Static and Dynamic Resistance
Measurements
Ali Husain
[Link]@[Link]
1
Q&A
Send us your questions
and comments during
the presentation
2
Agenda
Introduction
Static Resistance
Dynamic Resistance
Megger Solutions
Live Demo
3
What is a Circuit Breaker
A circuit breaker is an automatically operated electrical
switch designed to protect an electrical circuit from damage
caused by excess current from an overload or short circuit.
4
What Do I Need From a Circuit breaker
To be a Perfect Conductor when closed
To be a Perfect Insulator when opened
To Switch between Open/close safely during
Normal/Abnormal conditions like Faults , Short circuit , etc. …
5
Types of Circuit breakers
Low Voltage CBs Medium/High Voltage CBs
• Below 1000V • Greater than 1000V
• Will trip on own when there • Cannot trip on own, needs
is too much current external signal to trip ,
• Timing test is performed via e.g. Protection relays
current injection at actual • Testing Done Through
current levels Circuit Breaker analyzers
6
HV Circuit Breakers
Live Tank Dead Tank (Body Grounded)
• Vacuum (High Voltage) • Vacuum (Medium Voltage)
• Minimum Oil • Bulk Oil
• Air Blast • SF6
• SF6 • GIS
– Circuit Breaker • Hybrid
– Circuit Switcher • Generator CBs
• Air Blast
The majority nowdays are
SF6 breakers
7
Inside of a SF6 Circuit Breaker
Contact System
• Main Contacts
• Arching Contacts
Some breakers does not have
arcing contacts.
8
SF6 CB operation
Closed Main Arching Arching Opened
Contact Contact
separate separate
9
Static Resistance
Verify low contact resistance (micro ohm).
High current for accuracy.
Test current (DC):
• Minimum 100 A (IEEE)
• IEC standard requires at least 50 ADC
• +10% of rated current (recommended)
4 Wire Method measurement
Closed
10
Static Resistance Measurment(SRM)
Typical SRM Results:
Phase C
• Generator 1 – 10 mohm
Phase B
Phase A • Transmission 20-200 mohm
• Distribution 20-1000 mohm
Micro-Ohm
Meter
11
what about Arching Contacts ?
Static Resistance Measurements to
arching contact Arching
contact
Main (30mohm)
Main
contact
Arching (1000mohm)
Total R = 30//1000 =
29.12 mohm
Arching Contact Closed
resistance Negligible
12
Dynamic Resistance Measurement
Doing Resistance Measurement during
Opening Operation
Main (30mohm) Arching
Contacts
Arching (1000mohm)
Total R = 1000 = mohm
Arching Contact
resistance Measureable
Thus The Name Dynamic Resistance During Operation
Measurements (DRM)
13
Actual Measurement of DRM
Current
Resistance
Arching
Closed contacts only Opened
Very Difficult
to Find a
easy
number
How can I
make this
Better?
14
Travel Motion Test
Measurement Linear Angular
interface Type
Types of
Transducer
15
DRM + Travel Motion Test
Resistance curve
equal to voltage drop over breaker
[500 mΩ/div]
Movement starts
speed x time = Length of arcing contact
Main contact opens, arcing
contact conducting.
Travel curve
[10mm/div]
Small increase in resistance of
the main circuit when the main
contact fingers slide
Current curve
[100 A/div]
Arcing contact opens, current drops and
resistance is infinite.
22
I can get the Length of my Arching
contacts using DRM + Travel
16
17
Megger solutions
18
Megger History in CB Testing
TM1600 - 1989 EGIL - 1995
TM16 – 1984 DRM - 1993 TM1800 - 2005
TM1700s
2010
MA61 - 1994
DCM
Vibration testing – 2006
MA31 - 1988 1996
CABA - 1991 CABA Win - 1999
19
SDRM
STATIC / DYNAMIC RESISTANCE MEASUREMENT
ACCESSORY FOR EGIL/TM1700/TM1800
• SRM (Static Resistance Measurement)
• DRM (Dynamic Resistance Measurement)
• Small and light weight connected at breaker
• High Current Up to 250 A
• Three Models :
• SDRM201 For EGIL
• SDRM201 For TM1700/1800 (one Break Per
Phase)
• SDRM202 For TM1700/1800 (two Break Per
Phase)
20
MOM2 , MOM200/600A ,
MOM690
DLRO100E/X/H ,
DLRO200/600
MJOLNER 200/600
21
Summery
SRM is a Regular important test to Check Main contacts
DRM Non-invasive look at arcing contacts
Use high current for maximum resolution
Perform travel measurement simultaneously for best results
22
Thank you