Plumbing Load Analysis and Septic Design

This document provides a plumbing load analysis for two separate projects based on the Revised National Plumbing Code of the Philippines. For the first project: the minimum septic tank capacity is 1,500 gallons based on a total drainage fixture unit load of 28. The recommended septic tank dimensions are provided. For the second smaller project: the minimum septic tank capacity is 1,000 gallons based on a total drainage fixture unit load of 8. The recommended pipe sizes for drainage, soil, waste and vent pipes are specified for both projects based on the total fixture loads. For the first larger project: the recommended water supply main is 40mm diameter to supply the 88 total water supply fixture units.

Uploaded by

Neil Young
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views1 page

Plumbing Load Analysis and Septic Design

This document provides a plumbing load analysis for two separate projects based on the Revised National Plumbing Code of the Philippines. For the first project: the minimum septic tank capacity is 1,500 gallons based on a total drainage fixture unit load of 28. The recommended septic tank dimensions are provided. For the second smaller project: the minimum septic tank capacity is 1,000 gallons based on a total drainage fixture unit load of 8. The recommended pipe sizes for drainage, soil, waste and vent pipes are specified for both projects based on the total fixture loads. For the first larger project: the recommended water supply main is 40mm diameter to supply the 88 total water supply fixture units.

Uploaded by

Neil Young
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Plumbing Load Analysis: Presents tables summarizing various calculations related to plumbing loads, focusing on total drainage fixture units and other metrics.

PLUMBING LOAD ANALYSIS PLUMBING LOAD ANALYSIS

NOTE: All Computations, Sizes and Dimensions are based on the NOTE: All Computations, Sizes and Dimensions are based on the
Revised National Plumbing Code of the Philippines (RNPCP). Revised National Plumbing Code of the Philippines (RNPCP).
A. FOR THE SIZE AND CAPACITY OF THE SEPTIC TANK -1 A. FOR THE SIZE AND CAPACITY OF THE SEPTIC TANK - 2
1. DRAINAGE FIXTURE UNIT LOAD 1. DRAINAGE FIXTURE UNIT LOAD
FIXTURE UNIT NO. DFU LOAD FIXTURE UNIT NO. DFU LOAD
WC 7 4 28 WC 2 4 8
URI 0 3 0 URI 0 3 0
LAV 2 0 LAV 2 0
FD 2 0 FD 2 0
TOTAL DRAINAGE FIXTURE UNITS = 28 TOTAL DRAINAGE FIXTURE UNITS = 8
2. BASED ON THE TABLE B-2 OF RNPCP FOR 28 DFU TOTAL LOAD 2. BASED ON THE TABLE B-2 OF RNPCP FOR 8 DFU TOTAL LOAD
The minimum SEPTIC TANK CAPACITY shall be: The minimum SEPTIC TANK CAPACITY shall be:
1,500 gallons ( 5,677.5 liters) = 5.677 m3 5.677 cu.m. 1,000 gallons ( 3,785 liters) = 3.785 m3 3.785 cu.m.
3. BASED ON THE APPENDIX B.5.4 OF RNPCP 3. BASED ON THE APPENDIX B.5.4 OF RNPCP
3.a. DIGESTIVE CHAMBER 2/3 x 5.677 cu.m. = 3.785 cu.m. 3.a. DIGESTIVE CHAMBER 2/3 x 3.785 cu.m. = 2.523 cu.m.
W = 1.68 m L = 1.6 m D = 1.5m W = 1.5 m L = 1.0 m D = 1.5m
3.b. LEACHING CHAMBER (2-UNITS) 1/3 x 3.785 cu.m. cu.m. = 1.892 cu.m. 3.b. LEACHING CHAMBER (2-UNITS)
1/3 x 2.523 cu.m. cu.m. = 1.262 cu.m.
W = 1.68 m L = 0.9 m D = 1.5m W = 1.5 m L = 0.9 m D = 1.5m
B. FOR THE SIZE OF SOIL AND WASTE PIPE, DRAIN AND SEWER PIPE B. FOR THE SIZE OF SOIL AND WASTE PIPE, DRAIN AND SEWER PIPE
BASED ON THE TABLE 7-1 AND 7-2 OF RNPCP, THE SIZES OF FF. SHALL BE: BASED ON THE TABLE 7-1 AND 7-2 OF RNPCP, THE SIZES OF FF. SHALL BE:
Building Drain Pipe = 150mmØ Floor Drain Pipe = 50mmØ Building Drain Pipe = 150mmØ Floor Drain Pipe = 50mmØ
Building Sanitary Pipe = 150mmØ Vent Thru Roof Pipe = 50mmØ Building Sanitary Pipe = 150mmØ Vent Thru Roof Pipe = 50mmØ
Water Closet/Soil Pipe = 100mmØ Kitchen Sink Pipe = 50mmØ Water Closet/Soil Pipe = 100mmØ Kitchen Sink Pipe = 50mmØ
Lavatory Pipe = 50mmØ Drainage Pipe = 150mmØ Lavatory Pipe = 50mmØ Drainage Pipe = 150mmØ
C. FOR THE SIZE OF WATER SUPPLY AND BRANCH PIPE
WATER SUPPLY FIXTURE UNIT LOAD
FIXTURE UNIT NO. WSFU LOAD
WC 7 4 28
LAV 8 2 16
URI 0 3 0
HB 1 4 4
SH 8 4 32
KS 2 4 8
TOTAL WATER SUPPLY FIXTURE UNITS = 88
FROM CHART A-4 TO A-7 OF RNPCP, THE 88 WSFU INCLUDING
FRICTION LOSS, THE SUPPLY MAIN COLD WATER PIPE SHALL
BE 40 mmØ.
FROM WATER LINE TO FIXTURE PIPE, THE PIPE SIZE SHALL BE:
WC = 1/2"Ø URI = 1/2"Ø
LAV = 3/8"Ø KS = 1/2"Ø
SS = 3/4"Ø HB = 3/4"Ø
D. FOR WATER VOLUME DEMAND
FOR COMMERCIAL USE: ASSUME 10 GALLONS PER 1 WSFU
WATER VOLUME = 10 x 88 880 gal
FIRE RESERVE = 50 gal
TOTAL GALLONS = 930
3524.7 liters

USE: 3525 liters CAPACITY STAINLESS TANK


*note: FOR HORSEPOWER RATING OF TRANSFER PUMP (OPTIONAL)3525 liters
STAINLESS TANK WATER SUPPLY SHALL BE PUMP BY 1.0 hp ELECTRIC
MOTOR PUMP.