Shenzhen Center Power
CL150 2V 150Ah(10hr)
Tech.Co.Ltd,.
Overview
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid
General Features Battery Specification
Absorbent Glass Mat (AGM) technology for efficient gas
Performance Characteristics
recombination of up to 99% and freedom from
Nominal Voltage 2V
electrolyte maintenance or water adding.
Number of cell 1
Not restricted for air transport-complies with IATA/ICAO
Design Life 20 years
Special Provision A67.
Nominal Capacity 77℉(25℃)
UL-recognized component. 10 hour rate (15.0A, 1.8V) 150Ah
Can be mounted in any orientation. 5 hour rate (27.0A, 1.75V) 135Ah
Computer designed lead, calcium tin alloy grid for high 1 hour rate (97.5A, 1.6V) 97.5Ah
power density. Internal Resistance
Long service life, float or cyclic Fully Charged battery 77℉(25℃) ≤0.85mOhms
applications. Self-Discharge
Maintenance-free operation. 3% of capacity declined per month at 20℃(average)
Low self discharge. Operating Temperature Range
Case and cover available in both standard and flame Discharge -20~60℃
retardant ABS. Charge -10~60℃
Storage -20~60℃
Max. Discharge Current 77℉(25℃) 750A(5s)
Dimensions and Weight Charge Methods: Constant Voltage Charge 77℉(25℃)
Cycle use 2.40-2.45VPC
Length(mm / inch) 172/6.77 Maximum charging current 30A
Width(mm / inch) 102/4.02 Temperature compensation -5.0mV/℃
Height(mm / inch) 205/8.07 Standby use 2.20-2.30VPC
Total Height(mm / inch) 217/8.54 Temperature compensation -3.3mV/℃
Approx. Weight(Kg / lbs) 8.2/18.1
* Weight deviation: ± 3%
Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell 15min 30min 45min 1h 3h 5h 10h
1.60V 221 147 121 97.5 41.7 29.2 16.1
1.65V 210 141 116 94.1 40.4 28.5 15.9
1.70V 199 134 111 90.2 38.5 27.8 15.7
1.75V 188 127 106 86.3 37.5 27.0 15.3
1.80V 177 120 100 82.2 35.8 26.0 15.0
Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell 15min 30min 45min 1h 2h 3h 5h
1.60V 386 294 221 184 118 79.8 58.5
1.65V 365 279 210 176 114 77.9 57.5
1.70V 344 264 200 168 110 75.8 56.3
1.75V 323 249 189 160 106 73.5 55.1
1.80V 301 233 178 151 101 71.0 53.8
(Note)The above characteristics data are average values
obtained within three charge/discharge cycles not the mimimum
values.All data shall be changed without notice,Vision reserves
the right to explain and update the information contained
hereinto.
Shenzhen Center Power Tech.Co.Ltd,. STOCK CODE: 002733 www.vision-batt.com
Shenzhen Center Power
CL150 2V 150Ah(10hr)
Tech.Co.Ltd,.
Discharge characteristic (25 OC) Charging characteristic for standby use
120 0.17 2.40
Battery Voltag e
100 0.14 2.20
2.0 )Ratio
Charged Volume(%)
C h a r g eC u r r e n t (C A )
80 0.11 2.00 Discharge
V o l t a g e (V )/P e rC e l l
100%(0.1CAx10H)
Voltage(V)
---- 50%(0.1CAx5H)
15A 60 0.08 1.80 Charge
37.5A 27A
Charge Voltage(2.25V/Cell)
1.6 Charge Current 0.1CA
300A 150A 97.5A 40 0.05 1.60
Temperature2 5
20 0.02 1.40
)
0
1 2 3 5 10 20 30 60 2 3 5 10 20
min h
0 4 8 12 16 20 24
Discharge time Charging time (hours)
Relationship between Self-discharge characteristic
charging voltage and temperature
100
2.6
90
2.5
Voltage (V)
CY C 80
LE
2.4 US E
70
2.3 ST A N
D BY 60
US E 40℃ 20℃
30℃
2.2 50
40
-10 0 2 4 6 8 10 12 14 16 18 20
Ambient temperature( ℃) Storage time: months
Cycle service life in relation to
Life characteristics of standby use
120
depth of discharge
120
100
100
80
Capacity(%)
Capacity(%)
80
60 60
Testing conditions: floating voltage: 2.25 to 2.30V/Cell 100% D.O.D. 50% D.O.D. 30% Depth of discharge
ambient temperature:
o 25 ℃(77 oF)
40 40
20 20
0 0 400 800 1200 1600 2000 2400
0 5 10 15
Life(year) Number of cycles(cycles)
Temperature effects on float life Temperature effects on capacity
120
2.30V/Cell 100
20 01. C
80 0. 2 C
10 0.3C
Life(years)
60
1.0C
5 40
2.0C
20
0 0
10 20 30 40 50 -20 -10 0 10 20 30 40 50
Temperature (℃) Temperature( ℃)
Shenzhen Center Power Tech.Co.Ltd,. STOCK CODE: 002733 www.vision-batt.com