Datasheet SIEMENS SITRANS FUS080 Ultrasonic Transmitter
Datasheet SIEMENS SITRANS FUS080 Ultrasonic Transmitter
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
■ Overview ■ Design
The transmitter type SITRANS FUS080 is designed with fiber-
glass reinforced polyamide enclosure for remote or compact in-
stallation in normal areas. The remote versions are available with
up to 30 meter distance from flowmeter to transmitter. When or-
dering as a compact version in the series FUS380 and FUE380
the transducer cables are pre-mounted at the sensor.
The transmitter is available in an IP67/NEMA 4X/6 enclosure and
is designed for use in the flowmeters series:
• SONOKIT (1-path or 2-path)
• FUS380 (2-path)
• FUE380 (2-path)
3
The transmitter FUS080 is always ordered as part of a complete
SITRANS FUS080 is a transit time based transmitter designed flowmeter system.
for ultrasonic flow metering with any sensor in the FUS inline se-
ries SONOKIT, FUS380 and FUE380 up to DN 1200. It can be manually ordered separately as spare part prepro-
grammed with the given sensor data.
The ultrasonic flowmeter transmitter SITRANS FUS080 comes as
battery or mains powered version. The SITRANS FUS080 is de-
signed to measure flow water applications. ■ Integration
The SONOKIT retrofit flowmeter series are shown from The flowmeter pulse output is often used as input for an energy
page 3/282. The standard flowmeter series SITRANS FUS380 is meter or as input for digital systems for remote reading.
described from page 3/292. The type approved flowmeter series SITRANS FUS380 has two pulsel outputs, with functions that can
for flow metering in energy meter custody transfer systems are be individually selected.
named SITRANS FUE380.
The settings of the transmitter, e. g. flow and pulse output rate,
■ Benefits are defined when ordering the complete flowmeter.
• Battery-powered up to 6 years If the flowmeter forms part of an energy meter system for cus-
tody transfer, no further approvals are needed, except eventually
• 115/230 V mains-powered with back-up battery option in case local approvals on the flowmeter.
of mains power failure
• Fast measuring frequency 15 Hz/0.5 Hz (230 V AC/Battery)
• Easy one button straight forward display
• IrDA optical interface for local communication
• 2-path measuring principle for optimum accuracy
• Compact or remote mounting
• Measures on all district water qualities and water conductivi-
ties
• No pressure drop
• Long-term stability
• 2 galvanic isolated digital outputs for easy connection to a cal-
culator (potential free)
• 1 analog 4 to 20 mA output
• Bidirectional measurement, with 2 totalizers and outputs
• Dynamic range Qi (min) : Qs (max) up to 1:400
• Compact version with triax cables for highest EMC-protection
■ Application
The main application for flowmeters with the transmitter
SITRANS FUS080 is measurement of water flow in district heat-
ing plants, local networks, boiler stations, substations, chiller
plants, irrigations plants and other general water applications.
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
■ Technical specifications
Input Design
Measurement Flow by measuring the transit time Enclosure material Fibre-glass reinforced polyamide,
difference of ultrasonic signals light gray color
through ultrasonic transducers in the
Wall mounting kit IP67/NEMA 4X/6 terminal box for the
sensor pipes.
wall mounting of the transmitter, fiber-
Supporting of 1-path or 2-path sen- glass reinforced polyamide with stain-
sors in sizes DN 50 … 1200 measur- less steel bracket, cable glands
ing on water entries: 2 x 2 M20 or PG 13.5 for
Measuring rate power supply and outputs and
• Battery mode 0.5 Hz 2 x M20 or PG 13.5 for the sensor
cables, glands (supply and outputs
3
• Mains supply Up to 15 Hz
and double cable entries for sensor
• Back-up mode 0.5 Hz (at mains supply drop) cables) are included.
Flow rate 0.02 … 9 m/s (0.065 … 29.5 ft/s), Sensor cable Coaxial cable sets for remote trans-
bidirectional flow metering mitter up to 30 m (98.4 ft) long trans-
Output 2 pulse or status outputs (A and B), ducer cable, 75 Ω impedance,
individual galvanically isolated MOS cables sets are prepared for the con-
relay outputs, passive mode, nection to the sensors
max. ± 35 V AC/DC, max. 50 mA Triax cables or integral version
Max. pulse frequency 100 Hz at Qs (Qmax) Display and controls
Pulse value and length Selectable with the ordering of the Display LCD, 8 digits, additional 2 digits and
flowmeter symbols for status information
Output A function Pulse: forward, reverse, forward net, Resolution Totalized information can be dis-
reverse net (preset: forward) played with 1, 2 or 3 decimals or
Output B function Pulse: forward, reverse, forward net, automatic adjustment (default)
reverse net (preset: forward) Display setting Flow unit: Preset: m3/h
or alarm indication or call-up indica-
tion (preset: alarm) Volume unit: Preset: m3
Pulse value A and B 0.1 l/p, 0.25 l/p, 0.5 l/p, 1 l/p, 2.5 l/p, Push button One push button for menu selection
10 l/p, 25 l/p, 50 l/p, 100 l/p, 250 l/p, and display information
500 l/p, 1 m3/p, 2.5 m3/p, 5 m3/p, Communication (IrDA optical eye) IrDA – optical communication and
10 m3/p, 25 m3/p, 50 m3/p, 100 m3/p, control interface with Modbus RTU
250 m3/p, 500 m3/p, 1 000 m3/p protocol for read or write transmitter
Pulse length (depending on Qmax by 5, 10, 20, 50, 100, 200, 500 ms (stan- settings and data via PC and PDM
DN selection) dard 5 ms) tool
Alarm indication Path 1 (F1), path 2 (F2) internal, fail- Power supply
ure (F3, F4), powers supply warning Battery D-cell battery pack, 3.6 V LiSOCI
or low battery indication (F5), Qmax (Lithium Thionyl Chloride, 34 Ah),
overflow (F6), pulse overflow (F7, F8), replaceable, life- and working-time
internal data logger warning (F9) up to 6 years
Analog output Passive current output 4 ... 20 mA Mains 87 … 265 V AC (50 … 60 Hz) or
Data span pre-selectable depending 87 … 265 V AC (50 … 60 Hz) with D-
on pipe size cell single battery backup,
Rated operation conditions 2.6 V LiSOCI (Lithium Thionyl Chlo-
ride, 17 Ah), replaceable, life time up
Ambient conditions to 8 years
Ambient temperature Power consumption
• Operation -10 … +60 °C (14 … 140 °F) (MID
version: max. +55 °C (131 °F)) Mains version Approx. 2.5 VA
• Storage -40 … +85 °C (-40 … +185 °F) (bat-
tery included)
Enclosure rating IP67/NEMA 4X/6 to EN 60529 and
DIN 40050
Electromagnetic compatibility
• Emitted interference To EN 55011/CISPR-11
• Immunity To EN/IEC 61326-1 (Industry)
• MID approved (FUE380 series) Environment class E2 and M1
Mechanical vibration 2 g, 1 … 800 Hz sinusoidal in all
directions according to IEC 68-2-6
Weight of transmitter Approx. 1.5 kg (3.3 lb)
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
Alarm output On
2
Off
1 Type accuracy limits FUS380
Error
0 Alarm status No error
0 0.2 0.4 0.6 0.8 1 1.5 2 2.5 3 [m/s] 10
0 0.5 1 2 5 8 [ft/s] 33 Pulse output B can be used as stated above or as alarm or call-
up function.
5 Off
4
Call-up reset
3 FUE380 - admissible limits according
On
to OIML R 75 class 2
2 Call-up status Off
FUE380 - admissible limits according
to EN 1434 class 2
1 Call-up: the call-up output is active until manually reset by use of
PDM tool. The call-up function is activated when an alarm is ac-
0 tivated.
0 0.2 0.4 0.6 0.8 1 1.5 2 2.5 3 [m/s] 10
0 0.5 1 2 5 8 [ft/s] 33
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
3
Material (outside jacket) Black PE
4 mA Ambient temperature -10 … +70 °C
3.6 mA
(14 … 158 °F)
-100% Cut-off 100% Q Sensor coaxial cable for FUS380 /FUE380 series
Upper alarm limit Coaxial cable
Upper current limit High temperature coax- With special designed
Upper current scaling point ial cable (75 Ω) glands for connection in
the sensor/transducer
Lower current scaling point
Lower alarm limit Outside diameter Ø 5.13 mm (first 0.3 m
(0.98 ft) part to the trans-
ducer), Ø 5,8 mm (for
Bidirectional flow remaining cable to the
transmitter – black holt
melt junction part
mA between (Ø 16 mm,
22.6 mA length 70 mm)
20.5 mA Length Up to 30 m (98.4 ft)
between sensor and
20 mA transmitter
Material (outside jacket) Brown PTFE (0.3 m
(9.84 ft) part) and black
PE (for remaining cable)
Positive flow
mA
22.6 mA
20.5 mA
20 mA
4 mA
3.6 mA
Negative flow
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
Description Article No. When ordering: Inform on flowmeter order no. and flowmeter serial no.
(e.g. 7ME3400-xxxxx-xxxx-Z, XX.... and xxxxxxHxxx)
for use with SONOKIT
• English A5E03059912 Spare part transmitter for FUE380 approved systems (7ME3410)
integrated in FUS/FUE380 (only with MID approval marks, no MID verification – only a com-
• English A5E00730100 plete flowmeter can be MID-verified, i.e. sensor together with the
• German A5E00740611 transmitter)
All literature is available to download for free, in a range of lan- Description Article No. 3
guages, at
FUE080 transmitter 3.6 V battery A5E02734600
http://www.siemens.com/processinstrumentation/documentation (no battery included, to be
ordered separate) as spare part
Accessories transmitter for FUE380 flowmeter
series. Transmitter Article
Description Article No. No.7ME3450-0AA10-2AB0.
Sun lid for FUS080 transmitter A5E02328485 FUE080 transmitter 3.6 V battery A5E02734568
(frame and lid) (battery included) as spare part
transmitter for FUE380 flowmeter
series 1). Transmitter Article No.
7ME3450-0AA20-2AB0
FUE080 transmitter 230 V mains A5E02734539
as spare part transmitter for
Brace (holder) for optical IrDA A5E00695277 FUE380 flowmeter series. Trans-
eye mitter Article No. 7ME3450-
0AA30-2AB0
FUE080 transmitter 230 V mains A5E02734585
with backup-battery as spare part
transmitter for FUE380 flowmeter
IrDA infrared interface adapter FDK:087L4163 series. Transmitter Article No.
with USB for data acquisition with 7ME3450-0AA40-2AB0
1.2 m (3.9 ft) cable
When ordering: Inform on flowmeter order no. and flowmeter serial no.
(e.g. 7ME3410-xxxxx-xxxx-Z, XX.... and xxxxxxHxxx)
Process Device Manager SIMATIC PDM Spare part transmitter for SONOKIT systems
SIMATIC PDM See the Selec- (7ME3210/7ME3220)
For more details about SIMATIC tion and Order-
PDF please go to chapter 8 "Digi- ing data on Description Article No.
talization and Communication". chapter 8 "Digi-
talization and FUS080 transmitter 3.6 V battery A5E03048726
Communica- (no battery included, to be
tion" ordered separate) as spare part
transmitter for SONOKIT flowme-
ters. Transmitter Article No.
Spare parts 7ME3450-0AA10-2AA0
A spare part transmitter can be ordered for a specific system. In FUS080 transmitter 3.6 V battery A5E03048714
the description of the following spare part transmitters the re- (no battery included) as spare
lated transmitter Article No. found on the device silver front label part transmitter for SONOKIT flow-
is noted. meters 1). Transmitter Article No.
7ME3450-0AA20-2AA0
Spare part transmitter for FUS380 systems (7ME3400) FUS080 transmitter 230 V mains A5E03048701
as spare part transmitter for
Description Article No. SONOKIT flowmeters. Transmitter
FUS080 transmitter 3.6 V battery A5E02729700 Article No. 7ME3450-0AA30-
(no battery included, to be 2AA0
ordered separate) as spare part FUS080 transmitter 230 V mains A5E03048719
transmitter for FUS380 flowmeter with backup-battery as spare part
series. Transmitter Article No. transmitter for SONOKIT flowme-
7ME3450-0AA10-2AA0 ters. Transmitter Article No.
FUS080 transmitter 3.6 V battery A5E02729035 7ME3450-0AA40-2AA0
(battery included) as spare part When ordering: Inform on flowmeter order no. and flowmeter serial no.
transmitter for FUS380 flowmeter (e.g. 7ME3220-xxxxx-xxxx-Z, XX.... and xxxxxxHxxx)
series 1). Transmitter Article No.
7ME3450-0AA10-2AA0 1)
Lithium batteries are subject to special transportation regulations accord-
ing to United Nations "Regulation of Dangerous Goods, UN 3090 and
FUS080 transmitter 230 V mains A5E02699309
UN 3091". Special transport documentation is required to observe these
as spare part transmitter for
regulations. This may influence both transport time and costs.
FUS380 flowmeter series. Trans-
mitter Article No. 7ME3450-
0AA10-2AA0
FUS080 transmitter 230 V mains A5E02729610
with backup-battery as spare part
transmitter for FUS380 flowmeter
series. Transmitter Article No.
7ME3450-0AA40-2AA0
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
3
(392 °F) and black PVC for Sensor cables for FUS880 retrofitting system (7ME3440)
remaining transmitter part,
max. 70 °C (158 °F); imped-
ance 75 Ω Description Article No.
5 m (16.4 ft) cable set (4 pcs.) A5E01208092 Coaxial cable with trans-
for DN 50 … DN 80 (2“ … 3“) ducer connection
remote mounting for use in FUS880 and
SONO 3300 sensors; with 0.3
10 m (32.8 ft) cable set (4 pcs.) A5E01208114 m brown PTFE high tempera-
for DN 50 … DN 80 (2“ … 3“) ture transducer part, max. 200
remote mounting °C (392 °F) and black PVC for
20 m (65.6 ft) cable set (4 pcs.) A5E01208117 the remaining transmitter part,
for DN 50 … DN 80 (2“ … 3“) max. 70 °C (158 ºF); cable
remote mounting impedance 75 W.W.
• 1 × 10 m (32.8 ft) FDK:085L2400
30 m (98.4 ft) cable set (4 pcs.) A5E01208121
for DN 50 … DN 80 (2“ … 3“) • 1 × 20 m (65.6 ft) FDK:085L2401
remote mounting • 1 × 30 m (98.4 ft) FDK:085L2402
0.5 m (1.64 ft) cable set A5E01208126 Transducer spare part set of FDK:087H3007
(4 pcs.) for DN 50 … DN 80 two transducers with gaskets
(2“ … 3“) for compact version for STRANS FUS880 retrofit-
of FUS380/FUE380 ting systems
DN 100 … DN 1200 flowme-
ters
Coaxial cable for FUS080; with
0.3 m brown PTFE high temp.
transducer part, max. 200 °C
(392 °F) and black PVC for
remaining transmitter part,
max. 70 °C (158 °F); imped-
ance 75 Ω
5 m (16.4 ft) cable set (4 pcs.) A5E00695476
for DN 100 … DN 1200
(4“ … 48“) remote mounting
10 m (32.8 ft) cable set (4 pcs.) A5E00695479
for DN 100 … DN 1200
(4“ … 48“) remote mounting
20 m (65.6 ft) cable set (4 pcs.) A5E00695480
for DN 100 … DN 1200
(4“ … 48“) remote mounting
30 m (98.4 ft) cable set (4 pcs.) A5E00695483
for DN 100 … DN 1200
(4“ … 48“) remote mounting
1 m (3.28 ft) cable set (4 pcs.) A5E00695486
for DN 100 … DN 1200
(4“ … 48“) for compact ver-
sion of FUS380/FUE380
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
■ Dimensional drawings
FUS080 transmitter IP67/NEMA 4X/6, wall mounting and compact mounting
71 (2.8)
6 (0.24)
155 (6.10) 133 (5.24)
13 (0.5)
178 (7.01)
71 (2.8)
Ø12 (0.5)
3
155 (6.10)
Ø8 (0.3)
102 (4.02)
13 (0.5)
(0.98)
25
8.5 (0.34)
170 (6.69)
190 (7.45)
Transmitter wall mounted, dimensions in mm (inch) Transmitter compact mounted, dimensions in mm (inch)
Flow Measurement
SITRANS FS (ultrasonic)
Inline ultrasonic flowmeters
SITRANS FUS080/FUE080 transmitter
■ Circuit diagrams
Internal connection
Top of connection Board
External connection
Connection Variant
3
Passive output Positive logic
Open drain V
0V
Output A Shield I < 50 mA
V ≤ 35 V DC
Signal
R
Output B
Negative logic
V
0V
I < 50 mA V ≤ 35 V DC
R
Signal