Substation Electrical Single Line Diagram

This document provides a diagram of an electrical system with overhead and underground cabling. It includes a 11kV overhead line feeding into a 11kV line arrestor and disconnect fuse. From there, 11kV cable runs to a metering panel, switchgear, and transformer. Cables then run from the transformer to a generator control panel and motor control center. Grounding and neutral conductors connect various equipment to earth pits.

Uploaded by

Md osman gony
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views1 page

Substation Electrical Single Line Diagram

This document provides a diagram of an electrical system with overhead and underground cabling. It includes a 11kV overhead line feeding into a 11kV line arrestor and disconnect fuse. From there, 11kV cable runs to a metering panel, switchgear, and transformer. Cables then run from the transformer to a generator control panel and motor control center. Grounding and neutral conductors connect various equipment to earth pits.

Uploaded by

Md osman gony
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

From 11KV Over Head Line (REB)

50rm bare Copper Conductor


330kVA, 50HZ, 415V for Generator Body Earthing 50rm bare Copper Conductor
0.8 P.F. 3 Phase From earth pit-1
11KV LA
Diesel Generator 50 rm bare Copper Conductor From earth pit-2
11KV DOF Pole Mounted for Generator Neutral Grounding From earth pit-3
Earth
1X3CX50rm 11KV HT Cable Type NYSEYFGBY
Control Panel
630A TP
MCCB
HT Metering Panel Set 570A
70rm bare Copper Conductor
[Panel Board ECC]
1X3CX50rm 11KV HT Cable Type NYSEYFGBY
HT Switchgear
(630A VCB) 50rm BYA Cable
[Panel Board ECC]
4X1CX1X300rm NYY TPN
1X1CX50rm BYA Cabler for 1X3CX50rm 11KV HT Cable Type NYSEYFGBY
70rm bare Copper Conductor X-former Body Earthing
From earth pit-9 11/0.415KV, 50Hz, Dyn11
From earth pit-8
1X1CX300rm NYY Cable for 630kVA, Step Down Oil Immersed Transformer
From earth pit-5 X-former Neutral Grounding
From earth pit-4
4X1CX(2X300)rm NYY (TPN)
+1X1CX300rm BYA ECC [from earth pit 6 & 7]
LT Panel/Substation Room
Bus Bar Size: R=130.87 kW Interlocking (Manual)
Y=132.98 kW
(60mmx10)x2mm Copper (TPN),Capacity:960A B=126.80 kW 1000A TP MCCB 630A TP MCCB
60mmx5mm Copper (E),Capacity:480A Sum of Max. Load=390.65 kW Icu=50kA Icu=50kA
RYB RYB RYB RYB RYB RYB RYB RYB

630A TP MCCB

250A TP MCCB

250A TP MCCB

250A TP MCCB

200A TP MCCB

200A TP MCCB

200A TP MCCB
63A TP MCCB
[Panel Board ECC]
50rm BYA Cable

Set-570A

4X1CX150rm NYY TPN+1X1CX70rm BYA for ECC

4X1CX150rm NYY TPN+1X1CX70rm BYA for ECC

4X1CX150rm NYY TPN+1X1CX70rm BYA for ECC

4X1CX120rm NYY TPN+1X1CX70rm BYA for ECC

4X1CX120rm NYY TPN+1X1CX70rm BYA for ECC


MDB-1/Electric Room

Max.Load=58.55 kW
Max.Load=73.97 kW

Max.Load=89.77 kW

Max.Load=79.53 kW

Max.Load=88.83 kW
[Panel Board ECC]

MDB-3/middle side
180rm NYY Cable

MDB-2/East side
PFI Panel
380kVAR

MDB-1

MDB-2
Spare

Spare
PROJECT NAME: ADDRESS: CONSULTANT : DRAWN BY: CHECKED BY: DRAWING TITLE: DATE: PAGE NO.
Engr. Md. Osman Gony
Bangabondhu Sheck Mujib Silpa
Zhec Bow Semedric JV (WTP) Institute of Water Modeling Sr. Safety Officer Wang Yanchao (DPM) Electrical Single Line Diagram of Substation 20.07.2023
01 of 1
Nagar,Mirsorai,Bangladesh. Electrical Licence No ABC -2020000513