A09-D Vane Axial Fans

This document provides information on vane axial flow fans of the AXV-D series, including: - Direct driven and belt driven designs - Selection of fans based on required airflow and static pressure - Performance curves showing airflow and pressure for different fan sizes at various speeds - Dimensions and accessories also included The document contains technical details on fan construction, materials, and testing compliance. Selection examples and ordering information is given to specify fans for applications. Performance curves illustrate airflow vs pressure for fans from 500-2800mm diameter.

Uploaded by

Kim Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
317 views52 pages

A09-D Vane Axial Fans

This document provides information on vane axial flow fans of the AXV-D series, including: - Direct driven and belt driven designs - Selection of fans based on required airflow and static pressure - Performance curves showing airflow and pressure for different fan sizes at various speeds - Dimensions and accessories also included The document contains technical details on fan construction, materials, and testing compliance. Selection examples and ordering information is given to specify fans for applications. Performance curves illustrate airflow vs pressure for fans from 500-2800mm diameter.

Uploaded by

Kim Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Vane Axial Flow Fans

- Direct Driven
- Belt Driven

A09-D
#
Dongguan Wolter Chemco Ventilation Ltd. certifies
that the series AXV-D shown herein are licensed to
bear the AMCA Seal. The ratings shown are based
on tests and procedures performed in accordance
with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA
Certified Ratings Program.
Table of Content

Contents
Page 1

Fan Type Code


Page 2

Design Features
Page 2

Fan Selection
Page 3

Selection Sample
Page 3

AMCA FEG Rating


Page 4

Fan Performance Curves - 50Hz


Page 5~22

AMCA FEG Rating


Page 23

Fan Performance Curves - 60Hz


Page 24~41

Dimensions
Page 42~43

Accessories
Page 44

Sound Information
Page 45~47

Tubular sound attenuator for AXV-D


Page 48~49
Subject to change without prior notice.

A09-D V2015/July 1
Vane Axial Fans AXV-D
Technical information
Fan type code
AXV-D 800 / 20°
Pitch angle

AXV-D: impeller-Ø
500 ... 2800
Axial impeller blade type

Design features Belt driven design


Belt driven fan with single / dual motors can be mounted in various positions
Types and duty range to suit the actual site condition. Belt driven fans are used for applications
to extract more heavily polluted air i.e. presence of corrosive or hazardous
Wolter vane axial fans can be used for various applications in ventilation fumes, or dirt-laden, moist air or hot air from professional kitchens. Various
and process air technology. Standard diameters range from 500 to 2,800 mounting positions are illustrated.
mm, with airflow rates of up to 290 m³/s at static pressure increases of up
to 2,000 Pa. The high efficiencies and high pressures are achieved by the Ordering designations
use of the aerodynamically designed outlet guide vanes.
When ordering, please provide the following information:
Application > Fan type
The AXV-D range of vane axial fans is designed and tested to operate at > Fan code and type
standard temperatures as well as at elevated temperatures of 300°C for > Quantity required
60 (F300) and 120 minutes and 400°C for at least 120 minutes (F400),
according to DIN EN ISO 12101, part 3. The following fan curves are valid > Duty required at standard air and temperature (air volume in m³/h at static
for standard temperatures and 300°/60(120) minutes operation. To select a pressure in Pa).
fan for 400°C/120 minutes operation, please contact our technical support. > Motor power rating in kW
Well suited for industrial applications, ventilation and for conveying clean > Electrical supply
and dusty air where medium pressures are required with a high airflow
volume and fan efficiency. > Ancillaries required

Casing
Fan casings are made of steel, with flanges rolled on both sides. The pitch
circles of holes are in accordance with DIN 24 154, R2. The fan casings are
hot dipped galvanised as standard. Optional: Optimal corrosion protection
by powder-coating.
If motors require additional lubrication, tubes and grease-nipples are fitted
to the outside of the fan casing. An inspection hole, closed by a rubber plug,
allows controlling the direction of rotation.

Impellers
Hubs and impeller blades are made of highly corrosion resistant pressure-
cast aluminium alloy. The aero dynamical profile of the impeller blades
guarantees a high level of efficiency and low noise. The blade angle is
adjustable during standstill. The variable number of blades expands the
performance range. Dynamically balanced according to DIN ISO 1940-1,
balancing quality G6.3.

Motors Motor Mounting


Wolter uses closed squirrel cage motors according to IEC 34, if required at Zero Position
also in accordance with EPACT. Standard motors are class F with IP 55 0 deg
protection class. Multi speed versions with 2 or 3 speeds (Dahlander circuit
or separate windings) are also available, as well as explosion-proof versi-
ons or specific industrial executions such as marine-type fans. The motor 315 deg 45 deg
bearings have a L 10 life.

Fan performance curves


The performance curves for these fan types have been established in instal-
lation type - D (according to AMCA 210, ducted inlet and ducted outlet) and
represent the total pressure increase Δpt as a function of the volume flow. 270 deg 90 deg
The dynamic pressure pd2 refers to the outlet area of the fan.

Sound levels
The ascertaining of sound level follows the Reverberant Room Method
according to AMCA 300. The A-weighted inlet sound power levels LwiA is
shown on the performance curves.
225 deg 135 deg

180 deg
Motor Mounting Position - Specify in degree

2 A09-D V2015/July
AXV-D
!"
Selection example
Required duty point
> Volume flow: 12 m3/s
Performance
Curve
10
AXV-D1120-6,
AXV-D 1120, 50
50 Hz !"

�������������������
AXV-D 1120, 1440, 960, 720
4
30 36°
> Static pressure: 588 Pa

7.5
34°
3 32°

In order to calculate the total pressure, please add velocity pressure 20


30°

to static pressure (87 Pa dynamic pressure + 587 Pa static pressure


28°
2 5
26°

= 675 Pa total pressure) 22°


24°

> Fan speed: 1.440 1/min (4-pole)


10 20°
1 2.5 18°
16°
14° ������������3
Using the fan curve
12°
10°

250 1000

Total pressure pt [PA]


Having chosen a fan with adequate performance range for the required
duty point, plot volume flow and pressure. 400 p

At the point of intersection, the following data can be read: 200 800 j
q

> Motor speed or number of poles 1.440 1/min - 4-pole


r

300
> Pitch angle: 18 degrees
e k

150 600 s
f
> Absorbed power: 12,8 kW 36°
34°
> Sound Power Level: 111 dBA 200 a
m
32°
30°
100 400
b 28°
g n 26°
24°
22°
h 20°
c
100

st Setups
50 200 18°
16°
14°
12°
Lwi(A) a b c d e f g h j k m n p q r s
d
10° ��
4P 105 109 109 107 111 109 108 107 111 108 107 107 113 112 112 112 Speed

Pd
��
6P 93 98 98 96 100 98 96 96 100 97 96 96 102 100 100 100 [min-1]
��
8P 84 91 90 87 92 90 88 88 92 89 88 88 94 93 92 92
0 0 0
Calculation of motor power 0
1440 1/min
0
20000
5 10
40000
15
60000
20
80000
25
100000
30
1440
2880
2-pol
4-pol

There are two possibilities to calculate the motor power:


0 10000 20000 30000 40000 50000 60000 70000 1440
960
1) Calculation of absorbed power by using the fan curve in duty point: 960 1/min
0 5 10 15 20 4-pol
6-pol

12,8 kW

st Setups
0 10000 20000 30000 40000 50000 720
960
Motor power: 15 kW 720 1/min
0 2.5 5 7.5 10 12.5 15
.
8-pol
6-pol

������������ [m³/h]
2) Calculation according to peak absorbed power, see table below the [m³/s]

fan curve: 13 kW Peak absorbed power [kW] *Out of Range

n Pitch angle [°]

Motor power: 15 kW Nozzles


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 0,67 0,83 1,04 1,25 1,38 1,63 1,83 2,02 2,20 2,51 2,81 3,11 3,42 3,72 4,02 - -
motor 0,75 1,1 1,5 2,2 3 4
The given peak absorbed power is the maximum shaft absorbed power 960 1,60 1,96 2,45 2,95 3,28 3,86 4,33 4,78 5,26 5,94 6,65 7,37 8,09 8,82 9,54 - -

over the whole pitch angle curve in. motor 2,2 3 4 5,5 7,5 11
1440 5,40 6,62 8,28 9,97 11,0 13,0 14,6 16,2 17,8 20,0 22,4 24,9 27,3 29,7 32,2 - -
motor 5,5 7,5 11 15 18,5* 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance is for The A-weighted sound ratings shown have been calculated per AMCA International

t Fan Auxil
installation type D - Ducted inlet, Ducted outlet. Performance ratings do not Standard 301. Values shown are for inlet LwiA sound power levels for installation
include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

A09-D V2015/March 13

Nozzles

Test Setups
st Fan Auxil

Nozzles

Test Fan
Test Fan Auxilliary Fan
Settling
means

Settling
ISO 5801 Figure 73b means

AMCA 210 Figure 12 Settling


means

Outlet
ISO 5801chamber
Figure 73b
AMCA 210 Figure 12
ISO 5801 Figure 73b

ISO 5801 Figure 73b


A09-D V2015/July
AMCA
AMCA 210210 Figure
Figure 12 12 3
Outlet chamber
AMCA - FEG rating
Fan Efficiency Grade - AXV-D !"
Certified FEGs are determined in accordance with AMCA 205-12 Energy Efficiency Classification
for fans. In conjunction with AMCA 211-05 (Rev. 6/12) Certified Ratings Program, Product Rating
Manual for Fan Air Performance. This classification is based on fan peak (optimum) total efficiency
for a given fan speed, fan size and application category. For the purpose of energy classification,
the peak efficiency can be determined at a speed not higher than the maximum design speed of
the fan.

The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV-D 500 to AXV-D 2800 as shown in the table below.

Fan Fan Fan Fan Fan Fan


Fan Fan
Speed Outlet Area Efficiency Speed Outlet Area Efficiency
Model No. Model No.
(rpm) (m2) Grades (rpm) (m2) Grade
AXV-D 500 1440/960/720 0,1987 FEG71 AXV-D 1400 960/720/576 1,5504 FEG71
AXV-D 560 1440/960/720 0,2507 FEG71 AXV-D 1600 960/720/576 2,0232 FEG71
AXV-D 630 1440/960/720 0,3157 FEG71 AXV-D 1800 960/720/576 2,5588 FEG71
AXV-D 710 1440/960/720 0,3970 FEG71 AXV-D 2000 960/720/576 3,1573 FEG71
AXV-D 800 1440/960/720 0,4989 FEG71 AXV-D 2200 720/576/480 3,8186 FEG71
AXV-D 900 1440/960/720 0,6277 FEG71 AXV-D 2400 720/576/480 4,5428 FEG71
AXV-D 1000 1440/960/720 0,7901 FEG71 AXV-D 2500 720/576/480 4,9284 FEG71
AXV-D 1120 1440/960/720 0,9940 FEG71 AXV-D 2600 720/576/480 5,3297 FEG71
AXV-D 1250 1440/960/720 1,2272 FEG71 AXV-D 2800 720/576/480 6,1795 FEG71

90
FEG90

FEG85
80
FEG80

FEG75
Fan Peak Total Efficiency (%)

70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50

40

30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)

4 A09-D V2015/July
Notes:
[kW]
power (kw)

0.1
Performance
Curve
AXV-D 500, 1440, 960, 720, 50Hz
AXV-D 500, 50 Hz !" Hub: 150-7

0.75
AbsorbedPower

0.2 36°
34°
Absorbed

32°

0.5 30°
28°
0.05 26°

0.1 24°
22°
0.25 20°
16° 18°
12°
14° ρ = 1,2 kg/m3
10°

150
[PA]
∆pt(Pa)

Lwi(A) a b c d e f g h j k m n p q r s
80
Pressure

4P 95 95 95 95 100 100 101 101 94 93 93 95 93 93 93 93


6P 83 83 82 82 85 85 86 86 81 80 80 81 80 80 80 80
pressure

300 8P 74 74 73 72 75 74 75 75 71 71 70 72 71 72 72 72

70 125
Total
Total

250 p
60
100 q
j
50 200
e
k r
75
40 a
150 f
s

36°
30 m
34°
50
b
32°
100 g 30°
28°
20 n 26°
c 24°
25 22°
50 h
20°
10 18°
16°
14° Speed
d
Pd 10°
12° [min-1]

0 0 0
0 2000 4000 6000 8000 10000 1440
1440 1/min 4-pol
0 0.5 1 1.5 2 2.5 3

0 1000 2000 3000 4000 5000 6000 7000 960


960 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 6-pol

0 1000 2000 3000 4000 5000 720


720 1/min
0 0.25 0.5 0.75 1 1.25 1.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,025 0,029 0,034 0,038 0,043 0,046 0,052 0,060 0,068 0,074 0,080 0,086 0,092 0,097 0,103
motor 0,37
960 0,059 0,069 0,080 0,090 0,101 0,110 0,124 0,143 0,162 0,176 0,190 0,203 0,217 0,231 0,245
motor 0,37
1440 0,197 ,0,233 0,268 0,304 0,340 0,370 0,418 0,482 0,546 0,593 0,640 0,686 0,733 0,780 0,827
motor 0,37 0,55 0,75 1,1
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 5
AbsorbedPower [kW]
power(kw)

0.2
Performance
Curve
1.5
AXV-D 560, 1440, 960, 720, 50Hz
AXV-D 560, 50 Hz !" Hub: 169-7

0.4
0.15 36°
Absorbed

34°
0.3 1 32°
30°
0.1 28°
26°
0.2
24°
22°
0.5 20°
0.05 18°
0.1 14° 16°
12°
8° 10° ρ = 1,2 kg/m3
[PA]
∆p(Pa)

100 400 Lwi(A) a b c d e f g h j k m n p q r s


t

175 4P 99 99 99 98 104 104 105 105 98 97 97 99 97 97 97 97


Pressure

6P 86 87 86 85 89 89 90 90 85 84 84 85 84 84 84 84
pressure

8P 78 78 77 76 79 78 79 79 75 75 74 75 75 75 75 75
90
350
Total

150
Total

80 p

300
70 125 p
j
250
60 e
100 k
r

50 200 a
f
s
75
40 36°
150 m 34°
32°
b g
30 30°
50
28°
100 n 26°
20 c 24°
22°
h
25 20°
50 18°
10 16°
14° Speed
d 12° [min-1]
Pd 10°

0 0 0
0 2000 4000 6000 8000 10000 12000 14000 1440
1440 1/min 4-pol
0 0.5 1 1.5 2 2.5 3 3.5 4

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 960
960 1/min
0 0.5 1 1.5 2 2.5 6-pol

0 1000 2000 3000 4000 5000 6000 7000 720


720 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,044 0,052 0,060 0,068 0,076 0,083 0,093 0,108 0,122 0,132 0,143 0,153 0,164 0,174 0,185
motor 0,37
960 0,105 0,124 0,142 0,161 0,180 0,196 0,222 0,255 0,289 0,314 0,339 0,364 0,388 0,413 0,438
motor 0,37 0,55
1440 0,353 0,417 0,480 0,544 0,608 0,662 0,748 0,862 0,976 1,06 1,14 1,23 1,31 1,39 1,48
motor 0,37 0,55 0,75 1,1 1,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

6 A09-D V2015/July
(kw)
power [kW]
Performance
Curve
AXV-D 630, 1440, 960, 720, 50Hz
AXV-D 630, 50 Hz !" Hub: 189-7
0.75
Absorbed Power

0.3
36°
Absorbed

2 34°
32°
0.5 30°
0.2
28°
26°
24°
1 22°
0.1 0.25 20°
18°
14°
16° ρ = 1,2 kg/m3
12°
10°

∆pt (Pa)
[PA]

Lwi(A) a b c d e f g h j k m n p q r s
Pressure

125 500 4P 102 103 102 102 108 108 109 109 102 101 101 103 101 101 101 101
6P 90 90 90 89 93 93 94 94 89 88 88 89 88 88 88 88
pressure

8P 81 82 80 80 83 82 83 83 79 78 78 79 79 79 79 79
200
Total
Total

100 400 p

q
150 j

75 300 e

k r

a
f
100 s

50 200 36°
m 34°
b 32°
g 30°
28°
n
50 26°
25 100 c 24°
22°
h
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]

0 0 0
2500 5000 7500 10000 12500 15000 17500 20000 1440
1440 1/min
1 2 3 4 5 6 4-pol

2000 4000 6000 8000 10000 12000 14000 960


960 1/min
0.5 1 1.5 2 2.5 3 3.5 4 6-pol

2000 4000 6000 8000 10000 720


720 1/min
0.5 1 1.5 2 2.5 3 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,079 0,093 0,107 0,121 0,135 0,147 0,166 0,192 0,217 0,236 0,254 0,273 0,292 0,310 0,329
motor 0,37
960 0,186 0,220 0,253 0,287 0,321 0,349 0,394 0,455 0,515 0,559 0,603 0,647 0,691 0,736 0,780
motor 0,37 0,55 0,75 1,1
1440 0,629 0,743 0,854 0,968 1,08 1,18 1,33 1,53 1,74 1,89 2,03 2,18 2,33 2,48 2,63
motor 0,75 1,1 1,5 2,2 3
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 7
[kW]
power(kw)
AbsorbedPower

0.6
Performance
Curve
AXV-D 710, 1440, 960, 720, 50Hz
AXV-D 710, 50 Hz !" Hub: 212-7

4
36°
34°
Absorbed

1
0.4 32°
30°
28°
26°
2 24°
0.5 22°
0.2
20°
16° 18°
14°
10°
12° ρ = 1,2 kg/m3

[PA]

300
∆p(Pa)

Lwi(A) a b c d e f g h j k m n p q r s
t

4P 106 107 106 106 112 112 113 113 106 105 105 107 105 105 105 104
Pressure

6P 93 94 93 93 97 97 98 98 93 92 92 93 92 92 92 92
pressure

150 600 8P 85 85 84 84 87 86 87 87 83 82 82 83 83 83 83 83

250
Total
Total

p
125 500

200 q
j
100 400
e

k r
150
a
75 300 f
s

36°
m 34°
100
32°
50 200 b g 30°
28°
n
26°
c 24°
50 22°
25 100 h
20°
18°
14°
16° Speed
d 12° [min-1]
Pd 10°

0 0 0
0 5000 10000 15000 20000 25000 30000 1440
1440 1/min 4-pol
0 1 2 3 4 5 6 7 8

0 2500 5000 7500 10000 12500 15000 17500 20000 960


960 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6-pol

0 2000 4000 6000 8000 10000 12000 14000 720


720 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,139 0,165 0,189 0,215 0,240 0,261 0,295 0,340 0,385 0,418 0,451 0,484 0,517 0,550 0,583
motor 0,37 0,55 0,75
960 0,330 0,390 0,449 0,509 0,568 0,619 0,699 0,806 0,913 0,991 1,07 1,15 1,22 1,30 1,38
motor 0,37 0,55 0,75 1,1 1,5
1440 1,11 1,32 1,51 1,72 1,92 2,09 2,36 2,72 3,08 3,34 3,61 3,87 4,14 4,40 4,66
motor 1,5 2,2 3 4 5,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

8 A09-D V2015/July
[kW]
power(kw)
Performance
Curve
6 AXV-D 800, 1440, 960, 720, 50Hz
AXV-D 800, 50 Hz !" Hub: 250-6

36°
AbsorbedPower

1.5
0.6 34°
Absorbed

32°
4
30°
1 28°
0.4
26°
24°
2 22°
0.5 20°
0.2 18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆p(Pa)
t

200 p
Pressure
pressure

q
100 400 j
Total
Total

150 e k

75 300 f
s

36°
34°
a 32°
100 m
30°
50 200 b 28°
g n 26°
24°
22°
h
c 20°
50
25 100 18°
16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°

4P 96 99 98 97 101 99 97 97 100 97 97 96 103 101 101 101 Speed
Pd
6P 83 88 87 85 90 88 86 85 89 86 86 85 91 90 90 90 [min-1]
8P 74 80 80 77 82 80 78 77 82 79 78 78 84 82 82 82
0 0 0
0 5000 10000 15000 20000 25000 30000 35000 40000 1440
1440 1/min 4-pol
0 1 2 3 4 5 6 7 8 9 10 11

0 2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 960
960 1/min
0 1 2 3 4 5 6 7 6-pol

0 2500 5000 7500 10000 12500 15000 17500 20000 720


720 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,120 0,153 0,198 0,243 0,254 0,289 0,324 0,359 0,394 0,445 0,498 0,552 0,605 0,659 0,713
motor 0,37 0,55 0,75
960 0,284 0,363 0,469 0,575 0,601 0,684 0,767 0,850 0,933 1,05 1,18 1,31 1,43 1,56 1,69
motor 0,37 0,55 0,75 1,1 1,5 2,2
1440 0,957 1,23 1,58 1,94 2,03 2,31 2,59 2,87 3,15 3,56 3,98 4,41 4,84 5,27 5,71
motor 1,1 1,5 2,2 3 4 5,5 7,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 9
[kW]
power (kw)
Performance
Curve
AXV-D 900, 1440, 960, 720, 50Hz
AXV-D 900, 50 Hz !" Hub: 281-6
3 10
AbsorbedPower

36°
34°
1
Absorbed

32°
2 30°
28°
5 26°

0.5 24°
22°
1 20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

p
250
Pressure

q
pressure

125 500 j

r
Total
Total

200

e k
100 400
s
f

150 36°
34°
75 300 a
m
32°
30°
b
28°
100 g n 26°
50 200 24°
22°
h
c 20°
18°
50 16°
25 100 14°
d
12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 99 103 102 100 105 102 101 100 104 101 101 100 107 105 105 105 Speed
Pd 6P 86 92 91 89 93 91 89 89 93 90 89 89 95 94 94 94 [min-1]
8P 78 84 83 81 86 84 81 81 85 82 82 81 87 86 86 86
0 0 0
10000 20000 30000 40000 50000 1440
1440 1/min
2 4 6 8 10 12 14 4-pol

2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 960
960 1/min
1 2 3 4 5 6 7 8 9 10 6-pol

2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 27500 720
720 1/min
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,212 0,272 0,352 0,431 0,450 0,512 0,575 0,637 0,699 0,790 0,884 0,980 1,07 1,17 1,27
motor 0,37 0,55 0,75 1,1 1,5
960 0,504 0,645 0,833 1,02 1,07 1,21 1,36 1,51 1,66 ,187 2,09 2,32 2,55 2,78 3,00
motor 0,55 0,75 1,1 1,5 2,2 3
1440 1,70 2,18 2,81 2,45 3,60 4,10 4,60 5,09 5,59 6,32 7,07 7,84 8,60 9,37 10,1
motor 2,2 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

10 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 1000, 1440, 960, 720, 50Hz
AXV-D 1000, 50 Hz !" Hub: 315-6

36°
AbsorbedPower

2
15 34°
4 32°
Absorbed

1.5 30°

10 28°
26°
1
2 24°
22°
20°
5 18°
0.5 16°
14°
10°
12° ρ = 1,2 kg/m3

p
[PA]
∆pt(Pa)

175 700
300
Pressure

q
pressure

j
150 600
r
Total
Total

250
e k
125 500
s
f
200
36°
100 400 34°
a 32°
m
150 30°
b
75 300 28°
g n 26°
24°
100 22°
50 200 h 20°
c
18°
16°
50 14°
25 100 12°
d 10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 102 106 105 104 108 106 105 104 108 105 104 104 110 108 108 109 Speed
Pd 6P 90 95 94 92 97 95 93 93 97 94 93 93 99 97 97 97 [min-1]
8P 81 87 87 84 89 87 85 85 89 86 85 85 91 89 89 89
0 0 0
10000 20000 30000 40000 50000 60000 70000 80000 1440
1440 1/min 4-pol
2.5 5 7.5 10 12.5 15 17.5 20

5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 960
960 1/min
2 4 6 8 10 12 14 6-pol

5000 10000 15000 20000 25000 30000 35000 40000 720


720 1/min
1 2 3 4 5 6 7 8 9 10 11 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,378 0,484 0,625 0,766 0,800 0,911 1,02 1,13 1,24 1,40 1,57 1,74 1,91 2,08 2,25
motor 0,55 0,75 1,1 1,5 2,2 3
960 0,895 1,15 1,48 1,82 1,90 2,16 2,42 2,68 2,94 3,33 3,72 4,13 4,53 4,93 5,34
motor 1,1 1,5 2,2 3 4 5,5
1440 3,02 3,87 5,00 6,13 6,40 7,29 8,17 9,06 9,94 11,2 12,6 13,9 15,3 16,7 18,0
motor 4 5,5 7,5 11 15 18,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 11
[kW]
power (kw)

4
Performance
Curve
10 AXV-D 1120, 1440, 960, 720, 50Hz
AXV-D 1120, 50 Hz !" Hub: 353-6

30
AbsorbedPower

36°
34°
7.5
3
Absorbed

32°
30°
20
28°
2 5
26°
24°
22°
10 20°
1 2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

400 p
Pressure
pressure

q
200 800 j

r
Total
Total

300
e k

150 600 s
f

36°
34°
a 32°
200 m
30°
100 400 b 28°
g n 26°
24°
22°
h
c 20°
100
50 200 18°
16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 106 110 109 108 112 109 108 108 111 108 108 107 114 112 112 112 Speed
Pd 6P 93 99 98 96 101 98 97 96 100 97 97 96 102 101 101 101 [min-1]
8P 85 91 90 88 93 91 89 88 93 90 89 88 94 93 93 93
0 0 0
20000 40000 60000 80000 100000 1440
1440 1/min 4-pol
5 10 15 20 25 30

10000 20000 30000 40000 50000 60000 70000 960


960 1/min 6-pol
2 4 6 8 10 12 14 16 18 20

5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 720
720 1/min
2 4 6 8 10 12 14 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,670 0,858 1,11 1,36 1,42 1,62 1,81 2,01 2,20 2,49 2,79 3,09 3,39 3,69 4,00
motor 0,75 1,1 1,5 2,2 3 4
960 1,59 2,03 2,63 3,22 3,37 3,83 4,30 4,76 5,23 5,90 6,61 7,32 8,04 8,76 9,47
motor 2,2 3 4 5,5 7,5 11
1440 5,36 6,87 8,87 10,9 11,4 12,9 14,5 16,1 17,6 19,9 22,3 24,7 27,1 29,6 32,0
motor 5,5 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

12 A09-D V2015/July
[kW]
power(kw)
Performance
Curve
60 AXV-D 1250, 1440, 960, 720, 50Hz
AXV-D 1250, 50 Hz !" Hub: 420-6

36°
AbsorbedPower

15
6 34°
32°
Absorbed

40 30°
10 28°
4
26°
24°
22°
20
20°
2 5
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

Pressure t
[PA]
∆p(Pa)

300 1200
pressure

p
500
Total

j q
Total

250 1000
r
k
e
400

200 800
f
s
36°
300
a 34°
150 600 m 32°
b 30°
28°
g
200 n 26°
100 400 24°
22°
h
20°
c 18°
16°
100
50 200 14°
d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 4P 111 110 108 108 114 111 109 110 110 111 111 111 116 115 116 116 Speed
Pd 6P 100 100 99 98 103 100 98 99 99 101 100 100 105 105 105 106 [min-1]
8P 93 93 92 92 95 93 90 91 91 93 92 93 97 97 98 98
0 0 0
20000 40000 60000 80000 100000 120000 140000 1440
1440 1/min 4-pol
5 10 15 20 25 30 35 40

10000 20000 30000 40000 50000 60000 70000 80000 90000 100000 960
960 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 6-pol

10000 20000 30000 40000 50000 60000 70000 720


720 1/min
2.5 5 7.5 10 12.5 15 17.5 20 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 1,31 1,61 2,04 2,48 2,51 2,83 3,23 3,64 4,06 4,56 5,10 5,62 6,16 6,67 7,22
motor 1,5 2,2 3 4 5,5 7,5
960 3,10 3,81 4,85 5,88 5,94 6,71 7,66 8,63 9,61 10,8 12,1 13,3 14,6 15,8 17,1
motor 4 5,5 7,5 11 15 18,5
1440 10,5 12,9 16,4 19,9 20,1 22,7 25,9 29,1 32,4 36,5 40,8 44,9 49,3 53,4 57,7
motor 11 15 18,5 22 30 37 45 55 75
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 13
[kW]
power (kw)
Performance
Curve
30
AXV-D 1400, 960, 720, 576, 50Hz
AXV-D 1400, 50 Hz !" Hub: 472-6

6
AbsorbedPower

36°
34°
10 32°
Absorbed

20 30°
4 28°
26°
24°
5 22°
2 10 20°
18°
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

400
250 700
Pressure

p
pressure

350
600 j q
Total
Total

200
r
300 k
e
500

250
f
150 s
400 36°
200 a 34°
m 32°

300 b 30°
100 28°
150 g
n 26°
24°
200 22°
h
100 20°
c 18°
50 16°
14°
100 12°
50 d
10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 104 104 102 102 107 104 102 102 103 105 103 104 109 109 110 110 Speed
Pd 8P 96 96 95 95 99 96 94 95 94 97 96 96 101 101 101 102 [min-1]
10P 90 91 90 90 93 90 88 89 88 91 90 90 95 95 95 96
0 0 0
20000 40000 60000 80000 100000 120000 140000 960
1440
960 1/min
5 10 15 20 25 30 35 40 4-pol
6-pol

20000 40000 60000 80000 100000 720


960
720 1/min
5 10 15 20 25 30 6-pol
8-pol

10000 20000 30000 40000 50000 60000 70000 80000 90000 576
720
576 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 1,21 1,48 1,88 2,29 2,31 2,61 2,98 3,36 3,74 4,20 4,68 5,18 5,68 6,15 6,65
motor 2,2 3 4 5,5 7,5
720 2,35 2,89 3,68 4,47 4,51 5,09 5,82 6,55 7,30 8,20 9,14 10,1 11,0 12,0 13,0
motor 3 4 5,5 7,5 11 15
960 5,58 6,86 8,73 10,6 10,7 12,1 13,8 15,5 17,3 19,4 21,7 24,0 26,3 28,5 30,8
motor 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

14 A09-D V2015/July
[kW]
power (kw)
AbsorbedPower
Performance
Curve
60
AXV-D 1600, 960, 720, 576, 50Hz
AXV-D 1600, 50 Hz !" Hub: 539-6

36°
34°
10 20
Absorbed

32°
40 30°
28°
26°

10 24°
5 22°
20 20°
18°
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)
Pressure

500
pressure

300 p

800
j q
Total
Total

400 r
250 k
e

600
200 f
s
300
36°
a 34°
m 32°
150
400 b 30°
200 28°
g
n 26°
24°
100 22°
h 20°
200 c 18°
100 16°
50 14°
d 12°
10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 108 108 106 106 111 108 106 107 107 109 108 108 113 113 114 114 Speed
Pd 8P 100 101 99 99 103 100 98 99 99 101 100 100 105 105 105 106 [min-1]
10P 94 95 94 94 97 94 92 93 92 95 94 94 99 99 99 100
0 0 0
25000 50000 75000 100000 125000 150000 175000 200000 960
225000 1440
960 1/min
10 20 30 40 50 60 4-pol
6-pol

25000 50000 75000 100000 125000 150000 720


960
720 1/min
5 10 15 20 25 30 35 40 45 6-pol
8-pol

25000 50000 75000 100000 125000 576


720
576 1/min
5 10 15 20 25 30 35 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 2,34 2,87 3,65 4,44 4,48 5,06 5,78 6,51 7,25 8,14 9,08 10,0 11,0 11,9 12,9
motor 3 4 5,5 7,5 11 15
720 4,57 5,61 7,14 8,66 8,75 9,88 11,3 12,7 14,2 15,9 17,7 19,6 21,5 23,3 25,2
motor 5,5 7,5 11 15 18,5 22 30
960 10,8 13,3 16,9 20,5 20,7 23,4 26,7 30,1 33,5 37,7 42,0 46,5 51,0 55,2 59,7
motor 11 15 18,5 22 30 37 45 55 75
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 15
[kW]
power (kw)
Performance
Curve
AXV-D 1800, 960, 720, 576, 50Hz
AXV-D 1800, 50 Hz !" Hub: 606-6
100
36°
AbsorbedPower

20 40
34°
32°
Absorbed

30°
28°
26°
20 50
10 24°
22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

1200
[PA]
∆pt(Pa)
Pressure

400
pressure

600 p

1000 j q
Total

350
Total

500 r
k
e
300
800

250 400 f s

36°
600 a 34°
200 m 32°
300
b 30°
28°
g
n 26°
150 400
24°
200 22°
h 20°
100
c 18°
16°
200 14°
100
d 12°
50 10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 111 111 110 110 114 111 109 110 110 112 112 112 117 117 117 118 Speed
Pd 8P 104 104 103 103 107 104 102 102 102 105 104 104 109 109 109 110 [min-1]
10P 98 98 98 97 100 98 95 96 96 99 98 98 102 102 103 103
0 0 0
50000 100000 150000 200000 250000 300000 960
1440
960 1/min 4-pol
6-pol
10 20 30 40 50 60 70 80

25000 50000 75000 100000 125000 150000 175000 200000 225000 720
960
720 1/min
10 20 30 40 50 60 6-pol
8-pol

25000 50000 75000 100000 125000 150000 175000 576


720
576 1/min
5 10 15 20 25 30 35 40 45 50 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 4,21 5,17 6,58 7,98 8,06 9,10 10,4 11,7 13,0 14,6 16,3 18,1 19,8 21,4 23,2
motor 5,5 7,5 11 15 18,5 22 30
720 8,21 10,1 12,8 15,6 15,7 17,8 20,3 22,9 25,5 28,6 31,9 35,3 38,7 41,9 45,3
motor 11 15 18,5 22 30 37 45 55
960 19,5 23,9 30,4 26,9 37,3 42,1 48,1 54,2 60,4 67,8 75,6 83,6 91,7 99,3 107,4
motor 22 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

16 A09-D V2015/July
[kW]
power (kw)

40
Performance
Curve
75
AXV-D 2000, 50 Hz
AXV-D 2000, 960, 720, 576, 50Hz
!" Hub: 674-6

36°
AbsorbedPower

150 34°
30 32°
Absorbed

50 30°
28°
100
20 26°
24°
22°
25 20°
10 50 18°
16°
14° ρ = 1,2 kg/m3
12°
10°

1500
[PA]
∆pt(Pa)

800
500
Pressure
pressure

700 1250
j q
Total
Total

400 r
600 e k

1000

500 f
s
300
36°
750 a 34°
400 m 32°
b 30°
200 g 28°
300 n
26°
500
24°
22°
h
200 20°
c 18°
100 16°
250 14°
100 d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 6P 115 115 113 113 118 115 112 113 114 116 115 115 120 120 121 121 Speed
Pd 8P 107 107 106 106 110 107 105 106 106 108 107 107 112 112 112 113 [min-1]
10P 101 101 101 101 104 101 99 100 99 102 101 101 106 106 106 107
0 0 0
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5 960
1440
960 1/min 4-pol
6-pol
20 40 60 80 100 120

4 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 720
960
720 1/min 6-pol
10 20 30 40 50 60 70 80 90 8-pol

2.5x104 5.0x104 7.5x10


4
1.0x10
5
1.3x10
5
1.5x10
5
1.8x10
5
2.0x10
5
2.3x10
5
2.5x10
5
576
720
576 1/min
10 20 30 40 50 60 70 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 7,11 8,74 11,1 13,5 13,6 15,4 17,6 19,8 22,0 24,8 27,6 30,6 33,5 36,3 39,2
motor 7,5 11 15 18,5 22 30 37 45
720 13,9 17,1 21,7 26,4 26,6 30,0 34,3 38,7 43,1 48,4 53,9 59,7 65,4 70,9 76,6
motor 15 18,5 22 30 37 45 55 75 90
960 32,9 40,5 51,5 62,5 63,1 71,3 81,4 91,6 102,1 114,7 127,8 141,5 155,1 167,9 181,7
motor 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 17
Absorbed Power [kW]
power (kw)
Performance
Curve
AXV-D 2200, 720, 576, 480, 50Hz
AXV-D 2200, 50 Hz !" Hub: 741-6

36°
30 100 34°
50
32°
Absorbed

30°
28°
20
26°

50 24°
25 22°
20°
10 18°
16°
14°
12° ρ = 1,2 kg/m3
10°

1000
∆pt (Pa)
[PA]

600
Pressure

400 p
pressure

j q
Total

350 800
500
Total

r
e k

300
400
600 f s
250
36°
a 34°
300 m 32°
200
b 30°
400 28°
g
n 26°
150
200 24°
22°
h
20°
100 c 18°
200 16°
100 14°
d 12°
50 10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 110 110 109 109 113 110 108 109 108 111 110 110 115 115 115 116 Speed
Pd 10P 104 104 104 104 106 104 102 102 102 105 104 104 109 109 109 110 [min-1]
12P 99 100 99 99 101 99 97 98 97 100 99 99 104 104 104 105
0 0 0
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5 720
1440
720 1/min 4-pol
20 40 60 80 100 120 8-pol

4 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 576
960
576 1/min
10 20 30 40 50 60 70 80 90 6-pol
10-pol

5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
480
720
480 1/min
10 20 30 40 50 60 70 80 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 6,62 8,14 10,3 12,6 12,7 14,3 16,4 18,4 20,5 23,1 25,7 28,4 31,2 33,8 36,5
motor 7,5 11 15 18,5 22 30 37
576 11,4 14,1 17,9 21,7 21,9 24,8 28,3 31,9 35,5 39,9 44,4 49,2 53,9 58,4 63,1
motor 15 18,5 22 30 37 45 55 75
720 22,4 27,5 34,9 42,4 42,8 48,4 55,2 62,2 69,3 77,9 86,8 96,0 105,3 114,0 123,3
motor 30 37 45 55 75 90 110 132
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

18 A09-D V2015/July
AbsorbedPower [kW]
power(kw)
Performance
Curve
100 200 AXV-D 2400, 720, 576, 480, 50Hz
AXV-D 2400, 50 Hz !" Hub: 808-6

36°
34°
32°
Absorbed

40
30°
28°
50 100 26°
24°
20 22°
20°
18°
16°
14° ρ = 1,2 kg/m3
12°
10°

1200
[PA]
∆p(Pa)
t

500
Pressure

700
pressure

1000 j q
Total
Total

600
400 r
e k

800
500
f
s
300
36°
400
600 a 34°
m 32°
b 30°
300 28°
200 g
n 26°
400
24 °
22°
200 h
20°
c 18°
100 16°
200 14°
100 d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 113 113 112 112 115 113 110 111 111 113 113 113 118 117 118 118 Speed
Pd 10P 107 107 106 106 109 107 104 105 105 108 106 107 111 111 112 112 [min-1]
12P 102 102 102 102 104 102 99 100 100 103 101 102 106 106 107 107
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140

5.0x10
4
1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 576
960
576 1/min 6-pol
20 40 60 80 100 120 10-pol

5.0x104 1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 720


480
480 1/min
10 20 30 40 50 60 70 80 90 100 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 10,2 12,6 16,0 19,4 19,6 22,1 25,3 28,4 31,7 35,6 39,7 43,9 48,1 52,1 56,4
motor 11 15 18,5 22 30 37 45 55 75
576 17,7 21,7 27,6 33,5 33,8 38,2 43,6 49,2 54,7 61,5 68,5 75,9 83,2 90,0 97,4
motor 18,5 22 30 37 45 55 75 90 110
720 34,5 42,4 53,9 65,4 66,1 74,6 85,2 96,0 106,9 120,2 133,9 148,2 162,4 175,9 190,3
motor 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 19
[kW]
power (kw)
Performance
Curve
AXV-D 2500, 720, 576, 480, 50Hz
AXV-D 2500, 50 Hz !" Hub: 842-6

36°
Absorbed Power

60 200
100 34°
32°
Absorbed

30°

40 28°
26°

50 100 24°
22°
20°
20
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

800
Pressure

1200
pressure

p
500
700 j q
Total
Total

1000
r
600 e k
400

800
500 f
s

36°
300
a 34°
400
600 m 32°
b 30°
28°
g
300 n 26°
200
400 24°
22°
h 20°
200
c 18°
16°
100
200 14°
100 d
12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 114 114 113 113 117 114 112 113 112 115 114 114 119 119 119 120 Speed
Pd 10P 108 108 108 107 110 108 105 106 106 109 108 108 113 112 113 113 [min-1]
12P 103 103 103 103 105 103 100 101 101 104 103 103 108 108 108 108
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140

5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
4.5x10
5
5.0x10
5
576
960
576 1/min 6-pol
20 40 60 80 100 120 140 10-pol

5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
480
720
480 1/min
10 20 30 40 50 60 70 80 90 100 110 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 12,5 15,4 19,6 23,8 24,0 27,1 31,0 34,9 38,8 43,7 48,6 53,8 59,0 63,9 69,1
motor 15 18,5 22 30 37 45 55 75
576 21,7 26,6 33,8 41,1 41,5 46,9 53,5 60,3 67,1 75,4 84,0 93,0 102,0 110,4 119,5
motor 22 30 37 45 55 75 90 110 132
720 42,3 52,0 66,1 80,2 81,0 91,5 104,5 117,7 131,1 147,3 164,2 181,7 199,2 215,7 233,3
motor 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

20 A09-D V2015/July
AbsorbedPower [kW]
power(kw)
Performance
Curve
150 300 AXV-D 2600, 720, 576, 480, 50Hz
AXV-D 2600, 50 Hz !" Hub: 875-6

75 36°
34°
32°
Absorbed

100 200
30°
50 28°
26°
24°
100 22°
50
25 20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

1400
[PA]
∆p(Pa)

600
t
Pressure
pressure

800 p
1200
j q
Total

500
Total

700
r
k
1000 e

600
400
f s
500 800
36°
a 34°
300 m 32°
400
600 b 30°
g 28°
n 26°
200 300
24°
400 22°
h
20°
200 c 18°
16°
100 14°
200 12°
d
100 10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 115 115 114 114 118 115 113 114 114 116 115 115 120 120 120 121 Speed
Pd 10P 109 109 109 109 112 109 107 108 107 110 109 109 114 114 114 115 [min-1]
12P 104 105 104 104 106 104 102 103 102 105 104 104 109 109 109 110
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180 200

5.0x104 1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 4.5x105 5.0x105 5.5x105 576
960
576 1/min 6-pol
20 40 60 80 100 120 140 160 10-pol

5.0x104 1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 4.5x105 720
480
480 1/min
20 40 60 80 100 120 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 15,2 18,7 23,8 28,9 29,2 33,0 37,7 42,4 47,2 53,1 59,1 65,5 71,8 77,7 84,1
motor 18,5 22 30 37 45 55 75 90
576 26,3 32,4 41,2 50,0 50,4 57,0 65,1 73,3 81,6 91,7 102,2 113,1 124,0 134,3 145,3
motor 30 37 45 55 75 90 110 132 160
720 51,4 63,2 80,4 97,6 98,5 111,3 127,1 143,1 159,4 179,2 199,6 220,9 242,2 262,3 283,7
motor 55 75 90 110 132 160 200 250 315
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 21
[kW]
power (kw)

125
Performance
Curve
AXV-D 2800, 720, 576, 480, 50Hz
AXV-D 2800, 50 Hz !" Hub: 942-6

200 400
Absorbed Power

36°
100 34°
Absorbed

300 32°
150
30°
75
28°

200 26°
100
50 24°
22°
20°
50 100 18°
25 16°
14° ρ = 1,2 kg/m3
12°
10°

700
∆pt (Pa)
[PA]

1000
1500
Pressure

p
pressure

600 j q
Total

800 1250
Total

e k
500

1000
f
600 s
400 36°
a 34°
750 m 32°

300 b 30°
400 g
28°
n 26°
500 24°
200 22°
h
20°
c 18°
200 16°
250 14°
100 d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 117 118 116 116 120 117 115 116 116 118 117 118 122 122 122 123 Speed
Pd 10P 111 112 111 111 114 111 109 110 110 112 111 111 116 116 116 117 [min-1]
12P 106 107 107 106 109 106 104 105 105 107 106 106 111 111 111 112
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10 6.0x10
5 5
7.0x10
5
8.0x10
5 5 720
9.0x10 1440
720 1/min 4-pol
25 50 75 100 125 150 175 200 225 250 8-pol

5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 576
960
576 1/min
25 50 75 100 125 150 175 6-pol
200 10-pol

1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 5
6.0x10 480
720
480 1/min
25 50 75 100 125 150 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 22,0 27,1 34,5 41,8 42,3 47,7 54,5 61,4 68,4 76,8 85,6 94,8 103,9 112,5 121,7
motor 22 30 37 45 55 75 90 110 132
576 38,1 46,9 59,6 72,3 73,0 82,5 94,2 106,1 118,1 132,8 148,0 163,8 179,5 194,4 210,3
motor 45 55 75 90 110 132 160 200 250
720 74,4 91,5 116,4 141,2 142,6 161,1 184,0 207,2 230,8 259,4 289,0 319,8 350,6 379,7 *410,7
motor 75 110 132 160 200 250 315 355 400 -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

22 A09-D V2015/July
AMCA - FEG rating
Fan Efficiency Grade - AXV-D !"
Certified FEGs are determined in accordance with AMCA 205-12 Energy Efficiency Classification
for fans. In conjunction with AMCA 211-05 (Rev. 6/12) Certified Ratings Program, Product Rating
Manual for Fan Air Performance. This classification is based on fan peak (optimum) total efficiency
for a given fan speed, fan size and application category. For the purpose of energy classification,
the peak efficiency can be determined at a speed not higher than the maximum design speed of
the fan.

The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV-D 500 to AXV-D 2800 as shown in the table below.

Fan Fan Fan Fan Fan Fan


Fan Fan
Speed Outlet Area Efficiency Speed Outlet Area Efficiency
Model No. Model No.
(rpm) (m2) Grades (rpm) (m2) Grade
AXV-D 500 1728/1152/864 0,1987 FEG71 AXV-D 1400 1152/864/691 1,5504 FEG71
AXV-D 560 1728/1152/864 0,2507 FEG71 AXV-D 1600 1152/864/691 2,0232 FEG71
AXV-D 630 1728/1152/864 0,3157 FEG71 AXV-D 1800 1152/864/691 2,5588 FEG71
AXV-D 710 1728/1152/864 0,3970 FEG71 AXV-D 2000 1152/864/691 3,1573 FEG71
AXV-D 800 1728/1152/864 0,4989 FEG71 AXV-D 2200 864/691/576 3,8186 FEG71
AXV-D 900 1728/1152/864 0,6277 FEG71 AXV-D 2400 864/691/576 4,5428 FEG71
AXV-D 1000 1728/1152/864 0,7901 FEG71 AXV-D 2500 864/691/576 4,9284 FEG71
AXV-D 1120 1728/1152/864 0,9940 FEG71 AXV-D 2600 864/691/576 5,3297 FEG71
AXV-D 1250 1728/1152/864 1,2272 FEG71 AXV-D 2800 864/691/576 6,1795 FEG71

90
FEG90

FEG85
80
FEG80

FEG75
Fan Peak Total Efficiency (%)

70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50

40

30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)

A09-D V2015/July 23
Notes:
[kW]
power (kw)
Performance
Curve
1.5 AXV-D 500, 1728, 1152, 864, 60Hz
AXV-D 500, 60 Hz !" Hub: 150-7
0.4
AbsorbedPower

0.15 36°
Absorbed

34°
0.3 1 32°
30°
0.1 28°
26°
0.2
24°
22°
0.5
20°
0.05
0.1 18°
14°
16° ρ = 1,2 kg/m3
12°
10°

125 500
[PA]
∆pt(Pa)

Lwi(A) a b c d e f g h j k m n p q r s
102 101 101 101 107 107 108 108 101 100 101 102 99 99 99 99
Pressure

4P
200 6P 88 88 88 87 92 92 93 92 87 86 86 87 86 86 86 86
pressure

8P 80 79 78 78 81 81 82 82 77 76 76 78 77 77 77 77
Total

100 400
Total

150
q
75 300 j

e
k r

100 a
f
50 200 s
36°
m 34°
b 32°
g 30°
28°
50 n
26°
25 100 c 24°
22°
h
20°
18°
14°
16° Speed
d 12° [min-1]
Pd 10°

0 0 0
0 2000 4000 6000 8000 10000 12000 1728
1728 1/min 4-pol
0 0.5 1 1.5 2 2.5 3 3.5

0 1000 2000 3000 4000 5000 6000 7000 8000 1152


1152 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 6-pol

0 1000 2000 3000 4000 5000 6000 864


864 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,043 0,050 0,058 0,066 0,073 0,080 0,090 0,104 0,118 0,128 0,138 0,148 0,158 0,168 0,179
motor 0,37
1152 0,101 0,120 0,137 0,156 0,174 0,190 0,214 0,247 0,280 0,304 0,327 0,351 0,375 0,399 0,423
motor 0,37 0,55
1728 0,341 0,403 0,464 0,526 0,588 0,640 0,723 0,833 0,944 1,02 1,10 1,19 1,27 1,35 1,43
motor 0,37 0,55 0,75 1,1 1,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

24 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 560, 1728, 1152, 864, 60Hz
AXV-D 560, 60 Hz !" Hub: 169-7
0.75
AbsorbedPower

0.3

36°
2
Absorbed

34°
32°
0.5
0.2 30°
28°
26°
24°
1 22°
0.1 0.25 20°
16° 18°
12° 14°
8° 10° ρ = 1,2 kg/m3
[PA]
∆pt(Pa)

150 600 Lwi(A) a b c d e f g h j k m n p q r s


Pressure

4P 105 105 105 105 111 111 112 112 105 104 105 106 103 103 103 103
250 6P 92 92 91 91 96 96 97 97 91 90 90 91 90 90 90 90
pressure

8P 83 83 82 82 85 85 86 86 81 80 80 82 81 81 81 81
Total

125 500
Total

p
200

p
100 400
j

e
150
k r
75 300
a
f
s

100 36°
m
34°
50 200
b 32°
g 30°
28°
n
26°
50 c 24°
25 100 h
22°
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]

0 0 0
0 2500 5000 7500 10000 12500 15000 17500 1728
1728 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 4-pol

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 1152
1152 1/min
0 0.5 1 1.5 2 2.5 3 3.5 6-pol

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 864
864 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,076 0,090 0,104 0,118 0,131 0,143 0,162 0,186 0,211 0,229 0,247 0,265 0,283 0,301 0,319
motor 0,37
1152 0,181 0,214 0,246 0,279 0,311 0,339 0,383 0,441 0,500 0,543 0,586 0,628 0,671 0,714 0,757
motor 0,37 0,55 0,75 1,1
1728 0,610 0,721 0,829 0,940 1,05 1,14 1,29 1,49 1,69 1,83 1,98 2,12 2,26 2,41 2,55
motor 0,75 1,1 1,5 2,2 3
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 25
[kW]
power(kw)
AbsorbedPower

0.6
Performance
Curve
AXV-D 630, 1728, 1152, 864, 60Hz
AXV-D 630, 60 Hz !" Hub: 189-7

4
36°
Absorbed

1 34°
0.4 32°
30°
28°
26°
2 24°
0.2 0.5 22°
20°
16° 18°
14°
10° 12° ρ = 1,2 kg/m3

[PA]
∆p(Pa)

Lwi(A) a b c d e f g h j k m n p q r s
t

4P 108 109 109 109 115 115 116 116 106 105 109 110 107 107 107 107
Pressure

6P 95 96 95 95 100 100 101 101 94 94 94 95 94 94 94 94


pressure

175 700
8P 87 87 86 86 89 89 90 90 85 84 84 85 85 85 85 85
300
Total
Total

150 600
p
250

q
125 500
j

200 e

100 400 k r

a
f
150
s
75 300 36°
m 34°
b 32°
100 g
30°
50 200 28°
n
26°
c 24°
h 22°
50 20°
25 100
18°
14°
16° Speed
d
12° [min-1]
Pd 10°

0 0 0
0 5000 10000 15000 20000 25000 1728
1728 1/min 4-pol
0 1 2 3 4 5 6 7

0 2500 5000 7500 10000 12500 15000 17500 1152


1152 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 6-pol

0 2500 5000 7500 10000 12500 864


864 1/min
0 0.5 1 1.5 2 2.5 3 3.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,136 0,160 0,185 0,209 0,234 0,255 0,288 0,331 0,375 0,407 0,440 0,472 0,504 0,536 0,568
motor 0,37 0,55 0,75
1152 0,322 0,380 0,437 0,496 0,554 0,603 0,682 0,786 0,890 0,966 1,04 1,12 1,19 1,27 1,35
motor 0,37 0,55 0,75 1,1 1,5
1728 1,09 1,28 1,48 1,67 1,87 2,04 2,30 2,65 3,00 3,26 3,52 3,77 4,03 4,29 4,55
motor 1,1 1,5 2,2 3 4 5,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

26 A09-D V2015/July
[kW]
power (kw)

1
Performance
Curve
AXV-D 710, 1728, 1152, 864, 60Hz
AXV-D 710, 60 Hz !" Hub: 212-7

7.5
AbsorbedPower

2 36°
Absorbed

34°
32°
5 30°
28°
0.5 26°
1 24°
22°
2.5 20°
16° 18°
12°
14° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

Lwi(A) a b c d e f g h j k m n p q r s
400
Pressure

4P 112 113 112 113 119 119 120 120 113 112 113 114 111 111 111 110
6P 99 100 99 99 104 104 105 105 98 98 98 99 97 98 98 97
pressure

8P 90 91 90 90 93 93 94 94 89 88 88 89 88 88 89 88
200 800
Total
Total

300
q
150 600 j

k r

200 a
f
100 400 s

36°
m 34°
32°
b
g 30°
28°
100 n 26°
50 200
c 24°
22°
h
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]

0 0 0
5000 10000 15000 20000 25000 30000 35000 1728
1728 1/min
1 2 3 4 5 6 7 8 9 10 4-pol

2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 1152
1152 1/min
1 2 3 4 5 6 7 6-pol

2500 5000 7500 10000 12500 15000 17500 864


864 1/min
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,241 0,284 0,327 0,370 0,414 0,451 0,510 0,588 0,665 0,722 0,779 0,836 0,893 0,950 1,01
motor 0,37 0,55 0,75 1,1
1152 0,570 0,674 0,775 0,879 0,982 1,07 1,21 1,39 1,58 1,71 1,85 1,98 2,12 2,25 2,39
motor 0,75 1,1 1,5 2,2 3
1728 1,92 2,28 2,62 2,97 3,31 3,61 4,08 4,70 5,323 5,78 6,23 6,69 7,15 7,60 8,06
motor 2,2 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 27
[kW]
power(kw)
Performance
Curve
10 AXV-D 800, 1728, 1152, 864, 60Hz
AXV-D 800, 60 Hz !" Hub: 250-6

36°
AbsorbedPower

1 34°
7.5 32°
Absorbed

2 30°
28°
5 26°
0.5 24°
1 22°
20°
2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]

p
∆p(Pa)
Pressure t

150 600 q
pressure

j
250
r
Total
Total

125 500
e k
200
s
f
100 400 36°
34°
150 a 32°
m
75 300 30°
b 28°
g n 26°
100 24°
50 200 22°
h 20°
c
18°
16°
50 14°
25 100
12°
d 10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 102 104 104 102 106 104 103 102 106 103 102 102 108 106 107 107 Speed
Pd 6P 88 93 92 90 95 92 91 90 94 91 91 90 97 95 95 95 [min-1]
8P 80 85 84 82 87 85 83 82 87 84 83 83 89 87 87 87
0 0 0
5000 10000 15000 20000 25000 30000 35000 40000 45000 1728
1728 1/min 4-pol
1 2 3 4 5 6 7 8 9 10 11 12 13

5000 10000 15000 20000 25000 30000 1152


1152 1/min
1 2 3 4 5 6 7 8 6-pol

2500 5000 7500 10000 12500 15000 17500 20000 22500 864
864 1/min
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,207 0,265 0,342 0,419 0,438 0,499 0,559 0,620 0,680 0,768 0,860 0,953 1,05 1,14 1,23
motor
1152 0,490 0,627 0,811 0,994 1,04 1,18 1,32 1,47 1,61 1,82 2,04 2,26 2,48 2,70 2,92
motor
1728 1,65 2,12 2,74 3,35 3,50 3,99 4,47 4,96 5,44 6,15 6,88 7,63 8,37 9,12 9,86
motor
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

28 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 900, 1728, 1152, 864, 60Hz
AXV-D 900, 60 Hz !" Hub: 281-6

2 36°
AbsorbedPower

15 34°
4 32°
Absorbed

30°

10 28°
26°
1
2 24°
22°
20°
5 18°
16°
14°
12°
10° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

p
200 800
350
Pressure
pressure

q
j
175
Total

300 r
Total

150 600 e k
250
s
f
125 36°
200 34°
a
m 32°
100 400
30°
b
150 28°
g n 26°
75
24°
22°
100 c h 20°
50 200 18°
16°
14°
50 12°
25 d
a b c d e f g h
Lwi(A) j k m n p q r s
10°
Pd 8° 4P 106 108 107 106 110 108 107 106 109 107 106 106 112 110 110 110 Speed
6P 92 97 96 94 98 96 94 94 98 95 94 94 100 99 99 99 [min-1]
8P 83 89 88 86 90 88 87 86 90 87 86 86 92 91 91 91
0 0 0
10000 20000 30000 40000 50000 60000 1728
1728 1/min 4-pol
2 4 6 8 10 12 14 16 18

5000 10000 15000 20000 25000 30000 35000 40000 45000 1152
1152 1/min
2 4 6 8 10 12 6-pol

5000 10000 15000 20000 25000 30000 864


864 1/min
1 2 3 4 5 6 7 8 9 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,367 0,470 0,607 0,745 0,778 0,885 0,993 1,10 1,21 1,36 1,53 1,69 1,86 2,02 2,19
motor 0,37 0,55 0,75 1,1 1,5 2,2
1152 0,870 1,11 1,44 1,76 1,84 2,10 2,35 2,61 2,86 3,23 3,62 4,01 4,40 4,80 5,19
motor 1,1 1,5 2,2 3 4 5,5
1728 2,94 3,76 4,86 5,96 6,22 7,08 7,94 8,80 9,66 10,9 12,2 13,5 14,9 16,2 17,5
motor 3 4 5,5 7,5 11 15 18,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 29
[kW]
power (kw)

4
Performance
Curve
30
AXV-D 1000, 1728, 1152, 864, 60Hz
AXV-D 1000, 60 Hz !" Hub: 315-6

36°
AbsorbedPower

7.5 34°
3 32°
Absorbed

20 30°
28°
5
2 26°
24°
22°
10 20°
1 2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

p
Pressure

250 1000
pressure

q
400 j
Total

r
Total

200 800
e
k

300 f s

36°
150 600
34°
a
32°
m
30°
200 b
28°
100 400 g n 26°
24°
22°
h
c 20°

100 18°
50 200 16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 109 112 111 110 113 111 111 110 113 110 110 109 116 114 114 114 Speed
Pd 6P 95 100 99 97 102 100 98 98 101 98 98 98 104 102 102 102 [min-1]
8P 87 92 92 89 94 92 90 90 94 91 90 90 96 94 94 94
0 0 0
10000 20000 30000 40000 50000 60000 70000 80000 90000 1728
1728 1/min 4-pol
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25

10000 20000 30000 40000 50000 60000 1152


1152 1/min
2 4 6 8 10 12 14 16 6-pol

5000 10000 15000 20000 25000 30000 35000 40000 45000 864
864 1/min
2 4 6 8 10 12 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,653 0,836 1,08 1,32 1,38 1,57 1,76 1,96 2,15 2,42 2,71 3,00 3,30 3,60 3,89
motor 0,75 1,1 1,5 2,2 3 4
1152 1,55 1,98 2,56 3,14 3,28 3,73 4,18 4,64 5,09 5,75 6,43 7,13 7,83 8,53 9,22
motor 2,2 3 4 5,5 7,5 11
1728 5,22 6,68 8,64 10,6 11,1 12,6 14,1 15,6 17,2 19,4 21,7 24,1 26,4 28,8 31,1
motor 5,5 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

30 A09-D V2015/July
[kW]
power(kw)
AbsorbedPower
Performance
Curve
60 AXV-D 1120, 1728, 1152, 864, 60Hz
AXV-D 1120, 60 Hz !" Hub: 353-6

15 36°
6
34°
Absorbed

40 32°
30°
10
4 28°
26°
24°
20 22°
5 20°
2 18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]

600
∆p(Pa)

p
t
Pressure
pressure

300 1200
q
500 j
Total
Total

250 1000
e
k
400
f s
200 800
36°
34°
300 a 32°
m
150 600 30°
b
28°
g n 26°
200 24°
100 400 22°
c h 20°
18°
16°
100 14°
50 200
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 112 115 115 114 117 115 114 113 116 114 113 113 119 117 117 118 Speed
Pd 6P 99 104 103 101 105 103 102 101 105 102 102 101 107 106 106 106 [min-1]
8P 90 96 95 93 98 96 94 93 97 94 94 93 99 98 98 98
0 0 0
20000 40000 60000 80000 100000 120000 1728
1728 1/min 4-pol
5 10 15 20 25 30 35

10000 20000 30000 40000 50000 60000 70000 80000 90000 1152
1152 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 6-pol

10000 20000 30000 40000 50000 60000 864


864 1/min
2 4 6 8 10 12 14 16 18 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 1,16 1,48 1,92 2,35 2,45 2,79 3,13 3,47 3,81 4,30 4,82 5,34 5,86 6,38 6,91
motor 1,5 2,2 3 4 5,5 7,5
1152 2,75 3,52 4,54 5,57 5,82 6,62 7,43 8,23 9,03 10,2 11,4 12,7 13,9 15,1 16,4
motor 3 4 5,5 7,5 11 15 18,5
1728 9,27 11,9 15,3 18,8 19,6 22,4 25,1 27,8 30,5 34,4 38,5 42,7 46,9 51,1 55,3
motor 11 15 18,5 22 30 37 45 55
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 31
[kW]
power (kw)
Performance
Curve AXV-D 1250, 60 Hz
AXV-D 1250, 1728, 1152, 864, 60Hz
!" Hub: 420-6
30 100
AbsorbedPower

36°
10 34°
Absorbed

32°
20 30°
28°
50 26°

5 24°
22°
10 20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

450 800
Pressure

1750
pressure

p
400 700
Total

j q
1500
Total

350 r
600 k
e
1250
300
500 f
s

250 1000 36°


a 34°
400
m 32°
200 b 30°
750
28°
300 g n 26°
150 24°
22°
500 h 20°
200
100 c 18°
16°
14°
100 250 d 12°
50 10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 4P 115 115 113 112 119 115 113 114 114 116 116 116 121 120 121 121 Speed
Pd 6P 105 105 103 103 108 105 103 104 104 106 105 105 110 110 110 111 [min-1]
8P 97 98 96 96 100 97 95 96 96 98 97 98 102 102 102 103
0 0 0
25000 50000 75000 100000 125000 150000 175000 1728
1728 1/min
5 10 15 20 25 30 35 40 45 50 4-pol

20000 40000 60000 80000 100000 120000 1152


1152 1/min
5 10 15 20 25 30 35 6-pol

10000 20000 30000 40000 50000 60000 70000 80000 90000 864
864 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 2,26 2,78 3,53 4,29 4,33 4,89 5,59 6,29 7,01 7,88 8,78 9,71 10,6 11,5 12,5
motor 3 4 5,5 7,5 11 15
1152 5,36 6,59 8,38 10,2 10,3 11,6 13,2 14,9 16,6 18,7 20,8 23,0 25,2 27,3 29,6
motor 5,5 7,5 11 15 18,5 22 30
1728 18,1 22,2 28,3 34,3 34,7 39,1 44,7 50,3 56,1 63,0 70,2 77,7 85,2 92,2 99,8
motor 18,5 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

32 A09-D V2015/July
[kW]
power (kw)
AbsorbedPower
Performance
Curve
AXV-D 1400, 1152, 864, 691, 60Hz
AXV-D 1400, 60 Hz !" Hub: 472-6

20 36°
10
34°
40
Absorbed

32°
30°
28°
26°
5 10 24°
20 22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

1000
350
Pressure
pressure

p
500
j q
Total

300
Total

800
k r
e

400
250

f
s
600
200 36°
300 a 34°
m 32°
b 30°
150 28°
400 g
n 26°
200
24°
22°
100 h
20°
c 18°
200 16°
100 14°
50 d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 6P 108 108 107 106 112 109 107 108 108 110 109 110 114 114 114 115 Speed
Pd 8P 101 101 100 100 104 101 99 100 100 102 101 101 106 106 106 107 [min-1]
10P 95 95 94 94 98 95 93 94 93 96 95 95 100 100 100 101
0 0 0
25000 50000 75000 100000 125000 150000 175000 1152
1728
1152 1/min
5 10 15 20 25 30 35 40 45 50 4-pol
6-pol

20000 40000 60000 80000 100000 120000 864


1152
864 1/min
5 10 15 20 25 30 35 6-pol
8-pol

10000 20000 30000 40000 50000 60000 70000 80000 90000 100000 691
864
691 1/min
5 10 15 20 25 30 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 2,08 2,56 3,26 3,95 3,99 4,51 5,15 5,80 6,46 7,26 8,09 8,95 9,81 10,6 11,5
motor 2,2 3 4 5,5 7,5 11 15
864 4,07 5,00 6,36 7,72 7,79 8,80 10,1 11,3 12,6 14,2 15,8 17,5 19,2 20,7 22,4
motor 5,5 7,5 11 15 18,5 22 30
1152 9,64 11,8 15,1 18,3 18,5 20,9 23,8 26,8 29,9 33,6 37,4 41,4 45,4 49,2 53,2
motor 11 15 18,5 22 30 37 45 55
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 33
[kW]
power (kw)
Performance
Curve
AXV-D 1600, 1152, 864, 691, 60Hz
AXV-D 1600, 60 Hz !" Hub: 539-6
100
AbsorbedPower

20 40 36°
34°
Absorbed

32°
30°
28°
26°
20 50
10 24°
22°
20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)
Pressure

450 700
pressure

1200 p

j q
400
Total
Total

600
r
1000 k
350 e

500
300
800 f s

36°
250 400
a 34°
m 32°
600
b 30°
200
300 28°
g
n 26°
150 24°
400 22°
200 h
20°
100 c 18°
16°
200 14°
100 d 12°
50 10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 113 112 111 111 116 113 111 112 112 114 113 114 118 118 118 119 Speed
Pd 8P 105 105 104 104 108 105 103 104 104 106 105 105 110 110 111 111 [min-1]
10P 99 99 98 98 102 99 97 98 98 100 99 99 104 104 104 105
0 0 0
50000 100000 150000 200000 250000 1152
1728
1152 1/min
10 20 30 40 50 60 70 4-pol
6-pol

25000 50000 75000 100000 125000 150000 175000 864


200000 1152
864 1/min
5 10 15 20 25 30 35 40 45 50 55 6-pol
8-pol

20000 40000 60000 80000 100000 120000 140000 160000 691


864
691 1/min
5 10 15 20 25 30 35 40 45 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 4,04 4,97 6,32 7,66 7,74 8,74 9,98 11,2 12,5 14,1 15,7 17,4 19,0 20,6 22,3
motor 5,5 7,5 11 15 18,5 22 30
864 7,89 9,70 12,3 15,0 15,1 17,1 19,5 22,0 24,5 27,5 30,6 33,9 37,2 40,2 43,5
motor 11 15 18,5 22 30 37 45
1152 18,7 23,0 29,2 35,5 35,8 40,5 46,2 52,1 58,0 65,2 72,6 80,3 88,1 95,4 103,2
motor 22 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

34 A09-D V2015/July
[kW]
power (kw)

40
Performance
Curve
75
AXV-D 1800, 1152, 864, 691, 60Hz
AXV-D 1800, 60 Hz !" Hub: 606-6

36°
AbsorbedPower

150 34°
30 32°
Absorbed

30°
50
28°
100
20 26°
24°
22°
25 20°
10 50 18°
16°
12°
14° ρ = 1,2 kg/m3
10°

1750
[PA]
∆pt(Pa)

600
Pressure
pressure

p
1500
800 j q
Total

500
Total

r
1250 k
e

400
600
f
1000 s

36°
a 34°
300 m 32°
750 b 30°
400
g
28°
n 26°
200 24°
500 22°
h
20°
200 c 18°
16°
100 14°
250
d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 6P 116 116 114 114 119 116 114 115 116 117 117 118 122 122 122 123 Speed
Pd 8P 109 109 107 107 111 109 106 107 107 109 109 109 114 114 114 115 [min-1]
10P 103 103 102 102 105 103 100 101 101 104 103 103 108 107 108 108
0 0 0
50000 100000 150000 200000 250000 300000 350000 1152
1728
1152 1/min 4-pol
6-pol
10 20 30 40 50 60 70 80 90 100

50000 100000 150000 200000 250000 864


1152
864 1/min
10 20 30 40 50 60 70 6-pol
8-pol

25000 50000 75000 100000 125000 150000 175000 200000 225000 691
864
691 1/min
5 10 15 20 25 30 35 40 45 50 55 60 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 7,27 8,93 11,4 13,8 13,9 15,7 18,0 20,2 22,5 25,3 28,2 31,2 34,2 37,0 40,1
motor 7,5 11 15 18,5 22 30 37 45
864 14,2 17,4 22,2 26,9 27,2 30,7 35,1 39,5 44,0 49,4 55,1 61,0 66,8 72,4 78,3
motor 15 18,5 30 37 45 55 75 90
1152 33,6 41,4 52,6 63,8 64,5 72,8 83,1 93,6 104,3 117,2 130,6 144,5 158,5 171,6 185,6
motor 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 35
[kW]
power (kw)
Performance
Curve
300
AXV-D 2000, 60 Hz
AXV-D 2000, 1152, 864, 691, 60Hz
!" Hub: 674-6

36°
AbsorbedPower

34°
50 100 32°
Absorbed

30°
200
28°
26°
24°
25 50 22°
100 20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

1200
Pressure

2000
700
pressure

1000
Total

j q
Total

600
r
e k
1500
800
500
f
s

36°
400
600 a 34°
1000 m 32°
b 30°
300 g 28°
n 26°
400
24°
22°
200 h 20°
500
c 18°
16°
200 14°
100 d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 6P 119 119 118 117 123 120 118 119 119 120 120 121 125 125 125 126 Speed
Pd 8P 112 112 111 110 115 112 110 111 111 113 112 112 117 117 117 118 [min-1]
10P 106 106 105 105 109 106 104 105 104 107 106 106 111 111 111 112
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 1152
1728
1152 1/min 4-pol
6-pol
20 40 60 80 100 120 140

4 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 864
1152
864 1/min 6-pol
10 20 30 40 50 60 70 80 90 100 8-pol

5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
691
864
691 1/min
10 20 30 40 50 60 70 80 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 12,3 15,1 19,2 23,3 23,6 26,6 30,4 34,2 38,1 42,8 47,7 52,8 57,9 62,7 67,8
motor
864 24,0 29,5 37,5 45,5 46,0 52,0 59,3 66,8 74,4 83,6 93,2 103,1 113,1 122,4 132,4
motor
1152 56,9 70,0 89,0 108,0 109,0 123,1 140,6 158,4 176,4 198,3 220,9 244,5 268,0 290,2 313,9
motor
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

36 A09-D V2015/July
[kW]
power (kw)
Performance
Curve AXV-D 2200, 60 Hz
AXV-D 2200, 864, 691, 576, 60Hz
!" Hub: 741-6

100 200
36°
Absorbed Power

34°
50
32°
Absorbed

30°
28°
26°
50 100
24°
25 22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

1400
600
Pressure
pressure

p
800
1200 j q
Total

500
Total

r
k
e
1000
600
400
f s
800 36°
a 34°
300 m 32°
400 b 30°
600
28°
g
n 26°
200 24°
400 22°
h 20°
200 c 18°
16°
100 14°
200 12°
d
10°
Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 115 115 114 113 118 115 113 113 114 116 115 115 120 120 120 121 Speed
Pd 10P 109 109 108 108 112 109 107 107 107 110 109 109 114 114 114 115 [min-1]
12P 104 104 103 104 106 104 102 102 102 105 104 104 109 109 109 110
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5 5 864
5.0x10 1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140

4 5 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 691
4.0x10 1152
691 1/min 6-pol
10 20 30 40 50 60 70 80 90 100 110 10-pol

4 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 864
576
576 1/min
10 20 30 40 50 60 70 80 90 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 11,4 14,1 17,9 21,7 21,9 24,8 28,3 31,9 35,5 39,9 44,4 49,2 53,9 58,4 63,1
motor 15 18,5 22 30 37 45 55 75
691 19,8 24,3 30,9 37,5 37,9 42,8 48,9 55,0 61,3 68,9 76,8 85,0 93,1 100,9 109,1
motor 22 30 37 45 55 75 90 110
864 38,6 47,5 60,4 73,3 74,0 83,6 95,4 107,5 119,7 134,6 149,9 165,9 181,9 197,0 213,1
motor 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 37
[kW]
power(kw)

100
Performance
Curve
AXV-D 2400, 864, 691, 576, 60Hz
AXV-D 2400, 60 Hz !" Hub: 808-6

150 300 36°


AbsorbedPower

34°
75 32°
Absorbed

30°
100 200 28°
50 26°
24 °
22°
50 100 20°
25 18 °
16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆p(Pa)
t

700
Pressure

1000
p
pressure

1500
j q
Total

600
Total

r
800 1250 e
k

500

f
1000 s
600 36 °
400
a 34°
m 32°
750 30°
b
300 28°
400 g
n 26°
24°
500 22°
200 h 20°
c 18 °
200 16°
14°
250
100 d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 117 118 116 116 120 117 115 116 116 118 118 118 123 123 123 124 Speed
Pd 10P 111 112 111 111 114 111 109 110 110 112 111 112 116 116 117 117 [min-1]
12P 107 107 106 106 109 107 104 105 105 108 106 107 111 111 112 112
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5 864
1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180

1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
691
1152
691 1/min 6-pol
20 40 60 80 100 120 140 10-pol

4.5x10 576864
4 5 5 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 4.0x10
576 1/min
20 40 60 80 100 120 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 17,7 21,7 27,6 33,5 33,8 38,2 43,6 49,2 54,7 61,5 68,6 75,9 83,2 90,0 97,4
motor 18,5 22 30 37 45 55 75 90 110
691 30,5 37,5 47,7 57,9 58,5 66,0 75,4 84,9 94,6 106,3 118,5 131,1 143,7 155,7 168,4
motor 37 45 55 75 90 110 132 160 200
864 59,6 73,3 93,2 113,1 114,2 129,0 147,3 165,9 184,8 207,7 231,4 256,1 280,7 304,0 328,8
motor 75 110 132 160 200 250 315 355
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

38 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 2500, 864, 691, 576, 60Hz
AXV-D 2500, 60 Hz !" Hub: 842-6

200 400
Absorbed Power

36°
100 34°
Absorbed

32°
30°
28°

100 200 26°


50 24°
22°
20°
18°
16°
14° ρ = 1,2 kg/m3
12°
10°

1200
[PA]
∆pt(Pa)

800
Pressure
pressure

1000 j q
Total

1500
Total

r
600 e
k

800

f s

1000 36°
600 a
34°
400 m 32°
b 30°
28°
g
n 26°
400
24°
22°
500 h
200 20°
c 18°
16°
200 14°
d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 119 119 117 117 121 119 116 117 117 119 119 119 124 124 124 125 Speed
Pd 10P 113 113 112 112 115 113 110 111 111 114 113 113 118 118 118 118 [min-1]
12P 108 108 108 107 110 108 105 106 106 109 108 108 113 112 113 113
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5 864
1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180 200

5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 691
6.0x10 1152
691 1/min 6-pol
20 40 60 80 100 120 140 160 10-pol

5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
4.5x10
5
5.0x10
5
864
576
576 1/min
20 40 60 80 100 120 140 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 21,7 26,6 33,9 41,1 41,5 46,9 53,5 60,3 67,1 75,4 84,1 93,0 102,0 110,4 119,5
motor 22 30 37 45 55 75 90 110 132
691 37,4 46,0 58,5 71,0 71,7 81,0 92,5 104,1 116,0 130,4 145,2 160,7 176,2 190,8 206,4
motor 45 55 75 90 110 132 160 200 250
864 73,1 89,8 114,2 138,7 140,0 158,1 180,6 203,4 226,5 254,6 283,7 314,0 344,2 372,7 *403,2
motor 75 90 132 160 200 250 315 355 400 -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 39
AbsorbedPower [kW]
power (kw)

150
Performance
Curve AXV-D 2600, 60 Hz
AXV-D 2600, 864, 691, 576, 60Hz
!" Hub: 875-6

36°
400 34°
200
32°
Absorbed

100 30°
28°
26°

100 200 24°


22°
50
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°

[PA]
∆pt(Pa)

2000
1250
Pressure
pressure

p
Total

750 j q
Total

1000
1500 k
r
e

f
750 s
500
36°
1000 a 34°
m 32°
b 30°
500 g
28°
n 26°
24°
250 22°
h
500 20°
c 18°
250 16°
14°
d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 120 120 119 118 123 120 118 119 119 121 120 120 125 125 125 126 Speed
Pd 10P 114 114 113 113 117 114 112 113 112 115 114 114 119 119 119 120 [min-1]
12P 109 109 109 109 112 109 107 108 107 110 109 109 114 114 114 115
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10 5.0x10
5 5
6.0x10
5
7.0x10
5
8.0x10
5 864
1728
864 1/min 4-pol
8-pol
25 50 75 100 125 150 175 200 225

5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 691
1152
691 1/min 6-pol
25 50 75 100 125 150 175 10-pol

1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
576
864
576 1/min
25 50 75 100 125 150 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 26,3 32,4 41,2 50,0 50,5 57,0 65,1 73,3 81,6 91,7 102,2 113,1 124,0 134,3 145,3
motor 30 37 45 55 75 90 110 132 160
691 45,5 55,9 71,1 86,3 87,2 98,5 112,4 126,6 141,0 158,5 176,6 195,5 214,3 232,1 251,0
motor 55 75 90 110 132 160 200 250 315
864 88,9 109,3 138,9 168,6 170,3 192,3 219,6 247,4 275,5 309,6 345,0 381,8 *418,6 453,3 490,3
motor 90 110 160 200 250 315 355 400 - - -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

40 A09-D V2015/July
[kW]
power (kw)

200
Performance
Curve
AXV-D 2800, 864, 691, 576, 60Hz
AXV-D 2800, 60 Hz !" Hub: 942-6

36°
Absorbed Power

300 600 34°


32°
150
Absorbed

30°
28°
200 400
26°
100
24°
22°
20°
100 200
50 18°
16°
14°
12°
10° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

1000
Pressure

p
pressure

2000
1250 j q
Total
Total

r
750 k
e

1000
1500
f s

36°
750 a 34°
500
m 32°
1000 b 30°
28°
g
n 26°
500
24°
22°
h 20°
250
500 c 18°
16°
250 14°
d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 122 122 121 121 125 122 120 121 121 123 122 123 127 127 128 128 Speed
Pd 10P 116 116 115 115 119 116 114 115 115 117 116 116 121 121 121 122 [min-1]
12P 111 112 111 111 114 111 109 110 110 112 111 111 116 116 116 117
0 0 0
2.0x105 4.0x10
5
6.0x10
5
8.0x10
5
1.0x10
6 864
1728
864 1/min 4-pol
8-pol
50 100 150 200 250 300

5 5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 8.0x10 691
1152
691 1/min 6-pol
25 50 75 100 125 150 175 200 225 10-pol

1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5
864
576
576 1/min
25 50 75 100 125 150 175 20012-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 38,1 46,9 59,6 72,3 73,0 82,5 94,2 106,1 118,2 132,8 148,0 163,8 179,5 194,4 210,3
motor 45 55 75 90 110 132 160 200 250
691 65,9 81,0 103,0 125,0 126,2 142,5 162,8 183,3 204,2 229,5 255,7 283,0 310,2 336,0 363,4
motor 75 90 110 132 160 200 250 315 355 400
864 128,6 158,2 201,1 244,1 246,5 278,4 317,9 358,1 398,8 *448,2 499,4 552,7 605,9 656,2 709,7
motor 160 250 315 355 400 - - - - - -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.

A09-D V2015/July 41
Vane Axial Flow Fans
Dimensions AXV-D
ØTk Optional
Direct Driven s

Air flow Air flow

ØDa
ØDa

ØDi
ØDi

z x Ød
hF

k1 bF k1
E
I1 L I1
F

Belt Driven

z x Ød

Air flow

hF2
ØDa

ØTk
ØDi

hF

bF
K1 E
I1 F

Model Da Di hF hF2 zxd Tk E F L bF


size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
500 584 503 315 1041 12 x 12 551 440 500 152 70
560 664 565 345 1094 16 x 14 629 500 560 152 70
630 734 634 400 1246 16 x 14 698 570 630 152 70
710 814 711 450 1454 16 x 14 775 650 710 190 70
800 904 797 500 1544 12* x 14 861 730 800 190 80
900 1004 894 580 1746 12* x 14 958 830 900 200 80
1000 1105 1003 630 1821 12* x 14 1067 930 990 200 80
1120 1245 1125 690 1990 16* x 18 1200 1050 1110 240 100
1250 1370 1250 750 2175 16* x 18 1337 1180 1240 240 100
1400 1525 1405 830 2362 16* x 18 1475 1330 1390 260 100
1600 1725 1605 930 2550 20* x 18 1675 1530 1590 260 100

LH/1 LH/2
Model s k1 l1 motor s k1 l1 motor
size [mm] [mm] [mm] max. [mm] [mm] [mm] max.
500 2 327 401 112
560 2 327 401 112 3 624 700 160
630 2 327 401 112 3 624 700 160
710 2,5 326 401 112 2,5 490 565 132
800 2,5 316 401 112 3 614 700 160
900 3 429 515 132 4 612 700 160
1000 3 429 515 132 4 692 780 180
1120 4 522 630 160 4 892 1000 200
1250 4 522 630 160 4 892 1000 225
1400 4 892 1000 225
1600 4 892 1000 280

We reserve the right to alter measurements without notice in case of technical improvements.

42 A09-D V2015/July
Vane Axial Flow Fans
Dimensions !"
z - Ød

Ø Da
Ø Tk
Ø Di

hF

L2 E

L3 L1 F

Baugröße Da Di hF zxd Tk E F L1 L2 L3
size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1800 2010 1805 1120 24x18 1920 1660 1800 400 1200 1400
2000 2210 2005 1165 32x18 2120 1820 2000 445 1300 1500
2200 2440 2205 1265 32x18 2340 2020 2200 490 1400 1650
2400 2630 2405 1370 32x18 2530 2220 2400 550 1500 1800
2500 2740 2505 1420 36x24 2640 2320 2500 555 1530 1820
2600 2840 2605 1470 36x24 2740 2380 2600 590 1580 1850
2800 3150 2805 1570 36x24 3000 2500 2800 1300 1680 1900

We reserve the right to alter measurements without notice in case of technical improvements.

A09-D V2015/July 43
63
Vane Axial Flow Fans
Dimensions
Accessories AXV-D

ED GL-AXV EV-AXV LRK

Bellmouth inlet Matching flange Flexible connector compl. Air-operated damper

zx d

Ø Da
Ø Da
DDa

Ø Tk

Ø Tk
Ø Di

Ø Di
Da

Tk

Di

Da

Tk
Di
zx d

Ld
30 Le Lk U

Model Da Di Tk zxd DDa Ld Lk Le U


size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
355 438 359 405 8 x 12 435 165 250 130 -
400 484 401 448 12 x 12 507 165 250 130 -
450 534 450 497 12 x 12 555 165 250 130 15
500 584 504 551 12 x 12 617 165 250 130 45
560 664 565 629 16 x 14 667 165 250 130 80
630 734 634 698 16 x 14 757 165 250 130 120
710 814 711 775 16 x 14 816 170 350 130 60
800 904 797 861 12* x 14 915 250 350 130 110
900 1004 894 958 12* x 14 1015 250 350 130 170
1000 1105 1003 1067 12* x 14 1115 250 350 130 225
1120 1245 1125 1200 16* x 18 1243 250 350 130 255
1250 1370 1250 1337 16* x 18 1364 250 400 170 375
1400 1525 1405 1475 16* x 18 1523 250 400 170 450
1600 1725 1605 1675 20* x 18 1723 250 400 170 550

We reserve the right to alter measurements without notice in case of technical improvements.

44 A09-D V2015/July
Sound Information

Sound power levels


This term refers to the power which a source radiates as sound. Sound power levels are expressed in decibels with a reference level of 1 picoWatt. The sound
power level of a source remains the same regardless of its environment and the distance to the listener.
!"
If the sound power frequency spectrum is needed, for as follows: example, the design of sound attenuators, the A-weighted rated sound power levels at
particular octave band frequency LWA can be calculated by subtracting the relative sound Lwrel.

LWA = Lwi + Lwrel

Sound pressure level


These are pressure fluctuations generated by a source expressed in decibels with a reference level of 20 µPa. The sound pressure level varies with the
distance of a sound source to the listener and its environment.
Sound level reduction half sphere
∆L [dB] L [dB]

30
a: without reflexion
25 b: with reflexion
/ noise reduction

c: full sphere without reflexion


c
20
a
Noise reduction

15 b
Pegelabnahme

10

0
0,5 0,6 0,8 1 2 3 4 5 6 7 8 9 10
Distance [m]
Entfernung / distance [m]

Frequencies
Sound is split into different frequencies. Frequencies of human hearing range from about 20 cycles per second (Hz) to 20.000 cycles per second (Hz). For
practical purposes, WOLTER publishes noise data in eight octave bands with the centre frequencies of (63,) 125, 250, 500, 1000, 2000, 4000 and 8000 Hz.
Each fan has its own specific correction factor which is to be deducted from sound power according to the octave band.

A-weighted sound pressure level in dB (A)


The human ear is more sensitive to sound in some frequencies than in others. The A-weighting is an attempt to reflect this natural perception of sound. The
A-weighting is a set of figures which are applied to the sound pressure levels. The levels in each of the octave bands are added logarithmically to give a
single figure. The A-weighting over the octave band is as follows:
Table 1) Frequency [Hz] 63 125 250 500 1000 2000 4000 8000
A-weighting [dB] -25,5 -15,5 -8,5 -3 0 +1 +1 -1

Table 2)
Addition of sound levels Difference between two sound levels Add to the higher level
[dB] [dB]
0-1 3
2-3 2
4-9 1
>
=10 0

where:
L∑ = 10 · lg(10 0,1·L1 + 10 0,1·L2 + ... + 10 0,1·Ln ) L1 = sound level of a source 1
L∑ = resulting summation sound level

Summation of several congeneric sound levels


where:
L∑ = L1 + 10 · lg(z) z = number of sources
L1 = sound level of a single source
L∑ = resulting summation sound level

A09-D V2015/July 45
Vane Axial Flow Fans
Sound Information

Relative Sound Power Frequency Spectrum (Lwrel) [dB]

Fan Model Poles 63 125 250 500 1000 2000 4000 8000
Size [-] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz]
4 -6 -3 -8 -17 -25 -28 -30 -34
500 6 -3 -5 -12 -21 -25 -27 -30 -35
8 -2 -6 -13 -20 -22 -24 -28 -33
4 -6 -3 -8 -18 -26 -29 -31 -35
560 6 -3 -6 -12 -22 -26 -28 -31 -36
8 -2 -6 -14 -20 -23 -25 -29 -34
4 -6 -3 -8 -18 -27 -29 -32 -35
630 6 -2 -6 -12 -22 -26 -29 -31 -36
8 -2 -6 -14 -21 -24 -26 -30 -35
4 -6 -3 -9 -19 -27 -30 -32 -36
710 6 -2 -6 -13 -23 -27 -29 -32 -37
8 -2 -6 -14 -22 -24 -27 -30 -36
4 -8 -3 -7 -16 -18 -19 -21 -27
800 6 -4 -4 -12 -15 -17 -18 -22 -31
8 -3 -6 -13 -14 -15 -17 -23 -33
4 -8 -2 -7 -16 -18 -20 -21 -28
900 6 -4 -4 -13 -16 -18 -18 -22 -32
8 -2 -6 -13 -14 -16 -17 -24 -34
4 -7 -2 -8 -17 -19 -20 -22 -28
1000 6 -4 -4 -13 -16 -18 -19 -23 -32
8 -2 -6 -13 -15 -16 -18 -24 -35
4 -7 -2 -8 -17 -19 -21 -22 -29
1120 6 -4 -4 -13 -17 -19 -20 -24 -33
8 -2 -6 -14 -15 -17 -18 -25 -35
4 -7 -4 -8 -10 -13 -16 -18 -24
1250 6 -5 -5 -9 -11 -14 -17 -21 -29
8 -3 -7 -9 -12 -15 -18 -23 -33
6 -5 -5 -10 -12 -15 -18 -22 -30
1400 8 -4 -7 -9 -12 -15 -18 -24 -33
10 -4 -7 -9 -12 -15 -18 -25 -34
6 -5 -5 -10 -12 -16 -18 -22 -31
1600 8 -3 -7 -10 -12 -16 -18 -24 -34
10 -3 -7 -9 -12 -15 -19 -26 -35
• Sound power frequency spectrum calculated with this Lwrel are not licensed by AMCA International.

46 A09-D V2015/July
Sound Information

Fan Model Poles


Relative Sound Power Frequency Spectrum (Lwrel) [dB]

63 125 250 500 1000


!"
2000 4000 8000
Size [-] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz]
6 -5 -5 -10 -12 -16 -18 -23 -31
1800 8 -3 -7 -10 -13 -16 -19 -25 -34
10 -3 -8 -9 -13 -16 -19 -26 -35
6 -4 -5 -10 -13 -16 -19 -23 -31
2000 8 -3 -7 -10 -13 -16 -19 -25 -34
10 -3 -8 -10 -13 -16 -19 -27 -35
8 -3 -7 -11 -13 -17 -19 -25 -34
2200 10 -3 -8 -10 -13 -16 -20 -27 -36
12 -3 -7 -9 -13 -15 -20 -28 -36
8 -3 -8 -11 -14 -17 -20 -26 -35
2400 10 -3 -8 -10 -13 -16 -20 -27 -36
12 -3 -7 -10 -13 -16 -20 -28 -36
8 -3 -8 -11 -14 -17 -20 -26 -35
2500 10 -3 -8 -10 -14 -16 -20 -27 -37
12 -3 -7 -10 -13 -16 -20 -28 -36
8 -3 -8 -11 -14 -17 -20 -26 -35
2600 10 -3 -8 -10 -14 -17 -20 -27 -37
12 -3 -8 -10 -13 -16 -20 -28 -36
8 -3 -6 -11 -13 -17 -19 -24 -33
2800 10 -2 -8 -11 -14 -17 -20 -26 -35
12 -3 -8 -11 -14 -17 -20 -27 -36
• Sound power frequency spectrum calculated with this Lwrel are not licensed by AMCA International.

A09-D V2015/July 47
Tubular Sound Attenuator for AXV-D
SA, SPA

SPA 450 -1D


Length
z x Ød
Size
355...1600
Pod as option
Sound attenuator
SA - without pod
SPA - with pod

Attenuators made of galvanised sheet steel. Connecting flanges correspond


to those of the AXV axial fan series. ØDi
ls
ØTk

ØDSa

Size DSa Tk Di ls 1 Length Type Pitch angle Octave band mid-frequency [Hz]
x 1D x 2D SA-1D SPA-1D SA-2D SPA-2D
[mm] [mm] [mm] [mm] [mm] [kg] [kg] [kg] [kg] setting 63 125 250 500 1k 2k 4k 8k
1D SA-1D all 2 4 6 10 14 10 7 8
355 459 405 359 355 710 12 18 16 23 SPA-1D low 4 6 8 13 20 21 18 16
400 601 448 401 400 800 14 23 19 29 med 4 6 8 12 18 19 18 14
450 650 497 450 450 900 18 29 23 36 high 4 6 8 11 13 16 16 11
2D SA-2D low 4 7 12 18 22 17 12 13
med 4 7 11 17 21 17 13 12
high 4 7 10 15 19 16 13 10
SPA-2D low 7 10 15 24 32 35 30 28
med 7 10 15 21 26 26 24 22
high 7 10 15 16 15 17 13 13
500 704 551 504 500 1000 22 36 28 43 1D SA-1D all 3 4 8 14 14 9 8 7
560 765 629 565 560 1120 25 41 31 50 SPA-1D low 4 6 9 17 26 21 18 12
630 834 698 634 630 1260 29 47 37 59 med 4 6 9 17 23 20 18 11
710 911 775 711 710 1420 37 60 47 75 high 4 6 9 16 17 16 14 11
800 997 861 797 800 1600 69 108 90 141 2D SA-2D low 6 8 14 23 24 15 13 10
med 6 8 13 22 22 14 13 9
high 6 8 12 20 18 13 11 9
SPA-2D low 8 11 16 30 39 35 32 22
med 8 11 16 27 32 32 29 19
high 8 11 16 24 23 23 24 17
900 1094 958 894 900 1800 86 135 112 176 1D SA-1D all 3 4 9 14 12 8 7 7
1000 1203 1067 1003 1000 2000 125 190 156 234 SPA-1D low 4 6 11 22 21 16 14 11
1120 1325 1200 1125 1120 2240 132 210 169 260 med. 4 6 11 20 19 15 13 11
1250 1450 1337 1250 1250 2500 146 234 185 294 high 4 6 11 17 17 14 12 11
2D SA-2D low 6 8 14 22 20 13 12 10
med. 6 8 13 21 18 12 11 10
high 6 8 12 19 15 11 10 9
SPA-2D low 8 11 19 30 32 30 24 17
med. 8 11 19 26 27 26 22 17
high 8 11 19 21 20 22 20 16
1400 1605 1475 1405 1400 2800 197 316 250 397 1D SA-1D all 4 5 10 14 11 7 6 6
1600 1805 1675 1605 1600 3200 275 540 348 682 SPA-1D low 5 7 12 21 20 14 12 9
med. 5 7 12 19 18 13 11 9
high 5 7 12 15 16 12 10 8
2D SA-2D low 8 9 15 20 19 12 11 9
med. 8 9 14 20 17 11 10 9
high 8 9 13 19 14 10 9 9
SPA-2D low 10 14 22 28 31 29 18 15
med. 10 14 22 25 27 25 16 15
high 10 14 22 21 21 21 15 14
• Low, Medium and High Pitch Angle setting correspond to 10º, 22º and 35º pitch angle approximately: for other pitch angles use interpolation.

• Sizes 1800 - 2800 TBA.

48 A09-D V2015/July
!"
Tubular Sound Attenuator for AXV-D
SPA - Pressure Loss

Pressure Loss SPA - 1D


.
Volume Flow V [CFM]
1000 2000 5000 10000 20000 50000 100000 200000
500 2

300
1
200

Pressure inches water gause [in.WG]


0.5
Pressure Loss [Pa]

100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400

30 1600
0.1
20

0.05
10
0.03

5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]

Pressure Loss SPA - 2D


.
Volume Flow V [CFM]
1000 2000 5000 10000 20000 50000 100000 200000
500 2

300
1
200
Pressure inches water gause [in.WG]

0.5
Pressure Loss [Pa]

100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400

30 1600
0.1
20

0.05
10
0.03

5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]

• Performance of sound attenuator are not licensed by AMCA International.

A09-D V2015/July 49
Wolter Sales Network
Inland Poland: Hongkong:
Ing. Günther Rößler Wentoprodukt Wolter Asia Ltd.
D-07619 Schkölen 44-100 Gliwice Hong Kong
Tel. (+49) 03 66 94 / 22 359 Tel. (+48)32 331-34-24 Tel. (+852) 0 24 / 56 01 98
Fax (+49) 03 66 94 / 22 357 Fax (+48)32 729-76-53 Fax (+852) 0 24 / 56 02 90
[email protected] [email protected] [email protected]

Mattias Industrievertretungen Portugal: India:


D-16259 Bad Freienwalde Safe Park Ventilação Industrial Lda. Wolter Ventilators India Pvt. Ltd.
Tel. (+49)03344/301994 P-2675-240 Odivelas 867 D, Block-A, Sushant Lok, Phase-I,
Fax (+49)03344/301996 Tel. (+351) 21 93 / 75 265 Gurgaon - 122009 (Haryana)
[email protected] Fax (+351) 21 93 / 86 061 Tel. +91 124 2577797, 4261001-3
[email protected] [email protected]
Industrieservice Drexler
D-49080 Osnabrück Russia: Indonesia:
Tel. (+49) 0 541 / 20 04 88 3
Euroclimat-Prof PT. Agung Kipas Kastara.
Fax (+49) 0 541 / 20 04 88 4
RU-107082 Moskau ID-14440 Jakarta Indonesia
[email protected]
Tel. (+7) 4 95 / 97 57 530 Tel. +62 (0) 21 / 6667 6925, 6667 6926
Burkhardt Projekt GmbH Fax (+7) 4 95 / 97 57 530 Fax +62 (0) 21 / 6667 6927
D-67583 Guntersblum [email protected] [email protected]
Tel. (+49) 0 62 49 / 82 01 Korea:
Schweiz:
Fax (+49) 0 62 49 / 88 58
[email protected] Anson AG Zürich Kaceco-Wolter
CH-8055 Zürich 14-1, Dang-dong,Gunpo-shi, Gyeonggi-do
Friedrich Glock Tel. (+41) 0 44 / 46 11 111 Tel. +82 (0) 31 / 4773 104
D-97980 Bad Mergentheim Fax (+41) 0 44 / 46 13 111 Fax +82 (0) 31 / 4773 132
Tel. (+49) 0 79 31 / 37 44 [email protected] [email protected] / [email protected]
Fax (+49 )0 79 31 / 28 58
Ventra Technik AG Malaysia:
[email protected]
CH-8599 Salmsach
Tel. (+41) 0 71 / 46 11 447 Vibrantech (M) Sdn Bhd.
Europe Fax (+41) 0 71 / 46 11 448 47200 Petaling Jaya Selangor, Malaysia
[email protected] Tel. +603 (0) 7847 3500
Danmark: Fax +603 (0) 7847 3380
Air-Con Danmark A/S Turkey: [email protected]
DK-8400 Ebeltoft Air Trade Centre Ltd Sti Türkiye,
Tel. (+45)086/345111 Singapore:
TR-34418 Seyrantepe / Instanbul
Fax (+45)086/345810 Tel. (+90) 02 12 / 28 34 510 Wolter Pte. Ltd.
[email protected] Fax (+90) 02 12 / 27 83 964 SG-569738 Singapore
[email protected] Tel. (+65) 0 63 / 52 95 48
Hungary: Fax (+65) 0 63 / 52 95 47
Air-Technik Légtechnikal Kft. United Kingdom: [email protected]
HU-2040 Budaörs Wolter UK Ltd.
Tel. (+36)023/428533 Sri Lanka:
GB-B37 7UQ Solihull
Fax (+36)023/428544 Tel. (+44) 01 21 / 63 55 390 Sirocco Air Technologies (Pvt) Ltd.
[email protected] Fax (+44) 01 21 / 63 55 391 28/12, Gemunu Mawatha, Kotuwegoda,
[email protected] Rajagiriya, Sri Lanka
Ireland: Tel. +94 11 7 392 010
Finheat Ltd. Middle East and North Africa Fax +94 11 7 392 015
IE-Dublin 12, Walkinstown [email protected]
Tel. (+353)01/4564066 Egypt:
Fax (+353)01/4564071 Tiba Engineering Industries Co. Taiwan:
[email protected] Nasr City, Cairo Waxlink International Co., Ltd.
Tel. (+2) 02 / 40 22 866 8F No. 218 Roosevelt Rd., Sec. 6
Lithuania: Fax (+2) 02 / 40 44 771 Taipei, Taiwan
JSC Saldos Prekyba [email protected] Tel. (+886) 02 / 89 32 11 96
LT-78109 Siauliai Fax (+886) 02 / 89 32 11 97
Tel. (+37)041/540212 Israel: [email protected]
Fax (+37)041/596176 Lea Ventilation Industries Ltd.
[email protected] IL-27113 Kiriyat-Bialik, Israel Thailand:
Tel. (+972) 0 48 / 76 23 57 Wolter Ventilation Co., Ltd.
Netherlands: Fax (+972) 0 48 / 76 20 51 Thamai Kratumban Samutsakorn 74110
AirFan B. V. [email protected] Thailand
NL-7442 CX Nijverdal Tel. +66 (0) 3486 6555
Tel. (+31)054/8366366 United Arab Emirates, Kuwait, Fax +66 (0) 3486 6599
Fax (+31)054/8365320 Lebanon: [email protected]
[email protected] Wolter Ventilation LLC
Energy International Australia
Rucon B. V. Ventilatoren P.O. Box 3562 Sharjah, UAE
NL-3840 AG Harderwijk Tel. (+971) 06 / 53 43 477 The Sydney Fan Company.
Tel. (+31)034/1411670 Fax (+971) 06 / 53 43 756 NSW 2147, Sydney, Australia
Fax (+31)034/1411690 [email protected] Tel. +61 (0) 2 / 9624 4000
[email protected]
Fax +61 (0) 2 / 9624 4100
Österreich: Asia [email protected]
Wolter Werksvertretung Österreich China Mainland:
A-4040 Linz Taizhou Wolter Ventilation Co. Ltd.
Tel. (+43) 07 32 / 75 77 07 Hengjie, Luqiao District
Fax (+43)07 32 / 75 77 07 75 Taizhou City, Zhejiang
[email protected] Tel. (+86) 576 / 26 22 666 (26 52 888)
Fax (+86) 576 / 26 56 830

Wolter GmbH
Maschinen-und Apparatebau KG
Am Wasen 11
D-76316 Malsch / Germany
Tel. +49 (0) 7204/9201-0
Fax +49 (0) 7204/9201-11
www.wolter.eu
[email protected]
&
Air in Motion - Wolter Fans - www. wolterfans.de

Reference: A09-D, V2015/July, Printed in July, 2015

Dongguan Wolter Chemco Ventilation Ltd.(Wolter Asia) • Shipai / Dongguan / Guangdong / China
Tel. (+86)769 86557298 • Fax (+86)769 86557278 • www.wolterfans.com • [email protected]