Simotion c2xx Operating Manual
Simotion c2xx Operating Manual
Preface
___________________
Description 1
___________________
Operator control (hardware) 2
SIMOTION
___________________
Interfaces 3
SIMOTION C ___________________
Configuring and installing 4
___________________
Connecting 5
Operating Instructions
___________________
Addressing 6
___________________
Commissioning 7
___________________
Maintenance and servicing 8
___________________
Alarm, error, and system
messages 9
___________________
Technical data 10
___________________
Dimension drawing, spare
parts, and accessories 11
___________________
Standards, Certificates and
Approvals A
___________________
ESD guidelines B
02/2012
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the relevant information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Contents of manual
This document is part of the SIMOTION C documentation package.
SIMOTION C
Operating Instructions, 02/2012 3
Preface
● Spare parts/accessories
This section provides information on accessories and spare parts for SIMOTION C.
● Appendices with factual information for reference (for example, Standards and approvals,
ESD, etc.)
● Index to locate information
SIMOTION Documentation
An overview of the SIMOTION documentation can be found in a separate list of references.
This documentation is included as electronic documentation in the scope of delivery of
SIMOTION SCOUT. It comprises 10 documentation packages.
The following documentation packages are available for SIMOTION V4.3:
● SIMOTION Engineering System
● SIMOTION System and Function Descriptions
● SIMOTION Service and Diagnostics
● SIMOTION IT
● SIMOTION Programming
● SIMOTION Programming - References
● SIMOTION C
● SIMOTION P
● SIMOTION D
● SIMOTION Supplementary Documentation
SIMOTION C
4 Operating Instructions, 02/2012
Preface
Additional information
Click the following link to find information on the the following topics:
● Ordering documentation/overview of documentation
● Additional links to download documents
● Using documentation online (find and search in manuals/information)
[Link]
Please send any questions about the technical documentation (e.g. suggestions for
improvement, corrections) to the following e-mail address:
[Link]@[Link]
My Documentation Manager
Click the following link for information on how to compile documentation individually on the
basis of Siemens content and how to adapt this for the purpose of your own machine
documentation:
[Link]
Training
Click the following link for information on SITRAIN - Siemens training courses for automation
products, systems and solutions:
[Link]
FAQs
Frequently Asked Questions can be found in SIMOTION Utilities & Applications, which are
included in the scope of delivery of SIMOTION SCOUT, and in the Service&Support pages
in Product Support:
[Link]
Technical support
Country-specific telephone numbers for technical support are provided on the Internet under
Contact:
[Link]
SIMOTION C
Operating Instructions, 02/2012 5
Preface
Product disposal
SIMOTION C is an environmentally friendly product. It includes the following features:
● In spite of its excellent resistance to fire, the flame-resistant agent in the plastic used for
the housing does not contain halogens.
● Marking of the plastic materials as per ISO 11469.
● Less material used because the unit is smaller and with fewer components thanks to
integration in ASICs.
The product is to be disposed of in accordance with national regulations.
The product described in this manual can be recycled owing to its low pollutant content. To
recycle and dispose of your old device in an environmentally friendly way, please contact a
company that specializes in electronic waste.
SIMOTION C
6 Operating Instructions, 02/2012
Table of contents
Preface ...................................................................................................................................................... 3
1 Description............................................................................................................................................... 11
1.1 System overview ..........................................................................................................................11
1.2 I/O modules approved for SIMOTION .........................................................................................18
1.3 The fundamentals of motion control ............................................................................................20
1.4 Layout of the module ...................................................................................................................24
1.5 Nameplate....................................................................................................................................27
1.6 Versions of SIMOTION C.............................................................................................................29
2 Operator control (hardware)..................................................................................................................... 31
2.1 Control Elements .........................................................................................................................31
2.1.1 Mode selector...............................................................................................................................31
2.1.2 Micro Memory Card (MMC) .........................................................................................................32
2.2 Display elements..........................................................................................................................34
3 Interfaces................................................................................................................................................. 35
3.1 SIMOTION C interfaces ...............................................................................................................35
3.2 Ethernet interface.........................................................................................................................36
3.3 PROFINET interface (C240 PN) ..................................................................................................39
3.4 PROFIBUS DP interfaces ............................................................................................................42
3.5 Onboard drive interface (C230-2, C240) .....................................................................................45
3.6 Onboard measuring system interface (C230-2, C240) ................................................................52
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-
2, C240) .......................................................................................................................................63
3.7.1 Overview ......................................................................................................................................63
3.7.2 Configuration examples for C240: ...............................................................................................65
3.8 I/O interface..................................................................................................................................68
4 Configuring and installing ........................................................................................................................ 77
4.1 General requirements ..................................................................................................................77
4.2 Configuring an installation using SIMOTION C modules.............................................................78
4.2.1 Horizontal and vertical configuration............................................................................................78
4.2.2 Clearances ...................................................................................................................................79
4.2.3 Mounting dimensions of modules ................................................................................................80
4.2.4 Layout of modules on a rack........................................................................................................81
4.2.5 Layout of modules on several racks ............................................................................................82
SIMOTION C
Operating Instructions, 02/2012 7
Table of contents
SIMOTION C
8 Operating Instructions, 02/2012
Table of contents
SIMOTION C
Operating Instructions, 02/2012 9
Table of contents
SIMOTION C
10 Operating Instructions, 02/2012
Description 1
1.1 System overview
SIMOTION C
Operating Instructions, 02/2012 11
Description
1.1 System overview
System integration
SIMOTION offers an optimized system platform for automation and drive solutions where
priority is given to motion control applications and technological tasks.
The SIMOTION modular system consists of the SIMOTION SCOUT engineering system and
a common runtime system for various hardware platforms.
The truly innovative aspect of SIMOTION is that it does away with the traditional separation
between pure automation functions and motion functions.
3/&IXQFWLRQDOLW\
,(&
7KHV\VWHPDSSURDFKRI
0RWLRQ&RQWURO
HJSRVLWLRQLQJ 6,027,21
V\QFKURQRXVRSHUDWLRQ
7KHIXVLRQRIPRWLRQ
FRQWURO3/&DQG
7HFKQRORJ\ WHFKQRORJ\IXQFWLRQV
IXQFWLRQV
HJK\GUDXOLFFRQWURO
WHPSHUDWXUHFRQWURO
SIMOTION C
12 Operating Instructions, 02/2012
Description
1.1 System overview
SIMOTION can be used with all machines with motion control tasks. The focus is on a
simple and flexible solution to a wide variety of motion control tasks. In order to achieve this
in the best way possible, a new system approach has been introduced:
Motion control has been combined with two other open-loop control functions found in most
machines: PLC and technology functions.
This approach enables the motion control of axes and machine control within the same
system. The same applies to technology functions, such as pressure control of a hydraulic
axis. A seamless switch can be made from position-controlled positioning mode to pressure
control.
Combining the three open-loop control functions of motion control, PLC and technology
functions has the following benefits:
● Reduced engineering overhead and increased machine performance
● Time-critical interfaces between the individual components are no longer required
● Simple, uniform and transparent programming and diagnostics of the entire machine
SIMOTION C
Operating Instructions, 02/2012 13
Description
1.1 System overview
The following figures show system configurations with SIMOTION C230-2, C240 and
C240 PN.
3*3& 6
6,0$7,&
+0,GHYLFH
(WKHUQHW
352),%86'3
36 & 6,2
(7
2QERDUGGULYHLQWHUIDFH
352),%86'3LVRFKURQRXVHTXLGLVWDQW
(7
SIMOTION C
14 Operating Instructions, 02/2012
Description
1.1 System overview
6
3*3&
6,0$7,&
+0,GHYLFH
352),%86'3 (WKHUQHW
36 &31 6,2
(7
352),1(7,2
352),%86'3LVRFKURQRXVHTXLGLVWDQW (7
'5,9(&/L4
6,1$0,&6
6,1$0,&6
6,1$0,&6
&%(
(7
6,1$0,&6
6
,QIHHG 3RZHUVHFWLRQV
$FWLYH/LQH0RGXOH 0RWRU0RGXOH
Components
The most important components of a SIMOTION application with SIMOTION C and their
functions are listed below.
Note
The modules and devices approved for the SIMOTION C are listed in the SIMOTION PM 21
Catalog. This document is supplied in electronic format with SIMOTION SCOUT.
SIMOTION C
Operating Instructions, 02/2012 15
Description
1.1 System overview
Centralized I/O
Component Function
SIMOTION C ... is the motion control module. The SIMOTION C supplies the I/O
bus with 5 V; communicates over the I/O bus (backplane bus) with
the I/O modules.
You can use the integrated fast digital inputs of the SIMOTION C as:
B1 to B4: As homing inputs (C230-2, C240)
M1 and M2: As inputs for measuring inputs - local measuring
(C230-2, C240)
B1 to B4: As inputs for global measuring (C240, C240 PN)
Freely addressable process inputs
You can use the integrated fast digital outputs as:
Fast output cams
Freely addressable process outputs
Drive units with a ±10 V analog interface or stepper drives with a
pulse/direction interface can be connected to the onboard drive
interface (C230-2, C240). With the C240, the analog interfaces can
also be used as available process outputs.
Incremental encoders or absolute encoders can be connected to the
measuring system interface (C230-2, C240). With the C240, free
remaining encoder inputs of an axis channel can be used as the
input for a 16-bit up/down counter.
Power supply (PS) ... converts the line voltage (120/230 V AC) into an operating voltage
of 24 V DC to supply the SIMOTION C.
Signal modules (SM) ... adapt various process signal levels to the SIMOTION C (digital
input/digital output modules and analog input/analog output
modules).
Note:
All approved modules are listed in the PM 21 Catalog and in chapter
I/O modules approved for SIMOTION (Page 18).
Function modules (FM) ... relieve the CPU of computation-intensive tasks, for example,
counting.
Note:
All approved modules are listed in the PM 21 Catalog and in chapter
I/O modules approved for SIMOTION (Page 18).
Communications processors ... for data exchange
(CP) Note:
All approved modules are listed in the PM 21 Catalog and in chapter
I/O modules approved for SIMOTION (Page 18).
SIMOTION C
16 Operating Instructions, 02/2012
Description
1.1 System overview
Distributed I/O
Component Function
SIMOTION C ... is the motion control module.
Communicates via two PROFIBUS DP interfaces with:
– Programming device (PG/PC)
– SIMATIC HMI devices
– SIMATIC S7 controllers with PROFIBUS DP interface
– SIMATIC ET 200 I/O systems
– Drive units
– Other SIMOTION controllers
Communicates via an Ethernet interface with the programming
device (PG/PC)
The C240 PN also communicates via the PROFINET IO interface
with:
– Programming device (PG/PC) via Ethernet
– SIMATIC HMI devices
– SIMATIC S7 controllers with PROFINET IO interface
– SIMATIC ET 200 I/O systems with PROFINET IO interface
– Drive units
– Other SIMOTION controllers
Note:
All approved devices are listed in the PM 21 Catalog and in chapter
I/O modules approved for SIMOTION (Page 18).
Component Function
Programming device (PG/PC) ... configures, parameterizes, programs and tests SIMOTION.
SIMATIC HMI device ... is used for operator control and monitoring functions. It is not an
essential requirement for the operation of a SIMOTION C.
Note:
All approved devices are listed in the PM 21 Catalog.
Drive units ... convert speed setpoints into signals for controlling the motor and
supply the power required to operate the motors.
Note:
All approved devices are listed in the PM 21 Catalog.
SIMOTION C
Operating Instructions, 02/2012 17
Description
1.2 I/O modules approved for SIMOTION
Note
Please note that not all modules of the above-mentioned I/O or I/O systems are
approved for SIMOTION. Moreover, system-related functional differences can come
into play when these I/O or I/O systems are used on SIMOTION vs. on SIMATIC. For
example, special process-control functions (e.g. insertion and removal under voltage,
etc.) are not supported by SIMOTION for the SIMATIC ET 200M distributed I/O
system.
A detailed, regularly updated list of the I/O modules approved for use with SIMOTION,
as well as notes on their use, can be found on the Internet at:
[Link]
SIMOTION C
18 Operating Instructions, 02/2012
Description
1.2 I/O modules approved for SIMOTION
In addition to the I/O modules approved for SIMOTION, all certified standard slaves can, in
principle, be connected to SIMOTION if they support the following:
● Cyclic data traffic (DP-V0) and, possibly,
● Acyclic data traffic (DP-V1) or
● Isochronous data traffic (DP-V2)
These modules are integrated via the GSD file from the device manufacturer.
Note
Please note that in individual cases further boundary conditions must be fulfilled in order to
integrate a standard slave into SIMOTION. Some modules need "driver blocks", e.g. in the
form of function blocks, which make integration possible or much easier.
For modules approved for use with SIMOTION (e.g. S7-300 module FM 350-1, etc.), these
driver blocks:
Up to V3.2 SP1: SIMOTION Function Library
As of V4.0: SCOUT command library
SIMOTION C
Operating Instructions, 02/2012 19
Description
1.3 The fundamentals of motion control
Position-controlled motion control for servo axes via the onboard drive interface (C230-2, C240)
These enable position-controlled motion control of up to four axes. The C230-2/C240
provides one analog output per axis for the speed setpoint and one encoder input per axis
for the cyclic measurement of the actual position value.
6HUYRPRWRU
&& &RQYHUWHU (QFRGHU
3RZHUXQLW 0
'$& 6SHHG
VHWSRLQW a
3RVLWLRQ ; &XUUHQW
FRQWUROOHU
FRQWUROOHU
UHOHDVH 6SHHG $FWXDOVSHHGYDOXH
FRQWUROOHU
; $FWXDOSRVLWLRQYDOXH]HURPDUN
;
;
;
Figure 1-4 Servo system with converter, e.g. SIMODRIVE 611 universal, with built-in incremental
encoder
SIMOTION C
20 Operating Instructions, 02/2012
Description
1.3 The fundamentals of motion control
6HUYRPRWRU
&& &RQYHUWHU
(QFRGHU
6SHHG 0
'$& 3RZHUXQLW a
VHWSRLQW
3RVLWLRQ ;
&XUUHQW
FRQWUROOHU FRQWUROOHU
UHOHDVH 5RWRUSRVLWLRQ
$FWXDOSRVLWLRQ 6SHHG
YDOXH]HUR FRQWUROOHU
;PDUN
; $,(
;
;
Figure 1-5 Servo system with converter, e.g. SIMODRIVE 611 universal, with incremental encoder
6SHHG $FWXDOSRVLWLRQYDOXH]HURPDUN
FRQWUROOHU
Figure 1-6 Servo system with converter, for example SIMODRIVE 611 Universal
SIMOTION C
Operating Instructions, 02/2012 21
Description
1.3 The fundamentals of motion control
&\FOHFORFN 3RZHUXQLW 60
GLUHFWLRQ
([WHUQDO
3RVLWLRQ 3XOVH ;
FRQWUROOHU HQFRGHU UHOHDVH 5LQJFRXQWHU ]HURSXOVH
3KDVHFXUUHQW
FRQWUROOHU
5RWDWLRQ %%
PRQLWRULQJ ;
&RQWURO 6,0267(3
&&
(QFRGHU
3RZHUXQLW
&\FOH 60
3XOVH
GLUHFWLRQ 5LQJFRXQWHU
3RVLWLRQ 3KDVHFXUUHQW
FRQWUROOHU HQFRGHU ;
UHOHDVH FRQWUROOHU
; $FWXDOSRVLWLRQYDOXH]HURPDUN
;
;
;
SIMOTION C
22 Operating Instructions, 02/2012
Description
1.3 The fundamentals of motion control
Position-controlled motion control for servo axes (C240 PN, PROFINET IO)
The C240 PN enables position-controlled motion control of axes via PROFINET IO.
Figure 1-9 Servo system with converter, e.g. SINAMICS S120 with CBE20
SIMOTION C
Operating Instructions, 02/2012 23
Description
1.4 Layout of the module
0LFUR0HPRU\&DUG00&
0RXQWLQJUDLO
7\SHSODWH
(MHFWRUIRU
PLFURPHPRU\FDUG
%XVFRQQHFWRUIRU,2EXV
)URQWYLHZZLWKRXWIURQWGRRUV
0HPRU\PRGXOHVORWIRU (WKHUQHW0$&DGGUHVV
PLFURPHPRU\FDUG (WKHUQHWLQWHUIDFH;
(UURUDQGVWDWXVGLVSOD\V
6)
& 6,(0(16
; ; ;
'&9
581
67238
6WDWXVGLVSOD\V
6723 'LJLWDOLQSXWVRXWSXWV
581
%86) 67238
%86)
6723
05(6
; )URQWFRQQHFWRU
0RGHVHOHFWRUVZLWFK
'&9
&RQQHFWLRQIRUSRZHU 0
VXSSO\; /
0
;'3 ;'303,
; ; ;
,2LQWHUIDFH;
Figure 1-10 Position of the C230-2 interfaces and front panel elements
SIMOTION C
24 Operating Instructions, 02/2012
Description
1.4 Layout of the module
0LFUR0HPRU\&DUG00&
0RXQWLQJUDLO
7\SHSODWH
(MHFWRUIRU
PLFURPHPRU\FDUG
%XVFRQQHFWRUIRU,2EXV
)URQWYLHZZLWKRXWIURQWGRRUV
(WKHUQHW0$&DGGUHVV
0HPRU\PRGXOHVORWIRU
PLFURPHPRU\FDUG (WKHUQHWLQWHUIDFH;
(UURUDQGVWDWXVGLVSOD\V 6)
& 6,(0(16
; ; ;
'&9
581
67238
6WDWXVGLVSOD\V
6723 'LJLWDOLQSXWVRXWSXWV
581
%86)
6723
%86)
05(6
0RGHVHOHFWRUVZLWFK ; )URQWFRQQHFWRU
'&9
&RQQHFWLRQIRUSRZHU
0
VXSSO\; /
0
; ; ;
;'3 ;'303, ,2LQWHUIDFH;
Figure 1-11 Position of the C240 interfaces and front panel elements
SIMOTION C
Operating Instructions, 02/2012 25
Description
1.4 Layout of the module
0LFUR0HPRU\&DUG00&
0RXQWLQJUDLO
7\SHSODWH
(MHFWRUIRU
PLFURPHPRU\FDUG
%XVFRQQHFWRU
IRU,2EXV
)URQWYLHZZLWKRXWIURQWGRRUV
(WKHUQHW0$&DGGUHVV
0HPRU\PRGXOHVORWIRU 352),1(7,20$&DGGUHVV
PLFURPHPRU\FDUG (WKHUQHWLQWHUIDFH;
(UURUDQGVWDWXVGLVSOD\V
; ,( $8$%$$
6)
&31 6,(0(16
,(
;
31
3
3
3
6WDWXVGLVSOD\V
'&9 'LJLWDOLQSXWVRXWSXWV
581
67238 (7+(51(7SRUW/('
6723
/LQNJUHHQ
581
%86)
%86)
6723 $FWLYLW\\HOORZ
05(6
)URQWFRQQHFWRU
0RGHVHOHFWRUVZLWFK ;
352),1(7SRUW/('
/LQNJUHHQ
$FWLYLW\\HOORZ
'&9
Figure 1-12 Position of the C240 PN interfaces and front panel elements
SIMOTION C
26 Operating Instructions, 02/2012
Description
1.5 Nameplate
1.5 Nameplate
Note
The contents of the individual type plate fields on the current module may differ from those
described in this manual (e.g. updated product status, approvals and markings not yet
issued, etc.).
SIEMENS 6,027,21
& ,1387'&9$
$;,6&21752/ '2'&9$$','&9
%DUFRGH0/)%QR3$8$$$$
3 $8$$$$
%DUFRGH3URGXFW1R$( %DUFRGHYHUVLRQ
$( 9HUV$
%DUFRGHVHULDOQR673
673 1
%DUFRGH0$&DGGUHVV
0DGHLQ*HUPDQ\ ,1'&217(4
5$
0$&DGGUHVV 3URGXFWYHUVLRQ
6HULDOQXPEHU 2UGHUQXPEHU
0RGXOHGHVLJQDWLRQ &RQQHFWLRQSDUDPHWHUV
SIMOTION C
Operating Instructions, 02/2012 27
Description
1.5 Nameplate
%DUFRGH0/)%QR
%DUFRGHSURGXFWQR %DUFRGH0$&DGGUHVV
%DUFRGHVHULDOQR
%DUFRGHYHUVLRQ
[Link].
58RA
9HUVLRQ 0$&DGGUHVV
6HULDOQXPEHU &RQQHFWLRQSDUDPHWHU
2UGHUQR
0RGXOHGHVLJQDWLRQ
%DUFRGH0/)%QR
%DUFRGHSURGXFWQR %DUFRGH0$&DGGUHVV,(
%DUFRGHVHULDOQR %DUFRGH0$&DGGUHVV31
%DUFRGHYHUVLRQ
9HUVLRQ VW0$&DGGUHVV31
6HULDOQXPEHU 0$&DGGUHVV,(
2UGHUQR &RQQHFWLRQSDUDPHWHU
0RGXOHGHVLJQDWLRQ
SIMOTION C
28 Operating Instructions, 02/2012
Description
1.6 Versions of SIMOTION C
SIMOTION C
Operating Instructions, 02/2012 29
Description
1.6 Versions of SIMOTION C
Note
In order to take the different versions into account, the product will be referred to in this
manual as "SIMOTION C". Specific product designations will be used for information that
applies only to one product version, e.g. for SIMOTION C230-2, C240 or C240 PN.
SIMOTION C
30 Operating Instructions, 02/2012
Operator control (hardware) 2
2.1 Control Elements
Operating Explanations
mode
RUN SIMOTION C executes the user program (UP) and the associated system functions:
Reading process image of inputs
Execution of the user programs assigned to the execution system
Writing process image of outputs
The technology packages are active in this state. They can execute commands from
the user program.
Note:
With the C230-2, the key cannot be removed in this position.
STOPU SIMOTION C does not execute a user program.
The technology packages are active. Test and commissioning functions can be
executed. The user program is not active.
The I/O modules (SMs) are in a safe state.
With the C230-2, the key can be removed in this position so that no unauthorized
person can change the operating modes.
Note:
The toggle switch of the C240 / C240 PN does not have the "STOPU" switch setting.
You can switch to "STOPU" mode only via the SIMOTION SCOUT engineering
system.
In SIMOTION SCOUT, you can switch from the hardware settings "STOP" and "RUN"
to "STOPU" mode.
SIMOTION C
Operating Instructions, 02/2012 31
Operator control (hardware)
2.1 Control Elements
Operating Explanations
mode
STOP SIMOTION C does not execute a user program.
It is possible to load a complete user program.
All system services (communications, etc.) are active.
The I/O modules (SMs) are in a safe state.
The technology packages are inactive, i.e. all enables are deleted. No axis
motions can be executed.
Note:
With the C230-2, the key can be removed in this position so that no unauthorized
person can change the operating modes.
MRES Pushbutton position for memory reset on the SIMOTION C.
(memory A memory reset by means of a mode selector requires a specific sequence of
reset) operation, see chapter SIMOTION C memory reset (Page 154).
CAUTION
The micro memory card may only be inserted or removed when the control unit is
disconnected from the power supply.
SIMOTION C
32 Operating Instructions, 02/2012
Operator control (hardware)
2.1 Control Elements
CAUTION
The micro memory card may only be inserted or removed when the control unit is
disconnected from the power supply.
SIMOTION C
Operating Instructions, 02/2012 33
Operator control (hardware)
2.2 Display elements
LED displays
The following LED displays are on the front panel of the SIMOTION C. This table describes
the LEDs and their function.
LED Meaning
SF (red) This LED indicates a fault on the SIMOTION C.
5 VDC (green) This LED indicates that the power supply for the electronics is ready.
RUN (green) - This LED indicates that the user program is running.
SIMOTION C in RUN mode
STOPU (yellow) - This LED indicates that the technology packages (for example,
SIMOTION C in STOP user synchronous operation and cam) are active. The user program is not
program mode active.
STOP (yellow) - This LED indicates that no user program is running. The technology
SIMOTION C in STOP mode packages are not active.
BUS1F (red) - This LED indicates a fault on the SIMOTION C PROFIBUS DP1
Group fault interface (X8).
BUS2F (red) - This LED indicates a fault on the SIMOTION C PROFIBUS DP2/MPI
Group fault interface (X9).
Q0 to Q7 , I0 to I11 , These LEDs show the status of the digital inputs/outputs.
B1 to B4, M1, M2 (green) -
Digital inputs/digital outputs
The following LED displays are arranged the front cover of the SIMOTION C240 PN. This
table describes the LEDs and their function.
Table 2- 3 Status and fault displays behind the front cover (C240 PN)
LED Meaning
Ethernet link (X7) (green) This LED indicates a physical connection of the Ethernet
interface.
Ethernet activity (X7) (yellow) This LED indicates a data transfer via the Ethernet interface.
PROFINET link (X11 Px) (green) This LED indicates a physical connection of the PROFINET
interface at port x.
PROFINET activity (X11 Px) (yellow) This LED indicates a data transfer via the PROFINET
interface at port x.
PROFINET fault (X11) (red) This LED indicates a fault at the PROFINET interface.
PROFINET sync (X11) (green) This LED indicates synchronization status of the PROFINET
interface.
See also
Diagnosis using the LEDs (Page 165)
SIMOTION C
34 Operating Instructions, 02/2012
Interfaces 3
3.1 SIMOTION C interfaces
The interfaces and their meaning are described in following table.
Table 3- 1 Interfaces
Interfaces Description
Bus connector Rear-mounted connector for connecting to other S7 modules via the
I/O bus
Drive interface (onboard) 50-pin Sub-D connector X2 for the analog connection of analog and
(C230-2, C240) stepper drives (max. 4 axes)
Measuring system interface 15-pin Sub-D sockets X3 to X6 for connection of encoders (max. 4)
(onboard) (C230-2, C240)
I/O interface 40-pin front connectors X1 for connecting the fast digital inputs/digital
outputs including measuring inputs and external zero mark and for
wiring the READY relay
Power supply connection 4-pin screw-type terminal connection X10 for connecting the 24 V
load power supply
Memory module slot Slot for micro memory card (MMC)
PROFIBUS DP1 interface 9-pin Sub-D socket X8 for connection to the PROFIBUS DP. This
interface can be used for isochronous operation
PROFIBUS DP2/MPI 9-pin Sub-D socket X9 for connection to PROFIBUS DP (factory
interface setting) or an MPI bus
This interface can be used for isochronous operation.
Ethernet interface 8-pin RJ45 socket X7 for connection to an Industrial Ethernet
PROFINET interface with 3 x 8-pin RJ45 sockets X11 P1, X11 P2 and X11 P3 for connecting to
three ports (C240 PN) PROFINET subnets
SIMOTION C
Operating Instructions, 02/2012 35
Interfaces
3.2 Ethernet interface
Definition
Interface for connecting an Industrial Ethernet.
Industrial Ethernet is a communication network with a transmission rate of 10/100 Mbit/s.
The SIMOTION C provides the following functions via the Ethernet interface:
● Communication with STEP 7 and SIMOTION SCOUT
● Communication with distributed I/O (e.g. SIMATIC HMI)
● Communication between SIMOTION and SIMATIC NET OPC
The "SIMATIC NET SOFTNET S7 (S7 OPC server)"
software must be installed on the PG/PC for this function.
Note:
SOFTNET-S7 is a superset of SOFTNET-PG, i.e. SOFTNET-S7 contains Protocol
TPC/IP RFC 1006 as well.
For more information about the software packages, see SIMOTION Motion Control System,
PM 21 Catalog. This documentation is supplied in electronic format with SIMOTION SCOUT.
Connectable devices
A PG/PC can be connected to the Ethernet interface via a Fast Ethernet network. The PG
must be equipped with an Ethernet card and the corresponding software must be available.
SIMOTION C
36 Operating Instructions, 02/2012
Interfaces
3.2 Ethernet interface
Interface position
The following figures show the installation position and the designation of the interface on
the C230-2, C240 and C240 PN modules.
(WKHUQHW0$&DGGUHVV 6,(0(16 ; ; ;
HJ% &
;
581
6723
05(6
;
;'3 ;'303, ; ; ;
; ,( $8$%$$
,( 3
; 3
31 3
3URILQHW,20$&DGGUHVV
; 581
6723
05(6
;
Interface assignment
Designation: X7 (Ethernet)
Type: 8-pin RJ45 socket
SIMOTION C
Operating Instructions, 02/2012 37
Interfaces
3.2 Ethernet interface
Signal names
RDP, RDM - Receive Data +/-
TDP, TDM - Transmit Data +/-
Signal type
I - signal input
O - signal output
Note
You will find additional information about Ethernet in the SIMOTION SCOUT Communication
System Manual.
SIMOTION C
38 Operating Instructions, 02/2012
Interfaces
3.3 PROFINET interface (C240 PN)
Definition
A SIMOTION C240 PN provides an interface for connecting to PROFINET IO with three
ports (X11 P1, X11 P2, X11 P3) with a transmission rate of 100 Mbit/s. The PROFINET
interface supports the parallel operation of:
● IRT with the "high flexibility" and "high performance" options - isochronous real-time
communication:
– Equidistant transmission of input/output data between an IO controller and its IO
devices with high stability for time-critical applications (e.g. motion control). The
required bandwidth is in the bandwidth reserved for cyclic data. For "high flexibility", a
fixed bandwidth of the transmission resources is reserved for the real-time
communication. The "high flexibility" enables simple planning and expansion of the
system. For "high performance", a fixed bandwidth of the transmission resources is
also reserved for the real-time communication. The data traffic is further optimized and
accelerated through an additional topology planning. The "high performance" option
always requires a configuration of the topology.
– With the aid of IRT "high performance", IO devices (I/O modules and drive units) that
support IRT can be operated isochronously on PROFINET IO and data can be
exchanged between the SIMOTION devices via the controller-controller data
exchange broadcast.
● RT - real-time communication: Transmission of input/output data between an IO controller
and its IO devices in prioritized Ethernet message frames, but not isochronously. The
required bandwidth is in the bandwidth of PROFINET IO reserved for cyclic data.
● Standard Ethernet communication such as TCP/IP, UDP, HTTP, FTP, etc. as well as
communication with STEP 7 / SIMOTION SCOUT and communication with SIMATIC NET
OPC:
The required bandwidth is in the free bandwidth of PROFINET IO.
A SIMOTION C240 PN can be used as IO controller or I device. PROFINET IO differentiates
between an IO controller and the IO devices assigned to it. IO controller and IO devices form
a PROFINET IO system, comparable to a master-slave system on PROFIBUS DP.
SIMOTION C
Operating Instructions, 02/2012 39
Interfaces
3.3 PROFINET interface (C240 PN)
Connectable devices
The following devices can be connected to the PROFINET interface:
● PG/PC programming device
● SIMATIC HMI devices
● SIMATIC S7 controllers with PROFINET interface
● Distributed I/O (e.g. SIMATIC ET 200M) with PROFINET interface
● Drive units with PROFINET interface
● SIMOTION devices with PROFINET interface according to PROFIdrive profiles /
IEC61800-7
● Teleservice adapter
● Gateways
Note
All released modules and devices are listed in the PM 21 Catalog and in chapter I/O
modules approved for SIMOTION (Page 18). This documentation is supplied in electronic
format with SIMOTION SCOUT. Take note of the documentation on the individual
modules or devices!
Interface position
The following figure shows the mounting position and the designation of the PROFINET IO
interface on the module.
; ,( $8$%$$
,( 3
; 3
31 3
&31 6,(0(16
;3 581
6723
05(6
;
;3
;3
Figure 3-3 X11 interface position (C240 PN), three ports P1, P2, P3
The following LED displays are arranged behind the front cover of the SIMOTION C240 PN.
For a description of the LED displays, see section Display elements (Page 34).
SIMOTION C
40 Operating Instructions, 02/2012
Interfaces
3.3 PROFINET interface (C240 PN)
Interface assignment
Designation: X11 (PROFINET), three ports P1, P2, P3
Type: 8-pin RJ45 socket
Signal names
RDP, RDM - Receive Data +/-
TDP, TDM - Transmit Data +/-
Signal type
I - signal input
O - signal output
Note
You will find additional information about PROFINET in the SIMOTION SCOUT
Communication System Manual.
SIMOTION C
Operating Instructions, 02/2012 41
Interfaces
3.4 PROFIBUS DP interfaces
Connectable devices
The following devices can be connected to the PROFIBUS DP interfaces:
● PG/PC
● SIMATIC HMI devices
● SIMATIC S7 controllers with PROFIBUS DP interface
● Distributed I/O (e.g. SIMATIC ET 200M)
The digital inputs/digital outputs are updated in the position control cycle clock.
● SIMOTION controller
● Teleservice adapter
● Drive units with PROFIBUS DP interface (e.g. SIMODRIVE 611 universal) according to
PROFIdrive profiles / IEC61800-7.
Note
A teleservice adapter can only be connected to one of the two interfaces.
All released modules and devices are listed in the PM 21 Catalog and in chapter I/O
modules approved for SIMOTION (Page 18). This document is supplied in electronic
format with SIMOTION SCOUT.
Take note of the documentation on the individual modules or devices!
SIMOTION C
42 Operating Instructions, 02/2012
Interfaces
3.4 PROFIBUS DP interfaces
Interface positions
The following figure shows the mounting position and the designation of the interfaces on the
module.
'303,
& ; ; ;
6,(0(16
'3
581
6723
05(6
;
;
;
;'3 ;'303,
; ; ;
Interface assignments
Designation: X8, X9 DP1, DP2/MPI Type: 9-pin Sub-D socket connector
SIMOTION C
Operating Instructions, 02/2012 43
Interfaces
3.4 PROFIBUS DP interfaces
Signal names
Signal type
O - signal output
I/O - signal input/output
VO - voltage output
SIMOTION C
44 Operating Instructions, 02/2012
Interfaces
3.5 Onboard drive interface (C230-2, C240)
$1$/2*287
67(33(5&75/
& ; ; ;
6,(0(16
581
6723
05(6
;
;'3 ;'303,
; ; ;
;
SIMOTION C
Operating Instructions, 02/2012 45
Interfaces
3.5 Onboard drive interface (C230-2, C240)
Signal names
SIMOTION C
46 Operating Instructions, 02/2012
Interfaces
3.5 Onboard drive interface (C230-2, C240)
Signal type
O - signal output
VO - voltage output
K - switching contact
WARNING
Brief voltage peaks may occur at the analog outputs when the supply voltage is switched
on or off.
For this reason, it is important to make sure that the enable signals are wired correctly and
that the necessary safety regulations are met.
SIMOTION C
Operating Instructions, 02/2012 47
Interfaces
3.5 Onboard drive interface (C230-2, C240)
Stepper drives
Signals:
One clock pulse signal, direction signal, and enable signal is provided as a true and negated
signal.
● Setpoint (PULS)
The clock pulses control the motor. The motor performs one step for each rising pulse
edge.
Thus, the number of pulses output determines the angle of rotation, i.e. the distance to be
traversed.
The pulse frequency determines the rotational speed, i.e. the traversing speed.
CAUTION
If your drive unit responds to falling pulse edges, you must replace the true pulse signal
with the negated pulse signal when performing the wiring; failure to do so can cause
deviations to occur between the position calculated by the controller and the actual
position.
Note
If the direction of rotation of the motor is different, you can change the direction of rotation
by means of the "Reversal of traversing direction" configuration data element. Refer to
the technical documentation of your drive unit for the correct assignment of the signal
levels to the direction of rotation.
Note
The ENABLE signal is output at the same time with controller enable contact RF.
Alternatively, you can also use the relay contacts.
SIMOTION C
48 Operating Instructions, 02/2012
Interfaces
3.5 Onboard drive interface (C230-2, C240)
Signal parameters
All signals for stepper drives are output by means of differential signal line drivers in
accordance with the RS422 standard. For optimal reliability, the power unit should have
differential signal receivers or optical coupler inputs to enable symmetrical signal
transmission. An asymmetrical transmission is also possible, however, the maximum cable
length in this case is limited to 10 m.
Note
Because of the wide range of non-standardized input circuits of the drive units during
asymmetrical transmission, no responsibility can be taken for this function. In particular,
cable lengths and the limit frequency depend on the properties of the input circuit and the
cable being used. In addition, the GND reference potential should be isolated to prevent
electrical interference.
All outputs are electronically protected against short-circuit and thermal overload.
SIMOTION C
Operating Instructions, 02/2012 49
Interfaces
3.5 Onboard drive interface (C230-2, C240)
The following figure shows different possibilities for protective signal circuits.
6\PPHWULFWUDQVPLVVLRQZLWKGLIIHUHQWLDOLQSXWDFFRUGLQJWR56
,2
92' 5/
92/ 92+
*1'
6\PPHWULFDOWUDQVPLVVLRQZLWKRSWRFRXSOHULQSXW
/ืP
*1'
$V\PPHWULFDOWUDQVPLVVLRQZLWKRSWRFRXSOHULQSXW
/ืP
*1'
$V\PPHWULFDOWUDQVPLVVLRQZLWKYROWDJHLQSXW
/ืP
*1' *1'
Figure 3-6 Possible protective signal circuits for the stepper motor interface
SIMOTION C
50 Operating Instructions, 02/2012
Interfaces
3.5 Onboard drive interface (C230-2, C240)
&
6(73
$QDORJRXWSXW
5()327
&75(1
'LJLWDORXWSXW
&75(1
*1'
.
.
.
6(73
$QDORJRXWSXW
5()327
&75(1
'LJLWDORXWSXW
&75(1
*1'
See also
Overview (Page 63)
SIMOTION C
Operating Instructions, 02/2012 51
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Position of connectors
This figure shows the mounting position and the designation of the connector on the module.
& ; ; ; (1&2'(5
6,(0(16
;;
581
6723
05(6
;
; ; ;
;'3 ;'303, (1&2'(5
SIMOTION C
52 Operating Instructions, 02/2012
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Signal names
Signal type
VO - voltage output (supply)
O - output (5 V signal)
I - input (5 V signal)
SIMOTION C
Operating Instructions, 02/2012 53
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Note
If you operate drives via the PROFIBUS DP, you do not need to connect any encoders to
this interface. The encoders are connected directly to the drive.
SIMOTION C
54 Operating Instructions, 02/2012
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Note
Please note the drive manufacturer's wiring specifications. As the encoder interface of the
C230-2, C240 is non-isolated, it may be necessary to take special measures for EMC on a
case-by-case basis.
Encoder properties
Incremental encoder
Property Condition
Transmission procedure: Differential transmission using 5 V rectangular signals (as in RS422
standard)
Output signals:
Track A as non-inverted and inverted signal 8D8D
SIMOTION C
Operating Instructions, 02/2012 55
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
ุQV ุQV
$
$B1
%
%B1
ุQV
=
=B1
&RXQWSXOVHZLWKSXOVHTXDGUXSOLFDWLRQ
Note
If you want to connect incremental encoders without zero signals, then you must connect the
corresponding pins in the connector with the encoder power supply:
Pin 10 with Pin 7 or 9 (MEXT)
Pin 11 with Pin 4 or 6 (P5EXT)
SIMOTION C
56 Operating Instructions, 02/2012
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Property Features
Transmission procedure: Synchronous serial interface (SSI) with 5 V differential signal transmission
(as in RS422 standard)
Output signal: Data as non-inverted and inverted signal
Input signal: Clock shift as non-inverted and inverted signal
Format: Single/multi-turn
Resolution: max. 25 bits
Max. transmission rate: 1.5 Mbits/s
Current consumption: max. 300 mA
Message length: 13/21/25 cycles can be selected (asymmetric fir tree profile)
Encoder pulses per ≤ 2(message length -12)
revolution:
Data width: ≤ 12 + (log encoder pulses per revolution / log 2)
Note: The number of bit digits needed for representation of the
encoder pulses per revolution is calculated using (log encoder pulses
per revolution / log 2).
SIMOTION C
Operating Instructions, 02/2012 57
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
0D[LPXPHQFRGHUSXOVHVSHUUHYROXWLRQLQFUHY
GXULQJF\FOHV
GXULQJF\FOHV
GXULQJF\FOHV
1XPEHURIUHYROXWLRQV 1XPEHURILQFUHPHQWV
; ; ; ;
; ; ; ; ;
/HDGLQJ]HURVRIHQFRGHU 6XEVHTXHQW]HURVRIHQFRGHU
([DPSOH)LUWUHHHQFRGHUSURILOH[ELWGDWDZLGWK
0D[LPXPGDWDZLGWK
0LQLPXPPHVVDJHOHQJWK
Note
Please note the following:
Bit 20 of the number of revolutions is fixed on the 12th cycle, followed on the 13th cycle by
the most significant bit of the number of increments/revolution.
The leading and subsequent data bits transmitted by the encoder (or zeros) are not
evaluated by SIMOTION C.
The encoder used in the example should be configured as follows:
– Encoder pulses per revolution: 256
– Data width: 16
– Message length: 21 bits (or 25 bits)
– Message profile: Fir tree
SIMOTION C
58 Operating Instructions, 02/2012
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Right-justified profile
The most significant data bit is transmitted by the encoder with the first cycle. The configured
data width is monitored by the encoder driver depending on the configured message length.
The maximum encoder pulses per revolution is monitored depending on the data width
configured.
Configuration data:
SIMOTION C
Operating Instructions, 02/2012 59
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
)RUF\FOHFORFNV 0D[LPXPGDWDZLGWK
)RUF\FOHFORFNV
)RUF\FOHFORFNV
7RWDOYDOXHUDQJHRIWKHHQFRGHU
; ; ; ; ; ; ; ; ; ; ; ; ;
([DPSOHELWVLQJOHWXUQHQFRGHUGDWDZLGWKELWV
SIMOTION C
60 Operating Instructions, 02/2012
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Note
Please note the following:
The most significant data bit for the encoder's entire range of values is transmitted by the
encoder with the first cycle.
Subsequent data bits transmitted by the encoder (or zeros) are not evaluated by
SIMOTION C.
The encoder used in the example should be configured as follows:
– Encoder pulses per revolution: 4096
– Data width: 12
– Message length: 13 bits (or 21 bits or 25 bits)
– Message profile: Right-justified
Encoder supply 5 V
The 5 V supply voltage for the encoders is generated inside the module and is therefore
present at the Sub-D socket. This means you can supply the encoders via the connecting
cable without the need for additional wiring. The voltage supplied is protected electronically
against short circuits and thermal overload, and it is monitored. The encoder supply is not
isolated from the load power supply to the module.
Encoder supply 24 V
For encoders with an operating voltage of 24 V, the 24 VDC power is supplied to the Sub-D
sockets. This means you can supply the encoders via the connecting cable without the need
for additional wiring. The voltage supplied is protected electronically against short circuits
and thermal overload, and it is monitored. The encoder supply is not isolated from the load
power supply to the module.
SIMOTION C
Operating Instructions, 02/2012 61
Interfaces
3.6 Onboard measuring system interface (C230-2, C240)
Note
With certain selected set values for the position control cycle clock, the measured value
sampling in the C240 takes place at time Ti before the position control cycle clock time, see
"Actual value latch time" table, in chapter Technical data (Page 171). This behavior is similar
to that of PROFIBUS DP encoders.
$FWXDOYDOXHODWFKWLPH
3RVLWLRQFRQWUROF\FOHFORFNWLPH
7L 7 W
3RVLWLRQFRQWUROF\FOH
Supply voltage Encoder supply voltage range Current Max. cable length
consumption
5 VDC 4.75 V to 5.25 V < 300 mA 25 m
5 VDC 4.75 V to 5.25 V < 210 mA 35 m
24 VDC 20.4 V to 28.8 V < 300 mA 100 m
24 VDC 10 V to 30 V < 300 mA 250 m
SIMOTION C
62 Operating Instructions, 02/2012
Interfaces
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-2, C240)
3.7.1 Overview
The onboard drive interface and the measuring system interface can be used in the
application for the technology objects TO axis and TO externalEncoder, and for I/O variable.
The table below lists the combination possibilities for the C230-2/C240.
Note
A standard output and a drive cannot be used simultaneously on one axis channel.
The input (X3 to X6) used as a counter input cannot be used simultaneously as an encoder
input.
When a project is created and when a project is downloaded, a consistency check of the
permitted combinations per axis channel is automatically performed.
SIMOTION C
Operating Instructions, 02/2012 63
Interfaces
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-2, C240)
This results in the following possibilities in the application for the C240, for example:
● Configuration of hydraulic axes on the onboard resources of the C240
● Use of unassigned axis channels of the C240 as I/O variable for the user program
● Use of the analog outputs of the C240 as unassigned process outputs
Note: The resolution and the characteristic curve of the analog output of the C240 differ
from those of a SIMATIC S7 controller. The following table lists the digital values and
their associated analog values (characteristic curve).
See also
Connecting the drive units (Page 103)
SIMOTION C
64 Operating Instructions, 02/2012
Interfaces
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-2, C240)
SIMOTION C
Operating Instructions, 02/2012 65
Interfaces
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-2, C240)
SIMOTION C
66 Operating Instructions, 02/2012
Interfaces
3.7 Possible uses of onboard drive and measuring system interface in the application (C230-2, C240)
Note
Use of the drive and encoder interfaces as standard outputs and counter inputs is only
possible via their direct I/O address. Symbolic assignment is not available for this
application.
SIMOTION C
Operating Instructions, 02/2012 67
Interfaces
3.8 I/O interface
Front connector
Various encoders and actuators can be connected via digital inputs and outputs to the 40-pin
front connector X1 with single-wire connection.
)URQWFRQQHFWRULQZLULQJSRVLWLRQ /DEHOLQJRILQQHUGRRU
/ /
; 5'<
0 0
SIMOTION C
68 Operating Instructions, 02/2012
Interfaces
3.8 I/O interface
,QWHUQDOEDVLFFLUFXLW
/
6,027,21& 9
%
%
0
%
%
0
0
0
0
0RXWSXW 0LQSXW 9
6WDWXVGLVSOD\V JUHHQ
Figure 3-14 Terminal and block diagram of digital inputs/outputs on the SIMOTION C
SIMOTION C
Operating Instructions, 02/2012 69
Interfaces
3.8 I/O interface
SIMOTION C
70 Operating Instructions, 02/2012
Interfaces
3.8 I/O interface
Signal names
Signal type
DI - digital input (24 V signal)
DO - digital output (24 V signal)
K - switching contact
VI - voltage input
DANGER
Note
The connecting cable between the voltage source and the load current supply connector L+
and the associated reference potential M should not exceed a maximum length of 10 m.
SIMOTION C
Operating Instructions, 02/2012 71
Interfaces
3.8 I/O interface
SIMOTION C
72 Operating Instructions, 02/2012
Interfaces
3.8 I/O interface
● As inputs for measuring pulses for global measuring (B1 to B4) on the C240/C240 PN
Alternatively to the "external zero mark signals" function, these inputs can be used on the
C240 / C240 PN for global measuring.
Note: The inputs for global measurement (B1 to B4) can be used in addition to the inputs
for local measurement (M1, M2).
With a signal edge at the relevant input, the current actual values of one or more
encoders are measured with positioning accuracy in order to provide information for
determining lengths or distances (possible with any encoders included in the project).
The assignment of inputs is not fixed; the special use is activated in the SCOUT
engineering system during configuration of the Measuring Input TO (see the configuration
example below for global measuring).
Up to two edges can be measured for each position-control cycle clock of the Measuring
Input TO.
The measured values must be read from the user program before they can be overwritten
by a new measurement.
Global measuring can be used for the following applications:
– Several Measuring Input TOs on one axis/encoder where they can be active
simultaneously
– Several Measuring Input TOs are assigned to one measuring input (where one
Measuring Input TO is interconnected to one measuring input and the remaining
Measuring Input TOs are configured as listening measuring inputs)
This functionality enables one measuring input to act on several Measuring Input TOs
and thus on several axes / external encoders.
– In addition to single measuring, cyclic measuring is also supported
– Measuring on virtual axes
SIMOTION C
Operating Instructions, 02/2012 73
Interfaces
3.8 I/O interface
Note
Local measuring (onboard) on SIMOTION C
A measurement is only undertaken when there are at least 2 servo cycles between the
_enableMeasuringInput command being called and the real switching signal expected
on the probe (positive/negative flank).
In order to reliably guarantee time-critical processes, the programming should be
undertaken in a synchronous task, e.g. IPO-synchronous task. It may take up to 2
servo cycles for the measurement to be available in
Messtaster.counterMeasuredValue1 after the status change in
[Link] (POSITIVE => NEGATIVE or vice versa).
When the measurement result is received, the measurement position is stored. Once
the measurement has been taken, the state variable is set to TRIGGER_OCCURRED,
and the measured values can be evaluated using the measuredValue1 and
measuredValue2 variables for two measured edges.
The counterMeasuredValue1 and counterMeasuredValue2 counter variables are
defined for the measuredValue1 and measuredValue2 system variables and are
automatically incremented by a value of one for each measurement input. New results
can be traced immediately and can also be read from non-IPO-synchronous tasks.
You will find detailed information on this subject in the SIMOTION Function Manual
Output Cams and Measuring Inputs.
SIMOTION C
74 Operating Instructions, 02/2012
Interfaces
3.8 I/O interface
Figure 3-15 Configuration example for global measuring (without symbolic assignment)
With a signal edge at the measurement input, the current actual value of the assigned
encoder is recorded with an exact position.
SIMOTION C
Operating Instructions, 02/2012 75
Interfaces
3.8 I/O interface
READY output
The ready signal (RDY.1, RDY.2) is an isolated contact assembly (make contact).
The contact can be used for the safe shutdown of parts of the system, for example, through
integration in the EMERGENCY STOP circuit.
The following table describes the states of the enables and outputs in the respective
SIMOTION C operating states with an open or closed READY contact.
Additional references
You can find information about TO outputCam and Measuring Input TO in the SIMOTION
Output Cams and Measuring Inputs Function Manual.
SIMOTION C
76 Operating Instructions, 02/2012
Configuring and installing 4
4.1 General requirements
Overview
In this chapter we will explain how to design the mechanical configuration, prepare the
SIMOTION components for installation and install them.
During the installation of SIMOTION C modules, you must pay attention to the electrical
configuration. Therefore, also refer to the chapter Wiring (Page 91).
Open equipment
These modules are open equipment. This means they may only be installed in housings,
cabinets or in electrical service rooms that can be entered or accessed exclusively by means
of a key or tool. Housings, cabinets or electrical service rooms may only be accessed by
trained or authorized personnel.
SIMOTION C
Operating Instructions, 02/2012 77
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
Design
You can install the rack either horizontally or vertically. The horizontal configuration should
be used if possible.
9HUWLFDODUUDQJHPHQW +RUL]RQWDOPRXQWLQJ
6,027,21&DQGWKHSRZHUVXSSO\DUH
DOZD\VDUUDQJHGWRWKHOHIWRUEHORZ
SIMOTION C
78 Operating Instructions, 02/2012
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
4.2.2 Clearances
Rules
If you comply with the minimum clearances, you will:
● Ensure heat is dissipated from the modules
● Provide space to fit and remove modules
● Provide space to lay wiring
● Increase the mounting height of the rack to 205 mm!
To guarantee the functionality, clearances of 40 mm must be maintained.
Note
If you use a shield connecting element, the dimensions stated are measured from the
lower edge of the shield connecting element.
Clearances
The following figure shows the clearances between the individual racks and the clearance to
adjacent equipment, cable ducts, cabinet walls, etc.
PP
HJFDEOH PP
FKDQQHO
PP
D
PP D
PP PP
PP
SIMOTION C
Operating Instructions, 02/2012 79
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
SIMOTION C
80 Operating Instructions, 02/2012
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
Rules
The following rules apply with respect to the layout of the modules on a rack:
● Up to eight modules can be inserted to the right of the SIMOTION C.
● The number of plug-in modules is also limited by their power consumption from the
backplane bus (see Technical data table for the individual modules in the S7-300
Automation Systems, M7-300 Module Data Manual).
The total power consumption from the backplane bus of all modules that are mounted on
a rack must not exceed 1.2 A.
This figure shows the order of the modules in an installation with eight I/O modules.
36 6,027,21& ,2PRGXOHV
Installation of FM STEPDRIVE
The FM STEPDRIVE modules can be installed, in addition to the eight SMs. They have no
connection to the backplane bus and must therefore only be taken into consideration with
regard to the module width. In order to prevent the backplane bus from being interrupted, the
FM STEPDRIVE modules must always be configured as the last modules on the module
rack.
SIMOTION C
Operating Instructions, 02/2012 81
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
Overview
With the SIMOTION C, a 2-tier layout is possible.
Interface modules
Interface modules are required for the 2-tier layout which route the backplane bus from one
rack to the other. The SIMOTION C is always located on rack 0.
Rules
The following rules apply with respect to the layout of the modules on two racks:
● The interface module always occupies Slot 3 and is always left of the first signal module.
● No more than eight modules may be inserted per rack. These modules are always to the
right of the interface modules.
● The number of inserted modules is limited by the permissible power consumption from
the backplane bus. Total power consumption must not exceed 1.2 A (see Technical data
table for each module in the manual S7-300 Automation System, M7-300 Module Data).
SIMOTION C
82 Operating Instructions, 02/2012
Configuring and installing
4.2 Configuring an installation using SIMOTION C modules
2-tier layout
The figure below shows the 2-tier layout with SIMOTION C.
5DFN
&RQQHFWLQJFDEOH
,05 ,2PRGXOHV
5DFN
SIMOTION C
Operating Instructions, 02/2012 83
Configuring and installing
4.3 Installing
4.3 Installing
*URRYHIRUGULOOLQJDGGLWLRQDO +ROHIRUIL[LQJVFUHZ
KROHVIRUIL[LQJVFUHZV
'ULOOHGKROHIRUH[WUDIL[LQJVFUHZ
+ROHIRUFRQQHFWLQJDSURWHFWLYH
FRQGXFWRU +ROHIRUIL[LQJVFUHZ
SIMOTION C
84 Operating Instructions, 02/2012
Configuring and installing
4.3 Installing
PP
PP
PP
PP
FD FD
PP PP
D E
PP
Mounting screws
Choose one of the following types of screw to mount the mounting rail:
SIMOTION C
Operating Instructions, 02/2012 85
Configuring and installing
4.3 Installing
Note
Always make sure that there is a low-resistance connection to the protective conductor
(see figure below). If the rack is mounted on a movable frame, for example, make sure
that the line to the protective conductor is flexible.
PE connection
The figure below shows the proper way of connecting the protective conductor to the
mounting rail.
SIMOTION C
86 Operating Instructions, 02/2012
Configuring and installing
4.3 Installing
Accessories
Any accessories you need for installation are in the pack with the modules. Chapter Spare
parts and accessories (Page 184) contains a list of accessories and spare parts together
with the corresponding order numbers.
Installation sequence
The individual steps for the installation of the modules are described below:
1. Except for the SIMOTION C, each signal module is supplied with a bus connector. When
plugging in the bus connectors, always start with the SIMOTION C.
Take the bus connector from the next module and plug it into the bus connector of the
SIMOTION C. (The bus connector is located on the rear side, see Figure "Position of
interfaces and front panel elements").
You must not plug a bus connector into the "last" module in the row.
2. Fit the modules by hooking them into position, push them against the left-hand module
and lower them down into position.
3. Screw down the modules, applying a torque of 0.8 to 1.1 Nm.
SIMOTION C
Operating Instructions, 02/2012 87
Configuring and installing
4.3 Installing
581
67238
6723
SIMOTION C
88 Operating Instructions, 02/2012
Configuring and installing
4.3 Installing
SIMOTION C
Operating Instructions, 02/2012 89
Configuring and installing
4.3 Installing
SIMOTION C
90 Operating Instructions, 02/2012
Connecting 5
5.1 Wiring
Basic rules
Because of the wide range of uses of a SIMOTION C, only the basic rules for electrical
installation can be included in this section. At a minimum, you must comply with these basic
rules to ensure problem-free operation.
Safety regulations
In order to ensure safe operation of your equipment, implement the following measures,
adapting them to suit your conditions:
● An EMERGENCY OFF concept in accordance with the generally accepted rules of
current engineering practice (e.g. European standards EN 60204, EN 418, and similar).
● Additional measures for end position limiting of axes (e.g. hardware limit switches).
● Equipment and measures for protection of motors and power electronics in accordance
with the installation guidelines of the used drive units.
In addition, in order to identify hazards, we recommend that a risk analysis be conducted on
the entire system in accordance with the basic safety requirements set out in Appendix 1 of
EU Machinery Directive 89/392/EEC.
Additional references
Please also note the information in the following sections of this manual:
● Guidelines on Handling Electrostatic Sensitive Devices (ESD guidelines)
● For additional information on installing a system containing S7-300 process I/O, refer to
the "Wiring" section of the S7-300 Automation System, Hardware and Installation, CPU
Data Manual.
SIMOTION C
Operating Instructions, 02/2012 91
Connecting
5.1 Wiring
Supply voltage
The following table identifies the considerations required for the supply voltage.
Scope Requirement
Stationary systems without all-pole A power disconnect switch or a fuse must be provided in the
power disconnect switches electrical installation for the building.
Load power supply, power supply The set rated voltage range corresponds to the local supply
modules voltage.
All electric circuits The fluctuation/deviation of the supply voltage from the rated
value must be within the permissible tolerance (see Technical
data for S7-300 modules).
24 VDC supply
The following table identifies the considerations required for the 24 V supply.
Table 5- 3 24 V supply
Scope Requirement
buildings external lightning protection. Take lightning protection
measures
24 V DC supply lines, signal lines internal lightning protection (e.g. lightning conductors).
24 V supply Safe (electrical) isolation of extra-low voltage
SIMOTION C
92 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Scope Requirement
All plants or systems in which the The equipment or system is connected to a protective
SIMOTION C or S7-300 is installed conductor to discharge electromagnetic interference.
Supply, signal, and bus lines The wiring arrangement and installation complies with
EMC regulations.
Signal and bus lines A wire or conductor strand break must not cause any
undefined installation or system states.
DANGER
All interfaces of the SIMOTION C must operate only on circuits with safety extra-low
voltage (SELV).
Note
The I/O bus will not work if I/O-bus I/O are pulled out during operation. The SIMOTION must
be switched off and back on again when these are reinserted.
SIMOTION C
Operating Instructions, 02/2012 93
Connecting
5.1 Wiring
3*3&
(WKHUQHWFRQQHFWLQJ
03 FDEOH
&&
& 6,(0(16 ; ; ;
581
6723
05(6
;
352),%86'3
FRQQHFWLQJFDEOH
; ; ;
; ;
([W9SRZHUVXSSO\
)URQW
$[LV FRQQHFWRU
6HWSRLQWFDEOH
0HDVXULQJ
V\VWHPFDEOH 'LJLWDO
HJ6,02'5,9(
XQLYHUVDO RXWSXWV
HJLQFUHPHQWDOHQFRGHU
ZLWK56
5($'<
HJOLQHDUVFDOHZLWK &RQWDFW
(;(
HJ52'EXLOWLQ
'LJLWDO
HQFRGHULQ)7PRWRU
LQSXWVHJ
HJDEVROXWHHQFRGHU SUREH
66,
6,(0(16
6,02'5,9(
HJ6,02'5,9(
,5 )'' )'' )'' )'' DQDORJZLWKUHVROYHU
Figure 5-1 Overview of the cable connecting the C230-2/C240 to the servo drive (analog coupling) -
example
SIMOTION C
94 Operating Instructions, 02/2012
Connecting
5.1 Wiring
3*3&
(WKHUQHWFRQQHFWLQJ
FDEOH
03
6,027,21&
& 6,(0(16 ; ; ;
581
6723
05(6
;
; ; ;
; ;
352),%86'3 ([W9
FRQQHFWLQJFDEOH SRZHUVXSSO\
)URQW
FRQQHFWRU
'LJLWDORXWSXWV
5($'<FRQWDFW
HJ6,02'5,9(XQLYHUVDO
'LJLWDOLQSXWV
HJSUREH
6,(0(16 3UREH
6,02'5,9(
Figure 5-2 Overview of the cable connecting the SIMOTION C to the servo drive (digital connection)
- example
SIMOTION C
Operating Instructions, 02/2012 95
Connecting
5.1 Wiring
3*3&
(WKHUQHWFRQQHFWLQJ
FDEOH
03
&31
; ,( $8$%$$
,( 3
&31 ;
31
3
3
6,(0(16
581
6723
05(6
;
; ; 6<1&)$8/7
352),%86'3 ([W9
FRQQHFWLQJFDEOH 3RZHUVXSSO\
)URQW
FRQQHFWRU
352),1(7,2
'5,9(&/L4
'LJLWDORXWSXWV
6,1$0,&6
6,1$0,&6
6,1$0,&6
&%(
5($'<FRQWDFW
6,1$0,&6
6
Figure 5-3 Overview of the cable connecting the C240 PN to the servo drive (digital connection) -
example
SIMOTION C
96 Operating Instructions, 02/2012
Connecting
5.1 Wiring
3*3&
&RQQHFWLQJFDEOH
03 (WKHUQHW
&RQQHFWLQJFDEOH
352),%86'3
& ; ; ; 6,(0(16 6,(0(16
6,(0(16
581
6723
05(6
;
; ; ;
; ;
&& )067(3'5,9(
'LJLWDORXWSXWV
([W9 'LJLWDOLQSXWV
SRZHUVXSSO\ HJSUREH
5($'<FRQWDFW
6HWSRLQWFDEOH
Figure 5-4 Overview of the cable connecting the C230-2/C240 to the stepper drive - example
SIMOTION C
Operating Instructions, 02/2012 97
Connecting
5.1 Wiring
6,027,21&
; 'LJLWDOLQSXWVRXWSXWV
);$'ჰჰ 6,02'5,9(DQDORJXQLYHUVDO
VHWSRLQWV
ืPRSHQZLUHHQGV
; RU
&& );$(ჰჰ 3RZHUFRQWUROIRU
VWHSPRWRUV
ืP WR1P)067(3'5,9(
)RUPL[HGRSHUDWLRQZLWK
DQDORJD[HVYP
);ჰ&'ჰჰჰ
,QFUHPHQWDOHQFRGHU8%9'&
ืPDW9'& );ZLWK5677/
);ჰ&'ჰჰჰ
,QFUHPHQWDOHQFRGHU8%9'&
ืPDW9'& );ZLWK5677/
);ჰ&-ჰჰ 6,02'5,9(XQLYHUVDOZLWK
$QJXODULQFUHPHQWDOHQFRGHULQWHUIDFH
ืP
;WR;
&& );ჰ&-ჰჰ 6,02'5,9(DQDORJ
&RQWUROOHUSOXJLQ).PRWRUV
ืP ZLWKUHVROYHU
);ჰ&&ჰჰჰ $EVROXWHHQFRGHU);
ZLWK66,
ืPDW.ELWVV
ืPDW.ELWVV
);ჰ&'ჰჰ
/LQHDUVFDOHZLWK(;(
ืP
,QGXVWULDO(WKHUQHWEXVFDEOH
; (WKHUQHWEXVQRGHV
352),%86FDEOH
; 352),%86'3QRGH
DQG
; (6%';$
3URJUDPPLQJGHYLFH3*
ืP
,QGXVWULDO(WKHUQHWEXVFDEOH
352),1(7QRGHV
;3
;3
;3 ,QGXVWULDO(WKHUQHWEXVFDEOH
&31 3URJUDPPLQJGHYLFH3*
SIMOTION C
98 Operating Instructions, 02/2012
Connecting
5.1 Wiring
The setpoint and measuring system cables (see figure "Overview of connections" ) are
available in various lengths.
See PM 21 Catalog / NC 60 Catalog / ST 70 Catalog / CA 01 Catalog
For information about the PROFIBUS cable or Ethernet bus cable, see chapter Networking
(Page 122).
For additional information about PROFIBUS DP, PROFINET IO and Ethernet, see IK PI
Catalog
Front connector
For the wiring of the digital inputs/digital outputs, you need a 40-pole front connector (screw
type or spring tension type). This must be ordered separately.
Order no.: Screw type 6ES7 392-1AM00-0AA0
Spring type 6ES7 392-1BM01-0AA0
See ST 70 catalog/NC 60 catalog
SIMOTION C
Operating Instructions, 02/2012 99
Connecting
5.1 Wiring
DANGER
The 24 VDC should be configured as functional extra-low voltage with safe isolation.
Note
The connecting cable between the voltage source and the load current supply connector L+
and the associated reference potential M should not exceed a maximum length of 10 m.
Pin assignment
The table below shows the pin connections on the screw-type terminal block.
M Ground
L+ DC 24 V
M Ground
If you want to ground the reference potential, you must not remove the jumper between
terminals M and functional ground on the SIMOTION C.
SIMOTION C
100 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Line buffering
The PS 307 load current supplies from the S7-300 system guarantee mains buffering for 20
ms.
/
/ /RZYROWDJHGLVWULEXWLRQ
/ HJ716V\VWHP[9
1
3(
0RXQWLQJUDLO 6,027,21&
0
36
0
/ /
1 0
*URXQGLQJEDU
LQFDELQHW
Connecting comb
You can also use a connecting comb to connect the PS 307 power supply module to the
SIMOTION C. You will find the order numbers of the connecting comb required in chapter
Spare parts and accessories (Page 184).
Other 24 V connections
On the PS 307 power supply, there are 24 V connections available via the connecting comb
for connecting the supply of the I/O modules.
SIMOTION C
Operating Instructions, 02/2012 101
Connecting
5.1 Wiring
WARNING
You could come into contact with live wires if the power supply module and any additional
load power supplies are switched on.
Ensure that the system is de-energized when you wire the system!
36 6,027,21&
6WUDLQUHOLHI
&RQQHFWLQJFRPE
99
WR1P
Figure 5-7 Connect power supply module and SIMOTION C with connecting comb
SIMOTION C
102 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Note
Your module will not work in the case of reverse polarity. However, a built-in reverse polarity
protection will protect the electronics against damage.
Fuse
If a fault is present on the module, a built-in fuse protects the electronics against
consequential damage (e.g. fire). In this case, the module must be replaced.
Note
Only use shielded, twisted pair cables; the shield must be connected to the metallic or
metalized connector housing on the controller side. We recommend that you do not ground
the shield on the drive side. This is to separate low-frequency interferences from the analog
setpoint signal.
The pre-assembled cable available as an accessory provides the best possible immunity to
interference.
SIMOTION C
Operating Instructions, 02/2012 103
Connecting
5.1 Wiring
Connection of drives (e.g. SIMODRIVE 611 universal with analog setpoint interface) to the onboard
drive interface (C230-2, C240)
The figure below shows the connection of the C230-2, C240 to SIMODRIVE 611 universal
drive units.
& 6,(0(16
; ; ;
581
6723
05(6
;
; ; ;
&&
&RQQHFWLQJFDEOH
'ULYHXQLW
HJ6,02'5,9(XQLYHUVDO
6,(0(16
6,02'5,9(
Procedure:
1. Wire the free cable end of the connecting cable to the terminals on the drive unit. (The
terminal markings on the cable ends indicate the corresponding terminals for
SIMODRIVE devices.)
2. Open the front cover of the C230-2/C240 and connect the Sub-D socket (50-pin) to the
X2 connector.
3. Lock the connector using the finger screws. Close the front cover.
SIMOTION C
104 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Connecting cable
The connecting cable is a pre-assembled cable for four axes with an analog interface and
terminal designation for SIMODRIVE drive units.
The connecting cable is available in a choice of lengths.
See Catalog PM 21, NC 60, or ST 70
Wiring diagram
6,027,21& 6,02'5,9(XQLYHUVDO
9
&75(1
,QSXWHQDEOH
&75(1
6(73
5()327
&75(1
&75(1 $[LV
6(73
5()327
&75(1
&75(1 $[LV
6(73
5()327
&75(1
&75(1 $[LV
6(73
5()327
6KLHOG
)HUUXOHVZLWKODEHO
6KLHOGRQKRXVLQJ
:LUHVWZLVWHGDQGVKLHOGHGLQSDLUV
Figure 5-9 Terminal diagram for C230-2/C240 and SIMODRIVE 611 universal with analog setpoint
interface
SIMOTION C
Operating Instructions, 02/2012 105
Connecting
5.1 Wiring
Setpoint assignment
The assignment of the setpoints for axes 1 to 4 is fixed.
Setpoint output signals (X2) for drives with analog interface:
● SW1, BS1, RF1.1, RF1.2 for axis 1
● SW2, BS2, RF2.1, RF2.2 for axis 2
● SW3, BS3, RF3.1, RF3.2 for axis 3
● SW4, BS4, RF4.1, RF4.2 for axis 4
Note
When using the drive interface for standard outputs (C240 only), proceed as described in
chapter Onboard drive interface (C230-2, C240) (Page 45). Wire the free ends of the
connecting cable according to your application.
SIMOTION C
106 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Connection of stepper drives (e.g. FM STEPDRIVE) to the onboard drive interface (C230-2, C240)
The figure below shows the connection of the C230-2, C240 to FM STEPDRIVE drive units.
581
6723
05(6
;
; ; ;
&& )067(3'5,9(
&RQQHFWLQJFDEOH
Procedure:
1. Insert the Sub-D socket (15-pin) in the FM STEPDRIVE module.
2. Open the front cover of the C230-2/C240 and connect the Sub-D socket (50-pin) to the
X2 connector.
3. Lock the connector using the finger screws. Close the front cover.
SIMOTION C
Operating Instructions, 02/2012 107
Connecting
5.1 Wiring
Connecting cable
The connecting cable is a preassembled cable for four FM STEPDRIVE stepper motor drive
units.
See Catalog PM 21, NC 60.1, or ST 70
Wiring diagram
&& )067(3'5,9([
$[LV
$[LV
$[LV
$[LV
[[PPtZLUHIRUXSWRGULYHV
6KLHOG
6KLHOGRQKRXVLQJ
:LUHVWZLVWHGDQGVKLHOGHGLQSDLUV
SIMOTION C
108 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Setpoint assignment
The assignment of the setpoints for axes 1 to 4 is fixed.
Setpoint output signals (X2) for stepper drive:
● PULSE1, PULSE1_N, DIR1, DIR1_N, ENABLE1, ENABLE1_N for axis 1
● PULSE2, PULSE2_N, DIR2, DIR2_N, ENABLE2, ENABLE2_N for axis 2
● PULSE3, PULSE3_N, DIR3, DIR3_N, ENABLE3, ENABLE3_N for axis 3
● PULSE4, PULSE4_N, DIR4, DIR4_N, ENABLE4, ENABLE4_N for axis 4
& 6,(0(16 ; ; ;
581
6723
05(6
;
&RQQHFWLQJFDEOH
; ; ;
; ;
IRUH[DPSOH&
6,02'5,9(XQLYHUVDOGULYHXQLW
6,(0(16
6,02'5,9(
SIMOTION C
Operating Instructions, 02/2012 109
Connecting
5.1 Wiring
Procedure:
1. Insert the Sub-D connector (9-pin) into the drive unit.
2. Open the front door of the SIMOTION C and insert the Sub-D connector (9-pin) into the
X8/X9 socket.
3. Lock the connector using the finger screws. Close the front cover.
Connecting cable
Details about the bus cable, bus connector and installation can be found in chapter
Networking (Page 122).
Note
The maximum cable length is 100 m.
The terminating resistor must be switched in (switch position "On") at the beginning and end
of the bus segment. See figure "Bus connector (6ES7 ...): Terminating resistor connected
and disconnected" in chapter Network components for a PROFIBUS subnet (Page 125)
SIMOTION C
110 Operating Instructions, 02/2012
Connecting
5.1 Wiring
3*3&
(WKHUQHWFRQQHFWLQJ
FDEOH
03
&31
; ,( $8$%$$
,( 3
&31 ;
31
3
3
6,(0(16
581
6723
05(6
;
; ; 6<1&)$8/7
352),%86'3 ([W9
FRQQHFWLQJFDEOH 3RZHUVXSSO\
)URQW
FRQQHFWRU
352),1(7,2
'5,9(&/L4
'LJLWDORXWSXWV
6,1$0,&6
6,1$0,&6
6,1$0,&6
&%(
5($'<FRQWDFW
6,1$0,&6
6
SIMOTION C
Operating Instructions, 02/2012 111
Connecting
5.1 Wiring
Procedure:
1. Insert the PROFINET connector into the drive unit.
2. Open the front door of the C240 PN and insert the PROFINET connector into the X11 P1,
X11 P2 or X11 P3 socket.
Note
The strain relief provided for the PROFINET cable must be used in particular for vibrating
machines. The cables should be secured close to the controller to achieve high vibration
strength.
Connecting cable
Details about the bus cable, bus connector and installation can be found in chapter
Networking (Page 122).
Note
The maximum cable length is 100 m.
SIMOTION C
112 Operating Instructions, 02/2012
Connecting
5.1 Wiring
Note
Ensure that the polarity assignment of the signals is correct. Refer to the technical
documentation for your drive unit (e. g. FM STEPDRIVE, Function Description manual) and
chapter Onboard drive interface (C230-2, C240) (Page 45) of these operating instructions to
ensure that the interconnection is correct.
Mixed operation of drives on the onboard drive interface and use as standard output (C240 only)
Follow the procedure outlined for connecting analog drives.
Mixed operation of drives on the PROFIBUS DP and drives on the PROFINET IO (C240 PN)
Drives can be used in mixed operation.
Proceed as described for the connection of drives on the PROFIBUS DP or on the
PROFINET IO.
See also
Overview (Page 63)
SIMOTION C
Operating Instructions, 02/2012 113
Connecting
5.1 Wiring
Note
Always use shielded data cables. The shielding must be connected with the metallic or
metallized connector housing.
The pre-assembled cable available as an accessory provides the best possible immunity to
interference and adequately dimensioned cross-sections for the power supply to the
encoders.
& 6,(0(16
; ; ;
581
6723
05(6
;
; ; ;
&&
$[LV
&RQQHFWLQJFDEOH
7KHIROORZLQJHQFRGHUVFDQEHFRQQHFWHG
,QFUHPHQWDOHQFRGHUZLWK56
52'EXLOWLQHQFRGHULQ)7
66,DEVROXWHHQFRGHU
/LQHDUVFDOHZLWK(;(
6,02'5,9(DQDORJFRQWUROXQLW).PRWRUVZLWKUHVROYHU
6,02'5,9(XQLYHUVDOZLWKDQJXODULQFUHPHQFRGHULQWHUIDFH
SIMOTION C
114 Operating Instructions, 02/2012
Connecting
5.1 Wiring
SIMOTION C
Operating Instructions, 02/2012 115
Connecting
5.1 Wiring
Note
The assignment between the drive and encoder channel is permanent for position axes with
an encoderless stepper motor as a result of the actual value simulation required in the
hardware.
SIMOTION C
116 Operating Instructions, 02/2012
Connecting
5.1 Wiring
&&
/DEHOLQJRILQQHUGRRU
& ; ; ;
6,(0(16
/
581
6723
05(6
;
; ; ;
6KLHOGFRQQHFWLQJHOHPHQW
5($'<FRQWDFW
'LJLWDOLQSXWVRXWSXWV
0 0
3UREH
Connecting cables
Flexible cable, cross-section 0.25 to 1.5 mm2
Ferrules are not required.
You can use ferrules without an insulating collar in accordance with DIN 46228, Form A long
version.
You can connect two cables of 0.25 to 0.75 mm2 each in one ferrule.
Note
To achieve optimum interference suppression, a shielded cable must be used for connection
of measuring inputs or external zero mark.
Required Tools
3.5-mm screwdriver or power screwdriver
SIMOTION C
Operating Instructions, 02/2012 117
Connecting
5.1 Wiring
Shielded cables
If a shielded cable is used, the following additional actions are required:
1. Attach the cable shield to a grounded shielding bus immediately after the cable entry
point in the cabinet (strip the insulation off the cable for this purpose).
You can use the shield connecting element. This is mounted on the rail and can
accommodate up to eight shielding terminals.
2. Continue routing the shielded cable as far as the module but do not make a connection to
the shield there.
SIMOTION C
118 Operating Instructions, 02/2012
Connecting
5.1 Wiring
;
6KLHOGURXWHGRQVKLHOGFRQQHFWLQJ
HOHPHQW
6,027,21&
/
0H[WHUQ
Note
For the assignment of the front connector and the description of the I/O interface, refer to
chapter I/O interface (Page 68).
SIMOTION C
Operating Instructions, 02/2012 119
Connecting
5.1 Wiring
Application
With the shield connecting element, you can easily connect all the shielded wires of the
SIMOTION C or S7 modules to ground by directly connecting the shield connecting element
with the mounting rail.
The shield connecting element is 80 mm wide and provides space for two rows, each with
four shielding terminals.
SIMOTION C
120 Operating Instructions, 02/2012
Connecting
5.1 Wiring
6KLHOGWHUPLQDO )L[LQJEUDFNHW
(GJHD
SIMOTION C
Operating Instructions, 02/2012 121
Connecting
5.2 Networking
5.2 Networking
5.2.1 Configuring
The SIMOTION SCOUT online help shows you how to design and configure a PROFIBUS or
Ethernet subnet for your application.
device = node
Convention: All devices connected in a subnet will be referred to hereafter as nodes.
PROFIBUS addresses
In order for all nodes to communicate with each other, you must assign a 'PROFIBUS-
address" to each node before connecting them:
You set the PROFIBUS addresses for each node individually using the programming device
or PC (also by a switch on the slave for some PROFIBUS DP slaves).
The factory settings on the SIMOTION C are address 2 and baud rate 1.5 Mbit/s for both
PROFIBUS DP interfaces X8 and X9.
Tip: Mark the set address on the housing of all nodes in a subnet. You can then always see
which address is assigned to which node in your plant.
The "highest PROFIBUS addresses" are preset for each PROFIBUS subnet. You can
change these default settings.
SIMOTION C
122 Operating Instructions, 02/2012
Connecting
5.2 Networking
Segment
A segment is a bus cable between two terminating resistors. A segment with SIMOTION C
as the master can contain up to 64 slaves. In addition, a segment is limited by the permitted
cable length according to the baud rate (see chapter Onboard measuring system interface
(C230-2, C240) (Page 52)).
Components
Connect the individual nodes using bus connectors and the PROFIBUS cable, also refer to
chapter Network components for a PROFIBUS subnet (Page 125). Remember to provide a
bus connector with a programming device socket at the ends of the subnet. This will give you
the option of expanding the subnet if required (for example, for a programming device or
SIMATIC HMI device).
Use RS 485 repeaters for the connection between segments and for extending the cable.
Terminating resistor
A cable must be terminated with its own surge impedance to prevent line disturbances
caused by reflections. To this end, activate the terminating resistor at the first and last node
of a subnet or segment (see figure "Bus connector (6ES7...): Terminating resistor connected
and disconnected" in chapter Network components for a PROFIBUS subnet (Page 125)
Make sure that the nodes to which the terminating resistor is connected are always supplied
with voltage during power-up and operation.
SIMOTION C
Operating Instructions, 02/2012 123
Connecting
5.2 Networking
Example
The following figure shows an example configuration of a subnet with SIMOTION C.
6 ᆯ ᆯ
1HWZRUN
0D[P
PD[FDEOHOHQJWKP 0%DXG
IURPWHUPLQDWLQJUHVLVWRUWRWHUPLQDWLQJUHVLVWRU
(70
'ULYH
36 6,027,21& 6,02'5,9( 36 ,0 6060 60
XQLYHUVDO
; ;
ᆯ ᆱ
ᆱ ᆱ
1HWZRUN
ᆯ7HUPLQDWLQJUHVLVWRUHQDEOHG
ᆰ'3PDVWHU
ᆱ'3VODYH
WR[352),%86'3DGGUHVVHVRIQRGHV
6XSSO\
+LJKHVW352),%86DGGUHVV 3RVVLEOH352),%86QRGHV
V\VWHP
WR
WR
Segment in subnet
The baud rate determines the cable length of a subnet segment (see the following table).
Table 5- 8 Permitted cable lengths of a subnet segment for specific baud rates
SIMOTION C
124 Operating Instructions, 02/2012
Connecting
5.2 Networking
PROFIBUS cable
We can offer you e.g. the following PROFIBUS cables:
Features Values
Characteristic impedance Approx. 135 to 160 Ω (f = 3 to 20 MHz)
Loop resistance ≦ 115 Ω/km
Effective capacitance 30 nF/km
Damping 0.9 dB/100 m (f = 200 kHz)
Permissible conductor cross-section 0.3 mm2 to 0.5 mm2
Permitted cable diameter 8 mm ± 0.5 mm
SIMOTION C
Operating Instructions, 02/2012 125
Connecting
5.2 Networking
Features Limitations/constraints
Bending radius for a single bend ≥ 80 mm (10 x dA)
Bend radius for multiple bends ≥ 160 mm (20 x dA)
Permissible temperature range for installation - 40° C to + 60° C
Shelf and static operating temperature range - 40° C to + 60° C
Bus connector
The bus connector is used to connect the PROFIBUS cable to the PROFIBUS DP interfaces
(X8, X9), thus establishing a connection to additional nodes.
The following bus connectors are available:
● Up to 12 Mbits/s, cable outlet 90°
– Without PG socket (6ES7 972-0BA12-0XA0 or 6ES7 972-0BA50-0XA0)
– With PG socket (6ES7 972-0BB12-0XA0 or 6ES7 972-0BB50-0XA0)
● Up to 12 Mbits/s, canted cable turn
– Without PG socket (6ES7 972-0BA41-0XA0)
– With PG socket (6ES7 972-0BB41-0XA0)
7HUPLQDWLQJUHVLVWRU RQ 7HUPLQDWLQJUHVLVWRU RQ
VZLWFKHGLQ QRWVZLWFKHGLQ
RII RII
Figure 5-20 Bus connector (6ES7 ...): terminating resistor switched on and off
SIMOTION C
126 Operating Instructions, 02/2012
Connecting
5.2 Networking
WARNING
Overview
You can connect an Industrial Ethernet to the 8-pin RJ45 X7 socket, see Figure "Overview of
the cable connecting the SIMOTION C to the servo drive (digital connection) - example" in
chapter Overview of wiring diagram (Page 94).
Industrial Ethernet is a communication network with a transmission rate of 10/100 Mbits/s.
Communication between SIMOTION C, the PG/PC (e.g. STEP 7, SIMOTION SCOUT,
SIMATIC NET OPC), and the I/O devices provided for this purpose is supported by the
Ethernet.
A shielded twisted pair cable is used for the networking in this case. For additional
information, refer to the SIMATIC NET, Industrial Twisted Pair and Fiber Optic Networks
Manual. This document is supplied in electronic format with SIMOTION SCOUT.
The following connecting cables are recommended:
● SIMATIC NET, Ind. Ethernet TP XP CORD RJ45/RJ45, TP cable assembled with 2 RJ45
plugs, send and receive cables crossed
Order no.: 6XV1870-3R☐☐☐ (☐☐☐ - length code)
● SIMATIC NET, Ind. Ethernet TP CORD RJ45/RJ45, TP cable assembled with 2 RJ45
plugs
Order no.: 6XV1870-3Q☐☐☐ (☐☐☐ - length code)
You can obtain additional information about the different cable systems for Ethernet from
your SIEMENS contact.
Note
A crossover cable should be used for the direct connection of the controller to a PG/PC.
SIMOTION C
Operating Instructions, 02/2012 127
Connecting
5.2 Networking
Note
You can also write the user project and/or configuration with SIMOTION SCOUT and the
menu command "Load to file system" directly from the PC to the memory card (micro
memory card). To do this, select the device in the project navigator and execute the
"Load to file system" command in the context menu.
SIMOTION C
128 Operating Instructions, 02/2012
Connecting
5.2 Networking
Overview
You can connect a PROFINET node to the 8-pin RJ45 X11 P1, X11 P2 and X11 P3 sockets,
see Figure "Overview of the cable connecting the C240 PN to the servo drive (digital
connection) - example" in chapter Overview of wiring diagram (Page 94).
PROFINET is a communication network with a transmission rate of 100 Mbit/s.
You can use a PG/PC to communicate with STEP 7, SIMOTION SCOUT, and SIMATIC NET
OPC.
A shielded twisted pair cable is used for the networking in this case. For additional
information, refer to the SIMATIC NET, Industrial Twisted Pair and Fiber Optic Networks
Manual. This document is supplied in electronic format with SIMOTION SCOUT.
All ports of the PROFINET interface support auto-MDI(X) in contrast to the Ethernet
interface. A crossover cable is therefore not required for a direct connection to the PG/PC.
The following connecting cables are recommended:
● SIMATIC NET, Ind. Ethernet FC TP standard cable GP
Order no.: 6XV1840-2AH10 (sold by the meter)
● SIMATIC NET, Ind. Ethernet FC TP trailing cable GP
Order no.: 6XV1870-2D (sold by the meter)
● SIMATIC NET, Ind. Ethernet TP XP CORD RJ45/RJ45, TP cable assembled with two
RJ45 plugs, send and receive cables crossed
Order no.: 6XV1870-3R☐☐☐ (☐☐☐ - length code)
● SIMATIC NET, Ind. Ethernet TP CORD RJ45/RJ45, TP cable assembled with two RJ45
plugs
Order no.: 6XV1870-3Q☐☐☐ (☐☐☐ - length code)
The following bus connectors can be used with the C240 PN:
● SIMATIC NET, Ind. Ethernet FC RJ45 plug 145
Order no.: 6GK1901-1BB30-0AA0 (1 item)
Order no.: 6GK1901-1BB30-0AB0 (10 items)
You can obtain additional information about the different cable systems for PROFINET and
Ethernet from your SIEMENS contact.
SIMOTION C
Operating Instructions, 02/2012 129
Connecting
5.2 Networking
Note
You can also write the user project and/or configuration with SIMOTION SCOUT and the
menu command "Load to file system" directly from the PC to the memory card (micro
memory card). To do this, select the device in the project navigator and execute the
"Load to file system" command in the context menu.
SIMOTION C
130 Operating Instructions, 02/2012
Connecting
5.2 Networking
SIMOTION C
Operating Instructions, 02/2012 131
Connecting
5.2 Networking
SIMOTION C
132 Operating Instructions, 02/2012
Addressing 6
6.1 Slot-oriented address allocation for modules (default addresses for
centralized I/O)
Introduction
In the case of addressing based on the slot (default addressing), a module start address is
assigned to every slot number. Depending on the type of module, these are different
addresses for digital, analog, FM and CP modules (see table below). In this section we will
show you which module start address is assigned to which slot number. You need this
information to determine the module start addresses of the modules used.
Maximum configuration
The following figure shows a configuration of a rack and the possible slots. A 2-tier layout
with IM 365 is possible with SIMOTION C.
5DFN
6ORWQXPEHU
5DFN
6ORWQXPEHU
SIMOTION C
Operating Instructions, 02/2012 133
Addressing
6.1 Slot-oriented address allocation for modules (default addresses for centralized I/O)
Note
Do not insert any non-configured modules centrally. Modules that are installed but not
configured are repeatedly addressed via the I/O bus. This requires additional computing
time.
SIMOTION C
134 Operating Instructions, 02/2012
Addressing
6.2 User-assignable addressing on the SIMOTION C (centralized and distributed I/O)
User-assignable addressing
User-assignable addressing means you can assign an address of your choice to each
module or slot, for example, integrated inputs/outputs, drives. You make this assignment in
the hardware configuration (see SIMOTION SCOUT online help). Here you specify the
module start address on which all further module addresses will then be based.
advantages
Advantages of user-definable addressing:
● You can make the best possible use of the available address spaces because there are
no "address gaps" between the modules.
● When creating standard software, you can specify addresses which are independent of
the respective configuration of the SIMOTION modules.
SIMOTION C
Operating Instructions, 02/2012 135
Addressing
6.3 Addressing signal modules
Introduction
The following section describes signal module addressing in the default setting. You need
the information so that you can address the signal module channels in the user program.
HJ ,
%\WHDGGUHVV
0RGXOHVWDUWDGGUHVV
%\WHDGGUHVV
0RGXOHVWDUWDGGUHVV
%LWDGGUHVV
Figure 6-3 Addresses for the inputs and outputs of digital modules
SIMOTION C
136 Operating Instructions, 02/2012
Addressing
6.3 Addressing signal modules
C240
$GGUHVV
$GGUHVV
581
6723
05(6 $GGUHVV
$GGUHVV
$GGUHVV
$GGUHVV
6ORW
QXPEHU
Figure 6-4 Addresses for the inputs and outputs of the digital module in slot 4
SIMOTION C
Operating Instructions, 02/2012 137
Addressing
6.3 Addressing signal modules
& ,QSXWV
&KDQQHO$GGUHVV(
&KDQQHO$GGUHVV(
581
6723
05(6
2XWSXWV
&KDQQHO$GGUHVV$
&KDQQHO$GGUHVV$
6ORW
QXPEHU
Figure 6-5 Addresses for the inputs and outputs of the analog module in slot 4
SIMOTION C
138 Operating Instructions, 02/2012
Addressing
6.4 Addressing the onboard digital inputs and outputs of the SIMOTION C
6.4 Addressing the onboard digital inputs and outputs of the SIMOTION
C
The following figure shows the default start addresses of the onboard digital inputs/outputs.
$GGUHVV$ % $GGUHVV(
% $GGUHVV(
$GGUHVV$ % $GGUHVV(
% $GGUHVV(
$GGUHVV$ 0 $GGUHVV(
0 $GGUHVV(
$GGUHVV$ $GGUHVV(
$GGUHVV(
$GGUHVV(
$GGUHVV(
$GGUHVV(
$GGUHVV$ $GGUHVV(
$GGUHVV(
$GGUHVV$ $GGUHVV(
$GGUHVV(
$GGUHVV$ $GGUHVV(
$GGUHVV(
$GGUHVV$ $GGUHVV(
Note
These addresses can be modified by the user in the hardware configuration (see SIMOTION
SCOUT online help).
When used by a TO (e.g. measuring input/output cam), the address must be ≥ 64.
All start addresses/signal bits (64.4...64.7, 65.0...65.3, 65.6, 65.7, 67.4...67.7) not listed do
not have any defined values and consequently may not be used for evaluation.
As of SIMOTION V4.2, the onboard digital inputs/outputs of the C240 and C240 PN cannot
only be interconnected with variables via their direct addresses, by also by means of
symbolic assignment.
SIMOTION C
Operating Instructions, 02/2012 139
Addressing
6.5 Addressing the onboard drive and measuring system interface of the C230-2, C240
6.5 Addressing the onboard drive and measuring system interface of the
C230-2, C240
Use as a standard output is only possible by means of an I/O variable. The I/O variables
must be created on the addresses of the corresponding axis channel specified via the
hardware configuration (relating to the default start address).
Symbolic assignment is not available for this application.
The following figure shows the default start addresses of the onboard drive interface of the
C230-2/C240.
& &
$GGUHVV$ $QDORJ
$[LVFKDQQHO
$QDORJ
2QERDUGGULYHLQWHUIDFH VWHSSHUGULYH VWHSSHUGULYHRU
&& DQDORJRXWSXW
$GGUHVV$ 'LJLWDORXWSXW
VWHSSHUGULYH VWHSSHUGULYHRU
DQDORJRXWSXW
$GGUHVV$ 'LJLWDORXWSXW
$[LVFKDQQHO
$GGUHVV$ 'LJLWDORXWSXW
$GGUHVV$ $QDORJ $QDORJ
$[LVFKDQQHO
VWHSSHUGULYH VWHSSHUGULYHRU
; DQDORJRXWSXW
$GGUHVV$ 'LJLWDORXWSXW
An available encoder input of an axis channel (e.g. for a speed-controlled axis) can be used
as an input for a 16-bit up/down counter (90-degree pulse train of a connected TTL encoder,
zero pulse not required). The counter value can be accessed by means of an I/O variable
(default start address of the axis channel). Symbolic assignment is not available for this
application.
SIMOTION C
140 Operating Instructions, 02/2012
Addressing
6.5 Addressing the onboard drive and measuring system interface of the C230-2, C240
The following figure shows the default start addresses of the onboard measuring system
interface of the C230-2/C240.
2QERDUGPHDVXULQJV\VWHP
LQWHUIDFH&& & &
$[LVFKDQQHO
; ;
$GGUHVV( (QFRGHULQSXW (QFRGHULQSXWRU
FRXQWHULQSXW
$[LVFKDQQHO
$GGUHVV( (QFRGHULQSXW (QFRGHULQSXWRU
FRXQWHULQSXW
$[LVFKDQQHO
$GGUHVV( (QFRGHULQSXW (QFRGHULQSXWRU
FRXQWHULQSXW
$[LVFKDQQHO
$GGUHVV( (QFRGHULQSXW (QFRGHULQSXWRU
FRXQWHULQSXW
; ;
SIMOTION C
Operating Instructions, 02/2012 141
Addressing
6.5 Addressing the onboard drive and measuring system interface of the C230-2, C240
SIMOTION C
142 Operating Instructions, 02/2012
Commissioning 7
7.1 Requirements for commissioning
Requirements
Table 7- 1 Requirements
System requirements
Note
The readme file for the software version you are using provides information about the
hardware and software requirements.
Please take note of the information on the current CD for "SIMOTION SCOUT"!
For online operation, a connection must be established between the PG/PC and the
SIMOTION C via PROFIBUS DP, Ethernet or PROFINET (C240 PN), see chapter Overview
of wiring diagram (Page 94).
The programming device must be equipped with a PROFIBUS or Ethernet card.
You need an MMC adapter to write to the micro memory card (SIMOTION Kernel update) on
the PG/PC, see chapter Writing, formatting and erasing the Micro Memory Card (Page 147).
SIMOTION C
Operating Instructions, 02/2012 143
Commissioning
7.1 Requirements for commissioning
SIMOTION C
144 Operating Instructions, 02/2012
Commissioning
7.2 Inserting and changing the Micro Memory Card
(MHFWRUIRU
PLFURPHPRU\FDUG
Figure 7-1 Inserting the micro memory card into the SIMOTION C
Note
With the SIMOTION C240 / C240 PN, the micro memory card must always be inserted
for operation.
For the purpose of data backup, the contents of the micro memory card can be copied to
the hard drive of a PG/PC with an MMC card reader.
SIMOTION C
Operating Instructions, 02/2012 145
Commissioning
7.3 Initial Power ON
Requirements
● You have completed installation and the wiring of your system with SIMOTION C.
● The micro memory card is inserted.
● The mode selector must be set to STOP!
Initial Power ON
Switch on the power supply module.
● The 24 VDC LED on the power supply module is illuminated.
● On the SIMOTION C:
– The 5 VDC LED illuminates.
– All other LEDs light up briefly (approx. 2 seconds).
Note
For C230-2
With an empty micro memory card, the SIMOTION Kernel on the C230-2 is copied to
the micro memory card during power-up. This increases the duration of the power-up
by about 1.5 minutes.
For C240 / C240 PN
If a micro memory card is not inserted in the C240 or if the micro memory card does
not contain a SIMOTION Kernel, all LEDs except the RUN LED are illuminated on the
SIMOTION C240.
SIMOTION C
146 Operating Instructions, 02/2012
Commissioning
7.4 Writing, formatting and erasing the Micro Memory Card
Note
The micro memory card always comes formatted! With the C240 / C240 PN, the SIMOTION
Kernel is located on the micro memory card.
In order to ensure error-free functioning of the micro memory card in the SIMOTION C, the
card must not be repartitioned.
Using Windows media to modify or delete files on the micro memory card that were written
with "Copy RAM to ROM" can destroy the project.
Note
The micro memory card for the C230-2 can only be formatted in the "SIMOTION SCOUT"
engineering system.
As of Kernel Version 3.1, you will no longer be able to format the micro memory card by
means of the C230-2 mode selector.
The card must not be formatted with the PC.
Any saved license keys are also deleted during formatting. The license key must then be
reentered via SIMOTION SCOUT.
SIMOTION C
Operating Instructions, 02/2012 147
Commissioning
7.4 Writing, formatting and erasing the Micro Memory Card
The micro memory card can be formatted by calling this function in "SIMOTION SCOUT"
(see SIMOTION SCOUT online help).
Note
As of Kernel Version 2.1 in the C230-2 and micro memory card 6AU1 700-0AA02-0AA0, the
C230-2 transfers its stored kernel to the micro memory card after formatting only after the
C230-2 has been restarted. When the kernel is transferred, all LEDs on the C230-2 flash. If a
specific kernel version is required, it must be placed on the micro memory card manually.
If the C230-2 is switched off or de-energized during commissioning, this could damage the
file system on the micro memory card (data on the card can no longer be read). If this
occurs, the micro memory card must be reformatted.
The micro memory card must not be removed when energized.
SIMOTION C
148 Operating Instructions, 02/2012
Commissioning
7.5 User memory concept
3URJUDPPLQJGHYLFH
6,027,216&287(6
'RZQORDG
6,027,21&
9RODWLOHGDWD 1RQYRODWLOHGDWD
00& 5$0 195$0
5$0WR520
73V 'LDJQRVWLFEXIIHU
73V
8VHUGDWD
8VHUGDWD 5DPSXS 5HWHQWLYHXVHUDUHD
UHWDLQYDULDEOH
,3SDUDPHWHUV
'3SDUDPHWHUV
,3SDUDPHWHUV
'3SDUDPHWHUV
3RZHURII
$EVROXWHHQFRGHU
V\VWHP RIIVHW
5DPSXS
6,027,21NHUQHO 8SGDWH
6,027,21 6,027,21
.HUQHO .HUQHO
5DPSXS
SUHVHQWDVRSWLRQRQ00&ZLWK&WKLVPXVWDOZD\VEHSUHVHQWRQWKH00&ZLWK&&31
ZLWK&&31WKHNHUQHOLVQRWVWRUHGLQWKH)ODVKDVDUHVXOWRIZKLFKWKHPRGXOHLVQRWXSGDWHG
In the following sections, you will learn information about the user memories and the steps
involved in certain operations.
See also
Overview of data deletion (Page 154)
SIMOTION C
Operating Instructions, 02/2012 149
Commissioning
7.5 User memory concept
Property Meaning
Location In the NVRAM of the SIMOTION C, no back-up battery required
Backup time Unlimited
Note
IP and DP parameters in non-volatile data
If there is a configuration on the MMC, the IP and DP parameters are loaded from the MMC
during ramp-up, written to the non-volatile data and used by the SIMOTION C. The
SIMOTION C uses the addresses defined in these parameters to go online. The IP and DP
parameters in the non-volatile data are retained and used by the SIMOTION C if a ramp-up
is performed with an MMC that does not contain a configuration.
A SIMOTION C can therefore always go online if a configuration has been loaded at least
once with the SIMOTION SCOUT, or if the SIMOTION C has been ramped up once with an
MMC.
SIMOTION C
150 Operating Instructions, 02/2012
Commissioning
7.5 User memory concept
7DUJHW &RPPLVVLRQLQJ
GHYLFH &RQILJGDWDLQ
581
'RZQORDG
8SORDG
1H[W 72UHVWDUW
6\VWHP RULPPHGLDWHO\
YDULDEOHV
5$0WR
520 &RS\FXUUHQWGDWD
&RS\LQJ WR5$0
520 5$0 &XUUHQW5$0
0LFURPHPRU\FDUG ORDGPHPRU\ QRV\VWHP ZRUNLQJPHPRU\
YDULDEOHV
1RQYRODWLOH
GDWD
Non-volatile system
With the SIMOTION C230-2, the SIMOTION Kernel is stored as non-volatile data in a flash
memory. A C230-2 can therefore also ramp up without a memory card.
SIMOTION C
Operating Instructions, 02/2012 151
Commissioning
7.5 User memory concept
Note
The "Copy RAM to ROM" command does not save the actual values of the retain
variables to the MMC.
SIMOTION C ramp-up
During ramp-up, the SIMOTION Kernel is loaded to the "volatile data" area. A C230-2 loads
the kernel from the "non-volatile system" (integrated flash in the device), a C240/C240PN
loads the kernel from the MMC.
The following data is also loaded from the MMC during ramp-up:
● Technology packages and user data to the "volatile data"
● IP and DP parameters to the "non-volatile data"
SIMOTION C
152 Operating Instructions, 02/2012
Commissioning
7.5 User memory concept
NOTICE
If you do not save the "non-volatile data" to the MMC, it is lost when a spare part is used (in
the event of a module defect).
If an absolute encoder overflow occurs after _savePersistentMemoryData, the actual
position value is no longer correct after the non-volatile data is restored. In this case,
homing (absolute encoder adjustment) must be repeated.
Power failure
The "non-volatile data" is saved to the NVRAM of the SIMOTION C during a power failure.
The "non-volatile data" is available again at the next ramp-up. Thus, the SIMOTION C is
immediately ready for operation without data loss.
SIMOTION C
Operating Instructions, 02/2012 153
Commissioning
7.6 Deleting data
See also
SIMOTION C memory model (Page 149)
Introduction
During the memory reset, the "volatile data" in the RAM of the SIMOTION C and the "non-
volatile data" in the NVRAM, except for the communication configuration (baud rates,
network addresses, etc.), is deleted. The data on the MMC is retained during the memory
reset.
You must perform a memory reset of the SIMOTION C:
● When you want to undo changes you have made to your user data (programs,
configuration data, parameter assignments) that you have not backed up with the "Copy
RAM to ROM" menu command.
● If the SIMOTION C requests a memory reset with a flashing STOP LED (slow flashing)
(e.g. micro memory card has been removed).
● The "non-volatile data" does not match the project on the MMC and therefore an error
occurs.
You can perform the memory reset online via SIMOTION SCOUT or offline via the mode
selector on the SIMOTION C.
SIMOTION C
154 Operating Instructions, 02/2012
Commissioning
7.6 Deleting data
Note
Absolute encoder data is deleted during a memory reset operation and must therefore be
readjusted after the memory reset.
Reset-proof data
The following data is retained during a memory reset:
● TCP/IP and DP parameters
● Diagnostic buffer
● Data that was saved with the _savePersistentMemoryData, _saveUnitDataSet,
exportUnitDataSet and RAMtoROM commands
If backup files ([Link]/[Link]) have been backed up with
_savePersistentMemoryData, the data in these files is backed up again to the non-volatile
data after the memory reset. Users can therefore force the restoration of non-volatile data
by means of memory reset.
● Licenses
The technology packages and user data (configuration data, programs, parameterizations)
that were previously backed up to the micro memory card using the "Copy RAM to ROM"
menu command will be transferred to the "non-volatile data" area of the SIMOTION C during
the next ramp-up. Thus, an existing configuration on the MMC is loaded to the SIMOTION
device following the memory reset.
SIMOTION C
Operating Instructions, 02/2012 155
Commissioning
7.6 Deleting data
Note
The operation for the memory reset with the toggle switch is described below. The operation
with the key-operated switch of the C230-2 is similar to the operation with the toggle switch.
6723/('
RQ
$OO/('VRQ
2II W
V
PD[V
Figure 7-4 Mode selector operation sequence for the memory reset
SIMOTION C
156 Operating Instructions, 02/2012
Commissioning
7.6 Deleting data
Requirement
You can delete user data with SIMOTION SCOUT. To do so, you must be online on the
SIMOTION C. The following data is deleted during this operation:
● User data in the volatile data
● Non-volatile data, except for the IP and DP parameters
● User data on the MMC (user directories)
You can thus continue to go online to the SIMOTION C with your PG/PC. The licenses on
the MMC are retained.
SIMOTION C
Operating Instructions, 02/2012 157
Commissioning
7.6 Deleting data
Overview
SIMOTION C is supplied with preset parameters, such as the transmission rate or
PROFIBUS addresses. You can restore the factory settings with the mode selector. The
following data is deleted during this operation:
● "Non-volatile data" in the SIMOTION device
● The backup ([Link]/[Link]) of the non-volatile data on the MMC
● User data in the "volatile data" and on the MMC
● The communication configuration (IP and DP parameters) is set to the factory settings
The licenses on the micro memory card are retained.
Note
The communication configuration is now reset to the factory settings. The communication
configuration for the SIMOTION C must be repeated.
See also
Factory setting (Page 131)
SIMOTION C
158 Operating Instructions, 02/2012
Maintenance and servicing 8
8.1 SIMOTION kernel update
SIMOTION C
Operating Instructions, 02/2012 159
Maintenance and servicing
8.1 SIMOTION kernel update
Note
Following an update, if problems occur during restart, the "SF" LED will illuminate or the
"STOPU", "STOP", "BUS1F", and "BUS2F" LEDs will flicker. This means that the update was
not completed correctly.
To remedy this error, proceed as follows:
Power OFF/ON
Check whether the restart is being performed correctly
If the error occurs again, repeat the update or replace the module.
SIMOTION C
160 Operating Instructions, 02/2012
Maintenance and servicing
8.1 SIMOTION kernel update
Note
If the micro memory card does not contain a SIMOTION Kernel, all LEDs on the SIMOTION
C240 / C240 PN apart from the RUN LED are illuminated.
SIMOTION C
Operating Instructions, 02/2012 161
Maintenance and servicing
8.2 Removal and replacement of the SIMOTION C
Overview
You can only replace SIMOTION C as a complete unit.
WARNING
The SIMOTION C can only be replaced when the load power supply is switched off.
You must therefore switch off the power supply, e.g. by means of the on/off switch on the
PS module.
SIMOTION C
162 Operating Instructions, 02/2012
Maintenance and servicing
8.3 Module replacement without programming device or PC
Overview
If a defective SIMOTION C has to be replaced without using a PG/PC, you can transfer the
data of the defective module to the new module by simply inserting the micro memory card
of the defective module in the new module.
Requirement
When you commissioned your project, you must have used the menu command "Copy RAM
to ROM" of the SIMOTION SCOUT to save your project to the micro memory card, as
described in the chapter "User memory concept".
The following data are on the micro memory card and can be transferred to the new module:
● Technology packages (TP)
● User data (programs, configuration data, parameterizations, task configuration)
● DP parameters (DP addresses, baud rate)
● IP parameters (IP address, subnet mask, router address)
As the non-volatile data is in a memory within the module, it is lost when the module is
replaced.
If the non-volatile data is to be transferred to the new module, it must first be backed up on
the micro memory card of the module to be replaced. The restoration of the non-volatile data
must be triggered via a memory reset on the new module.
Note
If the non-volatile data is not restored, the retain variables are set to their initial values and
the diagnostics buffer with the history from the old module is no longer available.
SIMOTION C
Operating Instructions, 02/2012 163
Maintenance and servicing
8.3 Module replacement without programming device or PC
SIMOTION C
164 Operating Instructions, 02/2012
Alarm, error, and system messages 9
9.1 Diagnosis using the LEDs
Diagnostic LEDs
The LEDs are explained in the order in which they are positioned on the SIMOTION C.
SIMOTION C
Operating Instructions, 02/2012 165
Alarm, error, and system messages
9.1 Diagnosis using the LEDs
SIMOTION C
166 Operating Instructions, 02/2012
Alarm, error, and system messages
9.1 Diagnosis using the LEDs
SIMOTION C
Operating Instructions, 02/2012 167
Alarm, error, and system messages
9.1 Diagnosis using the LEDs
Note
During ramp-up of the SIMOTION C, the LEDs on the housing front are briefly illuminated.
You can carry out a detailed diagnosis with a programming device or PC and the
engineering aystem.
Projects cannot be downloaded in STOPU mode.
SIMOTION C
168 Operating Instructions, 02/2012
Alarm, error, and system messages
9.2 Combinations of LED displays
1 LED on
0 LED off
0,5/1 LED flashing (0.5 Hz)
2/1 LED flashing (2 Hz)
☆ LED flickers
→ Running light
x LED may light up
SIMOTION C
Operating Instructions, 02/2012 169
Alarm, error, and system messages
9.2 Combinations of LED displays
SIMOTION C
170 Operating Instructions, 02/2012
Technical data 10
10.1 Technical data
For information about user data, refer to chapter Properties of the user memory (Page 150).
System clocks
Note
With the SIMOTION C, errors can occur during Download or during the transition from STOP
to RUN if I/O bus modules and a system cycle clock > 8 ms (only with equidistant bus cycle)
are used. If an error occurs, set the system cycle clock ≤ 8 ms.
SIMOTION C
Operating Instructions, 02/2012 171
Technical data
10.1 Technical data
DP slave connections
Address areas
Connection values
SIMOTION C
172 Operating Instructions, 02/2012
Technical data
10.1 Technical data
SIMOTION C
Operating Instructions, 02/2012 173
Technical data
10.1 Technical data
SIMOTION C
174 Operating Instructions, 02/2012
Technical data
10.1 Technical data
Position control cycle clock [µs] Actual value latch time Ti [µs]
C230-2 C240
1500 0 0
1750 0 0
2000 0 0
2250 0 0
2500 0 0
2750 0 2
3000 0 0
3250 0 64
3500 0 0
3750 0 127
4000 0 0
4250 0 189
4500 0 0
4750 0 252
5000 0 0
5250 0 314
5500 0 2
5750 0 377
6000 0 0
6250 0 439
6500 0 64
6750 0 502
7000 0 0
7250 0 564
7500 0 127
7750 0 627
8000 0 0
SIMOTION C
Operating Instructions, 02/2012 175
Technical data
10.1 Technical data
24 V encoder supply
Max. 100 m at 300 kHz and max. 300 mA
(tolerance 10 to 30 V)
Cable length for absolute encoder (SSI)
24 V encoder supply Max. 250 m at 187.5 Kbits/s
(tolerance 10 to 30 V)
Max. 10 m at 1.5 Mbit/s
Electrically isolated No
Monitoring Short-circuit in encoder supply and faulty wire
SIMOTION C
176 Operating Instructions, 02/2012
Technical data
10.1 Technical data
Digital inputs
Number of inputs 18
Supply voltage 24 V DC (permissible range: 20.4 to 28.8 V)
Input voltage 0 signal: -3...5 V
1 signal: 11 to 30 V
Input current 0 signal: 15 mA
1 signal: 6 to 30 mA (typically 8 mA)
Input delay (I0 to I11, B1 to B4, M1 to M2) 0 → 1 signal: 15 μs (typically 6 μs)
1 → 0 signal: 150 μs (typically 40 μs)
Connection of a 2-wire encoder Supported
Permissible quiescent current 2 mA
Electrical isolation between inputs No
Electrical isolation between inputs and logic Yes
Insulation 500 V DC
Length of cable Max. 30 m
SIMOTION C
Operating Instructions, 02/2012 177
Technical data
10.1 Technical data
Digital outputs
Number of outputs 8
Supply voltage 24 V DC (permissible range: VL = 20.4 to 28.8 V)
Output voltage 1 signal: From VL1) - 0.8 V to VL1) V
Max. output current 1 signal: 5 mA. to 0.6 A (via supply voltage)
Total current of the outputs max. 4 A (at 0 to 40° C)
max. 2 A (at 40 to 55° C)
Extinguishing energy per output 400 mJ (not simultaneous)
Lamp load 5W
Switching rate 100 Hz (with resistive load)
2 Hz (with inductive load)
Short-circuit protection Yes
Max. leakage current 0 signal: 2 mA
Output delay (Q0...Q7) 0 → 1 signal: 500 μs (typically 150 μs) with RL = 60 Ohm
1 → 0 signal: 500 μs (typically 150 μs) with RL = 60 Ohm
Electrical isolation between No
outputs
Electrical isolation between Yes
outputs and logic
Insulation 500 V DC
Length of cable Max. 30 m
1) VL - Supply voltage of outputs
Note
The connecting cable between the voltage source and the load current supply connector L+
and the associated reference potential M should not exceed a maximum length of 10 m.
SIMOTION C
178 Operating Instructions, 02/2012
Technical data
10.2 Real-time clock
SIMOTION C
Operating Instructions, 02/2012 179
Technical data
10.4 Mechanical and climatic environmental conditions for operation of the SIMOTION C
Use conditions
The SIMOTION C is designed for use in a stationary, weather-protected installation.
The SIMOTION C satisfies the operating conditions for Class 3C2 in accordance with DIN
EN 60721 3-3 (operating locations with high traffic densities and in the immediate vicinity of
industrial equipment with chemical emissions).
The SIMOTION C must not be used in the following locations without additional measures
being taken:
● Locations with a high percentage of ionizing radiation
● Locations with severe operating conditions, e.g. due to:
– Dust accumulation
– Corrosive vapors or gases
● Installations requiring special monitoring, such as:
– Elevator installations
– Electrical installations in highly sensitive areas
An additional measure for the use of the SIMOTION C could be installation in a cabinet, for
example.
SIMOTION C
180 Operating Instructions, 02/2012
Technical data
10.4 Mechanical and climatic environmental conditions for operation of the SIMOTION C
Reduction of vibration
If the SIMOTION C is subjected to greater shocks or vibrations, you must take appropriate
measures to reduce the acceleration or the amplitude.
Installation on damping material (e.g. rubber-bonded metals) is recommended.
SIMOTION C
Operating Instructions, 02/2012 181
Technical data
10.5 Specifications for dielectric tests, safety class and degree of protection
Test Voltages
During the routine test, the insulation resistance is tested at the following test voltage in
accordance with IEC 1131 Part 2:
Safety class
Safety class I in accordance with IEC 536 (VDE 0106, Part 1), i.e. a protective-conductor
terminal is required on the mounting rail!
SIMOTION C
182 Operating Instructions, 02/2012
Dimension drawing, spare parts, and accessories 11
11.1 Dimension drawing
6,027,21&
6,(0(16
581
6723
05(6
SIMOTION C
Operating Instructions, 02/2012 183
Dimension drawing, spare parts, and accessories
11.2 Spare parts and accessories
SIMOTION C
184 Operating Instructions, 02/2012
Standards, Certificates and Approvals A
A.1 General rules
CE marking
Electromagnetic compatibility
Standards for EMC are satisfied, if the EMC Installation Guideline is observed.
SIMOTION products are designed for industrial use in accordance with product standard DIN
EN 61800-3, Category C2.
cULus Approval
Listed component mark for United States and the Canada Underwriters
Laboratories (UL) according to Standard UL 508, File E164110, File E115352,
File E85972.
EMC
USA
Federal This equipment has been tested and found to comply with the limits for a
Communications Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
Commission designed to provide reasonable protection against harmful interference when
Radio Frequency the equipment is operated in a commercial environment. This equipment
Interference generates, uses, and can radiate radio frequency energy and, if not installed
Statement and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
Shielded Cables Shielded cables must be used with this equipment to maintain compliance with
FCC regulations.
SIMOTION C
Operating Instructions, 02/2012 185
Standards, Certificates and Approvals
A.1 General rules
USA
Modifications Changes or modifications not expressly approved by the manufacturer could
void the user’s authority to operate the equipment.
Conditions of This device complies with Part 15 of the FCC Rules. Operation is subject to
Operations the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
CANADA
Canadian Notice This Class B digital apparatus complies with Canadian ICES-003.
Avis Canadien Cet appareil numérique de la classe B est conforme à la norme NMB-003 du
Canada.
SOUTH KOREA
For sellers or other user, please keep in mind that this device in an A-grade electromagnetic wave
device. This device is intended to be used in areas other than home.
The EMC limit values to be observed for Korea correspond to the limit values of the EMC product
standard for variable-speed electric drives EN 61800-3 of category C2 or the limit value class A,
Group 1 to EN55011. By implementing appropriate additional measures, the limit values according to
category C2 or limit value class A, Group 1, are observed. For this purpose, additional measures,
such as the use of an additional RFI suppression filter (EMC filter) may be necessary. In addition,
measures for EMC-compliant configuration of the plant are described in this Manual and/or the
Configuration Manual "EMC Installation Guideline". Please note that ultimately it is always the label
on the device that provides the decisive information on the compliance with standards.
Declaration of conformity
The current Declaration of conformity is available on the Internet at Declaration of conformity
([Link]
CAUTION
SIMOTION C
186 Operating Instructions, 02/2012
Standards, Certificates and Approvals
A.2 Safety of electronic controllers
C-Tick
AUSTRALIA
This product meets the requirements of the AS/NZS CISPR 22.
Introduction
The following remarks relate to fundamental criteria and apply irrespective of the type of
controller and the manufacturer.
Risk
A higher degree of safety standard applies to all applications and situations where there is a
risk of material damage or injury to persons if there is a failure. Special regulations specific to
the system apply to such applications. These must be taken into account for configuration of
the controller (e.g. VDE 0116 for furnaces).
For electronic controllers with safety responsibility, the measures required for preventing or
controlling faults depend on the hazard inherent in the plant. In this respect, the basic
measures listed above are no longer adequate once the hazard exceeds a certain potential.
Additional measures (e.g. double redundancy, tests, checksums, etc.) for the controller must
implemented and certified (DIN VDE 0801).
SIMOTION C
Operating Instructions, 02/2012 187
Standards, Certificates and Approvals
A.2 Safety of electronic controllers
SIMOTION C
188 Operating Instructions, 02/2012
ESD guidelines B
B.1 ESD definition
CAUTION
Electrostatic sensitive devices can be irreparably damaged by voltages that are far lower
than anything a person can perceive. These voltages occur if you touch a component or the
electrical connection of a module without having previously discharged any static from your
body. Any damage that occurs to a module as a result of overvoltage is generally not
recognized immediately and only comes to light after the equipment has been operating for
some time.
SIMOTION C
Operating Instructions, 02/2012 189
ESD guidelines
B.2 Electrostatic charging of individuals
9ROWDJHLQN9
N9 6\QWKHWLFPDWHULDO
:RRO
$QWLVWDWLFPDWHULDOHJZRRGRUFRQFUHWH
5HODWLYHDLUKXPLGLW\LQ
SIMOTION C
190 Operating Instructions, 02/2012
ESD guidelines
B.3 Basic measures for protection against discharge of static electricity
SIMOTION C
Operating Instructions, 02/2012 191
ESD guidelines
B.3 Basic measures for protection against discharge of static electricity
SIMOTION C
192 Operating Instructions, 02/2012
Index
In subnet, 124
Cables
shielded, 120
2 CE marking, 185
Characteristic impedance
2-tier layout, 83 see terminating resistor, 123
Clearances, 79
Clock, 179
A commissioning
Absolute encoder (SSI), 20, 52 System requirements, 143
Accessories, 184 Components
Actual value, 175 For PROFIBUS DP subnet, 123, 125
Actual value assignment, 116 Configuration examples, 65, 75
Address configuring
Default, 133 electrical design, 92
Address areas, 172 mechanical structure, 78
Technical data, 172 Connecting
Address assignment Bus connector, 126
based on module slot, 133 drive units, 103
user-assignable, 135 Encoder, 114
Addresses PG/PC, 144
analog module, 137 Power supply, 100
digital module, 136 Connecting cable, 99
FM and CP modules, 138 Ethernet-bus cable, 94
Ambient temperature for interface modules, 82
permissible, 78 Measuring system cable, 94, 114
analog module PROFIBUS DP cable, 94
Addresses, 137 Programming device, 94
Setpoint cable, 94
Connection values, 172
B cULus Approval, 185
Current consumption
Bus connector, 35 of a central configuration, 93
Connecting to module, 126
removing, 127
setting the terminating resistor, 126 D
Bus segment, 123
Declaration of conformity, 4, 186
Default address, 133
C Degree of protection, 182
IP 20, 182
C2xx Design
Disposal, 6 Configuring, 78
installation, 162 horizontal, 78
removal, 162 vertical, 78
replacement, 162 Diagnostics
wiring diagram - digital inputs/outputs (onboard), 69 LED display, 165
C2xx installation, 162 Digital input (onboard)
Cable lengths Connecting-up, 117
SIMOTION C
Operating Instructions, 02/2012 193
Index
Description, 72 F
Technical data, 177
Factory setting, 131
Digital input/digital output
Restore, 158
I/O bus, 119
Field of application, 12
digital module
Filter time, 51, 173
Addresses, 136
FM STEPDRIVE
Digital output (onboard)
Connection, 107
Description, 75
installation, 81
Technical data, 178
Front connector, 99
Wiring, 117
Front panel controls
Dimension drawings, 183
LED displays, 34
Dimensions, 172
DP slave
Connections, 123, 172
G
DP slave connections
Number, 123, 172 Global measuring
Drive interface C240/C240 PN, 73
as standard output, 51 Guideline
Signals, 47 ESD, 189
Drive- interface, 45
Assignment, 46
with analog interface, 47 H
Drive- interface
Highest PROFIBUS-address, 122
Stepper drives, 48
I
E
I/O modules, 18
Electrical design
Incremental encoder, 20, 55
Configuring, 92
Installation
Electromagnetic compatibility, 185
Layout of modules, 81, 82
EMC directives, 185
Installing, 84
EMC guidelines, 91
Modules, 87
EMERGENCY OFF concept, 91
Mounting rail, 84
Encoder, 52
Shield connecting element, 121
Absolute encoder, 52
Insulation test, 182
Connecting, 114
Integrated measurement electronics, 62
Incremental encoder, 52
Interface module, 82
Encoder power supply, 52
Connecting cable, 82
Environmental conditions, 180
Interface positions, 24, 25, 26
Climatic, 181
Interfaces, 35
Mechanical, 181
Drive- interface, 45
ESD guideline, 189
Ethernet interface, 36
Ethernet interface
I/O interface, 68
Assignment, 37
Measuring system interface, 52
Ethernet-subnet, 127
MPI, 42
External electrical interference
Power supply connection, 100
Protection, 93
PROFIBUS DP interface, 42
External zero marker, 72, 117, 119
IP 20, 182
SIMOTION C
194 Operating Instructions, 02/2012
Index
P
L
PE connection
Laying rules
on mounting rail, 86
PROFIBUS cable, 126
PG/PC
LED display
Connecting, 144
SIMOTION C diagnostics, 165
Power loss
LEDs, 165
of a central configuration, 93
Local measuring, 72
Power supply, 100
Setting supply voltage, 103
Probe, 117, 119
M
PROFIBUS address, 122
Measuring input, 72 Highest, 122
Memory model, 149 Rules, 122
Micro memory card, 32, 33 PROFIBUS cable, 125
Changing, 145 Laying rules, 126
inserting, 145 PROFIBUS device
Writing to, 147 Nodes, 122
Mode selector, 24, 25, 26 PROFIBUS DP subnet
Module Cable lengths, 124
Installing, 87 Components, 123, 125
Layout, 81, 82 PROFIBUS subnet
Mounting dimensions, 80 Segment, 124
Transportation and storage conditions, 179 PROFINET, 39
Module start address, 134 Protection against external electrical phenomena, 93
Module supply, 100 Protective signal circuits of the stepper motor
Motion control, 20 interface, 49
Mounting dimensions
of the modules, 80
Mounting rail R
Installing, 84
READY output, 76, 178
Length, 80
References, 4
PE connection, 86
Reliability
MPI subnet, 131
Risk, 187
MRES, 31
removing C2xx, 162
Replace module, 163
replacing C2xx, 162
N
Residual risk, 188
Network components, 125 Retaining bracket
Nodes, 122 Shielding terminal, 121
RUN, 31
O
Onboard drive interface
SIMOTION C
Operating Instructions, 02/2012 195
Index
S W
Safety class, 182 Weight, 172
Safety of electronic controllers, 187 Wiring, 91
Safety regulations, 91 Front connector, 117
EMERGENCY STOP devices, 91 Wiring diagram, 94
Segment, 123 Writing to
PROFIBUS subnet, 124 Micro memory card, 147
Setpoint, 175
Shield connecting element, 120
Shielding terminal, 120
SIMODRIVE 611 universal, connection, 104
SIMODRIVE 611-U, connection, 109
SIMOTION C memory reset, 154
Slot number, 88, 133
Allocating, 88
inserting, 89
Spare parts, 184
Standards and approvals, 4
Stepper drive, 48
Signals, 48
Stepper motor control, 22
Position-controlled, 22
STOP, 31
STOPU, 31
Supply voltage, 92
Setting, 103
System clocks, 171
System integration, 12
Components, 15
System overview, 11
T
Technical data, 171
Terminating resistor, 123
Adjusting to bus connector, 126
Test Voltages, 182
Type plate, 27
U
UL certification, 185
Use conditions, 180
User data
Deleting, 157
User-assignable addressing, 135
V
Vibration, 181
SIMOTION C
196 Operating Instructions, 02/2012