Transformer Routine Tests

The document reports on the routine tests conducted on Transformer No-11 from January 16, 2023 to February 14, 2023 for client Yotta Infrastructure Solutions LLP, including the winding resistance test and vector group test, and finds that the transformer is healthy with no impacts and periodic monitoring is recommended.

Uploaded by

manish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views9 pages

Transformer Routine Tests

The document reports on the routine tests conducted on Transformer No-11 from January 16, 2023 to February 14, 2023 for client Yotta Infrastructure Solutions LLP, including the winding resistance test and vector group test, and finds that the transformer is healthy with no impacts and periodic monitoring is recommended.

Uploaded by

manish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Efficienergi Consulting Private Limited.

Transformer Routine Tests


Transformer No-11
Report for Yotta Infrastructure Solutions LLP

MOB_TRT/REPORT | 2021/5/26 | v1.00 1


This Report is the Intellectual Property of M/s Efficienergi Consulting Pvt. Ltd. Plagiarism in Part or Full will be considered as theft of Intellectual
property. The Information in this Report is to be treated as Confidential.
Yotta Infrastructure Solutions LLP
Transformer Routine Tests

Transformer Routine Tests


Test Start Date January 16, 2023
Test End Date February 14, 2023
Report Date March 25, 2023

Client Details
Client Name Yotta Infrastructure Solutions LLP
Requester Name Shridhar Bapat
Rohit Singh
PO Number E -mail confirmation
PO Date January 16, 2023
Contact No. #9990669585

Site Details
Site Name Yotta D1 - Noida
Contact Person at Site Rohit Singh
Shikha Jain
Contact No. NA
9990669585
Address Greater Noida West Link Rd, Tusiana Village, Knowledge Park V,
City Greater Noida
State Uttar Pradesh
Pin 201306

Test and Report Information


Site Measurement done Santosh Warghade
Mr.Anwar Hussain
By Pranit Chavan

Ms.Gauri Thorat
Report Checked By Ms. Smita Vichare
Report Approved By Mr. Kartik Chaple
Mr.Nilesh Parekh

MOB_TRT/REPORT | 2021/5/26 | v1.00 2


This Report is the Intellectual Property of M/s Efficienergi Consulting Pvt. Ltd. Plagiarism in Part or Full will be considered as theft of Intellectual property. The Information in this
Report is to be treated as Confidential.
Transformer Routine Tests

Findings,Impacts and Recommendations

Test Finding Impacts Recommendation

All Tests Healthy No Impacts Periodic Monitoring is Required

1
Transformer Winding Resistance Test

NOTE: Result "Good" indicates the value of winding resistance deviation between any of two phases is less than +/- 5 %

Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE

KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry

Impedance
6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
Percentage (%)

Corrected Corrected Corrected


Measured Measured Measured Measured
Transformer Transformer Winding Winding Winding
Transformer Tapping Applied Current Winding winding winding winding % Deviation Remarks by Test
Winding Measurement Resistance (UV) Resistance (VW) Resistance (WU) Result
Name Number in Amps Temperature in Resistance (UV) Resistance (VW) Resistance (WU) between Phases Engineer
Material Side in Ohm (Ref 75° in Ohm (Ref 75° in Ohm (Ref 75°
Deg C Ohm Ohm Ohm
C) C) C)

Transformer Tag
Cu HV 1 1 25 0.3076 0.3089 0.3087 0.3669 0.3684 0.3682 0.42 Good
No 11
Transformer Tag
Cu HV 4 1 25 0.2831 0.2832 0.2828 0.3376 0.3378 0.3373 0.14 Good
No 11
Transformer Tag
Cu HV 7 1 25 0.2604 0.2606 0.2608 0.3106 0.3108 0.3111 0.15 Good
No 11
Transformer Tag
Cu LV 4 10 25 0.000300 0.000298 0.000296 0.000358 0.000355 0.000353 1.34 Good
No 11

TESTING DONE BY WITNESSED BY APPROVED BY


Santosh
Mr.Anwar Hussain
Warghade Sandeep Gupta Nilesh Chaple
Pranit Chavan

For Efficienergi
Consulting Pvt.
Ltd.

2
Transformer Vector Group Test
NOTE: Result "Vector Matched with Name plate Vector" indicates all arithmetical relations are maintained as in the below formula as per the vector group of transformer

Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE

KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry

Impedance Percentage (%) 6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11

Transformer
Transformer Measured Measured Measured Measured Measured Measured Measured Measured Measured Measured Remarks by Test
Nameplate Test Result Result
Name Vector Voltage 1U 1V Voltage 1V 1W Voltage 1W 1U Voltage 1W 2w Voltage 1V 2w Voltage 1V 2v Voltage 1W 2v Voltage 1U 2n Voltage 1V 2n Vector Engineer
1U-1V = 1U-2n + 1V-2n --
Condition Satisfied
Transformer Tag 1V-2W = 1V-2V --
Dyn11 424 424 421 409 410 410 425 9.99 415.5 Dyn11 Good
No 11 Condition Satisfied
1W-2W < 1W-2V --
Condition Satisfied

TESTING DONE BY WITNESSED BY APPROVED BY


Santosh
Mr.Anwar Hussain
Warghade Sandeep Gupta Nilesh Chaple
Pranit Chavan

For Efficienergi Consulting


Pvt. Ltd.

3
Transformer Voltage Ratio Test
NOTE: Result "Good" indicates the value of deviation between measured and reference tap position is less than +/- 0.5 %

Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE

KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry

Impedance Percentage (%) 6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11

Measured Measured Voltage % Voltage Deviation


Measured Reference
Measured Voltage vw Voltage wu Transfomation difference between Remarks by
Measured Voltage UV Measured Voltage VW Voltage WU Tap Positions
Transformer Name Tapping Number Voltage uv (Volts) (Volts) (Volts) Ratio w.r.t. Tap Between taps measured Result Test Engineer
(Volts)_Primary Side (Volts)_Primary Side (Volts) (%)
_Secondary Side _Secondary _Secondary position (HV/LV) wrt to Center and Ref tap
_Primary Side
Side Side Tap position (%)

Transformer Tag No11


1 416.1 415 415.8 15.18 15.17 15.2 27.37 7.76 7.5 0.26 Good

Transformer Tag No11


2 416.1 415 415 15.62 15.59 15.66 26.59 4.65 5 -0.35 Good

Transformer Tag No11


3 416.1 415 415 15.98 15.95 16.02 25.99 2.30 2.5 -0.20 Good

Transformer Tag No11


4 416.1 415 415 16.33 16.31 16.4 25.41 0.02 0 0.02 Good

Transformer Tag No11


5 423 423.3 423.5 17.03 17.12 17.07 24.79 -2.41 -2.5 -0.09 Good

Transformer Tag No11


6 423.1 423.4 423.3 17.59 17.55 17.64 24.06 -5.30 -5 0.30 Good

Transformer Tag No11


7 429.1 428.7 429.6 18.18 18.19 18.25 23.57 -7.22 -7.5 -0.28 Good

For Efficienergi Consulting


Pvt. Ltd.
TESTING DONE BY WITNESSED BY APPROVED BY
Santosh Warghade
Mr.Anwar Hussain Sandeep Gupta Nilesh Chaple
Pranit Chavan

4
Transformer Insulation Resistance Test

NOTE: Result "Good" indicates the value of insulation resistance for one minute is more than minimum required value, i.e 2 Mega Ohm per KV.

HV Current in
Serial Number 3223400002001 Number of Taps 7 118.1 Manufacturer QRE
Ampere

LV nominal Type of
KVA Rating 2250 Nominal Tap 4 433 Dry
Voltage in Volts Transformer
Impedance LV nominal
6 HV Voltage in Volts 11000 3000.18 Vector Group Dyn11
Percentage (%) Current in Ampere

TRANSFORMER INSULATION RESISTANCE TEST - BEFORE HIPOT TEST


Measured Measured Measured
Insulation Insulation Insulation
Transformer Name Time in mins Applied Voltage Applied Voltage Result Remarks
Resistance Resistance (HV_G) Resistance (LV_G)
(HV_LV)(Gohm) (Gohm) (Gohm)
Transformer Tag
1 Before Hi-Pot Test 5000 341 334 62.3 Good
No 11

TESTING DONE BY WITNESSED BY APPROVED BY


Mr.Anwar Hussain

Santosh Warghade Sandeep Gupta Nilesh Chaple


Pranit Chavan

For Efficienergi
Consulting Pvt. Ltd.

5
Transformer Magnetic Balance Test
NOTE: Result "Good" indicates the value of Magnetic Unbalance Percentage is less than +/- 2%

Serial Number 3223400002001 Number of Taps 7 HV Current in Ampere 118.1 Manufacturer QRE

KVA Rating 2250 Nominal Tap 4 LV nominal Voltage in Volts 433 Type of Transformer Dry

Impedance
6 HV Voltage in Volts 11000 LV nominal Current in Ampere 3000.18 Vector Group Dyn11
Percentage (%)

Measured Measured Measured


Measured Measured Measured Measured Measured Measured Magnetic Magnetic Remarks by
Voltage_Sec Voltage_Seco Voltage_Sec
Transformer Name Test Condition Voltage_Primary UV Voltage_Primary VW Voltage_Primary WU Voltage_Secondary Voltage_Secondary Voltage_Secondary wu Unbalance Unbalance Result Test
ondary uN ndary vN ondary wN
(Volts) (Volts) (Volts) uv (Volts) vw (Volts) (Volts) (%) (Volts) Engineer
(Volts) (Volts) (Volts)

Transformer Tag No
R-open 173.6 414 240.1 3.94 9.4 5.45 0 0 0 0.07% 0.3 Good
11
Transformer Tag No
Y-open 80.8 335.3 415.8 1.83 7.64 9.45 0 0 0 -0.07% -0.3 Good
11
Transformer Tag No
B-open 414.7 298.3 115.7 9.41 6.83 2.59 0 0 0 0.17% 0.7 Good
11

APPROVED
WITNESSED BY
BY
For Efficienergi Consulting
TESTING DONE BY
Mr.Anwar Hussain
Santosh Warghade Sandeep Gupta Nilesh Chaple Pvt. Ltd.
Pranit Chavan

6
Transformer Magnetic Current Test
NOTE: Result "Good" indicates if Excitation current < 50 mili-Amperes, then difference between two higher currents should be less than 10%.

HV Current in
Serial Number 3223400002001 Number of Taps 7 118.1 Manufacturer QRE
Ampere

LV nominal Voltage
KVA Rating 2250 Nominal Tap 4 433 Type of Transformer Dry
in Volts
Impedance LV nominal Current
6 HV Voltage in Volts 11000 3000.18 Vector Group Dyn11
Percentage (%) in Ampere

Applied Applied Applied % Deviation Remarks by


Transformer Measured Current Measured Current Measured Current
Transformer Name Voltage_Primary UV Voltage_Primary VW Voltage_Primary WU Between Result Test
Measurement Side IU (mA) IV (mA) IW (mA)
(Volts) (Volts) (Volts) Measured Phases Engineer

Transformer Tag No
HV 416 415 415 23 17 17 31.58 Moderate
11

TESTING DONE BY WITNESSED BY APPROVED BY


Mr. Anwar Hussain
Santosh Warghade
Sandeep Gupta Nilesh Chaple
Pranit Chavan

For Efficienergi
Consulting Pvt.
Ltd.