Uninterruptible Power Systems
Supernova 33000
Operation ManualAll rights reserved.
The information in this document is Subject to change without notice.
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, three phase in Three phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network
functions, smart appearance, complying with EMC and safety standards, The UPS
meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.4s Operon Modes.
42 um ont U8.
AA TALEO Dn
44am sen,
‘Sane sytem commissioning,
‘6D MessagesToubleshooting
41 ens.
32
3
38
3
val
2
3
45
1. Safety
Important safety instructions - Save these instructions
‘There exists dangerous votage and high temperature inside the UPS. During the
instalation, operation and maintenance, please abide the local safely intractons and relative
taws, ctherwise it wil result in personnel injury or equipment damage. Safety instructions inthis
‘manual act @8 a supplementary for the local safety instructions, Our company wil not assume
‘he labilly that caused by disobeying safety instuctons.
4.1 Safety notes
1 Even no connection with utility power, 220/290/240VAC vollage may stil exist at UPS
terminal
2. Forthe sake of human being safety, please wall earn he UPS before starting it
'8. Don't open or damage battery, for the liquid spl rom the batiery is strongly poisenous and
dohanmtul to body!
4 Please avoid short circuit between anode and cathode of battery, otherwise, wil cause
‘spark or fre!
5. Dont cisassemble the UPS cover, or there may be an electie shock!
6. Check if there exists high voltage before touching the battery
7. Working environment and storage way wil affect the lifetime and reliably ofthe UPS. Avoid
the UPS from working under folowing environment fr long time
‘ Area where the humidy and temperature is out ofthe specified range(temperature 0
to 40°, relative humidy 5%-95%)
‘ Direct sunlight or locaton nearby heat
‘© Vibration Area with possibilty to get the UPS crashed.
“© Area with erosive gas, fammable gas, excessive dust, etc
‘8. Keep ventilations in good concitions otherwise the components inside the UPS wil be
‘overheated which may affect the ife ofthe UPS.
1.2 Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage2 Main Features
sh frequency online UPS,
sutrree outa .
ot oe
‘ese supe Oro}ems, SUC 2 blackout, oy,
ost of lating of d2t2a8IN9 EXE, high voting "age,
urs ore sutcen P+ ytion (THD), noise intertey ie,
oe a hamonie ast rence, tegen
ao 0
re se esr 0 COMPU ein, Automate
os a
cpscnoe ores sequent
i Se
atures
saps
poe secure UPS system, of which input curentis keg na
0? ee
nese os.
owas bem La
‘ (OSP); en
ae is ertled by Digta! Signal Processor (DSP); enhance, i,
is ees UP pectin, nd seleagnostis and 80 on ag
508
ret, poe
cxrigeele
one 3s, the battery voltage of this series UPS can,
‘osve eo {o your convenience, e conigued
ax iocks, he batery voltage ofthis series UPS can be
“i fa rg los 040 Docks according to your convenes "oud at
sabi,
‘crag Cents confguale
Ve stro nosey et te cpacy ofthe batters a8 Wel as reasonable charig
cares elma carggcurent Constant voltage mode, constant curent mode 9
{oang node canbe swithed atomatcaly and smoothly.
“¢hegnt Charging Method
‘The sefes UPS adopts advanced three-stage charging method—
sae ign eure constant caren charging
lo uranieeto cage beck o 90%;
sage: Constant Voage
‘hor tote batery and make sure batteries are fly charged
| sage: foting mode,
‘Woh Sap charg nebo extends the Me ofthe batteries and guarantees fast charging
#1c0 097
MOAED Wa LED eos, eur may easy get UPS stat and ts operon!
,
rameters, Such 88 inpwoutput votage, frequency & loads, batley % and ambient
temperature, etc,
“@ntetigent Monitoring Function
‘ia optional SNMP Card, you may remetely control and moritor the UPS.
PO Function
‘The series UPS may be completely shut off when the EPO is pressed. REPO function
(Remote EPO) is also availabe in this series UPS,
3. Installation
3.4 Unpack checking
1. Don'tlean the UPS wnen moving it out rom the packaging
2. Check the appearance to see if the UPS is damaged or not curing the transportation, do not
‘switch on the UPS if any damage found, Please contac the dealer ight away,
8. Check the accessories according to the packing list and contact the dealer in case of missing
parts.
3.2 Cabinet Outlook
‘com:
Side View
Front View\—12
43
ar View (terminal block without cover)
'30-40kVA Rear View (terminal block without cover)
102004 Re
ee (olsen (1) LOD panel (2) lnteligentSiot 1 (SNMP carl Relay cara)
amen (4) Parallel por 4 (@)Ineligant Slot 2 (SNMP card Relay card) | () Battery Power Switch
Pa (@) Parallel por 2 (©) Dry contact port (© USB port
cd (@) Power Switch (7) RS485 port (@) REPO port
1) REPO pat (10) WP Switch (9) RS232 (10) Parallel port
Fane aa ime Gath ie chy cacy (11) Maintenance etch & its cover (12) UP Swich
(1s) Marterence sich is cover (14) Intetigent Slot 2 (SNMP card! Relay card) (ESO Seth, a ok tr nod, tA REY
aaa ieee (15) Ground
3.3 LCD control panel
Eas
LCD control panel introduction
‘af operation and malotenance,
amet conte tateet 1000 aNd 80m resp
Sais
anere cotie yrment, a ‘it
potest psn acer Sts tom gn an terpenes Mg,
ore ra ogra er a aala Ga e
~
espns so
Serine gg tat 8 a eB OC
eae es wre gee mes 8 by yay
rn es a BS
ero ca re, it might bein 8 condensing
wi Sonn,
et el of Pe UENO Say SRO Tg
vas
eae
ea emicement re NDS hin
onssee none a ning batlrye and capocty. n'a no ira
tance tel aches Bee eos Koes ae
soso eto 8. .
‘i
Spa
she
WARNING! rmance data are quoted for an
Type tae Petr and 26°C. Operating it above this ePerating
ra
epee te paratn below tis range wt ca
te
pate eee
pt te ey UM De ord 8 ooo an
joes ects Oo ®
CAUTION!
used battery must be recharged every months Tom,
As nat ys ad wn Set Ten
‘the time required for recharging the batteries.
\poratily
ing it for
ere see
cettabuamanea pe ere aM eto atone
ance
Reta e ne eecus to
| ts | ao 200 | 3000 | 3500 | 4000 | 4500 | sooo |
Toad
100% | 95%
: 0% | 85% | 80% | 75% | 70% | e5%
{The UPS cooing is depending on fan, 80 It should be kept in good air ventilation area.
‘Tae many veiton oles onthe front and rear, so they should not be blocked by any exotic
‘35 External Protective Devices,
Fer
“evra. teeny ol, eel cet breaker at he ng AC supply and
‘te bate, This chapter proves guidines for qualia instars that must have the Krowodge of
Toca wna practoes fr te eaupment to be nse =
etme Ure tact of over-cuent
“Tho UPS tnd is associated tates ar protected agains the efecto over eee
outa compte terme-magnes creche’ or @ et lure) ete ase 1
the baer. —
“auPs output
Ary eternal dibuon board uses for oad stun shal be tte with protective
vies thal may avoid the tak of UPS oveonded eae
‘sovercurrent
rotation device sha be ins at the srbuton pane of heincoming sin supp.
"may ently he power cables cent capacty as well asthe overoad capac ofthe System.
CAUTION,
Select a thermo magnetic circult-breaker with an IEC 60847-2 tip,
curve C (normal) for 125% of the current as listed below.
3.6 Power Cables ane
‘The caie design shal compl wit the votages and cuents pone is section, indy
fotow focal wing practices and take into consideration the environmental conditions (emperatre
‘and physical support media)
WARNING! ae
Upon starting, Please ensure that you are aware of the location and
‘operation of the external isolators which are connected to the UPS. om
input/bypass supply of the mains distribution panel. Check to see it
‘these supplies are electrically isolated. And post and necessary =
‘warning signs to prevent any inadvertent operation.
‘For future expansion purpose, Ris economical to instal power cable secording tothe ful rating
‘capacty inal. The dlameter of cable's shown below:
CAUTION.
Protective earth cable: Connect each cabinet to the main ground,
‘system. For Grounding connection, follow the shortest route
possible.
WARNING!
Fallure to follow adequate earthing procedures may result i
electromagnetic interference or in hazards involving electric shoc
and firewaned on S288 COMME I Povey ag
Sa
srgower sou and ato al overs,
Sere sees 8 PY cee wan tg
ol ye nets
oe
vet Oe i mF
weer
Let ®
qo20e
spelel eles iter:
role ONS Ss a
fe Sersfelelel® eee
@
°8
22
@ @
sa gt at pase AU) input phase B12), npg
nce {)routput phase B(L2), output phase cist Phase
enc ey Ar ity rete There ae 9 cole oba
fa eee
soni: > =
4 falel ele
[eo [ehelE acts man a
sreleleleie|ei ele
e@
e @ @
mralseperce ramet rg Input phase ALY), Nput phase B(L2), input
cate ap pase NL). una pase (2), ctl pase Cl), capt
C13 pb psi, batlry negative. There are 3 Connectors of GROUND
Andere eral Bok
‘Choose appropiate power cable. (Refer to the table above) and pay attention to the
‘dametr lhe conection teminal ofthe cable that should be greater than or equal to that of
the comecien pales,
WARNING!
If the load equipment is not ready to accept power on the
arrival of the commissioning engineer then ensure that the syste”
output cables are safely isolated at their ends
Connect the safety earth and any necessary bonding earth
cables to the copper earth screw located on the floor of the
‘equipment below the power connections. All cabinets in the UPS
‘must be grounded properly.
CAUTION
‘The earthing and neutral bonding arrangement must be in
accordance with local and national codes of practice.
3.8 Battery connection
10-30KVA:
‘The UPS adopts postive and negative double battery framework totaly 18pes(gpional 18/20)
in series A neutal cable i retrieved from the joint between the cathode ofthe 8 (8"/10") and the
anode ofthe & (108711 of the batteries. Then the neuval cable, the batery Postve and the battery
‘egave are connected with the UPS respectively. The baer sets between the Battery anode and
{he neutral are caled posive balteres and tat between neutral and cathode are cated negative
‘ones. The user can choose the capac and the numbers ofthe batteries according to their desire.
Extemal battery connections for long-run unit.
Posie banery Negative baton
onthe ONDpices
40KVA:
“The UPS adopts positive and negative double battery framework, totally 18pcs (optional 18
0ween te ren te heuney (tZereSy
ro be ee Storae. Then the neural Calt®*/oy,
1500m ower the rated power for
for use
Dimensions(O>W>H) s2e250x888
“Heian KG) 11857 70s Tries
‘CE,ENIEC 62040-2,ENTEC 62040-4-4
Battery number : 18pcs
Battery number: 76pcs, TORVAS
"2% with linear load SOG AOKVALH)
5% wih non linear load me “a
Siandardonit '3 Phase 4 Wires and Ground
stanlsc OPS | standart 2120Vee (zo Rated Volage 3e01400/475VE6
eames 12008 | ytavanl . ‘vottage Range SATS
run unit Optional Vat
ioe — [22H ey. | anevtoavietzavee tte, Frequency Range 45-50/z al SOHT64-GGhc at Oz [ao sera)
Soeve108vie120- optional) Power Factor aa
‘ge (1118/20068 (Current THO! $3%(100% nonlinear toad)
al fo = 3
par (no Max ota 20825 otonal 105 55 20%)
standard uni fac: +20%4(Optional +10% +15%
crapecoentl), [1388 274 soars wal 2:78 Bypass Voltage Range 2aaVac: +15%(optonal+10%)
Seyret :
come |e oe | tag nmunt ta ae 0n Min voage: 45% (penal 10% 208, 20%)
‘apocty staid) | pax. curent 108 Frequency protection range: +10%
“Tyo Bator: Os Utly to bypass: Ome Generator Input pi
Transform “aadst10%: los 60min 125%: last 10min 150% ast. praee: 3 Phase 4 Wires and Ground
‘ACMode ‘min, 150% change to bypass immediately Rated Voltage "380/4001415Vac
Bat {Loads 10%: last 10min, $125%: last ¢min, $150%: last omens, 08
Overoad | ode '5S, >150% shut down UPS immediately Voltage Regulation H%
Utilit
Bypass | preter on | Breaker 32A Breaker 40A Mod | 21% 22%, 24%, 25%, 210% of he rated equency(optona)
Frequency
Crea 0A peak 140A peak Battery
Sha c output aoe (6016020.2%)H2
Protection
[—Srotrout__[_120Apeek [|_|
Tine Made: Switch to Bypass, Backup Mode: Shut down UPS
immediately
a
7 Upon Power On and Software Control
‘Shut down UPS immediately
‘Advanced Battery Management
‘Complies with EN62040-2
”
Batiery number
Battery number: 20p¢8 se ew3erw anges
D
1
Battery number : 18pcs,
‘2% wth inear load
5% with non tnear load
|| —___ssstnronrearont
%—_ ~ ~—s
eS 2
a
—_—_—
to describe the fout with move deat
ae a seae tees
(@x20pes t2VeAr) ‘nuit pao OP Way. Some Fag
ong un unt Optra hag ines
nae ‘ere nut Option ANA TE aan, Input power supar
296V/4108V/2120Vde a nftvbe M2 connecter SUPPI i
KS (se/1820pes options G2naneatiores, Input votge lo
tory an vu The nt avten ot ge
age Curent a isnot ew
ee ee tent es ler eink a cin a fear ‘The inputbreakesse
Setectordng|s baheg nM toa ere {saeomatonvny | petottearct omen
‘capacty installed) foes natant on. | Sr Mate oh PU breaker,
Let ne UPS OPeTBES | ou cate not wet tog, MPAA wap
Transfer Time Usliy to Bary: Gris; Uy to bypaae Gow 2 | so mae comect Sretwet | comeeice
‘ead 10% as Gomi, 125%: lst 1mm, ago Output cable does
‘AC Mode ‘min, >150% change o bypass inmediagy [|e UPS sors, but | wel cong one mt
TSSGETIO% ast TOmin, | LeadeT 10% ato wjcate anY ‘Output breaker donot
7 in wthave
Fie | EZ astm steams | tas wat ron Onn output on switch on
Cwstoedi ies, | amen eee: down | last tmin, >180% shes 3 | voltage. ce
UPS immediately UPS immediately paean as a Utility voltage exceed:
Bypass Breaker 3A, Breaker 800 i sty LEDIS fasting | Upc nput ones
Protection ‘Short Circuit 164A Peak br ‘does nc
3 SEE | || ae
immesat hing
LEDis ashing | ore damaged. on
Battery Low ‘Alarm and Switch of Large is reversely connected.
‘Selt-diagnostics LUpon Power On and Software Control Pocharge voltage and | Baten ‘number and.
EPO(ontoan ‘Shut down UPS immediatly A comet 8 | number and capacy eta a
Battery ‘Advanced Battery Management correctly.
05
Noise Suppression ‘Complies wih EN62040-2 |_| Scazer beeps every a
‘Anns | — abie Vies Une Fare, Baty Low. Overton $7 Fa Rironeand LOD, | Ovefoad Remove some ad
Sous TS ais Une Mose, Bross Mod. ate ow, ate Ba 6 _| isplay “output = Fi
Overioad & | ‘The UPS output is ‘Make sure the load is notin short
ovage, Ouipat tong beeps, LCD src
Dispia "input Voltage, Input Frequency, Output Vi a Bure zerfault code | short circuit ireut, and then restart the UPS.
pen, Reading On the LCD Frequency, Load Percentage, Battery Voltage & Ir 7 | display *29"tault
Temperature ‘The UPSis settoECO | Setthe! ‘UPS working mode 16 UPS
oie See ara pone, Couper dy anak, | 'S only works on | mode, orthe transfer | ype(non-parelich orto esate
‘Communication interfac {ntetigent slot, SNMP card (optional), Relay card (optional) re UPS oa {imes to bypass mode | mes of transfering to bypass or
8} bypass m are limited festa the UPS
aes oc~400 Battery switch is not
empereiure 250~ 550 propery closed: ose the battery sith:
Revekronnntrt{'Strepe Terabe itn coma Or baton oP: | Change te se
Hurilty pone Recharge the batey
tL __ Ate, ——— eee Cannot Black stat | Battery quantiy et | Festa Ne a Actos
2261250%068 9 wrong; the battery quantity quantity,
Dimensions(OxWsH ) > Power beakerinthe | Sitenn'teporee eae:
Other el Zan : fear pane! not switch
Conformance ‘CE, EN/IEC 62040-2,ENIEC 62040-1-1 ON.
Safety Conform
ary Buzzer beeps ‘Consult with your local agent
blems and Solution continuously and LCD | upsisoutotower | Con
Append 2 Fraps Instatation, wing or operation 10 | indicates 1.59.15, ete
wr etapa ten ange eee hat fault codes
Please check these aspects first. If all these aecoces ara chacies
‘consult with local agent right away and provide below int
(41) Product model name and serial number.
»aax.3 use communication port definition
‘Appen'
Definition of port:
mnaconrvomenttoomemenelhe tt
CUS pot UPSUSB pot _| Description
Fat Pat ae
Faz Pine PC: OPLUS sgnar
Pas Pins PC DMINUS Sgrar
Ping Pind Signal ground
‘Avaliable function of USB
“Monitor UPS power status.
4 Monitor UPS alarm info.
{Monitor UPS running parameters.
‘ Timing offon seting,
CConmuricatn data format
Baud rte —— 960009
Byte length —— sb
End bt —— Abit
Party check ——none
A CAUTION!
‘USB, RS232 and RS485 interface cannot be used at the same timo,
you can only use one of them at one time.
Appendix 4 RS232 6,
patton of Male port
Neti}
TxD 218|Nc
Ryo [a{ZINe
Ne[@|8\Nc
e cp 5 [SINc
caecion ptveen PC RS222 ort ard UPg gry es
ft
PC RS292 port
alte fonction of RS282
‘ Motitor UPS power sa
+ Monitor UPS alarm inf,
* Monitor UPS running parameters,
+ Timing offen seting
8-252 communication data format
Baud rate seo0nps
Byte length — apt
End bt — 103
Parity check ——none
CAUTION
you can only use one of them at one time.
mn
| ™MUNKcation Port
pa
ss
efinition
USB, RS232 and RS485 interface cannot be used at the same tine,gags communication port definition
‘Appendix 5 R
Definition of por | el
: rd UPS RSAES port
te Devices RSABS POU
conection boven pemecnas
pans) | esetoton
fuses
pas a
Pin 2/4 485 -"B
Pit eer, =—
Pind ie G2
otal incon f RASS
“¢ Montr UPS power tS,
“¢ Monitor UPS alarm inf.
“¢ onitor UPS roing parameters
4 Tig fon etna
“esatery environment emgerature mente
age modulton depending on bates temperature
‘charging v0
communication dea format
aud rte —— 9600008
Byte length ——— 8bit
End bt-—— tb
Party check ——none
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.
S485 port pin7 is 12Vde!
8
appendix 6 Dry contact port
ost of Male port: Communication
Port definition
Dr ci
Yeontact
23
fis ae
Rese we
Reape s
reps
pation
UPS
Pint
Pina
Pins
Ping
uncon descipion:
© Monitor UPS status;
“© Monitor UPS battery satus
© Shutdown UPS,Appendix 7 REPO instruction
Definition of port:
Connection diagram:
‘ont Ups.
3
PST
Connection between the button and UPS REPO port.
Button UPS REPO
Pin 4
Pin2
‘Arremote emergency stop switch (Dry contact signal and “normally open’ - not provided) can be
+ . 4 a
installed in a remote location and connection through simple wires to the REPO conneco
Yr.
‘The remote switch can be connected to several UPS in a parallel architecture allowing the user
ser
stops all units at once.