PT.ESA MASIV TEKNIK reported on maintenance work done on generator sets at a BSSN building location on January 3, 2023. Alarms were showing on the Woodward and Deepsea control modules that prevented the generator sets from starting automatically during power outages. The issues were resolved by manually resetting the Woodward module settings and using Deepsea configuration software to clear fault codes and check parameters on the DSE module. After the maintenance work, the generator sets were able to start and run normally during subsequent power outages.

Uploaded by

boy qsi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views4 pages

Report BSSN

PT.ESA MASIV TEKNIK reported on maintenance work done on generator sets at a BSSN building location on January 3, 2023. Alarms were showing on the Woodward and Deepsea control modules that prevented the generator sets from starting automatically during power outages. The issues were resolved by manually resetting the Woodward module settings and using Deepsea configuration software to clear fault codes and check parameters on the DSE module. After the maintenance work, the generator sets were able to start and run normally during subsequent power outages.

Uploaded by

boy qsi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

PT.

ESA MASIV TEKNIK


General Contractor - Trading - Marine Automation
REPORT
Komplek Ruko Puriloka Blok D No 7 Baloi Kota
Batam Centre Batam Kepulauan Riau 29433
Phone : 0778 4163 290 Mobile : 0812 7659 7878Email : [email protected]

To : BSSN Date : January, 3 2023


Attn : Mr Dede Location : Building

DESCRIPTION DATE REMARKS

January Showing Alarm MAINTENANCE DAY


3 2023 EXCEEDED ON Display Woordward
Remote Panel Genset Both

CAUSED : Generator Sets Cannot online


When PLN Blackout

ACTION : Module Need To Reset Alarm


By Manual Direct To Display Module Or
Use Woordward Interface Software

Location Building Genset BSSN

January Showing Alarm MAINTENANCE INTERVAL


3 2023 On deepsea Control Module On ATS
Panel

ACTION : Need To Reset With Deepsea


Configuration Suite Software Interface
Beetwen PC To Human Machine Interface

Location : Building Genset BSSN


Page 1

PT.ESA MASIV TEKNIK


General Contractor - Trading - Marine Automation
REPORT
Komplek Ruko Puriloka Blok D No 7 Baloi Kota
Batam Centre Batam Kepulauan Riau 29433
Phone : 0778 4163 290 Mobile : 0812 7659 7878Email : [email protected]

To : BSSN Date : January, 3 2023


Attn : Mr Dede Location : Building

DESCRIPTION DATE REMARKS

January Perform Connect Deepsea Configuration


3 2023 Suite To DSE 8620MKII
Erase Or Clear Fault Code On Module

Also Check All Parameter Generator Sets


On The DSE Suites Then Makesure All OK

January The Result Is No Alarm Again On Deepsea


3 2023 Module Or Clear Module

Then Genset Can online Again When


PLN Blackout
Page 2

PT.ESA MASIV TEKNIK


REPORT
General Contractor - Trading - Marine Automation
Komplek Ruko Puriloka Blok D No 7 Baloi Kota
Batam Centre Batam Kepulauan Riau 29433
Phone : 0778 4163 290 Mobile : 0812 7659 7878Email : [email protected]

To : BSSN Date : January, 3 2023


Attn : Mr Dede Location : Building

DESCRIPTION DATE REMARKS

January Perform Test Reset Diret To The Module


3 2023 Woordward easygen 2000

Then Clear Fault Code Or Make Module


back To Default Setting

Januari The Result Is No Alarm Or Faultcode


3 2023 Again On The Woordward Remote Panel

Then Generator Set Can Online Again


Or when PLN Blackout The Genset Can
Runn Normaly
Page 3