MANUFACTURER’S NAME & ADDRESS: QAP OF FOAM TENDER PROJECT: SAIL -WB PO NO: – 6500000161
INDUS FIRE SAFETY PVT. LTD. QAP NO. IF-QAP-SAIL-WB-01-FT. DATE – 20/07/2022
903 Atlantis Heights, Sarabhai Compound, [Link] ITEM – MULTIPURPOSE TENDER
VADODARA-390 023 (Gujarat) DATE – 06/08/2022 PAGE - 1 of 2
1 2 3 4 5 6 7 8 9 10
SL. COMPONENTS CHARACTERISTIC CLASSIFI TYPE OF QUANTUM REF. DOC. ACCEPTANCE AGENCY REMARK
NO & OPERATION CHECK CATION CHECK OF CHECK
M C
1 Chassis Make, Engine No. Major Visual, 100% As per Chassis P V
1st Stage Chassis No. Review of Specification/PO Documents
Inspection Doc.
Raw Material 1. Visual Major Visual, Drawing, P V
2 Structural Steel Dimensional Min. Drawing, PO Specification
& Tank RM 10% Specification.
2. Chemical & Major Visual ----- Manufacturers V V
1st Stage Physical Test Certificates
Inspection
1. Fabrication Major Visual & 100% As per App. P V
3 Fabricated Dime. Drawing & As per App.
Items Specification Drawing
Water & Foam Leakage As per I.S. As per App.
Tanks etc. 2. Tanks Major test. 100% (I.S-10460-1983) Drawing P V
(0. 3 Bar)
1st Stage
Inspection
4 Final Inspection 1. Hydro Test of Major Visual 100% As per As per Approved
of Complete Pipe Line & Specification Documents P V
Fire Truck. Valves.
2. Painting Quality Major Visual 100% As per As per Approved
(both internal & specification Documents P V
external)
3. Performance Major
Test. Physical 100% As per As per Approved P W
A. Pump Running specification Documents
Test & Performance
B. Priming Physical 100% As per App Data As per Approved
Performance Test Sheet. Documents P W
MANUFACTURER’S NAME & ADDRESS: QAP OF FOAM TENDER PROJECT: SAIL-WB PO NO: – 6500000161
INDUS FIRE SAFETY PVT. LTD. QAP NO. IF-QAP-SAIL-WB-01-FT. DATE – 20/07/2022
903 Atlantis Heights, Sarabhai Compound, [Link] ITEM – MULTIPURPOSE TENDER
VADODARA-390 023 (Gujarat) DATE – 06/08/2022 PAGE - 2 of 2
1 2 3 4 5 6 7 8 9 10
SL. COMPONENTS CHARACTERISTIC CLASSIFI TYPE OF QUANTUM REF. DOC. ACCEPTANCE AGENCY REMARK
NO & OPERATION CHECK CATION CHECK OF CHECK
M C
C. Control panel Physical 100% As per App Data As per Approved
operational check Sheet. Documents P W
Final Inspection
of Complete D. Monitor Major Operational 100% As per App Data As per Approved
Fire Truck. Performance Sheet. Documents P W
E. Water Hose Reel Functional. 100% As per App Data As per Approved
Testing. Sheet. Documents P W
4. Electrical Major Functional 100% Approved As per Approved
Function Test. Documents/Specifi Documents. P W
cation.
5. Road test Major Physical 100% Approved As per Approved
Documents/Specifi Documents. P W
cation.
6. Static Stability & Major Visual 100% Approved As per Approved
Gradient test. Documents/Specifi Documents. P W
cation.
7. Completeness of Major Visual 100% Approved As per Approved
Equipment. Documents/Specifi Documents. P W
cation.
For INDUS FIRE SAFETY PVT. LTD. M – INDUS/MANUFACTURER.
C – NTPC TANDA
P – PERFORM
(Stamp & Signature) V – VERIFY
W – WITNESS