EN FANOX DATA SILC FeederGeneratorProtection ProtectionRelays R10
EN FANOX DATA SILC FeederGeneratorProtection ProtectionRelays R10
82
Functions diagram SIL-C
BUS SIL-C
3 or 4
27 27V1 59 59N/G 47 24 81 81R 78
32 60VTS
3
67NI 67N/51N 67/51 SOFT 50 50N 46 46BC 37 49 SHB
60CTS
AFD* 64REF
CLP
52
HLT 79 52 74TCS 68 86 25*
3
27-L* 59-L*
49T
1 1 1 1 * Optional
67G/51G Inverse Time Directional* Measured Neutral 81R Rate of change of Frequency (ROCOF)
Overcurrent
78 Out of Step (Vector Shift)
67NI Directional isolated calculated neutral overcurrent
24 Overfluxing
67GI Directional isolated measured neutral overcurrent
CLP Cold Load pickup
SOTF Switch On To Fault
79 AC Reclosing device
46 Phase balance current protection
HLT Hot Line Tag
46BC Broken Conductor Detection
52 Breaker Wear Monitoring
64REF Restricted earth fault
25 Synchro Check
37 Instantaneous phase undercurrent
50BF Circuit Breaker Failure
49 Thermal overload
74TCS Trip Circuit Supervision
49T External Trip
60CTS Phase CT Supervision
SHB Second Harmonic Blocking
60VTS Phase VT Supervision
59 Instantaneous phase overvoltage (Bus Bar)
Instantaneous Calculated/Measured neutral 86 Trip Lockout
59N/G overvoltage (Bus Bar)
68 Zone Selection Interlocking (ZSI)
59L Instantaneous phase overvoltage (Line)
PGC Programmable logic control
47 Phase Balance voltage protection (Bus Bar) * ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51,
ANSI 51G and ANSI 51N respectively by setting the “Directionality”
parameter to NO.
ADDITIONAL FUNCTIONS
SER Sequential Event Recording
CNT Counters
DFR Disturbance Fault Recording
RTC Real Time Clock
LDP Load Data Profiling
ALRM Alarm panel
MET Metering
PGC Programmable Logic Control
STTG Settings Groups
HMI Human Machine Interface
CMMD Commands
83
Technical parameters SIL-C
Deactivation level: 95% Current tap: 0.050 to 20.000 xIn (step 0.001xIn)
Time delay: 0.000 to 300.000 s (step 0.001 s) Curve, current activation level: 110%
Function 50G-1 Activation level: 100% Curve, current deactivation level: 100%
± 30 ms or ± 5% (greater of both)
84
Technical parameters SIL-C
Time delay: 0.000 to 300.000 s (step 0.001 s) Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn)
Time dial (TMS): 0.05 to 25.00 (step 0.01) High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Function 67GI
If Curve type IEC: 0.05 to 1.00 (step 0.01) Time delay: 0.000 to 300.000 s (step 0.001 s)
If Curve type IEEE: 0.10 to 25.00 (step Operating angle: 0 to 359º (step 1º)
0.01)
Halfcone angle: 10 to 170º (step 1º)
Current tap: 0.010 to 20.000 xIn (step 0.001xIn)
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Function 67G/51G-1 Polarization voltage: 0.08 to 2.00 xUn (step 0.01xUn)
Temporized deactivation
Operating angle: 0 to 359º (step 1º)
Function 67G/51G-2 Timing accuracy: ± 30 ms or ± 5% (greater of both)
Halfcone angle: 10 to 170º (step 1º)
Function enable: No/Alarm/Trip/ SHB Trip
Curve, current activation level: 110%
Current tap: 0.050 to 20.000 xIn (step 0.001xIn)
Curve, current deactivation level: 100%
Time delay: 0.020 to 300.000 s (step 0.001 s)
Defined time, current activation level: 100% Function 64REF Neutral SHB Tap: 5 to 50% (step 1%)
Defined time, current deactivation level: 95%
Activation level: 100%
Voltage activation level: 100%
Deactivation level: 95%
Voltage deactivation level: 95%
Temporized deactivation
Temporized deactivation
Timing accuracy: ± 35 ms or ± 5% (greater of both)
Timing accuracy for IEC and IEEE curves selection:
Function enable: No/Alarm/Trip/SHB Trip
± 30 ms or ± 5% (greater of both)
Current tap: 0.010 to 30.000 xIn (step 0.001xIn)
Timing accuracy for defined time curve selection:
Time delay: 0.000 to 295.000 s (step 0.001 s)
± 35 ms or ± 0.5% (greater of both)
Safe Time: 0.020 to 300.000 s (step 0.001 s)
Function enable: No/Alarm/Trip/SHB Trip Function SOTF
Activation level: 100%
Directionality: No/Forward/Reverse
Deactivation level: 95%
Low Current Tap: 0.050 to 30.000 xIn (step 0.001xIn)
Temporized deactivation
High Current Tap: 0.050 to 30.000 xIn (step
0.001xIn) Timing accuracy: ± 35 ms or ± 0.5% (greater of both)
Low Voltage Tap: 0.08 to 2.00 xUn (step 0.01xUn) Function enable: No/Alarm/Trip
High Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn) Current tap: 0.100 to 2.400 In (step 0.001xIn)
Function 67NI ζ heating: 3 to 600 min (step 1 min)
Time delay: 0.000 to 300.000 s (step 0.001 s)
Operating angle: 0 to 359º (step 1º) ζ cooling: 1 to 6 xζ heating (step 1)
Function 49
Halfcone angle: 10 to 170º (step 1º) Alarm: 20 to 99% (step 1%)
Activation level: 100% Trip level: 100%
Deactivation level: 95% Deactivation level: 95% of alarm level
Temporized deactivation Timing accuracy: ± 5% respect of theorical value.
Timing accuracy: ± 30 ms or ± 5% (greater of both) Function enable: No/Yes
Current Tap: 5 to 50% (step 1%)
Reset Time: 0.000 to 300.000 (step 0.001 s)
Function SHB Block Threshold: 0.010 to 30.000xIn (step 0.001xIn)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Function enable: Yes/No
Settings group: 1 to 4 (step 1)
No load time: 0.020 to 300.000 s (step 0.001 s)
Function CLP
Cold load time: 0.020 to 300.000 s (step 0.001 s)
Open breaker activation 0.8% In and reset
threshold: 1% In
85
Technical parameters SIL-C
86
Technical parameters SIL-C
Function 78 Function blocked if phase B voltage is lower than 20 Repetitive number of openings: 1 to 100,000 (step 1)
volts P-N (35 volts P-P)
Time for repetitive number of openings: 1 to 300 min
Temporized deactivation (step 1 min)
Measurement accuracy: ±1º or ±10% (greater of Function 52 Maximum opening time: 0.020 to 300.000 s (step
both) 0.001 s)
Maximum closing time: 0.020 to 300.000 s (step
0.001 s)
Circuit breaker status monitoring:
Current measurements: Open breaker activation and
reset threshold: 0.8% In (Without using contacts)
Using contacts: 52a or 52b and 52a and 52b
87
Technical parameters SIL-C
4 settings groups
Settings tables < 70 mVA
Selectable by input, communications, user
commands or general setting.
Energizing Burden of power supply unit:
SER 3072 events Quantities
88
Technical parameters SIL-C
Phase currents (IA, IB, IC), neutral (IN, 3I0), positive 24-230 Vac/dc (24-220 Vdc (±20%) / 100-230 Vac
sequence (I1) and negative sequence (I2) I2/I1 Power supply (±15%))
Maximum current (Imax), thermal Image (TI), Second
harmonic (IA2H, IB2H IC2H), Current Total Harmonic Burden: 24-230 Vdc/Vac: < 20 VA
Distortion (THD-A, THD-B and THD-C). Operating temperature: -40 to 70ºC
Current Fundamental values (DFT) Environmental
Storage temperature: -40 to 80ºC
measurements conditions
Sampling: 32 samples/cycle Relative humidity: 95%
2% precision in a band covering ±20% of nominal Metallic box
current and ±4% in the rest of the range
Panel mounted
Current measurement range: From 0.01 to 30 times
the nominal current Mechanical Vertical assembly: HxWxD: 198x107x145.01 (mm)
Phase voltage (VA, VB, VC), Line Voltage (VL)*, characteristics Horizontal assembly: HxWxD: 107x198x145.01 (mm)
phase-phase voltage (UAB, UBC, UCA), neutral
voltage (VR, 3V0), positive sequence (V1) and IP-54
negative sequence (V2), Maximum voltage (VMAX) The required screws to fix the relay should be M4
and V/f.
(*) Optional depending on model
Fundamental values (DFT)
NOTE: ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51,
Sampling: 32 samples/cycle ANSI51G and ANSI 51N respectively by setting the “Directionality” parameter
to NO.
Voltage Measured voltage: 1% precision in a band covering
measurements ±20% of nominal voltage and 4% in the rest of the
range (ambient temperature)
Calculated voltage: 2% precision in a band covering
±20% of nominal voltage and 4% in the rest of the
range (ambient temperature)
- With VTs: 3-250 V measured voltage (6-250 V
calculated voltage)
- Direct connection: From 12 to 1000 V
Current Angles: IA, IB, IC, IN and 3I0.
89
Dimensions and cutout SIL-C
Horizontal assembly
CUT-OUT
PATTERN
90
Dimensions and cutout SIL-C
Vertical assembly
CUT-OUT
PATTERN
91
A
Connections diagram SIL-C
A
BUS B
C
A1 A2 A3 A4 A5 A6 A7 A8
A B C N
MEASUREMENT
INPUTS
COMMON
VOLTAGE
INPUTS
B3
B4
COMMON
B5
B6
B7
B8 SIL-C
B9 Protection Relay
B10
52 B11
B12
OUTPUTS
LINE
SAFETY
GND GROUND
AC/DC
POWER
B1 Power Supply
AUX.
COM B2
92
A
Connections diagram SIL-C
C B
A
BUS B
C
A1 A2 A3 A4 A5 A6 A7 A8
A B C N
MEASUREMENT
INPUTS
COMMON
VOLTAGE
INPUTS
B3
B4
COMMON
B5
B6
B7
B8 SIL-C
B9 Protection Relay
52 B10
B11
B12
OUTPUTS
LINE
SAFETY
GND GROUND
AC/DC
POWER
B1 Power Supply
AUX.
COM B2
93
Selection & Ordering data SIL-C
SIL-C
Feeder & Generator Protection Relay
PHASE CURRENT MEASUREMENT
0 1 A or 5 A
NEUTRAL CURRENT MEASUREMENT
0 1 A or 5 A
VOLTAGE MEASUREMENT
0 Up to 1000 V (direct connection) or 250 V (with VTs)
POWER SUPPLY
C 24-230 Vac/dc
ADDITIONAL FUNCTIONS
0 -
1 +25 + 27-L + 59-L
COMMUNICATIONS
A A: USB (Modbus RTU) + RS485: (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial)
B B: USB (Modbus RTU) + RS485 (Modbus RTU, IEC60870-5-103 or DNP3.0
Serial) + RJ45 (Modbus TCP or DNP3.0 TCP or IEC60870-5-104)) + Web
Server + SNTP Protocol + IRIG-B
INPUTS AND OUTPUTS
1 11 Inputs + 5 Outputs
MECHANICAL ASSEMBLY
C Vertical Assembly
D Horizontal Assembly
E Vertical Assembly with anticorrosive treatment
F Horizontal Assembly with anticorrosive treatment
LANGUAGE
A English, Spanish, German and French
E English, Spanish, Turkish and Russian
F English, Spanish, German and Portuguese
ADAPTATION
B (2) 50 + SOTF + 50G + 50N + (4) 67/51 + (2) 67G/51G + (2) 67N/51N + 67GI
+ 67NI + 64REF + 46 + 46BC + 49 + 49T + 37 + (2) 27+ 27V1 + (2) 59 + (2)
59N/G + 47 + (4) 32 + (4) 81U/O + (4) 81R + 78 + (2) 24 + 79 + 74TCS +
60CTS + 60VTS + 50BF + SHB + CLP + 52 + 86 + HLT
0 0 0 C 0 A 1 C A B SIL C 0 0 0 C 0 A 1 C A B
SIL-C
(*) ANSI 67, ANSI 67G and ANSI 67N can be converted into ANSI 51, ANSI 51G and ANSI 51N respectively by setting the “Directionality” parameter