Active Filters in HVDC Applications: Working Group 14.28
Active Filters in HVDC Applications: Working Group 14.28
ACTIVE FILTERS
IN HVDC APPLICATIONS
Working group
14.28
April 2003
ACTIVE FILTERS
IN HVDC APPLICATIONS
Working Group
14.28
Fourteen active DC filters and one active AC filter exist already in HVDC converter stations. The
interest on active filters for HVDC systems is mainly due the fact that a single active filter is able to
mitigate effectively diverse harmonics simultaneously, which otherwise should require several passive
filters to achieve a comparable result. They can also contribute for reducing the size of the smoothing
reactors used at the DC side and to reduce losses. They are also able to cope with harmonic resonance
problems and to adapt themselves to changes in the harmonic impedance of the system, which are
important characteristics, specially for the connection to the AC side.
This report prepared by the Working Group 14.28 presents both DC and AC active filters, including the
existing installations. The items of the report are nearly arranged in two consecutive parts, the first one
treating the DC application, while the second one covers the AC filters. As active DC and AC filters
share many concepts, the reader interested in such a subject is encouraged to look for it in both parties.
Page 1
CONTENTS
Page 2
2.5.1 Shunt connected active filter ......................................................................................29
2.5.2 Series connected active filter .....................................................................................30
2.6 PARALLEL AND SERIES CONFIGURATION ...................................................................30
2.6.1 Hybrid filter schemes .................................................................................................31
2.7 CONVERTER CONFIGURATIONS .....................................................................................32
2.7.1 Converters ..................................................................................................................32
2.7.2 STATCOM.................................................................................................................34
2.8 ACTIVE AC FILTER CONFIGURATIONS..........................................................................36
2.8.1 Active ac filters for low voltage application ..............................................................36
2.8.2 Active ac filters for medium voltage application .......................................................36
2.8.3 Active ac filters for HVDC applications....................................................................37
2.9 SERIES CONNECTED ACTIVE FILTERS ..........................................................................38
2.10 CONTROL SYSTEM .............................................................................................................38
2.10.1 Introduction ................................................................................................................38
2.10.2 Description of a generic active power filter controller ..............................................38
2.10.3 Calculation of reference current.................................................................................39
2.10.4 Synchronous reference frame (SRF) ..........................................................................41
2.10.5 Other control approaches ...........................................................................................42
2.10.6 HVDC AC active filter control approach...................................................................42
2.11 EXISTING ACTIVE AC FILTER APPLICATIONS.............................................................42
2.11.1 Low and medium voltage ...........................................................................................42
2.11.2 High voltage applications...........................................................................................42
2.12 OVERVIEW ON FILTER SOLUTIONS FOR HVDC SYSTEMS .......................................46
2.12.1 Solution with conventional passive filters .................................................................46
2.12.2 Solution with continuously tuned passive filters .......................................................47
2.12.3 Solution with active filters .........................................................................................47
2.12.4 Solution with continuously tuned passive filters and active filters............................48
2.12.5 Study cases with the Cigré HVDC model ..................................................................48
2.13 FUTURE TECHNOLOGIES ..................................................................................................50
2.14 CONCLUSIONS ON ACTIVE AC FILTERS........................................................................50
3 LIST OF MEMBERS ....................................................................................................................51
4 BIBLIOGRAPHY ..........................................................................................................................51
Page 3
1 ACTIVE DC FILTERS IN HVDC APPLICATIONS
The conversion process in an HVDC transmission system introduces harmonic currents into the DC
transmission lines and the AC grid connected to the HVDC converters. These harmonic currents may
cause interference in the adjacent systems, like telecommunication equipment. The conventional solution
to reduce the harmonics has been to install passive filters in HVDC converter stations [1]. When the
power line consist of cables, this filtering is normally not necessary. The development of power
electronics devices and digital computers has made it possible to achieve a new powerful way for a
further reduction of harmonic levels, namely, active filters.
The active filters can be divided into two groups,
active AC and DC filters. Active DC filter Filter Passive DC filter
installations are in operation in several HVDC cost
links and have been economically competitive due
to increased demand on telephone interference
levels on the DC overhead lines (Figure 1.1.1). An
active AC filter is already in operation as well. In
addition to the active DC filter function of
mitigating the harmonic currents on the DC
overhead lines, the active AC filters may be Active DC filte
required as part of several solutions in the HVDC r
scheme to improve reactive power exchange with
the AC grid and to improve the dynamic stability.
Already in the 1960’s there were attempts to Allowable
develop and install an active filter in a HVDC Interference
level
converter station in Sweden, but the project turned
out unsuccessfully. In the middle of the 1980's the Figure 1.1.1 Conceptual diagram of allowable
technological development of the presently interference level and DC filter cost
installed active filters was initiated. Mainly two
reasons make the projects successful. Primarily,
the prices on semiconductors have decreased dramatically and secondly, digital computers are getting
more powerful.
The reasons to develop first the active DC Filter and subsequently the active AC filter, were:
• Active AC and DC filters consists of two parts, a passive part and a corresponding active part which
are loaded with the same currents. Due to the fact that the passive AC filter is used to supply the
HVDC converter demand of reactive power and thereby loaded with the fundamental current, the
required rating of the DC filter active part is lower than the one of the AC filter active part.
• The control philosophy for the active DC filter is less complex than for the AC one.
• The present HVDC applications where active AC filter are feasible will be limited, due to the fact that
AC filters are also required to supply the HVDC converter demand of reactive power. Often the filter
size is therefore already well above the filtering demand.
Page 4
1.2 TECHNICAL DEMANDS TO DISTURBANCES ON THE DC SIDE
The main reason why specifying demands on the DC circuit is to keep disturbances in nearby telephone
lines within an acceptable limit, which will vary depending on whether the telephone system consists of
overhead lines or underground cables which are generally shielded and therefore have a better
immunity [2]. A summary is given below to illustrate the demands which made feasible to install the
active filters. As described, the demand on disturbances can appear as an harmonic current on the DC
line or as an induced voltage “Uind” in a fictive telephone line. The reader should keep in mind that the
harmonic demand, the specific HVDC system and surroundings (earth resistivity, telephone system etc.)
all together define the DC filter solution.
50 50
1
Uind = å ( 2* π * f
n=1
n * M * In * p n )
2
, Ipe =
p16
* å (k n
2
* pn * I n )
n=1
where fn is the frequency of the n'th harmonic, M is the mutual inductance between the telephone line and
f1 * n
the power line, k n = 800 , In is the vectorial sum of the n'th harmonic current flowing in the line
conductors (Common mode/earth mode current). pn is the n'th psophometric weighting factor defined by
CCITT Directives 1963 [3] (see also Table 1.2.1) and p16 is the 16th psophometric weighting factor. The
characteristic harmonics n=12, 24, 36, 48 as well as the non-characteristic harmonics up to n=50 shall be
considered.
Frequency/Hz 50 100 300 600 800 1000 1200 1800 2400 3000
n 1 2 6 12 16 20 24 36 48 60
pn Factor 0.0007 0.009 0.295 0.794 1.000 1.122 1.000 0.760 0.634 0.525
pn * k n 0.00004 0.001 0.111 0.595 1.000 1.403 1.500 1.710 1.902 1.969
Active DC filters use a controllable converter to introduce currents in the network, presenting a
waveform which counteracts the harmonics. This clause describes types of power stages, converters to be
used in active filters and the possible connections in HVDC schemes.
Page 5
1.3.1 Semiconductors available for a power stage
Three types of semiconductors, suitable for use in an active filter, are available at present:
• The MosFET
• The IGBT
• The GTO
The MosFET is an excellent switching device capable of switching at very high frequencies with
relatively low losses, but with limited power handling capability.
The IGBT has a switching frequency capability which, although very good and sufficient to handle the
frequencies within the active DC filter range, is inferior to the MosFET. However the IGBT power
handling is significantly higher than the MosFET.
The GTO has the highest power handling capacity, but with a relatively limited switching speed far
below the required frequency range for active DC filter. The use of GTO will probably be limited to
handle frequencies below a few hundred of Hertz.
The relatively high frequency band for active DC filtering excludes the use of thyristors and GTO. Even
though the MosFET and IGBT are suited as switching elements in a power stage, the limited power
handling capacity on MosFET and the installed cost evaluations tend to point on the use of IGBT in
future power stages.
Page 6
1.3.2.2 Voltage source converters (VSC)
In the VSC the DC element is a voltage source.
This may be a DC power supply or, in the case of
an active DC filter application, an energy storage
+
unit. In practice, the voltage source for an active C
AC (Volts) V -
DC filter power stage is usually a capacitor with a
small power supply to offset the power stage
losses. A VSC also has the property that its AC
output appears as a voltage source.
The circuit of a simple VSC is shown in Figure
1.3.2. Figure 1.3.2 Simple voltage source converter
Page 7
Smoothing
Reactor
Active Pole
Filter
4
Passive
DC Filter
HVDC
Converter
Active Active
Filter Filter
3 2
Active Active
Filter Filter
5a 5b
Active
Filter
1 Electrode
Page 8
The disadvantages are:
• Even by an optimal design, the rating of “Tc” and the active filter part will be considerable.
• The “Tc” side of the HVDC converter has no earth potential, which should be considered in the design
of the HVDC converter and the transformer “Tc”.
Page 9
1.4 MAIN COMPONENTS IN AN ACTIVE DC FILTER
The active DC filter is a hybrid filter consisting of a passive and an active part. The passive part can
usually be defined as a double tuned passive filter which connects the active part with the DC line. The
active part in the DC filter is defined as the components within the box shown in Figure 1.4.1. All the
components in the active part shall ensure proper function of the active filter in steady state conditions
and during faults.
Figure 1.4.1 shows the active filter components in the filters today.
Light guide
HVDC
Converter
Control
system
Protection
Arrester circuit Amplifier
Bypass
Disconnector Power
Supply
Electrode
Page 10
main capacitor has 1 µF. The root sum of squares of a typical measured current spectrum through the
smoothing reactor gives 15.7 Arms. The current spectrum is used to calculate the assumed voltage which
is required for the active part to compensate the harmonics for the three mentioned filter configurations
shown in Figure 1.4.2.
The reader should pay attention to the fact that the calculated case in Table 1.4.1 is a simplified case,
with a short overhead line connected to a long HVDC cable. The HVDC cable mitigates the influence
from the other HVDC converter. The calculated example will only illustrate the impact of rating on the
active part with selection of different passive parts. In the “real” rating of the DC filter design, the
designer has to include various other parameters.
The primary costs in the design of a conventional DC filter are the smoothing reactor and the main DC
filter capacitor connected to the DC line. If one disregards the smoothing reactor, which costs the same
or more than the main capacitor, the cost of the main capacitor is approximately 90 % of the totals, while
the reactors, the low voltage capacitor and resistors have small influence on the total cost.
Impedance /
4
Assumed Single Single Double 10
1
10
of the HVDC converter and the component deviation. Figure 1.4.2 Impedance characteristic of
Hence it is not necessary for the filter designer to different passive filters
optimise the filter in that respect. When an active DC
filter is used, the frequency deviation will change
from a performance issue to a rating question on the VSC. In a recent project with long HVDC lines,
resistive elements in the passive part of the DC filter have been inserted to reduce the resonance in the
overall system.
The DC capacitor will always be a part of the active DC filter, connecting the active part with high
voltage DC line. In future active DC filters, parts of the resonance circuit or the additional components in
the passive filter are expected to be replaced by larger power stages, since the price of the power stages
decrease rapidly.
Page 11
by a photocell array at the sensor and a second light guide connected to the control equipment. The
following data has to be taken into account when designing the transducer.
• A very high DC current through the current transducer. The DC current makes it difficult to use an
iron core transformer.
• The second harmonic current can be of considerable size (more than 10 Arms), where the harmonics at
other frequencies is in the size of 10 mA, when the control is active.
• Some current transducers may need a power supply at the high voltage DC transmission level. The
current transducer can be equipped with an electronic unit to communicate with ground level
equipment.
• The current measurement with the analogue/digital conversion must be accurate within a large
temperature range from minimum ambient temperature with minimum load in the winter to maximum
ambient temperature with sun and a maximum load in the summer.
• The current transducer shall be able to measure the current with sufficient bandwidth (typical 1,5 to 2
times the selected active range for the control) to secure a well performing control in the active
frequency range (normally in the range 300 to 3000 Hz).
Page 12
low impedance, making a minimum impact on the original passive filter characteristic.
The aim of an active DC filter control is to mitigate the harmonic currents on the pole line and/or the
electrode line current which are originated at the local HVDC converter station, so that the interference
on telephone lines, adjacent to the HVDC lines may be brought within allowable limits. The active DC
filter creates virtually a low impedance path between the pole and electrode lines (or ground, depending
on the configuration of the system) at the chosen harmonic frequencies. In this way, the harmonics are
guided through the DC filter and thereby prevented from entering the HVDC line, so that the disturbance
on the line is diminished.
Below are some of the items that meet an important part of the design specification of the active filter
control:
• The required distortion level
• The modes of operation of the HVDC transmission.
• The type of HVDC transmission.
• The number of terminals in the HVDC system.
• Single active DC filter / multiple active DC filters.
• The control system must be able to recover from abnormal system conditions.
Page 13
The quantity il is the measured harmonic current in the transmission line, Iconv is the disturbance current
from the HVDC converter and Ifilt is the compensation current from the active DC filter. The total line
current Iline is the sum of Iconv and Ifilt. The external process is the transfer function between the output
voltage from the active DC filter uactive and the current Ifilt.
The controller of Figure 1.5.1 consists of four blocks. The first block filters the input signal, to limit its
frequency contents to within the operational range of the active filter (typically 300 – 3000 Hz).
The second block identifies each individual harmonic and then refer it to a set of two orthogonal vectors
(cos nωt, sin nωt - where the integer n corresponds to the harmonic order and ω to 2πf0 and f0
represents the fundamental frequency). The block receives a synchronising signal derived from the
converter AC voltage to enable the controller to adapt to changes in the network frequency. Notch filters,
usually connected in parallel [6], may be used to isolate the individual harmonics.
Iconv
Uactive Ifilt Iline
External Process
PWM Current
Amplifier Transformer
il
Controller Measured
line current
ua cos(nωt) Compensation cos(nωt) Input
sin(nωt) PI Controller sin(nωt) Filter
Synchronisation
The third block performs the function of filter and PI controller. The block also compensates the external
process at the harmonic frequency nf0.
The fourth block combines the output of the previous blocks into a signal with suitable amplitude, phase
and harmonic contents to form the compensating signal.
An example of a measured transfer function of the external process is shown in Figure 1.5.2.
Page 14
Figure 1.5.2 Measured transfer function of external system, Baltic Cable HVDC link
1.5.1.3 The combined control system using feedforward and feedback control
In the combined control system, the major control (feedforward control) mitigates the harmonics. The
feedback controller then plays a supporting role by correcting loop errors that result from measurements
and changing networks. The stability of the active DC filter control, the dynamic specifications of the
active filter and the cost/availability of high bandwidth voltage measurement equipment are some of the
factors that will determine whether the combined controller will be used. It should be mentioned that the
combined feedback and feedforward control system will be considerably more complex than the
conventional feedback control system and has not yet been used in any HVDC systems.
Page 15
Iconv
Uactive Ifilt Iline
External Process
PWM Voltage
Amplifier Measurement
Controller
u conv
ua cos(nωt) Compensation cos(nωt) Input
sin(nωt) PI Controller sin(nωt) Filter
Synchronisation
Page 16
1.6 PROJECT DESCRIPTIONS AND DC FILTER SOLUTIONS
Several active DC filters are in operation in HVDC schemes today. All of the installed active DC filters
for HVDC applications have been manufactured by ABB Power Systems AB and by Siemens AG. This
clause will describe the background of the installed active filters.
In 1991 a test installation of an active DC filter was in operation at the Lindome Converter Station [18].
The first commercial active DC filter was installed at the Tjele Converter Station in the Skagerrak 3
HVDC Intertie commissioned in 1993, the second active DC filter was installed at the Baltic Cable
HVDC Link commissioned 1994. In the Chandrapur-Padghe HVDC Bipole Project two active DC filters
in each station have been commissioned in 2001. In the Tian-Guang long distance HVDC project two
active filters plus one spare active filter in each station have been installed in 2001. One active filter at
both Thailand and Malaysia sides of the EGAT-TNB HVDC Interconnector project have also been
commissioned in 2001.
Page 17
filters in both stations had to be installed. Due to the low impedance of the DC line and cable seen from
Kruseberg, the number of filter branches would be impractical and definitely not economical.
Pole 3
Skagerrak HVDC Intertie
Smoothing Reactor Current transducer
Filter
active part
Pole 1 Pole 2
250 kV, 1000 A 250 kV, 1000 A
Smoothing Reactor Smoothing Reactor
Passive Passive
Filter Filter
Current transducer
Figure 1.6.1 Simplified diagram, showing active filter connection
Filter
active part
Page 18
1.6.3 Chandrapur-Padghe HVDC power transmission project
The DC filter is a passive double tuned 2/6 filter and passive double tuned high-pass 12/24 filter with an
active part. The 2/6 filter is necessary due to resonance with the DC line. Four active filters are installed
and each active DC filter is connected from the pole line to neutral bus (Figure 1.6.3).
The control strategy is to minimise earth mode current. The active DC filters works on whole multiples
of the fundamental frequency in the frequency range 350-2500 Hz. The project was the first project with
four active filters co-operating in one transmission.
The active filter solution in Chandrapur-Padghe replaces one additional passive filter branch in each pole
and station compared to a purely passive solution.
Filter 1 Filter 2
active part active part
Filter 3 Filter 4
active part active part
Page 19
The active filter solution in the Tian - Guang HVDC project replaces one additional passive filter branch
in each pole and station and reduces the size of the smoothing reactor compared to a purely passive
solution.
Filter active
part 2
Filter passive
part 2
500 kV,
900 MW
Page 20
TNB - EGAT HVDC Interconnection (1st stage)
Current
transducer
Current
transducer
To illustrate the performance of the active DC filter, a pole line current was measured in the Skagerrak 3
HVDC Intertie. pole 3 was operated as monopole and the transmitted power level was 240 MW. The pole
line current with and without the active part is shown in Figure 1.7.1. The first current spectrum shows
the line current with the active part not in operation and the second spectrum shows the line current with
the active part in operation.
1 60
The psophometric current (see clause 1.2) I pe = ⋅ å (k n ⋅ p n ⋅ I n )2 of the current spectrum shown
p16 n =1
in Figure 1.7.1, was reduced from 4780 mA to 255 mA. The major harmonic line currents are shown in
Table 1.7.1.
Page 21
Figure 1.7.1 Measured line current spectra, pole 3 operated as monopole.
Page 22
1.8 CONCLUSIONS ON ACTIVE DC FILTERS
• The need for active DC filters is a consequence of stringent demand on telephone systems. Further
introduction of digital and optical systems can reduce these requirements.
• Series connections of active filters in the main HVDC circuit are conceivable, but some basic
problems have to be solved before the solution becomes recommendable.
• All active DC filters implemented today and in the near future will be configured as a hybrid filter,
where the passive filter is used to connect the active part with the high voltage DC line.
• The type most suited to the active filter power stage, particularly high power ones, is the voltage
source converter.
• The relative high frequencies for active filtering exclude thyristors and GTO. Consequently MosFET
and IGBT are used in voltage source converters.
• Although analog control circuit in theory is possible, digital computer assisted controls are preferred.
• All control systems in existing and expected systems with active DC filters use feedback control, but
feedforward control or a combination might be a future option.
• Adequate protection of the voltage source converter is essential for active DC filter schemes.
Page 23
2 ACTIVE AC FILTERS IN HVDC APPLICATIONS
Non-linear loads and sources cause voltage distortion of the sine wave in electrical distribution and
transmission networks. The primary sources of electrical energy, synchronous generators or over-
synchronous running asynchronous generators, produce nearly undistorted sine waves.
Classical loads such as uncontrolled motors, heaters and incandescent lamps connected to a sinusoidal
source will take nearly undistorted currents. This is in contrast to fluorescent lamps, controlled motor
drives, computers and TV sets. Most of the distortion in LV and MV distribution networks is caused by
such loads, and may even be propagated into HV networks. In particular the 5th harmonic is of great
concern for the utilities, particularly during the evening hours. The increasing non-linear loads over the
last ten years are topic of many conferences on power quality.
For larger loads such as traction rectifiers, 12 pulse instead of 6 pulse operation shifts the distortion to
the 11th and 13th harmonics. Sometimes passive filters in single or double tuned configurations are used.
These filters are less effective for distributed loads and non-characteristic harmonics.
HVDC converters feeding into an existing HVAC network are a source of distortion themselves. From
the beginning of the HVDC transmission, these problems have been recognised and passive filters for the
11/13th and 23/25th harmonics are applied in all existing schemes. The filters also contribute to the
compensation of the inductive character of the rectifier and inverter.
The interest in active power filters has grown over a number of years due to more stringent requirements
and guidelines placed on customers and supply utilities such as the IEEE 519 or IEC1000 series. These
place maximum limits on various current and voltage harmonics generated and drawn at the point of
common coupling (PCC). Requirements to develop low-cost and robust active filters with
multifunctional control capabilities, such as sag and dip compensation has emerged from industry. The
developments in active power filters have also motivated their application for HVDC, on the AC, DC or
both sides of the HVDC converter [22],[23],[24],[25].
In contrast to passive filters designed to operate at distinct frequencies, active filters can cover a range of
frequencies, including non-characteristic harmonics. Active filters for the HVDC side are already in
operation and have been discussed in the first part of this report (published in [26]). The power
requirements for HVAC side may be considerably higher. Only one plant is under operation at the AC
side of an HVDC converter station, as a pilot project, and it is also described in this report.
In future HVDC projects new converter technology may be applied, implying that the reactive power can
be separated from the AC filters and thereby make the use of active AC filter more interesting. The most
promising technologies are the Capacitor Commutated Converters (CCC) and the Controlled Series
Capacitor Converter (CSCC), but also GTO controlled converters are able to keep the reactive power
demand from the converter within a minimum.
For tutorial reasons, LV and MV applications of active filters with different control schemes are also
discussed briefly .
Many loads produce harmonics at low and medium voltage networks. Fluorescent tubes and lamps as
well as computers and other electronic devices generate harmonics. For the low and medium voltage, the
Page 24
grid owner may need to install filters at the distribution bus if the voltage distortion caused by all small
harmonic sources in the system is unacceptable. When connecting HVDC converter stations or large
loads to the AC system, that generate harmonics like industrial rectifiers, large motor drives and
electrical arc furnace plants, AC filters are usually installed as a part of these loads or HVDC system in
order to ensure that the injection of harmonics into the AC system is limited to acceptable levels.
Filtering is required due to the following effects of harmonics:
- Additional stresses
The waveform distortion causes losses, resulting in additional heating, and stresses in both
customer's and utility's equipment.
- Maloperation of electronic equipment
Also the harmonics may cause maloperation of electronic equipment and protective equipment, e.g.
protection relays.
- Telecommunication system disturbance
In the case of overhead lines with nearby telecommunication lines, the harmonics may interfere with
the telecommunication via inductive couplings between the two systems. Even the induced voltages
in telecommunication and other low voltage system caused by harmonics flowing in the AC system
may result in voltages higher than the regulations with respect to human safety.
A discussion on the permissible distortion limits is included in the report "Guide to the Specification and
Design Evaluation of AC Filters for HVDC Systems" by the WG 14.30 [27]. Some typical values are
considered in the item 2.12.5 of the present report.
Page 25
filter are avoided. In order to obtain an adequate passive filter design, detailed studies are required to be
performed.
In a typical double tuned filter is shown in Figure 2.3.1.
In Cigré technical brochure no. 139 [27], passive AC filters for HVDC systems are described and
discussed in detail.
With high demand on filter efficiency, it may
be difficult to maintain the reactive power
balance with the AC system and at the same
time to meet the filtering requirements. In this
case more sophisticated solutions should be
applied, such as continuously tuned filters,
active filters or hybrid filters.
2.3.2.1 Introduction
Figure 2.3.2 Continuously tuned filter
As mentioned above, conventional bandpass
filters (for example, 11th and 13th) have to be
equipped with damping resistors to achieve a
broad band characteristic allowing them to
cope with the frequency variations of the AC
network and the variations in component
values due to temperature changes.
Consequently, filtering at high harmonic levels
may require a number of large harmonic filter
banks.
Figure 2.3.2 shows a continuously tuned filter.
A continuously tuned AC filter is always tuned
to the harmonic frequency (e.g. 11th or 13th)
and has a high Q-factor thus giving high
performance and low losses. In the Figure 2.3.3 Principal overview of a filter reactor
continuously tuned filter, the tuning frequency with variable inductance
is automatically adjusted to provide perfect
tuning irrespective of frequency excursions
and component variations. The filters therefore
need no additional damping resistor. The
perfect tuning is achieved by variations of the
inductance of the filter reactor. Just one
continuously tuned filter is sufficient to
provide the required filtering for a particular α
harmonic.
Page 26
winding, the total magnetic flux in the reactor is influenced, thereby changing the inductance. The
linearity of the rate of change of inductance with respect to the control current is high, which simplifies
designing to avoid instability in tuning control.
Unlike passive filters, where the harmonic reduction depends on the combination of filter impedance and
network impedance, active filters use power electronics to produce a voltage or a current with the proper
waveform to mitigate selected harmonics or harmonics inside a given frequency range.
The active filter output has to present all selected harmonics, each one with the amplitude and phase that
are required to counteract the harmonic sources. To get this, voltages and/or currents are measured in the
HVDC station and processed by a suitable control equipment using signal processing techniques. An
IGBT converter (see 2.7, "Converter configurations") produces the necessary voltages or currents as
determined by the control equipment. For HV applications, like HVDC, the active filter will be generally
connected to the network through a passive filter, thus building a hybrid filter scheme.
Due to its nature, active filters present the following characteristics:
• High effectiveness. The harmonics can be mitigated effectively, even if the network impedance is
very low at the harmonic frequencies.
• One active filter alone can mitigate several harmonics simultaneously. This results in smaller place
requirements and simpler filter arrangements in comparison to passive filter solutions.
• In contrast to passive filters, active filters do not introduce any resonance with the network.
This results from the fact that active filters reduce each particular harmonic just by injecting a
controlled voltage or current with the frequency of that harmonic.
• Active filters do not add reactive power to the network, by the same reason as in the last point.
• Elimination of existing resonance effects.
This is achieved through the cancellation of the harmonic voltage on the filter busbar or harmonic
Page 27
current in the lines. Other control method was presented in [24].
• Flexibility for changing frequency characteristics within the rated capability.
Changes, like for instance selection of harmonics to be filtered, can be made just by settings in the
software.
• Self-adaptation to changes in the network frequency.
• Self-adaptation to changes in the network harmonic impedance. Self-tuning control algorithms can
extend this characteristic, so that the necessary performance is reached even though the harmonic
impedance of the network varies over a wide range.
• The characteristic of the same active filter can be optimised for harmonic voltage (e.g. total harmonic
distortion THD, Telephone Harmonic Form Factor THFF, telephone interference factor TIF ) or
harmonic current (e.g. IT product, equivalent disturbing current), depending on the measured
magnitudes and control settings.
The active filter may be connected to the network through a comparatively small passive filter, which can
be switched on before starting the HVDC converter and then stay permanently in service. This
combination between active and passive filters is called a hybrid filter. The additional demand on
reactive power is than covered by capacitor banks and eventually few passive filters.
The use of hybrid filters in HVDC schemes could be considered due to the above listed reasons. Some
cases where these filters should be considered:
• Very small harmonic distortion levels are envisaged.
• The reactive power compensation can be performed with less filters than the amount of passive
filters required for harmonic elimination.
• A passive filter solution gets complex due to resonance with the network
• Other harmonic sources in the network have to be regarded and a current-optimised filter solution is
preferred (rather than a voltage-optimised solution).
• In the series compensated HVDC schemes (Capacitor Commutated Converter CCC, Controlled
Series Capacitor Converter CSCC).
• When an existing filter installation could be up-graded by adding an active part (due to more
harmonics, resonance problems, etc.)
Page 28
2.5 OPERATION PRINCIPLES OF ACTIVE FILTERS
Is Il
Voltage If Harmonic
Sourc e generator
Active
filter
Figure 2.5.1 Shunt connection
Page 29
The active filter needs to be sized only for the harmonic currents, generated by the non-linear load and
not for the full load current. For higher voltages than the voltage level of the active part, a coupling
transformer will be used.
Us Ul
Net Uf Load
Source
Harmonic Active
producing filter
load
In some cases, the combined features of parallel and series configurations may be needed at one location.
A DC link between the two active filters may be used for transfer of active power between the active
filters.
Page 30
Net Load
Source
DC
Active Link Ac tive
filter filter
The following table summarises the preferred configurations depending on the origin of the harmonic
distortion (load or source side) considering common LV and MV applications.
Source Load
Shunt
Distorted Series +
Series
Page 31
Is Il
Voltage If Harmonic
Source generator
Ac tive
filter
Figure 2.6.2 Hybrid configuration
2.7.1 Converters
Basically, two types of converters can be used in active AC filters, the voltage source converter and the
current source converter. In both cases, the converter can present a three-phase (three or four wire type)
or a single-phase structure.
AC
grid
Page 32
2.7.1.2 Voltage source converter
This is the preferred configuration, because it is the most cost-effective. Almost all active filters, which
have been put into operation, have adopted the voltage source PWM inverter structure.
Figure 2.7.2 Three phase 2 level voltage source converter (three-wire type).
The neutrally clamped 3 level converter is used to minimise the losses or to increase power handling
capability. This topology can also compensate unbalanced currents.
Figure 2.7.3 Three phase 3 level voltage source converter (three-wire type).
Page 33
2.7.1.3 Single-phase voltage source converter
Single phase active filters are based on a single phase voltage source bridges shown below. Although
three-phase converters have been used for most low and medium voltage applications, three separate
single-phase converters can be used in the three phase active filter applications also.
2.7.2 STATCOM
The term STATCOM (Static Synchronous Compensator) stands for a device using GTOs , IGCT
(Integrated Gate Commutated Thyristor) or IGBT to produce reactive power at the network frequency.
WG14-19 has prepared a full document on STATCOM principles and applications [28].
This section presents basic principles of the STATCOM and explains how it can be conceived to
incorporate active filter features. The STATCOM can also be used as active filter, if the device is fast
enough (either a high switching frequency or multi levels or a combination).
Page 34
small amount, a voltage appears across the inductor which leads by 90o and a current will flow
which is in phase with the system voltage, i.e. active power is delivered to the STATCOM
5 - The last case is when the system and STATCOM voltages are the same amplitude and the
STATCOM leads the system by a small amount. The inductor voltage now lags the system by 90o
and the current is in anti-phase with the system voltage and active power is returned from the
STATCOM to the system
6 - All operating modes can be performed simultaneously.
In practice no4 and no5 are limited to control the DC voltage of the STATCOM. For other applications,
large energy storage elements are required.
The conditions above are not exclusive, and accordingly combinations of real and reactive current can
be made to flow.
Page 35
order harmonics, but for high power statcoms the range of controllable harmonics can be very wide. With
the use of IGCT and IGBT even low power statcom can handle a wide range of harmonics.
Page 36
for higher voltages, but these are rather suited for advanced forms of reactive power compensation and
voltage regulation. The implementation of harmonic elimination features with these installations is
conceivable, at least for low order harmonics (see 2.7.2.4).
70 mH
10 0.7 µF 21 mH 10
10 20 30 40 50 10 20 30 40 50
Harmonic order
ACTIVE
ACTIVE FILTER
FILTER
Figure 2.8.1 Active filter connected to the HV Figure 2.8.2 Active filter connected to the HV
system through a single-tuned passive filter system through a double tuned passive filter
Page 37
In some HVDC applications, larger reactive
power may be desirable at the active filter
branch. Or an active filter may be installed in
series with an existing passive filter, to improve
an scheme already in operation. In both cases,
the fundamental current in the filter will be
considerable, which should be disadvantageous
compared with the previous examples, as the
fundamental current flows through the active Fundamental
ACTIVE
part of the filter as well. Figure 2.8.3 shows a FILTER Harmonics current
solution that can be used in this case to prevent component
the fundamental current from flowing in the
active filter. In this figure, an LC circuit tuned at
the fundamental frequency was introduced in
parallel with the active part. The LC path takes Figure 2.8.3 Using an LC circuit to deviate the
over the fundamental component of the current, fundamental current component
while the harmonics flow in the active part. This
solution is used in the active AC filter installed
at the Tjele station (Eltra), in Denmark.
During network disturbances or filter switching, high transient currents will flow in the active filter. To
cope with this, the active filter should be equipped with a fast by-passing device, like a thyristor switch.
The by-pass should be initiated if overcurrent is detected and be removed after the overcurrent has
disappeared, with a delay of some hundred milliseconds to match the network typical disturbance times.
This solution is feasible if the current in the insertion point is low. However, in most cases, at least some
hundreds of amperes flow in the line, which makes this arrangement costly with respect to installation
and losses. In addition the equipment must be located at line potential, which increase the cost as well.
Due to these reasons, this solution is not recommended for transmission systems, however it could be
feasible for applications close to end-users in the distribution systems to improve voltage quality.
2.10.1 Introduction
Various control algorithms are applied to active power filtering. It is not the aim of this report to discuss
the various advantages and disadvantages of each but rather to provide a holistic idea of the most well
known techniques. Some of these algorithms were evaluated in reference [29].
Some of the most common algorithms that can be used are described below.
Page 38
The controller normally has as input the supply voltage us, and the line current il. The active filter
controller consists normally of a digital outer-loop and analogue or digital inner loop (PWM) controller,
imbedded into digital signal processors and gate arrays. The input to the PWM inner loop controller is
the injected current if and the DC-link voltage udc. Based on the generated reference current iref, the
converter generates a current which is filtered by a low-pass filter with at least 1 – 2 kHz cut-off
frequency. Normally a step-up transformer is provided. In order to have a bandwidth of for instance 1 – 2
kHz, the required switching frequency of the active filter should be at least 3 - 5 kHz.
The injected current if of an idealised active filter is such that the instantaneous sum of this injected
current and the distorted load current is equal to the active current ia,. In practice the active current is an
ideal sinusoid with the amplitude proportional to the load conductance G at fundamental frequency, as
discussed in the following equation (assuming us as the fundamental frequency component of the supply
voltage) [30],[31]:
i f (t ) = il (t ) − ia (t ) = il (t ) − G.u s (t ) (4)
External inputs to the active filter controller may also be included to input the set references for
maximum harmonic levels, THD, individual harmonic limits, reactive power demands, etc.
Page 39
sub-divided the apparent power into two orthogonal components namely active power and fictitious
power. Active power is based on the rate of energy transferred per time unit and is only available after
some time. This means that it is not possible to compensate for fictitious power components in real time.
This approach is recommended by the International Electrotechnical Commission (IEC). Several time
domain implementations of active filter control have been used [30],[32],[33],[34],[35],[36], [37], [38].
One of the most successfully commercialised algorithms for active filter controllers is based on the
instantaneous reactive power theory (IRPT). Akagi [33] introduced the IRPT, depicted in Figure 2.10.2.
He defined a new electrical quantity, the instantaneous reactive power (q) as a unique value determined
by using the instantaneous values of the three phase voltages and load currents. The related equations are
also included here.
3 to 2 phase
ilr (t) iα
ils (t) 3 HP-Filter 2 to 3 phase
ilt (t) iβ iα q iα q(ac) irh* (t)
2
Calculate 2
ish* (t)
p (7)
vr(t) vα iβ q iβ q(ac) 3 ith* (t)
vs(t) 3
vt(t) vβ
2
é vo ù é1 / 2 1 / 2 1 / 2 ù év r ù
ê ú 2ê ú
ê vα ú = ê 1 − 1 / 2 − 1 / 2 ú êêv s úú (5)
3ê
êv β ú
ë û ë 0 3 / 2 − 3 / 2úû êë vt úû
éio ù é1 / 2 1/ 2 1 / 2 ùéir ù
ê ú 2ê 1 ú
−1 / 2 −1 / 2 úêêis úú
êiα ú = 3ê (6)
êiβ ú ê 0 3 / 2 − 3 / 2úûêëit úû
ë û ë
é po ù évo 0 0 ù éio ù
ê pú = ê0 vα
úê ú
vβ ú êiα ú
ê ú ê (7)
êë q úû ê 0 −vβ vα úû êëiβ úû
ë
Page 40
−1
éirh* ù é1/ 2 1 0 ù évo 0 0 ù é po ù
ê*ú 2ê úê ú
êish ú = 3 ê1/ 2 −1/ 2 3 / 2 ú.ê 0 vα vβ ú êê pac úú (8)
êith* ú ê1/ 2 −1/ 2 − 3 / 2ú ê 0 − v v ú êq ú
ë û ë ûë β α û ë ac û
The measured three phase voltages and currents are converted into α−β co-ordinates using (5) and (6).
The instantaneous power is defined as the vector sum of the dot products of the α−β co-ordinates and
reactive power as the vector product of the α−β co-ordinates as shown in (7). The fundamental of the
source current is transformed by these calculations to DC components of the instantaneous active and
reactive power and harmonic values. A high-pass filter and the conversion back to three phases with (8)
can extract the harmonic components. The theory is also extended to include zero-phase sequence
components and instantaneous active power (p). It was implemented in various three-phase topologies
[32],[33].
éi s ù ée ù
ê qdc ú é cos(ω t ) sin(ω t ) ù êiqdc ú
ê s ú = ê− sin(ω t ) cos(ω t )ú ê e ú (10)
êi ú ë û i
ëê ddc ûú
ë ddc û
é ù
ê 1 0 úú
éiar ù ê
êi ú = 2 ê− 1 3 ú. éiqdc
s ù
ê as ú ê 2 ê s ú
3 2 ú êëiddc úû (11)
êëiat úû ê ú
ê− 1 − 3ú
êë 2 2 úû
The three phase currents are converted into the two phase α−β co-ordinates in a similar way as in
equation (6), excluding the zero-phase sequence components. By using (9), these two stationary reference
frame quantities (is) are then converted into two synchronous rotating reference frame quantities (ie). The
fundamental frequency components are now transformed into a DC quantity and the harmonics to AC
components which are separated using a low pass filter . A PI controller ensures zero steady state control
error. The resulting DC components are then converted back to the stationary reference frame with (10).
The three active current components of the load current are calculated by using (11).
Page 41
2.10.5 Other control approaches
Bhattacharya [38] introduced a method to control an active filter based on the synchronous reference
frame technique [34] extended into the flux domain by integrating the voltage. Several other approaches
are developed which differs somewhat form these original approaches[39]. Some implementations
estimators used neural networks and Kalman filters in electrical networks with highly dynamic
characteristics, with varied success[36]. In some cases the harmonic current reference is generated in a
selective harmonic approach and sometimes injected without any line current feedback [40],[41],[42].
Page 42
The only active AC filter at the HVAC network to date is in operation at the HVDC converter station of
Tjele (Eltra) in Denmark.
Page 43
400 kV Bus
Capacitive Existing
potential Optical passive
transformer interface filter
ZF2
From the
other phases
ACTIVE AC FILTER
To/From main
Simadyn D components of
cubicle the other phases
Common (control and (in the container)
control and auxiliary protection)
equipment
1 3 4 5 6 7
IGBT 9
conv. LP 8
Main components
(one set for each phase)
LV room MV room
Legend: -Control -Transformers
-IGBT converters -Switchgear
1 - IGBT-Converter -Low voltage equipment -Medium voltage equipment
2 - Inductor for the adaption
2,5 m
of the inductivity
3 - Thyristor switch for
converter protection
(U> , I> ) 3,3 m
4 - Transformer
5 - Low-pass Filter
6 - Vacuum switch
7 - ZnO-Arester
8 - Isolating and ground switches
9 - LC-branch to deviate the 3,9 m
50 Hz current component
8,3 m
Figure 2.11.1 Structure of the active AC filter at the HVDC station of Tjele (Eltra), Denmark
Page 44
2.11.2.2 Harmonic control system
The principle of the harmonic control is illustrated in Figure 2.11.2. The voltage at the 400 kV bus is
sensed by a voltage transformer and transmitted to the active filter through optical fibres ending directly
in the control equipment. Each selected harmonic present in the input signal is split into two components
in the frequency domain and separated by the block (3). This one feeds a complex controller (4), which
has essentially a low-pass filter and a PI characteristics. The output of the controller is than shifted back
to the time domain by multiplication by cos(hωt) and sin(hωt), where h is the order of the harmonic, ω is
the network angular frequency and t is the time. There is such a controller for each selected harmonic and
these operate simultaneously.
The PWM amplifier block (8) embodies the IGBT converter and other above listed components of the
active filter. The output voltage Uactive of the active filter influences the filter current Iflt, which is
combined with the harmonic current Iharm in the network (essentially due to the HVDC converter), in
order to eliminate the harmonics in the 400 kV voltage bus, Ubus. Because the harmonic impedance at the
AC bus changes with the network configuration, a self-tuning system (7) follows up these changes and
adapts the harmonic controllers accordingly.
IHARM
EXTERNAL PROCESS
9 IFLT 10
Coupling UBUS
Network
(passive filter)
Voltage transformer
UACTIVE
Optical 1
interface
PWM 8
Amplifier
CONTROL EQUIPMENT
IGBT 6 Self-tuning 7
control system
HARMONIC CONTROLLER
Figure 2.11.2 Basic harmonic control loop of the active AC filter at Tjele, Denmark
Page 45
2.11.2.3 Field measurements
The graphics in Figure 2.11.3 show results of site
measurements.
The figure shows plots from a measurements of
the 400 kV busbar voltage at the of the Eltra's
Tjele substation, Denmark without (top) and with
(bottom) active filter control. It can be seen that
the active filter causes a strong reduction of the
selected harmonics. A reduction of more than
30 dBV is shown (Figure 2.11.3) for the 23rd
harmonic in this case.
The measurement was performed using a 5 7 11 13 23 25
Harmonic numbers
35 37 47 49
This section gives an overview on the application of the previously discussed filter technologies in
HVDC stations. A comparison using study cases based on the Cigré benchmark model is also included.
Page 46
2.12.2 Solution with continuously tuned passive filters
Page 47
assigned to the filters that consist of active (hybrid) filters. The balance reactive power compensation is
provided by the series capacitors. This solution has the following main advantages:
• Needs small size filters that facilitate fulfilment of voltage change on switching in a weak a.c.
network.
• Avoids the use of shunt reactors or Static Var Compensators (SVC) at minimum load, particularly in
a weak a.c. network.
• Gives high performance (see item 2.4) and low losses.
• Avoids frequent switching of filters thus reducing wear and maintenance requirement on the
switchgear.
2.12.4 Solution with continuously tuned passive filters and active filters
This solution may comprise active ac filters with moderate amplifier rating and continuously tuned
passive filters, providing high efficiency with both series compensated and conventional HVDC
converter stations. In this solution continuously tuned 11th and 13th filters can be combined with an active
filter for higher harmonics (for example, 23rd to 49th).
The three filter configurations that satisfy the specified performance are
1- Conventional 11/13th, 24/36th and high pass third harmonic tuned filters (HP3 filters)
2- Continuously tuned 11th and 13th filters, with conventional HP24, HP36 and HP3 passive filters
3- Continuously tuned 11th and 13th filters, a conventional HP3 passive filter for the 3rd harmonic and
an active (hybrid) filter for higher order harmonics supplying 75 MVAR reactive power.
The used filter and system impedance data are presented in Figure 2.12.1 .
The performance requirements are defined in terms of the following parameters:
Parameter Limit
Dn, (Individual Harmonic Distortion) 1.0 % for all odd harmonics
0.5 % for all even harmonics
THD 1.5 %
THFF 1.0 %
Page 48
HP24, HP36 HP3 11/13th 24/36th
C1 C1 C1 C1
L1 L1 R1
C2
L1 R1 L1 R1 C2 L2 R2 C2 L2 R2
C1 C1
L1
o
+ 80
Rad=2000 Ohm
C2 L2
L1 o R
- 80
ACTIVE
FILTER
-jX
Rmin = 4 Ohms
Page 49
The highest values of each of the performance parameters at rated (1000 MW) power are:
The configurations with the continuously tuned filter and active filters (configuration 3) give better
performance as compared to that with the conventional passive filters.
These results cannot be generalised. For drawing conclusions for specific projects, the calculations need
to consider realistic input data regarding AC system, e.g. harmonic impedance and reactive compensation
requirements. Also filter detuning (important for passive filters) has to be considered.
Voltage source converters (VSC) are expected for DC interconnections in the future. By this reason less
requirements for external reactive power demand and low frequency harmonic distortion compensation
would be required in the future. In such a case at large power ratings, passive or small active filters may
be included to compensate non-characteristics harmonics at higher frequencies than the PWM switching
frequency of the main VSC. By this method of operation, the VSC can compensate lower order
harmonics internally. At this moment voltage source DC-link converters are available at the 100 – 350
MVA power range at DC-links of 100 – 150 kV DC.
The application on the LV and MV range in Custom power, active power and power quality mitigating
devices are expected to accelerate in the future, increasing both in power rating and performance.
• For HVDC solutions a hybrid active power filter would be required in order to minimise the power
rating of the active power filter and maximise the performance of the full filter.
• For retrofitting existing HVDC links with increased power quality problems in networks, it is
expected that active filter configurations will be added to existing passive filter solutions.
• For series compensated HVDC systems, hybrid active power filters and/or tuneable passive solutions
may be more cost effective than a pure passive solution.
• Active filters using multi-level topologies may be connected directly to the MV and LV networks
without the use of transformers.
• It may be advantageous to connect active filters for HV networks via an existing or special coupling
transformer. In such a case the current regulating reactor may be included into the design of the
series impedance of the transformer. For protection purposes it is unlikely to connect the active filter
on HV networks directly onto the supply voltage.
Page 50
• In the future voltage source converter DC links may combine the harmonic filter and reactive power
demand into a single power solution for HV networks.
3 LIST OF MEMBERS
The WG 14.28 members are: Prof. GC Damstra (Convenor, The Netherlands), M Pereira (Secretary,
Germany), N Andersen (Denmark), T Aritsuka (Japan), R Dass (India), Prof. JHR Enslin (South Africa),
PJ Fitz (England), S Gunnarsson (Sweden), NH Jendal (Norway), J Schonek (France), PL Sørensen
(Denmark).
4 BIBLIOGRAPHY
[1] CIGRÉ WG 14-30. “Guide to the Specification and Design Evaluation of AC Filters for HVDC
Systems.”, Technical Brochure 139, April 1999.
[2] CIGRÉ Task Force 14.03.02, "DC Side Harmonics and Filtering in HVDC Transmission
Systems." Technical Brochure Ref. 92 , April 1995.
[3] “Directives concerning the protection of telecommunication lines against harmful effects from
electricity lines”, by The International Telecommunication Union, New Dehli-1960, edition 1963.
[4] Lozinova N.G., Mazurov M.I., "Research on Active Filter for the HVDC Transmission Line".
Transactions of NIIPT, №56, 1997, St.-Petersburg (in Russian).
[5] Zmaznov E.Y., Lozinova N.G. "Development of Active DC Filter for the HVDC Power
Transmission Line". IV Symposium "Electrical Engineering 2001", paper 1-28, Moscow region,
2001 (in Russian)
[6] Zhang W., “On Feedback Control of Active DC Filters in HVDC Cable links with coastal lines”.
Royal Institute of Technology, Stockholm 1995.
[7] Mohan N., Peterson H.A., Long W.F, Dreifuerst G.R., Vithayathil J.J., “Active filters for ac
harmonic suppression” ,A 77 026-8, IEEE 1977.
[8] Mohan N., “Modified high pass filters for HVDC converter terminals”, A 79 423-5, CH1458-
9/79/0000-4235, IEEE 1979.
[9] Wong C., “Feasibility Study of AC- and DC-side Active Filters for HVDC Converter Terminals”,
IEEE Trans. on Power Delivery, vol 4, no. 4, pp. 2067-2075, Oct 1989.
[10] Broche C, “Harmonic reduction in dc link current of a PWM induction motor drive by active
filtering”, IEEE Trans. Power Electronics, vol. 7, no. 4, pp 633-643, Oct. 1992.
[11] Peng F.Z., “A new approach to harmonic compensation in power systems-series connection of
passive and active filters”, IEEE Trans. on industry Applications, Vol. 27, No.6, pp. 1020-1025,
Nov./Dic. 1991.
[12] Vaupel G., “Wide-band filter with actively reduced losses for power systems”, EPE ’95, Sevilla,
Vol. 0. Pp. 1-16.
Page 51
[13] Watanabe E.H., “Series active filter for the DC side of the HVDC transmission systems”, Proc.
IPEC-Tokyo, Japan, pp 1024-1030, Apr. 1990.
[14] W. Stygar and G. Gerdin, “High Frequency Rogowski Coil Response Characteristics,” IEEE
Trans. on Plasma Science, vol. PS-10, no. 1, March 1982, pp. 40-44.
[15] H.P. Mercure, P. Bard, “Direct measurement of residual harmonic currents on a + and - 450kV DC
line using Rogowski coils,” 7th International Symposium on High Voltage Engineering, Dresden,
August 1991.
[16] Nyman et al, “Baltic Cable,” Cigre Colloquium Paper 1.4, 1995.
[17] Nyman et al, “The Baltic Cable HVDC project” Cigre Session, 1996.
[18] Zhang et al, “Active DC filter for HVDC system- A Test Installation in the Konti-Skan dc Link at
Lindome Converter Station,” IEEE Trans. on Power Delivery, vol. 8, no. 3, July 1993, pp. 1599-
1606.
[19] Holtzhausen, Enslin, Venter, “An evaluation of different active filter topologies for the Cahora
Bassa HVDC project,” Cigré SC-14 International Colloquium on HVDC and FACTS,
Johannesburg, South Africa, 28 - 30 September 1997.
[20] A Horn; LA Pittorino; JHR Enslin: "Evaluation of Active Power Filter Algorithms under non-
sinusoidal and unbalanced conditions," IEEE PES, 7 th International Conference on Harmonics
and Quality of Power (ICHQP-96), Las Vegas, Nevada, USA, pp 217-224, 16-18 Oct 1996
[21] LA Pittorino; JA du Toit; JHR Enslin: "Evaluation of converter topologies and controllers for
power quality compensators under unbalanced conditions", IEEE Power Electronics Specialists
Conference (PESC-97), St Louis, Missouri, USA, pp 1127 - 1133, 22 - 27 June 1997.
[22] HN Holtzhausen, JHR Enslin, AC Britten, "The reduction in the equivalent disturbing current of
an HVDC line using an active DC power filter", 8th International Power Quality Applications
Conference (PQA '98), Cape Town, SA, Session 5, 9-11 November 1998.
[23] JHR Enslin, "Unified approach to power quality mitigation", IEEE International Symposium on
Industrial Electronics (ISIE'98), Vol 1, pp 8-11, 7-10 July 1998. (Invited plenary paper)
[24] T.N.Le, M.Pereira, K.Renz, G.Vaupel, "Active Damping of Resonances in Power Systems".
IEEE/PES Summer Meeting, Vancouver, B.C., Canada, July 1993.
[25] M.Pereira, G.Wild, "Experience with the application of active AC and DC filter in HVDC
systems", IEEE / PES T&D 2002 Latin America, São Paulo, Brazil, March 2002.
[26] Cigré Electra ref. no. 187, "Active DC filters in HVDC applications", WG 14.28, 1999.
[27] Cigré technical brochure no. 139, "Guide to the Specification and Design Evaluation of AC Filters
for HVDC Systems", WG 14.30, 1999.
[28] Cigré technical brochure ref. no. 144, "Static synchronous compensator (STATCOM)", WG
14.19, 1999.
[29] A Horn; LA Pittorino; JHR Enslin: "Evaluation of Active Power Filter Algorithms under non-
sinusoidal and unbalanced conditions," IEEE PES, 7 th International Conference on Harmonics and
Quality of Power (ICHQP-96), Las Vegas, Nevada, USA, pp 217-224, 16-18 Oct 1996.
[30] JHR Enslin; JD van Wyk: "A new control philosophy for power electronic converters as fictitious
power compensators", IEEE Transactions on Power Electronics, vol PEL-5, no 1, pp 88-97, Jan
1990.
[31] S. Fryze, “Wirk-, Blind-, und Scheinleistung in Elektrisch Stromkreisen mit
nichtsinusoidalformigen Verlauf von Strom und Spannung,” ETZ, vol. 53, no. 25, 1932, pp. 596-
599, 625-627, 700-702.
Page 52
[32] H. Fujita and H. Akagi, “A Practical Approach to Harmonic Compensation in Power Systems -
Series Connection of Passive and Active Filters,” IEEE Trans. on Ind. Appl., vol. 27, no. 6,
November/December 1991, pp.1020-1025.
[33] H. Akagi, Y. Kanazawa and A. Nabae, “Instantaneous Reactive Power Compensators Comprising
Switching Devices without Energy Storage Components,” IEEE Trans. on Ind. Appl., vol. IA-20,
no. 3, May/June 1984, pp. 625-630.
[34] S. Bhattacharya, D.M. Divan and B. Banerjee, “Synchronous Frame Harmonic Isolator using
Active Series Filter,” EPE 1991, pp. 3-030 - 3-035.
[35] P. Jintakosonwit, H. Fujita and H. Akagi: “Control and performance of a fully-digital-controlled
shunt active filter for installation on a power distribution system” IEEE Trans. on Power
Electronics, vol. 17, no. 1, Jan. 2002, pp. 132-140.
[36] JHR Enslin; JD van Wyk; M Naudé: "Adaptive closed-loop control of dynamic power filters as
fictitious power compensators", IEEE Transactions on Industrial Electronics, vol IE-37, no 3, pp
203-211, June 1990.
[37] G. Dinkel and R. Gretsch, “Kompensator für Oberschwingungen und Blindleistung,” ETZ Archiv,
vol. 9 no. 1, pp. 9-14, 1987.
[38] S. Bhattacharya, A. Veltman, D.M. Divan and R.D. Lorenz, “Flux-Based Active Filter
Controller,” IEEE Trans. on Ind. Appl., vol. 32, no. 3, May/June 1996, pp. 491-501.
[39] G.W.Chang, "A New Method for Determining Reference Compensating Currents of Three-Phase
Shunt Active Power Filters". IEEE Power Engineering Review, April 2002, pp. 68-70.
[40] M.Pereira, K.Sadek, "Application of Power Active Filters for Mitigation of Harmonics".
Stockholm Power Tech symposium, June 1995.
[41] D. Basic, V.S. Ramsden, and P.K. Muttik, “Harmonic Filtering of High-Power 12-Pulse Rectifier
Loads with a selective Hybrid Filter,” IEEE Trans. on Industrial Electronics, vol. 48, no. 6,
December 2001, pp. 1118-1127.
[42] P-T Cheng, S. Bhattacharya and D.M. Divan, “Operations of the dominant harmonic active filter
(DHAF) under realistic utility conditions”, IEEE Trans. on Industry Applications, vol 37, no 4, pp
1037-1044, July/Aug 2001
[43] Akagi, H: “New Trends in Active Filters for Power Conditioning,” IEEE Trans. on Industry
Applications, vol. 32, no. 6, Nov./Dec. 1996, pp. 1312-1322.
[44] Cigré Working Group 14-31 - Technical report on custom power.
[45] J.H.R. Enslin and J.D. van Wyk, “Measurement and Compensation of Fictitious Power Under
Nonsinusoidal Voltage and Current Conditions,” IEEE Trans. on Instrumentation and
Measurement, vol. 37, no. 3, September 1988, pp. 403-408.
[46] P.-J. Randewijk and J.H.R. Enslin, “Inverting DC Traction Substation with Active Filtering
Incorporated,” IEEE PESC’95 Conf. Proceedings, Atlanta, USA, June 1995, pp.360-366.
[47] G.L. van Harmelen and J.H.R. Enslin, ”Real-Time Dynamic Control of Dynamic Power Filters in
Supplies with High Contamination,” IEEE Trans. on Power Electr., vol. 8, no. 3, July 1993, pp.
301-308.
[48] R.G. Coney, “The Impact of Power Quality on Industry in Africa,” IEEE AFRICON’96 Conf.
Proceedings, Stellenbosch, South Africa, September 1996, pp. 21-27.
[49] A. van Zyl, J.H.R. Enslin and R. Spée, “A New Unified Approach to Power Quality
Management,” IEEE Trans. on Industry Applications, vol 32, no 6, pp 1323-1330, Nov/Dec 1996.
Page 53