IMP Supernova 33000 UPS Operations Manual

Uploaded by

YT Zhou
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
0% found this document useful (0 votes)
916 views25 pages

IMP Supernova 33000 UPS

IMP Supernova 33000 UPS Operations Manual

Uploaded by

YT Zhou
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
im Uninterruptible Power Systems Supernova 33000 Operation Manual All rights reserved. The information in this document is Subject to change without notice. Publish statement Thank you for purchasing this series UPS. This series UPS is an intelligent, three phase in Three phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, The UPS meets the world’s advanced level. Read this manual carefully before installation This manual provides technical support to the operator of the equipment. 4s Operon Modes. 42 um ont U8. AA TALEO Dn 44am sen, ‘Sane sytem commissioning, ‘6D MessagesToubleshooting 41 ens. 32 3 38 3 val 2 3 45 1. Safety Important safety instructions - Save these instructions ‘There exists dangerous votage and high temperature inside the UPS. During the instalation, operation and maintenance, please abide the local safely intractons and relative taws, ctherwise it wil result in personnel injury or equipment damage. Safety instructions inthis ‘manual act @8 a supplementary for the local safety instructions, Our company wil not assume ‘he labilly that caused by disobeying safety instuctons. 4.1 Safety notes 1 Even no connection with utility power, 220/290/240VAC vollage may stil exist at UPS terminal 2. Forthe sake of human being safety, please wall earn he UPS before starting it '8. Don't open or damage battery, for the liquid spl rom the batiery is strongly poisenous and dohanmtul to body! 4 Please avoid short circuit between anode and cathode of battery, otherwise, wil cause ‘spark or fre! 5. Dont cisassemble the UPS cover, or there may be an electie shock! 6. Check if there exists high voltage before touching the battery 7. Working environment and storage way wil affect the lifetime and reliably ofthe UPS. Avoid the UPS from working under folowing environment fr long time ‘ Area where the humidy and temperature is out ofthe specified range(temperature 0 to 40°, relative humidy 5%-95%) ‘ Direct sunlight or locaton nearby heat ‘© Vibration Area with possibilty to get the UPS crashed. “© Area with erosive gas, fammable gas, excessive dust, etc ‘8. Keep ventilations in good concitions otherwise the components inside the UPS wil be ‘overheated which may affect the ife ofthe UPS. 1.2 Symbols used in this guide WARNING! Risk of electric shock CAUTION! Read this information to avoid equipment damage 2 Main Features sh frequency online UPS, sutrree outa . ot oe ‘ese supe Oro}ems, SUC 2 blackout, oy, ost of lating of d2t2a8IN9 EXE, high voting "age, urs ore sutcen P+ ytion (THD), noise intertey ie, oe a hamonie ast rence, tegen ao 0 re se esr 0 COMPU ein, Automate os a cpscnoe ores sequent i Se atures saps poe secure UPS system, of which input curentis keg na 0? ee nese os. owas bem La ‘ (OSP); en ae is ertled by Digta! Signal Processor (DSP); enhance, i, is ees UP pectin, nd seleagnostis and 80 on ag 508 ret, poe cxrigeele one 3s, the battery voltage of this series UPS can, ‘osve eo {o your convenience, e conigued ax iocks, he batery voltage ofthis series UPS can be “i fa rg los 040 Docks according to your convenes "oud at sabi, ‘crag Cents confguale Ve stro nosey et te cpacy ofthe batters a8 Wel as reasonable charig cares elma carggcurent Constant voltage mode, constant curent mode 9 {oang node canbe swithed atomatcaly and smoothly. “¢hegnt Charging Method ‘The sefes UPS adopts advanced three-stage charging method— sae ign eure constant caren charging lo uranieeto cage beck o 90%; sage: Constant Voage ‘hor tote batery and make sure batteries are fly charged | sage: foting mode, ‘Woh Sap charg nebo extends the Me ofthe batteries and guarantees fast charging #1c0 097 MOAED Wa LED eos, eur may easy get UPS stat and ts operon! , rameters, Such 88 inpwoutput votage, frequency & loads, batley % and ambient temperature, etc, “@ntetigent Monitoring Function ‘ia optional SNMP Card, you may remetely control and moritor the UPS. PO Function ‘The series UPS may be completely shut off when the EPO is pressed. REPO function (Remote EPO) is also availabe in this series UPS, 3. Installation 3.4 Unpack checking 1. Don'tlean the UPS wnen moving it out rom the packaging 2. Check the appearance to see if the UPS is damaged or not curing the transportation, do not ‘switch on the UPS if any damage found, Please contac the dealer ight away, 8. Check the accessories according to the packing list and contact the dealer in case of missing parts. 3.2 Cabinet Outlook ‘com: Side View Front View \—12 43 ar View (terminal block without cover) '30-40kVA Rear View (terminal block without cover) 102004 Re ee (olsen (1) LOD panel (2) lnteligentSiot 1 (SNMP carl Relay cara) amen (4) Parallel por 4 (@)Ineligant Slot 2 (SNMP card Relay card) | () Battery Power Switch Pa (@) Parallel por 2 (©) Dry contact port (© USB port cd (@) Power Switch (7) RS485 port (@) REPO port 1) REPO pat (10) WP Switch (9) RS232 (10) Parallel port Fane aa ime Gath ie chy cacy (11) Maintenance etch & its cover (12) UP Swich (1s) Marterence sich is cover (14) Intetigent Slot 2 (SNMP card! Relay card) (ESO Seth, a ok tr nod, tA REY aaa ieee (15) Ground 3.3 LCD control panel Eas LCD control panel introduction ‘ af operation and malotenance, amet conte tateet 1000 aNd 80m resp Sais anere cotie yrment, a ‘it potest psn acer Sts tom gn an terpenes Mg, ore ra ogra er a aala Ga e ~ espns so Serine gg tat 8 a eB OC eae es wre gee mes 8 by yay rn es a BS ero ca re, it might bein 8 condensing wi Sonn, et el of Pe UENO Say SRO Tg vas eae ea emicement re NDS hin onssee none a ning batlrye and capocty. n'a no ira tance tel aches Bee eos Koes ae soso eto 8. . ‘i Spa she WARNING! rmance data are quoted for an Type tae Petr and 26°C. Operating it above this ePerating ra epee te paratn below tis range wt ca te pate eee pt te ey UM De ord 8 ooo an joes ects Oo ® CAUTION! used battery must be recharged every months Tom, As nat ys ad wn Set Ten ‘the time required for recharging the batteries. \poratily ing it for ere see cettabuamanea pe ere aM eto atone ance Reta e ne eecus to | ts | ao 200 | 3000 | 3500 | 4000 | 4500 | sooo | Toad 100% | 95% : 0% | 85% | 80% | 75% | 70% | e5% {The UPS cooing is depending on fan, 80 It should be kept in good air ventilation area. ‘Tae many veiton oles onthe front and rear, so they should not be blocked by any exotic ‘35 External Protective Devices, Fer “evra. teeny ol, eel cet breaker at he ng AC supply and ‘te bate, This chapter proves guidines for qualia instars that must have the Krowodge of Toca wna practoes fr te eaupment to be nse = etme Ure tact of over-cuent “Tho UPS tnd is associated tates ar protected agains the efecto over eee outa compte terme-magnes creche’ or @ et lure) ete ase 1 the baer. — “auPs output Ary eternal dibuon board uses for oad stun shal be tte with protective vies thal may avoid the tak of UPS oveonded eae ‘sovercurrent rotation device sha be ins at the srbuton pane of heincoming sin supp. "may ently he power cables cent capacty as well asthe overoad capac ofthe System. CAUTION, Select a thermo magnetic circult-breaker with an IEC 60847-2 tip, curve C (normal) for 125% of the current as listed below. 3.6 Power Cables ane ‘The caie design shal compl wit the votages and cuents pone is section, indy fotow focal wing practices and take into consideration the environmental conditions (emperatre ‘and physical support media) WARNING! ae Upon starting, Please ensure that you are aware of the location and ‘operation of the external isolators which are connected to the UPS. om input/bypass supply of the mains distribution panel. Check to see it ‘these supplies are electrically isolated. And post and necessary = ‘warning signs to prevent any inadvertent operation. ‘For future expansion purpose, Ris economical to instal power cable secording tothe ful rating ‘capacty inal. The dlameter of cable's shown below: CAUTION. Protective earth cable: Connect each cabinet to the main ground, ‘system. For Grounding connection, follow the shortest route possible. WARNING! Fallure to follow adequate earthing procedures may result i electromagnetic interference or in hazards involving electric shoc and fire waned on S288 COMME I Povey ag Sa srgower sou and ato al overs, Sere sees 8 PY cee wan tg ol ye nets oe vet Oe i mF weer Let ® qo20e spelel eles iter: role ONS Ss a fe Sersfelelel® eee @ °8 22 @ @ sa gt at pase AU) input phase B12), npg nce {)routput phase B(L2), output phase cist Phase enc ey Ar ity rete There ae 9 cole oba fa eee soni: > = 4 falel ele [eo [ehelE acts man a sreleleleie|ei ele e@ e @ @ mralseperce ramet rg Input phase ALY), Nput phase B(L2), input cate ap pase NL). una pase (2), ctl pase Cl), capt C13 pb psi, batlry negative. There are 3 Connectors of GROUND Andere eral Bok ‘Choose appropiate power cable. (Refer to the table above) and pay attention to the ‘dametr lhe conection teminal ofthe cable that should be greater than or equal to that of the comecien pales, WARNING! If the load equipment is not ready to accept power on the arrival of the commissioning engineer then ensure that the syste” output cables are safely isolated at their ends Connect the safety earth and any necessary bonding earth cables to the copper earth screw located on the floor of the ‘equipment below the power connections. All cabinets in the UPS ‘must be grounded properly. CAUTION ‘The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice. 3.8 Battery connection 10-30KVA: ‘The UPS adopts postive and negative double battery framework totaly 18pes(gpional 18/20) in series A neutal cable i retrieved from the joint between the cathode ofthe 8 (8"/10") and the anode ofthe & (108711 of the batteries. Then the neuval cable, the batery Postve and the battery ‘egave are connected with the UPS respectively. The baer sets between the Battery anode and {he neutral are caled posive balteres and tat between neutral and cathode are cated negative ‘ones. The user can choose the capac and the numbers ofthe batteries according to their desire. Extemal battery connections for long-run unit. Posie banery Negative baton onthe ONDpices 40KVA: “The UPS adopts positive and negative double battery framework, totally 18pcs (optional 18 0 ween te ren te heuney (tZereSy ro be ee Storae. Then the neural Calt®*/oy, 1500m ower the rated power for for use Dimensions(O>W>H) s2e250x888 “Heian KG) 11857 70s Tries ‘CE,ENIEC 62040-2,ENTEC 62040-4-4 Battery number : 18pcs Battery number: 76pcs, TORVAS "2% with linear load SOG AOKVALH) 5% wih non linear load me “a Siandardonit '3 Phase 4 Wires and Ground stanlsc OPS | standart 2120Vee (zo Rated Volage 3e01400/475VE6 eames 12008 | ytavanl . ‘vottage Range SATS run unit Optional Vat ioe — [22H ey. | anevtoavietzavee tte, Frequency Range 45-50/z al SOHT64-GGhc at Oz [ao sera) Soeve108vie120- optional) Power Factor aa ‘ge (1118/20068 (Current THO! $3%(100% nonlinear toad) al fo = 3 par (no Max ota 20825 otonal 105 55 20%) standard uni fac: +20%4(Optional +10% +15% crapecoentl), [1388 274 soars wal 2:78 Bypass Voltage Range 2aaVac: +15%(optonal+10%) Seyret : come |e oe | tag nmunt ta ae 0n Min voage: 45% (penal 10% 208, 20%) ‘apocty staid) | pax. curent 108 Frequency protection range: +10% “Tyo Bator: Os Utly to bypass: Ome Generator Input pi Transform “aadst10%: los 60min 125%: last 10min 150% ast. praee: 3 Phase 4 Wires and Ground ‘ACMode ‘min, 150% change to bypass immediately Rated Voltage "380/4001415Vac Bat {Loads 10%: last 10min, $125%: last ¢min, $150%: last omens, 08 Overoad | ode '5S, >150% shut down UPS immediately Voltage Regulation H% Utilit Bypass | preter on | Breaker 32A Breaker 40A Mod | 21% 22%, 24%, 25%, 210% of he rated equency(optona) Frequency Crea 0A peak 140A peak Battery Sha c output aoe (6016020.2%)H2 Protection [—Srotrout__[_120Apeek [|_| Tine Made: Switch to Bypass, Backup Mode: Shut down UPS immediately a 7 Upon Power On and Software Control ‘Shut down UPS immediately ‘Advanced Battery Management ‘Complies with EN62040-2 ” Batiery number Battery number: 20p¢8 se ew3erw anges D 1 Battery number : 18pcs, ‘2% wth inear load 5% with non tnear load || —___ssstnronrearont % —_ ~ ~—s eS 2 a —_—_— to describe the fout with move deat ae a seae tees (@x20pes t2VeAr) ‘nuit pao OP Way. Some Fag ong un unt Optra hag ines nae ‘ere nut Option ANA TE aan, Input power supar 296V/4108V/2120Vde a nftvbe M2 connecter SUPPI i KS (se/1820pes options G2naneatiores, Input votge lo tory an vu The nt avten ot ge age Curent a isnot ew ee ee tent es ler eink a cin a fear ‘The inputbreakesse Setectordng|s baheg nM toa ere {saeomatonvny | petottearct omen ‘capacty installed) foes natant on. | Sr Mate oh PU breaker, Let ne UPS OPeTBES | ou cate not wet tog, MPAA wap Transfer Time Usliy to Bary: Gris; Uy to bypaae Gow 2 | so mae comect Sretwet | comeeice ‘ead 10% as Gomi, 125%: lst 1mm, ago Output cable does ‘AC Mode ‘min, >150% change o bypass inmediagy [|e UPS sors, but | wel cong one mt TSSGETIO% ast TOmin, | LeadeT 10% ato wjcate anY ‘Output breaker donot 7 in wthave Fie | EZ astm steams | tas wat ron Onn output on switch on Cwstoedi ies, | amen eee: down | last tmin, >180% shes 3 | voltage. ce UPS immediately UPS immediately paean as a Utility voltage exceed: Bypass Breaker 3A, Breaker 800 i sty LEDIS fasting | Upc nput ones Protection ‘Short Circuit 164A Peak br ‘does nc 3 SEE | || ae immesat hing LEDis ashing | ore damaged. on Battery Low ‘Alarm and Switch of Large is reversely connected. ‘Selt-diagnostics LUpon Power On and Software Control Pocharge voltage and | Baten ‘number and. EPO(ontoan ‘Shut down UPS immediatly A comet 8 | number and capacy eta a Battery ‘Advanced Battery Management correctly. 05 Noise Suppression ‘Complies wih EN62040-2 |_| Scazer beeps every a ‘Anns | — abie Vies Une Fare, Baty Low. Overton $7 Fa Rironeand LOD, | Ovefoad Remove some ad Sous TS ais Une Mose, Bross Mod. ate ow, ate Ba 6 _| isplay “output = Fi Overioad & | ‘The UPS output is ‘Make sure the load is notin short ovage, Ouipat tong beeps, LCD src Dispia "input Voltage, Input Frequency, Output Vi a Bure zerfault code | short circuit ireut, and then restart the UPS. pen, Reading On the LCD Frequency, Load Percentage, Battery Voltage & Ir 7 | display *29"tault Temperature ‘The UPSis settoECO | Setthe! ‘UPS working mode 16 UPS oie See ara pone, Couper dy anak, | 'S only works on | mode, orthe transfer | ype(non-parelich orto esate ‘Communication interfac {ntetigent slot, SNMP card (optional), Relay card (optional) re UPS oa {imes to bypass mode | mes of transfering to bypass or 8} bypass m are limited festa the UPS aes oc~400 Battery switch is not empereiure 250~ 550 propery closed: ose the battery sith: Revekronnntrt{'Strepe Terabe itn coma Or baton oP: | Change te se Hurilty pone Recharge the batey tL __ Ate, ——— eee Cannot Black stat | Battery quantiy et | Festa Ne a Actos 2261250%068 9 wrong; the battery quantity quantity, Dimensions(OxWsH ) > Power beakerinthe | Sitenn'teporee eae: Other el Zan : fear pane! not switch Conformance ‘CE, EN/IEC 62040-2,ENIEC 62040-1-1 ON. Safety Conform ary Buzzer beeps ‘Consult with your local agent blems and Solution continuously and LCD | upsisoutotower | Con Append 2 Fraps Instatation, wing or operation 10 | indicates 1.59.15, ete wr etapa ten ange eee hat fault codes Please check these aspects first. If all these aecoces ara chacies ‘consult with local agent right away and provide below int (41) Product model name and serial number. » aax.3 use communication port definition ‘Appen' Definition of port: mnaconrvomenttoomemenelhe tt CUS pot UPSUSB pot _| Description Fat Pat ae Faz Pine PC: OPLUS sgnar Pas Pins PC DMINUS Sgrar Ping Pind Signal ground ‘Avaliable function of USB “Monitor UPS power status. 4 Monitor UPS alarm info. {Monitor UPS running parameters. ‘ Timing offon seting, CConmuricatn data format Baud rte —— 960009 Byte length —— sb End bt —— Abit Party check ——none A CAUTION! ‘USB, RS232 and RS485 interface cannot be used at the same timo, you can only use one of them at one time. Appendix 4 RS232 6, patton of Male port Neti} TxD 218|Nc Ryo [a{ZINe Ne[@|8\Nc e cp 5 [SINc caecion ptveen PC RS222 ort ard UPg gry es ft PC RS292 port alte fonction of RS282 ‘ Motitor UPS power sa + Monitor UPS alarm inf, * Monitor UPS running parameters, + Timing offen seting 8-252 communication data format Baud rate seo0nps Byte length — apt End bt — 103 Parity check ——none CAUTION you can only use one of them at one time. mn | ™MUNKcation Port pa ss efinition USB, RS232 and RS485 interface cannot be used at the same tine, gags communication port definition ‘Appendix 5 R Definition of por | el : rd UPS RSAES port te Devices RSABS POU conection boven pemecnas pans) | esetoton fuses pas a Pin 2/4 485 -"B Pit eer, =— Pind ie G2 otal incon f RASS “¢ Montr UPS power tS, “¢ Monitor UPS alarm inf. “¢ onitor UPS roing parameters 4 Tig fon etna “esatery environment emgerature mente age modulton depending on bates temperature ‘charging v0 communication dea format aud rte —— 9600008 Byte length ——— 8bit End bt-—— tb Party check ——none CAUTION! USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. S485 port pin7 is 12Vde! 8 appendix 6 Dry contact port ost of Male port: Communication Port definition Dr ci Yeontact 23 fis ae Rese we Reape s reps pation UPS Pint Pina Pins Ping uncon descipion: © Monitor UPS status; “© Monitor UPS battery satus © Shutdown UPS, Appendix 7 REPO instruction Definition of port: Connection diagram: ‘ont Ups. 3 PST Connection between the button and UPS REPO port. Button UPS REPO Pin 4 Pin2 ‘Arremote emergency stop switch (Dry contact signal and “normally open’ - not provided) can be + . 4 a installed in a remote location and connection through simple wires to the REPO conneco Yr. ‘The remote switch can be connected to several UPS in a parallel architecture allowing the user ser stops all units at once. 4s

You might also like