Válvula de Controle Sansom E83843en
Válvula de Controle Sansom E83843en
Old design
New design
These mounting and operating instructions assist you in mounting and operating the device
safely. The instructions are binding for handling SAMSON devices.
ÎÎ For the safe and proper use of these instructions, read them carefully and keep them for
later reference.
ÎÎ If you have any questions about these instructions, contact SAMSON‘s After-sales Service
Department (aftersalesservice@[Link]).
The mounting and operating instructions for the devices are included in
the scope of delivery. The latest documentation is available on our website
at [Link] > Service & Support > Downloads > Documentation.
! DANGER ! NOTICE
Hazardous situations which, if not avoided, Property damage message or malfunction
will result in death or serious injury
Note
! WARNING Additional information
Hazardous situations which, if not avoided,
could result in death or serious injury
Tip
Recommended action
2 EB 8384-3 EN
Contents
EB 8384-3 EN 3
Contents
4 EB 8384-3 EN
Contents
EB 8384-3 EN 5
Note
The functions of the EXPERTplus Valve Diagnostics are described in the Operating
Instructions u EB 8389. EB 8389 is included on the enclosed CD-ROM and is available
on our website.
6 EB 8384-3 EN
Safety instructions and measures
EB 8384-3 EN 7
Safety instructions and measures
Safety features
Upon failure of the air supply or electric signal, the positioner vents the actuator, causing the
valve to move to the fail-safe position determined by the actuator.
Explosion protection
−− Explosive dust atmospheres of zone 21 or zone 22
The following applies to type of protection Ex i in combustible dust atmospheres:
If intrinsic safety is impaired by the influence of dust, an enclosure complying with
Clause 6.1.3 of EN 60079-11 with at least in degree of protection IP 5X must be used.
The requirements according to Clause 6.1.3 apply to the cable glands accordingly. The
degree of ingress protection is verified by a test according to IEC 60529 and EN 60079-
0 (e.g. performed by VDE).
For use in the presence of combustible dust in compliance with type of protection
Ex tb IIIC (protection by enclosure), observe Clause 5.6.3 of EN 60079-14.
8 EB 8384-3 EN
Safety instructions and measures
EB 8384-3 EN 9
Safety instructions and measures
Referenced documentation
The following documents apply in addition to these mounting and operating instructions:
−− Operating instructions for valve diagnostics: u EB 8389
−− The mounting and operating instructions of the components on which the positioner is
mounted (valve, actuator, valve accessories, etc.).
10 EB 8384-3 EN
Safety instructions and measures
! DANGER
EB 8384-3 EN 11
Safety instructions and measures
! NOTICE
Incorrect assignment of the terminals will damage the positioner and will lead to mal-
function.
For the positioner to function properly, the prescribed terminal assignment must be ob-
served.
ÎÎ Connect the electrical wiring to the positioner according to the prescribed terminal
assignment.
12 EB 8384-3 EN
Markings on the device
2.1 Nameplate
Input 3
4 4
Diagnostics EXPERTplus
See technical data for ambient temperature
Firmware 5
Diagnostics EXPERTplus
Model 3730 - 3 6
7 Serial no. 8
Firmware 5
Var.-ID
Model 3730 - 3 6
SAMSON AG D-60314 Frankfurt Made in Germany
Var.-ID 7 Serial no. 8
SAMSON AG D-60314 Frankfurt Made in Germany
1 Supply pressure
2 Type of protection for explosion-protected devices 5 Firmware version (see section 2.3)
3 Input signal 6 Model no.
4 Features: Yes/ No 7 Configuration ID
−− Fault indicator 8 Serial number
−− Position indicator 9 Compliance
−− Analog input signal x
−− Binary input
−− Leakage detection
−− Limit switch, inductive
−− Limit switches, software
−− Solenoid valve
EB 8384-3 EN 13
Markings on the device
14 EB 8384-3 EN
Markings on the device
Positioner Type 3730-3 x x x x x x x x 0 x 0 0 x 0 x x
Special application
Without 0
Device completely free of paint-impairing substances 1
Exhaust air with ¼ NPT connection, back of housing sealed 2
Attachment according to VDI/VDE 3847 including interface 6
Attachment according to VDI/VDE 3847 prepared for interface 7
Special version
Without 0 0
IECEx Ex ia IIC T6...T4 Gb; Ex ia IIIC T80°C Db 1 1 2
Ex tb IIIC T80°C Db 5 3 4
Ex nA IIC T6 Gc, Ex tc IIIC T80°C Dc 8 1 3
EAC Ex 1Ex ia IIC T6...T4 Gb; Ex ia IIIC T80°C Db; Ex tb IIIC T80°C Db 1 1 4
2Ex ic IIC T6...T4 Gc; 2Ex nA IIC T6...T4 Gc X; Ex tc IIIC T80°C Dc X 8 2 0
EB 8384-3 EN 15
Markings on the device
Firmware revisions
Old New
1.30 1.40
All EXPERTplus functions can be used over HART® communication in this firmware ver-
sion and higher.
The fault alarm contact is triggered by the condensed state of the positioner.
It is always active with 'Maintenance alarm' condensed state.
• When Code 32 = YES: also active with 'Function check' condensed state
• When Code 33 = YES: also active with 'Maintenance required/Maintenance de-
manded' condensed state
The "Function check" condensed state is additionally set for Test A1, A2, fault alarm out-
put and position transmitter.
The min./max. values of the temperature monitoring can be reset.
1.40 1.41
Internal revisions
1.41 1.42
Internal revisions
1.42 1.51
All EXPERTplus diagnostic functions are available without having to activate them in the
positioner (u EB 8389 on EXPERTplus Valve Diagnostics).
Optional binary input with following actions:
• Transmit switching state
• Activate local write protection
• Switch between automatic and manual modes
• Various diagnostic functions u EB 8389 (EXPERTplus valve diagnostics)
The pressure limit (Code 16) is no longer automatically set during initialization.
1.51 1.54
Internal revisions
1.54 1.55
Analog input x option to connect commercially available position sensors with a 4 to
20 mA signal
Code 4: the setting for 300 mm has been added to the pin position
1.55 1.56
Internal revisions
1.56 1.61
Additional function: the step response test can be started by a rising edge at the binary
input (u EB 8389 on EXPERTplus valve diagnostics).
16 EB 8384-3 EN
Design and principle of operation
3 Design and principle of oper- (output variable y) is produced for the actua-
tor.
ation
The positioner consists of a travel sensor sys-
ÎÎ Refer to Fig. 1 tem (2) proportional to resistance, an analog
The electropneumatic positioner is mounted i/p converter with a downstream air capacity
on pneumatic control valves and is used to booster (7) and the electronics with microcon-
assign the valve position (controlled vari- troller (5).
able x) to the control signal (set point w). The The positioner is fitted with three binary con-
electric signal from a controlling system is tacts as standard: A fault alarm output indi-
compared to the travel or the rotational angle cates a fault to the control room and two con-
of the control valve and a signal pressure figurable software limit switches are used to
indicate the end positions of the valve.
1 Control valve
22
BE 2 Travel sensor
3 PD controller
Serial
20 16 4 A/D converter
Interface
13 5 Microcontroller
21 FSK mm
% A3 6 i/p converter
S 7 Air capacity booster
15
4 5 8 Pressure regulator
w 19 A2
9 Flow regulator
14
10 Volume restriction
A1 11* Inductive limit switch
14 12* Solenoid valve
24 V DC w
13* Analog position transmitter
PD
x 2 11 14 Software limit switch, alarm
17 18 3 1/2
15 Fault alarm output, alarm 3
12 G G
16 Display
6 17* Actuation of solenoid valve
9
18* Electrical insulation
19 D/A converter
8 10 20 Communication interface
1
y 21 HART® connection
Q x 22 Binary input BE*
7
* Option
EB 8384-3 EN 17
Design and principle of operation
18 EB 8384-3 EN
Design and principle of operation
EB 8384-3 EN 19
Design and principle of operation
Note
The HART® device revision as well as the in-
3.5 Device overview and oper-
dicating and operating modules supported ating controls
by the Type 3730-3 Positioner can be found ÎÎ See section 6.
on the SAMSON website (u [Link].
de > SERVICE & SUPPORT > Downloads >
Device integration > 3730-3 > 'Device Revi-
sion' to 'Firmware' assignment).
20 EB 8384-3 EN
Design and principle of operation
3.6 Accessories
Table 1: General accessories
Designation Order no.
Reversing amplifier for double-acting actuators Type 3710
Black plastic (6 to 12 mm clamping range) 8808-1011
Blue plastic (6 to 12 mm clamping range) 8808-1012
Cable gland M20x1.5 Nickel-plated brass (6 to 12 mm clamping range) 1890-4875
Nickel-plated brass (10 to 14 mm clamping range) 1922-8395
Stainless steel 1.4305 (8 to 14.5 mm clamping range) 8808-0160
Powder-coated aluminum 0310-2149
Adapter M20x1.5 to ½ NPT
Stainless steel 1400-7114
S 0510-0522
M 0510-0510
Lever L 0510-0511
XL 0510-0512
XXL 0510-0525
Retrofit kit for inductive limit switch 1 x SJ2-SN 1402-1770
Isolated USB interface adapter (SAMSON SSP interface to USB port) inc. TROVIS-VIEW CD-ROM 1400-9740
Serial interface adapter (SAMSON SSP interface to RS-232 port on a computer) 1400-7700
TROVIS-VIEW 6661 (download available: u [Link] > SERVICE & SUPPORT > Downloads > TROVIS-VIEW)
EB 8384-3 EN 21
Design and principle of operation
22 EB 8384-3 EN
Design and principle of operation
EB 8384-3 EN 23
Design and principle of operation
24 EB 8384-3 EN
Design and principle of operation
Attachment to Size AA5, heavy-duty version (e.g. Air Torque 10 000) 1400-9992
rotary actuators Bracket surface corresponds to fixing level 2, heavy-duty
1400-9974
version
SAMSON Type 3278 with 160 cm² and VETEC Type S160 and Type R, heavy-du-
1400-9385
ty version
1400-5891
SAMSON Type 3278 with 320 cm² and VETEC Type S320, heavy-duty version and
1400-9974
G ¼ 1400-7461
Connecting plate (6)
¼ NPT 1400-7462
G ¼ 1400-7458
Pressure gauge bracket (7)
Accessories for ¼ NPT 1400-7459
positioner Stainless steel/brass 1402-0938
Pressure gauge mounting kit up to max.
6 bar (output/supply) Stainless steel/stainless steel 1402-0939
Bracket to mount the positioner on a wall (Note: The other fastening parts are to
0309-0184
be provided at the site of installation as wall foundations vary from site to site).
1) Only new connecting plates can be used with new actuators (Index 01). Old and new plates are not interchange-
able.
EB 8384-3 EN 25
Design and principle of operation
Note
The M lever is included in the scope of delivery.
S, L, XL levers for attachment according to IEC 60534-6 (NAMUR) are available as
accessories (see Table 4 on page 23). The XXL lever is available on request.
26 EB 8384-3 EN
Design and principle of operation
EB 8384-3 EN 27
Design and principle of operation
The technical data for the explosion-protected devices may be restricted by the
Type 3730-3 Positioner
limits specified in the test certificates.
Temperature ≤0.15 %/10 K
Influences Supply air None
Effect of vibration ≤ 0.25 % up to 2000 Hz and 4 g according to IEC 770
Complying with EN 61000-6-2, EN 61000-6-3, EN 61326-1 and NAMUR
Electromagnetic compatibility
Recommendation NE 21
One M20x1.5 cable gland for 6 to 12 mm clamping range
Electrical connections Second M20x1.5 threaded connection additionally available
Screw terminals for 0.2 to 2.5 mm² wire cross-section
Degree of protection IP 66/NEMA 4X
Observing the requirements of IEC 61508, the systematic capability of the pilot
Use in safety-instrumented
valve for emergency venting as a component in safety-instrumented systems is
systems (SIL)
given.
Emergency venting at 0 mA set
Use is possible on observing the requirements of IEC 61511 and the required
point and using optional
hardware fault tolerance in safety-instrumented systems up to SIL 2 (single device/
solenoid valve
HFT = 0) and SIL 3 (redundant configuration/HFT = 1).
Explosion protection Refer to Table 14
Communication (local) SAMSON SSP interface and serial interface adapter
Software requirements (SSP) TROVIS-VIEW with database module 3730-3
HART® field communication protocol
Communication (HART®) Impedance in HART® frequency range: Receiving 350 to 450 Ω · Sending approx.
115 Ω
For handheld
Device description for Type 3730-3
Software communicator
require- DTM file according to specification 1.2, suitable for integrating the device into
ments For computer frame applications that support the use of FDT/DTM (e.g. PACTware); other
integrations (e.g. AMS, PDM) available
Binary contacts
For connection to the binary input of the PLC acc.
to IEC 61131-2, Pmax = 400 mW or for connection NAMUR switching amplifier
For connection to
to NAMUR switching amplifier acc. to EN 60947- acc. to EN 60947-5-6
5-6
Two software limit switches, reverse polarity protection, floating, configurable switching characteristics (default set-
tings in table)
Version No explosion protection Ex
Signal
No response Non-conductive ≤1.0 mA
state
Response Conductive (R = 348 Ω) ≥2.2 mA
28 EB 8384-3 EN
Design and principle of operation
The technical data for the explosion-protected devices may be restricted by the
Type 3730-3 Positioner
limits specified in the test certificates.
One fault alarm contact, floating
Version No explosion protection Ex
Signal
No fault alarm Conductive (R = 348 Ω) ≥2.2 mA
state
Fault alarm Blocked ≤1.0 mA
Materials
Die-cast aluminum EN AC-AlSi12(Fe) (EN AC-44300) acc. to DIN EN 1706,
Housing
chromated and powder paint coated · Special version: stainless steel 1.4408
External parts Stainless steel 1.4404/316L
Cable gland M20x1.5, black polyamide
Die-cast aluminum housing: approx. 1.0 kg
Weight
Stainless steel housing: approx. 2.2 kg
Compliance ·
EB 8384-3 EN 29
Design and principle of operation
30 EB 8384-3 EN
Design and principle of operation
Number ZETC/17/2018
0Ex ia IIC T6X;
STCC Date 2018-04-27
-3
2Ex s II T6 X
Valid until 2021-04-26
Number RU C-DE.AA87.B.01278
1Ex ia IIC T6...T4 Gb;
Date 2018-11-30 Ex ia IIIC T80°C Db;
Ex tb IIIC T80°C Db
Valid until 2023-11-29
Number A/P/HQ/MH/104/1116
Number 11-KB4BO-0224
Number GYJ17.1408X
Ex ic IIC T4~T6 Gc;
NEPSI Date 2017-11-21 Ex nA IIC T4~T6 Gc;
Ex tD A22 IP66 T80°C
Valid until 2022-11-20
EB 8384-3 EN 31
Design and principle of operation
Number RU C-DE.AA87.B.01278
3730
Number GYJ17.1408X
Ex ic IIC T4~T6 Gc;
NEPSI Date 2017-11-21 Ex nA IIC T4~T6 Gc;
Ex tD A22 IP66 T80°C
Valid until 2022-11-20
32 EB 8384-3 EN
Design and principle of operation
3.8 Dimensions in mm
External position
sensor
28
15
46
70
70
34
70
Direct attachment
212
89
85
34
58
14
40 28
85
164
EB 8384-3 EN 33
Design and principle of operation
164
24
62
164
83
62
164
34 EB 8384-3 EN
Design and principle of operation
EB 8384-3 EN 35
Design and principle of operation
Heavy-duty version
52
80
56
Reversing amplifier 1)
86
80
30
130
86
Ø101 166
Light version
50
76
80
49
59
Reversing amplifier 1)
79
50
130
150
1) Reversing amplifier
−−Type 3710 (see drawing of heavy-duty version for dimensions)
−−1079-1118/1079-1119, no longer available
(see drawing of light version for dimensions)
36 EB 8384-3 EN
Design and principle of operation
Lever
z
10...17
y
x
16
Lever x y z
S 17 mm 25 mm 33 mm
M 25 mm 50 mm 66 mm
L 70 mm 100 mm 116 mm
XL 100 mm 200 mm 216 mm
XXL 200 mm 300 mm 316 mm
Actuator
Dimensions in mm
Ød
EB 8384-3 EN 37
38 EB 8384-3 EN
Measures for preparation
EB 8384-3 EN 39
40 EB 8384-3 EN
Mounting and start-up
5 Mounting and start-up −−Do not mount the positioner with the back
of the device facing upward.
−−Do not seal or restrict the vent opening
! NOTICE
when the device is installed on site.
Risk of malfunction due to incorrect mounting
parts/accessories. ÎÎObserve mounting position (see Fig. 3).
Only use the mounting parts and accessories
ÎÎDo not seal or restrict the vent opening
listed in these mounting and operating in-
(see Fig. 2) when the device is installed
structions to mount and install the positioner.
on site.
Pay attention to the type of attachment.
! NOTICE
Risk of damage to the positioner due to in-
correct mounting position.
EB 8384-3 EN 41
Mounting and start-up
42 EB 8384-3 EN
Mounting and start-up
Vent opening
!
Fig. 3: Permissible mounting Fig. 4: M lever with pin position 35
positions
2
1.1
1.2
1 Lever
1 1.1 Nut
1.2 Disk spring
2 Follower pin
EB 8384-3 EN 43
Mounting and start-up
5.3 Direct attachment Make sure that the gasket (14) points to-
wards the actuator yoke.
5.3.1 Type 3277-5 Actuator 5. 15 mm travel: Keep the follower pin (2)
ÎÎ Required mounting parts and accesso- on the M lever (1) on the back of the po-
ries: Table 2 on page 21. sitioner in the pin position 35 (delivered
state).
ÎÎ Observe travel tables on page 26.
7.5 mm travel: Remove the follower pin
Actuator with 120 cm² (see Fig. 6) (2) from the pin position 35, reposition it
Depending on the type of positioner attach- in the hole for pin position 25 and screw
ment, the signal pressure is routed either left tight.
or right of the yoke through a hole to the ac- 6. Insert formed seal (15) into the groove of
tuator diaphragm. Depending on the fail- the positioner housing and insert the seal
safe action of the actuator "actuator stem ex- (10.1) on the back of the housing.
tends" or "actuator stem retracts" (valve clos- 7. Place positioner on the cover plate (10)
es or opens upon supply air failure), the swi- in such a manner that the follower pin
tchover plate (9) must first be attached to the (2) rests on the top of the follower clamp
actuator yoke. Align the switchover plate (3). Adjust the lever (1) correspondingly
with the corresponding symbol for left or and open the positioner cover to hold the
right attachment according to the marking positioner shaft in position at the cap or
(view looking onto the switchover plate). rotary pushbutton. The lever (1) must rest
1. Mount connecting plate (6) or pressure on the follower clamp with spring force.
gauge bracket (7) with pressure gauges Mount the positioner on the cover plate
on the positioner, making sure the two (10) using the two fixing screws.
seals (6.1) are seated properly.
2. Remove screw plug (4) on the back of Note
the positioner and seal the signal pres- The following applies to all types of attach-
sure output (38) on the connecting plate ment except for direct attachment to
(6) or on the pressure gauge bracket (7) Type 3277-5: the signal pressure output at
with the stopper (5) included in the ac- the back must be sealed by the screw plug
cessories. (4, order no. 0180-1436) and the associat-
3. Place follower clamp (3) on the actuator ed O-ring (order no. 0520-0412) (delivered
stem, align it and screw tight so that the state, parts included in the scope of deliv-
mounting screw is located in the groove ery).
of the actuator stem.
8. Mount cover (11) on the other side.
4. Mount cover plate (10) with narrow side
Make sure that the vent plug is located at
of the cut-out (Fig. 6, on the left) pointing
the bottom when the control valve is in-
towards the signal pressure connection.
44 EB 8384-3 EN
Mounting and start-up
1.1
1.2
Cut-out of
cover plate
10.1
9 11
6.1 10
6
6
5 ! NOTICE
Fig. 6: Direct attachment – Signal pressure connection for Type 3277-5 Actuator with 120 cm²
EB 8384-3 EN 45
Mounting and start-up
stalled to allow any condensed water 5. Place positioner on the cover plate in
that collects to drain off. such a manner that the follower pin (2)
rests on the top of the follower clamp (3).
5.3.2 Type 3277 Actuator Adjust the lever (1) correspondingly and
open the positioner cover to hold the po-
ÎÎ Required mounting parts and accesso- sitioner shaft in position at the cap or ro-
ries: Table 3 on page 22. tary pushbutton. The lever (1) must rest
ÎÎ Observe travel tables on page 26. on the follower clamp with spring force.
Mount the positioner on the cover plate
Actuators with 175 to 750 cm² effective ar-
(10) using the two fixing screws.
eas (see Fig. 7)
6. Make sure that the tip of the gasket (16)
Mount the positioner on the yoke. The signal
projecting from the side of the connec-
pressure is routed to the actuator over the
tion block is positioned to match the ac-
connection block (12), for actuators with fail-
tuator symbol for the actuator's fail-safe
safe action "actuator stem extends" internal-
action "actuator stem extends" or "actu-
ly through a hole in the valve yoke and for
ator stem retracts". If this is not the case,
"actuator stem retracts" through an external
unscrew the three fastening screws and
pipe.
lift off the cover. Turn the gasket (16) by
1. Place follower clamp (3) on the actuator 180° and re-insert it.
stem, align it and screw tight so that the The old connection block version (Fig. 7,
mounting screw is located in the groove bottom) requires the switch plate (13) to
of the actuator stem. be turned to align the actuator symbol
2. Mount cover plate (10) with narrow side with the arrow marking.
of the cut-out (Fig. 7, on the left) pointing 7. Place the connection block (12) with the
towards the signal pressure connection. associated seals against the positioner
Make sure that the gasket (14) points to- and the actuator yoke and fasten using
wards the actuator yoke. the screw (12.1). For actuators with fail-
3. For actuators with 355, 700 or 750 cm², safe action "actuator stem retracts", ad-
remove the follower pin (2) on the M le- ditionally remove the stopper (12.2) and
ver (1) on the back of the positioner from mount the external signal pressure pipe.
pin position 35, reposition it in the hole 8. Mount cover (11) on the other side.
for pin position 50 and screw tight. Make sure that the vent plug is located at
For actuators 175, 240 and 350 cm² the bottom when the control valve is in-
with 15 mm travel, keep the follower pin stalled to allow any condensed water
(2) in pin position 35. that collects to drain off.
4. Insert formed seal (15) into the groove of
the positioner housing.
46 EB 8384-3 EN
Mounting and start-up
2
M lever
1.1
1.2
Cut-out of
cover plate (10)
View C
16 View A 16
G
C
SUPPLY
G 3/8
SUPPLY
Actuator stem 16 12 12.1 12.2
Retracts Extends A
View B
Connection
13 block (old) with
12 switch plate (13)
SUPPLY Actuator stem retracts B
Fig. 7: Direct attachment – Signal pressure connection for Type 3277 Actuator with 175 to 750 cm²
EB 8384-3 EN 47
Mounting and start-up
The positioner is attached to the control valve 4. Select required lever size (1) M, L or XL
using a NAMUR bracket (10). and pin position according to the actua-
tor size and valve travel listed in the trav-
1. Screw the two bolts (14) to the bracket
el table on page 26.
(9.1) of the stem connector (9), place the
follower plate (3) on top and use the Should a pin position other than position 35
screws (14.1) for fastening. with the standard M lever be required or an
L or XL lever size be required, proceed as
Actuator sizes 2800 cm² and 1400 cm²
follows:
with 120 mm travel:
−− For a travel of 60 mm or smaller, −− Fasten the follower pin (2) in the as-
screw the longer follower plate (3.1) signed lever hole (pin position as speci-
directly to the stem connector (9). fied in the travel table). Only use the lon-
−− For a travel exceeding 60 mm, mount ger follower pin (2) included in the
the bracket (16) first and then the fol- mounting kit.
lower plate (3) to the bracket togeth- −− Place the lever (1) on the shaft of the po-
er with the bolts (14) and screws sitioner and fasten it tight using the disk
(14.1). spring (1.2) and nut (1.1).
2. Mount NAMUR bracket (10) to the con- Move lever once all the way as far as it
trol valve as follows: will go in both directions.
−− For attachment to the NAMUR rib, 5. Place positioner on the NAMUR bracket
use an M8 screw (11) and toothed in such a manner that the follower pin
lock washer directly in the yoke hole. (2) rests in the slot of the follower plate
−− For attachment to valves with rod- (3, 3.1). Adjust the lever (1) correspond-
type yokes, use two U-bolts (15) ingly.
around the yoke. Align the NAMUR Screw the positioner to the NAMUR
bracket (10) according to the em- bracket using its two fastening screws.
bossed scale so that the follower
plate (3) is shifted by half the angle
range to the NAMUR bracket (the
48 EB 8384-3 EN
Mounting and start-up
15
11
Attachment to
NAMUR rib
10
9
9.1
3.1
Additional bracket for
16
actuators with 2800 cm²
and travel ≥ 60 mm
14
1 3
XL and L lever 1
1 Lever 14.1
1.1 Nut
1.2 Disk spring
2 Follower pin 2
3 Follower plate
1.1
3.1 Follower plate 6.1 6 7 8
1.2
6 Connecting plate
6.1 Seals 1
7 Pressure gauge bracket
8 Pressure gauge
mounting kit
9 Stem connector
9.1 Bracket
10 NAMUR bracket
11 Screw
14 Bolt
14.1 Screws
15 U-bolt
! NOTICE
16 Bracket
Only use the connecting plate (6) included in the accessories to
connect supply and output.
Never screw threaded parts directly into housing.
EB 8384-3 EN 49
Mounting and start-up
50 EB 8384-3 EN
Mounting and start-up
1.1
1.2 13.1
11
1
11.1
3 12
12.1
20
Exh.
2
19
1.1
1.2
1 Lever 6 6.2 6.1
1
1.1 Nut
1.2 Disk spring 4
2 Follower pin
3 Follower clamp 12.1 Seal
4 Screw plug 13 Adapter block 5
5 Stopper 13.1 Screws
6 Adapter bracket 17 Turnboard
6.1 Screws 17.1 Formed seal
6.2 Formed seal 17.2 Screws 6.3
6.3 Screws 18 Dummy plate
11 Cover 18.1 Screws
11.1 Vent plug 19 Air blocker
12 Connecting plate 20 Retaining screw
EB 8384-3 EN 51
Mounting and start-up
7. Insert the screws (13.1) through the mid- Place positioner on the adapter block
dle holes of the adapter block (13). (13) in such a manner that the follower
8. Place the connecting plate (12) together pin (2) rests on the top of the follower
with the seal (12.1) onto the screws clamp (3). Adjust the lever (1) corre-
(13.1) corresponding to the fail-safe ac- spondingly and open the positioner cov-
tion "actuator stem extends" or "actuator er to hold the positioner shaft in position
stem retracts". The fail-safe action that at the cap or rotary pushbutton.
applies is determined by aligning the The lever (1) must rest on the follower
groove of the adapter block (13) with the clamp with spring force.
groove of the connecting plate (12) Fasten the positioner to the adapter block
(Fig. 10). (13) using the two fastening screws (6.3).
Actuator stem Make sure the formed seal (6.2) is prop-
extends retracts erly seated.
12. Mount cover (11) on the other side to the
yoke. Make sure that the vent plug is lo-
12 Connecting plate
Z cated at the bottom when the control
13 Adapter block
valve is installed to allow any condensed
water that collects to drain off.
12
13
52 EB 8384-3 EN
Mounting and start-up
Attachment to NAMUR rib (see Fig. 11) is placed around the yoke: screw the four
ÎÎ Required mounting parts and accesso- studs into the NAMUR connection block
ries: Table 5 on page 23. (10). Place the NAMUR connection block
on the rod and position the formed plate
ÎÎ Observe travel tables on page 26.
(15) on the opposite side. Use the nuts
1. Series 240 Valves, actuator size up to and toothed lock washers to fasten the
1400-60 cm²: Screw the two bolts (14) formed plate onto the studs. Align the
to the bracket of the stem connector or marking on the NAMUR valve connec-
directly to the stem connector (depending tion (on the side marked '1') to 50 %
on the version), place the follower plate travel.
(3) on top and use the screws (14.1) to
3. Place the adapter bracket (6) on the po-
fasten it.
sitioner and mount using the screws
Type 3251 Valve, 350 to 2800 cm²: (6.1). Make sure that the seals are cor-
Screw the longer follower plate (3.1) to rectly seated. For positioners with air
the bracket of the stem connector or di- purging, remove the stopper (5) before
rectly to the stem connector (depending mounting the positioner. For positioners
on the version). without air purging, replace the screw
Type 3254 Valve, 1400-120 to 2800 plug (4) with a vent plug.
cm²: Screw the two bolts (14) to the 4. Select required lever size (1) M, L or XL
bracket (16). Fasten the bracket (16) on- and pin position according to the actua-
to the stem connector, place the follower tor size and valve travel listed in the trav-
plate (3) on top and use the screws el table on page 26.
(14.1) to fasten it.
Should a pin position other than position 35
Mount the positioner on the NAMUR rib with the standard M lever be required or an
as shown in Fig. 11. L or XL lever size be required, proceed as
2. For attachment to the NAMUR rib, fas- follows:
ten the NAMUR connection block (10) −− Fasten the follower pin (2) in the as-
directly into the existing yoke bore using signed lever hole (pin position as speci-
the screw and toothed lock washer (11). fied in the travel table). Only use the lon-
Align the marking on the NAMUR valve ger follower pin (2) included in the
connection (on the side marked '1') to mounting kit.
50 % travel.
−− Place the lever (1) on the shaft of the po-
For attachment to valves with rod-type sitioner and fasten it tight using the disk
yokes using the formed plate (15), which spring (1.2) and nut (1.1).Move lever
EB 8384-3 EN 53
Mounting and start-up
once all the way as far as it will go in adapter block to the signal pressure con-
both directions. nection of the actuator. Seal the Y2 port
5. Insert the formed seal (6.2) in the groove with a blanking plug.
of the adapter bracket. For double-acting actuators and actua-
6. Insert the formed seal (17.1) into the tors with air purging, connect the Y2
turnboard (17) and mount the turnboard port of the adapter block to the signal
to the adapter block (13) using the pressure connection of the second actua-
screws (17.2). tor chamber or spring chamber of the
actuator.
7. Mount the blank plate (18) to the turn-
board using the screws (18.1). Make
sure that the seals are correctly seated. 5.6 Attachment according to
VDI/VDE 3847-2
Note Attachment according to VDI/VDE 3847-2
A solenoid valve can also be mounted in for PFEIFFER SRP (single-acting) and DAP
place of the blank plate (18). The orientation (double-acting) rotary actuators in sizes 60
of the turnboard (17) determines the mount- to 1200 with NAMUR interface and air
ing position of the solenoid valve. Alterna- purging of the actuator's spring chamber al-
tively, a restrictor plate can be mounted lows the direct attachment of the positioner
(u AB 11). without additional piping.
Additionally, the positioner can be replaced
8. Fasten the adapter block (13) to the
quickly while the process is running by
NAMUR connection block using the
blocking the air in single-acting actuators.
screws (13.1).
9. Insert the vent plug into the Exh. connec- Procedure to block the actuator in place
tion. (see Fig. 12):
10. Place the positioner on the adapter block 1. Unscrew the red retaining screw (1).
(13) in such a manner that the follower 2. Turn the air blocker (2) on the bottom of
pin (2) rests on the top of the follower the adapter block according to the in-
plate (3, 3.1). Adjust the lever (1) corre- scription.
spondingly.
Fasten the positioner to the adapter block
(13) using the two fastening screws (6.3).
Make sure the formed seal (6.2) is prop-
erly seated.
11. For single-acting actuators without air
purging, connect the Y1 port of the
54 EB 8384-3 EN
Mounting and start-up
13 13.1
17.1 17 17.2
18
18.1
11
3 10
16
20
Exh.
19 14 3.1
1 Lever 14.1
1.1 Nut 3
1.2 Disk spring
2 Follower pin
3 Follower plate 1
3.1 Follower plate 13.1 Screws 1.1 2
4 Screw plug 14 Bolt 1.2 6 6.2 6.1
5 Stopper 14.1 Screws
6 Adapter bracket 15 Formed plate 4
6.1 Screws 16 Bracket
6.2 Formed seal 17 Turnboard
6.3 Screws 17.1 Formed seal 5
10 NAMUR connection 17.2 Screws
block 18 Dummy plate
11 Screw with toothed 18.1 Screws
lock washer 19 Air blocker
6.3
13 Adapter block 20 Retaining screw
EB 8384-3 EN 55
Mounting and start-up
56 EB 8384-3 EN
Mounting and start-up
1 Adapter block
2 Fastening screws 2
3 Follower wheel
4 Adapter bracket 1
5 Fastening screws
6 Fastening screws
EB 8384-3 EN 57
Mounting and start-up
5.6.2 Version for double- ings (8) and terminal plate (9) onto the
adapter bracket using the associated fas-
acting actuator tening screws (10).
A reversing amplifier must be additionally ÎÎ Make sure that the seals are correctly
mounted for applications with double-acting seated.
(DAP) actuators or applications with sin- 8. Remove the vent plug at the adapter
gle-acting (SAP) actuators that include par- block and seal the opening with the G ¼
tial stroke testing. screw plug.
In this case, a special adapter bracket (4) is 9. Mount the turnboard marked 'Doppel'
required for mounting. for double-acting actuators or the turn-
ÎÎ Refer to Fig. 16. board marked 'PST' for single-acting ac-
1. Fasten the adapter block (1) to the actua- tuators with partial stroke testing. See
tor's NAMUR interface using the four Fig. 15.
fastening screws (2). ÎÎ Make sure that the seals are correctly
ÎÎ Make sure that the seals are correctly seated.
seated.
2. Mount the follower wheel (3) onto the ac-
tuator shaft. Use the matching adapter
(see Table 6 on page 24).
3. Place the adapter bracket (4) onto the
adapter block (1) and fasten it using the
fastening screws (5).
ÎÎ Make sure that the seals are correctly
seated.
4. Insert and fasten the follower pin into the
90° position on the positioner's lever (see
Fig. 13 on page 56).
5. Align the positioner on the adapter
bracket (1) in such a way that the follow-
er pin engages into the actuator's follow-
er wheel (3).
6. Fasten the positioner onto the adapter Fig. 15: Mounting the turnboard
bracket (4) using the fastening screws
(6).
7. Mount the Type 3710 Reversing Amplifi-
er (7) together with the two guide bush-
58 EB 8384-3 EN
Mounting and start-up
8
7
2 6
10
1
1 Adapter block
2 Fastening screws
3 Follower wheel
3 4 Adapter bracket
5 Fastening screws
6 Fastening screws
7 Reversing amplifier
8 Guide bushings
9 Terminal plate
10 Fastening screws
Fig. 16: Mounting on a double-acting actuator or single-acting actuator with partial stroke testing
EB 8384-3 EN 59
Mounting and start-up
11 11
11 Intermediate plate
Fig. 17: Intermediate plate for actuators in sizes 900 and 1200 for AA4 interface
60 EB 8384-3 EN
Mounting and start-up
12 Dummy plate
13 Solenoid valve
14 Turnboard
14
12 13
EB 8384-3 EN 61
Mounting and start-up
62 EB 8384-3 EN
Mounting and start-up
9.1
9.2
1 Lever
9.3 1.1 Nut
1.2 Disk spring
! NOTICE 1.1 2 Follower pin
Only use the connecting plate (6) 3 Follower plate
2 6 Connecting plate
included in the accessories to connect
supply and output. 6.1 Seals
7 Pressure gauge bracket
Never screw threaded parts directly 1.2 8 Pressure gauge
into housing.
1 mounting kit
S lever 9 Stem connector
6 9.1 Bracket
6.1
7
8
9.2 Bolt
9.3 Screws
10 Bracket
10.1 Screw
11 Hex bar
11.1 Screws
12.1 Screws
EB 8384-3 EN 63
Mounting and start-up
2. Place coupling wheel (4) with flat side nection side of the positioner housing
facing the actuator on the follower clamp (see section 5.9).
(3). Refer to Fig. 22 to align slot so that it 6. Unscrew the standard follower pin (2)
matches the direction of rotation when from the positioner's M lever (1). Use the
the valve is in its closed position. metal follower pin (Ø 5 mm) included in
3. Fasten the coupling wheel (4) and follow- the mounting kit and screw tight into the
er clamp (3) tightly onto the actuator hole for pin position 90°.
shaft using screw (4.1) and disk spring 7. Place positioner on the top bracket (10)
(4.2). and fasten tight. Taking the actuator's di-
4. Fasten the bottom pair of brackets (10.1) rection of rotation into account, adjust le-
with the bends pointing either facing to ver (1) so that it engages in the slot of
the inside or to the outside (depending the coupling wheel (4) with its follower
on the actuator size) onto the actuator pin (Fig. 22). It must be guaranteed that
housing. Position the top pair of brackets the lever (1) is parallel to the long side of
(10) and fasten. the positioner when the actuator is at
5. Mount connecting plate (6) or pressure half its angle of rotation.
gauge bracket (7) with pressure gauges 8. Stick the scale plate (4.3) on the coupling
on the positioner, making sure the two wheel so that the arrow tip indicates the
seals are seated properly. Double-acting closed position and it can be easily read
springless rotary actuators require the when the valve is installed.
use of a reversing amplifier on the con-
64 EB 8384-3 EN
Mounting and start-up
6.1
6
(7, 8)
10 1
1.2
1.1
2
10.1 4.3
4
5
! NOTICE
80 mm
Only use the connecting
plate (6) included in the ac-
cessories to connect supply
and output. 130 mm
Never screw threaded parts
directly into housing. Slot
EB 8384-3 EN 65
Mounting and start-up
place spacers (11) underneath, if neces- 4. Fasten coupling wheel (4) on the slotted
sary. actuator shaft or adapter (3) using screw
2. For SAMSON Type 3278 and VETEC (4.1) and disk spring (4.2).
S160 Rotary Actuators, fasten the 5. Unscrew the standard follower pin (2)
adapter (5) onto the free end of the shaft from the positioner's M lever (1). Attach
and for VETEC R Actuator, place on the the follower pin (Ø5 mm) included in the
adapter (5.1). For Type 3278, VE- mounting kit to pin position 90°.
TEC S160 and VETEC R Actuators, place 6. Mount connecting plate (6) for required
on the adapter (3), for VDI/VDE version, G ¼ connecting thread or pressure
only use the adapter when it is required gauge bracket (7) with pressure gauges
due to the actuator size. on the positioner, making sure the two
3. Stick adhesive label (4.3) onto the cou- seals (6.1) are seated properly. Dou-
pling in such a manner that the yellow ble-acting springless rotary actuators re-
part of the sticker is visible in the window quire the use of a reversing amplifier on
of the housing when the valve is OPEN. the connection side of the positioner
Adhesive labels with explanatory sym- housing (see section 5.9).
bols are enclosed and can be stuck on 7. For actuators with a volume of less than
the enclosure, if required. 300 cm³, screw the screw restriction (or-
der no. 1400-6964) into the signal pres-
sure output of the positioner (or the out-
Actuator turning
counterclockwise
put of the pressure gauge bracket or con-
necting plate).
1
8. Place positioner on housing (10) and
screw it tight. Taking the actuator's direc-
tion of rotation into account, adjust lever
(1) so that it engages in the correct slot
with its follower pin (Fig. 22).
10
4
Actuator turning
clockwise
66 EB 8384-3 EN
Mounting and start-up
4.1 4.1
4.2 4.2
4 4
4.3 4.3
3 3
5.1
10.1
10.1 10
11
10
5
EB 8384-3 EN 67
Mounting and start-up
Note
Note
The rubber seal (1.4) is not required and can
How the outputs are marked depends on the
be removed when the sealing plug is used.
reversing amplifier used:
−−Type 3710: Output 1/2 = Y1/Y2
6. After initialization, set Code 16 (Pressure
−−1079-1118 and 1079-1119:
limit) to No.
Output 1/2 = A1/A2
68 EB 8384-3 EN
Mounting and start-up
A1 Z
A2
Z
Output 38
A1
EB 8384-3 EN 69
Mounting and start-up
70 EB 8384-3 EN
Mounting and start-up
EB 8384-3 EN 71
Mounting and start-up
6. Place the mounting plate together with 7. Mount cover (11) on the other side.
the sensor onto the actuator yoke so that Make sure that the vent plug is located at
the follower pin (2) rests on the top of the the bottom when the control valve is in-
follower clamp (3). It must rest on it with stalled to allow any condensed water
spring force. Fasten the mounting plate that collects to drain off.
(21) onto the actuator yoke using both
fixing screws.
2
3
11
1.1
1.2
20
21
9 Signal pressure
Vent plug
Fig. 26: Mounting for Type 3277-5 Actuator (left) and Type 3277 Actuator (right)
72 EB 8384-3 EN
Mounting and start-up
5.10.2 Mounting the position 120 to 350 cm² actuators with 15 mm rated
travel. For other actuator sizes or travels, se-
sensor with attachment lect the lever and pin position from the travel
according to table in section 3.6.1. L and XL levers are in-
IEC 60534-6 cluded in the mounting kit.
ÎÎ Required mounting parts and accesso- 3. Place the lever (1) and disk spring (1.2)
ries: Table 8 on page 25. on the sensor shaft. Place the lever in
mid-position and hold it in place. Screw
ÎÎ Refer to Fig. 27
on the nut (1.1).
1. Place the lever (1) on the position sensor
4. Screw the two bolts (14) to the bracket
in mid-position and hold it in place. Un-
(9.1) of the stem connector (9), place the
thread the nut (1.1) and remove the lever
follower plate (3) on top and use the
together with the disk spring (1.2) from
screws (14.1) for fastening.
the sensor shaft.
5. Place the bracket with the sensor at the
2. Screw the position sensor (20) onto the
NAMUR rib in such a manner that the
bracket (21).
follower pin (2) rests in the slot of the fol-
The standard attached M lever with the fol- lower plate (3), then screw the bracket
lower pin (2) at position 35 is designed for using its fixing screws onto the valve.
1 Lever
1.1 Nut
1.2 Disk spring
2 Follower pin
3 Follower plate
9 Stem connector
9.1 Bracket
14 Bolt
2 14.1 Screws
20 Position sensor
21 Bracket
EB 8384-3 EN 73
Mounting and start-up
5.10.3 Mounting the position 2. Screw the position sensor (20) onto the
bracket (21).
sensor to Type 3510
3. Select the S lever (1) from the accessories
Micro-flow Valve and screw the follower pin (2) into the
ÎÎ Required mounting parts and accesso- hole for pin position 17. Place the lever
ries: Table 8 on page 25. (1) and disk spring (1.2) on the sensor
ÎÎ Refer to Fig. 28 shaft. Place the lever in mid-position and
hold it in place. Screw on the nut (1.1).
1. Place the lever (1) on the position sen-
sor in mid-position and hold it in place. 4. Place follower clamp (3) on the valve
Unscrew the nut (1.1) and remove the stem connector, align at a right angle
standard attached M lever (1) together and screw tight.
with the disk spring (1.2) from the sen- 5. Position the bracket (21) with the position
sor shaft. sensor on the valve yoke and screw tight,
making sure the follower pin (2) slides
into the groove of the follower clamp (3).
1.1
20 21 1.2
3 1 Lever
1.1 Nut
1.2 Disk spring
2 Follower pin
3 Follower clamp
20 Position sensor
21 Bracket
74 EB 8384-3 EN
Mounting and start-up
5.10.4 Mounting on rotary ac- 3. Replace the follower pin (2) normally at-
tached to the lever (1) with the metal fol-
tuators lower pin (Ø 5 mm) from the accessories
ÎÎ Required mounting parts and accesso- and screw it into the hole for pin position
ries: Table 8 on page 25. 90°.
ÎÎ Refer to Fig. 29 4. Place the lever (1) and disk spring (1.2)
1. Place the lever (1) on the position sensor on the sensor shaft. Place the lever in
in mid-position and hold it in place. Un- mid-position and hold it in place. Screw
thread the nut (1.1) and remove the lever on the nut (1.1).
together with the disk spring (1.2) from Follow the instructions describing attachment
the sensor shaft. to the standard positioner in section 5.8.
2. Screw the position sensor (20) onto the Instead of the positioner, attach the position
mounting plate (21). sensor (20) with its mounting plate (21).
20
21
1 Lever
1.1 Nut
1.2 Disk spring
2 Follower pin
20 Position sensor
21 Mounting plate
2 1 1.1, 1.2
EB 8384-3 EN 75
Mounting and start-up
3 2 1
1 Leakage sensor
2 Screw
3 Plug connection
76 EB 8384-3 EN
Mounting and start-up
5.12 Retrofitting an inductive 6. Attach the rotary switch (5). Make sure
the flattened side of the positioner shaft is
limit switch turned so that the rotary switch (5) can be
Required retrofit kit: attached with the metal tag next to the
Limit switch Order no. 1402-1770 proximity switch.
7. On start-up of the positioner, set the op-
tion inductive alarm under Code 38 from
Note No to YES.
The same requirements apply to retrofitting a
unit as to servicing the positioner. For explo- 1
sion-protected positioners, the requirements
2
in Servicing explosion-protected devices
need to be kept. Check the "Limit switch, in- 4
ductive" box on the nameplate after install-
3
ing the limit switch.
EB 8384-3 EN 77
Mounting and start-up
78 EB 8384-3 EN
Mounting and start-up
Note
The adapter uses one of the M20x1.5 con-
nections in the housing which means only
one cable gland can be installed.
EB 8384-3 EN 79
80 EB 8384-3 EN
Mounting and start-up
! WARNING
Risk of injury by possible movement of ex-
posed parts (positioner, actuator or valve)
after connecting the signal pressure.
Do not touch or block exposed moving parts. Output 38 Supply 9
EB 8384-3 EN 81
Mounting and start-up
82 EB 8384-3 EN
Mounting and start-up
5.15.4 Signal pressure (output) The ambient temperature ranges of the ta-
bles in the EC type examination certificate
The signal pressure at the output (38) of the apply for the assignment between the per-
positioner can be restricted to 1.4 bar, missible ambient temperature, temperature
2.4 bar or 3.7 bar in Code 16. class, maximum short-circuit currents and
The limitation is not activated [No] by de- maximum power Pi and P0.
fault.
The following applies additionally: For posi-
tioners in type of protection Ex tb
5.16 Electrical connections (Type 3730-35) and type of protection Ex nA
For electrical installation, observe the rele- (Type 3730-38), the cable glands and blank-
vant electrotechnical regulations and the ac- ing plugs must be certified according to
cident prevention regulations that apply in EN 60079-7 (Ex e).
the country of use. In Germany, these are Selecting cables and wires
the VDE regulations and the accident pre-
Observe Clause 12 of EN 60079-14 for in-
vention regulations of the employers’ liability
stallation of the intrinsically safe circuits.
insurance.
Clause [Link] applies when running multi-
! DANGER core cables or wires with more than one in-
trinsically safe circuit.
Risk of fatal injury due to the formation of
an explosive atmosphere. The radial thickness of the insulation of a
The following regulations apply to installation conductor for common insulating materials
in hazardous areas: EN 60079-14 (e.g. polyethylene) must not be smaller than
(VDE 0165, Part 1) Explosive Atmospheres – 0.2 mm. The diameter of an individual wire
Electrical Installations Design, Selection and in a fine-stranded conductor must not be
Erection. smaller than 0.1 mm. Protect the conductor
ends against splicing, e.g. by using wire-end
! WARNING ferrules.
Incorrect electrical connection will render the When two separate cables or wires are used
explosion protection unsafe. for connection, an additional cable gland
−−Adhere to the terminal assignment. can be installed. Seal cable entries left un-
−−Do not undo the enameled screws in or on used with plugs. Fit equipment used in ambi-
the housing. ent temperatures below –20 °C with metal
−−Do not exceed the maximum permissible cable entries.
values specified in the EC type examina-
Equipment for use in zone 2/zone 22
tion certificates when interconnecting in-
trinsically safe electrical equipment (Ui or In equipment operated according to type of
U0, li or I0, Pi or P0, Ci or C0 and Li or L0). protection Ex nA (non-sparking equipment)
EB 8384-3 EN 83
Mounting and start-up
according to EN 60079-15, circuits may be The fuses must be installed outside the haz-
connected, interrupted or switched while en- ardous area.
ergized only during installation, mainte-
Cable entry
nance or repair.
The special conditions of use mentioned in Cable entry with M20x1.5 cable gland, 6 to
the statement of conformity are to be ob- 12 mm clamping range.
served for the rated values and the installa- There is a second M20x1.5 threaded hole in
tion of the series-connected fuse for intercon- the housing that can be used for additional
nection of Ex nA circuits. connection, when required. The screw termi-
nals are designed for wire cross-sections of
For Ex nA equipment (non-sparking equip-
0.2 to 2.5 mm². Tighten the screws by 0.5 to
ment), circuits may be connected, interrupted
0.6 Nm.
or switched while energized only during in-
stallation, maintenance or repair. The wires for the set point must be connect-
ed to the terminals 11 and 12 located in the
−− Positioners with type of protection Ex nA
housing.
or Ex tc can be used with a closed cover
Only use a current source. OVERLOAD ap-
(no window) or or with a cover with win-
pears on the display when the set point ex-
dow.
ceeds 22 mA.
−− The Types 3730-31, 3730-35 and 3730-
38 Positioners are 100 % identical in de- ! NOTICE
sign, except for the marking and the
The connection of a voltage source (U ≥ 7 V
housing cover.
or U ≥ 2 V when connected to the wrong
−− For type of protection Ex nA, the VCC pole) can damage the positioner.
connection in the interface adapter must Only use a current source and never a volt-
be connected in series with a fuse ac- age source!
cording to IEC 60127, 250 V F or T with
a fuse rating of IN ≤40 mA. In general, it is not necessary to connect the
−− The signal current circuit must be con- positioner to a bonding conductor. Should
nected in series with a fuse according to this be required, however, this conductor can
IEC 60127-2/VI, 250 V T with a fuse be connected inside the device.
rating of IN ≤63 mA. Depending on the version, the positioner is
−− The transmitter current circuit must be equipped with inductive limit switches and/
connected in series with a fuse according or a solenoid valve.
to IEC 60127-2/VI, 250 V T with a fuse The position transmitter is operated on a
rating of IN ≤40 mA. two-wire circuit. The usual supply voltage to
84 EB 8384-3 EN
Mounting and start-up
! NOTICE
Malfunction due the current falling below 5.16.1 Connecting the electrical
minimum current.
Do not allow the set point to fall below
power
3.8 mA.
! NOTICE
Accessories Risk of malfunction due to incorrect sequence
of mounting, installation and start-up.
Cable glands M20x1.5 Order no.
Keep the following sequence.
Black plastic 1. Remove the protective caps from the
(6 to 12 mm clamping range) 8808-1011
pneumatic connections.
Blue plastic
2. Mount the positioner on the valve.
(6 to 12 mm clamping range) 8808-1012
3. Connect the supply air.
Nickel-plated brass
(6 to 12 mm clamping range) 1890-4875
4. Connect the electrical power.
5. Perform settings.
Nickel-plated brass
(10 to 14 mm clamping range) 1922-8395
Stainless steel 1.4305
ÎÎ Connect the electrical power (mA signal)
(8 to 14.5 mm clamping range) 8808-0160 as shown in Fig. 33.
EB 8384-3 EN 85
Mounting and start-up
Point-to-point:
The bus address/polling address must al-
ways be set to zero (0).
86 EB 8384-3 EN
Mounting and start-up
A3 A2 A1 G
+81 -82 +11 -12 +83 -84 +51 -52 +41 -42 +31 -32 +31 -32
Analog input x
No Binary input of a PLC acc. to IEC 61131-2
ex (Pmax = 400 mW) or switching amplifier acc. Binary input
24 V DC mA
to EN 60947-5-6
Solenoid valve Control signal Leakage
(optional)
Ex Switching amplifier according to
EN 60947-5-6 sensor
A3 Limit switches
Fault alarm A2 A1 A
Software Software
optionally Position transmitter
inductive with two-wire
transmitter supply
unit
4 to 20 mA 3730-30
Controller/
control station
3730-31
EB 8384-3 EN 87
Mounting and start-up
Note
Communication errors may occur when the
process controller/control station output is
not HART®-compatible.
Alternatively, a 250 Ω resistor can be con-
nected in series and a 22 µF capacitor can
be connected in parallel to the analog out-
put. The load for the controller output will in-
crease as a result.
Controller/control
station
88 EB 8384-3 EN
Operation
−− AIR TO OPEN applies to a valve opening −− For a connection at the back (Type 3277-
as the signal pressure increases. 5), set restriction to MIN BACK.
−− AIR TO CLOSE applies to a valve closing −− For actuators 240 cm² and larger, set to
as the signal pressure increases. MAX SIDE for a side connection and to
MAX BACK for a connection at the back.
The signal pressure is the pneumatic pressure
%
at the output of the positioner applied to the
mm mm
actuator.
%
S
Initialization key Cap and rotary switch Metal tag of proximity switch
SSP interface
INTERFACE
SERIAL
ACTUATES
CAUTION
VALVE
INIT
OPEN/AIR TO
CLOSE
CLOSE
OPEN
%
mm mm
%
S Volume restriction
MAX SIDE
MIN BACK
MIN SIDE
MAX BACK
Rotary pushbutton
Q
EB 8384-3 EN 89
Operation
Closed-loop
Malfunction/fault Manual mode operation Code
INTERFACE
SERIAL
ACTUATES
CAUTION
AUtO Automatic
VALVE
INIT
OPEN
RES Reset
RUN Start
SAFE Fail-safe position
SUb Substitute calibration
tEStinG Test function active
Fig. 37: Display
90 EB 8384-3 EN
Operation
blinks: The positioner is not initialized. These icons indicate that an error has oc-
Operation only possible over manual set curred.
point (Code 1). A classified status can be assigned to each
−− (automatic mode) error. Classifications include “No message”,
The positioner is in closed-loop operation “Maintenance required”, “Maintenance de-
and follows the mA signal. manded” and “Maintenance alarm“ (see
u EB 8389 on EXPERTplus valve diagnos-
−− S SAFE
tics).
The positioner vents the output. The valve
moves to the mechanical fail-safe posi- Enable configuration
tion. This indicates that the codes marked with an
Bar graph: asterisk (*) in the code list are enabled for
configuration (see section 11.4).
In manual and automatic modes, the
bars indicate the set point deviation that de-
pends on the sign (+/–) and the value. One 6.1 Serial interface
bar element appears per 1 % set point devi- The positioner must be supplied with at least
ation. 4 mA.
If the positioner has not been initialized, ( The positioner can be connected directly to
blinks on the display), the bar graph indi- the computer over the local serial interface
cates the lever position in degrees in relation and the serial interface adapter.
to the mid-axis. One bar element corre-
The operator software is TROVIS-VIEW with
sponds to approximately a 5° angle of rota-
installed device module 3730-3.
tion. The fifth bar element blinks (reading >
30°) if the permissible angle of rotation has
EB 8384-3 EN 91
Operation
6.2 HART® communication The word 'HART' then blinks on the display
when Code 3 is selected. This locking func-
The positioner must be supplied with at least tion can only be disabled over HART® com-
4 mA. The FSK modem must be connected in munication.
parallel to the current loop.
On-site operation is enabled by default.
A DTM file (Device Type Manager) conform-
ing to the Specification 1.2 is available for
communication. This allows the device, for
6.2.1 Dynamic HART® vari-
example to be run with the PACTware user ables
interface. The HART® specification defines four dynam-
All the positioner's parameters are accessi- ic variables consisting of a value and an en-
ble over the DTM and the user interface. gineering unit. These variables can be as-
For start-up and settings, proceed as de- signed to device parameters as required. The
scribed in section 7. Refer to the code list in universal HART® command 3 reads the dy-
section 11.4 for the parameters necessary namic variables out of the device. This al-
for the user interface. lows manufacturer-specific parameters to al-
so be transferred using a universal com-
mand.
Note
If complex functions are started in the posi- In the Type 3730-3 Positioner, the dynamic
tioner, which require a long calculation time variables can be assigned by the DD or in
or lead to a large quantity of data being TROVIS-VIEW [Settings > Operation unit] as
saved in the volatile memory of the posi- shown in Table 15.
tioner, the alert 'busy' is issued by the DTM
file.
This alert is not an error message and can
be simply confirmed.
92 EB 8384-3 EN
Operation
EB 8384-3 EN 93
94 EB 8384-3 EN
Operating the positioner
! NOTICE
Risk of malfunction due to incorrect sequence of mounting, installation and start-up.
Keep the following sequence.
1. Remove the protective caps from the pneumatic connections.
2. Mount the positioner on the valve.
3. Connect the supply air.
4. Connect the electrical power.
5. Perform settings.
tEStinG runs across the display and the fault alarm icon appears
and blinks on the display when the positioner has not been initial-
ized. The reading indicates the lever position in degrees in relation to
the mid-axis.
Code 0 is displayed when a positioner has been initialized. The po-
sitioner is in the last active operating mode.
The positioner performs a test in the start-up phase while following its automation task at the
same time.
! WARNING
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
During the start-up phase, operation on site is unrestricted, yet write access is limited.
EB 8384-3 EN 95
Operating the positioner
Note
The switch position is prompted prior to an initialization. After an initialization has been
completed, changing the switch position does not have any effect on the operation of the po-
sitioner.
The volume restriction Q serves to adapt the air output capacity to the size of the actuator:
−− Actuators with a transit time < 1 s, e.g. linear actuators with an effective area smaller
than 240 cm², require a restricted air flow rate (MIN).
−− Actuators with a transit time ≥ 1 s do not require the air flow rate to be restricted (MAX).
96 EB 8384-3 EN
Operating the positioner
The position of volume restriction Q also depends on how the signal pressure is routed at the
actuator in SAMSON actuators:
'SIDE' inscription
–– For actuators with a signal pressure connection at the side, e.g. Type 3271-5
–– For actuators from other manufacturers
'BACK' inscription
−− For actuators with a signal pressure connection at the back, e.g. Type 3277-5
The following applies to positioners with optional analog input x: the MIN SIDE setting
must always be used for actuators with an air volume of less than one liter.
! NOTICE
Malfunction due to changed start-up settings.
Initialize an initialized positioner again after the position of the volume restriction has been
changed.
EB 8384-3 EN 97
Operating the positioner
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
98 EB 8384-3 EN
Operating the positioner
To ensure the positioner is working properly, the outer bar elements must not blink while the
valve is moving through the operating range.
Exit Code 1 by pressing the rotary pushbutton ( ).
The permissible range has been exceeded when the displayed angle is more than 30° and
the outer right or left bar element blinks. The positioner goes to the fail-safe position (SAFE).
After canceling the fail-safe position (SAFE) (see section 7.11.2) it is absolutely essential that
you check the lever and pin position as described in section 5.
! WARNING
Risk of injury due to the actuator stem extending or retracting.
Before exchanging the lever or changing the pin position, disconnect the supply air and
electrical auxiliary power.
EB 8384-3 EN 99
Operating the positioner
! WARNING
Risk of injury by exposed moving parts on the positioner, actuator or valve.
Do not touch or block exposed moving parts.
! NOTICE
The process is disturbed by the movement of the actuator or valve.
Do not perform the initialization while the process is running. First isolate the plant by closing
the shut-off valves.
ÎÎ Check the max. permissible signal pressure of the valve before starting initialization.
During initialization, the positioner issues an output signal pressure up to the maximum
supply pressure supplied. If necessary, limit the signal pressure by connecting an up-
stream pressure reducing valve.
Note
Reset positioner to its default settings (see section 7.9) before mounting it on a different actu-
ator or changing its mounting position.
During initialization the positioner adapts itself optimally to the friction conditions and the
signal pressure required by the control valve. The type and extent of auto tuning depends on
the initialization mode selected:
−− Maximum range (MAX) (standard range)
Initialization mode for simple start-up of valves with two clearly defined mechanical end
positions, e.g. three-way valves (see section 7.6.1)
−− Nominal range (NOM)
Initialization mode for all globe valves (see section 7.6.2)
−− Manually selected range (MAN)
Initialization mode for globe valves with an unknown nominal range (see section 7.6.3)
−− Substitute calibration (SUb)
This mode allows a positioner to be replaced while the plant is running, with the least
amount of disruption to the plant (see section 7.6.4).
For normal operation, simply start initialization by pressing the INIT key after mounting the
positioner on the valve and defining the fail-safe position and setting the volume restriction.
100 EB 8384-3 EN
Operating the positioner
The positioner only needs to work with its default settings. If necessary, perform a reset (see
section 7.9).
Note
An initialization procedure in progress can be canceled by pressing the rotary pushbutton.
STOP is displayed for three seconds and the positioner changes to the fail-safe position
(SAFE). Clear the fail-safe position again over Code 0 (see section 7.11.2).
Initialization successfully
completed. Positioner in
% automatic mode ( )
Note
When Code 48 - h0 = YES, the diagnostics automatically start to plot the reference graphs
(drive signal steady-state d1 and hysteresis d2) after initialization has been completed. This
is indicated by tESt and d1 or d2 appearing on the display in alternating sequence.
An error during the plotting of the reference graphs is indicated on the display over Code 48
- h1 and Code 81.
The reference graphs do not have any effect on closed-loop operation.
EB 8384-3 EN 101
Operating the positioner
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
102 EB 8384-3 EN
Operating the positioner
Start initialization:
Note
The maximum possible travel must always be greater than the nominal travel entered. If this
is not the case, initialization is automatically canceled (error message Code 52) because the
nominal travel could not be achieved.
EB 8384-3 EN 103
Operating the positioner
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
104 EB 8384-3 EN
Operating the positioner
Start initialization:
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
EB 8384-3 EN 105
Operating the positioner
Start initialization:
106 EB 8384-3 EN
Operating the positioner
By entering the blocking position (Code 35), closing direction (Code 34), pin position (Code
4), nominal range (Code 5) and direction of action (Code 7), the positioner can calculate the
positioner configuration.
! NOTICE
Perform a reset before re-initializing the positioner if the substitute positioner has already
been initialized. Refer to section 7.9.
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
EB 8384-3 EN 107
Operating the positioner
Note
Do not change the pressure limit (Code 16). Only change the control parameters KP (Code
17) and TV (Code 18) if the settings of the replaced positioner are known.
108 EB 8384-3 EN
Operating the positioner
TV level
Default: 2
EB 8384-3 EN 109
Operating the positioner
Start initialization:
Since initialization has not been completed, the error code 76 (no emergency mode) and
possibly also error code 57 (control loop) may appear on the display. These alarms do not
influence the positioner’s readiness for operation.
ÎÎ If the positioner shows a tendency to oscillate in automatic mode, the parameters KP and
TV must be slightly corrected. Proceed as follows:
–– Set TV (Code 18) to 4.
–– If the positioner still oscillates, the gain KP (Code 17) must be decreased until the posi-
tioner shows a stable behavior.
110 EB 8384-3 EN
Operating the positioner
! WARNING
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
! NOTICE
The process is disturbed by the movement of the actuator stem.
Do not perform zero calibration while the process is running. First isolate the plant by closing
the shut-off valves.
The positioner must be connected to the supply air to perform the zero calibration.
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
EB 8384-3 EN 111
Operating the positioner
Note
The inductive limit switch replaces the software limit switch A1 with terminal assignment
+41/–42.
Each switching position can optionally be set to indicate when the tag has entered the field
or when it has left the field.
The second software limit switch remains effective, the function of the software limit switch A1
is disabled.
Software adaptation
−− Code 38 (inductive alarm is set to YES).
−− The inductive limit switch is connected to the terminals +41/–42 (see section 5.16).
−− The device is set up accordingly in the delivered state.
Note
During adjustment or testing, the switching point must always be approached from mid-posi-
tion (50 %).
To guarantee the switching under all ambient conditions, adjust the switching point approx.
5 % before the mechanical stop (OPEN – CLOSED).
112 EB 8384-3 EN
Operating the positioner
Contact function:
−− Tag leaving the field > contact is closed.
−− Tag entering the field > contact is opened.
Contact function:
−− Tag leaving the field > contact is closed.
−− Tag entering the field > contact is opened.
EB 8384-3 EN 113
Operating the positioner
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
Note
Code 36 - diAG allows just the diagnosis data (EXPERTplus) to be reset. Refer to the Operat-
ing Instructions for EXPERTplus valve diagnostics u EB 8389.
114 EB 8384-3 EN
Operating the positioner
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid and the display returns to Code 0.
EB 8384-3 EN 115
Operating the positioner
116 EB 8384-3 EN
Operating the positioner
The positioner automatically returns to Code 0 if no settings are made within 120 seconds,
but remains in the manual mode.
EB 8384-3 EN 117
118 EB 8384-3 EN
Servicing
8 Servicing Filters
There are filters with a 100 µm mesh size in
the pneumatic connections for supply and
Note
output which can be removed and cleaned,
The positioner was checked by SAMSON
if required.
before it left the factory.
−−The product warranty becomes void if ser- Supply air pressure reducing stations
vice or repair work not described in these The maintenance instructions of any up-
instructions is performed without prior stream supply air pressure reducing stations
agreement by SAMSON's After-sales Ser- must be observed.
vice department.
−−Only use original spare parts by
SAMSON, which comply with the original
8.1 Firmware update
specifications. Firmware updates on positioners currently
in operation can be performed as
The positioner does not require any mainte- described below. Only individuals with a
nance. written approval may perform updates.
Housing cover Approved individuals are named by
SAMSON's Total Quality Management and
Occasionally, the window in the cover may
assigned a test mark.
need to be cleaned.
Laptops and computers connected to the
! NOTICE power supply must only be interconnected
with intrinsically safe equipment if the
Incorrect cleaning will damage the window.
SAMSON isolated USB interface adapter
The window is made of Makrolon® (new de-
(order no. 1400-9740) is connected in-
sign) and will be damaged when cleaned
between for software programming or test
with abrasive cleaning agents or agents con-
routines.
taining solvents.
−−Do not rub the window dry. Updates outside the hazardous area:
−−Do not use any cleaning agents containing ÎÎ Remove the positioner and perform the
chlorine or alcohol or abrasive cleaning update outside the hazardous area.
agents.
−−Use a non-abrasive, soft cloth for cleaning. Updates on site:
ÎÎ Updates on site are only permitted after
the plant operator presented a signed
hot work permit.
EB 8384-3 EN 119
Servicing
120 EB 8384-3 EN
Malfunctions
EB 8384-3 EN 121
Malfunctions
122 EB 8384-3 EN
Decommissioning and removal
EB 8384-3 EN 123
Decommissioning and removal
124 EB 8384-3 EN
Appendix
Required specifications
Please submit the following details:
−− Order number and position number in
the order
−− Type, serial number, firmware version,
device version
EB 8384-3 EN 125
Appendix
3 Enable configuration Enables changing of data (automatically deactivated when the rota-
[No], YES, ESC ry pushbutton has not been operated for 120 s). HART blinks on the
display when the on-site operation is locked over HART® communi-
cation. Codes marked with an asterisk (*) can only be read and not
overwritten. Similarly, codes can only read over the SSP interface.
126 EB 8384-3 EN
Appendix
5* Nominal range Nominal valve travel or opening angle must be entered for nominal
mm or angle °, ESC (NOM) or substitute (SUb) initialization.
The possible adjustment range depends on the pin position from the
table for Code 4.
Indicates maximum travel/angle reached during initialization after
initialization has been successfully completed.
6* Init mode Select the initialization mode
[MAX] Maximum range MAX: Travel/angle of the closure member from the CLOSED
position to the opposite stop in the actuator.
NOM Nominal range
NOM: Travel/angle of the closure member measured from the
MAN Manual setting
CLOSED position to the indicated OPEN position.
SUb Emergency mode
MAN: Manually selected range
ZP Zero calibration
SUb: Substitute calibration (without initialization)
ESC Stop
EB 8384-3 EN 127
Appendix
11* Travel/angle upper limit Limits travel/angle to the entered value (upper limit). The character-
(upper x-limit) istic is not adapted.
50.0 to 120.0 %, Example: In some applications, it is better to limit the valve travel,
[100.0 %] of the operating e.g. if a certain minimum medium flow is required or a maximum
range, No, ESC flow must not be reached.
The lower limit must be adjusted with Code 10 and the upper limit
with Code 11.
If a tight-closing function has been set up, it has priority over the
travel limitation.
When set to No, the valve can be opened past the nominal travel
with a set point outside of the 0 to 100 % range.
128 EB 8384-3 EN
Appendix
EB 8384-3 EN 129
Appendix
130 EB 8384-3 EN
Appendix
Exponential reading from The total valve travel is saved in a non-volatile memory after every
9999 travel cycles on- 1000 full valve travel cycle.
wards
24* LV total valve travel Limit value of total valve travel. If the limit is exceeded, the and
1000 to 99 · 107 icons are indicated.
[1.000000], ESC
Exponential reading from
9999 travel cycles on-
wards
EB 8384-3 EN 131
Appendix
When a positioner has not been initialized, the software limit switch-
es always register the signal as in the state of no response.
If there is no mA signal at the terminals 11/12, the software limit
switches both switch to ≤ 1.0 mA (Ex) or non-conducting (without
explosion protection).
Note: The fault alarm output always switches to ≤1.0 mA/
non-conducting in case of a fault; it has ≥2.2 mA/R = 348 Ω when
there is no fault.
26* Limit A1 Alarm A1 responds when the value falls below the limit.
0.0 to 100.0 %, [2.0 %] of Software limit value A1 is displayed or can be changed in relation
the operating range, No, to the operating range.
ESC The setting has no effect when an inductive limit switch is installed.
27* Limit A2 Alarm A2 responds when the value exceeds the limit.
0.0 to 100.0 %, [98.0 %] Software limit value A2 is displayed or can be changed in relation
of the operating range, to the operating range.
No, ESC
132 EB 8384-3 EN
Appendix
29* Position transmitter x/ix 3) Operating direction of the position transmitter: it indicates assign-
[], , ESC ment between travel/angle position and output signal i based on
CLOSED position.
The operating range (see Code 8) of the valve is represented by the
4 to 20 mA signal. Values exceeding or falling below the limits 2.4
and 21.6 mA can be indicated.
When the positioner has not been mounted (set point smaller than
3.6 mA), the signal is 0.9 mA and 3.8 mA the positioner has not
been initialized. When YES is set in Code 32, the position transmit-
ter issues the value as per Code 30 during initialization or zero cali-
bration. When No is set in Code 32, 4 mA is issued during a run-
ning calibration.
30* Fault alarm ix 3) Select if and how alarms that cause the fault alarm contact to be
HI, LO, [No], ESC switched are also indicated by the position transmitter.
HI ix =21.6 ±0.1 mA or LO ix =2.4 ±0.1 mA
31* Position transmitter test 3) Testing the position transmitter. Values can be entered in relation to
–10.0 to 110.0 % of the the operating range.
operating range, [default The momentary valve position is used in initialized positioners local-
value is last indicated val- ly as the start value (bumpless changeover to the test mode). When
ue of the position transmit- testing by software, the entered simulation value is issued as the po-
ter], ESC sition feedback signal for 30 seconds.
3)
Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.
EB 8384-3 EN 133
Appendix
35* Blocking position Enter the blocking position (distance to CLOSED position)
[0.0] mm/° /%, ESC Only necessary with SUb initialization mode.
36* Reset Std: Resets all parameters and diagnosis data to their default
[No], Std, diAG, ESC settings. After a reset, the positioner must be re-initialized.
134 EB 8384-3 EN
Appendix
48*
Diagnostic parameters u EB 8389
49*
EB 8384-3 EN 135
Appendix
Recommended action Check attachment and pin position, set operating mode from SAFE to
MAN and re-initialize the positioner.
51 Δx < permissible Insufficient measuring span of the lever.
range • Pin not mounted properly
• Wrong lever
An angle of rotation smaller than 16° at the positioner shaft only gener-
ates an alarm. An angle below 9° leads to the initialization being can-
celed.
Status classification [Maintenance required]
Recommended action Check attachment and re-initialize the positioner.
52 Attachment • Invalid positioner attachment
• Nominal travel/angle (Code 5) could not be achieved during NOM ini-
tialization (no tolerance downwards permissible).
• Mechanical or pneumatic fault, e.g. wrong lever selected or supply pres-
sure too low to move to the required position.
Status classification [Maintenance required]
Recommended action Check attachment and supply pressure. Re-initialize the positioner.
Under certain circumstances, it may be possible to check the maximum
travel/angle by entering the actual pin position and then performing a
MAX initialization.
After initialization has been completed, the Code 5 indicates the maximum
achieved travel or angle.
136 EB 8384-3 EN
Appendix
Error codes – Condensed state message active, when prompted, Err appears.
Recommended action When fault alarms exist, they are displayed here.
53 Initialization time Initialization takes too long. The positioner returns to the previous operat-
exceeded ing mode.
(Init time >) • No pressure in supply line or pneumatic leakage
• Supply air failure during initialization
Status classification [Maintenance required]
Recommended action Check attachment and supply air line. Re-initialize the positioner.
54 Initialization – 1)
A solenoid valve is installed (Code 45 = YES) and has not been
solenoid valve connected or not properly. As a result, actuator pressure cannot
build up. The alarm is generated when you attempt to initialize the
positioner.
2)
If you attempt to initialize the positioner from the fail-safe position
(SAFE).
Status classification [Maintenance required]
Recommended action 1)
Check connection and supply voltage of the solenoid valve (Code 45
High/Low).
2)
Set the MAN mode in Code 0. Re-initialize the positioner.
55 Transit time too short Actuator transit times detected during initialization are so short that opti-
(transit time <) mal positioner tuning is impossible.
Status classification [Maintenance required]
Recommended action Check the volume restriction setting as described in section 7.2. Re-
initialize the positioner.
56 Pin position Initialization canceled because selected NOM and SUB initialization
modes require the pin position to be entered.
Status classification [Maintenance required]
Recommended action Enter pin position over Code 4 and nominal travel/angle over Code 5.
Re-initialize the positioner.
EB 8384-3 EN 137
Appendix
Operational errors
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
57 Control loop Control loop error, the valve no longer follows the controlled variable
Additional indication at the within tolerable times (tolerance band alarm Code 19).
fault alarm contact • Actuator blocked
• Positioner attachment shifted subsequently
• Supply pressure no longer suffices.
Status classification [Maintenance required]
Recommended action Check attachment.
58 Zero point Zero point incorrect
Error can occur when the positioner's attachment position is shifted or
when the valve trim is worn, particularly with soft-sealed plugs.
Status classification [Maintenance required]
Recommended action Check valve and attachment of the positioner. If OK, perform a zero
calibration over Code 6 (see section 7.7).
We recommend to re-initialize the positioner if zero deviates by more
than 5 %.
59 Auto-correction Errors in the positioner's data section are detected detected by automatic
monitoring and corrected automatically.
Status classification [No message]
Recommended action Automatic
60 Fatal error Error in safety-relevant data that cannot be corrected automatically. Pos-
Additional indication at the sible cause: EMC disturbances.
fault alarm contact The valve is moved to fail-safe position.
Status classification Maintenance alarm (cannot be classified)
Recommended action Reset over Code 36 – Std. Re-initialize the positioner.
138 EB 8384-3 EN
Appendix
Hardware errors
Error codes – Condensed state message active, when prompted, Err appears.
Recommended action When fault alarms exist, they are displayed here.
62 x signal Actuator's measured value recording failed.
The conductive plastic element is defective.
The device continues functioning in emergency mode but it must be re-
placed as quickly as possible.
The emergency mode on the display is indicated by a blinking closed-
loop operation icon and 4 dashes instead of the position reading.
Note on the open-loop operation: If the measuring system has failed, the
positioner is still in a reliable state. The positioner switches to emergency
mode where the position cannot be accurately controlled anymore. How-
ever, the positioner continues operation according to its set point so that
the process remains in a safe state.
Status classification [Maintenance demanded]
Recommended action Return positioner to SAMSON AG for repair.
63 w too low The set point is considerably smaller than 4 mA (0 %). This happens when
the positioner's power supply does not meet the standard requirements.
This state is indicated on the positioner display by LOW blinking.
Status classification [No message]
Recommended action Check set point.
If necessary, adjust the current source's lower limit so that no values lower
than 4 mA can be applied.
64 i/p converter (y) Current circuit of i/p converter interrupted.
Status classification Maintenance alarm (cannot be classified)
Recommended action Cannot be remedied. Return positioner to SAMSON AG for repair.
EB 8384-3 EN 139
Appendix
Error appendix
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
65 Hardware Initialization key jammed (firmware version R 1.51 and higher)
Additional indication at A hardware error has occurred. The positioner changes to the fail-safe
the fault alarm contact position (SAFE).
Status classification [Maintenance alarm]
Recommended action Confirm error and return to automatic mode or perform a reset and
re-initialize the positioner. If this is not successful, return positioner to
SAMSON for repair.
66 Data memory No more data can be written to the memory, e.g. because written data
Additional indication at deviate from read data. The valve moves to the fail-safe position.
the fault alarm contact
Data errors
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
68 Control parameters Error in control parameters.
Additional indication at
the fault alarm contact
Recommended action Confirm error, perform a reset and re-initialize the positioner.
140 EB 8384-3 EN
Appendix
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
69 Potentiometer Error in digital potentiometer parameters
parameters
Additional indication at
the fault alarm contact
Recommended action Confirm error. Check and, if necessary, change the settings of the re-
quired parameters.
73 Internal device Internal device error
error 1
Status classification [Maintenance required]
EB 8384-3 EN 141
Appendix
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
76 No emergency mode The travel measuring system of the positioner has a self-monitoring
function (see Code 62).
An emergency mode (open-loop control) is not available for certain
actuators, such as double-acting actuators. In case of a travel sensing
error, the positioner vents the output (Output 38) or A1 in double-acting
actuators. During the initialization, the positioner automatically checks
whether the actuator has such a function or not.
Status classification [No message]
Diagnosis errors
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
79 Diagnostic messages Messages generated by the extended diagnostics
Status classification Maintenance required (cannot be classified)
142 EB 8384-3 EN
Appendix
Error codes – Recommended Condensed state message active, when prompted, Err appears.
action When fault alarms exist, they are displayed here.
81 Reference graphs Error occurred during plotting the reference graphs for drive signal y
steady-state or drive signal y hysteresis.
• Reference test canceled
• Reference line for drive signal y steady-state or drive signal y
hysteresis was not adopted.
Error messages are not yet saved in a non-volatile memory. They cannot
be reset.
Status classification [No message]
Recommended action Check and, if necessary, perform a new reference test.
EB 8384-3 EN 143
Note
A characteristic can only be defined (user-defined characteristic) using a workstation/
operating software (e.g. TROVIS-VIEW).
50
50 50
144 EB 8384-3 EN
SAMSON butterfly valve linear (select SAMSON butterfly valve equal percentage
characteristic: 3) (select characteristic: 4)
Travel/angle [%] Travel/angle [%]
100 100
50 50
VETEC rotary plug valve linear (select VETEC rotary plug valve equal percentage
characteristic: 5) (select characteristic: 6)
Travel/angle [%] Travel/angle [%]
100 100
50 50
Segmented valve ball linear (select Segmented valve ball equal percentage (select
characteristic: 7) characteristic: 8)
Travel/angle [%] Travel/angle [%]
100 100
50 50
EB 8384-3 EN 145
146 EB 8384-3 EN
Seite 1 von 3
,(&([&HUWLILFDWH
RI&RQIRUPLW\
,17(51$7,21$/(/(&7527(&+1,&$/&200,66,21
,(&&HUWLILFDWLRQ6FKHPHIRU([SORVLYH$WPRVSKHUHV
IRUUXOHVDQGGHWDLOVRIWKH,(&([6FKHPHYLVLWZZZLHFH[FRP
Status: &XUUHQW
Applicant: 6$0621$*0HVVXQG5HJHOWHFKQLN
Weismuellerstrasse 3
D-60314 Frankfurt am Main
*HUPDQ\
Marking: ([LD,,&777
,3DQG,37&
6LJQDWXUH
IRUSULQWHGYHUVLRQ
'DWH
3K\VLNDOLVFK7HFKQLVFKH
%XQGHVDQVWDOW37%
%XQGHVDOOHH
%UDXQVFKZHLJ
*HUPDQ\
[Link] 24.02.2005
EB 8384-3 EN 147
Seite 2 von 3
Page of
Manufacturer: 6$0621$*0HVVXQG5HJHOWHFKQLN
Weismuellerstrasse 3
D-60314 Frankfurt am Main
*HUPDQ\
Manufacturing location(s):
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and
found to comply with the IEC Standard list below and that the manufacture’rs quality system, relating to the Ex products
covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This
certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents
as amended.
67$1'$5'6
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified
documents, was found to comply with the following standards:
,(& Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition: 3.1
,(& Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i'
Edition: 4
,(& Electrical apparatus for use in the presence of combustible dust - Part 1-1: Electrical
Edition: 2 apparatus protected by enclosures and surface temperature limitation - Specification for
apparatus
7(67 $66(660(175(32576
$VDPSOHVRIWKHHTXLSPHQWOLVWHGKDVVXFFHVVIXOO\PHWWKHH[DPLQDWLRQDQGWHVWUHTXLUHPHQWVDVUHFRUGHGLQ
[Link] 24.02.2005
148 EB 8384-3 EN
Seite 3 von 3
Page of
(48,30(17
(TXLSPHQWDQGV\VWHPVFRYHUHGE\WKLVFHUWLILFDWHDUHDVIROORZV
General description: The Model 3730-31 HART® capable Positioner is a single- or double-acting positioner with
communication capability intended for attachment to pneumatic control valves or rotary actuators. The Positioner is of the
self-balancing type and adapts itself automatically to the attached valve or actuator respectively. The positioner server for
matching valve stem positions (controlled variable x) with the control signal (reference variable W) in the 4-20mA range.
Nominal travels of 3,6 to 200mm are possible with linear actuators, or angles of rotation of 24 ° to 100 ° with rotary
actuators. Features: Simple attachment to current linear and rotary actuators with interface for SAMSON- direct
attachment. NAMUR- rib; attachment to rod-type yoke acc. to IEC 60534-6-1. Any mounting position of the positioner.
Options: Position indicator, software proximity switches, inductive proximity switch, forced routing function, fault alarm
output, external displacement transducer and serial interface. In the ex version the fault alarm output, the software
proximity switches and the inductive proximity switch are analysed by a NAMUR-switching amplifier according to EN
50227.
&21',7,2162)&(57,),&$7,21 12
[Link] 24.02.2005
EB 8384-3 EN 149
150 EB 8384-3 EN
EB 8384-3 EN 151
152 EB 8384-3 EN
EB 8384-3 EN 153
154 EB 8384-3 EN
EB 8384-3 EN 155
156 EB 8384-3 EN
EB 8384-3 EN 157
158 EB 8384-3 EN
EB 8384-3 EN 159
160 EB 8384-3 EN
EB 8384-3 EN 161
162 EB 8384-3 EN
EB 8384-3 EN 163
164 EB 8384-3 EN
EB 8384-3 EN 165
166 EB 8384-3 EN
EB 8384-3 EN 167
168 EB 8384-3 EN
EB 8384-3 EN 169
170 EB 8384-3 EN
EB 8384-3 EN 171
EU Konformitätserklärung / EU Declaration of Conformity /
Déclaration UE de conformité
Die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung trägt der Hersteller/
This declaration of conformity is issued under the sole responsibility of the manufacturer/
La présente déclaration de conformité est établie sous la seule responsabilité du fabricant.
Für das folgende Produkt / For the following product / Nous certifions que le produit
wird die Konformität mit den einschlägigen Harmonisierungsrechtsvorschriften der Union bestätigt /
the conformity with the relevant Union harmonisation legislation is declared with/
est conforme à la législation d'harmonisation de l'Union applicable selon les normes:
EN 61000-6-2:2005, EN 61000-6-3:2007
EMC 2014/30/EU
+A1:2011, EN 61326-1:2013
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3
D-60314 Frankfurt am Main
Deutschland/Germany/Allemagne
172 EB 8384-3 EN
EU Konformitätserklärung / EU Declaration of Conformity /
Déclaration UE de conformité
Die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung trägt der Hersteller/
This declaration of conformity is issued under the sole responsibility of the manufacturer/
La présente déclaration de conformité est établie sous la seule responsabilité du fabricant.
Für das folgende Produkt / For the following product / Nous certifions que le produit
EN 61000-6-2:2005, EN 61000-6-3:2007
EMC 2014/30/EU
+A1:2011, EN 61326-1:2013
Explosion Protection 94/9/EC (to 2016-04-19) EN 60079-0:2012/A11:2013,
Explosion Protection 2014/34/EU (from 2016-04-20) EN 60079-11:2012, EN 60079-31:2014
RoHS 2011/65/EU EN 50581:2012
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3
D-60314 Frankfurt am Main
Deutschland/Germany/Allemagne
ce_3730-31_de_en_fra_fra_rev07.pdf
EB 8384-3 EN 173
EU Konformitätserklärung / EU Declaration of Conformity /
Déclaration UE de conformité
Die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung trägt der Hersteller/
This declaration of conformity is issued under the sole responsibility of the manufacturer/
La présente déclaration de conformité est établie sous la seule responsabilité du fabricant.
Für das folgende Produkt / For the following product / Nous certifions que le produit
EN 61000-6-2:2005, EN 61000-6-3:2007
EMC 2014/30/EU
+A1:2011, EN 61326-1:2013
EN 60079-0:2012/A11:2013,
Explosion Protection 2014/34/EU
EN 60079-11:2012, EN 60079-31:2014
RoHS 2011/65/EU EN 50581:2012
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3
D-60314 Frankfurt am Main
Deutschland/Germany/Allemagne
ce_3730-35_de_en_fra_fra_rev07.pdf
174 EB 8384-3 EN
EU Konformitätserklärung / EU Declaration of Conformity /
Déclaration UE de conformité
Die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung trägt der Hersteller/
This declaration of conformity is issued under the sole responsibility of the manufacturer/
La présente déclaration de conformité est établie sous la seule responsabilité du fabricant.
Für das folgende Produkt / For the following product / Nous certifions que le produit
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3
D-60314 Frankfurt am Main / Germany
EB 8384-3 EN 175
EU Konformitätserklärung / EU Declaration of Conformity /
Déclaration UE de conformité
Die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung trägt der Hersteller/
This declaration of conformity is issued under the sole responsibility of the manufacturer/
La présente déclaration de conformité est établie sous la seule responsabilité du fabricant.
Für das folgende Produkt / For the following product / Nous certifions que le produit
EN 61000-6-2:2005, EN 61000-6-3:2007
EMC 2014/30/EU
+A1:2011, EN 61326-1:2013
Explosion Protection 94/9/EC (bis/to 2016-04-19) EN 60079-0:2009, EN 60079-1:2007,
Explosion Protection 2014/34/EU (ab/from 2016-04-20) EN 60079-11:2012
RoHS 2011/65/EU EN 50581:2012
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3
D-60314 Frankfurt am Main
Deutschland/Germany/Allemagne
176 EB 8384-3 EN
EB 8384-3 EN 177
178 EB 8384-3 EN
EB 8384-3 EN 179
EB 8384-3 EN
2019-11-05 · English
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
samson@[Link] · [Link]