Technical Specifications

ASP 31-302
Group: Controls
Part Number: ASP 31-302
Date: February 2015

Daikin Single Duct VAV Box

Description
The MQTHI5 is our high performance single duct air
terminal product line. This series is available in a wide
range of sizes with available capacities from 80 to 8000
CFM. The MQTHI5 sets the standard in the industry for
construction, performance and quality.

Available Features
Units include:
• Round inlet collar on unit sizes 6"–16"
• Rectangular inlets on sizes 20" and 24"
MQTH15 Single Duct Air Terminal
• Outlets are rectangular with slip and drive connections
• An external 20-gauge control mounting panel
• Control panel covers included on all units
Single Duct VAV Box

Single Duct VAV Box

Figure 1: MQTH15 Components


Standard insulation is dual density
Units size 6 through 16 are constructed glass fiber. Optional liners are For long life and continuous operation,
with a seamless butt weld primary inlet available including Thermopure® the damper shaft rotates in a long life, low
valve to minimize leakage and prevent (closed cell foam), foil face and friction, self-lubricating Thermoplastic
the damper from binding metal liner bearing (not visible in photo)

Control mounting plate and


control cover are shipped
For set-up and balancing standard on all units (right hand
purposes, all units are shipped controls and coil connections
with a convenient balancing are standard) tightly in place
chart located on the outside of
the terminal for conversion from
velocity pressure to CFM
Terminal unit is shipped
with the required control
and power wiring diagrams
The inlet tube for the TH-500
includes a bead that strengthens
the tube and provides recess for
flex duct straps
All units include barbed fittings
to secure tubing tightly in place

Multi-quadrant Averaging Flow


Sensor provides an accurate flow
signal and can maintain accuracy
after a certified balancer has Control panel includes stand-offs
All units are shipped with easy to allow mounting of controls
calibrated the terminal. (Shipped access balancing taps. The
standard on all units) without penetrating the casing
extra ports can be used to read
CFM (through velocity pressure)
directly at the unit

Figure 2: MQTH15 Details

VAV Box Inlet Damper Drive Shaft


Bead formed
on inlet tube
for rigidity and
to allow for a
tight flex duct
connection

Damper position indicator

Seamless weld

Pressure Lines

Brass barbed fittings for tube


connection to VAV Controller
Average signal • Red stripe: Low pressure tap
pressure is obtained • Blue stripe: High pressure tap
in 4 quadrants

Metal sensor tubes extend


through the inlet tube,
allowing external connections
(shown with dust covers)

ASP 31-302 (02/15) ©2015 Daikin Applied | (800) 432–1342 | [Link]