Bay Transformer Protection Relay Settings

1) The document evaluates protection relay settings for a bay transformer between PT. ABB Sakti Industri and PT. Star Ajibarang Purwokerto. 2) It analyzes the settings for overcurrent, ground fault, differential, and voltage regulation relays on the 150kV high voltage and 10.5kV low voltage sides. 3) The evaluation compares existing and proposed settings for pickup values, time delays, and operating curves to protect the transformer.

Uploaded by

Bravery Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
261 views5 pages

Bay Transformer Protection Relay Settings

1) The document evaluates protection relay settings for a bay transformer between PT. ABB Sakti Industri and PT. Star Ajibarang Purwokerto. 2) It analyzes the settings for overcurrent, ground fault, differential, and voltage regulation relays on the 150kV high voltage and 10.5kV low voltage sides. 3) The evaluation compares existing and proposed settings for pickup values, time delays, and operating curves to protect the transformer.

Uploaded by

Bravery Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Protection Setting Relay - Page 1: Details protection relay settings and evaluations for bay transformer on specific groups and types on page 1 with corresponding remarks.
  • Protection Setting Relay - Page 2: Continues detailing protection relay settings and evaluations for bay transformer, focusing on additional relay types and settings on page 2.
  • Protection Setting Relay - Page 3: Provides more protection relay settings and evaluation details for bay transformer focusing on differential relay parameters on page 3.
  • Protection Setting Relay - Page 4: Continues protection relay settings with specific focus on REF and CT settings for bay transformer on page 4.
  • Protection Setting Relay - Page 5: Concludes the report with additional settings related to AVR (Automatic Voltage Regulator) and the final evaluations on page 5.

PT.

ABB SAKTI INDUSTRI GI 150kV PELANGGAN BAY TRANSFORMER


PT. STAR AJIBARANG PURWOKERTO

PROTECTION SETTING RELAY


PARAMETER EVALUATION OF PROTECTION RELAY SETTING FOR BAY TRANSFORMER

Evaluation Setting Relay Proposed Setting Remarks


Type Relay OCR/GFR
HV Side
OCR HV Side (150kV)
Type ABB REF 615
Setting Group 1 Yes
Iset I> 0,77 x In
Operating Time 0,3
Operating Curve SI-IEC

Setting Group 1 Yes


Iset I>> High set 7,02 x In
Operating Time 40 ms
Operating Curve Instantaneous Time

GFR HV Side (150kV)


Setting Group 1 On
Iset I0> 0,15 x In
Operating Time 0,55 TMS
Operating Curve SI-IEC

Setting Group 1 Off


Iset I0>> High set x In
Operating Time ms
Operating Curve

Page : 1 of 5
PT. ABB SAKTI INDUSTRI GI 150kV PELANGGAN BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

PROTECTION SETTING RELAY


PARAMETER EVALUATION OF PROTECTION RELAY SETTING FOR BAY TRANSFORMER

Evaluation Setting Relay Proposed Setting Remarks


Type Relay OCR/GFR
LV Side
OCR LV Side (10,5kV)
Type ABB REF 615
Setting Group 1 Yes
Iset I> 0,82 (4,10 A) x In
Operating Time 0,16 TMS
Operating Curve SI-IEC

Setting Group 1 Yes


Iset I>> High set 5,16 (25,8 A) x In
Operating Time 0,1 s
Operating Curve IEC Def Time

Setting Group 1 Off


Iset I>>> High set x In
Operating Time s
Operating Curve

GFR LV Side (10,5kV)


Setting Group 1 On
Iset I0> 0,14 (0,69 A) x In
Operating Time 0,32 TMS
Operating Curve SI-IEC

Setting Group 1 Off


Iset I0>> High set x In
Operating Time ms
Operating Curve IEC Def Time

Setting Group 1 Off


Iset I0>>> High set x In
Operating Time ms
Operating Curve IEC Def Time

Page : 2 of 5
PT. ABB SAKTI INDUSTRI GI 150kV PELANGGAN BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

PROTECTION SETTING RELAY


PARAMETER EVALUATION OF PROTECTION RELAY SETTING FOR BAY TRANSFORMER

Evaluation Setting Relay Proposed Setting Remarks


Type Relay 87T/87N

Differential Trafo (T2W)


Type ABB RET 670
Setting Group 1 Yes
IdMin 0,3 IB
Slope Section 2 20 %
Slope Section 3 80 %
End Section -1 1,2 IB
End Section -2 3 IB
Ih-2 15 %
Ih-5 30 %
Cross Block On
Neg Seq On
IdAlarm 0,15 IB
t delay Alarm 10 s
Neg SeqROA 60 deg
IdUnre 10 IB

Page : 3 of 5
PT. ABB SAKTI INDUSTRI GI 150kV PELANGGAN BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

PROTECTION SETTING RELAY


PARAMETER EVALUATION OF PROTECTION RELAY SETTING FOR BAY TRANSFORMER

Evaluation Setting Relay Proposed Setting Remarks


Type Relay 87T/87N

REF-1
Type ABB RET 670
Setting Group 1 Yes
IdMin 0,19 %IB
Ibase 300 A
CTFactorPri1 1
CTFactorPri2 1
CTFactorSec1 1
CTFactorSec2 1

REF-2
Type ABB RET 670
Setting Group 1 Yes
IdMin 1 %IB
Ibase 4000 A
CTFactorPri1 1
CTFactorPri2 1
CTFactorSec1 1
CTFactorSec2 1

Page : 4 of 5
PT. ABB SAKTI INDUSTRI GI 150kV PELANGGAN BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

PROTECTION SETTING RELAY


PARAMETER EVALUATION OF PROTECTION RELAY SETTING FOR BAY TRANSFORMER

Evaluation Setting Relay Proposed Setting Remarks


Type Relay 84
CT : 4000/5 A In = 5A
VT : 10,5kV/100V Vn = 100V

AVR (Automatic Voltage Regulator)


Type ABB RET 670
Setting Group 1 Yes
Bandwith 1,5 %
Delay T1 40 s
T1 Linear Linear
Delay T2 10 s
Over voltage 110 %
Under voltage 90 %
Over Current 120 %
Norm Transf Voltage 10,5 kV
Current 4000 A
Under voltage Block On
Under voltage Delay 5 s
CT Terminals 5 A
Volatge Level 100 v

Page : 5 of 5