COOLING TECHNOLOGY INSTITUTE
P. O. Box 681807, Houston, Texas 77268 • 3845 Cypress Creek Parkway, Ste 420, Houston, Texas 77068
Phone: 281.583.4087 • Fax: 281.537.1721 • email: vmanser@ [Link] • [Link]
August 25, 2021
(Revision 1)
Delta Cooling Towers Pvt. Ltd.
1st Floor, Bhagwati Sadan, Plot no. 8, Community Centre,
BH Block (East), Shalimar Bagh, DELHI-110088 (INDIA)
Subject: CTI Cooling Tower Certification for the
Delta Cooling Towers Pvt. Ltd.
DFC – 60UX Cooling Towers
Greetings:
The Delta Cooling Towers Pvt. Ltd. line of DFC – 60UX counter-flow, induced-draft, cooling
towers, as described in your original application and subsequent revisions through August 9, 2021,
has satisfactorily fulfilled the requirements for certification of thermal performance by the Cooling
Technology Institute (CTI), as set forth in the CTI Certification Standard STD-201(19). A listing of
the forty-one (41) DFC – 60UX models currently encompassed by this certification is included with
this letter for reference.
The Delta Cooling Towers Pvt. Ltd. line of DFC – 60UX cooling towers has been assigned and
should use CTI Certification Validation Number C85A-18R01. You are hereby authorized and
encouraged to properly display the CTI Certification Logo in all pertinent literature for the line and
required to affix the CTI Certification Label to all towers comprising the line, as provided in the CTI
STD-201 Certification Standard.
This CTI Certification requires the successful completion of a CTI Annual Reverification Test
to remain in effect in subsequent years.
Very truly yours,
Michael G. Womack, PE
CTI Thermal Certification Administrator
COOLING TECHNOLOGY INSTITUTE
P. O. Box 681807, Houston, Texas 77268 • 3845 Cypress Creek Parkway, Ste 420, Houston, Texas 77068
Phone: 281.583.4087 • Fax: 281.537.1721 • email: vmanser@ [Link] • [Link]
Delta Cooling Towers Pvt. Ltd.
DFC – 60UX Line of CTI Certified Cooling Towers
CTI Certification Validation Number C85A-18R01
August 25, 2021
Single Cell Models
6070 UX 6200 UX
6080 UX 6220 UX
6100 UX 6240 UX
6115 UX 6260 UX
6130 UX 6280 UX
6140 UX 6300 UX
6160 UX 6330 UX
6170 UX 6360 UX
6180 UX
Multi-cell Models
2-Cell Models 3-Cell Models 4-Cell Models 6-Cell Models 8-Cell Models 9-Cell Models
6400 UX 6900 UX 61K2 UX 62K4 UX 62K2 UX 62K5 UX
6450 UX 61K0 UX 61K3 UX 62K7 UX 62K3 UX 62K6 UX
6500 UX 61K1 UX 61K4 UX 63K0 UX 62K8 UX
6600 UX 61K5 UX
6700 UX 61K6 UX
6800 UX 61K8 UX
62K0 UX
See Footnotes, Next Page
Page 2 of 3
COOLING TECHNOLOGY INSTITUTE
P. O. Box 681807, Houston, Texas 77268 • 3845 Cypress Creek Parkway, Ste 420, Houston, Texas 77068
Phone: 281.583.4087 • Fax: 281.537.1721 • email: vmanser@ [Link] • [Link]
Delta Cooling Towers Pvt. Ltd.
DFC – 60UX Line of CTI Certified Cooling Towers
CTI Certification Validation Number C85A-18R01
August 25, 2021
Footnotes:
1. The above models use side, end or bottom water inlet configuration.
2. The above listed models use standard construction materials - FRP (Fiberglass Reinforced Plastic)
casing, basin/sump, fan deck & fan cylinder; HDG (Hot Dipped Galvanized) steel structure; GI
hardware; direct driven fan; fixed type water distribution system & splash cups; PVC honeycomb fill;
PVC extruded ‘C’ section drift eliminators; and, 415 Volt/50 Hz/3 Phase fan motor with extended shaft.
3. The above models can be provided with fan motors suitable for 220V, 380V or 460V and 60Hz. Flame
proof motors can also be provided without impact on capacity. Optional high efficiency motors are also
available.
4. Certification includes alternate casing and basin materials without compromising on the thermal
performance of the above models. Such modified models will be suffixed ‘A’. Alternate stainless steel
hardware is also available.
Certified Model Number Examples:
Example 1: DFC 6400 UX
DFC (-60 UX) – Line Designation
6400 UX – Model Number (Two-cell Model)
Page 3 of 3
CTI Thermal Certification Test Report
T85A-114-19C
Annual Reverification Test (Carryover)
On the Delta Cooling Towers Pvt. Ltd.
DFC – 60UX Line, Model 6360 UX
1-cell, Induced-draft, Counter-flow Cooling Tower
Tested At a Customer Site
in Delhi, India
For Delta Cooling Towers Pvt. Ltd.
1st Floor, Bhagwati Sadan, Plot no. 8, Community Centre
BH Block (East), Shalimar Bagh, DELHI-110088 (INDIA)
Test Date: June 22, 2021
Test No. T85A-114-19C
Prepared by: Michael G. Womack, P.E.
CTI Thermal Certification Administrator
c/o CleanAir Engineering
Summary
McHale and Associates, Inc. (McHale) has been designated by the Cooling Technology
Institute (CTI) to conduct thermal certification tests as set forth in the CTI STD-201(19) certification
standard. A CTI Annual Reverification Test was performed for Delta Cooling Towers Pvt. Ltd.
(Delta) on their DFC – 60UX line, model 6360 UX, 1-cell, induced-draft, counter-flow cooling tower.
The test was conducted at a Delta Customer Facility in Delhi, India. The purpose of the CTI Annual
Reverification Test is to verify the thermal performance of the subject model as required to maintain
CTI Certification of the line of cooling towers, and to support Revision 1 of the certification, adjusting
the rated capacity of certain models. The work was performed by McHale as an independent
contractor licensed by the CTI for STD-201 testing services.
The Annual Reverification Test was conducted on June 22, 2021, in accordance with the CTI
Standard for Performance Rating of Evaporative Heat Rejection Equipment, STD-201RS(19). The
test data were acquired in accordance with the CTI Acceptance Test Code for Water-Cooling Towers,
ATC-105(00). All thermal parameters were measured with precision platinum RTD temperature
probes and recorded using a data acquisition system consisting of a multi-channel data logger
interfaced with a laptop computer. The circulating water flow was measured using a hydraulic pitot
tube with an air-over-water manometer. Fan motor power was measured with a clamp-on digital
kilowatt meter. Following the test, the computer system was used to average the test data, assist with
selection of time periods for analysis, and calculate the test results.
The test results were calculated for one time period selected during the Annual Reverification
Test by using the manufacturer's expanded rating table and the methods of analysis as specified in the
CTI STD-201 certification standard. The data indicate that the Delta model 6360 UX cooling tower
was operating at 95.5% of its published capacity during the test on June 22, 2021, which exceeds the
95% minimum allowed by the CTI STD-201.
Therefore, the Delta Cooling Towers Pvt. Ltd., DFC – 60UX line of cooling towers has
fulfilled the testing requirement to maintain thermal certification as per CTI STD-201, and to support
Revision 1 of the certification.
The CTI STD-201 Certification requires the successful completion of a CTI Annual
Reverification Test on a different model each year to remain in effect in the subsequent year.
Clean Air Engineering, Inc.
Thermal Certification Administration Services
Prepared by:
Michael G. Womack, P.E.
CTI Certification Administrator
Page 2 of 9