Date : 05/10/2021
Test Report No. : 003472
abb
ROUTINE TEST CERTIFICATE
Purchaser's Name : SMART ELECTRIC INDIA PRIVATE LIMITED
Sale Order No. 4202423450
Type of Breaker VD4/W 12.12.25
Serial Number of Breaker 1VYN020121003472
Rated Voltage 12 kV
Insulation Level 28/75 kV/kVpk
Rated Current 1250 A
Breaking Capacity 26.3 kA
Rated Frequency 50 Hz
Mass 100 Kg
Rated Control Voltage for Trip Coil 110 V DC
Rated Control Voltage for Close Coil 110 V DC
Rated Control Voltage for Motor 230 V AC
Year of Manufacture 2021
R O U T I N E T E S T S A C C O R D I N G T O I E C 62271-100
1. MECHANICAL OPERATION TESTS : Satisfactory.
1.1 5 closing and 5 opening operations at 110% of control voltage
1.2 5 closing and 5 opening operations at 85% of control voltage
1.3 5 closing and 5 opening operations at rated control voltage
1.4 5 opening operations at 70% control voltage
1.5 5 closing - opening operations at 100% of control voltage
1.6 5 opening - 0.3 sec- closing operations at 100% control voltage
P.T.O.
Date : 05/10/2021
Test Report No: 003472
abb
1.7 Opening - 0.3 sec - closing operation at rated control voltage.
1.7.1 Travel and contact diagrams 1 DIV = 5mm
1.7.2 Operating Speed (m/s) 1.7.3 Operating time (ms)
Perameter R Y B Pole R Y B
Open 1.18 1.21 1.17 Open 49.3 49.3 48.8
Close 0.98 1.02 1.04 Close 62.7 62.7 62.8
1.7.4 Travel (mm) R Y B
Total Travel 15.4 15.31 15.4
Max. Over Travel on Opening 11.78 12.33 12.71
Max. Over Travel on Closing 4.47 4.51 4.57
Max. Bounce on Opening 0.4 0.46 0.45
Contact Spring Travel 3.71 3.71 3.6
2. RESISTANCE OF MAIN CIRCUIT : Satisfactory
Resistance in micro Ohms measured at 100A DC.
R - Pole = 25 Y - Pole = 26 B - Pole = 25
3. DIELECTRICAL TESTS : Satisfactory
3.1 Main circuit : 28 kV, 50Hz for 60s
Breaker Position Test Voltage connected to Earth connected to
Close R and B-poles Frame and Y-pole
Close Y - pole Frame, R and B-pole
Open Top Terminal Frame and Bottom terminal
Open Bottom Terminal Frame and Top terminal
3.2 Auxiliary circuits : 2 kV, 50 Hz, for 60 s (Motor disconnected)
4. VISUAL INSPECTION : Satisfactory
The Circuit Breaker has been successfully tested and accepted as described above
Digitally signed by ABB
Date: 2023.06.28 [Link] +05:30
Location: Nashik
INBT-007 Toll Free no: 18004200707
Email:ppmvsupport@[Link]
Note: This is Computer generated RTC. No Signature is required.