A09-D Vane Axial Fans
A09-D Vane Axial Fans
- Direct Driven
- Belt Driven
A09-D
#
Dongguan Wolter Chemco Ventilation Ltd. certifies
that the series AXV-D shown herein are licensed to
bear the AMCA Seal. The ratings shown are based
on tests and procedures performed in accordance
with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA
Certified Ratings Program.
Table of Content
Contents
Page 1
Design Features
Page 2
Fan Selection
Page 3
Selection Sample
Page 3
Dimensions
Page 42~43
Accessories
Page 44
Sound Information
Page 45~47
A09-D V2015/July 1
Vane Axial Fans AXV-D
Technical information
Fan type code
AXV-D 800 / 20°
Pitch angle
AXV-D: impeller-Ø
500 ... 2800
Axial impeller blade type
Casing
Fan casings are made of steel, with flanges rolled on both sides. The pitch
circles of holes are in accordance with DIN 24 154, R2. The fan casings are
hot dipped galvanised as standard. Optional: Optimal corrosion protection
by powder-coating.
If motors require additional lubrication, tubes and grease-nipples are fitted
to the outside of the fan casing. An inspection hole, closed by a rubber plug,
allows controlling the direction of rotation.
Impellers
Hubs and impeller blades are made of highly corrosion resistant pressure-
cast aluminium alloy. The aero dynamical profile of the impeller blades
guarantees a high level of efficiency and low noise. The blade angle is
adjustable during standstill. The variable number of blades expands the
performance range. Dynamically balanced according to DIN ISO 1940-1,
balancing quality G6.3.
Sound levels
The ascertaining of sound level follows the Reverberant Room Method
according to AMCA 300. The A-weighted inlet sound power levels LwiA is
shown on the performance curves.
225 deg 135 deg
180 deg
Motor Mounting Position - Specify in degree
2 A09-D V2015/July
AXV-D
!"
Selection example
Required duty point
> Volume flow: 12 m3/s
Performance
Curve
10
AXV-D1120-6,
AXV-D 1120, 50
50 Hz !"
�������������������
AXV-D 1120, 1440, 960, 720
4
30 36°
> Static pressure: 588 Pa
•
7.5
34°
3 32°
At the point of intersection, the following data can be read: 200 800 j
q
300
> Pitch angle: 18 degrees
e k
150 600 s
f
> Absorbed power: 12,8 kW 36°
34°
> Sound Power Level: 111 dBA 200 a
m
32°
30°
100 400
b 28°
g n 26°
24°
22°
h 20°
c
100
st Setups
50 200 18°
16°
14°
12°
Lwi(A) a b c d e f g h j k m n p q r s
d
10° ��
4P 105 109 109 107 111 109 108 107 111 108 107 107 113 112 112 112 Speed
8°
Pd
��
6P 93 98 98 96 100 98 96 96 100 97 96 96 102 100 100 100 [min-1]
��
8P 84 91 90 87 92 90 88 88 92 89 88 88 94 93 92 92
0 0 0
Calculation of motor power 0
1440 1/min
0
20000
5 10
40000
15
60000
20
80000
25
100000
30
1440
2880
2-pol
4-pol
12,8 kW
st Setups
0 10000 20000 30000 40000 50000 720
960
Motor power: 15 kW 720 1/min
0 2.5 5 7.5 10 12.5 15
.
8-pol
6-pol
������������ [m³/h]
2) Calculation according to peak absorbed power, see table below the [m³/s]
over the whole pitch angle curve in. motor 2,2 3 4 5,5 7,5 11
1440 5,40 6,62 8,28 9,97 11,0 13,0 14,6 16,2 17,8 20,0 22,4 24,9 27,3 29,7 32,2 - -
motor 5,5 7,5 11 15 18,5* 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance is for The A-weighted sound ratings shown have been calculated per AMCA International
t Fan Auxil
installation type D - Ducted inlet, Ducted outlet. Performance ratings do not Standard 301. Values shown are for inlet LwiA sound power levels for installation
include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
A09-D V2015/March 13
Nozzles
Test Setups
st Fan Auxil
Nozzles
Test Fan
Test Fan Auxilliary Fan
Settling
means
Settling
ISO 5801 Figure 73b means
Outlet
ISO 5801chamber
Figure 73b
AMCA 210 Figure 12
ISO 5801 Figure 73b
The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV-D 500 to AXV-D 2800 as shown in the table below.
90
FEG90
FEG85
80
FEG80
FEG75
Fan Peak Total Efficiency (%)
70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50
40
30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)
4 A09-D V2015/July
Notes:
[kW]
power (kw)
0.1
Performance
Curve
AXV-D 500, 1440, 960, 720, 50Hz
AXV-D 500, 50 Hz !" Hub: 150-7
0.75
AbsorbedPower
0.2 36°
34°
Absorbed
32°
0.5 30°
28°
0.05 26°
0.1 24°
22°
0.25 20°
16° 18°
12°
14° ρ = 1,2 kg/m3
10°
8°
150
[PA]
∆pt(Pa)
Lwi(A) a b c d e f g h j k m n p q r s
80
Pressure
300 8P 74 74 73 72 75 74 75 75 71 71 70 72 71 72 72 72
70 125
Total
Total
250 p
60
100 q
j
50 200
e
k r
75
40 a
150 f
s
36°
30 m
34°
50
b
32°
100 g 30°
28°
20 n 26°
c 24°
25 22°
50 h
20°
10 18°
16°
14° Speed
d
Pd 10°
12° [min-1]
8°
0 0 0
0 2000 4000 6000 8000 10000 1440
1440 1/min 4-pol
0 0.5 1 1.5 2 2.5 3
A09-D V2015/July 5
AbsorbedPower [kW]
power(kw)
0.2
Performance
Curve
1.5
AXV-D 560, 1440, 960, 720, 50Hz
AXV-D 560, 50 Hz !" Hub: 169-7
0.4
0.15 36°
Absorbed
34°
0.3 1 32°
30°
0.1 28°
26°
0.2
24°
22°
0.5 20°
0.05 18°
0.1 14° 16°
12°
8° 10° ρ = 1,2 kg/m3
[PA]
∆p(Pa)
6P 86 87 86 85 89 89 90 90 85 84 84 85 84 84 84 84
pressure
8P 78 78 77 76 79 78 79 79 75 75 74 75 75 75 75 75
90
350
Total
150
Total
80 p
300
70 125 p
j
250
60 e
100 k
r
50 200 a
f
s
75
40 36°
150 m 34°
32°
b g
30 30°
50
28°
100 n 26°
20 c 24°
22°
h
25 20°
50 18°
10 16°
14° Speed
d 12° [min-1]
Pd 10°
8°
0 0 0
0 2000 4000 6000 8000 10000 12000 14000 1440
1440 1/min 4-pol
0 0.5 1 1.5 2 2.5 3 3.5 4
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 960
960 1/min
0 0.5 1 1.5 2 2.5 6-pol
6 A09-D V2015/July
(kw)
power [kW]
Performance
Curve
AXV-D 630, 1440, 960, 720, 50Hz
AXV-D 630, 50 Hz !" Hub: 189-7
0.75
Absorbed Power
0.3
36°
Absorbed
2 34°
32°
0.5 30°
0.2
28°
26°
24°
1 22°
0.1 0.25 20°
18°
14°
16° ρ = 1,2 kg/m3
12°
10°
8°
∆pt (Pa)
[PA]
Lwi(A) a b c d e f g h j k m n p q r s
Pressure
125 500 4P 102 103 102 102 108 108 109 109 102 101 101 103 101 101 101 101
6P 90 90 90 89 93 93 94 94 89 88 88 89 88 88 88 88
pressure
8P 81 82 80 80 83 82 83 83 79 78 78 79 79 79 79 79
200
Total
Total
100 400 p
q
150 j
75 300 e
k r
a
f
100 s
50 200 36°
m 34°
b 32°
g 30°
28°
n
50 26°
25 100 c 24°
22°
h
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]
8°
0 0 0
2500 5000 7500 10000 12500 15000 17500 20000 1440
1440 1/min
1 2 3 4 5 6 4-pol
A09-D V2015/July 7
[kW]
power(kw)
AbsorbedPower
0.6
Performance
Curve
AXV-D 710, 1440, 960, 720, 50Hz
AXV-D 710, 50 Hz !" Hub: 212-7
4
36°
34°
Absorbed
1
0.4 32°
30°
28°
26°
2 24°
0.5 22°
0.2
20°
16° 18°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
300
∆p(Pa)
Lwi(A) a b c d e f g h j k m n p q r s
t
4P 106 107 106 106 112 112 113 113 106 105 105 107 105 105 105 104
Pressure
6P 93 94 93 93 97 97 98 98 93 92 92 93 92 92 92 92
pressure
150 600 8P 85 85 84 84 87 86 87 87 83 82 82 83 83 83 83 83
250
Total
Total
p
125 500
200 q
j
100 400
e
k r
150
a
75 300 f
s
36°
m 34°
100
32°
50 200 b g 30°
28°
n
26°
c 24°
50 22°
25 100 h
20°
18°
14°
16° Speed
d 12° [min-1]
Pd 10°
8°
0 0 0
0 5000 10000 15000 20000 25000 30000 1440
1440 1/min 4-pol
0 1 2 3 4 5 6 7 8
8 A09-D V2015/July
[kW]
power(kw)
Performance
Curve
6 AXV-D 800, 1440, 960, 720, 50Hz
AXV-D 800, 50 Hz !" Hub: 250-6
36°
AbsorbedPower
1.5
0.6 34°
Absorbed
32°
4
30°
1 28°
0.4
26°
24°
2 22°
0.5 20°
0.2 18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
∆p(Pa)
t
200 p
Pressure
pressure
q
100 400 j
Total
Total
150 e k
75 300 f
s
36°
34°
a 32°
100 m
30°
50 200 b 28°
g n 26°
24°
22°
h
c 20°
50
25 100 18°
16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8°
4P 96 99 98 97 101 99 97 97 100 97 97 96 103 101 101 101 Speed
Pd
6P 83 88 87 85 90 88 86 85 89 86 86 85 91 90 90 90 [min-1]
8P 74 80 80 77 82 80 78 77 82 79 78 78 84 82 82 82
0 0 0
0 5000 10000 15000 20000 25000 30000 35000 40000 1440
1440 1/min 4-pol
0 1 2 3 4 5 6 7 8 9 10 11
0 2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 960
960 1/min
0 1 2 3 4 5 6 7 6-pol
A09-D V2015/July 9
[kW]
power (kw)
Performance
Curve
AXV-D 900, 1440, 960, 720, 50Hz
AXV-D 900, 50 Hz !" Hub: 281-6
3 10
AbsorbedPower
36°
34°
1
Absorbed
32°
2 30°
28°
5 26°
0.5 24°
22°
1 20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
p
250
Pressure
q
pressure
125 500 j
r
Total
Total
200
e k
100 400
s
f
150 36°
34°
75 300 a
m
32°
30°
b
28°
100 g n 26°
50 200 24°
22°
h
c 20°
18°
50 16°
25 100 14°
d
12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 99 103 102 100 105 102 101 100 104 101 101 100 107 105 105 105 Speed
Pd 6P 86 92 91 89 93 91 89 89 93 90 89 89 95 94 94 94 [min-1]
8P 78 84 83 81 86 84 81 81 85 82 82 81 87 86 86 86
0 0 0
10000 20000 30000 40000 50000 1440
1440 1/min
2 4 6 8 10 12 14 4-pol
2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 960
960 1/min
1 2 3 4 5 6 7 8 9 10 6-pol
2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 27500 720
720 1/min
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,212 0,272 0,352 0,431 0,450 0,512 0,575 0,637 0,699 0,790 0,884 0,980 1,07 1,17 1,27
motor 0,37 0,55 0,75 1,1 1,5
960 0,504 0,645 0,833 1,02 1,07 1,21 1,36 1,51 1,66 ,187 2,09 2,32 2,55 2,78 3,00
motor 0,55 0,75 1,1 1,5 2,2 3
1440 1,70 2,18 2,81 2,45 3,60 4,10 4,60 5,09 5,59 6,32 7,07 7,84 8,60 9,37 10,1
motor 2,2 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
10 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 1000, 1440, 960, 720, 50Hz
AXV-D 1000, 50 Hz !" Hub: 315-6
36°
AbsorbedPower
2
15 34°
4 32°
Absorbed
1.5 30°
10 28°
26°
1
2 24°
22°
20°
5 18°
0.5 16°
14°
10°
12° ρ = 1,2 kg/m3
8°
p
[PA]
∆pt(Pa)
175 700
300
Pressure
q
pressure
j
150 600
r
Total
Total
250
e k
125 500
s
f
200
36°
100 400 34°
a 32°
m
150 30°
b
75 300 28°
g n 26°
24°
100 22°
50 200 h 20°
c
18°
16°
50 14°
25 100 12°
d 10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 102 106 105 104 108 106 105 104 108 105 104 104 110 108 108 109 Speed
Pd 6P 90 95 94 92 97 95 93 93 97 94 93 93 99 97 97 97 [min-1]
8P 81 87 87 84 89 87 85 85 89 86 85 85 91 89 89 89
0 0 0
10000 20000 30000 40000 50000 60000 70000 80000 1440
1440 1/min 4-pol
2.5 5 7.5 10 12.5 15 17.5 20
5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 960
960 1/min
2 4 6 8 10 12 14 6-pol
A09-D V2015/July 11
[kW]
power (kw)
4
Performance
Curve
10 AXV-D 1120, 1440, 960, 720, 50Hz
AXV-D 1120, 50 Hz !" Hub: 353-6
30
AbsorbedPower
36°
34°
7.5
3
Absorbed
32°
30°
20
28°
2 5
26°
24°
22°
10 20°
1 2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
400 p
Pressure
pressure
q
200 800 j
r
Total
Total
300
e k
150 600 s
f
36°
34°
a 32°
200 m
30°
100 400 b 28°
g n 26°
24°
22°
h
c 20°
100
50 200 18°
16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 106 110 109 108 112 109 108 108 111 108 108 107 114 112 112 112 Speed
Pd 6P 93 99 98 96 101 98 97 96 100 97 97 96 102 101 101 101 [min-1]
8P 85 91 90 88 93 91 89 88 93 90 89 88 94 93 93 93
0 0 0
20000 40000 60000 80000 100000 1440
1440 1/min 4-pol
5 10 15 20 25 30
5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 720
720 1/min
2 4 6 8 10 12 14 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
720 0,670 0,858 1,11 1,36 1,42 1,62 1,81 2,01 2,20 2,49 2,79 3,09 3,39 3,69 4,00
motor 0,75 1,1 1,5 2,2 3 4
960 1,59 2,03 2,63 3,22 3,37 3,83 4,30 4,76 5,23 5,90 6,61 7,32 8,04 8,76 9,47
motor 2,2 3 4 5,5 7,5 11
1440 5,36 6,87 8,87 10,9 11,4 12,9 14,5 16,1 17,6 19,9 22,3 24,7 27,1 29,6 32,0
motor 5,5 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
12 A09-D V2015/July
[kW]
power(kw)
Performance
Curve
60 AXV-D 1250, 1440, 960, 720, 50Hz
AXV-D 1250, 50 Hz !" Hub: 420-6
36°
AbsorbedPower
15
6 34°
32°
Absorbed
40 30°
10 28°
4
26°
24°
22°
20
20°
2 5
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
Pressure t
[PA]
∆p(Pa)
300 1200
pressure
p
500
Total
j q
Total
250 1000
r
k
e
400
200 800
f
s
36°
300
a 34°
150 600 m 32°
b 30°
28°
g
200 n 26°
100 400 24°
22°
h
20°
c 18°
16°
100
50 200 14°
d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 4P 111 110 108 108 114 111 109 110 110 111 111 111 116 115 116 116 Speed
Pd 6P 100 100 99 98 103 100 98 99 99 101 100 100 105 105 105 106 [min-1]
8P 93 93 92 92 95 93 90 91 91 93 92 93 97 97 98 98
0 0 0
20000 40000 60000 80000 100000 120000 140000 1440
1440 1/min 4-pol
5 10 15 20 25 30 35 40
10000 20000 30000 40000 50000 60000 70000 80000 90000 100000 960
960 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 6-pol
A09-D V2015/July 13
[kW]
power (kw)
Performance
Curve
30
AXV-D 1400, 960, 720, 576, 50Hz
AXV-D 1400, 50 Hz !" Hub: 472-6
6
AbsorbedPower
36°
34°
10 32°
Absorbed
20 30°
4 28°
26°
24°
5 22°
2 10 20°
18°
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
400
250 700
Pressure
p
pressure
350
600 j q
Total
Total
200
r
300 k
e
500
250
f
150 s
400 36°
200 a 34°
m 32°
300 b 30°
100 28°
150 g
n 26°
24°
200 22°
h
100 20°
c 18°
50 16°
14°
100 12°
50 d
10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 104 104 102 102 107 104 102 102 103 105 103 104 109 109 110 110 Speed
Pd 8P 96 96 95 95 99 96 94 95 94 97 96 96 101 101 101 102 [min-1]
10P 90 91 90 90 93 90 88 89 88 91 90 90 95 95 95 96
0 0 0
20000 40000 60000 80000 100000 120000 140000 960
1440
960 1/min
5 10 15 20 25 30 35 40 4-pol
6-pol
10000 20000 30000 40000 50000 60000 70000 80000 90000 576
720
576 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 1,21 1,48 1,88 2,29 2,31 2,61 2,98 3,36 3,74 4,20 4,68 5,18 5,68 6,15 6,65
motor 2,2 3 4 5,5 7,5
720 2,35 2,89 3,68 4,47 4,51 5,09 5,82 6,55 7,30 8,20 9,14 10,1 11,0 12,0 13,0
motor 3 4 5,5 7,5 11 15
960 5,58 6,86 8,73 10,6 10,7 12,1 13,8 15,5 17,3 19,4 21,7 24,0 26,3 28,5 30,8
motor 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
14 A09-D V2015/July
[kW]
power (kw)
AbsorbedPower
Performance
Curve
60
AXV-D 1600, 960, 720, 576, 50Hz
AXV-D 1600, 50 Hz !" Hub: 539-6
36°
34°
10 20
Absorbed
32°
40 30°
28°
26°
10 24°
5 22°
20 20°
18°
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
Pressure
500
pressure
300 p
800
j q
Total
Total
400 r
250 k
e
600
200 f
s
300
36°
a 34°
m 32°
150
400 b 30°
200 28°
g
n 26°
24°
100 22°
h 20°
200 c 18°
100 16°
50 14°
d 12°
10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 108 108 106 106 111 108 106 107 107 109 108 108 113 113 114 114 Speed
Pd 8P 100 101 99 99 103 100 98 99 99 101 100 100 105 105 105 106 [min-1]
10P 94 95 94 94 97 94 92 93 92 95 94 94 99 99 99 100
0 0 0
25000 50000 75000 100000 125000 150000 175000 200000 960
225000 1440
960 1/min
10 20 30 40 50 60 4-pol
6-pol
A09-D V2015/July 15
[kW]
power (kw)
Performance
Curve
AXV-D 1800, 960, 720, 576, 50Hz
AXV-D 1800, 50 Hz !" Hub: 606-6
100
36°
AbsorbedPower
20 40
34°
32°
Absorbed
30°
28°
26°
20 50
10 24°
22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
1200
[PA]
∆pt(Pa)
Pressure
400
pressure
600 p
1000 j q
Total
350
Total
500 r
k
e
300
800
250 400 f s
36°
600 a 34°
200 m 32°
300
b 30°
28°
g
n 26°
150 400
24°
200 22°
h 20°
100
c 18°
16°
200 14°
100
d 12°
50 10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 111 111 110 110 114 111 109 110 110 112 112 112 117 117 117 118 Speed
Pd 8P 104 104 103 103 107 104 102 102 102 105 104 104 109 109 109 110 [min-1]
10P 98 98 98 97 100 98 95 96 96 99 98 98 102 102 103 103
0 0 0
50000 100000 150000 200000 250000 300000 960
1440
960 1/min 4-pol
6-pol
10 20 30 40 50 60 70 80
25000 50000 75000 100000 125000 150000 175000 200000 225000 720
960
720 1/min
10 20 30 40 50 60 6-pol
8-pol
16 A09-D V2015/July
[kW]
power (kw)
40
Performance
Curve
75
AXV-D 2000, 50 Hz
AXV-D 2000, 960, 720, 576, 50Hz
!" Hub: 674-6
36°
AbsorbedPower
150 34°
30 32°
Absorbed
50 30°
28°
100
20 26°
24°
22°
25 20°
10 50 18°
16°
14° ρ = 1,2 kg/m3
12°
10°
8°
1500
[PA]
∆pt(Pa)
800
500
Pressure
pressure
700 1250
j q
Total
Total
400 r
600 e k
1000
500 f
s
300
36°
750 a 34°
400 m 32°
b 30°
200 g 28°
300 n
26°
500
24°
22°
h
200 20°
c 18°
100 16°
250 14°
100 d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 6P 115 115 113 113 118 115 112 113 114 116 115 115 120 120 121 121 Speed
Pd 8P 107 107 106 106 110 107 105 106 106 108 107 107 112 112 112 113 [min-1]
10P 101 101 101 101 104 101 99 100 99 102 101 101 106 106 106 107
0 0 0
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5 960
1440
960 1/min 4-pol
6-pol
20 40 60 80 100 120
4 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 720
960
720 1/min 6-pol
10 20 30 40 50 60 70 80 90 8-pol
A09-D V2015/July 17
Absorbed Power [kW]
power (kw)
Performance
Curve
AXV-D 2200, 720, 576, 480, 50Hz
AXV-D 2200, 50 Hz !" Hub: 741-6
36°
30 100 34°
50
32°
Absorbed
30°
28°
20
26°
50 24°
25 22°
20°
10 18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
1000
∆pt (Pa)
[PA]
600
Pressure
400 p
pressure
j q
Total
350 800
500
Total
r
e k
300
400
600 f s
250
36°
a 34°
300 m 32°
200
b 30°
400 28°
g
n 26°
150
200 24°
22°
h
20°
100 c 18°
200 16°
100 14°
d 12°
50 10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 110 110 109 109 113 110 108 109 108 111 110 110 115 115 115 116 Speed
Pd 10P 104 104 104 104 106 104 102 102 102 105 104 104 109 109 109 110 [min-1]
12P 99 100 99 99 101 99 97 98 97 100 99 99 104 104 104 105
0 0 0
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5 720
1440
720 1/min 4-pol
20 40 60 80 100 120 8-pol
4 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 576
960
576 1/min
10 20 30 40 50 60 70 80 90 6-pol
10-pol
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
480
720
480 1/min
10 20 30 40 50 60 70 80 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 6,62 8,14 10,3 12,6 12,7 14,3 16,4 18,4 20,5 23,1 25,7 28,4 31,2 33,8 36,5
motor 7,5 11 15 18,5 22 30 37
576 11,4 14,1 17,9 21,7 21,9 24,8 28,3 31,9 35,5 39,9 44,4 49,2 53,9 58,4 63,1
motor 15 18,5 22 30 37 45 55 75
720 22,4 27,5 34,9 42,4 42,8 48,4 55,2 62,2 69,3 77,9 86,8 96,0 105,3 114,0 123,3
motor 30 37 45 55 75 90 110 132
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
18 A09-D V2015/July
AbsorbedPower [kW]
power(kw)
Performance
Curve
100 200 AXV-D 2400, 720, 576, 480, 50Hz
AXV-D 2400, 50 Hz !" Hub: 808-6
36°
34°
32°
Absorbed
40
30°
28°
50 100 26°
24°
20 22°
20°
18°
16°
14° ρ = 1,2 kg/m3
12°
10°
8°
1200
[PA]
∆p(Pa)
t
500
Pressure
700
pressure
1000 j q
Total
Total
600
400 r
e k
800
500
f
s
300
36°
400
600 a 34°
m 32°
b 30°
300 28°
200 g
n 26°
400
24 °
22°
200 h
20°
c 18°
100 16°
200 14°
100 d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 113 113 112 112 115 113 110 111 111 113 113 113 118 117 118 118 Speed
Pd 10P 107 107 106 106 109 107 104 105 105 108 106 107 111 111 112 112 [min-1]
12P 102 102 102 102 104 102 99 100 100 103 101 102 106 106 107 107
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140
5.0x10
4
1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 576
960
576 1/min 6-pol
20 40 60 80 100 120 10-pol
A09-D V2015/July 19
[kW]
power (kw)
Performance
Curve
AXV-D 2500, 720, 576, 480, 50Hz
AXV-D 2500, 50 Hz !" Hub: 842-6
36°
Absorbed Power
60 200
100 34°
32°
Absorbed
30°
40 28°
26°
50 100 24°
22°
20°
20
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
800
Pressure
1200
pressure
p
500
700 j q
Total
Total
1000
r
600 e k
400
800
500 f
s
36°
300
a 34°
400
600 m 32°
b 30°
28°
g
300 n 26°
200
400 24°
22°
h 20°
200
c 18°
16°
100
200 14°
100 d
12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 114 114 113 113 117 114 112 113 112 115 114 114 119 119 119 120 Speed
Pd 10P 108 108 108 107 110 108 105 106 106 109 108 108 113 112 113 113 [min-1]
12P 103 103 103 103 105 103 100 101 101 104 103 103 108 108 108 108
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140
5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
4.5x10
5
5.0x10
5
576
960
576 1/min 6-pol
20 40 60 80 100 120 140 10-pol
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
480
720
480 1/min
10 20 30 40 50 60 70 80 90 100 110 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 12,5 15,4 19,6 23,8 24,0 27,1 31,0 34,9 38,8 43,7 48,6 53,8 59,0 63,9 69,1
motor 15 18,5 22 30 37 45 55 75
576 21,7 26,6 33,8 41,1 41,5 46,9 53,5 60,3 67,1 75,4 84,0 93,0 102,0 110,4 119,5
motor 22 30 37 45 55 75 90 110 132
720 42,3 52,0 66,1 80,2 81,0 91,5 104,5 117,7 131,1 147,3 164,2 181,7 199,2 215,7 233,3
motor 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
20 A09-D V2015/July
AbsorbedPower [kW]
power(kw)
Performance
Curve
150 300 AXV-D 2600, 720, 576, 480, 50Hz
AXV-D 2600, 50 Hz !" Hub: 875-6
75 36°
34°
32°
Absorbed
100 200
30°
50 28°
26°
24°
100 22°
50
25 20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
1400
[PA]
∆p(Pa)
600
t
Pressure
pressure
800 p
1200
j q
Total
500
Total
700
r
k
1000 e
600
400
f s
500 800
36°
a 34°
300 m 32°
400
600 b 30°
g 28°
n 26°
200 300
24°
400 22°
h
20°
200 c 18°
16°
100 14°
200 12°
d
100 10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 115 115 114 114 118 115 113 114 114 116 115 115 120 120 120 121 Speed
Pd 10P 109 109 109 109 112 109 107 108 107 110 109 109 114 114 114 115 [min-1]
12P 104 105 104 104 106 104 102 103 102 105 104 104 109 109 109 110
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5 720
1440
720 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180 200
5.0x104 1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 4.5x105 5.0x105 5.5x105 576
960
576 1/min 6-pol
20 40 60 80 100 120 140 160 10-pol
5.0x104 1.0x105 1.5x105 2.0x105 2.5x105 3.0x105 3.5x105 4.0x105 4.5x105 720
480
480 1/min
20 40 60 80 100 120 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 15,2 18,7 23,8 28,9 29,2 33,0 37,7 42,4 47,2 53,1 59,1 65,5 71,8 77,7 84,1
motor 18,5 22 30 37 45 55 75 90
576 26,3 32,4 41,2 50,0 50,4 57,0 65,1 73,3 81,6 91,7 102,2 113,1 124,0 134,3 145,3
motor 30 37 45 55 75 90 110 132 160
720 51,4 63,2 80,4 97,6 98,5 111,3 127,1 143,1 159,4 179,2 199,6 220,9 242,2 262,3 283,7
motor 55 75 90 110 132 160 200 250 315
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 21
[kW]
power (kw)
125
Performance
Curve
AXV-D 2800, 720, 576, 480, 50Hz
AXV-D 2800, 50 Hz !" Hub: 942-6
200 400
Absorbed Power
36°
100 34°
Absorbed
300 32°
150
30°
75
28°
200 26°
100
50 24°
22°
20°
50 100 18°
25 16°
14° ρ = 1,2 kg/m3
12°
10°
8°
700
∆pt (Pa)
[PA]
1000
1500
Pressure
p
pressure
600 j q
Total
800 1250
Total
e k
500
1000
f
600 s
400 36°
a 34°
750 m 32°
300 b 30°
400 g
28°
n 26°
500 24°
200 22°
h
20°
c 18°
200 16°
250 14°
100 d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 117 118 116 116 120 117 115 116 116 118 117 118 122 122 122 123 Speed
Pd 10P 111 112 111 111 114 111 109 110 110 112 111 111 116 116 116 117 [min-1]
12P 106 107 107 106 109 106 104 105 105 107 106 106 111 111 111 112
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10 6.0x10
5 5
7.0x10
5
8.0x10
5 5 720
9.0x10 1440
720 1/min 4-pol
25 50 75 100 125 150 175 200 225 250 8-pol
5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 576
960
576 1/min
25 50 75 100 125 150 175 6-pol
200 10-pol
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 5
6.0x10 480
720
480 1/min
25 50 75 100 125 150 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
480 22,0 27,1 34,5 41,8 42,3 47,7 54,5 61,4 68,4 76,8 85,6 94,8 103,9 112,5 121,7
motor 22 30 37 45 55 75 90 110 132
576 38,1 46,9 59,6 72,3 73,0 82,5 94,2 106,1 118,1 132,8 148,0 163,8 179,5 194,4 210,3
motor 45 55 75 90 110 132 160 200 250
720 74,4 91,5 116,4 141,2 142,6 161,1 184,0 207,2 230,8 259,4 289,0 319,8 350,6 379,7 *410,7
motor 75 110 132 160 200 250 315 355 400 -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
22 A09-D V2015/July
AMCA - FEG rating
Fan Efficiency Grade - AXV-D !"
Certified FEGs are determined in accordance with AMCA 205-12 Energy Efficiency Classification
for fans. In conjunction with AMCA 211-05 (Rev. 6/12) Certified Ratings Program, Product Rating
Manual for Fan Air Performance. This classification is based on fan peak (optimum) total efficiency
for a given fan speed, fan size and application category. For the purpose of energy classification,
the peak efficiency can be determined at a speed not higher than the maximum design speed of
the fan.
The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV-D 500 to AXV-D 2800 as shown in the table below.
90
FEG90
FEG85
80
FEG80
FEG75
Fan Peak Total Efficiency (%)
70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50
40
30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)
A09-D V2015/July 23
Notes:
[kW]
power (kw)
Performance
Curve
1.5 AXV-D 500, 1728, 1152, 864, 60Hz
AXV-D 500, 60 Hz !" Hub: 150-7
0.4
AbsorbedPower
0.15 36°
Absorbed
34°
0.3 1 32°
30°
0.1 28°
26°
0.2
24°
22°
0.5
20°
0.05
0.1 18°
14°
16° ρ = 1,2 kg/m3
12°
10°
8°
125 500
[PA]
∆pt(Pa)
Lwi(A) a b c d e f g h j k m n p q r s
102 101 101 101 107 107 108 108 101 100 101 102 99 99 99 99
Pressure
4P
200 6P 88 88 88 87 92 92 93 92 87 86 86 87 86 86 86 86
pressure
8P 80 79 78 78 81 81 82 82 77 76 76 78 77 77 77 77
Total
100 400
Total
150
q
75 300 j
e
k r
100 a
f
50 200 s
36°
m 34°
b 32°
g 30°
28°
50 n
26°
25 100 c 24°
22°
h
20°
18°
14°
16° Speed
d 12° [min-1]
Pd 10°
8°
0 0 0
0 2000 4000 6000 8000 10000 12000 1728
1728 1/min 4-pol
0 0.5 1 1.5 2 2.5 3 3.5
24 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 560, 1728, 1152, 864, 60Hz
AXV-D 560, 60 Hz !" Hub: 169-7
0.75
AbsorbedPower
0.3
36°
2
Absorbed
34°
32°
0.5
0.2 30°
28°
26°
24°
1 22°
0.1 0.25 20°
16° 18°
12° 14°
8° 10° ρ = 1,2 kg/m3
[PA]
∆pt(Pa)
4P 105 105 105 105 111 111 112 112 105 104 105 106 103 103 103 103
250 6P 92 92 91 91 96 96 97 97 91 90 90 91 90 90 90 90
pressure
8P 83 83 82 82 85 85 86 86 81 80 80 82 81 81 81 81
Total
125 500
Total
p
200
p
100 400
j
e
150
k r
75 300
a
f
s
100 36°
m
34°
50 200
b 32°
g 30°
28°
n
26°
50 c 24°
25 100 h
22°
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]
8°
0 0 0
0 2500 5000 7500 10000 12500 15000 17500 1728
1728 1/min
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 4-pol
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 1152
1152 1/min
0 0.5 1 1.5 2 2.5 3 3.5 6-pol
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 864
864 1/min
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,076 0,090 0,104 0,118 0,131 0,143 0,162 0,186 0,211 0,229 0,247 0,265 0,283 0,301 0,319
motor 0,37
1152 0,181 0,214 0,246 0,279 0,311 0,339 0,383 0,441 0,500 0,543 0,586 0,628 0,671 0,714 0,757
motor 0,37 0,55 0,75 1,1
1728 0,610 0,721 0,829 0,940 1,05 1,14 1,29 1,49 1,69 1,83 1,98 2,12 2,26 2,41 2,55
motor 0,75 1,1 1,5 2,2 3
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 25
[kW]
power(kw)
AbsorbedPower
0.6
Performance
Curve
AXV-D 630, 1728, 1152, 864, 60Hz
AXV-D 630, 60 Hz !" Hub: 189-7
4
36°
Absorbed
1 34°
0.4 32°
30°
28°
26°
2 24°
0.2 0.5 22°
20°
16° 18°
14°
10° 12° ρ = 1,2 kg/m3
8°
[PA]
∆p(Pa)
Lwi(A) a b c d e f g h j k m n p q r s
t
4P 108 109 109 109 115 115 116 116 106 105 109 110 107 107 107 107
Pressure
175 700
8P 87 87 86 86 89 89 90 90 85 84 84 85 85 85 85 85
300
Total
Total
150 600
p
250
q
125 500
j
200 e
100 400 k r
a
f
150
s
75 300 36°
m 34°
b 32°
100 g
30°
50 200 28°
n
26°
c 24°
h 22°
50 20°
25 100
18°
14°
16° Speed
d
12° [min-1]
Pd 10°
8°
0 0 0
0 5000 10000 15000 20000 25000 1728
1728 1/min 4-pol
0 1 2 3 4 5 6 7
26 A09-D V2015/July
[kW]
power (kw)
1
Performance
Curve
AXV-D 710, 1728, 1152, 864, 60Hz
AXV-D 710, 60 Hz !" Hub: 212-7
7.5
AbsorbedPower
2 36°
Absorbed
34°
32°
5 30°
28°
0.5 26°
1 24°
22°
2.5 20°
16° 18°
12°
14° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
Lwi(A) a b c d e f g h j k m n p q r s
400
Pressure
4P 112 113 112 113 119 119 120 120 113 112 113 114 111 111 111 110
6P 99 100 99 99 104 104 105 105 98 98 98 99 97 98 98 97
pressure
8P 90 91 90 90 93 93 94 94 89 88 88 89 88 88 89 88
200 800
Total
Total
300
q
150 600 j
k r
200 a
f
100 400 s
36°
m 34°
32°
b
g 30°
28°
100 n 26°
50 200
c 24°
22°
h
20°
18°
16°
d 14° Speed
Pd 10°
12° [min-1]
8°
0 0 0
5000 10000 15000 20000 25000 30000 35000 1728
1728 1/min
1 2 3 4 5 6 7 8 9 10 4-pol
2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 1152
1152 1/min
1 2 3 4 5 6 7 6-pol
A09-D V2015/July 27
[kW]
power(kw)
Performance
Curve
10 AXV-D 800, 1728, 1152, 864, 60Hz
AXV-D 800, 60 Hz !" Hub: 250-6
36°
AbsorbedPower
1 34°
7.5 32°
Absorbed
2 30°
28°
5 26°
0.5 24°
1 22°
20°
2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
p
∆p(Pa)
Pressure t
150 600 q
pressure
j
250
r
Total
Total
125 500
e k
200
s
f
100 400 36°
34°
150 a 32°
m
75 300 30°
b 28°
g n 26°
100 24°
50 200 22°
h 20°
c
18°
16°
50 14°
25 100
12°
d 10° Lwi(A) a b c d e f g h j k m n p q r s
8° 4P 102 104 104 102 106 104 103 102 106 103 102 102 108 106 107 107 Speed
Pd 6P 88 93 92 90 95 92 91 90 94 91 91 90 97 95 95 95 [min-1]
8P 80 85 84 82 87 85 83 82 87 84 83 83 89 87 87 87
0 0 0
5000 10000 15000 20000 25000 30000 35000 40000 45000 1728
1728 1/min 4-pol
1 2 3 4 5 6 7 8 9 10 11 12 13
2500 5000 7500 10000 12500 15000 17500 20000 22500 864
864 1/min
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,207 0,265 0,342 0,419 0,438 0,499 0,559 0,620 0,680 0,768 0,860 0,953 1,05 1,14 1,23
motor
1152 0,490 0,627 0,811 0,994 1,04 1,18 1,32 1,47 1,61 1,82 2,04 2,26 2,48 2,70 2,92
motor
1728 1,65 2,12 2,74 3,35 3,50 3,99 4,47 4,96 5,44 6,15 6,88 7,63 8,37 9,12 9,86
motor
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
28 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 900, 1728, 1152, 864, 60Hz
AXV-D 900, 60 Hz !" Hub: 281-6
2 36°
AbsorbedPower
15 34°
4 32°
Absorbed
30°
10 28°
26°
1
2 24°
22°
20°
5 18°
16°
14°
12°
10° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
p
200 800
350
Pressure
pressure
q
j
175
Total
300 r
Total
150 600 e k
250
s
f
125 36°
200 34°
a
m 32°
100 400
30°
b
150 28°
g n 26°
75
24°
22°
100 c h 20°
50 200 18°
16°
14°
50 12°
25 d
a b c d e f g h
Lwi(A) j k m n p q r s
10°
Pd 8° 4P 106 108 107 106 110 108 107 106 109 107 106 106 112 110 110 110 Speed
6P 92 97 96 94 98 96 94 94 98 95 94 94 100 99 99 99 [min-1]
8P 83 89 88 86 90 88 87 86 90 87 86 86 92 91 91 91
0 0 0
10000 20000 30000 40000 50000 60000 1728
1728 1/min 4-pol
2 4 6 8 10 12 14 16 18
5000 10000 15000 20000 25000 30000 35000 40000 45000 1152
1152 1/min
2 4 6 8 10 12 6-pol
A09-D V2015/July 29
[kW]
power (kw)
4
Performance
Curve
30
AXV-D 1000, 1728, 1152, 864, 60Hz
AXV-D 1000, 60 Hz !" Hub: 315-6
36°
AbsorbedPower
7.5 34°
3 32°
Absorbed
20 30°
28°
5
2 26°
24°
22°
10 20°
1 2.5 18°
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
p
Pressure
250 1000
pressure
q
400 j
Total
r
Total
200 800
e
k
300 f s
36°
150 600
34°
a
32°
m
30°
200 b
28°
100 400 g n 26°
24°
22°
h
c 20°
100 18°
50 200 16°
14°
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 109 112 111 110 113 111 111 110 113 110 110 109 116 114 114 114 Speed
Pd 6P 95 100 99 97 102 100 98 98 101 98 98 98 104 102 102 102 [min-1]
8P 87 92 92 89 94 92 90 90 94 91 90 90 96 94 94 94
0 0 0
10000 20000 30000 40000 50000 60000 70000 80000 90000 1728
1728 1/min 4-pol
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25
5000 10000 15000 20000 25000 30000 35000 40000 45000 864
864 1/min
2 4 6 8 10 12 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 0,653 0,836 1,08 1,32 1,38 1,57 1,76 1,96 2,15 2,42 2,71 3,00 3,30 3,60 3,89
motor 0,75 1,1 1,5 2,2 3 4
1152 1,55 1,98 2,56 3,14 3,28 3,73 4,18 4,64 5,09 5,75 6,43 7,13 7,83 8,53 9,22
motor 2,2 3 4 5,5 7,5 11
1728 5,22 6,68 8,64 10,6 11,1 12,6 14,1 15,6 17,2 19,4 21,7 24,1 26,4 28,8 31,1
motor 5,5 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
30 A09-D V2015/July
[kW]
power(kw)
AbsorbedPower
Performance
Curve
60 AXV-D 1120, 1728, 1152, 864, 60Hz
AXV-D 1120, 60 Hz !" Hub: 353-6
15 36°
6
34°
Absorbed
40 32°
30°
10
4 28°
26°
24°
20 22°
5 20°
2 18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
600
∆p(Pa)
p
t
Pressure
pressure
300 1200
q
500 j
Total
Total
250 1000
e
k
400
f s
200 800
36°
34°
300 a 32°
m
150 600 30°
b
28°
g n 26°
200 24°
100 400 22°
c h 20°
18°
16°
100 14°
50 200
12°
d Lwi(A) a b c d e f g h j k m n p q r s
10°
8° 4P 112 115 115 114 117 115 114 113 116 114 113 113 119 117 117 118 Speed
Pd 6P 99 104 103 101 105 103 102 101 105 102 102 101 107 106 106 106 [min-1]
8P 90 96 95 93 98 96 94 93 97 94 94 93 99 98 98 98
0 0 0
20000 40000 60000 80000 100000 120000 1728
1728 1/min 4-pol
5 10 15 20 25 30 35
10000 20000 30000 40000 50000 60000 70000 80000 90000 1152
1152 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 6-pol
A09-D V2015/July 31
[kW]
power (kw)
Performance
Curve AXV-D 1250, 60 Hz
AXV-D 1250, 1728, 1152, 864, 60Hz
!" Hub: 420-6
30 100
AbsorbedPower
36°
10 34°
Absorbed
32°
20 30°
28°
50 26°
5 24°
22°
10 20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
450 800
Pressure
1750
pressure
p
400 700
Total
j q
1500
Total
350 r
600 k
e
1250
300
500 f
s
10000 20000 30000 40000 50000 60000 70000 80000 90000 864
864 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
864 2,26 2,78 3,53 4,29 4,33 4,89 5,59 6,29 7,01 7,88 8,78 9,71 10,6 11,5 12,5
motor 3 4 5,5 7,5 11 15
1152 5,36 6,59 8,38 10,2 10,3 11,6 13,2 14,9 16,6 18,7 20,8 23,0 25,2 27,3 29,6
motor 5,5 7,5 11 15 18,5 22 30
1728 18,1 22,2 28,3 34,3 34,7 39,1 44,7 50,3 56,1 63,0 70,2 77,7 85,2 92,2 99,8
motor 18,5 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
32 A09-D V2015/July
[kW]
power (kw)
AbsorbedPower
Performance
Curve
AXV-D 1400, 1152, 864, 691, 60Hz
AXV-D 1400, 60 Hz !" Hub: 472-6
20 36°
10
34°
40
Absorbed
32°
30°
28°
26°
5 10 24°
20 22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
1000
350
Pressure
pressure
p
500
j q
Total
300
Total
800
k r
e
400
250
f
s
600
200 36°
300 a 34°
m 32°
b 30°
150 28°
400 g
n 26°
200
24°
22°
100 h
20°
c 18°
200 16°
100 14°
50 d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 6P 108 108 107 106 112 109 107 108 108 110 109 110 114 114 114 115 Speed
Pd 8P 101 101 100 100 104 101 99 100 100 102 101 101 106 106 106 107 [min-1]
10P 95 95 94 94 98 95 93 94 93 96 95 95 100 100 100 101
0 0 0
25000 50000 75000 100000 125000 150000 175000 1152
1728
1152 1/min
5 10 15 20 25 30 35 40 45 50 4-pol
6-pol
10000 20000 30000 40000 50000 60000 70000 80000 90000 100000 691
864
691 1/min
5 10 15 20 25 30 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 2,08 2,56 3,26 3,95 3,99 4,51 5,15 5,80 6,46 7,26 8,09 8,95 9,81 10,6 11,5
motor 2,2 3 4 5,5 7,5 11 15
864 4,07 5,00 6,36 7,72 7,79 8,80 10,1 11,3 12,6 14,2 15,8 17,5 19,2 20,7 22,4
motor 5,5 7,5 11 15 18,5 22 30
1152 9,64 11,8 15,1 18,3 18,5 20,9 23,8 26,8 29,9 33,6 37,4 41,4 45,4 49,2 53,2
motor 11 15 18,5 22 30 37 45 55
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 33
[kW]
power (kw)
Performance
Curve
AXV-D 1600, 1152, 864, 691, 60Hz
AXV-D 1600, 60 Hz !" Hub: 539-6
100
AbsorbedPower
20 40 36°
34°
Absorbed
32°
30°
28°
26°
20 50
10 24°
22°
20°
18°
16°
12°
14° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
Pressure
450 700
pressure
1200 p
j q
400
Total
Total
600
r
1000 k
350 e
500
300
800 f s
36°
250 400
a 34°
m 32°
600
b 30°
200
300 28°
g
n 26°
150 24°
400 22°
200 h
20°
100 c 18°
16°
200 14°
100 d 12°
50 10° a b c
Lwi(A) d e f g h j k m n p q r s
8° 6P 113 112 111 111 116 113 111 112 112 114 113 114 118 118 118 119 Speed
Pd 8P 105 105 104 104 108 105 103 104 104 106 105 105 110 110 111 111 [min-1]
10P 99 99 98 98 102 99 97 98 98 100 99 99 104 104 104 105
0 0 0
50000 100000 150000 200000 250000 1152
1728
1152 1/min
10 20 30 40 50 60 70 4-pol
6-pol
34 A09-D V2015/July
[kW]
power (kw)
40
Performance
Curve
75
AXV-D 1800, 1152, 864, 691, 60Hz
AXV-D 1800, 60 Hz !" Hub: 606-6
36°
AbsorbedPower
150 34°
30 32°
Absorbed
30°
50
28°
100
20 26°
24°
22°
25 20°
10 50 18°
16°
12°
14° ρ = 1,2 kg/m3
10°
8°
1750
[PA]
∆pt(Pa)
600
Pressure
pressure
p
1500
800 j q
Total
500
Total
r
1250 k
e
400
600
f
1000 s
36°
a 34°
300 m 32°
750 b 30°
400
g
28°
n 26°
200 24°
500 22°
h
20°
200 c 18°
16°
100 14°
250
d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 6P 116 116 114 114 119 116 114 115 116 117 117 118 122 122 122 123 Speed
Pd 8P 109 109 107 107 111 109 106 107 107 109 109 109 114 114 114 115 [min-1]
10P 103 103 102 102 105 103 100 101 101 104 103 103 108 107 108 108
0 0 0
50000 100000 150000 200000 250000 300000 350000 1152
1728
1152 1/min 4-pol
6-pol
10 20 30 40 50 60 70 80 90 100
25000 50000 75000 100000 125000 150000 175000 200000 225000 691
864
691 1/min
5 10 15 20 25 30 35 40 45 50 55 60 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 7,27 8,93 11,4 13,8 13,9 15,7 18,0 20,2 22,5 25,3 28,2 31,2 34,2 37,0 40,1
motor 7,5 11 15 18,5 22 30 37 45
864 14,2 17,4 22,2 26,9 27,2 30,7 35,1 39,5 44,0 49,4 55,1 61,0 66,8 72,4 78,3
motor 15 18,5 30 37 45 55 75 90
1152 33,6 41,4 52,6 63,8 64,5 72,8 83,1 93,6 104,3 117,2 130,6 144,5 158,5 171,6 185,6
motor 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 35
[kW]
power (kw)
Performance
Curve
300
AXV-D 2000, 60 Hz
AXV-D 2000, 1152, 864, 691, 60Hz
!" Hub: 674-6
36°
AbsorbedPower
34°
50 100 32°
Absorbed
30°
200
28°
26°
24°
25 50 22°
100 20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
1200
Pressure
2000
700
pressure
1000
Total
j q
Total
600
r
e k
1500
800
500
f
s
36°
400
600 a 34°
1000 m 32°
b 30°
300 g 28°
n 26°
400
24°
22°
200 h 20°
500
c 18°
16°
200 14°
100 d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 6P 119 119 118 117 123 120 118 119 119 120 120 121 125 125 125 126 Speed
Pd 8P 112 112 111 110 115 112 110 111 111 113 112 112 117 117 117 118 [min-1]
10P 106 106 105 105 109 106 104 105 104 107 106 106 111 111 111 112
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 1152
1728
1152 1/min 4-pol
6-pol
20 40 60 80 100 120 140
4 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 864
1152
864 1/min 6-pol
10 20 30 40 50 60 70 80 90 100 8-pol
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
691
864
691 1/min
10 20 30 40 50 60 70 80 10-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
691 12,3 15,1 19,2 23,3 23,6 26,6 30,4 34,2 38,1 42,8 47,7 52,8 57,9 62,7 67,8
motor
864 24,0 29,5 37,5 45,5 46,0 52,0 59,3 66,8 74,4 83,6 93,2 103,1 113,1 122,4 132,4
motor
1152 56,9 70,0 89,0 108,0 109,0 123,1 140,6 158,4 176,4 198,3 220,9 244,5 268,0 290,2 313,9
motor
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
36 A09-D V2015/July
[kW]
power (kw)
Performance
Curve AXV-D 2200, 60 Hz
AXV-D 2200, 864, 691, 576, 60Hz
!" Hub: 741-6
100 200
36°
Absorbed Power
34°
50
32°
Absorbed
30°
28°
26°
50 100
24°
25 22°
20°
18°
16°
14°
12° ρ = 1,2 kg/m3
10°
8°
[PA]
∆pt(Pa)
1400
600
Pressure
pressure
p
800
1200 j q
Total
500
Total
r
k
e
1000
600
400
f s
800 36°
a 34°
300 m 32°
400 b 30°
600
28°
g
n 26°
200 24°
400 22°
h 20°
200 c 18°
16°
100 14°
200 12°
d
10°
Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 115 115 114 113 118 115 113 113 114 116 115 115 120 120 120 121 Speed
Pd 10P 109 109 108 108 112 109 107 107 107 110 109 109 114 114 114 115 [min-1]
12P 104 104 103 104 106 104 102 102 102 105 104 104 109 109 109 110
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5 5 864
5.0x10 1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140
4 5 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 691
4.0x10 1152
691 1/min 6-pol
10 20 30 40 50 60 70 80 90 100 110 10-pol
4 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 864
576
576 1/min
10 20 30 40 50 60 70 80 90 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 11,4 14,1 17,9 21,7 21,9 24,8 28,3 31,9 35,5 39,9 44,4 49,2 53,9 58,4 63,1
motor 15 18,5 22 30 37 45 55 75
691 19,8 24,3 30,9 37,5 37,9 42,8 48,9 55,0 61,3 68,9 76,8 85,0 93,1 100,9 109,1
motor 22 30 37 45 55 75 90 110
864 38,6 47,5 60,4 73,3 74,0 83,6 95,4 107,5 119,7 134,6 149,9 165,9 181,9 197,0 213,1
motor 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 37
[kW]
power(kw)
100
Performance
Curve
AXV-D 2400, 864, 691, 576, 60Hz
AXV-D 2400, 60 Hz !" Hub: 808-6
34°
75 32°
Absorbed
30°
100 200 28°
50 26°
24 °
22°
50 100 20°
25 18 °
16°
14°
10°
12° ρ = 1,2 kg/m3
8°
[PA]
∆p(Pa)
t
700
Pressure
1000
p
pressure
1500
j q
Total
600
Total
r
800 1250 e
k
500
f
1000 s
600 36 °
400
a 34°
m 32°
750 30°
b
300 28°
400 g
n 26°
24°
500 22°
200 h 20°
c 18 °
200 16°
14°
250
100 d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 117 118 116 116 120 117 115 116 116 118 118 118 123 123 123 124 Speed
Pd 10P 111 112 111 111 114 111 109 110 110 112 111 112 116 116 117 117 [min-1]
12P 107 107 106 106 109 107 104 105 105 108 106 107 111 111 112 112
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5 864
1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
691
1152
691 1/min 6-pol
20 40 60 80 100 120 140 10-pol
4.5x10 576864
4 5 5 5 5 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 3.0x10 3.5x10 4.0x10
576 1/min
20 40 60 80 100 120 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 17,7 21,7 27,6 33,5 33,8 38,2 43,6 49,2 54,7 61,5 68,6 75,9 83,2 90,0 97,4
motor 18,5 22 30 37 45 55 75 90 110
691 30,5 37,5 47,7 57,9 58,5 66,0 75,4 84,9 94,6 106,3 118,5 131,1 143,7 155,7 168,4
motor 37 45 55 75 90 110 132 160 200
864 59,6 73,3 93,2 113,1 114,2 129,0 147,3 165,9 184,8 207,7 231,4 256,1 280,7 304,0 328,8
motor 75 110 132 160 200 250 315 355
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
38 A09-D V2015/July
[kW]
power (kw)
Performance
Curve
AXV-D 2500, 864, 691, 576, 60Hz
AXV-D 2500, 60 Hz !" Hub: 842-6
200 400
Absorbed Power
36°
100 34°
Absorbed
32°
30°
28°
800
Pressure
pressure
1000 j q
Total
1500
Total
r
600 e
k
800
f s
1000 36°
600 a
34°
400 m 32°
b 30°
28°
g
n 26°
400
24°
22°
500 h
200 20°
c 18°
16°
200 14°
d 12°
10° a b c d e f g h
Lwi(A) j k m n p q r s
8° 8P 119 119 117 117 121 119 116 117 117 119 119 119 124 124 124 125 Speed
Pd 10P 113 113 112 112 115 113 110 111 111 114 113 113 118 118 118 118 [min-1]
12P 108 108 108 107 110 108 105 106 106 109 108 108 113 112 113 113
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5 864
1728
864 1/min 4-pol
8-pol
20 40 60 80 100 120 140 160 180 200
5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 691
6.0x10 1152
691 1/min 6-pol
20 40 60 80 100 120 140 160 10-pol
5.0x104 1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
4.5x10
5
5.0x10
5
864
576
576 1/min
20 40 60 80 100 120 140 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 21,7 26,6 33,9 41,1 41,5 46,9 53,5 60,3 67,1 75,4 84,1 93,0 102,0 110,4 119,5
motor 22 30 37 45 55 75 90 110 132
691 37,4 46,0 58,5 71,0 71,7 81,0 92,5 104,1 116,0 130,4 145,2 160,7 176,2 190,8 206,4
motor 45 55 75 90 110 132 160 200 250
864 73,1 89,8 114,2 138,7 140,0 158,1 180,6 203,4 226,5 254,6 283,7 314,0 344,2 372,7 *403,2
motor 75 90 132 160 200 250 315 355 400 -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 39
AbsorbedPower [kW]
power (kw)
150
Performance
Curve AXV-D 2600, 60 Hz
AXV-D 2600, 864, 691, 576, 60Hz
!" Hub: 875-6
36°
400 34°
200
32°
Absorbed
100 30°
28°
26°
2000
1250
Pressure
pressure
p
Total
750 j q
Total
1000
1500 k
r
e
f
750 s
500
36°
1000 a 34°
m 32°
b 30°
500 g
28°
n 26°
24°
250 22°
h
500 20°
c 18°
250 16°
14°
d 12°
10° Lwi(A)a b c d e f g h j k m n p q r s
8° 8P 120 120 119 118 123 120 118 119 119 121 120 120 125 125 125 126 Speed
Pd 10P 114 114 113 113 117 114 112 113 112 115 114 114 119 119 119 120 [min-1]
12P 109 109 109 109 112 109 107 108 107 110 109 109 114 114 114 115
0 0 0
1.0x105 2.0x10
5
3.0x10
5
4.0x10 5.0x10
5 5
6.0x10
5
7.0x10
5
8.0x10
5 864
1728
864 1/min 4-pol
8-pol
25 50 75 100 125 150 175 200 225
5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 691
1152
691 1/min 6-pol
25 50 75 100 125 150 175 10-pol
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
576
864
576 1/min
25 50 75 100 125 150 12-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 26,3 32,4 41,2 50,0 50,5 57,0 65,1 73,3 81,6 91,7 102,2 113,1 124,0 134,3 145,3
motor 30 37 45 55 75 90 110 132 160
691 45,5 55,9 71,1 86,3 87,2 98,5 112,4 126,6 141,0 158,5 176,6 195,5 214,3 232,1 251,0
motor 55 75 90 110 132 160 200 250 315
864 88,9 109,3 138,9 168,6 170,3 192,3 219,6 247,4 275,5 309,6 345,0 381,8 *418,6 453,3 490,3
motor 90 110 160 200 250 315 355 400 - - -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
40 A09-D V2015/July
[kW]
power (kw)
200
Performance
Curve
AXV-D 2800, 864, 691, 576, 60Hz
AXV-D 2800, 60 Hz !" Hub: 942-6
36°
Absorbed Power
30°
28°
200 400
26°
100
24°
22°
20°
100 200
50 18°
16°
14°
12°
10° ρ = 1,2 kg/m3
8°
[PA]
∆pt(Pa)
1000
Pressure
p
pressure
2000
1250 j q
Total
Total
r
750 k
e
1000
1500
f s
36°
750 a 34°
500
m 32°
1000 b 30°
28°
g
n 26°
500
24°
22°
h 20°
250
500 c 18°
16°
250 14°
d 12°
10° Lwi(A) a b c d e f g h j k m n p q r s
8° 8P 122 122 121 121 125 122 120 121 121 123 122 123 127 127 128 128 Speed
Pd 10P 116 116 115 115 119 116 114 115 115 117 116 116 121 121 121 122 [min-1]
12P 111 112 111 111 114 111 109 110 110 112 111 111 116 116 116 117
0 0 0
2.0x105 4.0x10
5
6.0x10
5
8.0x10
5
1.0x10
6 864
1728
864 1/min 4-pol
8-pol
50 100 150 200 250 300
5 5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 8.0x10 691
1152
691 1/min 6-pol
25 50 75 100 125 150 175 200 225 10-pol
1.0x105 2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5
864
576
576 1/min
25 50 75 100 125 150 175 20012-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
576 38,1 46,9 59,6 72,3 73,0 82,5 94,2 106,1 118,2 132,8 148,0 163,8 179,5 194,4 210,3
motor 45 55 75 90 110 132 160 200 250
691 65,9 81,0 103,0 125,0 126,2 142,5 162,8 183,3 204,2 229,5 255,7 283,0 310,2 336,0 363,4
motor 75 90 110 132 160 200 250 315 355 400
864 128,6 158,2 201,1 244,1 246,5 278,4 317,9 358,1 398,8 *448,2 499,4 552,7 605,9 656,2 709,7
motor 160 250 315 355 400 - - - - - -
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Power rating (kW) does not include transmission losses.
A09-D V2015/July 41
Vane Axial Flow Fans
Dimensions AXV-D
ØTk Optional
Direct Driven s
ØDa
ØDa
ØDi
ØDi
z x Ød
hF
k1 bF k1
E
I1 L I1
F
Belt Driven
z x Ød
Air flow
hF2
ØDa
ØTk
ØDi
hF
bF
K1 E
I1 F
LH/1 LH/2
Model s k1 l1 motor s k1 l1 motor
size [mm] [mm] [mm] max. [mm] [mm] [mm] max.
500 2 327 401 112
560 2 327 401 112 3 624 700 160
630 2 327 401 112 3 624 700 160
710 2,5 326 401 112 2,5 490 565 132
800 2,5 316 401 112 3 614 700 160
900 3 429 515 132 4 612 700 160
1000 3 429 515 132 4 692 780 180
1120 4 522 630 160 4 892 1000 200
1250 4 522 630 160 4 892 1000 225
1400 4 892 1000 225
1600 4 892 1000 280
We reserve the right to alter measurements without notice in case of technical improvements.
42 A09-D V2015/July
Vane Axial Flow Fans
Dimensions !"
z - Ød
Ø Da
Ø Tk
Ø Di
hF
L2 E
L3 L1 F
Baugröße Da Di hF zxd Tk E F L1 L2 L3
size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1800 2010 1805 1120 24x18 1920 1660 1800 400 1200 1400
2000 2210 2005 1165 32x18 2120 1820 2000 445 1300 1500
2200 2440 2205 1265 32x18 2340 2020 2200 490 1400 1650
2400 2630 2405 1370 32x18 2530 2220 2400 550 1500 1800
2500 2740 2505 1420 36x24 2640 2320 2500 555 1530 1820
2600 2840 2605 1470 36x24 2740 2380 2600 590 1580 1850
2800 3150 2805 1570 36x24 3000 2500 2800 1300 1680 1900
We reserve the right to alter measurements without notice in case of technical improvements.
A09-D V2015/July 43
63
Vane Axial Flow Fans
Dimensions
Accessories AXV-D
zx d
Ø Da
Ø Da
DDa
Ø Tk
Ø Tk
Ø Di
Ø Di
Da
Tk
Di
Da
Tk
Di
zx d
Ld
30 Le Lk U
We reserve the right to alter measurements without notice in case of technical improvements.
44 A09-D V2015/July
Sound Information
30
a: without reflexion
25 b: with reflexion
/ noise reduction
15 b
Pegelabnahme
10
0
0,5 0,6 0,8 1 2 3 4 5 6 7 8 9 10
Distance [m]
Entfernung / distance [m]
Frequencies
Sound is split into different frequencies. Frequencies of human hearing range from about 20 cycles per second (Hz) to 20.000 cycles per second (Hz). For
practical purposes, WOLTER publishes noise data in eight octave bands with the centre frequencies of (63,) 125, 250, 500, 1000, 2000, 4000 and 8000 Hz.
Each fan has its own specific correction factor which is to be deducted from sound power according to the octave band.
Table 2)
Addition of sound levels Difference between two sound levels Add to the higher level
[dB] [dB]
0-1 3
2-3 2
4-9 1
>
=10 0
where:
L∑ = 10 · lg(10 0,1·L1 + 10 0,1·L2 + ... + 10 0,1·Ln ) L1 = sound level of a source 1
L∑ = resulting summation sound level
A09-D V2015/July 45
Vane Axial Flow Fans
Sound Information
Fan Model Poles 63 125 250 500 1000 2000 4000 8000
Size [-] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz]
4 -6 -3 -8 -17 -25 -28 -30 -34
500 6 -3 -5 -12 -21 -25 -27 -30 -35
8 -2 -6 -13 -20 -22 -24 -28 -33
4 -6 -3 -8 -18 -26 -29 -31 -35
560 6 -3 -6 -12 -22 -26 -28 -31 -36
8 -2 -6 -14 -20 -23 -25 -29 -34
4 -6 -3 -8 -18 -27 -29 -32 -35
630 6 -2 -6 -12 -22 -26 -29 -31 -36
8 -2 -6 -14 -21 -24 -26 -30 -35
4 -6 -3 -9 -19 -27 -30 -32 -36
710 6 -2 -6 -13 -23 -27 -29 -32 -37
8 -2 -6 -14 -22 -24 -27 -30 -36
4 -8 -3 -7 -16 -18 -19 -21 -27
800 6 -4 -4 -12 -15 -17 -18 -22 -31
8 -3 -6 -13 -14 -15 -17 -23 -33
4 -8 -2 -7 -16 -18 -20 -21 -28
900 6 -4 -4 -13 -16 -18 -18 -22 -32
8 -2 -6 -13 -14 -16 -17 -24 -34
4 -7 -2 -8 -17 -19 -20 -22 -28
1000 6 -4 -4 -13 -16 -18 -19 -23 -32
8 -2 -6 -13 -15 -16 -18 -24 -35
4 -7 -2 -8 -17 -19 -21 -22 -29
1120 6 -4 -4 -13 -17 -19 -20 -24 -33
8 -2 -6 -14 -15 -17 -18 -25 -35
4 -7 -4 -8 -10 -13 -16 -18 -24
1250 6 -5 -5 -9 -11 -14 -17 -21 -29
8 -3 -7 -9 -12 -15 -18 -23 -33
6 -5 -5 -10 -12 -15 -18 -22 -30
1400 8 -4 -7 -9 -12 -15 -18 -24 -33
10 -4 -7 -9 -12 -15 -18 -25 -34
6 -5 -5 -10 -12 -16 -18 -22 -31
1600 8 -3 -7 -10 -12 -16 -18 -24 -34
10 -3 -7 -9 -12 -15 -19 -26 -35
• Sound power frequency spectrum calculated with this Lwrel are not licensed by AMCA International.
46 A09-D V2015/July
Sound Information
A09-D V2015/July 47
Tubular Sound Attenuator for AXV-D
SA, SPA
ØDSa
Size DSa Tk Di ls 1 Length Type Pitch angle Octave band mid-frequency [Hz]
x 1D x 2D SA-1D SPA-1D SA-2D SPA-2D
[mm] [mm] [mm] [mm] [mm] [kg] [kg] [kg] [kg] setting 63 125 250 500 1k 2k 4k 8k
1D SA-1D all 2 4 6 10 14 10 7 8
355 459 405 359 355 710 12 18 16 23 SPA-1D low 4 6 8 13 20 21 18 16
400 601 448 401 400 800 14 23 19 29 med 4 6 8 12 18 19 18 14
450 650 497 450 450 900 18 29 23 36 high 4 6 8 11 13 16 16 11
2D SA-2D low 4 7 12 18 22 17 12 13
med 4 7 11 17 21 17 13 12
high 4 7 10 15 19 16 13 10
SPA-2D low 7 10 15 24 32 35 30 28
med 7 10 15 21 26 26 24 22
high 7 10 15 16 15 17 13 13
500 704 551 504 500 1000 22 36 28 43 1D SA-1D all 3 4 8 14 14 9 8 7
560 765 629 565 560 1120 25 41 31 50 SPA-1D low 4 6 9 17 26 21 18 12
630 834 698 634 630 1260 29 47 37 59 med 4 6 9 17 23 20 18 11
710 911 775 711 710 1420 37 60 47 75 high 4 6 9 16 17 16 14 11
800 997 861 797 800 1600 69 108 90 141 2D SA-2D low 6 8 14 23 24 15 13 10
med 6 8 13 22 22 14 13 9
high 6 8 12 20 18 13 11 9
SPA-2D low 8 11 16 30 39 35 32 22
med 8 11 16 27 32 32 29 19
high 8 11 16 24 23 23 24 17
900 1094 958 894 900 1800 86 135 112 176 1D SA-1D all 3 4 9 14 12 8 7 7
1000 1203 1067 1003 1000 2000 125 190 156 234 SPA-1D low 4 6 11 22 21 16 14 11
1120 1325 1200 1125 1120 2240 132 210 169 260 med. 4 6 11 20 19 15 13 11
1250 1450 1337 1250 1250 2500 146 234 185 294 high 4 6 11 17 17 14 12 11
2D SA-2D low 6 8 14 22 20 13 12 10
med. 6 8 13 21 18 12 11 10
high 6 8 12 19 15 11 10 9
SPA-2D low 8 11 19 30 32 30 24 17
med. 8 11 19 26 27 26 22 17
high 8 11 19 21 20 22 20 16
1400 1605 1475 1405 1400 2800 197 316 250 397 1D SA-1D all 4 5 10 14 11 7 6 6
1600 1805 1675 1605 1600 3200 275 540 348 682 SPA-1D low 5 7 12 21 20 14 12 9
med. 5 7 12 19 18 13 11 9
high 5 7 12 15 16 12 10 8
2D SA-2D low 8 9 15 20 19 12 11 9
med. 8 9 14 20 17 11 10 9
high 8 9 13 19 14 10 9 9
SPA-2D low 10 14 22 28 31 29 18 15
med. 10 14 22 25 27 25 16 15
high 10 14 22 21 21 21 15 14
• Low, Medium and High Pitch Angle setting correspond to 10º, 22º and 35º pitch angle approximately: for other pitch angles use interpolation.
48 A09-D V2015/July
!"
Tubular Sound Attenuator for AXV-D
SPA - Pressure Loss
300
1
200
100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400
30 1600
0.1
20
0.05
10
0.03
5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]
300
1
200
Pressure inches water gause [in.WG]
0.5
Pressure Loss [Pa]
100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400
30 1600
0.1
20
0.05
10
0.03
5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]
A09-D V2015/July 49
Wolter Sales Network
Inland Poland: Hongkong:
Ing. Günther Rößler Wentoprodukt Wolter Asia Ltd.
D-07619 Schkölen 44-100 Gliwice Hong Kong
Tel. (+49) 03 66 94 / 22 359 Tel. (+48)32 331-34-24 Tel. (+852) 0 24 / 56 01 98
Fax (+49) 03 66 94 / 22 357 Fax (+48)32 729-76-53 Fax (+852) 0 24 / 56 02 90
[email protected] [email protected] [email protected]
Wolter GmbH
Maschinen-und Apparatebau KG
Am Wasen 11
D-76316 Malsch / Germany
Tel. +49 (0) 7204/9201-0
Fax +49 (0) 7204/9201-11
www.wolter.eu
[email protected]
&
Air in Motion - Wolter Fans - www. wolterfans.de
Dongguan Wolter Chemco Ventilation Ltd.(Wolter Asia) • Shipai / Dongguan / Guangdong / China
Tel. (+86)769 86557298 • Fax (+86)769 86557278 • www.wolterfans.com • [email protected]