Pre-And Primary Treatment: Technical 6X9 /industrial Water Quality/Eckenfelder /866-1/chapter 3
Pre-And Primary Treatment: Technical 6X9 /industrial Water Quality/Eckenfelder /866-1/chapter 3
CHAPTER 3
Pre- and Primary
Treatment
3.1 Introduction
The objective of pre- and primary treatment is to render a wastewa-
ter suitable for discharge to a POTW (publicly owned treatment
works) or subsequent biological or physical chemical treatment.
Pretreatment of industrial wastewaters discharged to POTWs is a
major technical issue specifically regulated by EPA. This issue and
case histories are presented in Chap. 17. The concentrations of pol-
lutants that make prebiological treatment desirable are summarized
in Table 3.1. Pretreatment is often used to reduce or eliminate inhibi-
tion or toxicity to the biological process. It may also be used to ren-
der biorefractory organics more biodegradable through chemical
oxidation or other methods.
Some potential toxicants include heavy metals, pesticides, prior-
ity pollutants, and so on. Those found to be most significant of one
organic chemical manufacturing corporation are:
1. Surfactants
2. Cationic polymers
3. Free ammonia
4. Nitrite
5. Chlorine
6. Pesticides
7. Metals
8. Temperature
65
Downloaded from Digital Engineering Library @ McGraw-Hill ([Link])
Copyright © 2008 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
66 Chapter Three
Pollutant or System
Condition Limiting Concentration Kind of Pretreatment
Suspended solids >125 mg/L Sedimentation,
flotation, lagooning
Oil or grease >35 Skimming tank or
separator
Toxic ions Precipitation or ion
exchange
Pb ≤0.1 mg/L
Cu + Ni + CN ≤1 mg/L
Cr 6
+ Zn ≤3 mg/L
Cr 3
≤10 mg/L
pH 6 to 9 Neutralization
Alkalinity 0.5 lb alkalinity as Neutralization for
CaCO3/lb BOD removed excessive alkalinity
Acidity Free mineral acidity Neutralization
Organic load >2:1 Equalization
variation
Sulfides >100 mg/L Precipitation or
stripping with recovery
Ammonia >500 mg/L (as N) Dilution, ion exchange,
pH adjustment, and
stripping
Temperature >38°C in reactor Cooling
P r e - a n d P r i m a r y Tr e a t m e n t 67
Gravity
oil Flotation
separation
Coagulation
Equalization Neutralization and Sedimentation
precipitation
Source
control
3.2 Equalization
Variation in wastestream flows, constituents, and concentrations
can significantly reduce the efficiency of unit processes and efflu-
ent quality. Most equations utilized for design assume steady-state
conditions. Effluent permits are typically based on average as well
as maximum discharge limits. Hence, variability reduction is criti-
cal to compliance with treatment and sustainability goals. Equal-
ization therefore is a very important unit process typically
preceding other pre- and primary treatment and subsequent treat-
ment methods.
The objective of equalization is to minimize or control fluctua-
tions in wastewater characteristics in order to provide optimum con-
ditions for subsequent treatment processes. The size and type of the
equalization basin varies with the quantity of waste and the variabil-
ity of the wastewater stream. The basin should be of a sufficient size
68 Chapter Three
1490
1341
1192
Influent BOD (mg/L)
1043
894
745 Influent
596 48
Effluent BOD (mg/L)
447 36
Effluent
298 24
149 12
0 0
0.01 0.1 0.5 1 2 5 10 20 30 405060 70 80 90 95 98 99 99.9 99.99
Percent less than or equal to
P r e - a n d P r i m a r y Tr e a t m e n t 69
70 Chapter Three
Qin = Qout
Constant volume
High level
Variable volume
Example 3.1. Given the data in Table 3.2, design an equalization basin for a
constant outflow from the basin. The data are plotted as the summation of
inflow versus time as shown in Fig. 3.5. The treatment rate is (193,300 gal/day)/
(1440 min/day) = 134 gal/min (507 L/min). The required storage volume is
41,000 gal + 8000 gal residual or 49,000 gal (186 m3).
P r e - a n d P r i m a r y Tr e a t m e n t 71
1.5
Cumulative inflow
Cumulative volume (million gal)
1.0
Maximum
storage
required
Municipal
10 100
05 50
Industrial
72 Chapter Three
P r e - a n d P r i m a r y Tr e a t m e n t 73
200
150
V1 = 41,000 gal
Cumulative gallons 103
100
50
V2 = 8000 gal
0
8 12 4 8 12 4 8
Time of day
Δ t(Si 2 )
t= (3.1)
2(Se 2 )
Example 3.2. A waste with a total flow of 5 million gal/d (0.22 m3/s or
19,000 m3/d) was characterized as shown in Fig. 3.6. Extensive data were
collected every 4 h for 17 d. The average BOD was 690 mg/L and the maximum
value was 1185 mg/L.
Design calculations with activated sludge systems have indicated that the
effluent from the equalization basin must not exceed 896 mg/L in order to meet
the effluent quality criteria of an average BOD of 15 mg/L and a maximum
concentration of 25 mg/L from the activated sludge system.
74 Chapter Three
1400
1200
1000
BOD (mg/L)
800
2 = 990 – 380
= 610
600 = 305
400
0
0.01 0.1 1 2 5 10 20 30 40 60 80 90 95 99 99.9 99.99
Probability of BOD being less than or equal to given value (%)
Solution
(a) Calculate the mean, standard deviation, and variance of the influent.
These parameters may be calculated graphically from Fig. 3.6.
(b) From this plot obtain the 50 percent value:
(c) Calculate the standard deviation, Si, as half the difference in the values
that occur at the 15.9 (50.0 minus 34.1) and 84.1 (50.0 plus 34.1) percentile
levels from Fig. 3.6:
value at 84 .1 % − value at 15 .9 %
Si =
2
990 − 380
=
2
= 3 05 mg/L
Si2 = (305)2
X = 690 mg/L
X max = 896 mg/L
P r e - a n d P r i m a r y Tr e a t m e n t 75
The necessary condition for 95 percent of effluent BOD values to be less
than 896 mg/L is
X max − X
Se =
Z
896 − 690
=
1 . 65
= 125 mg/L
Se2 = (125)2
= 15 , 625 mg 2 /L2
Δ t(Si2 )
t=
2(Se2 )
4(93 , 025)
=
2(15 , 625)
= 11 . 9 h
≈ 0.. 5 d
76 Chapter Three
Example 3.3. A survey of the discharge from a chemical plant showed the
following results:
Mean
Time Period Flow gal/min TOC, mg/L
8 to 10 A.M. 450 920
10 to 12 noon 620 1130
12 to 2 P.M. 840 1475
2 to 4 P.M. 800 1525
4 to 6 P.M. 340 910
6 to 8 P.M. 270 512
8 to 10 P.M. 570 1210
10 to 12 midnight 1100 1520
0 to 2 A.M. 1200 1745
2 to 4 A.M. 800 820
4 to 6 A.M. 510 410
6 to 8 A.M. 570 490
dVi (1)
= Q0i − Qei = Q0i − Q0avg
dt
P r e - a n d P r i m a r y Tr e a t m e n t 77
where Vi = volume in the basin at time t for time interval i, gal
Q0i = influent flow rate at time interval i, gpm
Qe i = effluent flow rate at time interval i, gpm
Q0avg = daily average influent flow rate, gpm
C0i = influent concentration at time interval i, mg/L
Ci = concentration in the basin and effluent concentration at time t
for time interval i, mg/L
Assuming that Q0i, Qei, and C0i are constant during each time interval,
separation of variables, integration, and rearrangement of Eqs. (1) and (2) lead
to the following expressions for the volume Vi( f ) and the TOC concentration
Ci( f ) in the basin at the end of each time interval, respectively.
A
Ci ( f ) = C0i − (4)
(1 + BΔ ti )D
where
A = C0i − C(i − 1) ( f )
Q0i − Q0avg
B=
V(i − 1) ( f )
Q0i
D=
Q0i − Q0avg
The TOC mass Mei( f ) that left the equalization basin during each time interval
can be calculated by
1. The values for the first time interval (first row in the following table) are
calculated as:
• With the mean influent flow and concentration, the influent volume
and mass of TOC are calculated.
• The effluent flow rate, which is the same for all time intervals, is
calculated by dividing the total influent volume by the total time.
• For an initial basin volume (guess), the final volume is calculated by
using Eq. (3).
• For an initial concentration (guess), the final concentration is
calculated by using Eq. (4).
• The mass of TOC that left the basin is calculated by using Eq. (5).
2. The values for the other time intervals are calculated in a similar fashion
but the initial volume and concentration for each time interval are the
final volume and concentration of the previous time interval.
03_EckenFelder_Ch03_065-136.indd78 78
8 to 10 450 920 54,000 414 672.5 673 278,200 251,500 1009 993
10 to 12 620 1130 74,400 701 672.5 681 251,500 245,200 993 1028
12 to 14 840 1475 100,800 1240 672.5 745 245,200 265,300 1028 1174
14 to 16 800 1525 96,000 1221 672.5 828 265,300 280,600 1174 1278
16 to 18 340 910 40,800 310 612.5 842 280,600 240,700 1278 1225
18 to 20 270 512 32,400 138 672.5 791 240,700 192,400 1225 1125
20 to 22 570 1210 68,400 690 672.5 767 192,400 180,100 1125 1151
22 to 24 1100 1520 132,000 1673 672.5 843 180,100 231,400 1151 1327
0 to 2 1200 1745 144,000 2096 672.5 960 231,400 294,700 1327 1504
2 to 4 800 820 96,000 657 672.5 946 294,700 310,000 1504 1318
Pre- and Primary Treatment
4 to 6 510 410 61,200 209 672.5 829 310,000 290,500 1318 1150
6 to 8 570 490 68,400 280 672.5 725 290,500 278,200 1150 1009
Mean = 802 lb
Maximum = 960 lb
8/8/08 [Link] PM
Technical 6x9 /Industrial Water Quality/EckenFelder /866-1/Chapter 3
P r e - a n d P r i m a r y Tr e a t m e n t 79
3. The volume guessed for the first time interval is modified until the
maximum initial or final volume in the basin is the selected volume.
4. The concentration guessed for the first time interval is modified until it
matches the final concentration for the last time interval.
5. The maximum and average masses leaving the basin are determined and the
peaking factor is calculated as the ratio of the maximum to average values.
The results of the calculations for a basin volume of 310,000 gal are presented
in the following table. Repetition of the calculations for different volumes allows
the plotting of the peaking factor as a function of the basin volume as presented
in Fig. 3.7.
1.5
1.4
Effluent mass rate peaking factor
1.3
1.2
1.1
1.0
0 100,000 200,000 300,000 400,000 500,000 600,000
Volume (gal)
FIGURE 3.7 Variation in effluent mass rate peaking factor with basin volume
for a variable-volume equalization basin.
80 Chapter Three
8000 1000
5000
600
4000 500
3000 400
300
2000
200
1000
100
0 0
0 1 2 3 4 5 6 7 8 9 10
Equalization basin volume (Mgal)
1000
700
600
500
400
300
200
100
0
0 1 2 3 4 5 6 7 8 9 10
Equalization basin volume (Mgal)
P r e - a n d P r i m a r y Tr e a t m e n t 81
25,000
No balancing PF = 1.28 PF = 1.46
24-h balancing
20,000 12-h balancing
COD conc. (mg/L)
15,000
10,000
5,000
j
0
1 11 21 31 41 51 61 71 81 91 101 111 121 131
Hours
From plant
Monitor High-
(TOC, TOD, UV, etc.) strength
holding
pond
Constant
flow
Equalization
basin
To biological treatment
82 Chapter Three
P r e - a n d P r i m a r y Tr e a t m e n t 83
3.3 Neutralization
Many industrial wastes contain acidic or alkaline materials that
require neutralization prior to discharge to receiving waters or prior
to chemical or biological treatment. For biological treatment, a pH in
the biological system generally should be maintained between 6.5
and 8.5 to ensure optimum biological activity. The biological process
itself provides a neutralization and a buffer capacity as a result of the
production of CO2, which reacts with caustic and acidic materials.
The degree of preneutralization required depends, therefore, on the
ratio of BOD removed and the causticity or acidity present in the waste.
These requirements are discussed in Chap. 6. It should be noted that
some organic acids, such as acetic or formic, may result in an increase
in pH during biological treatment.
Types of Processes
Mixing Acidic and Alkaline Wastestreams
This process requires sufficient equalization capacity to effect the
desired neutralization.
Example 3.4. A wastewater flow of 100 gpm (0.38 m3/min) with 0.1 N H2SO4
requires neutralization prior to secondary treatment. This flow is to be neutralized
to a pH of 7.0 using a limestone bed. Figure 3.12 presents the results of a series
of laboratory pilot tests using a 1-ft- (30.5-cm-) diameter limestone bed. These
data are for upflow units, with the effluent being aerated to remove residual
CO2. Assume limestone is 60 percent reactive.
Design a neutralization system specifying:
84 Chapter Three
Waste
acid Conveyor
Recycle
pump
Effluent
3 ft
of
limestone
10
0.1 N H2SO4
7
pH value
4 ft
3 ft
5 2 ft
1 ft
0.5 ft
2
0 500 1000 1500 2000
Rate of flow (gal/ft2 • h)
Note: ft = 30.5 cm
FIGURE 3.12 Allowable limestone bed loading rate vs. bed depth
determination.
Solution
(a) Most economical bed depth. Hydraulic loadings to get pH 7.0 with various
depths of limestone bed: From the figure the allowable hydraulic loadings
are estimated to be:
Note: ft = 30.5 cm
gal/(ft2 · h) = 4.07 × 10–2 m3/(m2 · h)
P r e - a n d P r i m a r y Tr e a t m e n t 85
Flow rate per unit limestone volume: The required flow rate per unit
volume of bed can be calculated by:
hydraulic loading
Q/V =
bed depth
By plotting the flow rate per unit limestone volume against the limestone
bed depth, the most economical bed depth of limestone is found to be
⯝ 3 ft (0.91 m). This is the depth that gives the maximum flow per unit
volume; see Fig. 3.13.
(b) Weight of acid per day to be neutralized. The weight of acid can be calculated
by
500
Q/V (gal/[ft3 • h])
300
100
0 1 2 3 4
Bed depth (ft)
Note: ft = 30.5 cm
gal/(ft3 • h) = 0.134 m3/(m3 • h)
86 Chapter Three
P r e - a n d P r i m a r y Tr e a t m e n t 87
Basic agents
Acidic agents
• Sulfuric acid—strong
• Carbon dioxide—weak
System
Batch treatment is used for waste flows to 100,000 gal/d (380 m3/d).
Continuous treatment employs automated pH control. Where air is
used for mixing, the minimum air rate is 1 to 3 ft3/(min ft2) (0.3 to
0.9 m3/[min m2]) at 9 ft (2.7 m) liquid depth. If mechanical mixers are
used, 0.2 to 0.4 hp/thousand gal (0.04 to 0.08 kW/m3) is required.
Control of Process
The automatic control of pH for wastestreams is one of the most trou-
blesome, for the following reasons:
03_EckenFelder_Ch03_065-136.indd88 88
sizes)
Shipping Bags, barrel, Bags Bags (80 lb), Barrels, Bags Drum (735, Carboys,
container bulk (50 lb),∗ bulk barrels, bulk drums, bulk (100 lb), bulk 100, 450 lb) drums (825 lb),
bulk
Bulk weight, Powder 48 to 25 to 50 40 to 70 27.9%, 34 to 62 Varies 106, 114
lb/ft3 71; crushed 0.53 lb/gal†;
70 to 100 31.45%,
9.65 lb/gal
Commercial — Normally 75 to 99%, 27.9, 31.45, 99.2% 98% 60° Be, 77.7%;
strength 13% Ca(OH)2 normally 35.2% 66° Be, 93.2%
90% CaO
Pre- and Primary Treatment
Water Nearly Nearly Nearly Complete 0.58 @ 32°F, 3.5 @ 32°F, Complete
solubility, insoluble insoluble insoluble 1.04 @ 50°F, 4.3 @ 50°F,
lb/gal 1.79 @ 68°F, 9.1 @ 68°F,
3.33 @ 86°F 9.2 @ 86°F
Feeding form Dry slurry Dry or slurry Dry or slurry Liquid Dry, liquid Solution Liquid
used in fixed (must be
8/8/08 [Link] PM
Feeding type Volumetric Volumetric Dry- Metering Volumetric Metering Metering
pump metering volumetric, pump feeder, pump pump
pump wet slurry metering
(centrifugal pump
03_EckenFelder_Ch03_065-136.indd89 89
pump)
Accessory Slurry tank Slurry tank Slurry tank, Dilution tank Dissolving Solution tank —
equipment slaker tank
Suitable Iron, steel Iron, steel, Iron, steel, Hastelloy Iron, steel Iron, steel —
handling plastic, plastic, A, selected
materials rubber hose rubber hose plastic and
rubber types
Comments — — Provide — Can cake Dissolving Provide
means for solid forms for spill
cleaning generate cleanup and
slurry transfer much heat neutralization
pipes
Pre- and Primary Treatment
∗lb 0.4536 = kg
†
lb/gal 0.1198 = kg/L
‡
0.555 (°F 32) = °C
8/8/08 [Link] PM
90
To neutralize 1 mg/L
Acidity or Alkalinity Neutralization Factor,
(Expressed as CaCO3) Assuming 100% Purity
Chemical Formula Equivalent Weight Requires n mg/L for all Compounds
Basicity
Calcium carbonate CaCO3 50 1.000 1.000/0.56 = 1.786
03_EckenFelder_Ch03_065-136.indd90 90
Calcium oxide CaO 28 0.560 0.560/0.56 = 1.000
Calcium hydroxide Ca(OH)2 37 0.740 0.740/0.56 = 1.321
Magnesium oxide MgO 20 0.403 0.403/0.56 = 0.720
Magnesium hydroxide Mg(OH)2 29 0.583 0.583/0.56 = 1.041
Dolomitic quicklime (CaO)0.6(MgO)0.4 24.8 0.497 0.497/0.56 = 0.888
Dolomitic hydrated lime [Ca(OH)2]0.6 [Mg(OH)2]0.4 33.8 0.677 0.677/0.56 = 1.209
Sodium hydroxide NaOH 40 0.799 0.799/0.56 = 1.427
Sodium carbonate Na2CO3 53 1.059 1.059/0.56 = 1.891
Sodium bicarbonate NaHCO3 84 1.680 1.680/0.56 = 3.00
Pre- and Primary Treatment
Acidity
Sulfuric acid H2SO4 49 0.980 0.980/0.56 = 1.750
Hydrochloric acid HCl 36 0.720 0.720/0.56 = 1.285
Nitric acid HNO3 62 1.260 1.260/0.56 = 2.250
TABLE 3.6 Neutralization Factors for Common Alkaline and Acid Reagents
8/8/08 [Link] PM
Technical 6x9 /Industrial Water Quality/EckenFelder /866-1/Chapter 3
P r e - a n d P r i m a r y Tr e a t m e n t 91
12
10
8
pH = 7 Second stage control
pH value
4
pH = 3.5 First stage control
0 1000 2000
mg lime/L of waste
92 Chapter Three
Slaked lime
Slurry storage
Acid waste
pH control
Mixer
Equalizing
tank or
lagoon
Bypass
pH control
To treatment
or disposal
Alkaline waste
Note: The selection of neutralizing agent will depend on availability, chemical cost, and
feeding methods.
P r e - a n d P r i m a r y Tr e a t m e n t 93
The average lime dosage in the first stage is
The average lime dosage is 2700 lb/d (1.35 ton/d) (1230 kg/d). With this
dosage and type of lime each basin should be designed with a detention time
of 5 min.
Use two tanks, 4.6 ft (1.40 m) diameter × 4.1 ft (1.25 m) deep, so that diameter
and depth are approximately equal.
To maintain proper mixing in the reactor tanks, the power level required for
5 min detention time, D/T = 0.33, is 0.2 hp/thousand gal (40 W/m3) (Fig. 3.16).
Use 0.1-hp (75-W) mixers in each reaction tank.
Either one or two standard wall baffles, 180º apart, and one-twelfth to one-
twentieth of the width of the tank diameter, located 24 in (61 cm) from the
periphery of the impeller, are recommended for this operation.
1.0
0.8
0.6
0.4
0.3
0.2
D/T = 0.20
hp/thousand gal
D/T = 0.33
0.1
0.08
0.06 D/T = 0.50
0.04
0.03
Neutralization and D = turbine diameter
0.02 blending selection T tank diameter
0.01
1 2 3 4 6 8 10 20 50 100
Detention time (min)
Note: hp/thousand gal = 198 W/m3
94 Chapter Three
3.4 Sedimentation
Sedimentation is employed for the removal of suspended solids from
wastewaters. The process can be considered in three basic classifica-
tions, depending on the nature of the solids present in the suspen-
sion: discrete, flocculent, and zone settling. In discrete settling, the
particle maintains its individuality and does not change in size, shape,
or density during the settling process. Flocculent settling occurs when
the particles agglomerate during the settling period with a resulting
change in size and settling rate. Zone settling involves a flocculated
suspension which forms a lattice structure and settles as a mass,
exhibiting a distinct interface during the settling process. Compac-
tion of the settled sludge occurs in all sedimentation but will be con-
sidered separately under thickening.
Discrete Settling
A particle will settle when the impelling force of gravity exceeds the
inertia and viscous forces. The terminal settling velocity of a particle is
defined by the relationship
4 g( ρs − ρl )D
v= (3.3)
3Cd ρl
When the Reynolds number is small, i.e., less than 1.0 (small par-
ticles at low velocity), the viscous forces are predominant and
24
Cd = (3.4)
N Re
where
vDρl
N Re = (3.5)
μ
rl and m are the density and viscosity of the liquid, respectively. Sub-
stitution of Eq. (3.4) in Eq. (3.3) yields Stokes’ law:
ρs − ρl
v= gD2 (3.6)
18μ
P r e - a n d P r i m a r y Tr e a t m e n t 95
1.0
0.1
Particle diameter (cm)
0.001
0.01 0.1 1 10
Settling velocity (cm/s)
96 Chapter Three
D Inlet Outlet
v
zone zone
vo
Sludge zone
t
(a) Discrete
v
D Inlet Outlet
zone vo zone
Sludge zone
t
(b) Flocculent
where Q = rate of flow through the tank and A = tank surface area. All
particles with settling velocities greater than vo will be completely
removed, and particles with settling velocities less than vo will be
removed in the ratio v/vo, as shown in Fig. 3.18. The removal of dis-
crete particles is independent of tank depth and is a function of the
overflow rate only.
When the suspension to be removed has a wide range of particle
sizes, the total removal is defined by the relationship
1 fo
Total removal = (1 − fo ) +
vo ∫0 v df (3.9)
P r e - a n d P r i m a r y Tr e a t m e n t 97
Values of v/vo
1.0 2.0 1.5 1.2
1.1
1.0
0.9
0.9
0.8 0.8
0.7 0.7
Removal ratio rr
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0
0.1 0.5 1 5 10 50 100
Values of vH/2E
Removal ratios for turbulent sedimentation
Figure 3.19 shows the effect of turbulence in reducing the removal ratio
of particles having a settling velocity v from the theoretical value of
v/vo, where vo refers to the overflow rate. The ratio vH/2E is a parame-
ter of turbulent intensity, where H is the depth and E is a coefficient of
turbulent transport. For narrow channels, Camp has shown the ratio to
be equal to 122v/V, where V is the average channel velocity.
Scour occurs when the flow-through velocity is sufficient to resus-
pend previously settled particles; it is defined by the relationship:
8β
vc = gD (S − 1) (3.10)
f
98 Chapter Three
Flocculent Settling
Flocculent settling occurs when the settling velocity of the particle
increases as it settles through the tank depth, because of coalescence
with other particles. This increases the settling rate, yielding a curvilin-
ear settling path, as shown in Fig. 3.18b. Most of the suspended solids
in industrial wastes are of a flocculent nature. For discrete particles, the
efficiency of removal is related only to the overflow rate, but when
flocculation occurs, both overflow rate and detention time become
significant.
Since a mathematical analysis is not possible in the case of floc-
culent suspensions, a laboratory settling analysis is required to estab-
lish the necessary parameters. The laboratory settling study can be
conducted in a column of the type shown in Fig. 3.20. A minimum
diameter of 5 in (12.7 cm) is recommended to minimize wall effects.
Taps are located at 2-ft (0.61-m) depth intervals.
The concentration of suspended solids must be uniform at the
start of the test; sparging air into the bottom of the column for a few
minutes will accomplish this. It is also essential that the tempera-
ture be maintained constant throughout the test period to eliminate
settling interference by thermal currents. Suspended solids are
determined on samples drawn off at selected time intervals up to
120 min. The data collected from the 2-ft (0.61 m), 4-ft (1.22 m), and
6-ft (1.83-m) depth taps are used to develop the settling rate–time
relationships.
The results obtained are expressed in terms of percent removal
of suspended solids at each tap and time interval. These removals
are then plotted against their respective depths and times, as shown
in Fig. 3.21. Smooth curves are drawn connecting points of equal
removal. The curves thus drawn represent the limiting or maximum
settling path for the indicated percent; that is, the specified percent
suspended solids will have a net settling velocity equal to or greater
than that shown, and would therefore be removed in an ideal set-
tling tank of the same depth and detention time. The calculation of
removal can be illustrated from the data of Fig. 3.21.
The overflow rate vo is the effective depth, 6 ft (1.83 m), divided by
the time required for a given percent to settle this distance. All particles
having a settling velocity equal to or greater than vo will be 100 percent
removed. Particles with a lesser settling velocity v will be removed in
the proportion v/vo. For example, referring to Fig. 3.21a, at a detention
period of 60 min and a 6-ft (1.83-m) settling depth (vo = 6 ft/h [1.83 m/h]),
50 percent of the suspended solids are completely removed; that is,
50 percent of the particles have a settling velocity equal to or greater
than 6 ft/h (1.83 m/h). Particles in each additional 10 percent range will
be removed in the proportion v/vo or in the proportion to the average
P r e - a n d P r i m a r y Tr e a t m e n t 99
6 in OD
5 12 in ID
1 in
1
4 2 12 in bolts
2 ft
Rubber gasket
8 ft 8 in
1 in
2 ft
Sludge sample
and drain
Lucite
2 ft Rubber
1 in
gasket
12 in
1 in
Note:
in = 2.54 cm
ft = 30.48 cm
FIGURE 3.20 Laboratory settling column for the evaluation of flocculent settling.
depth settled to the total depth of 6 ft (1.83 m). The average depth to which
the 50 to 60 percent range has settled in Fig. 3.21b is 3.8 ft (1.16 m). The
percent removal of this fraction is therefore 3.8 ft/6.0 ft (1.16 m/1.83 m), or
63 percent of the 10 percent. Each subsequent percent range is computed in
a similar manner, and the total removal developed as shown in Table 3.8.
The total removal of suspended solids of 62.4 percent can be accom-
plished at an overflow rate of 6 ft/h = 1080 gal/(d ft2) (44 m3/[d m2])
at a retention period of 60 min. In a similar manner various percent
70
2 27 39 50 60 70
Depth (ft)
30 40 50 60
4 36 28 44 48 64
C0 = 393 mg/L
6 26 40 35 38 50 60
50 100
Time (min)
(a)
0
2 31 46 63 71 73 75
Depth (ft)
70
50 60
20 30 40
4 22 31 42 60 61 67
C0 = 550 mg/L
6 15 24 45 59
50 100
Time (min)
(b)
Note: ft = 0.3048 m
P r e - a n d P r i m a r y Tr e a t m e n t 101
Example 3.6. Laboratory data were obtained on the settling of a paper mill waste
(Table 3.9). Design a settling tank to produce a maximum effluent suspended
solids of 150 mg/L.
Removal, %
Time, min 2 ft 4 ft 6 ft
Initial solids, 393 mg/L
5 26
10 27 36 40
20 39 28 35
40 50 44 38
60 60 48 50
120 70 64 60
Initial solids, 550 mg/L
15 31 22 15
20 46 31
40 63 42 24
60 71 60 45
90 73 61
120 75 67 59
Note: ft = 30.48 cm
Solution. With the values given in Table 3.9, Fig. 3.21 can be drawn and
Table 3.10 can be constructed by calculating the percent removal, the velocity,
and the overflow rate of different times as indicated above.
By plotting the SS removal versus overflow rate and time, Figs. 3.22 and 3.23
can be drawn.
From Figs. 3.22 and 3.23:
For 393 mg/L:
393 − 150
Percent removal = × 100 = 62
393
Overflow ra te = 770 gal/(d ⋅ ft 2 )(31 .4 m 3 /[d ⋅ m 2 ])
Detention time = 74 min
550 − 150
Percent removal = × 100 = 73
550
Overflow ra te = 540 gal/(d ⋅ ft 2 )(22 .0 m 3 /[d ⋅ m 2 ])
Detention time = 104 min
Design:
540
Overflow rate = = 360 gal/(d ⋅ ft 2 )(14 .7 m 3 /[d ⋅ m 2 ])
1 .5
104 min
Detention time t = × 1 .75 = 3 h
60 min/h
P r e - a n d P r i m a r y Tr e a t m e n t 103
90
Suspended solids removal (%)
70
50
550
393
30
0 1000 2000 3000 4000
Overflow rate (gal/[d • ft2])
Note: gal/(d • ft2) = 4.07 10 –2 m3/(d • m2)
90
Suspended solids removal (%)
550
70
393
50
30
0 50 100
Detention time (min)
t × flow
Effective depth =
A
3 h × 106 gal/d 0 . 134 ft 3 /gal
= ×
2780 ft 2 2 4 h/d
= 6 ft (1 .8 m)
The sedimentation performances for various pulp and paper-mill wastes are
summarized in Table 3.11.
03_EckenFelder_Ch03_065-136.indd104 104
0.75 136 85 90 50 1.15 940
1.36 10,000 360 62 85 24 5.40 430
2.5 1,185 395 96.1 19 5.3 525
31 524 195 110 42 25 9.4 438
30 850 250 95 80 25 0.5 1910
3.3 2,000 90 85 2.6 1028
0.25 50 100 100 80 25 4.5 39
0.301 1,150 250 110 98 50 90
35 4,000 200 100 90 10–15 1.5 374
Pre- and Primary Treatment
8/8/08 [Link] PM
Fine paper 6 200 65 95 90 3.9 695
6.0 254 235 90 50 34 2.2 890
9.9 500 364 70–100 90 35 2.4 1120
3.5 300 250 65 95 48 6.0 372
03_EckenFelder_Ch03_065-136.indd105 105
7.5–9.0 560 126 65 80 42 4.0 670
Miscellaneous 7 430 250 70 70 20 1.8 505
14 1,000 330 73 65 60 911
25 75 100 90 0.0 6.9 17
17 100 425 95 50 5.9 846
0.5 200 200 85 90 1.9 1590
1.0 1,000 900 100 95 2.9 509
°C =
5 (°F ⫺ 32).
9
gal/(d ⭈ ft2) = 4.07 ⫻ 10–2 m3/(d ⭈ m2).
Source: Adapted from Committee on Industrial Waste Practice of SED.
8/14/08 [Link] PM
Technical 6x9 /Industrial Water Quality/EckenFelder /866-1/Chapter 3
Zone Settling
Zone settling is characterized by activated sludge and flocculated
chemical suspensions when the concentration of solids exceeds
approximately 500 mg/L. The floc particles adhere together and the
mass settles as a blanket, forming a distinct interface between the floc
and the supernatant. The settling process is distinguished by four
zones, as shown in Fig. 3.25. Initially, all the sludge is at a uniform
concentration A, as shown in Fig. 3.25.
During the initial settling period the sludge settles at a uniform
velocity. The settling rate is a function of the initial solids concen-
tration A. As settling proceeds, the collapsed solids D on the bot-
tom of the settling unit build up at a constant rate. C is a zone of
transition through which the settling velocity decreases as the
result of an increasing concentration of solids. The concentration of
solids in the zone settling layer remains constant until the settling
interface approaches the rising layers of collapsed solids, III, and a
transition zone occurs. Through the transition zone C, the settling
velocity will decrease because of the increasing density and viscos-
ity of the suspension surrounding the particles. When the rising
layer of settled solids reaches the interface, a compression zone
occurs in stage IV.
In the separation of flocculent suspensions, both clarification of
the liquid overflow and thickening of the sludge underflow are
involved. The overflow rate for clarification requires that the average
rise velocity of the liquid overflowing the tank be less than the zone
settling velocity of the suspension. The tank surface area require-
ments for thickening the underflow to a desired concentration level
are related to the solids loading to the unit and are usually expressed
in terms of a mass loading (pounds of solids per square foot per day
or kilograms per square meter per day) or a unit area (square feet per
pound of solids per day or square meters per kilogram per day).
The mass loading concept for the thickening of industrial sludges
is developed in Chap. 11.
P r e - a n d P r i m a r y Tr e a t m e n t 107
90
Suspended solids removal (%)
80
70
Overflow rate = 1000–1400 gal/(d • ft2)
Detention = 1.5–2.0 h
T = 95–105°F
60
0 500 1000
Initial concentration C0 (mg/L)
Note:
gal/(d • ft 2) = 4.07 10 –2 m3/(d • m 2)
°C = 59 (°F – 32)
Clarifiers
Clarifiers may be either rectangular or circular. In most rectangular
clarifiers, scraper flights extending the width of the tank move the
settled sludge toward the inlet end of the tank at a speed of about
1 ft/min (0.3 m/min). Some designs move the sludge toward the
effluent end of the tank, corresponding to the direction of flow of the
density current. A typical unit is shown in Fig. 3.26.
Circular clarifiers may employ either a center-feed well or a
peripheral inlet. The tank can be designed for center sludge with-
drawal or vacuum withdrawal over the entire tank bottom.
Circular clarifiers are of three general types. With the center-feed
type, the water is fed into a center well and the effluent is pulled off
at a weir along the outside. With a peripheral-feed tank, the effluent
is pulled off at the tank center. With a rim-flow clarifier, the periph-
eral feed and effluent drainoff are also along the clarifier rim, but this
type is usually used for larger clarifiers.
I II III IV
B
B
B
A A A
C
C
D D
D
Height of sludge-liquid interface
Zone Transition
settling zone Compression
(A) (C) (D)
Time
P r e - a n d P r i m a r y Tr e a t m e n t 109
P r e - a n d P r i m a r y Tr e a t m e n t 111
Peripheral feed
Dye concentration
Center feed
Time (min)
Cover distribution
chamber if desired
A Platform
Trash
Rack
B B
C C
Oil retention
baffle Designed for inserting
rubber balloon stoppers
Vertical for diverting flows for
baffle cleaning separator sections.
Sluice gates or gate valves
Flight may be installed if desired.
scraper
Sludge pump
chain
sprocket
Section A-A
Wood flight
scraper
Oil retention
baffle
A
Section B-B
Section C-C
FIGURE 3.29 Example of general arrangement for API separator. (Courtesy of the
American Petroleum Institute)
The hydraulic loading varies with temperature and the specific grav-
ity of the oil. Nominal flow rates are specified for a temperature of
20°C and a specific gravity of 0.9 for the oil. A hydraulic loading of
0.5 m3/(h m2) of actual plate area will usually result in separation of
0.006-cm droplets. A 50 percent safety factor is usually employed for
design purposes. A plate separator is shown in Fig. 3.34.
Several types of filtration devices have proved effective in remov-
ing free and emulsified oils from refinery-petrochemical wastewaters.
These vary from filters with sand media to those containing special
1,000,000
800,000
600,000
Conventional oil-water separator
400,000
Parallel-plate separator
200,000
100,000
80,000
60,000
40,000
FIGURE 3.30 Correlation between influent and effluent oil levels for existing oil-water separators.
20,000
10,000
8,000
6,000
Note: The data in this figure are taken from the 1985 API Refinery Survey.
4,000
Influent oil (mg/L)
2,000
1,000
800
600
400
200
100
80
60
40
20
10
10,000
8,000
6,000
4,000
2,000
1,000
800
600
400
200
100
80
60
40
20
10
113
Downloaded from Digital Engineering Library @ McGraw-Hill ([Link])
Copyright © 2008 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
4,000
2,000
1,000
800
Effluent oil (mg/L)
600
400
200
100
80
60
40
20
10
1
6
8
10
20
40
60
80
100
200
400
600
800
1000
Inverse surface loading rate (ft2/[ft3 • min])
Note: The data in this figure are taken from the 1985 API Refinery Survey.
P r e - a n d P r i m a r y Tr e a t m e n t 115
100
90
80
OWS
effluent
70
Probability (%)
60
Raw
50 wastewater
40
30
20
10
0
0 50 100 150 200 250 300 350 400 450
Oil (mg/L)
800
700
600
500
Effluent oil (mg/L)
400
300
200
100
0
0 500 1000 1500 2000
Influent oil (mg/L)
Recovered oil to
skimmed oil tanks
Separated oil
Separated solids
to disposal
media which exhibit a specific affinity for oil. One type is an upflow
unit using a graded silica medium as the filtering and coalescing sec-
tion. Even the small particles and globules are separated and retained
on the medium. The oil particles, which flow upward by gravity dif-
ferential and fluid flow, rise through the coalescent medium and
through the water phase from which the oil is separated and collected
near the top of the separator. The bed is regenerated by introducing
wash water at a rapid rate and evacuating the solids and remaining oil.
This filtration and coalescing process is often enhanced by the use of
polymer resin media. The primary application of these units are for
selected in-plant streams which are dirt-free. Another application
would be ballast water treatment following phase separation.
Emulsified oily materials require special treatment to break the
emulsions so that the oily materials will be free and can be separated
by gravity, coagulation, or air flotation. The breaking of emulsions is
a complex art and may require laboratory or pilot-scale investigations
prior to developing a final process design.
Emulsions can be broken by a variety of techniques. Quick-breaking
detergents form unstable emulsions which break in 5 to 60 min to 95
to 98 percent completion. Emulsions can be broken by acidification,
the addition of alum or iron salts, or the use of emulsion-breaking
polymers. The disadvantage of alum or iron is the large quantities of
sludge generated.
P r e - a n d P r i m a r y Tr e a t m e n t 117
wastes under the Resource Conservation and Recovery Act (RCRA).
These include:
RCRA Hazardous
Waste Designation
• Oil separator bottom sludges K051
• Slop oil emulsions K049
• DAF float K048
• Heat exchanger bundles K050
• Leaded tank bottoms K052
• Primary oil separator sludges F037
and desalter muds
• Miscellaneous sludge floats F038
Electrical
Process power
water
Desalted
Alternate
crude
Unrefined
crude Gravity settler
Effluent
Heater Emulsifier water
Process Recovered
oil Emulsion
water
breaker
Desalter
Heater Chemicals
e
Raw crud CPI
Mixed
effluent DAF oil Refinery Final
CPI equalization
Effluent removal WWTP effluent
Separated tanks
solids
Mud
removal Coker
Solids
disposal
P r e - a n d P r i m a r y Tr e a t m e n t 119
3.8 Flotation
Flotation is used for the removal of suspended solids and oil and
grease from wastewaters and for the separation and concentration of
sludges. The waste flow or a portion of clarified effluent is pressur-
ized to 50 to 70 lb/in2 (345 to 483 kPa or 3.4 to 4.8 atm) in the presence
of sufficient air to approach saturation. When this pressurized air-
liquid mixture is released to atmospheric pressure in the flotation
unit, minute air bubbles are released from solution. The sludge flocs,
suspended solids, or oil globules are floated by these minute air bub-
bles, which attach themselves to and become enmeshed in the floc
particles. The air-solids mixture rises to the surface, where it is
skimmed off. The clarified liquid is removed from the bottom of the
flotation unit; at this time a portion of the effluent may be recycled
back to the pressure chamber. When flocculent sludges are to be clar-
ified, pressurized recycle will usually yield a superior effluent quality
since the flocs are not subjected to shearing stresses through the
pumps and pressurizing system.
P r e - a n d P r i m a r y Tr e a t m e n t 121
the oxygen and nitrogen solubilities in water follow Henry’s law over
a wide pressure range. Vrablick19 has shown that although a linear
relationship exists between pressure and solubility for most indus-
trial wastes, the slope of the curve varies, depending on the nature of
the waste constituents present. The solubility of air in water at atmo-
spheric pressure is shown in Table 3.14.
The quantity of air that will theoretically be released from solu-
tion when the pressure is reduced to 1 atm can be computed from
P
s = sa − sa (3.11)
Pa
⎛fP ⎞
s = sa ⎜ − 1⎟ (3.12)
⎝ Pa ⎠
where f is the fraction of saturation in the retention tank.
The performance of a flotation system depends on having suffi-
cient air bubbles present to float substantially all of the suspended
solids. An insufficient quantity of air will result in only partial flota-
tion of the solids, and excessive air will yield no improvement. The
performance of a flotation unit in terms of effluent quality and solids
concentration in the float can be related to an air/solids (A/S) ratio,
which is usually defined as mass of air released per mass of sus-
pended solids in the influent waste:
A sa R ⎛ f P ⎞ (3.13)
= − 1⎟
S SaQ ⎜⎝ Pa ⎠
where Q = wastewater flow
R = pressurized recycle
Sa = influent oil and/or suspended solids
0.08
0.06
Air/solids ratio (lb/lb)
0.04
A/S = 0.03
0.02
0 10 20 30 40 50 60
Effluent oil and grease (mg/L)
P r e - a n d P r i m a r y Tr e a t m e n t 123
Retention
tank
Air Thickened
sludge
Waste
influent Flotation tank
Pressurizing Pressure-
pump reducing
valve
Effluent
(a)
Influent waste
Pressure-
reducing
valve
Air release
Air
Recycle injection Effluent
Retention
tank
(b)
P r e - a n d P r i m a r y Tr e a t m e n t 125
Inductors
Valve manual Overflow weir
Pneumatic level
controller
Oily water
influent Treated
effluent
Pneumatic
valve
Float product by
gravity to sump
Sampling hose
Cork plug
Hose clamp
Rubber seat
Air cock
Pressure gauge
Air
Inlet valve
Check nut
Air-bleed valve
Top plate
Air sparger
Riser tube
Pressure chamber
A 1 . 3sa R (P − 1)
=
S QSa
P r e - a n d P r i m a r y Tr e a t m e n t 127
100 100
90 Alum 90 Polymer
80 80
70 70
Residual (%)
Residual (%)
60 60
50 Turbidity 50
40 40 Turbidity
30 30
20 Oil 20
10 10 Oil
0 0
0 10 20 30 40 50 60 70 80 0 2 4 6 8 10 12
Alum dose (mg/L) Polymer dose (mg/L)
Calculate:
100
90
80
70
Oil-water system
Probability (%)
60
influent
DAF to DAF
50
effluent
40
30
20
10
0
0 20 40 60 80 100 120 140 160
Oil (mg/L)
FIGURE 3.43 Oil removal by chemical flocculation and DAF. (Adapted from
Galil and Rebhum, 1993.)
140
Note: Influent oil to
API separator:
120 50% value = 1020 mg/L
90% value = 2150 mg/L 90% value = 105 mg/L
100
DAF
80
Oil (mg/L)
influent
50% value = 68 mg/L
60
40
0
1 10 30 50 90 99 99.9
Percent equal to or less than
P r e - a n d P r i m a r y Tr e a t m e n t 129
∗Alum most common, 100–300 mg/L. Polyelectrolyte, 1–5 mg/L, is occasionally added
The air/solids ratio for effluent oil and grease of 20 mg/L is found from Fig. 3.37:
A
= 0 . 03 lb air released/lb solids applied
S
At 103°F (39.4°C) the weight solubility of air is 18.6 mg/L from Table 3.14. The
value of f is assumed to be 0.85.
Solution
(a) The recycle rate is
( A/ S) QSa
R=
sa ( fP/ Pa − 1)
(b) The hydraulic loading for oil removal is determined from Fig. 3.45,
and is 2.6 gal/(min ft2) (0.11 m3/[min m2]) for an effluent of 20 mg/L.
The required surface area is
Q+R
A=
loading
150 + 8 . 75
=
2.6
= 61 ft 2 ( 5 .7 m 2 )
40 Pressure = 50 lb/in2
Varied recycle
Effluent oil and grease (mg/L)
30
20
10
P r e - a n d P r i m a r y Tr e a t m e n t 131
(c) Sludge quantities generated:
⎛ lb/million gal ⎞
× (million gal/106 gal) ⎜ 8 .34 ⎟⎠
⎝ mg/L
3.9 Problems
3.1. An industry is required to equalize its wastewater and discharge it such
that the load in BOD/day to a POTW is constant over 24 h. The POTW sewage
flow is 6.47 million gal/d, with a BOD of 200 mg/L. The diurnal sewage
variation in flow is shown in Fig. P3.1. The industrial waste flow is 3.17 million
gal/d, with a BOD of 1200 mg/L, and is constant over 10 h (8 A.M. to 6 P.M.).
15
11.6
Rate of flow (million gal/d)
10
1.6
1.6
0
8 A.M. 2 P.M. 8 P.M. 2 A.M. 8 A.M.
Hours of the day
FIGURE P3.1
3.3. An acidic industrial wastewater flow of 150 gal/min (0.57 m3/min) with
a peak factor of 1.2 is to be neutralized to pH 6.0 using lime. The titration curve
is as follows:
P r e - a n d P r i m a r y Tr e a t m e n t 133
pH mg Lime/L Waste
1.8 0
1.9 500
2.05 1000
2.25 1500
3.5 2000
4.1 2100
5.0 2150
7.0 2200
Determine:
(a) The lime feed rate for each stage in a two-stage system.
(b) The lime storage capacity (ft3) based on the controlling requirement
of either the mean monthly requirement or the maximum two-week
requirement. Assume the use of pebbled quicklime (CaO), which has
a bulk density of 65 lb/ft3 (1060 kg/m3).
(c) The capacity of the lime slaker and mechanism for transporting the bulk
lime based on the maximum estimated requirements.
(d) The mean and maximum slaking water requirements assuming a
10 percent by weight slurry.
(e) The size of the slurry control tank based on a minimum resident time
of 5 min.
(f) The size of the caustic storage tank based on 24-h caustic feed (NaOH) at
the maximum extended usage equivalent to a hydrated lime requirement
of 1000 mg/L. Assume NaOH is available with a purity of 98.9 percent
and a solubility of 2.5 lb/gal (300 kg/m3).
(g) The maximum caustic (NaOH) feed rate for backup of the lime
system.
3.4. A laboratory settling analysis for a pulp and paper mill effluent gave the
following results for Co = 430 mg/L, T = 29°C:
(a) Design a settling tank to remove 70 percent of the suspended solids for
1 million gal/d flow (3785 m3/d). (Apply appropriate factors and neglect
initial solids effects.)
(b) What removal will be attained if the flow is increased to 2 million gal/d
(7570 m3/d)?
Note: ft = 30.5 cm
3.5. A wastewater has a flow of 250 gal/min (0.95 m3/min) and a temperature
of 105°F (40.5°C). The concentration of oil and grease is 150 mg/L and the
suspended solids 100 mg/L. An effluent concentration of 20 mg/L is required.
An alum dosage of 30 mg/L is required. The required A/S is 0.04 and the
surface loading rate is 2 gal/(min ft2) (0.081 m3/[min m2]). The operating
pressure is 65 lb/in2 gage (4.4 relative atm).
Compute:
References
1. Novotny, V., and A. J. England: Water Res., vol. 8, p. 325, 1974.
2. Patterson, J. W., and J. P. Menez: Am. Inst. Chem. Engrs. Env. Prog., vol. 3, p. 2,
1984.
3. Thomas, O., and D. Constant: “Trends in Optical Monitoring, Trends in
Sustainable Production—From Wastewater Diagnosis to Toxicity Management
and Ecological Protection,” IWA Press, issue 1, vol. 49, London, 2004.
4. Tully, T. J.: Sewage Ind. Wastes, vol. 30, p. 1385, 1958.
5. Okey, R. W. et al.: Proc. 32nd Purdue Industrial Waste Conf., Ann Arbor Science
Pub., 1977.
6. Hazen, A.: Trans. ASCE, vol. 53, p. 45, 1904.
7. Camp, T. R.: Trans. ASCE, vol. 111, p. 909, 1946.
8. Dobbins, W. E.: “Advances in Sewage Treatment Design,” Sanitary Engineering
Division, Met. Section, Manhattan College, May 1961.
9. Committee on Industrial Waste Practice of SED: J. Sanit. Engrg. Div. ASCE,
December 1964.
10. Sutherland, R.: Ind. Eng. Chem., p. 630, May 1947.
11. Greenfield, R. E., and G. N. Cornell: Ind. Eng. Chem., p. 583, May 1947.
12. American Petroleum Institute: Manual on Disposal of Refinery Wastes, vol. 1, New
York, 1959.
13. Azad, H. S. (editor): Industrial Wastewater Management Handbook, McGraw-Hill,
New York, 1976.
P r e - a n d P r i m a r y Tr e a t m e n t 135
14. Ford, D. L., private communication.
15. Galil, N., and M. Rebhum: Water Sci. Tech., vol. 27, no. 7–8, p. 79, 1993.
16. Jones, H. R.: Pollution Control in the Petroleum Industry, Noyes Data Corp.,
Princeton, New Jersey, 1973.
17. Pray, H. A.: Ind. Eng. Chem., vol. 44, pt. 1, p. 146, 1952.
18. Frolich, R.: Ind. Eng. Chem., vol. 23, p. 548, 1931.
19. Vrablick, E. R.: Proc. 14th Ind. Waste Conf., 1959, Purdue University.
20. Hurwitz, E., and W. J. Katz: “Laboratory Experiments on Dewatering Sewage
Sludges by Dissolved Air Flotation,” unpublished report, Chicago, 1959.