Transformer Routine Tests
Transformer Routine Tests
Client Details
Client Name Yotta Infrastructure Solutions LLP
Requester Name Shridhar Bapat
Rohit Singh
PO Number E -mail confirmation
PO Date January 16, 2023
Contact No. #9990669585
Site Details
Site Name Yotta D1 - Noida
Contact Person at Site Rohit Singh
Shikha Jain
Contact No. NA
9990669585
Address Greater Noida West Link Rd, Tusiana Village, Knowledge Park V,
City Greater Noida
State Uttar Pradesh
Pin 201306
Ms.Gauri Thorat
Report Checked By Ms. Smita Vichare
Report Approved By Mr. Kartik Chaple
Mr.Nilesh Parekh
1
Transformer Winding Resistance Test
NOTE: Result "Good" indicates the value of winding resistance deviation between any of two phases is less than +/- 5 %
Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE
KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry
Impedance
6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
Percentage (%)
Transformer Tag
Cu HV 1 1 25 0.3076 0.3089 0.3087 0.3669 0.3684 0.3682 0.42 Good
No 11
Transformer Tag
Cu HV 4 1 25 0.2831 0.2832 0.2828 0.3376 0.3378 0.3373 0.14 Good
No 11
Transformer Tag
Cu HV 7 1 25 0.2604 0.2606 0.2608 0.3106 0.3108 0.3111 0.15 Good
No 11
Transformer Tag
Cu LV 4 10 25 0.000300 0.000298 0.000296 0.000358 0.000355 0.000353 1.34 Good
No 11
For Efficienergi
Consulting Pvt.
Ltd.
2
Transformer Vector Group Test
NOTE: Result "Vector Matched with Name plate Vector" indicates all arithmetical relations are maintained as in the below formula as per the vector group of transformer
Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE
KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry
Impedance Percentage (%) 6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
Transformer
Transformer Measured Measured Measured Measured Measured Measured Measured Measured Measured Measured Remarks by Test
Nameplate Test Result Result
Name Vector Voltage 1U 1V Voltage 1V 1W Voltage 1W 1U Voltage 1W 2w Voltage 1V 2w Voltage 1V 2v Voltage 1W 2v Voltage 1U 2n Voltage 1V 2n Vector Engineer
1U-1V = 1U-2n + 1V-2n --
Condition Satisfied
Transformer Tag 1V-2W = 1V-2V --
Dyn11 424 424 421 409 410 410 425 9.99 415.5 Dyn11 Good
No 11 Condition Satisfied
1W-2W < 1W-2V --
Condition Satisfied
3
Transformer Voltage Ratio Test
NOTE: Result "Good" indicates the value of deviation between measured and reference tap position is less than +/- 0.5 %
Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE
KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry
Impedance Percentage (%) 6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
4
Transformer Insulation Resistance Test
NOTE: Result "Good" indicates the value of insulation resistance for one minute is more than minimum required value, i.e 2 Mega Ohm per KV.
HV Current in
Serial Number 3223400002001 Number of Taps 7 118.1 Manufacturer QRE
Ampere
LV nominal Type of
KVA Rating 2250 Nominal Tap 4 433 Dry
Voltage in Volts Transformer
Impedance LV nominal
6 HV Voltage in Volts 11000 3000.18 Vector Group Dyn11
Percentage (%) Current in Ampere
For Efficienergi
Consulting Pvt. Ltd.
5
Transformer Magnetic Balance Test
NOTE: Result "Good" indicates the value of Magnetic Unbalance Percentage is less than +/- 2%
Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE
KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry
Impedance
6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
Percentage (%)
Transformer Tag No
R-open 173.6 414 240.1 3.94 9.4 5.45 0 0 0 0.07% 0.3 Good
11
Transformer Tag No
Y-open 80.8 335.3 415.8 1.83 7.64 9.45 0 0 0 -0.07% -0.3 Good
11
Transformer Tag No
B-open 414.7 298.3 115.7 9.41 6.83 2.59 0 0 0 0.17% 0.7 Good
11
APPROVED
WITNESSED BY
BY
For Efficienergi Consulting
TESTING DONE BY
Mr.Anwar Hussain
Santosh Warghade Sandeep Gupta Nilesh Chaple Pvt. Ltd.
Pranit Chavan
6
Transformer Magnetic Current Test
NOTE: Result "Good" indicates if Excitation current < 50 mili-Amperes, then difference between two higher currents should be less than 10%.
HV Current in
Serial Number 3223400002001 Number of Taps 7 118.1 Manufacturer QRE
Ampere
LV nominal Voltage
KVA Rating 2250 Nominal Tap 4 433 Type of Transformer Dry
in Volts
Impedance LV nominal Current
6 HV Voltage in Volts 11000 3000.18 Vector Group Dyn11
Percentage (%) in Ampere
Transformer Tag No
HV 416 415 415 23 17 17 31.58 Moderate
11
For Efficienergi
Consulting Pvt.
Ltd.