Areas used to record the device
address and SLC number.

Figure 6.1 M300MJ Monitor Module

6.1.2 Zone Interface Module


M302MJ is similar to the M300MJ, except it is used to monitor compatible two-wire, 24 volt,
conventional (non-addressable) smoke detectors on a Style B (Class B) or Style D (Class A) IDC.

24 VDC –
24 VDC + SLC–
Rotary
IDC Return – SLC+ Switches
IDC Return +
IDC Out +
IDC Out –
FZMtpH.wmf

Areas used to record the device


address and SLC number.

Figure 6.2 M302MJ Zone-interface Module

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 33


Monitor Modules Description

6.1.3 Dual Monitor Module


M300DJ is similar to the M300MJ, except intended for use in intelligent two-wire systems
providing two independent Style B (Class B) IDCs at two separate, consecutive addresses.

Rotary
Switches
9 H–
Address +1 { 8 H+ SLC–

SLCDualMod-simplified.wmf
7L+ SLC+
Base Address { 6L–

Areas used to record the device


address and SLC number.

Figure 6.3 Dual Monitor Module

6.1.4 Miniature Monitor Module


M301MJ is intended to monitor a Style B (Class B) IDC; it is offered in a smaller package for
mounting directly in the electrical box of the device being monitored.

Rotary 14 15 0 1 ADDRESS 0 1 Label – Use to record the


Switches
13
12
2
3
2
3
device address and SLC
LOOP
11 4 4 number.
10 5 5
9 8 7 6 9 8 7 6
TENS ONES

IDC (+) Violet SLC (+) Red

SLC (-) Black

FMM-101.cdr
IDC (-) Yellow

Figure 6.4 Miniature Monitor Module

6.1.5 M300MJ-4-20 4-20mA Monitor Module


M300MJ-4-20 is intended for use in intelligent, two-wire systems, allowing Control Panels to
interface and monitor two-wire or three-wire sensors with a 4-20mA signal output.

Non-Resettable
{24 VDC (-)
24 VDC (+) SLC (-)

{
(-) SLC (+)
To 4-20mA Rotary Switches
Sensing Device Sense
(+)

T9 is only used in three-wire


sensor applications. For two-
wire applications, T8 is used
for negative (-) wiring.
Area used to record the device
address and SLC number.

Figure 6.5 M300MJ-4-20 4-20mA Monitor Module

34 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Setting an SLC Address for a Module Monitor Modules

6.2 Setting an SLC Address for a Module


FlashScan capable control or relay modules, as well as detectors, can be set to one of 159 addresses
(01-159) and are factory preset with an address of “00”. CLIP mode detectors and panels are
limited to addresses 01-99.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to
the desired address. The unit shown in Figure 6.6 is set at address “35”. When finished, mark the
address on the module face in the place provided.

SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Breakaway Tab - Modules come
with a raised breakaway tab on the
TENS rotary switch. This tab must
be removed when the module is on
an FACP that uses more than 99
Type H Rotary addresses.
Switches

Type V Rotary
Switches
Dual monitor modules: On dual monitor modules, only even
numbers appear on the ONES rotary switch. The module takes
both the selected address and the next-higher address.

Figure 6.6 Setting SLC Address on Module

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 35


Monitor Modules NFPA Style B IDC Using Monitor Modules

6.3 NFPA Style B IDC Using Monitor Modules


Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Each M300MJ module takes one
address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 6.7 shows typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the M300MJ monitor module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.
4. See “Power Considerations” on page 53 for information on supervising 24 VDC power.

From Supply

24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable
Manual pull
station

To Next IDC
or
47K ELR
Supervision Device
(supplied
with module)
SLC
Heat
detector
SLC-idcB1tpH.wmf

IDC

Figure 6.7 Typical Style B IDC Wiring with M300MJ

36 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


NFPA Style D IDC Using Monitor Modules Monitor Modules

6.4 NFPA Style D IDC Using Monitor Modules


Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each M300MJ module takes one address on the SLC. Use the rotary switches on the module to set
it to the required SLC address.
Figure 6.8 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC
using the M300MJ module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.
4. See “Power Considerations” on page 53 for information on supervising 24 VDC power.

From
Supply

24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable

Manual pull
station

To Next IDC
or
Supervision Device

SLC

Heat
detector SLC-idcD1tpH.wmf

IDC

Figure 6.8 Typical Style D IDC Wiring with M300MJ

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 37


Monitor Modules NFPA Style B IDC Using Dual Monitor Modules

6.5 NFPA Style B IDC Using Dual Monitor Modules


Connect the SLC wiring to the M300DJ module terminals 1 (–) and 2 (+).
Use the rotary switches on the module to set it to the required SLC address. Each dual module takes
two addresses on the SLC. Circuit ‘L’ corresponds to the address set on rotary switches. Circuit ‘H’
will automatically respond at the next higher address. The Circuit L “base address” is always an
even number; the lowest possible address is 02. The Circuit H “base + 1” address is always odd.
Use caution to avoid duplicate addressing of modules on the system.
Each IDC (H & L) is power limited to 230 microamps @ 24 VDC.
Figure 6.9 shows typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the M300DJ dual monitor.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.

Manual
Pull
Station

47K
ELR 47K
ELR
SLC
Heat
Detector
M300DJ

Base +1 Address
SLC-idcB3fdm1.wmf

Base Address (IDC Circuit H)


(IDC Circuit L)

Figure 6.9 Typical Style B IDC Wiring with M300DJ

38 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


NFPA Style B IDC Using Zone Interface Modules Monitor Modules

6.6 NFPA Style B IDC Using Zone Interface Modules


Connect the SLC wiring to the M302MJ module terminals 1 (–) and 2 (+). Each module takes one
address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 6.10 shows typical wiring for a supervised and power-limited NFPA Style B (Class B) IDC
using the M302MJ module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.

24 VDC Resettable power.


90 mA External 24 volt supply required
(Non-resettable power may be used for IFC-
320/E/C, IFC2-640/E, IFC-640/E, IFC2-3030,
Two-wire or IFC-3030 when operating in FlashScan
smoke mode.)
detectors
3.9K ELR
(supplied with module)
SLC

M302MJ

IDC SLC-idcB2tpH.wmf

Figure 6.10 Typical Style B IDC Wiring with M302MJ

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 39


Monitor Modules NFPA Style D IDC Using Zone Interface Modules

6.7 NFPA Style D IDC Using Zone Interface Modules


Connect the FlashScan SLC wiring to the M302MJ module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address.
Figure 6.11 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC
using the M302MJ zone interface modules.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.

24 VDC Resettable power.


90 mA External 24 volt supply required
(Non-resettable power may be used for
Two-wire IFC-320/E/C, IFC2-640/E, IFC-640/E,
smoke IFC2-3030, or IFC-3030 when operating in
detectors FlashScan mode.)

SLC

M302MJ

IDC

SLC-idcD2tpH.wmf
3.9K ELR
(supplied with module)

Figure 6.11 Typical Style D IDC Wiring with the M302MJ

Figure 6.12

40 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Section 7: Control Modules

7.1 Description
The M300CJ module is an addressable module that can be used for monitoring and switching 24
VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z
(Class A) circuits. It can also be used for audio/voice applications and fire-fighters telephone; these
two types of applications are documented separately. For UL 9th edition audio applications, refer to
the Digital Voice Command Manual and the Digital Audio Amplifiers Manual. For UL 8th edition
audio applications, refer to the Voice Alarm System Manual or FireVoice 25/50 Manual. The
module has a resistor on the back (refer to Figure 7.2) that must be removed when it is used on an
FFT-7 or FFT-7S telephone circuit.
The M300CJ-REL is an addressable module used to switch an external power supply to a solenoid.
The M300CJ-REL can be configured for NFPA Class B or Class A wiring. When using the
M300CJ-REL for Class B applications, remove jumper J1 (refer to Figure 7.4) on the back.
Refer to the Device Compatibility Document for a list of compatible UL Listed Fire Alarm
Releasing Solenoids. For more information on the module specifications refer to the Installation
Instructions provided with these devices.

„ Setting an SLC Address


Each module is factory preset with an address of “00.” To set an SLC address refer to “Setting SLC
Address on Module” on page 35.

7.2 Wiring a NAC with Addressable Control Modules


Figure 7.1 and Figure 7.2 show the connections to wire the M300CJ module for powering a 24
VDC NAC.

24 VDC Nonresettable Power (–)*


24 VDC Nonresettable Power (+)* SLC (–)
Style Z NAC (+) SLC (+)
Style Z NAC (–)
Style Y/Z NAC (–)
Style Y/Z NAC (+) SLCModule-simplified.wmf
NOTE:
• Module polarities are shown in alarm condition.
• *Can also be used in audio/voice and fire-fighters
telephone applications (70.7 VRMS max audio or
telephone); refer to the Voice Alarm System
Manual, FireVoice 25/50 Manual or DVC Manual
as appropriate for your equipment.

Figure 7.1 M300CJ Wiring Connections

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 41


Control Modules Wiring a NAC with Addressable Control Modules

Rear View Jumper J1 must be removed when using the M300CJ


on an FFT-7 or FFT-7S telephone circuit (see the
Voice Alarm System Manual, FireVoice 25/50 Manual
or DVC Manual as appropriate for your equipment) and
when supervising 24VDC NAC power using the
no-relay alternative wiring (see Appendix A.2.3, “Using
the Addressable Control Module Without Relay”).

Prying tool

FCMBackJump.wmf, FCMBackJumpcl.wmf
To remove J1 from the:
1. Insert a small prying tool, such
as a screwdriver or probe,
behind J1.
2. Using the tip of the prying tool,
slide J1 toward the rear of the so
J1 that it exits from the slot in the
back.

NOTE: When using IFC-3030/IFC2-3030 and the Control type ID, do not remove jumper J1.

Figure 7.2 M300CJ Top and Rear View - Jumper Location

7.2.1 Wiring a Solenoid with the M300CJ-REL


Figure 7.3 shows the connections to wire the M300CJ-REL to a solenoid.

J1

24 VDC (-)
SLC (-) When using the
24 VDC (+)
M300CJ-REL for Class B
Solenoid A (-) SLC (+) applications, remove jumper
Solenoid A (+) J1.
Solenoid B/A (+)
Solenoid B/A (-)

M300CJ-REL M300CJ-REL
Wiring Connections Rear View - Jumper Location

Figure 7.3 M300CJ-REL Wiring Connections and Rear View - Jumper Location

NOTE: The M300CJ-REL will not function on an SLC loop that is programmed for CLIP mode.

42 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules Control Modules

7.3 Wiring a Style Y NAC (Two-Wire) with Addressable


Control Modules
A supervised and power-limited NFPA Style Y (Class B) Notification Appliance Circuit (NAC)
using the M300CJ module. Polarized alarm notification appliances are shown connected to the
module in a two-wire configuration.
1. See “Power Considerations” on page 53 for information on monitoring 24 VDC power.
2. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
3. A power supervision relay is required only on the last module of the power run.
(IFC-3030 only: If using one of the IFC-3030’s FlashScan type IDs that provide built-in power
supervision, no relay is required.)
4. Do not Tap or branch a Style Y circuit.
5. Terminate the circuit across the last device using a UL-listed End-of-Line Resistor 47K,
1/2-watt, SSD P/N A2143-00 (ELR-47K in Canada).
6. Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
7. Refer to Device Compatibility Document for compatible notification appliances and relays.
SLC
24 VDC Nonresettable power

A power supervision
relay is required only on
the last module of the
ELR power run. (only: If
24 VDC Notification using one of the’s
47K, 1/2-watt
Appliances FlashScan type IDs that
provide built-in power
supervision, no relay is
required.)

SLC-nacY.wmf
NAC

Module polarities are shown in alarm condition

Figure 7.4 NFPA Style Y Notification Appliance Circuit

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 43


Control Modules Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules

7.4 Wiring a Style Z NAC (Four-Wire) with Addressable


Control Modules
A supervised and power-limited NFPA Style Z (Class A) Notification Appliance Circuit (NAC)
using the M300CJ module. Polarized alarm notification appliances are shown connected to the
module in a four-wire configuration.
1. See “Power Considerations” on page 53 for information on supervising 24 VDC power.
2. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
3. A power supervision relay is required only on the last module of the power run.
(IFC-3030 only: If using one of the IFC-3030’s FlashScan type IDs that provide built-in power
supervision, no relay is required.)
4. Do not T-Tap or branch a Style Z circuit.
5. Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
6. Refer to the Device Compatibility Document for compatible notification appliances and relays.

24 VDC Nonresettable power SLC

24 VDC
notification
appliances

NAC Return
A power supervision relay
is required only on the last
NAC Out module of the power. (only:

SLC-nacZtpH.wmf
If using one of the’s
FlashScan type IDs that
provide built-in power
supervision, no relay is
Module polarities are shown in Alarm. required.)

Figure 7.5 NFPA Style Z Notification Appliance Circuit

44 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Connecting a Releasing Device to the Addressable Control Module Control Modules

7.5 Connecting a Releasing Device to the Addressable


Control Module
The M300CJ-REL module can control 1 A of current. Make sure to keep total system current
within the limits of the power supply. You can power the module from the power supply of the
Control Panel or any UL 864-listed 24 VDC regulated power-limited power supply for Fire
Protective Signaling. For more information, refer to the Device Compatibility Document.

NON-RESETABLE 24 VDC
POWER SUPPLY ISOLATED,
REGULATED, POWER LIMITED
PER NFPA 70. LISTED FOR
FIRE PROTECTION WITH (-)
BATTERY BACKUP.
SLC (-)
Module polarities are shown in alarm condition. (+)
All wiring shown is supervised and power-limited. SLC (+)

Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.

M300CJ-REL

Figure 7.6 NPFA Class B Wiring of the M300CJ-REL

NON-RESETABLE 24 VDC
POWER SUPPLY ISOLATED,
REGULATED, POWER LIMITED When using the
PER NFPA 70. LISTED FOR M300CJ-REL for Class B
FIRE PROTECTION WITH applications, remove jumper J1.
BATTERY BACKUP.
Module polarities are shown in alarm condition.
All wiring shown is supervised and power-limited. (-)
(+)
SLC (-)
SLC (+)

Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.
M300CJ-REL

Figure 7.7 NPFA Class A Wiring of the M300CJ-REL

Critical Requirements. When connecting a releasing device to the M300CJ-REL module, note
the following:
1. See “Power Considerations” on page 52 for information on monitoring 24 VDC power.
2. Do not T-tap or branch a Style Y or Style Z circuit.
3. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the M300CJ-
REL.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 45


Control Modules Connecting a Releasing Device to the Addressable Control Module

4. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of
connections.
5. All applications using the M300CJ-REL are power-limited:
a. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
b. Circuits are supervised against opens and shorts.
6. Refer to your FACP’s Programming Manual for instructions on setting the Soak Timer.
The M300CJ-REL module must be programmed with the correct releasing type code listed in your
FACP’s Programming Manual.

46 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Section 8: Relay Module

8.1 Description
The M300RJ module is an addressable module that provides two isolated sets of Form-C relay
contacts.
Ratings for the dry relay contacts on a Form-C module are:
• Resistive – 2 amps @ 30 VDC (e.g. Electronic devices and strobes)
• Inductive – 1 amp @ 30 VDC (0.6pF) (e.g. Mechanical bells and horns)
• Pilot Duty – 0.5 amp @ 125 VAC (0.35pF) (e.g. Using a smaller relay to trip another relay)
For more information on the module specifications refer to the Installation Instructions provided
with this device. For information on transponders, refer to the specific transponder manual.

„ Setting an SLC Address


Each relay module is factory preset with an address of “00.” To set an SLC address refer to
Section 6.2, “Setting an SLC Address for a Module”, on page 35.

8.2 Wiring the Addressable Relay Module (Form-C Relay)


The figure below shows the M300RJ module wired to the Control Panel.
SLC

C
NC
NO
C
NC NO
SLC-frmCtpH.wmf

Figure 8.1 Relay Module Wiring Connections

Figure 8.2

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 47


Section 9: Intelligent Detector Bases

9.1 Description
The B501J and B210LPJ Detector Bases, the B224RB plug-in relay detector base, and the
B501BH sounder base provide the connection between the SLC and a variety of intelligent
detectors. Use the B501B-FTXJ Detector Base with all HARSH™ detectors.
For more information refer to the Installation Instructions documents provided with these devices.

„ Setting the Detector Address


Each intelligent detector head is factory preset with an address of “00.” To set an SLC address refer
to “Setting an SLC Address for a Module” on page 35.

9.2 Wiring a Detector Base


Figure 9.1 shows typical wiring of the B210LPJ or B501J detector base connected to an SLC. An
optional RA400Z Remote LED Annunciator is shown connected to the base.

SLC

Use a female disconnect


to wire the RA400Z (–) to
Terminal 1 (–).

To next device
on SLC

B501 only: For connection of


cable shield

RA400Z
SLC-B501wire.wmf

Remote LED
Annunciator
(Optional)

NOTE: The B210LPJ base wiring is identical to the B501J, except there is no shield terminal.

Figure 9.1 Wiring of the B501J Detector Base

48 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Wiring a Detector Base Intelligent Detector Bases

Figure 9.2 shows typical wiring of the B501B-FTXJ detector base (for use with a HARSH™
detector) connected to an SLC. An optional RA400Z Remote LED Annunciator is shown
connected to the base.

SLC
To next device
on SLC

For connection of
cable shield

Power to next
To compatible device
UL Listed
Power Supply

RA400Z
Remote LED
Annunciator
(Optional)
B710HD.wmf

NOTE: Use a spade lug to wire the Remote LED Annunciator (–) to Terminal 2 (–).

Figure 9.2 Wiring of the B501B-FTXJ Detector Base

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 49


Intelligent Detector Bases Wiring an Isolator Base

9.3 Wiring an Isolator Base


The Isolator Base will isolate its detector from short circuits that occur on the SLC connected at
terminals 3 and 2. It will not isolate its installed detector from short circuits that occur on the SLC
connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during a short
circuit is not acceptable, and an isolator module must be installed as shown in the figure below.
SLC Out

SLC In

Conduit

SLC-224BIwire.wmf
M500XJ
Isolator Module

Figure 9.3 Wiring an Isolator Base

9.4 Wiring a Relay Base


Figure 9.4 shows typical wiring of the B224RB plug-in relay detector base connected to an SLC.

To next device
on SLC
For connection of
cable shield

3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf

Figure 9.4 Wiring of the B224RB Plug-in Relay Detector Base

50 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Wiring a Sounder Base Intelligent Detector Bases

9.5 Wiring a Sounder Base


Figure 9.5 shows typical wiring of the B501BH, and B501BHT sounder bases.

OUT
+4 –5

4 5

3 21

IN External supply
-3 – 2 +1

Class A Optional Wiring


Intelligent
Monitor
Optional Sounder Interconnect* Module
SLC B+
UL-listed
Compatible
FACP UL-listed
EOL
SLC B- Resistor
47K

(-) Power
External (+) Power

B501BHWiring.wmf
24V
Supply
UL-listed
Class A Optional Wiring EOL Relay
24V

*Grouping of up to 6 model B501BHT temporal tone sounder bases.

Figure 9.5 Wiring of the B501BH/B501BHT Sounder Bases

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 51


Section 10: Addressable Manual Pull Station

10.1 Description
The JBG-12LX is an addressable manual pull station with a key-lock reset feature.
For more information refer to the Installation Instructions document provided with the devices.

„ Setting an SLC address


Each unit is factory preset with an address of “00.” To set an SLC address refer to “Setting an SLC
Address for a Module” on page 35.

10.2 Wiring a Manual Pull Station


Typical wiring for the JBG-12LX Manual Pull Station to an SLC.

To next device
+ on SLC
SLC +

US PAT 444 0991

SLC-nbg12.cdr

Figure 10.1 Wiring the JBG-12LX Pull Station to an SLC

52 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Appendix A: Power Considerations

A.1 Supplying Power to 24 VDC Detectors and NACs


Resistance and Size
To determine the maximum allowable resistance that can be tolerated in supplying power to
24 VDC four-wire devices and NACs, use the calculations below. These simplified equations
assume that the devices are at the end of a long wire run. With the computed resistance and using
the manufacturers specifications for the desired wire, select the proper gauge wire for the power
run.
For Four-Wire Detectors:
(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)

For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)

Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage (see Table A.1 below)
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in
alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated

NOTE: This simplified equation assumes that the devices are at the end of a long wire run.

The minimum supply voltages produced by Johnson Controls power supplies are listed below:
FACP Vms Power Supply Vms
IFC-200 19.4 FCPS-24/E 19.1
IFC-640/E 19.15 FCPS-24S6/FCPS-24S8 19.1
KAPS-24 on IFC2-640 or 20.16V MPS-24A/E 19.6
IFC-320
MPS-24B/E 20.1
MPS-400 19.23
ACPS-2406/E 19.8
AMPS-24/E 20.27
ACPS-610/E 19.4

Table A.1 Minimum Supply Voltage

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 53


Power Considerations Supervising 24 VDC Power

A.2 Supervising 24 VDC Power


There are options for supervising 24 VDC power, as discussed below.
• Using FlashScan Type Codes with Built-In Power Supervision (IFC-3030 only)
• Power Supervision Relay
• Using the M300CJ module without relay

A.2.1 Using Type Codes with Built-In Power Supervision on


IFC-3030
Certain FlashScan type codes have external power supervision built into the software. For details,
refer to “Devices Requiring External Power Supervision” in the appropriate installation manual.

A.2.2 Power Supervision Relay


Power used to supply 24 VDC detectors, notification appliances (using the M300CJ) and two wire
detectors (using the M302MJ) can be supervised with a power supervision relay. This relay,
energized by the 24 VDC power itself, is installed at the end of each respective power run and
wired in line with the supervised circuit of any intelligent module.
When power is removed from the relay, the normally closed contacts open the supervised circuit,
generating a trouble condition. Therefore, the relay needs to be installed at the end of the
supervised circuit, so as to not disrupt the operating capability of all the devices on that circuit. The
relay can be installed in line with any leg (+ or –) of the supervised NAC or IDC circuit, either a
two or a four-wire style.
See Figure A.1 and Figure A.2. Refer to the Device Compatibility Document for compatible
notification appliances and relays.

24 VDC Power from


Control Panel or
Power Supply
Last device on the SLC loop
(M300CJ or M302MJ)

Power Supervision
Relay
(EOLR-1)

SLC-psrtpH.cdr

Supervised NAC or IDC


ELR
(Use 47K with M300CJ
or 3.9K with M302MJ)

Figure A.1 Supervised 24 VDC Circuit

54 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Supervising 24 VDC Power Power Considerations

24 VDC Power from


Control Panel or Power Supply

M300CJ
ELR 47K

Power Supervision
Relay
(EOLR-1)

ELR 47K Supervised NAC or IDC

M300MJ

SLC-psr-2addresstpH.wmf
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 55


Power Considerations Supervising 24 VDC Power

A.2.3 Using the Addressable Control Module Without Relay


An alternate method of supervising 24 VDC power fed to the Notification Appliance Circuit of the
M300CJ module eliminates the need for a power supervision relay. This method uses a Notification
Appliance Circuit from the control panel or power supply to supply power to the M300CJ modules.
The control panel supervises this circuit, which can be either a Style Y or Style Z.
Style Y NAC Power Wiring
Program the NAC from the control panel for general alarm. (Refer to the programming manual or
programming section of the FACP documentation for instructions.) Note that if the NAC is a coded
output, the M300CJ output will be coded as well.
Refer to the Device Compatibility Document for compatible notification appliances.
• The circuit is supervised and power-limited.
• In this circuit, an external ELR is required at end of the NAC circuit.
• Refer to the respective control panel installation manual for NAC terminal block connection
information and ELR value.
• Remove internal resistor on each M300CJ (see instructions in Figure 7.2 on page 42).
Connect the NAC power as follows:
NAC Terminal Block (24 VDC)
M300CJ

Circuit supervised
by control panel

M300CJ

SLC-nacY1tpH.wmf

Note: Drawing shows power wiring


only; SLC Wiring not shown.

Figure A.3 NFPA Style Y NAC Power (Alternate)

56 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Supervising 24 VDC Power Power Considerations

Style Z NAC Power Wiring (Alternate)


Program the NAC from the control panel for general alarm. (Refer to the programming manual or
programming section of the FACP documentation for instructions.) Note that if the NAC is a coded
output, the M300CJ output will be coded as well.
Refer to the Device Compatibility Document for compatible notification appliances.
• The circuit is supervised and power-limited.
• In this circuit, an external ELR is not required at end of the NAC circuit.
• Refer to the respective control panel installation manual for NAC terminal block connection
information.
• Remove internal resistor on each M300CJ (see instructions in Figure 7.2 on page 42).
Connect the NAC power as follows:
NAC Terminal Block
(24 VDC)

M300CJ

Circuit supervised
by control panel

M300CJ

SLC-nacZ1tpH.wmf
Note: Drawing shows power wiring
only; SLC Wiring not shown.

Figure A.4 NFPA Style Z NAC Power (Alternate)

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 57


Appendix B: SLC Surge Suppression

B.1 Introduction
There are one primary and three secondary UL–listed surge protectors approved for use with the
FACPs listed in this appendix.
Primary Surge Protector:
• 326-2M TII Station Protector
Secondary Surge Protectors:
• DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL
33771 (800) 753-2345.
• SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
• PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119

NOTE: For detailed information refer to the installation documentation supplied with the unit.

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building.
• Install primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring
connected to the surge suppressor input may be routed outside the building as shown below.

Building #2 Building #1

P P
FACP
P = Primary
S = Secondary S

P P S
SLC-ssbuild1.cdr

Surge Suppressor

58 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Installation SLC Surge Suppression

B.2 Installation
Mounting of the secondary surge suppressor must be inside the FACP enclosure or in a separate
enclosure listed for fire protective signaling use.
• Locate on an available stud and secure with nut.
• Unit is connected in series with the SLC Loop to protect the Control Panel.
• Provide a common ground to eliminate the possibility of a differential in ground potentials.

B.2.1 IFC-200
DTK-2LVLP-F Connections
2LVLP-F

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block

2LVLP-F


+

SLC-lvlp1.cdr
SLC Loop
IN OUT

PLP-42N Connections
PLP-42N
GRND
L4

L4

Optional Four-wire Return Loop


OUTPUT
L3
INPUT

L3

Style 6 (Class A)
L2

L2
L1

L1

SLC Terminal Block


PLP-42N


GRND
L4

L4

+
OUTPUT
L3
INPUT

L3
L2

L2

SLC-plpn1.cdr

SLC Loop
L1

L1

NOTE:

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 59


SLC Surge Suppression Installation

SLCP-30 Connections
SLCP-30

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block
SLCP-30
SLC Loop

+

SLC-slcp1.cdr
IN OUT

B.2.2 IFC-300, IFC-400


DTK-2LVLP-F Connections
2LVLP-F

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT

SLC Terminal Block


2LVLP-F

+

SLC-lvlp2.cdr
SLC Loop
IN OUT

PLP-42N Connections
PLP-42N
GRND
L4

L4

Optional Four-wire Return Loop


OUTPUT
L3
INPUT

L3

Style 6 (Class A)
L2

L2
L1

L1

PLP-42N SLC Terminal Block

+
GRND
L4

L4


OUTPUT
L3
INPUT

L3
L2

SLC-plpn2.cdr
L2

SLC Loop
L1

L1

NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection

60 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Installation SLC Surge Suppression

SLCP-30 Connections
SLCP-30

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT

SLCP-30 SLC Terminal Block


SLC Loop
+

SLC-slcp2.cdr
IN OUT

B.2.3 IFC-1010 & IFC-2020 (JLIB-200A or JLIB-400)


DTK-2LVLP-F Connections
2LVLP-F

– SLC Terminal Block


+
SLC Loop

+
Optional Four-wire

SLC-lvlp3.cdr
Return Loop IN OUT
Style 6 (Class A)

NOTE: Do not connect shield (if present) to surge protector or fire panel.

PLP-42N Connections
PLP-42N

SLC Terminal Block


GRND
L4

L4
OUTPUT
L3
INPUT

L3

SLC Loop
L2

L2
L1

L1

SLC-plpn3.cdr

Optional Four-wire
Return Loop
Style 6 (Class A)

NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection. Do not connect shield (if present) to surge protector or fire panel.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 61


SLC Surge Suppression Installation

SLCP-30 Connections
SLCP-30

– SLC Terminal Block


+
SLC Loop –
+

SLC-slcp3.cdr
Optional Four-wire
Return Loop IN OUT
Style 6 (Class A)

NOTE: Do not connect shield (if present) to surge protector or fire panel.

B.2.4 IFC-640/E, IFC-3030/IFC2-3030


DTK-2LVLP-F Connections
2LVLP-F

– SLC Terminal Block


+
SLC Loop

+
Optional Four-wire

SLC-lvlp3.cdr
Return Loop IN OUT
Style 6 (Class A)

NOTE: Do not connect shield (if present) to surge protector or fire panel.

PLP-42N Connections
PLP-42N

SLC Terminal Block


GRND
L4

L4
OUTPUT
L3
INPUT

L3

SLC Loop
L2

L2
L1

L1

SLC-plpn3.cdr
Optional Four-wire
Return Loop
Style 6 (Class A)

NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection. Do not connect shield (if present) to surge protector or fire panel.

SLCP-30 Connections
SLCP-30

– SLC Terminal Block


+
SLC Loop –
+
SLC-slcp3.cdr

Optional Four-wire
Return Loop IN OUT
Style 6 (Class A)

NOTE: Do not connect shield (if present) to surge protector or fire panel.

62 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Appendix C: Terminal Conversion Charts for V-type
and H-type Devices

C.1 M300RJ

Common 2 SLC -
Closed 2 SLC - Common 2
Closed 2 SLC +
Open 2 SLC +
Common 1 Open 2
Closed 1 Common 1
Open 1 Closed 1 Open 1

Type V Type H

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Normally Open (1) 5

5 Normally Closed (1) 6

6 Relay Common (1) 7

7 Normally Open (2) 8

8 Normally Closed (2) 9

9 Relay Common (2) 10

N/A Unused 4

N/A Unused 11

Table C.1 M300RJ Terminal Conversions

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 63


Terminal Conversion Charts for V-type and H-type Devices M300CJ and M302MJ

C.2 M300CJ and M302MJ

Solenoid A- VDC -
Solenoid A+ SLC - VDC + SLC -
SLC + Solenoid A- SLC +
Solenoid B/A +
VDC - Solenoid A+
Solenoid B/A - Solenoid B/A +
VDC + Solenoid B/A -

Type V Type H

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 VDC - 11

4 VDC + 10

5 Unused 5

6 Solenoid B/A - 6

7 Solenoid B/A + 7

8 Solenoid A + 8

9 Solenoid A - 9

N/A Unused 3

N/A Unused 4

Table C.2 M300CJ and M302MJ Terminal Conversions

64 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


M300MJ Terminal Conversion Charts for V-type and H-type Devices

C.3 M300MJ

Class A Supervision -
Class A Supervision+ SLC - SLC -
Class A/B Supervision + SLC + Class A Supervision - SLC +
Class A/B Supervision - Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -

Type V Type H

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Unused 4

5 Unused 5

6 Class A/B Supervision - 6

7 Class A/B Supervision + 7

8 Class A Supervision + 8

9 Class A Supervision - 9

N/A Unused 10

N/A Unused 11

Table C.3 M300MJ Terminal Conversions

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 65


Appendix D: Canadian Versions of SLC Devices
Note: Only FlashScan/CLIP devices are listed for releasing applications.

UL-listed SLC Device ULC-listed SLC Device


2951TMJ (Acclimate™) 2951TMJA Intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection
(135°F/57.2°C). FlashScan capable.
FSB-200, FSB-200S FSB-200A, FSB-200SA Addressable, intelligent, single-ended beam smoke detector
with built-in sensitivity testing. FlashScan and CLIP mode.
1951J 1951JA Addressable, intelligent smoke detector that incorporates an
ionization sensing chamber. Designed to provide open area
protection. FlashScan capable.
2951J 2951JA Analog, addressable intelligent smoke detector that uses a
photoelectric sensing chamber. Listed for use in ducts.
Designed to provide open area protection. FlashScan
capable.
2951TJ 2951TJA Adds thermal sensors that will alarm at a fixed temperature
of 135°F (57°C).
5951J 5951JA Intelligent thermistor sensing circuit for fast response.
Designed to provide open area protection with 50 foot
spacing capability. A fixed temperature sensor with 135°F
fixed temperature alarm. FlashScan capable.
5951RJ 5951RJA Incorporates a thermal rate of rise of 15°F (9.4°C).
FlashScan capable.
5951HJ High temperature sensor with 190°F (87.8°C) fixed
temperature alarm.
DH300PL DH300PLA Photoelectric Duct Detector, Low-flow
DH300RPL DH300RPLA Photoelectric Duct Detector, Low-flow
FTX-P1J Smoke detector that provides early warning smoke
detection in hostile environments where traditional smoke
detectors are not practical. Discontinued.
FTX-P2J FTX-P2JA Smoke detector provides early warning smoke detection in
hostile environments where traditional smoke detectors are
not practical.
7251J Early detection laser detector, similar to the 7351J, but
limited to CLIP mode operation only. Discontinued.
7351JLow Profile Laser 7351JA An advanced intelligent photoelectric detector that uses a
Detector laser diode, special optics, and signal processing to obtain
extremely high sensitivity.
Bases
B210LPJ B210LPJA Standard U.S. Low-Profile base (6", 15.24 cm)
B501J B501JA Standard European flangeless base (4", 10.16 cm)
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includesB501J Sounder base with temporal
sounder (UL 8th Edition)
B501BH-2, B501BHT-2 B501BH-2A, B501BHT-2A Sounder base, includesB501J Sounder base with temporal
sounder (UL 9th Edition)
B224RB B224RBA Low Profile Intelligent relay base
B510B-FTXJ B510B-FTXJA Base for a hostile environment detector.
Monitor and Zone Interface Modules
M300MJ M300MJA Used for normally open contact alarm initiating devices,
such as manual pull stations, four-wire smoke detectors,
heat detectors, waterflow, and supervisory devices
M302MJ M302MJA Used to interface with two-wire smoke detectors in addition
to normally open contacts

66 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Canadian Versions of SLC Devices

UL-listed SLC Device ULC-listed SLC Device


M300DJ M300DJA (CLIP) Two independent 2-wire Initiating Device Circuits (IDCs) at
two separate, consecutive addresses. Wire supervised IDCs
as NFPA Style B (Class B) or Style D (Class A) circuits. The
modules come with a thermoplastic cover for mounting to a
4-inch (10.16 cm) square mounting box.
M301MJ M301MJA Functionally similar to the M300MJ Monitor Module, but
offered in a smaller package for mounting directly in the
electrical box of the device being monitored. (Class B input
circuit only.)
JBG-12LX JBG-12LXA An addressable manual pull station with key-lock reset
feature. The addressable module is housed within the pull
station.
Control Modules
M300CJ M300CJA Control Module, NAC: Addressable Control Module used as
Notification Appliance Circuits (NACs) to power and
supervise compatible, UL-listed notification appliances.
Wired supervised NACs as NFPA Style Y (Class B) or Style
Z (Class A). The modules come with a thermoplastic cover
for mounting to a 4-inch (10.16 cm) square mounting box.
M300RJ M300RJA Relay Control Module is similar to the M300CJ except used
as a Form-C control relay module.
Fault Isolator Module
M500XJ M500XJA The Fault Isolator Module protects the system against wire-
to-wire short circuits on the SLC. It should be placed
between groups of sensors in a Style 6 or Style 7 SLC to
isolate short- and open-circuit problems and protect the rest
of the loop so it can continue to operate normally. It is not
addressable, but listed here due to its use in an SLC
Multi-input/output modules
XPIQ XPIQ Quad Intelligent Audio Transponder - The XPIQ is an
integrated audio amplification and distribution subsystem
that can direct up to four low-level audio signals through four
audio amplifiers to integrated, continuously supervised
speaker circuits. An on-board power supply charges and
supervises battery backup.
XP6-C XP6-CA Controls six NAC or speaker/telephone circuits. (Not listed
for use in releasing applications.)
XP6-R XP6-RA Controls six Form-C relays.
XP10-M XP10-MA Supervises ten Class-B addressable Initiating Device
Circuits (IDC) which monitor normally open contact initiating
devices.
XP6-MA XP6-MAA Monitors six zones of conventional two-wire detectors.

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 67


Numerics–H

Numerics D
1251J 14 DC resistance 18
1351J 14 degraded mode 12, 33
1551J 14 detector bases
1951J 14 list of 13
2351J/2351TJ 14 see also isolator bases
2351TMJ 13 Detectors
24 VDC power 53–56 Detector bases 66
alternate method of supervising 56 listing 66
monitoring and switching NAC power 41 detectors
2951J/2951TJ 14 24 VDC 54
2951J-COPTIR 13 listing 14
2951TMJ 13 devices
3251J Discontinued December 1, 2001 addressable 28
5351J/5351RJ 14 auxiliary 13
5951J/5951RJ 14 isolator 28
7251J 14 maximum number between isolators 28
7351J 14 SLC capacity 15
supervised 54
A dry contact ratings 47
dry-contact 13
A77-716B DTK-2LVLP-F 58
Replaced by EOLR-1
dual monitor module 12, 34, 38
See power supervision relay
duplicate addressing 38
ACPS-2406 15
ACPS-2406/E 53
ACPS-610/E 14, 53 E
address capacity 28 electrical interference 17
addressable devices 28 End-of-Line-Resistor 43, 56, 57
addressable modules 12, 33 EOLR-1 See power supervision relay
Addressable Modules (Overview) 66
AMPS-24/E 15, 53 F
analog intelligent devices 11
auxiliary devices 13 FACP, see Fire Alarm Control Panels
factory preset 35
fault 15, 29, 31
B fault condition 28
B210LPJ 48 Fault Isolator Module, see isolator module
B224BI, see isolator bases FCPS-24 53
B501B-FTXJ 13, 48 Fire Alarm Control Panels 8, 58
B501J 48 Fire alarm service 36, 37, 38, 39, 40
bases 13 FlashScan 11, 16, 29
building entry/exit 58 floating segments 25
Form-C contacts 47
C Form-C relays 67
four-wire configuration 44
cabinet 23 FSB-200, FSB-200S 13, 66
circuit fault 12
circuit, speaker/telephone 12
CLIP (Classic Loop Interface Protocol) 11, 16 G
coded output 56, 57 general alarm 56, 57
common ground 59 ground terminal 60, 61, 62
communications loop 29 group poll 11
conduit, types of 23–25 grouped fashion 11
connector screw 23
connectors, crimp-on 60, 61, 62 H
control modules 12
HARSH™ 49
Control Modules (Overview) 67

68 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


I–O

I M302MJ, see zone interface module 33


M500FPJ 12
IDC, see Initiating Device Circuits
M500XJ, see isolator module
IFC-1010/IFC-2020 17, 18, 22
metal conduit 24, 31
IFC-200 18, 21
Miniature monitor module 34
IFC2-3030/IFC-3030 20
module circuits, configuring 33
IFC2-640/E 8
modules
IFC-300/IFC-400 18, 22
addressable 12
IFC-3030 17
control 12
IFC-320/E/C 8
h-type 65
IFC-640 17, 21
isolator 12
Initiating Device Circuits 12, 33–40
monitor 12
integral relay 28
relay 13
isolator bases 13, 28, 29, 32
v-type 65
how they work 29
monitor module 12, 33, 36
wiring 50
dual see dual monitor module
isolator devices 28
miniature, see miniature monitor module
isolator modules 12, 31, 32
zone interface see zone interface module
how they work 28
Monitor Modules (Overview) 66
wiring of 28
MPS-24A 53
MPS-24B 53
J MPS-400 53
JBG-12LX 52, 67 Multi-Input/Output Modules 67
JLIB-200 18 multiplex subsystem 13
JLIB-200A, JLIB-400 17, 22
junction box 24 N
NAC 12
K NAC power 41, 57
key-lock reset 52 wiring 56
NAC terminal block 56
L NEC Article 800 58
NFPA Style 4
LCM-320/LEM-320 17, 20
wiring 26
LED Annunciator, remote 48, 49
NFPA Style 6
LED operation 16
wiring 27
LEM-320
with isolator modules 31
on IFC2-3030/IFC-3030 20
NFPA Style 7 28
on IFC-3030, see LCM-320/LEM-320 with isolator device 32
on IFC-640 17, 21
NFPA Style B
local building code 58 IDC wiring 36, 38, 39
Loop Resistance 17, 18 NFPA Style D
Style 6 & 7 19 IDC wiring 37, 40
loops 20 NFPA Style Y 41
LPX-751/L 14 wiring 43
NFPA Style Z 41
M wiring 44
M300CJ 41, 43, 44, 45, 54, 56, 57 normally closed contacts 54
M300CJ-REL 12, 42 Notification Appliance Circuit 12, 56
M300DJ, see dual monitor module see also NAC
M300MJ 37 notification appliances 54
M300MJ, see monitor module 33
M300MJ-4-20 12, 34 O
Terminal Designations 34
Output relays
M300RJ, see Relay modules
Connections 67
M301MJ, see miniature monitor module
M302MJ, see zone interface module

Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 69


P–Z

P surge protector 11, 58


PLP-42N 58
Polling Protocols 11 T
power run 53, 54 telephone circuit 12
power supervision relay 43, 44, 54 terminal block, NAC 57
power supplies 14, 53 termination of shield 23
power-limited 56 transponders 13
proper gauge wire 53 trouble conditions 15, 28
pull stations 14, 32 trouble warning 29
addressable manual, wiring 52 T-tapping 18, 26, 27, 31, 32
twisted shielded pair wiring 17
Q twisted unshielded pair wiring 17
twisted-pair wire 24
Quad Intelligent Audio Transponder
two-wire configuration 43
see also XPIQ 67
two-wire detectors 54

R V
RA400Z 48, 49
VIEW® 14
ratings, dry contact 47
relay bases 13, 28
relay module 13, 47, 67 W
wiring 47 Waterflow alarm service, automatic and manual
Releasing Device 36, 37, 38, 39, 40
M300CJ Connections 45 wire length
remote switching center 13 four-wire SLC 20
RFX Wireless Interface two-wire SLC 19
(Discontinued as of Dec. 31, 2005) 14 wire nuts 24
rotary switches 8, 35, 38, 39, 40 wire size 17
wiring
S isolator bases 50
isolator modules 28
SDRF-751 14
NACs 56
Security service 36, 37, 38, 39, 40
pull stations 52
shield 62
relay modules 47
shield drain wire 23
SLCs 36, 37, 38, 39, 40
shielded wire 24
wiring pair 58
shield-termination 23
wiring style requirements 15
short circuit 28, 29
Signaling Line Circuit 11
see also SLC X
SLC XP Series Transponders 13
capacity of devices 15 XP5-C Transponder 12
performance 15 XP5-M Transponder 12
setting an SLC address 35 XP6-C, XP10-M, XP6-MA 67
terminal block 24 XP6-CA 67
trouble conditions 15 XPIQ (Overview) 67
wiring 36, 37, 38, 39, 40
SLCP-30 58
sounder bases 13, 28
Z
speaker circuit 12 zone interface module 12, 33, 39, 40
Sprinkler supervision 36, 37, 38, 39, 40
standard bases 13
Style 4, Style 6, Style 7, Style B, Style D, Style Y,
Style Z see NFPA Style 26
supervised circuits 54, 56
supervised devices 54
suppressors, surge 58

70 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009


Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009 71
Controls Group www.johnsoncontrols.com
507 E. Michigan Street
P.O. Box 423 Release G
Milwaukee, WI 53201 Printed in U.S.A.

You might also like