Product data sheet
Specifications
controller M200 40 IO relay
+Ethernet
TM200CE40R
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Easy Modicon M200
Product or component type Logic controller
[Us] rated supply voltage 100...240 V AC
Discrete I/O number 40
Discrete input number I2...I5: 4 fast input
I0, I1, I6, I7: 4 high speed input
I8...I23: 16 regular input
Discrete output number 16 relay
Discrete input voltage 24 V
Discrete input voltage type DC
Discrete input current 7 mA for input
Discrete input logic Sink or source (positive/negative) type 1 conforming to EN/IEC 61131-2
Discrete output voltage 24 V DC
220 V AC
Discrete output current 2A
Discrete output type Relay normally open
Power consumption in VA 59…69 VA at 100...240 V AC (with max I/O)
Complementary
Maximum number of I/O 4 with 128 discrete output(s) for transistor output
expansion module 4 with 80 discrete output(s) for relay output
Supply voltage limits 85…264 V
Network frequency 50/60 Hz
Inrush current 50 A
Voltage state 1 guaranteed >= 15 V for input
Voltage state 0 guaranteed <= 5 V for input
Input impedance 3.3 kOhm for discrete input
Response time 5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input
5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input
100 µs turn-off, I2...I5 terminal(s) for fast input
35 µs turn-on, I2...I5 terminal(s) for fast input
100 µs turn-off, I8...I13 terminal(s) for regular input
35 µs turn-on, I8...I13 terminal(s) for regular input
10 ms turn-off, Q0...Q15 terminal(s) for relay output
10 ms turn-on, Q0...Q15 terminal(s) for relay output
125 µs turn-off, I14...I23 terminal(s) for regular input
Dec 8, 2022 1
55 µs turn-on, I14...I23 terminal(s) for regular input
Configurable filtering time 0 ms for input
3 ms for input
12 ms for input
Output voltage limits 30 V DC
250 V AC
Maximum current per output 4 A
common
Electrical durability 100000 cycles AC-12, 240 V, 480 VA, resistive
100000 cycles DC-12, 24 V, 48 W, resistive
Switching frequency 0.1 Hz with maximum load
Mechanical durability 20000000 cycles for relay output
Minimum load 10 mA at 5 V DC for relay output
Memory capacity 512 byte internal flash for backup of programs
Data storage equipment 32 GB micro SD card (optional)
Battery type BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)
Backup time 3 years at 25 °C (by interruption of power supply)
Execution time for 1 0.3 ms for event and periodic task
KInstruction
Execution time per instruction 0.2 µs Boolean
Exct time for event task 60 µs response time
Clock drift <= 90 s/month at 25 °C
Regulation loop Adjustable PID regulator up to 14 simultaneous loops
Control signal type Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode)
Pulse/direction at 100 kHz for fast input (HSC mode)
Single phase at 100 kHz for fast input (HSC mode)
CW/CCW at 100 kHz for fast input (HSC mode)
Counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
Integrated connection type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with terminal block connector and RS485 interface
Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface
Ethernet Modbus TCP/IP Ethernet with RJ45 connector and 1 Ethernet port 10/100BASE-T interface
Isolated serial link serial 2 with terminal block connector and RS485 interface
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
12 Mbit/s for USB
10/100 Mbit/s for bus length of 100 m for Ethernet Modbus TCP/IP
Communication port protocol USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Ethernet Modbus TCP/IP: Modbus TCP/IP client/server
Local signalling 1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED per channel (green) for I/O state
2 LEDs (green) for communication (LK/ACT 10/100)
Electrical connection Mini B USB 2.0 connectorfor a programming terminal
RJ45 connectorfor connecting Ethernet network
removable screw terminal blockfor inputs
removable screw terminal blockfor outputs
removable screw terminal block, 4 terminal(s) for connecting the serial link1
removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply
Maximum cable distance Unshielded cable: <50 m for input
between devices Shielded cable: <10 m for fast input
Shielded cable: <10 m for high speed input
Unshielded cable: <150 m for output
Insulation Non-insulated between inputs
Between output and internal logic at 1780 V AC
Between output groups at 1780 V AC
Between supply and internal logic at 1780 V AC
Between input and internal logic at 500 V AC
Between fast input and internal logic at 500 V AC
2
Dec 8, 2022
Between input groups at 500 V AC
Sensor power supply 24 V DC at 300 mA supplied by the controller
Marking CE
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715
Height 90 mm
Depth 70 mm
Width 175 mm
Net weight 0.512 kg
Environment
IP degree of protection IP20 with protective cover in place
Product certifications RCM
IACS E10
CSA
cULus
Standards EN/IEC 61010-2-201
EN/IEC 61131-2
Electromagnetic compatibility Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC
61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to EN/IEC
61000-4-3
Magnetic field at power frequency - test level: 30 A/m conforming to EN/IEC 61000-4-8
Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to EN/IEC
61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to EN/IEC
61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to EN/IEC
61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to EN/IEC
61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to EN/IEC
61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to EN/IEC
61000-4-5
Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to EN/
IEC 55011
Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to EN/
IEC 55011
Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to EN/IEC 55011
Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to EN/IEC 55011
Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to EN/IEC
61000-4-4
Shock resistance 15 gn for 11 ms
30 gn for 6 ms
Immunity to microbreaks 10 ms
Vibration resistance 3.5 mm at 5…8.4 Hz on symmetrical rail
1 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.7 Hz on panel mounting
2 gn at 8.7…150 Hz on panel mounting
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
Ambient air temperature for 0…55 °C (horizontal installation)
operation
Ambient air temperature for -25…70 °C
storage
Pollution degree <= 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Dec 8, 2022 3
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 9.498 cm
Package 1 Width 13.66 cm
Package 1 Length 18.72 cm
Package 1 Weight 771 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 2 Weight 9773 g
Unit Type of Package 3 P12
Number of Units in Package 3 288
Package 3 Height 95 cm
Package 3 Width 80 cm
Package 3 Length 120 cm
Package 3 Weight 243552 g
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
known to the State of California to cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
4
Dec 8, 2022
Product data sheet TM200CE40R
Dimensions Drawings
Dimensions Drawings
Dimensions
Dec 8, 2022 5
Product data sheet TM200CE40R
Mounting and Clearance
Mounting and Clearance
Mounting on a Rail
Direct Mounting on a Panel Surface
Mounting Position
6
Dec 8, 2022
Clearance
TMCR2•••Installation
Dec 8, 2022 7
TMCR2••• De-Installation
8
Dec 8, 2022
Dec 8, 2022 9
Product data sheet TM200CE40R
Connections and Schema
Wiring Diagram / Connections Schema
AC Power Supply
(*) Type T fuse
Digital Inputs Positive Logic (Sink)
(*) Type T fuse
(**) Fast inputs
(1) The COM0 and COM1 terminals are not connected internally.
Digital Inputs Negative Logic (Source)
(*) Type T fuse
(**) Fast inputs
(1) The COM0 and COM1 terminals are not connected internally.
10
Dec 8, 2022
Relay Outputs - Negative Logic (Sink)
(*) Type T fuse
(1) The COM0 and COM1 terminals are not connected internally.
(2) A free wheeling diode or an RC snubber
Relay Outputs - Positive Logic (Source)
(*) Type T fuse
(1) The COM0 and COM1 terminals are not connected internally.
(2) A free wheeling diode or an RC snubber
Ethernet Connection
Pin N° Signal
1 TD +
2 TD —
3 RD+
4 —
5 —
6 RD —
7 —
8 —
Dec 8, 2022 11
USB Mini-B Connection
SL1 Connection
D1 : D1 (A+)
D0 : D0 (B-)
Shield : Shield
COM : O V Com
12
Dec 8, 2022
Product data sheet TM200CE40R
Performance Curves
Derating Curves
Relay Outputs
X: Ambient temperature (°C / °F)
Y: Output load current (%)
Recommended replacement(s)
Dec 8, 2022 13