2022 Aeuc
2022 Aeuc
UTILITY CODE
Established by the
Electrical Utilities Sub-Council,
Safety Codes Council
August 2022
Copyright
All rights reserved. No part of this book may be used or reproduced in any form
or by any means, without prior permission of the Safety Codes Council.
Safety Codes Council - 500, 10405 Jasper Avenue, Edmonton, Alberta Canada, T5J 3N4
(780) 413-0099 1-888-413-0099 Fax (780) 424-5134
[Link]
For this Code to be comprehensive and complete, users must have access to two CSA Standards, namely CSA
Standard C22.3 No. 1:20, Overhead Systems, and CSA Standard C22.3 No.7:20 Underground Systems.
General arrangement
The Alberta Electrical Utility Code (the AEUC) is divided into numbered Sections, each covering a specific
topic related to the work. The Sections are divided into numbered Rules, with captions for easy reference,
as follows:
(a) Numbering system - Even numbers have been used throughout to identify Sections and Rules.
Rule numbers consist of the Section number separated by a hyphen from the 3-digit figure. The
intention is that odd numbers may be used for new Rules required by interim revisions. Due to the
introduction of some new Rules and the deletion of some existing Rules during the revision of
each edition, the Rule numbers for any particular requirement are not always the same in
successive editions.
(c) Tables - Tabulated information has been included in order to best organize information and to
avoid unnecessary repetition of information. Tabulated information is not intended to be a
mandatory requirement. Information provided in Tables may be made a requirement of the AEUC
by the Rule which references the Table.
(d) Figures - Several figures have been included in this edition of the AEUC. Users are reminded that the
included figures are intended only as examples of the requirements of the AEUC and are not
intended to be mandatory requirements.
(e) Appendices - Notes on Rules have been grouped into appendices. Informational notes are not
intended to be mandatory requirements. Notes on Rules located in the AEUC are found in Appendix
B. Notes on Rules found in CSA C22.3 No. 1 are included in Appendix C. Notes on Rules found in CSA
C22.3 No. 7 are found in Appendix D. Information included in Appendix B, C, or D may be made a
requirement of the AEUC by a Rule which references the informational note.
Identification of Changes
Changes from the last edition of the AEUC are indicated with a triangle where a requirement has been
added or amended. A triangle is not included where the change to a Rule is due to simple re-numbering,
grammar correction, text formatting, or other non-functional change. The null symbol denotes the
removal of a requirement. Care must be taken not to rely on the change markers to determine the current
requirements of the AEUC.
Additional Contributors
Dzmitry Akishyn Glen Kulak Noel Smith
EPCOR Stantec Fortis Alberta
CONTENTS
PREFACE 2
ACKNOWLEDGEMENT 3
CONTENTS 4
SECTION 0 - OBJECT, SCOPE, AND DEFINITIONS 5
Object 5
Scope 5
Definitions 6
SECTION 2 - GENERAL RULES 9
SECTION 6 - GROUNDING OF OTHER THAN OVERHEAD AND UNDERGROUND POWERLINES 13
Grounding of Generating Stations and Substations 13
Grounding of Buildings, Pipelines, Fences, and Other Objects in Proximity to Generating Stations
or Substations 16
SECTION 8 - SUBSTATIONS AND ELECTRICAL EQUIPMENT INSTALLATIONS 19
Electrical Equipment Buildings 19
Working Space near Electrical Equipment 21
Liquid-Filled Electrical Equipment 21
Guarding and Protection of Live Parts 23
Electrical Equipment and Station Yard 24
Fences 26
Circuit Breakers, Fuses, and Switches 28
SECTION 10 - OVERHEAD SYSTEMS 31
SECTION 12 - UNDERGROUND SYSTEMS 33
FIGURES 37
Figure 1 ~ Ground Electrode and Gradient Control 37
Figure 2 ~ Examples of Ground Electrodes 37
Figure 3 ~ Minimum Clearances about Live Parts 38
Figure 4 ~ Guarding of Live Parts 38
Figure 5 ~ Dimensions of Working Space near Live Parts on Panelboards and Control Panels Indoors 39
Figure 6 ~ Substation Fence Horizontal Separation for Exposed Parts 39
Figure 7 ~ Typical Grounding Plan View – Fence Grounding Interconnection 40
Figure 8 ~ Typical Substation Fence Grounding Application 41
TABLES 43
Table 1 ~ Safe Limits of Approach Distances from Overhead Power Lines for Persons and Equipment 43
Table 3 ~ Minimum Separation or Clearance from Live Parts 43
Table 4 ~ Minimum Spacing for Outdoor Switches in Free Air 44
Table 5 ~ Minimum Vertical Design Clearances above Ground or Rails 45
Table 6 ~ Minimum Design Clearances of Supply Conductors Attached to Buildings 46
Table 7 ~ Minimum Design Clearances from Wires and Conductors Not Attached to Buildings, Signs,
and Similar Plant 47
Table 9 ~ Minimum Grades of Construction for Crossings 48
APPENDIX A - Safety Rules 49
APPENDIX B - Notes on Rules 51
APPENDIX C - Notes on Rules Found in C22.3 No. 1:20 Overhead Systems 57
APPENDIX D - Notes on Rules Found in C22.3 No. 7:20 Underground Systems 59
Compliance with this Code coupled with proper maintenance will provide an essentially safe installation. This
Code is not intended as an instructional manual for untrained persons.
This Code and any standards referenced herein do not make or imply any assurance or guarantee by the
authority adopting this Code, with respect to life expectancy, durability, or operating performance of
equipment and materials referenced herein.
Scope
(See Appendix B.)
Existing installations, including maintenance replacements, maintenance additions, and additions that meet
the original design that currently comply with prior editions of this Code need not be modified to comply with
this edition of the Code except as might be required for safety reasons by the authority having jurisdiction.
Communication lines, circuits, and systems under the scope of this Code include communication systems
owned by electric utilities for the sole purpose of the operation of the electrical utility system.
Communication utilities which fall under federal jurisdiction are excluded from the scope of this Code. This
notwithstanding, the clearances identified in this Code shall apply to communication systems owned or
maintained by communication utilities but installed on electrical utility infrastructure.
Definitions
(See Appendix B.)
For the purpose of correct interpretation, certain terms have been identified in this Code in bold text. Where
such terms or their derivatives appear throughout this Code, they shall be understood to have the meanings
shown below. For terms not specifically defined below, the meaning shall come from the latest revision of
C22.3 No. 1 or C22.3 No.7 if the term is defined therein, and from an ordinary dictionary if not.
authority having jurisdiction – the organization, office, or individual legally authorized to enforce this Code,
unless otherwise noted, and having jurisdiction over specified territory. (See Appendix B.)
combustible dust – dust particles that present a fire or explosion hazard when dispersed and ignited in air.
combustible flyings – solid particles, including fibres that may be suspended in air and can settle out of the
atmosphere under their own weight.
communication system(s) – any physical apparatus, device, line, network segment, or other thing that is used
or is capable of being used for electronic transmission of information over distances. The information may be
in the form of voice telephone calls, data, text, images, or video. Transmission may be by wire, radio, optical
cable, electromagnetic, or other similar means.
communication utility – any corporation, company, individual or association of individuals, or its lessees,
trustees or receivers, that owns, operates, manages or controls all or a part of any plant or equipment for the
provision of telecommunications service, directly or indirectly to or for the public.
competent – adequately qualified, suitably trained and with sufficient experience to safely perform work
without supervision or with only a minimal degree of supervision.
electric distribution system – as defined in the Alberta Hydro and Electric Energy Act. (See Appendix B.)
electric utility – an entity as defined in the Electric Utilities Act. (See Appendix B.)
fire point – the lowest temperature of a liquid in an open container at which vapours are evolved fast enough
to support continuous combustion.
gradient control conductor(s) – a buried conductor used to control touch potential and step potential.
ground potential – the voltage between the point in the earth under consideration and a point in the earth
considered to be at zero voltage.
ground potential gradient – the rate of change with respect to the distance along or through the earth,
expressed in volts per unit distance.
ground resistance – the ohmic resistance measured by the two-probe method or equivalent measuring
method.
guarded – covered, fenced, enclosed, or otherwise protected by means of suitable covers or casings, barrier
rails or screens, mats or platforms, designed to limit the likelihood, under normal conditions, of dangerous
approach or accidental contact by persons or objects.
isolated – to disconnect completely a device or circuit from other devices or circuits, separating it physically,
electrically, and mechanically from all sources of electrical energy. (See Appendix B.)
non-propagating liquid – an insulating liquid that, when subjected to a source of ignition, may burn but the
flame does not spread from the source of ignition.
operator of a utility system or operator of the utility system – the owner of the electrical utility system, and
may include an organization, office, or individual designated by the owner to make policy decisions affecting
the utility.
step potential – the difference in voltage level from one foot of a person to the opposite foot. This can be
felt when a person steps across an energized path of earth. The worker forms a parallel path to the earth
and current flows through the worker as well as the earth. This can result in harmful current levels in some
situations.
substation(s) – as defined in the Alberta Hydro and Electric Energy Act. (See Appendix B.)
transmission line – as defined in the Alberta Hydro and Electric Energy Act. (See Appendix B.)
touch potential – the difference in voltage level between energized electric lines or equipment and the earth.
This may be felt by a person standing on the ground when they contact the electric lines or equipment and
complete a parallel path to earth. The voltage may be supplied by a power system element such as a portable
generator, or by unintentional energization. or by induction. Touch potential can vary greatly, as it depends
on the distance from where the worker is standing to the location of the source voltage.
(1) No person shall construct, maintain, or replace objects, or conduct activities near electrical utility
systems or other objects described in the Scope, except in accordance with this Code.
If a person contravenes any of the Rules of this Code and an unsafe condition exists, then the system, object
or activity shall be altered in a manner and within time limits specified by the authority having jurisdiction.
If there is any conflict between any provisions of CSA Standard C22.1, Canadian Electrical Code, Part I, and
this Code, the provincial ministry responsible for the adoption of these codes shall determine which provision
shall apply.
If standards or other documents referenced in this Code have been amended, revised, or supplemented, the
amendments, revisions, or supplements may be used where special permission has been granted.
If any installation, construction, building or other improvement, or equipment has been installed, placed,
or erected and the installation, placing, or erection results in some other existing installation, construction,
building or other improvement, or equipment being in contravention of this Code, then the installation,
construction, building or other improvement, or equipment last placed in point of time shall be considered as
being in contravention of this Code.
(1) No person shall interfere with, tamper with, or wilfully damage electrical utility systems covered by
this Code.
(2) Electrical utility system poles and structures shall be kept free of all materials and equipment not
required for the system, unless permitted by the operator of the utility system.
(3) No person shall make attachments to electrical utility system poles and structures unless
authorization has been received from the operator of the utility system.
(4) No person shall climb electrical utility system poles or structures or make connections or
disconnections to electrical utility system equipment unless the person has been authorized to do so
by the operator of the utility system.
(5) No person shall enter an electrical utility system generating station, substation, subsurface chamber,
equipment room, or similar location unless that person is authorized to enter by the operator of the
utility system.
(1) This Rule applies to activities near overhead powerlines and not the movement of persons,
equipment, buildings, vehicles, or objects under overhead powerlines.
(2) A person must contact the operator of the utility system before activities other than those in
Subrule (1) are undertaken or equipment is operated within 7.0 meters of an energized overhead
line to:
(a) determine the voltage of the power line; and
(b) establish the appropriate safe limit of approach distance listed in Table 1.
(3) Except as provided for in Subrule (4), a person must ensure that the safe limit of approach distance,
as established in Subrule (2), is maintained and that no activities are undertaken and no equipment is
operated at distances less than the established safe limit of approach distance.
(4) A person must notify the operator of the utility system before activities are undertaken or
equipment is operated in the vicinity of the power line at distances less than the safe limit of approach
distances listed in Table 1, and obtain the operator’s assistance in protecting persons involved.
(5) Notwithstanding Subrules (1) through (4), Table 1 does not apply to utility workers falling under the
OH&S Code, Part 40 Utility Workers – Electrical.
(6) A person must ensure that earth or other materials are not placed under or beside an overhead
power line if doing so reduces the safe clearance to less than the Minimum Vertical Design
Clearances above Ground or Rails as defined in Table 5 of this Code and the safe limit of approach
distances listed in Table 1.
(7) A person must follow the direction of the operator of the utility system in maintaining the
appropriate safe clearance when conducting activities near an overhead power line.
(8) If an activity is being carried out near the safe limits of approach distances specified in Table 1,
the person completing the activity shall assign a competent person to act as an observer whose only
responsibility is to ensure that the safe limit of approach distances will be maintained.
(9) A person shall not excavate or perform similar operations in the vicinity of an overhead or
underground power line if it reduces the electrical and structural integrity of the power line including
associated grounding equipment.
No person shall construct or place buildings or other objects within the minimum clearances from overhead
equipment or lines prescribed by this Code unless it is acceptable to the authority having jurisdiction and the
operator of the utility system.
(1) The safe limit of approach distances listed in Table 1 do not apply to a transported load, equipment,
or building that is transported under energized overhead power lines.
(2) If the total height, including equipment transporting it, is less than 4.15 m, the load can be moved
under lines.
(3) If the height of the equipment, building, or object exceeds 4.15 m and the equipment, building, or
object must be moved under overhead power lines or communication lines, the following
precautions shall be taken:
a) the person or persons responsible for moving the equipment, building, or object shall contact the
operators of the overhead lines before the move has started and request assistance;
b) the operators of the overhead lines shall comply with the request for assistance as soon as
possible; and
c) the operators of the overhead lines shall provide assistance in accordance with the requirements
of the Occupational Health and Safety Act and the Safety Codes Act.
2-020 Excavation Activities in the Vicinity of Underground Power Lines (See Appendix B.)
(1) Before an excavation is started, the person responsible for the excavation shall contact the operator
of the underground cables in the area to determine:
(a) if underground cables are present at the excavation site;
(b) if direct supervision is required during the excavation activity; and
(c) if specific safety measures are required to complete the excavation activity.
(2) Before an excavation is commenced, the operator of the underground cables shall identify and mark
any underground cables that could be interfered with when the excavation is undertaken at the
proposed excavation site.
(3) The person responsible for an excavation shall ensure that no excavations are undertaken within 1 m
of any underground utility cable unless:
(a) the excavation is done under the care and control of the operator of the underground cables; and
(b) the excavation method is acceptable.
The minimum clearance between the highest point of an amusement ride or area where high equipment may
be displayed and an overhead power line, measured horizontally between the nearest vertical planes formed
by the amusement ride or the displayed equipment and the overhead power line, shall be:
(a) the height of the amusement ride or displayed equipment, or 8 m, whichever is greater for
overhead power lines operated at voltages above 750 V phase to phase;
(b) as specified in Clause (a) for overhead power lines with bare conductors operated at voltages
below 750 V phase to phase; and
(c) 3 m for overhead power lines with insulated or polyethylene-covered conductors operated at
voltages below 750 V phase to phase.
(1) No person shall install lighting fixtures, lighting circuits, garlands, or any other apparatus used for
decorative purposes on electrical utility system poles or structures unless the operator of the utility
system approves the installation.
(2) The installation and removal of decorative lighting on electrical utility system poles and structures
shall be controlled by the operator of the utility system.
(3) Decorative lighting equipment installed on electrical utility system poles and structures must
be approved.
2-028 Plans
The operator of the utility system shall maintain, and produce when required by the authority having
jurisdiction, documents, including but not limited to drawings and specifications, covering new construction
of or alterations to an electrical utility system.
(1) If underground pipelines are installed in rural areas, the operator of the utility system shall ensure
that a separation of 8 m is maintained from:
(a) the poles and structures of an overhead power line operating at voltages above 750 V phase to
phase; or
(b) an electrical utility system pole with earth return system grounding and conductors operating
below 750 V phase to phase.
(2) If the separation described in Subrule (1) cannot be met, the separation may be reduced if:
(a) the operator of the utility system locates buried ground conductors; and
(b) the installation is acceptable.
(1) The operator of a utility system shall ensure that the equipment and lines are:
(a) not energized unless the equipment and lines meet the requirements of this Code; and
(b) inspected at regular intervals, as required; and
(c) maintained in accordance with this Code.
(2) The operator of an electrical utility system shall ensure that equipment or lines not in use are
maintained in accordance with this Code.
(3) The operator of a communication system shall ensure that equipment or lines not in use are
maintained in accordance with this Code.
All electrical utility and communication systems covered by this Code shall be grounded in order to:
(a) reduce the risk of exposure to harmful voltages and the danger of electrical shock;
(b) stabilize system voltages;
(c) facilitate the operation of protective devices to reduce the risk and duration of harmful
voltages; and
(d) protect communication circuits, control circuits, and other equipment.
Substation and generating station grounding shall follow the grounding principles and practices outlined in
the latest publication of IEEE 80 or CAN/CSA-C22.3 No. 61936-1, Section 10.
(1) The ground resistance of a generation station or substation grounding system shall be established so
that the ground potential rise resulting from the fault current flowing from the grounding system to
earth does not exceed 3 kV peak.
(2) If the requirements of Subrule (1) cannot be met, the grounding system must be designed,
engineered, and constructed in accordance with recognized industry standards.
(3) A generation station or substation shall have a measured ground resistance value for the
grounding system.
(1) Subject to Subrule (2), at generation stations and substations, generator and transformer neutrals of
star grounded systems shall be grounded with a ground conductor connected to the ground grid.
(2) Subrule (1) does not apply where an impedance grounded system is used.
(1) Neutral conductors entering generating stations or substations shall be grounded with a ground
conductor connected to the ground grid.
(2) Impedance grounding devices may be used for the grounding system required by Subrule (1).
(1) All current and non-current-carrying metallic equipment located within 3 m of a generation station or
substation, or located within a substation, shall be grounded or bonded in accordance with this Rule.
(2) All metallic structures contained within the station or substation shall be bonded to the grounding
grid at a minimum of one point.
(4) All current-carrying metallic equipment shall be grounded to the ground grid.
(1) Non-current-carrying metallic equipment that enters a generating station or substation shall be
grounded or isolated in accordance with this Rule.
(2) Lightning protection wires that terminate at generation stations or substations shall be grounded to
the ground grid.
(3) Railway tracks entering generating stations or substations shall be isolated at the station or substation
boundary to prevent the transfer of unsafe potentials to the tracks outside the station or substation.
(4) Guy wires shall be grounded or bonded in accordance with Section 10 of this Code.
(5) All other non-current-carrying metallic equipment entering a generating station or substation shall
be effectively isolated, or precautions shall be taken where necessary to control unsafe potential
transfers.
Communication and control circuits entering a generating station or substation shall be isolated where
necessary to prevent the transfer of unsafe potentials out of the station or substation.
6-116 Grounding of Generating Station and Substation Fences (See Appendix B.)
Fences enclosing substations and metallic fences located in proximity to generating stations where unsafe
touch potential or step potential may be transferred to the fence or area adjacent to the fence shall be
grounded in accordance with this rule. See Figures 7 and 8 for:
(2) A ground conductor not smaller than No. 4 AWG shall connect the ground electrodes required by
Subrule (1) to:
(a) the base of the fence post;
(b) two places on the chain link fabric; and
(c) each barbed wire strand.
(3) An extra flexible conductor not smaller than No. 2 AWG shall be used to ground hinged gates to the
gate post.
(4) A ground grid conductor or gradient control conductor connected to the gate post ground conductor
shall be placed across all gate openings.
(5) If fences are located less than 3.0 m horizontally from generating station equipment, substation
equipment, ground grid conductors, gradient control conductors, or where unsafe touch potential
or step potential may be transferred to the fence or the area adjacent to the fence:
(a) a gradient control conductor shall be installed around the fence at a horizontal distance of 500 to
1000 mm from the fence;
(b) a gradient control conductor connected to the conductor required by Clause (a), shall be
installed 500 to 1000 mm beyond the area where gates in the open position extend beyond the
gradient control conductor required by Clause (a); and
(c) two or more physically separated ground grid conductors shall be used to connect the gradient
control conductor enclosing the fence to the generating station or substation ground grid.
(6) The gradient control conductor required by Subrule (5) shall be connected to the ground conductors
required by Subrule (2).
(7) At generating stations or substations where the ground grid is extensive, the ground electrodes
required at the line posts may be omitted where:
(a) additional physically separated interconnecting ground grid conductors are installed to connect
the fence gradient control conductor to the ground grid; and
(b) no unsafe touch potential or step potential will be transferred to the fence or the area adjacent
to the fence.
(8) If buildings are used to enclose generating stations or substations or to form part of the enclosure:
(a) metallic structural parts shall be grounded to the ground grid; and
(b) if metallic surfaces are used on the outside of the building and unsafe touch potential or step
potential may be transferred to the metallic surface, or the area adjacent to the metallic surface,
a gradient control conductor connected to the ground grid shall be installed around the building
or part of the building at a horizontal distance of 500 to 1000 mm from the building.
(9) A surface material layer of suitable resistivity may be used to supplement the gradient control
protection required by Subrules (5) and (8) or to eliminate the requirement for gradient control
conductors.
(10) The composition of the surface material described in Subrule (9) shall not include
conducting material.
Electrical equipment referred to in Rule 6-100(2) at generating stations or located within substation buildings
that is required to operate the station or substation but is not a part of an electrical utility system shall be
grounded in accordance with the requirements of CSA Standard C22.1, Canadian Electrical Code, Part I.
Grounding conductor used for grounding current-carrying equipment or ground grid conductor shall be sized
such that overall energy does not cause:
(a) mechanical failure,
(b) annealing, or
(c) thermal damage.
Rules 6-200 to 6-210 apply to the grounding of buildings, pipelines, fences, and other objects in proximity to a
generating station or substation.
6-202 Buildings
If buildings are located in proximity to generating stations or substations or form part of a generating station
or substation enclosure, the buildings shall be grounded in accordance with Rule 6-116 (8) to (10).
6-204 Pipelines
(1) All pipelines in proximity to a generating station or substation shall be effectively isolated or
precautions shall be taken where necessary to control unsafe potential transfers.
(2) Specific considerations with pipelines are the transfer of potential to cathodic protection systems or
coating stress levels under fault conditions.
(1) Metallic fences located in proximity to generating station or substation fences where unsafe touch
potential or step potential may be transferred to the fence or area adjacent to the fence shall be
grounded in accordance with Rule 6-116.
(2) Metallic fences joining generating station or substation fences shall have insulating sections not
less than 3 m in length installed between the metallic fence and the generating station or
substation fence.
All other non-current-carrying metallic equipment in proximity to a generating station or substation shall be
effectively isolated, or precautions shall be taken where necessary to control unsafe touch potential or step
potential.
This Section applies to substations and electrical equipment installations used by an operator of the utility
system in the exercise of its function as a utility, in:
(a) the portion of generation facilities that are used to provide interconnection to a utility system up
to the demarcation point, as established between the generator and utility;
(b) substations that are enclosed with fencing or enclosed in a building;
(c) a mobile or temporary substation application; and
(d) substations that have some or all components individually enclosed with no overall
exterior fence.
8-004 General
All substations and electrical equipment shall be designed, engineered, and constructed in accordance with
recognized industry standards, and shall be installed to reduce the hazard as far as practicable.
8-006 Maintenance
(1) Substations and electrical equipment shall comply with this Code when placed in service and shall
thereafter be periodically maintained and inspected as required.
(2) Substations and electrical equipment shall be maintained in good working order.
New equipment shall be thoroughly inspected and tested before being put into service.
Infrequently used equipment or wiring maintained for future service shall be inspected and tested before use
in order to determine its fitness for service.
Equipment or wiring used for emergency electrical services shall be inspected and tested in accordance
with the manufacturer’s specifications, or with the specifications authenticated by a registered engineering
professional to determine its fitness for service.
In substation buildings, all rooms or spaces in which electrical supply equipment is installed shall comply with
the following requirements:
(a) they shall be non-combustible as far as practicable;
(b) they shall not be used for the storage of unnecessary materials;
(c) they shall be free from combustible dust, conductive dust, combustible flyings, flammable gas, or
acid fumes in dangerous quantities;
8-016 Floors, Passageways, Guardrails, Handrails, Permanent Ladders, and Toe Boards
Floors, passageways, guardrails, handrails, permanent ladders, and toe boards shall be installed and
maintained in accordance with the applicable Occupational Health and Safety standards.
(1) The supporting surfaces above live parts shall be without openings.
(2) Toe boards at least 150 mm high shall be provided at all edges, and the lower edge of the toe board
shall be flush with the platform.
8-020 Exits
(1) Each room or space and each working space around equipment shall have a suitable means of exit,
which shall be kept clear of all obstructions.
(2) Where the size of the room or space or the arrangement of cables and equipment is such that one
means of exit may become inaccessible, two or more exits shall be provided and located to best
serve the intended purpose.
(3) Where doors are used for emergency exits, panic hardware shall be provided to permit easy exit.
The horizontal dimensions of the working space in front of exposed live parts operating at a maximum
potential of 750 V phase to phase shall be not less than the following and as per Figure 5:
(a) for parts on one side of more than 150 V to ground, and no exposed live or grounded parts on
the other side of the working space, 0.9 m;
(b) for parts on one side of more than 150 V to ground, and exposed live or grounded parts of the
other, 1.2 m;
(c) for parts on one side of less than 150 V to ground, and no exposed live or grounded parts on the
other side, a minimum of 0.75 m; and
(d) for parts on one side of less than 150 V to ground, and exposed live or grounded parts on the
other side, 0.9 m.
(1) Fire extinguishers approved for use on electrical fires shall be provided near every substation building
exit door.
(2) Notwithstanding Subrule (1), a fire extinguisher approved for use on electrical fires shall be provided
at each interior exit where the nature of the work warrants it, or as required by Rule 8-020 (2).
(1) Adequate and readily accessible working space with secure footing shall be maintained about all
electrical parts or equipment which require adjustment or examination while in service.
(2) Where necessary, steps and handrails shall be installed on or about large electrical equipment to
allow ready access to controls or ancillaries.
(3) A minimum working space 0.9 m by 0.9 m by 2.2 m high shall be provided outside the guard zone.
(See Figure 3.)
(1) No current-carrying parts of more than 750 V phase to phase shall be exposed (unguarded) unless
those parts are effectively isolated by elevation.
(2) Subrule (1) does not apply where such parts are occasionally left exposed by the removal of
covers of entrances into enclosures such as switch and instrument transformer cells or
switchgear compartments.
(3) When exposing energized parts per Subrule (2) for any purpose (including buses and disconnections
in compartments), the working space shall be provided in accordance with the requirements of
Rule 8 030(3).
Separation or clearance about normally elevated or isolated parts requiring occasional adjustment shall be
provided so that persons need not come within the guard zone near adjacent energized parts unless they are
guarded in accordance with Rule 8-200.
Pulleys, belts, and other equipment used in the mechanical transmission of power shall be safeguarded in
accordance with the applicable Occupational Health and Safety standards.
Parts of equipment, such as handles, levers, and operating arms, which may move suddenly in such a way that
persons in the vicinity are liable to be injured by being struck, shall be guarded or isolated.
This rule applies to electrical equipment containing insulating liquids with a fire point of less than 300° C.
1) If liquid-filled electrical equipment is installed outdoors, the operator of the utility system shall
ensure that:
a) the electrical equipment is not placed on a pad or foundation at ground level unless all live parts
are enclosed, fenced or elevated so as to be inaccessible to unauthorized persons;
b) the electrical equipment is arranged or protected to minimize fire hazards in proportion to the
amount of liquid contained by one or more of the following methods as applicable:
i) space separations;
ii) fire resistant barriers;
iii) automatic extinguishing systems;
iv) crushed-rock absorption beds;
v) enclosures which confine the liquid of a ruptured tank; or
vi) sloping grade away from buildings; and
c) if the electrical equipment is located adjacent to a building, it shall be installed in accordance
with the requirements of CSA Standard C22.1, Canadian Electrical Code, Part I.
2) If the liquid-filled electrical equipment is installed indoors, the operator of the utility system shall
ensure that the installation:
a) meets the requirements of CSA Standard C22.1, Canadian Electrical Code, Part I; and
b) is equipped with fireproof doors where the doorways provide an opening from the outside of the
building to the enclosure containing the equipment.
This rule applies to electrical equipment containing insulating liquids that are non-propagating and have a fire
point of 300° C or greater.
(1) If the liquid-filled electrical equipment is installed outdoors, the operator of the utility system shall
ensure that:
(a) the electrical equipment is spaced a minimum of 6 m from any building ventilation, window, or
door; and
(b) if a barrier is in place to prevent spray of liquid to areas listed in Clause (a), then the spacing
requirement of Clause (a) does not apply.
(2) If the liquid-filled electrical equipment is installed indoors, the operator of the utility system shall
ensure that:
(a) the installation meets the requirements of CSA Standard C22.1, Canadian Electrical Code,
Part I; and
(b) each pressure relieving device is separately vented to the outside of the building if the liquid is
capable of producing explosive or toxic gases.
The operator of the utility system shall ensure that liquid-filled electrical equipment containing harmful
material capable of causing adverse environmental or health effects:
(a) is provided with the means to prevent or mitigate the propagation of the liquid; and
(b) bears appropriate warning signs concerning any health or environmental hazards associated
with the liquid; and provides reference to information indicating the proper methods of using,
handling, and disposing of the liquid.
(1) Guards shall be provided near all live parts that operate above 150 V phase to ground without an
adequate insulating covering, unless their location gives sufficient horizontal or vertical separations
or clearances, or a combination thereof, in order to eliminate the possibility of accidental human
contact.
(2) Separations or clearances from any live part to permanent supporting surface for persons shall equal
or exceed those shown in Figure 3 and Table 3.
(3) The application of the distances in Table 3 and use in Figure 3 are absolute values from the reference
surface plane.
Guards shall be sufficiently strong and shall be supported securely enough to prevent them from being
displaced or deflected by a person slipping and falling against them.
(1) Parts having clearances equal to or greater than those specified in Table 3, Columns 3 and 4 shall be
considered guarded by location.
(2) Parts shall be considered guarded by isolation where all entrances to enclosed spaces, runways, and
ladders are kept locked, and warning signs are posted at all entrances, in which case no other
permanent guards need be supplied.
(3) Effectively grounded metal cable sheaths are suitable guards. Metal conduit or other suitable
protection shall be provided where cables are exposed to mechanical damage.
(4) Guards less than 0.1 m outside of the guard zone shall completely enclose the parts from contact up
to the heights listed in Column 3 of Table 3.
(5) Guards shall not be closer to the live parts than the limits listed in Column 5 of Table 3, unless
suitable insulating material is used with circuits of less than 2.5 kV to ground.
(6) Where they are more than 0.1 m outside the guard zone, the guards shall be a minimum of 2.5 m
above the floor for indoor applications.
(7) Covers or guards that may be removed while the parts they guard are energized shall be arranged so
that they cannot readily be brought into contact with energized parts.
(8) If the vertical separation or clearance in Column 3 of Table 3 cannot be obtained, guardrails may
be used.
(10) Where guardrails are used, they shall be located at a horizontal separation or clearance of at least
1 m (and preferably not more than 1.2 m) from the nearest point of the guard zone which is less
than 2.5 m above ground, and shall be fitted with a suitable warning sign. (See Figure 4.)
(12) The insulation covering energized conductors or parts exceeding 750 V phase to phase, on its own,
shall not be considered to be a guard.
(13) For parts less than 750 V phase to phase, positive barriers, enclosures, or similar arrangements shall
be used, but in dry places which are not exposed to mechanical damage, other insulation suitable for
the voltage involved may be used as a guard.
(14) Notwithstanding this Rule, on circuits where other guarding is impracticable, such as at the back of
switchboards or in equivalent sheltered locations, insulating mats or platforms with an insulating
value suitable for the voltage involved may be used so that a person is isolated from other live parts
or ground.
(1) Electrical equipment and circuits shall be identified for safety purposes, and the method of
identification shall be uniform throughout the electrical utility system.
(2) Identification marks shall not be placed on removable covers or casings where the interchanging of
these removable parts would result in incorrect identification.
(3) All signage shall be clearly visible, securely fastened, and maintained in legible condition.
CSA Standard C22.1, Canadian Electrical Code, Part I, applies to the installation of storage batteries.
Provision shall be made for shorting the secondary circuits of current transformers and the current
transformer secondary winding, except where functional requirements do not permit the shorting of such
circuits.
The secondary circuits of instrument transformers shall be effectively grounded, except where functional
requirements do not permit the grounding of such circuits.
(1) Suitable precautions shall be taken to protect station equipment from lightning which might enter
from associated overhead lines.
(2) Where surge arresters are installed in a building, they shall be located well away from passageways,
combustible parts of the building, and all equipment other than the equipment they protect unless
they are of the non-fragmenting type.
(3) The conductor between an arrester and any monitoring device shall be treated as an indeterminate
potential and guarded as such.
Dry type transformers installed in a building shall be installed in accordance with the requirements of CSA
Standard C22.1, Canadian Electrical Code, Part I.
All substation fences, switching enclosures, padmount transformers and similar equipment shall display
suitable high voltage warning signs at all gates and doors; all enclosures over 2.5 m in any dimension shall
have additional signs displayed on all sides at least once every 12 m.
8-220 Locking
All enclosures shall be made secure from entry by unauthorized persons by locking or other
acceptable means.
Adequate illumination shall be provided to enable proper operation and maintenance of electrical equipment.
(1) Provision for dissipation of stored charge of disconnected capacitors shall be present.
(2) Stored energy warning signs shall be installed on the capacitor enclosure entrance or the capacitor-
elevated support structure.
(1) All switchgear components shall be secured and levelled in a manner consistent with service
conditions and manufacturer’s instructions.
(2) Switchgear surfaces shall not be used as physical support for any item unless specifically designed for
that purpose.
(3) Switchgear interior areas shall not be used as storage areas unless specifically designed for
that purpose.
ALBERTA ELECTRICAL UTILITY CODE - Sixth Edition, 2022 25
SECTION 8 - SUBSTATIONS AND ELECTRICAL EQUIPMENT INSTALLATIONS
(4) When installed, switchgear arc flash discharge plenums for gaseous and molten decomposition
products shall be installed to exit the building away from doors, stairwells, and outdoor equipment,
and a controlled no-entry discharge zone shall be established outside the building.
(5) Notwithstanding Subrule (4), if other safety devices are used to reduce the internal switchgear
pressure resulting from a fault, they must be arranged and installed with consideration for their
potential hazards to personnel. The accumulation of dangerous concentrations of gas decomposition
products in switching room areas shall be prevented.
8-240 Grounding
All non-current-carrying metal parts of electrical equipment shall be grounded or bonded in accordance with
Section 6 of this Code.
(1) For the purpose of ensuring safety to operating and construction personnel walking under or
adjacent to energized circuits, minimum separations or clearances between live parts and finished
grade, as outlined in Table 3, shall be observed.
(2) The separations or clearances referred to in Subrule (1) may be used as a guide for substation
design, but in no case shall the unguarded live parts be located at separations or clearances less than
the minimums outlined in Table 3.
(3) In areas where vehicles may travel in substation yards, separation or clearance in accordance with
Column 5 of Table 3, plus 4.2 m vehicle height shall be provided.
Fences
8-300 General Requirements of Substation Fences (Appendix B)
(1) Electrical utility system equipment with exposed energized parts that are not individually enclosed,
located in a building or on an elevated platform in accordance with the requirements of Section 10 of
this Code shall be enclosed within a fence constructed in accordance with this rule.
(2) The horizontal separation between the exterior fence and exposed energized parts shall not be less
than 2.5 m for voltages up to and including 200 kV (phase to phase), and no less than 4 m for voltages
greater than 200 kV (phase to phase) for the area, as defined in Figure 6.
(3) The fence, excluding barbed wire, shall be not less than 1.8 m high.
(4) Subject to Subrule (5), fence posts shall be set at a depth of not less than 1.0 m.
(5) Subrule (4) does not apply where lesser setting depths are required due to ground conditions,
or portable fencing is used, and methods designed, engineered, and constructed in accordance with
recognized industry standards are used to brace and anchor the fence.
(6) If soil conditions are unstable, fences shall be braced or foundations designed to provide the same
stability provided in stable soil conditions.
(8) If a building that is not owned by the operator of the utility system is located within 2.0 m of the
fence or forms parts of the fence, a guard system shall be designed, engineered, and constructed
in accordance with recognized industry standards. The guard shall be placed on the building where
there is danger that persons accessing the building roof may fall into the fenced enclosure or
inadvertently place conductive objects into the fenced enclosure.
(1) Metal posts shall be of 80 mm nominal pipe size (11.3 kg/m) for corner, terminal, and gate posts and
50 mm nominal size (5.4 kg/m) for line posts. For gate openings greater than 6 m the metal gate
posts shall be 100 mm nominal pipe size (16.1 kg/m).
(2) Chain link fabric shall be made with minimum 3.6 mm nominal wire size and have a mesh not greater
than 50 mm.
(3) Chain link fabric shall be securely attached to all posts, gate frames, and rails.
(4) Chain link fabric shall be reinforced as necessary at top and bottom to prevent distortion and shall
extend to within 50 mm of the ground.
(5) Top rails shall be of 32 mm nominal pipe size (3.35 kg/m) and shall be provided with suitable
expansion joints, where necessary.
(6) Three or more separate strands of barbed wire supported by the posts or brackets on the posts
shall be placed at the top of the fence and gates, extending vertically or obliquely out from the
fenced enclosure.
(1) Other materials, combination of material, or style of fencing may be used for electrical utility system
fencing enclosing electrical equipment if:
(a) the material(s) and construction method(s) are designed, engineered, and constructed in
accordance with recognized industry standards;
(b) The fence has features that guard against and discourage unauthorized entry access;
(c) Non-flame-propagating materials are used; and
(d) Any exposed metallic components are bonded in accordance with Section 6 of this Code.
(2) Subrule (1)(c) does not apply to the section of isolation fence required by Rule 6-206(2).
(1) Gates should open outwardly but, where it is necessary that they open inwardly:
(a) they shall not come within 1.5 m of the frame or enclosure of any electrical equipment; and
(b) shall have a separate outward opening personnel gate installed.
(2) Gates shall be adequately braced as necessary and double gates should be used where the width of
the opening exceeds 1.5 m.
(5) Notwithstanding Subrules (1), (2), and (3), cantilever sliding gates are acceptable provided that:
(a) a manual opening method is provided;
(b) the slide mechanism is on the interior of the substation fence; and
(c) supporting posts shall meet or exceed requirements of 8-300 and 8-302.
(1) Steel or iron parts shall be either hot dipped galvanized or electroplated with non-ferrous metal.
(2) Aluminium parts shall be suitably treated against corrosion where they will come in contact with the
earth or with concrete.
(3) Wooden isolation fence parts shall be made from preserved wood to prevent wood rot. Current
utility wood preservation practices shall be followed.
(1) Substation yards shall be drained to afford secure footing for vehicular/personnel access and inhibit
the growth of weeds.
(2) Substations enclosures shall not be used for storage of unnecessary materials.
The grounding of substation fences shall meet the requirements of Section 6 of this Code.
(1) Suitable circuit breakers, disconnects, or switches shall be inserted in the leads to all supply
equipment and all outgoing supply circuits in accordance with this Rule.
(2) Any load breaking or interrupting device which has no visual means to determine if contacts are open
shall be preceded by a visual disconnecting means or proven positive means of determining that the
circuit or system is de-energized.
(3) Where two or more pieces of electrical supply equipment or supply lines are operated as a single
unit, no switch is necessarily required between them.
(4) Where a local emergency or stand-by system could operate in conjunction with the operator of the
utility system, suitable approved equipment shall be installed to prevent the possibility of feedback
from one system to the other.
(1) Each conductor (except neutral conductors, grounded conductors, bonding & grounding conductors,
and conductors of circuits, the opening of which may cause a special hazard by the interruption of
service or removal of protection) shall be protected against excessive current by a suitable fuse or
other automatic circuit breaking device or by the design of the system.
(2) All outgoing circuits shall be protected by suitable current limiting or interrupting equipment, or by
the design of the system except for:
(a) a motor driven generator or rotary converter not operated in parallel with other machines or
batteries if the supply leads to such apparatus are already protected by fuses or automatic
circuit breakers;
(b) grounded conductors;
(c) circuits for field excitation;
(d) leads of alternating-current generators;
(e) leads connecting two or more pieces of electrical supply equipment operated as a single
unit; and
(f) leads of series transformers;
(g) secondary leads of current transformers or other similar circuits when the opening of such
circuits may cause hazard to life or property through interruption of service; or
(h) conductors run between the secondary of a transformer and the nearest downstream
distribution centre provided the conductors are suitably protected by protection on the primary
side of the transformer.
(1) All switches, fuses, automatic circuit breakers, and other control devices shall be:
(a) readily and safely accessible to authorized persons;
(b) arranged or marked to identify the equipment controlled by them; and
(c) except for fuses, shall indicate whether they are open or closed.
(2) All switches which are accessible to unauthorized persons shall have provision for locking them in
both the open and closed positions.
(3) Cutouts, fuses, disconnects, or switches which are pole mounted shall be located so that they are
readily accessible from climbing and working spaces.
(4) Such devices or their connecting leads shall not extend into the climbing space but may extend
wholly, or in part, into the working space of poles.
(5) Adequate switching spaces or aisles shall be provided to allow safe hookstick operation of all
substation overhead switches.
(1) Switches shall be installed and maintained so as to prevent the danger of accidental operation.
(2) For switching devices that can be operated remotely and automatically, the control circuit shall be
provided with a positive disconnecting means near the switching device.
8-408 Suitability
(1) All switches shall have adequate voltage, current-carrying, current-interrupting, and short-circuit
rating for their application.
(2) An acceptable insulated live line tool designed and manufactured to industry-recognized standards
shall be provided for the operation of all disconnects and fuses where required.
(1) The handles or control mechanism for all switches throughout any system shall have, insofar as
practical, the same position when open and a uniformly different position when closed in order to
minimize operating errors.
(2) Where it is necessary to depart from the practice prescribed in Subrule (1), the switches shall be
marked to minimize the possibility of mistakes in operation.
Electrical equipment which requires maintenance work upon it shall have an industry recognized means of
disconnecting it from all ungrounded conductors of its supply circuit.
All enclosures or parts of enclosures such as doors, covers, and tanks shall be firmly secured in place.
(1) Switches used to disconnect transformers, cables, and lines having magnetic or capacitive de-
energization currents shall be spaced to comply with the minimum requirements (live part to live
part and live part to grounded structure) prescribed in Table 4.
(2) Minimum electrical clearances for switches shall take into consideration all potential positions of the
live parts before, during, and after switch operation.
(1) Fuses shall be capable of being disconnected from the source of supply before being removed
or replaced.
(2) Notwithstanding Subrule (1), where fuses cannot be disconnected from the source of supply before
handling, acceptable insulating tools or handles designed and manufactured to industry-recognized
standards shall be used.
All vented fuses for the expulsion of gases, arc plasma, and molten metal shall have:
(1) Clearances for vented material from any operating equipment, adjacent fuse, or controls; or
(2) A protective barrier to prevent or divert the vented material away from any operating equipment,
adjacent fuse, or controls.
CSA Standard C22.3 No.1:20, Overhead Systems, shall be the standard for the construction and maintenance
of overhead electrical utility and communication systems, with amendments to that standard as follows:
(2) Subclause (1) does not apply if the risk of locating the overhead power line in the area
described in Subclause (1) can be reduced to an acceptable level and the inspection authority
having jurisdiction approves the installation.
(6) Remove Table 4 (Clause [Link]) and refer to Column VIII of Table 5 attached.
(Minimum Design Clearances from Wires and Conductors not Attached to Buildings, Signs, and
Similar Plant)
An overhead power line adjacent to a hazardous area as described above shall maintain a horizontal
clearance from the hazardous area equal to the height of the supporting structure unless:
(a) The supporting structure is of H-Frame or Grade 1 construction; or
(b) The supporting structure is guyed away from the hazardous area.
Where a power line adjacent to a hazardous area described above is deflected towards the hazardous
area, additional precautions shall be taken to prevent conductors from entering the hazardous area
due to failure of a conductor fastening.
Devices that can emit sparks or glowing embers, such as fuses and arrestors, where practicable, shall
not be located on poles adjacent to the hazardous locations identified above.
(1) Buildings: If buildings are located in proximity to supply lines and unsafe or objectionable potentials
exist or may exist on or adjacent to the metallic parts of the building as a result of the supply lines,
the metallic parts shall be grounded at 2 or more physically separated locations with a minimum size
No. 6 AWG ground conductor connected to a ground electrode.
(2) Pipelines: If pipelines are located in proximity to supply lines, the pipelines shall be grounded
or controlled in accordance with CSA Standard C22.3 No. 6-13, Principles and Practices of Electrical
Coordination Between Pipelines and Electric Supply Lines. (See Appendix B.)
(3) Metallic Fences Subjected to Objectionable Potentials: Where unsafe or objectionable potentials
may be present on metallic fences located in parallel with supply lines, the metallic fences shall be
grounded at appropriate intervals with a minimum size No. 6 AWG ground conductor connected to a
ground electrode.
(4) Close Metallic Objects: Where unsafe or objectionable potentials may be present on other metallic
objects located in proximity to supply lines, the metallic objects shall be grounded with a minimum
size No. 6 AWG ground conductor connected to a ground electrode.
1.1 Scope
This Standard applies to the lines and equipment associated with underground electric supply and
communication systems located entirely outside buildings and fenced supply stations.
This Standard, which forms part of the Canadian Electrical Code, Part III, covers the requirements for
construction of underground systems and includes electric supply and communication circuits that
are installed alone, in joint use, or in proximity to each other or other facilities.
Corrosion control shall be considered in the design of underground installations. Methods for
corrosion control include material selection, coatings, and cathodic protection (see CSA C22.3 No.
4). Corrosion control methods may be adjusted based on facility testing and maintainance and by
engineering judgement.
Where different systems serve the same consumer, the grounds of the different systems shall be
bonded. A single grounding conductor may be used for both supply and communication grounding,
provided that the ground connection is of sufficiently low impedance and of sufficient current-
carrying capacity to prevent the buildup of voltages that can result in a hazard to persons or
equipment.
The neutral shall be of sufficient size and ampacity for the intended use, and shall be connected to a
ground electrode at each piece of active electrical equipment and a sufficient number of additional
ground electrodes (not including grounds at consumer’s services) to prevent electric shock hazard to
persons caused by the buildup of excessive steady-state neutral-to-earth voltage.
[Link]
When designing the grounding of an earth return system, the following factors shall be considered:
(a) soil resistivity,
(b) touch potential and step potential under steady-state and fault conditions,
(c) magnitude of fault currents, and
(d) frequency and number of ground electrodes installed.
[Link]
Where earth return systems are used the following criteria shall be met:
(a) the resistance-to-ground of any individual electrode shall not exceed 25 Ω and the resistance of
the grounding installation without interconnection to the consumer’s service grounding system
shall not exceed 6 Ω. Where these readings cannot be achieved, an additional two electrodes
connected in parallel or two deep-driven electrodes shall be used. If the required readings
cannot be achieved with the two additional electrodes, the grounding system shall be extended
into a multi-grounded system until the 6 Ω interconnected reading can be obtained;
(b) measures shall be taken to prevent electric shock hazard to persons caused by the buildup of
steady-state neutral-to-earth voltage;
(c) the grounding installation shall consist of a redundant grounding system with ground electrodes
separated by a distance greater than their depth that are located on different sides of the pole or
on separate poles;
(d) the transformer primary neutral terminal, transformer case, lightning arrester, grounded
conductor, and secondary neutral terminal shall:
(i) be connected to the ground electrode using the appropriate ground conductor; or
(ii) have a suitable warning placed on the pole where primary and secondary neutrals are
not connected.
Grounding systems shall be periodically tested for resistance, and periodically inspected and
maintained, to ensure that the grounding systems comply with the requirements of this Code.
If unsafe or objectionable ground current flows or may flow on other equipment, steps shall be taken
to mitigate such current to safe or unobjectionable levels.
(1) Power cable sheaths and metallic raceways shall be grounded at both ends unless circulating
current flow on the cable sheath or raceway causes problems or cannot be tolerated, in which
case the cable sheath or raceway shall be grounded at one end only.
(2) Subject to Subrule (5), the electrical conductivity of metallic raceways and cable trays shall be
continuous throughout their length.
(3) Subject to Subrule (5), the current-carrying capacity of conductors or connections used to make
metallic raceways or cable trays electrically continuous shall be:
(a) capable of carrying the electrical utility system fault current; or
(b) equal to or greater than the current-carrying capacity of the metallic raceway or cable tray.
(4) Subject to Subrule (5), metallic cable trays shall be grounded at intervals not exceeding 15 m.
(5) Subrules (2) to (4) do not apply where isolated grounding systems designed, engineered, and
constructed in accordance with recognized industry standards are used.
FIGURES
Figure 5 ~ Dimensions of Working Space near Live Parts on Panelboards and Control Panels Indoors
(See Rule 8-022.)
TABLES
Table 1 ~ Safe Limits of Approach Distances from Overhead Power Lines for Persons and Equipment
(See Rule 2-014.)
Operating voltage of overhead power line between line Safe limit of approach distance for persons and equipment
conductors unless otherwise specified
0 - 750 V insulated or polyethylene
covered conductors¹ 0.3 m
0 - 750 V bare, uninsulated 1.0 m
Above 750 V insulated conductors¹,² 1.0 m
0.75 kV - 40 kV 3.0 m
69 kV, 72 kV 3.5 m
138 kV, 144 kV 4.0 m
230 kV, 260 kV 5.0 m
500 kV 7.0 m
500 kV DC Pole-Ground 7.0 m
¹ Conductors must be insulated or covered throughout their entire length to comply with these groups.
² Conductors must be manufactured to rated and tested insulation levels.
Table 2, Stranded Copper Conductor Sizes Required to Conduct Electrical Utility System Fault Current, has been
deleted. Table numbers for Tables 3 through 9 have not been adjusted so as to maintain table numbering
consistency with previous AEUC revisions.
Line to ground Equivalent phase Minimum vertical Minimum horizontal Minimum separation
voltage (maximum) to phase voltage separation or separation or or clearance to
(kVrms) (kVrms) clearance to clearance to guard live parts
unguarded parts unguarded parts (guard zone)
(m) (m) (m)
¹ The separations or clearances in Column (5) of this table are solely for guidance in installing guards without definite
engineering design, and are not to be considered as a requirement for such engineering design; i.e., the minimum separations or
clearances in the above table are not intended to refer to the separations or clearances between live parts and the walls of cells,
compartments, or enclosing structures. They do not apply to the separations between bus bars and supporting structures, or to
the clearances between the blade of a disconnecting switch and its base.
² Minimum separations or clearances shall satisfy either switching surge or B.I.L. duty requirements, whichever is greater.
Switching surge factor is an expression of the maximum Switching Surge Crest Voltage in terms of the maximum Line to Neutral
Crest Voltage of the power system. Basic Insulation Level B.I.L. - represents the insulation level of the System.
³ Parts over or near passageways through which material may be carried, or in or near spaces such as corridors, storerooms,
and boiler rooms used for non-electrical work, shall be guarded or given separations or clearances in excess of those specified,
such as may be necessary to secure reasonable safety. The guards shall be substantial and, where practical, completely shield or
enclose, without openings, the live parts. When in spaces used for non-electrical work, covers shall be removable only by means
of tools or keys.
⁴ Parts of indeterminate potential, such as telephone wires exposed to induction from high voltage lines, ungrounded neutral
connections, ungrounded frames, ungrounded parts of lightning arresters, ungrounded instrument cases connected directly to
the high voltage circuit, ungrounded parts of power cable terminations and cable shields, and other substation components
subject to voltage build-up if not grounded shall, where practical, be guarded on the basis of the maximum voltage which may
be present.
⁶ Clearances shown for 500 kV HVDC are based on a TOV factor of 1.5.
¹ Includes Alternating Current and Direct Current Voltages commonly found in Alberta.
² Where a line runs parallel to land accessible to vehicles but is over land not requiring clearance for vehicles, the wire can
swing out over the area accessible to vehicles or, at voltages over 200 kV AC, vehicles can be subjected to a hazard from
induced voltages. These vertical clearances apply where the conductor (in the swing condition, where specified) is over, or
within the following horizontal distances from the edge of, land accessible to vehicles:
(a) 0.0 m for communication circuits and 0 to 50 kV phase to phase AC supply circuits;
(b) 0.9 m for 50 to 90 kV phase to phase AC supply circuits;
(c) 1.7 m for 120 to 150 kV phase to phase AC supply circuits; (Table continues on next page)
(d) 6.1 m for 250 to 350 kV phase to phase AC supply circuits;
³ Generally restricted to Urban areas.
⁴ Provincial and municipal authorities may designate certain roads and highways as high load corridors and set specific
ground clearances for these routes.
⁵ This category includes farm fields and access roads to farm fields, as well as entrances to farm yards.
⁶ This clearance can be reduced to 3.5 m in the last span connecting the overhead supply to the consumer’s service point of
attachment.
Over 5 Not enclosed in effectively grounded metallic sheath 3.0 ⁵ 1.5 ³ 3.0 ³
to 22 kV Enclosed in effectively grounded metallic sheath 0.0 0.0 0.0
3.0 plus 3.6 plus 3.6 plus
Over 22 kV 0.01 m/kV 0.01 m/kV 0.01 m/kV
over 22 kV over 22 kV ³,⁴ over 22 kV ³,⁴
¹ The tabulated clearances are applicable to nonmetallic buildings or buildings whose metallic parts are effectively grounded.
Otherwise, a study to determine suitable greater clearances may be necessary, because of electrostatic induction.
² For inaccessible surfaces, this may be reduced to 0.08 m. At the service attachment point, this may be further reduced to 0.02 m.
³ Carrying conductors of these voltage classes over buildings should be avoided if other suitable construction can be carried out.
⁴ Where it is deemed necessary to carry conductors of these voltage classes over buildings, investigations should be made to
determine if additional measures, including increased clearances, are required to ensure that safe and suitable use can be made of
the building crossed over.
⁵ This value may be reduced to 1.5 m when windows that can be opened, fire escapes, and balconies are not present on the
building adjacent to the conductor.
Table 7 ~ Minimum Design Clearances from Wires and Conductors Not Attached to Buildings, Signs, and
Similar Plant
(See Rule 10-002 ⁸ and CSA C22-3 No. 1-10 Clauses [Link], [Link].)
Minimum clearances (meters) from wire to:
Signs, billboards, lamp and traffic
Wire or Conductor Buildings ¹, ² sign standards, above-ground
pipelines, and similar plant
Horizontal Vertical to Horizontal Vertical to
to surface ³ surface to object ³ object
Guys, communication cables, and drop wires 0.0 0.08 0.0 0.08
Supply conductors
Insulated or grounded 1.0 2.5 ⁴ 0.3 0.5
0 to Enclosed in effectively grounded metallic sheath 0.0 0.0 0.0 0.08
750 V
Neither insulated nor grounded, nor enclosed in effectively 1.0 2.5 ⁴ 1.0 0.5
grounded metallic sheath
Over Not enclosed in effectively grounded metallic sheath 3.0 ⁷ 3.0 ⁵ 3.0 3.0
0.75 to
22 kV Enclosed in effectively grounded metallic sheath 0.0 0.0 0.0 0.08
3.0 plus 3.6 plus 3.0plus 3.6 plus
Over 22 kV ⁵,⁶ 0.01 m/kV 0.01 m/kV 0.01 m/kV 0.01 m/kV
over 22 kV over 22 kV over 22 kV over 22 kV
¹ Clearances over or adjacent to portions of a building normally traversed by pedestrians or vehicles are covered by
Tables 5 and 6.
² The tabulated clearances are applicable to nonmetallic buildings or buildings whose metallic parts are effectively grounded.
Otherwise, a study to determine suitable greater clearances may be necessary, due to electrostatic induction.
(See Clause [Link].)
³ To these values the conductor swing must be added, in accordance with Clause [Link].
⁴ This clearance may be reduced to 1 m for portions of the building considered normally inaccessible.
⁵ Carrying conductors of these voltage classes over buildings should be avoided if other suitable construction can be carried out.
⁶ Where it appears necessary to carry conductors of these voltage classes over buildings, additional measures should be
investigated, including increased clearances, to ensure that safe and suitable use can be made of the building crossed over.
⁷ This value may be reduced to 1.5 m when windows that can be opened, fire escapes, and balconies are not present on the
building adjacent to the conductor.
⁸ Voltages are rms line-to-ground unless otherwise noted.
⁹ See Table 1 for safety work clearances.
¹ The grade of construction may be Grade 2 where one of the following conditions exists:
(a) the supply and communication lines have coordinated electrical protection (see Clause 4.4.);
(b) where coordinated electrical protection is not practical, the supply conductors have a rated tensile strength of
12.4 kN or greater; or
(c) the supply conductors are enclosed in effectively grounded continuous metallic sheathed cable.
² The communication line may be Grade 3 where the supply conductors are in effectively grounded continuous metallic
sheathed cable.
³ Grade 3 construction may be used where the supply conductors at the upper level are in effectively grounded continuous
metallic sheathed cable.
The Province of Alberta Hydro and Electric Energy Act (2000 ed., current as of December 5, 2019) (HEEA)
defines an electric distribution system as follows:
“electric distribution system” means any system, works, plant, equipment or service for the delivery,
distribution or furnishing of electric energy directly to the consumers, but does not include a power plant or
transmission line;
The HEEA definitions for “power plant” and “transmission line” are provided below.
Electric Utility
The Province of Alberta Electric Utilities Act (2003 ed., current as of May 12,2020) defines electric utility as
follows:
“electric utility” means an isolated generating unit, a transmission facility, or an electric distribution system
that is used
(i) directly or indirectly for the public, or
(ii) to supply electricity to members of an association whose principal object is to supply electricity to
its members,
the owner of which
i. is required by this Act or the regulations to apply to the Commission for approval of a tariff,
ii. is permitted by this Act or the regulations to apply to the Commission for approval of a tariff, and has
applied for that approval, or
iii. passes a bylaw that has been approved by the Lieutenant Governor in Council under section 138,
but does not include an arrangement of conductors intended to distribute electricity solely on
property of which a person is the owner or a tenant, for use solely by that person and solely on that
property of a facility exempted by Commission rules made under section 117.
Isolated
Such separation may not eliminate all of the effects of electromagnetic induction.
Power Plant
The Province of Alberta Hydro and Electric Energy Act (2000 ed., current as of December 5, 2019) defines a
power plant as follows:
“power plant” means the facilities for the generation and gathering of electric energy from any source.
Substation
The Province of Alberta Hydro and Electric Energy Act (2000 ed., current as of December 5, 2019) defines a
substation as follows:
“substation” means a part of a transmission line that is not a transmission circuit and includes equipment for
transforming, compensating, switching, rectifying or inverting of electric energy flowing to, over or from the
transmission line.
Transmission Line
The Province of Alberta Hydro and Electric Energy Act (2000 ed., current as of December 5, 2019) defines a
transmission line as follows:
“transmission line” means a system or arrangement of lines of wire or other conductors and transformation
equipment, wholly in Alberta, whereby electric energy, however produced, is transmitted in bulk, and includes
(i) transmission circuits composed of the conductors that form the minimum set required to so transmit
electric energy,
(ii) insulating and supporting structures,
(iii) substations,
(iv) operational and control devices, and
(v) all property of any kind used for the purpose of, or in connection with, or incidental to, the operation
of the transmission line,
but does not include a power plant or an electric distribution system.
Note that HEEA considers a substation to be within the definition of a transmission line.
Scope
The rules of this code are not considered to be retroactive, and therefore existing installations are not
generally required to be upgraded to meet the new or revised requirements of this Code unless an unsafe
condition exists or the existing installation is being renovated or altered. This item should be coordinated with
the authority having jurisdiction prior to design/construction.
Unobstructed working space around, near, and in front of utility equipment, such as padmount transformers
and pedestals, must be maintained to the requirements of the operator of the utility system.
The operator of the utility system’s determination of the requirement for direct supervision will be based on
several factors, including the reliability of the excavator and the type of installation involved.
6-000 Scope
Grounding of overhead and underground electrical utility and communication systems are covered under
Sections 10 and 12 of this Code.
6-002 Object
Objectives of Grounding
(a) Adequate grounding is required to prevent dangerous conditions which may arise at
electrical installations. Structures and equipment may become energized from a power
circuit by failure of insulation, operation of protective devices, breakage or displacement of a
conductor, arcing from the power circuit, or induction.
(b) There is always some resistance between a complete grounding connection and the earth,
and fault currents passing through this resistance may cause a potential difference between
grounded apparatus and the earth and may create a hazard. For example, with a ground rod
in soil of uniform resistivity, the greatest potential gradient exists in the region immediately
adjacent to the rod. Measurements show that 90 % of the total potential difference may
exist within 6 to 10 feet from the rod that is approximately within the reach or stride
of a person, so that a potential difference exists between their feet when placed apart.
Moreover, any metallic connection to the rod may transfer the potential at the rod to points
remote from the rod itself.
(c) Potential difference may be created in ungrounded systems without large fault currents.
For example, accidental contact of non-current-carrying equipment by a phase conductor
could impose a potential on the equipment with, perhaps, negligible fault current. It is
therefore imperative to provide a low resistance path between the grounding connection
and earth in order to control potential differences.
For public safety it is required that facilities and equipment accessible to the public be free from
hazardous potentials. This applies particularly to metallic fences surrounding supply stations
and to metallic facilities such as communication circuits, railway tracks, and pipelines entering a
supply station.
(a) For the safety of personnel, a grounding system must ensure that accessible non-current-
carrying metal parts are maintained at the same potential, and that the difference between
this potential and that of the surrounding earth is not dangerous.
(a) Obviously it is impossible to prevent at all times, in all places, and under all conditions,
the presence of dangerous voltages. However, in most cases the hazard can be reduced to
an extremely low value by careful, intelligent design. Hazardous potential differences usually
occur only when fault current flows. These potential differences can occur within electrical
supply stations as well as at other locations.
An adequate grounding system is essential to protect equipment by discharging into the earth
the energy released by lightning discharges, fault currents, and other system disturbances.
Otherwise these disturbances may cause extensive damage to equipment and apparatus,
including non-associated equipment such as communication cables, etc. Such damage might
include insulation breakdown, electrically ignited explosions, and fires, all of which may present
hazards to personnel.
An adequate grounding system is essential also for the proper operation of the supply system.
The grounding system must, at times, carry heavy power and fault currents without being
damaged and without causing dangerous potential gradients on the surface of the earth. The
severity of ground potential rise, in terms of duration and magnitude, is dependent on many
things, such as operation of protective devices, system conditions, and effectiveness of overhead
ground cables, etc. These in turn are dependent on the effectiveness of the grounding system.
(1) & (2)The specification of ground potential rise (GPR) value does not imply that substation or
generating station safety is achieved. The purpose for the GPR limit specified is to provide a point
where consideration of the external assets such as telecommunication personnel and assets may
become a concern. Refer to IEEE 487 for further discussion on the purpose of having a 3kVpeak
limit. In all cases, consideration of the influence of transferring voltages to external assets should
be evaluated.
(3) Measurement of the ground resistance of the grounding systems provides a base point of historical
reference to evaluate the performance of the grounding system after construction. Seasonal
variations in the soil conditions can significantly influence the resistance of the substation. Therefore,
resistance testing for the substations are typically performed in seasons when the influence of frozen
soil is not present.
The definitions and applications of grounding and bonding are as per Section 0, Section 10-000 Series, and
Section 36-000 Series of CSA Standard C22.1, Canadian Electrical Code, Part I.
This rule is intended as a progressive evaluation of all subrules and not intended as standalone requirements.
Subrules may supersede specific previous subrules requirements.
Figures 7 and 8 show the progression of the fencing grounding interconnections requirements. Figures outline
where the subrules of 6-116 are applied.
References to minimum conductor size in subrules (2) and (3) are based on minimum electrical characteristics
for grounding/bonding a fence. A #4 AWG minimum conductor matches commentary found in the AEUC
Appendix D (§15.2) for current-carrying capacity.
The primary purpose of fence grounding is to prevent or mitigate touch and step potential hazards. If these
hazards are shown not to be present or the potential mitigated, a fencing system may be isolated from the
grounding system.
8-014 Buildings
Electrical equipment often contains gases for insulation medium, or DC equipment can have gas generation
under certain conditions. Subrule 8-14(j) is intended to cover the appropriate gas release scenario by
either having active ventilation to prevent build up or triggered ventilation for specific scenarios. This is all
determined by the gas scenario created by the equipment installed in the building.
Where extreme local environmental conditions exist, higher fences shall be considered to prevent:
(a) inadvertent entry of pedestrian and animal traffic; and
(b) blown conductive debris from nearby facilities.
8-306 Gates
Fences with only inward opening vehicle gates shall have a separate personnel gate installed adjacent to the
inward opening gate, or a personnel gate built into the main vehicle gate to enable personnel entry into the
substation for emergency access and snow removal.
The substation yards should not contain material that is not required for equipment replacement/ sparing for
speed of restoration, and should not include any consumables / general construction material (e.g., copper
wiring,). These consumable items are targets for theft and the intention is to limit the access or entries into a
live substation.
Securing firmly requires some form of latching, physical interlock, clasping, bolting, or screwing, and shall not
solely rely on the weight of part of the enclosure or friction fit.
The measurement point is from any point along the switch path from the blade to neighbouring structures
and other live parts. The intention is to consider the dynamic distance during switch operation, as the blade
may be energized and arcing may occur.
(2) Pipelines
Guidance for pipelines located in proximity to electrical utility system HVDC transmission lines can be found
in Influence of High Voltage DC Power Lines on Metallic Pipelines, published by Canadian Association of
Petroleum Producers and available on the CAPP website.
Guidance for pipelines located in proximity to distribution lines can be found in Inductive Coordination of
Distribution Lines and Pipelines, published by Alberta Power Industry Consortium.
The Electrical Utilities Sub-Council (EUSC) agreed that the descriptions in the AEUC Table 5 (CSA C22.3 No.1
Table 2) under the column “Location of Wires or Conductors” were vague and interpretation was difficult
and required clarification. Reference to the heights of vehicles that may be passing under the aerial lines was
added to the AEUC Table 5 for clarity. It was also determined that clearances in the 2002 edition were more
appropriate, so the values in the chart were changed back to that edition.
Trolley systems were prevalent in Alberta up to the year 2010. The Trolley transportation systems are not
prevalent in Alberta, so this column was removed. Refer to CSA C22.3 No. 1 for further information.
Voltages were modified in the 2013 edition of the AEUC to reflect what is considered standard in Alberta.
References to voltages that are not used in Alberta were removed.
The description at the top of Table 5 was modified in the 2013 edition of the AEUC to identify the voltage as
line to ground, and the DC column for 500kV DC was added for clarity. DC transmission voltages were not
referenced in the 2007 edition.
Table 5 notes were redone based on recalculation of transmission voltages and the following sample
calculations.
Sample Calculation for max 150kV AC line to ground Flashover (260kV AC Line to Line)
From CSA C22.3 No.1 Table A.1, the switching surge factor or switching overvoltage (SOV) for a maximum
line to ground voltage of 150kV is 2.75p.u. (per unit).
150kV is a root mean square (RMS) value that must be converted to a peak voltage value. For a sinusoid
wave form, this conversion factor is the square root of 2.
(Note that Table A.1 of the CSA C22.3 No.1 shows 1586 mm)
Example, for a road crossing allowing a 5.3m vehicle and load combined height:
This clearance is close to what the current version of the AEUC requires (7.3 m).
+/- 500 kV DC governed by DC electric field level limits for general public exposure. The International
Commission on Non-Ionizing Radiation Protection (ICNIRP) suggests a limit for general public exposure of
less than 28 kV/m, which will result in ground clearance of 12.2m
Example, for a road crossing allowing a 5.3m vehicle and load combined height:
Alternate calculation: use +/- 450 kV clearance and add 0.005 m/kV for each kV over 450 kV (as
recommended by note on CSA C22.3 No. 1, Table 4.)
The description was changed in Table 5 under “Location of Wires or Conductors” (Column 1) based on the
height of equipment, building, or object being transported on the highways in Alberta.
15.1 General
(1) For bare grounding conductors, the short time ampacity is the current that the conductor can carry
for the time during which the current flows without melting or affecting the design characteristics of
the conductor.
(2) For insulated grounding conductors, the short time ampacity is the current that the conductor can
carry for the applicable time without affecting the design characteristics of the insulation.
(3) Where grounding conductors at one location are paralleled, the increased total current capacity may
be considered.
Typically, grounding conductors should have a minimum current-carrying capacity of #4 AWG copper size or
equivalent.
See Figures 1 and 2 for examples of Ground Electrode and Gradient Control
When the cross sectional area or mass of the grounding system equipment/assembly has been reduced by
corrosion to less than 80% of the original amount, the grounding system equipment/assembly should be
replaced.
(1) The conductor used in gradient control to form loops and connections to grounding conductors or
electrodes on electrical utility systems should be sufficient to prevent burn-off of the gradient control
conductors when fault currents flow on the grounding conductors or electrodes.
(2) If gradient conductors are required at pad-mounted electrical equipment locations, the loops should:
(a) be placed not less than 500 mm nor more than 1000 mm apart; and
(b) be located not less than 200 mm below grade level.
(3) If gradient control conductor loops are placed around pad-mounted electrical equipment, two or
more physically separated gradient control conductors should be used to interconnect the gradient
loops to the grounding system.
(Note: These clauses have been taken from the CSA C22.3 No. 1:20, Overhead Systems.)
Where a single electrode resistance exceeds 25 Ω, up to two additional electrodes connected in parallel or up
to two deep-driven electrodes should be used unless it is clear that additional electrodes will not significantly
reduce the resistance.
The intent of the 25 Ω limit is to provide a starting point (or target) to confirm the interconnected resistance is
below 6 Ω.
The following steps are recommended to mitigate current described in Clause 15.11:
(a) grounding the other equipment;
(b) improving the grounding system;
(c) changing the locations of ground connections or ground electrodes;
(d) eliminating parallel paths; or
(e) using other mitigation methods designed, engineered, and constructed in accordance with
recognized industry standards.
CSA C22.3 No.7:20, Section 16.3 permits the use of coloured ducts for identification of different systems, and
defines the colours that are suggested for different systems. Coloured ducts are not required by Section 16.3,
but may be required by the utility.