Ba00100den 1311
Ba00100den 1311
BA00100D/06/EN/13.11
71130013
Valid as of software version
V 1.02.XX (electronics board)
Brief operating instructions Proline Prosonic Flow 91
Safety instructions ä5
First familiarize yourself with the safety instructions to be able to carry out the following work steps quickly and easily.
Here, you can find information on:
• The designated use of the measuring device
• The operational safety
• The safety symbols and conventions used in the document
▼
Connecting the transmitter ä 30
Install the sensors using the transmitter software.
Therefore connect the transmitter first to the power supply.
▼
Display and operating elements ä 34
A brief overview of the different display and operating elements to allow you to start quickly.
▼
Installing the sensors ä 10
Installing the flowrate measuring sensors Prosonic Flow W (clamp-on)
▼
Sensor Setup ä 46
Measuring devices with a local display:
Use the "Sensor Setup" ( ä 46) to determine the data required for sensor installation such as sensor distance, wire
length, pipe materials, sound velocity in liquids, etc.
• The system provides you with the sensor distance for the W "clamp-on" versions as distance data.
For the W sensors, you also receive the data in the form of a letter for sensor 1 and in the form of a number for
sensor 2. You can thus easily position the sensors with the aid of the mounting rail.
Measuring devices without a local display:
No Sensor Setup is available for devices without a local display.
The sensor installation procedure for such devices is explained on.
▼
Customer-specific configuration ä 49
Complex measurement tasks require the configuration of additional functions which you can individually select, set and
adapt to your process conditions using the function matrix. There are two options:
• Setting parameters via the configuration program "FieldCare"
• Setting parameters via the local display (optional)
All functions are described in detail, as is the function matrix itself ä 75.
! Note!
Always start troubleshooting with the checklist on ä 55 if faults occur after commissioning or during operation. This
takes you directly (via various queries) to the cause of the problem and the appropriate remedial measures.
2 Endress+Hauser
Proline Prosonic Flow 91 Table of contents
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 5 3.10.2 Connecting and Grounding Prosonic Flow W
DN 15 to 65 (½ to 2½") Multicore cable . . 28
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.10.3 Cable specifications . . . . . . . . . . . . . . . . . . 29
1.2 Installation, commissioning, operation . . . . . . . . . . . 5
3.11 Connecting the measuring unit . . . . . . . . . . . . . . . 30
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.11.1 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . 30
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.11.2 Terminal assignment . . . . . . . . . . . . . . . . . 31
1.5 Notes on safety conventions and icons . . . . . . . . . . . 6
3.11.3 HART connection . . . . . . . . . . . . . . . . . . . 31
3.12 Potential equalization . . . . . . . . . . . . . . . . . . . . . . . 32
2 Identification . . . . . . . . . . . . . . . . . . . . 7 3.13 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 32
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.14 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 33
2.1.1 Nameplate of the transmitter . . . . . . . . . . . . 7
2.1.2 Nameplate of the sensor . . . . . . . . . . . . . . . 8 4 Operation . . . . . . . . . . . . . . . . . . . . . . 34
2.1.3 Nameplate of the connections . . . . . . . . . . . 8
4.1 Display and operating elements . . . . . . . . . . . . . . . 34
2.2 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 9
4.2 Brief guide to the function matrix . . . . . . . . . . . . . . 35
2.3 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 9
4.2.1 General notes . . . . . . . . . . . . . . . . . . . . . . 36
4.2.2 Enabling the programming mode . . . . . . . . 36
3 Installation . . . . . . . . . . . . . . . . . . . . . 10 4.2.3 Disabling the programming mode . . . . . . . . 36
3.1 Incoming acceptance, transport and storage . . . . . . 10 4.3 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.1.1 Incoming acceptance . . . . . . . . . . . . . . . . . 10 4.3.1 Operating options . . . . . . . . . . . . . . . . . . . 37
3.1.2 Transport . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.3.2 Device description files for
3.1.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 operating programs . . . . . . . . . . . . . . . . . 38
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 11 4.3.3 Device variables . . . . . . . . . . . . . . . . . . . . . 38
3.2.1 Installation dimensions . . . . . . . . . . . . . . . 11 4.3.4 Universal / common practice
3.2.2 Mounting location . . . . . . . . . . . . . . . . . . . 11 HART commands . . . . . . . . . . . . . . . . . . . 39
3.2.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . . 12 4.3.5 Device status/diagnosis messages . . . . . . . 44
3.2.4 Inlet and outlet runs . . . . . . . . . . . . . . . . . 12
3.2.5 Sensor selection and arrangement . . . . . . . 13 5 Commissioning . . . . . . . . . . . . . . . . . . 45
3.3 Preparatory steps prior to installation . . . . . . . . . . . 14 5.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.4 Determining the necessary installation distances . . 14 5.2 Switching on the measuring device . . . . . . . . . . . . 45
3.4.1 Installation distances for Prosonic Flow W 5.3 Commissioning via a configuration program . . . . . . 46
clamp-on . . . . . . . . . . . . . . . . . . . . . . . . . 14 5.3.1 Sensor Setup/sensor installation . . . . . . . . . 46
3.4.2 Determining values for 5.3.2 Commissioning . . . . . . . . . . . . . . . . . . . . . 47
installation distances . . . . . . . . . . . . . . . . . 14 5.3.3 Data backup/transmission . . . . . . . . . . . . . 48
3.5 Mechanical preparation . . . . . . . . . . . . . . . . . . . . . 15 5.4 Application specific commissioning . . . . . . . . . . . . . 49
3.5.1 Mounting the sensor holder with 5.4.1 Zero point adjustment . . . . . . . . . . . . . . . . 49
U-shaped screws (small nominal diameters) 15 5.5 Data storage devices . . . . . . . . . . . . . . . . . . . . . . . 50
3.5.2 Mounting the sensor holder with strapping 5.5.1 HistoROM/T-DAT (transmitter DAT) . . . . . 50
bands (small nominal diameters) . . . . . . . . 16
3.5.3 Premounting the strapping bands
(medium nominal diameters) . . . . . . . . . . . 17 6 Maintenance . . . . . . . . . . . . . . . . . . . . 51
3.5.4 Premounting the strapping bands 6.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 51
(large nominal diameters) . . . . . . . . . . . . . 18 6.2 Coupling fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.6 Installing Prosonic Flow W sensor . . . . . . . . . . . . . 19
3.6.1 Installing Prosonic Flow W 7 Accessories . . . . . . . . . . . . . . . . . . . . . 52
(DN 15 to 65 / ½ to 2½") . . . . . . . . . . . . . 19
3.6.2 Installing Prosonic Flow W 7.1 Device-specific accessories . . . . . . . . . . . . . . . . . . . 52
(DN 50 to 4000 / 2" to 160") . . . . . . . . . . 21 7.2 Accessories specific to measuring principle . . . . . . . 52
3.7 Mounting the transmitter . . . . . . . . . . . . . . . . . . . 26 7.3 Communication-specific accessories . . . . . . . . . . . . 53
3.8 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 26 7.4 Service-specific accessories . . . . . . . . . . . . . . . . . . . 54
3.9 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.10 Connecting and grounding Prosonic Flow W 8 Troubleshooting . . . . . . . . . . . . . . . . . 55
(DN 50 to 4000 / 2 to 160") 8.1 Troubleshooting instructions . . . . . . . . . . . . . . . . . 55
Two single coaxial cables . . . . . . . . . . . . . . . . . . . . 27 8.2 Diagnosis code messages . . . . . . . . . . . . . . . . . . . . 56
3.10.1 Connecting Prosonic Flow W . . . . . . . . . . 27 8.2.1 Category F diagnosis code messages . . . . . 56
8.2.2 Category C diagnosis code messages . . . . 57
Endress+Hauser 3
Proline Prosonic Flow 91 Table of contents
9 Technical data . . . . . . . . . . . . . . . . . . . 66
9.1 Technical data at a glance . . . . . . . . . . . . . . . . . . . 66
9.1.1 Application . . . . . . . . . . . . . . . . . . . . . . . . 66
9.1.2 Function and system design . . . . . . . . . . . . 66
9.1.3 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
9.1.4 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
9.1.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . 67
9.1.6 Performance characteristics . . . . . . . . . . . . 70
9.1.7 Operating conditions: Installation . . . . . . . 71
9.1.8 Operating conditions: Environment . . . . . . 72
9.1.9 Operating conditions: Process . . . . . . . . . . 72
9.1.10 Mechanical construction . . . . . . . . . . . . . . 73
9.1.11 Human interface . . . . . . . . . . . . . . . . . . . . 73
9.1.12 Certificates and approvals . . . . . . . . . . . . . 74
9.1.13 Ordering information . . . . . . . . . . . . . . . . . 74
9.1.14 Accessories . . . . . . . . . . . . . . . . . . . . . . . . 74
9.1.15 Documentation . . . . . . . . . . . . . . . . . . . . . 74
4 Endress+Hauser
Proline Prosonic Flow 91 Safety instructions
1 Safety instructions
Endress+Hauser 5
Safety instructions Proline Prosonic Flow 91
1.4 Return
The following procedures must be carried out before a flowmeter requiring repair or calibration, for
example, is returned to Endress+Hauser:
• Always enclose a duly completed "Declaration of Contamination" form. Only then can
Endress+Hauser transport, examine and repair a returned device.
! Note!
You will find a preprinted "Declaration of Contamination" form at the back of this manual.
• Enclose special handling instructions if necessary, for example a safety data sheet as per
Regulation (EC) No 1907/2006 REACH.
• Remove all residues. Pay special attention to the grooves for seals and crevices which could
contain residues. This is particularly important if the substance is hazardous to health, e.g.
flammable, toxic, caustic, carcinogenic, etc.
# Warning!
• Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused
through plastic.
• Costs incurred for waste disposal or injury (burns, etc.) due to inadequate cleaning will be charged
to the owner-operator.
# Warning!
"Warning" indicates an action or procedure which, if not performed correctly, can result in personal
injury or a safety hazard. Comply strictly with the instructions and proceed with care.
" Caution!
"Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect
operation or destruction of the device. Comply strictly with the instructions.
! Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.
6 Endress+Hauser
Proline Prosonic Flow 91 Identification
2 Identification
Prosonic Flow 91
Order Code: XXXXX-XXXXXXXXXXXX IP67 / NEMA/Type4X 5
1 Ser.No.: 12345678901
TAG No.: ABCDEFGHJKLMNPQRST
85-250VAC
2 50-60Hz 12VA
-25°C(-13°F)<Tamb>+60°C(+140°F) 6
i 7
4
N12895
a0005873
Fig. 1: Nameplate specifications for the "Prosonic Flow 91" transmitter (example)
1 Order code /serial number: see the specifications on the order confirmation for the meanings of the individual
letters and digits
2 Power supply, frequency, power consumption
3 Outputs available:
I-OUT (HART): with current output (HART)
PULSE-OUT: with pulse/status output
4 Reserved for additional information on device version (approvals, certificates)
5 Permitted ambient temperature range
6 Degree of protection
7 Please comply with the Operating Instructions
Endress+Hauser 7
Identification Proline Prosonic Flow 91
Prosonic Flow W
Order Code: XXXXX-XXXXXXXXXXXX
1 i 6
Ser.No.: 12345678901 RY
2 Type:W-CL-1F-M-B CH 1
3 DN100 - DN4000
4 0°C(+32°F)…+130°C(+266°F)
5
OPEN CLOSE
6
IP68
7 NEMA
Warning: To maintain
Type/NEMA X or IP
ENDRESS+HAUSER
68700 Cernay France
8 Tamb/Tumg:-20°…+60°C
a0005874
Fig. 2: Nameplate specifications for the "Prosonic Flow W" sensors (example)
1 Ordering code/serial number: See the specifications on the order confirmation for the meanings of the
individual letters and digits.
2 Sensor type
3 Recommended operating range for sensor type
4 Fluid temperature range
5 Reserved for information on special products
6 Please comply with the Operating Instructions
7 Reserved for additional information on device version (approvals, certificates)
8 Degree of protection
9 Permitted ambient temperature range
319740-0000
$
24 25 26 27 1 2
+ – + – L1 (L+) N (L–)
RLmax. = 700 Ohm
Active: 4...20 mA
I-OUT (HART)
d’Alimentation
fmax: 100 Hz
PULSE-OUT
Versorgung /
Supply /
250 mA
Tension
HART
a0005394
8 Endress+Hauser
Proline Prosonic Flow 91 Identification
Endress+Hauser 9
Installation Proline Prosonic Flow 91
3 Installation
3.1.2 Transport
The devices must be transported in the container supplied when transporting them to the measuring
point.
3.1.3 Storage
Note the following points:
• Pack the measuring device in such a way as to protect it reliably against impact for storage
(and transportation).
The original packaging provides optimum protection.
• The storage temperature corresponds to the ambient temperature range of the transmitter, the
measuring sensors and the corresponding sensor cables ä 72.
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
10 Endress+Hauser
Proline Prosonic Flow 91 Installation
a0001103
Endress+Hauser 11
Installation Proline Prosonic Flow 91
3.2.3 Orientation
Vertical orientation
Recommended orientation with upward direction of flow (View A). Entrained solids sink down.
Gases rise away from the measuring sensor when fluid is not flowing. The piping can be completely
drained and protected against buildup.
Horizontal orientation
In the recommended installation range in a horizontal installation position (View B), gas and air
accumulation at the pipe cover and problematic buildups at the bottom of the pipe have a minor
influence on the measurement.
A C C
B
a0001105
Fig. 5: Orientation
A Vertical: Recommended installation with vertical/upward direction of flow
B Horizontal: Recommended installation range with horizontal orientation
C Recommended installation range max. 120°
³ 15 x DN ³ 3 x DN
³ 20 x DN
1
³ 20 x DN
2
3 ³ 15 x DN
A0013079
12 Endress+Hauser
Proline Prosonic Flow 91 Installation
1 2
A0005728
Recommendations
The number of traverses required depends on th sensor type, the nominal diameter and the
thickness of the pipe wall. We recommend the following types of mounting:
W-CL-1F
DN 650 to 4000 (26" to 160") 1 MHz (or 0.5 MHz) 1 traverses 2)
W-CL-05F
1) The installation of clamp-on sensors is principally recommended in the 2 traverse type installation. This type of
installation allows the easiest and most comfortable type of mounting. However, in certain applications a 1 traverse
installation may be preferred.
These include:
• Certain plastic pipes with wall thickness > 4 mm (0,16 in)
• Lined pipes
• Applications with fluids with high acoustic damping
2) 0.5 MHz sensors are also recommended for applications with composite material pipes such as GRP*) and may be
recommended for certain lined pipes, pipes with wall thickness >10 mm, or applications with media with high acoustic
damping. In addition, for these applications we principally recommend mounting the W sensors in a 1 traverse
configuration.
3)
6 MHz sensors for applications where flow velocity 10m/s (32.8Hz/s)
Endress+Hauser 13
Installation Proline Prosonic Flow 91
14 Endress+Hauser
Proline Prosonic Flow 91 Installation
Prosonic Flow For the measuring range Pipe nominal diameter Secured by
91W DN 15 to 65 (½ to 2½") DN 32 (1¼") Sensor holder with U-shaped screws
(small nominal diameters) ä 15
DN 32 (1¼") Sensor holder with strapping bands
(small nominal diameters) ä 16
91W DN 50 to 4000 DN 200 (8") Strapping bands
(2 to 160") (medium nominal diameters) ä 16
Welded bolts ä 14
DN 200 (8") Strapping bands
(large nominal diameters) ä 18
Welded bolts ä 14
Procedure
1. Disconnect the sensor from the sensor holder.
2. Position the sensor holder on the pipe.
3. Put the U-shaped screws through the sensor holder and slightly lubricate the thread.
4. Screw nuts onto the U-shaped screws.
5. Set the holder to the exact position and tighten the nuts evenly.
# Warning!
Risk of damaging plastic or glass pipes if the nuts of the U-shaped screws are tightened too
much! The use of a metal half-shell is recommended (on the opposite side of the sensor) when
working with plastic or glass pipes.
! Note!
The visible pipe surface "A" must be smooth to ensure good acustic contact.
A0011524
Fig. 8: Mounting the Prosonic Flow-sensor holder (DN 15 to 65 / ½ to 2½") with U-shaped screws
Endress+Hauser 15
Installation Proline Prosonic Flow 91
Procedure
1. Disconnect the sensor from the sensor holder.
2. Position the sensor holder on the pipe.
3. Wrap the strapping bands around the sensor holder and pipe without twisting them.
4. Guide the strapping bands through the strapping band locks (strapping screw is pushed up).
5. Tighten the strapping bands as tight as possible by hand.
6. Set the sensor holder to the correct position.
7. Push down the strapping screw and tighten the strapping bands so that they cannot slip.
8. Where necessary, shorten the strapping bands and trim the cut edges.
# Warning!
Risk of injury. To avoid sharp edges, trim the cut edges after shortening the strapping bands.
A0011525
Fig. 9: Positioning the sensor holder and mounting the strapping bands
! Note!
The visible pipe surface "A" must be smooth to ensure good acustic contact.
A0011526
16 Endress+Hauser
Proline Prosonic Flow 91 Installation
Procedure
1
2
A0001109
Fig. 11: Premounting strapping bands for pipe diameters DN 200 (8")
1 Mounting bolt
2 Strapping band
3 Strapping screw
Endress+Hauser 17
Installation Proline Prosonic Flow 91
Procedure
1. Measure the pipe circumference.
2. Shorten the strapping bands to one length (pipe circumference + 32 cm (12.6 in)) and trim the
cut edges.
# Warning!
Risk of injury. To avoid sharp edges, trim the cut edges after shortening the strapping bands.
in)
(20
mm
00
³5
3.
A0015461
Fig. 12: Premounting strapping bands for pipe diameters DN > 600 (24 ")
1 Mounting bolt with guide*
2 Strapping band*
3 Strapping screw
* Distance between mounting bolt and strapping band lock min 500 mm (20 in)
18 Endress+Hauser
Proline Prosonic Flow 91 Installation
Prerequisites
• The installation distance (sensor distance) is known ä 14.
• The sensor holder is already mounted ä 15.
Material
The following material is needed for mounting:
• Sensor incl. adapter cable
• Connecting cable for connecting to the transmitter
• Coupling fluid for an acoustic connection between the sensor and pipe
Procedure
1. Set the distance between the sensors as per the value determined for the sensor distance.
Press the sensor down slightly to move it.
A0011529
Fig. 13: Setting the distance between the sensors as per the value for the sensor distance
a Sensor distance
b Contact surfaces of the sensor
2. Coat the contact surfaces of the sensors with an even layer of coupling fluid
(approx. 0.5 to 1 mm / 0.02 to 0.04") thick.
3. Fit the sensor housing on the sensor holder.
! Note!
• Avoid to use a thick layer of the coupling fluid (less is more).
• Clean and reapply new coupling fluid when sensor is removed from the pipe.
A0011527
Endress+Hauser 19
Installation Proline Prosonic Flow 91
A0011528
20 Endress+Hauser
Proline Prosonic Flow 91 Installation
Installation for measurement via one traverse (DN 600 to 4000 /24" to 160")
Prerequisites
• The installation distances (sensor distance and wire length) are known ä 14.
• The strapping bands are already mounted ä 16.
Material
The following material is needed for mounting:
• Two strapping bands incl. mounting bolts and centering plates where necessary
(already mounted ä 16)
• Two measuring wires, each with a cable lug and a fixer to position the strapping bands
• Two sensor holders
• Coupling fluid for an acoustic connection between the sensor and pipe
• Two sensors incl. connecting cables.
Procedure
1. Prepare the two measuring wires:
– Arrange the cable lugs and fixer such that the distance they are apart corresponds to the wire
length (SL).
– Screw the fixer onto the measuring wire.
SL
1 2 3 4 5 6 7 8 9 10 11
A0001112
Fig. 16: Fixer (a) and cable lugs (b) at a distance that corresponds to the wire length (SL)
A0001113
Endress+Hauser 21
Installation Proline Prosonic Flow 91
5. Loosen the screws of the fixers on the measuring wires and remove the measuring wires from
the mounting bolt.
6. Fit the sensor holders over the individual mounting bolts and tighten securely with the
retaining nut.
A0001114
7. Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
(0.04") thick, going from the groove through the center to the opposite edge.
! Note!
• Avoid to use a thick layer of the coupling fluid (less is more).
• Clean and reapply new coupling fluid when the sensor is removed from the pipe.
• On rough pipe surface e.g. GRP pipes ensure that the gaps crevices within the surface roughness
are filled. Apply suffizienet copling fluid.
A0011373
Fig. 19: Coating the contact surfaces of the sensor with coupling fluid
22 Endress+Hauser
Proline Prosonic Flow 91 Installation
A0001115
Fig. 20: Mounting the sensor and connecting the connecting cable
This completes the mounting process. The sensors can now be connected to the transmitter via the
connecting cables ä 27.
Installation for measurement via two traverses (DN 50 to 600 /2" to 24")
Prerequisites
• The installation distance (position sensor) is known ä 14.
• The strapping bands are already mounted ä 16.
Material
The following material is needed for mounting:
• Two strapping bands incl. mounting bolts and centering plates where necessary
(already mounted ä 16)
• A mounting rail to position the strapping bands
• Two mounting rail retainers
• Two sensor holders
• Coupling fluid for an acoustic connection between the sensor and pipe
• Two sensors incl. connecting cables.
Procedure
1. Position the strapping bands with the aid of the mounting rail.
– Slide the mounting rail with the bore identified by the letter from POSITION SENSOR over
the mounting bolt of the strapping band that is permanently fixed in place.
– Position the movable strapping band and slide the mounting rail with the bore identified by
the numerical value from POSITION SENSOR over the mounting bolt.
Endress+Hauser 23
Installation Proline Prosonic Flow 91
22
G
A0001116
Fig. 21: Determining the distance in accordance with the mounting rail (e.g. POSITION SENSOR G22)
A0001117
5. Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
(0.04") thick, going from the groove through the center to the opposite edge.
! Note!
• Avoid to use a thick layer of the coupling fluid (less is more).
• Clean and reapply new coupling fluid when the sensor is removed from the pipe.
• On rough pipe surface e.g. GRP pipes ensure that the gaps crevices within the surface roughness
are filled. Apply suffizienet copling fluid.
A0011373
Fig. 23: Coating the contact surfaces of the sensor with coupling fluid
24 Endress+Hauser
Proline Prosonic Flow 91 Installation
A0011376
This completes the mounting process. The sensors can now be connected to the transmitter via the
connecting cables ä 30.
4 x 45°
A0003237
Endress+Hauser 25
Installation Proline Prosonic Flow 91
" Caution!
• The ambient temperature range (–25 to +60 °C; –13 to +140 °F) may not be exceeded at the
mounting location. Avoid direct sunlight.
• If a warm pipe is used for the installation, ensure that the housing temperature does not exceed
the max. permitted value of +60 °C (+140 °F).
Mount the transmitter as illustrated in å 26.
A B
190 (7.48) &185 (&3.34)
172.5 (6.79)
Esc Esc
- + E - + E
80
(3.15)
mm (inch)
a0005819
Installation Notes
Are the measuring point number and labeling correct (visual inspection)? -
26 Endress+Hauser
Proline Prosonic Flow 91 Installation
3.9 Wiring
! Note!
The outer shield of the sensor connecting cable (triaxial cable) is grounded by a ground disk in the
cable feedthrough (A). This grounding is absolutely essential to ensure correct measurement.
1. Unscrew the cover (c) of the cable gland (A). Remove the rubber seal (d).
2. Guide the sensor connecting cables (a, b) through the cover of the cable gland.
3. Guide the sensor connecting cables individually through the ground disk in the cable gland
holder (g) and into the connection compartment.
4. Plug in the connectors of the sensor connecting cables.
Left sensor upstream (a), right sensor downstream (b).
The connector engages with a click when correctly plugged in.
5. Spread the rubber seal (d) along side slits (e.g. using a screwdriver) and fix the cables in place
appropriately. Push up the rubber seal in the cable gland until the sensor cable sleeves are
pressed against the ground disk.
6. Close the cover of the cable gland (c) so that it is tight.
7. In the connection compartment, fix the two sensor connecting cables in place in the holder (i)
provided.
h
g
b
A f
e
a b
d
c
i
a0005843
Endress+Hauser 27
Installation Proline Prosonic Flow 91
5
7
4
1
6
40 mm
3 2
15 mm
a0015587
Procedure
! Note!
The red marked cable is sensor "up"; the blue marked cable is sensor "down".
! Note!
The cable gland can be released from the cable by unscrewing and removing tha cable gland cover.
Then retract the grounding mechanism (G) with pair of pliers. The retraction of the mechanism does
not require strong force (strong force might destroy the screen). It might be required to lift the
internal hooks of the grounding mechanism out of a locked position by pressing the grounding
mechanism further forward by turning the cable gland clockwise. Remove the cable gland cover
again. Then retry to retract with the pair of pliers.
28 Endress+Hauser
Proline Prosonic Flow 91 Installation
DOWN
Check
T-DAT
Field-
UP
a0005875
Endress+Hauser 29
Installation Proline Prosonic Flow 91
3.11.1 Transmitter
# Warning!
• Risk of electric shock.
Switch off the power supply before opening the device. Do not install or wire the device while it
is connected to the power supply. Failure to comply with this precaution can result in irreparable
damage to the electronics.
• Risk of electric shock.
Connect the protective earth to the ground connection on the housing before the power supply
is applied.
• Compare the specifications on the nameplate with the local supply voltage and frequency.
The national regulations governing the installation of electrical equipment also apply.
• The transmitter must be included in the general circuit protection system.
1. Unscrew cover of the electronics compartment from the transmitter housing.
2. Press the side latches and flip down the cover of the connection compartment.
3. Feed the cable for the power supply and the signal cable through the appropriate cable entries.
4. Remove the terminal connectors from the transmitter housing and connect the cable for the
power supply and the signal cable:
– Wiring diagram å 30
– Terminal assignment ä 31
5. Plug the terminal connectors back into the transmitter housing.
! Note!
The connectors are coded so you cannot mix them up.
6. Secure the ground cable to the ground terminal.
7. Flip up the cover of the connection compartment.
8. Screw the cover of the electronics compartment firmly onto the transmitter housing.
e b
e b e b
f c
a
g d
i
24 25 26 27 1 2
h + – + – L1 N
(L+) (L-)
a0005838
30 Endress+Hauser
Proline Prosonic Flow 91 Installation
! Note!
Functional values of the outputs and power supply ä 67
³ 250 W – 27
+26
2
4
3
1
a0005573
2 ³ 250 W –27
1 +26
3
RS 232 4
a0005574
Endress+Hauser 31
Installation Proline Prosonic Flow 91
a0001138
Fig. 33: Installation instructions for cable entries on the transmitter housing
1
a0001139
Fig. 34: Installation instructions for IP 67/68 degree of protection for sensor connectors
32 Endress+Hauser
Proline Prosonic Flow 91 Installation
Does the supply voltage match the specifications on the nameplate? • 85 to 250 V AC (50 to 60 Hz)
• 20 to 28 V AC (50 to 60 Hz),
10 to 40 V DC
Are the power supply and signal cables correctly connected? See the wiring diagram inside
the cover of the terminal
compartment
Are all cable entries installed, firmly tightened and correctly sealed? ä 32
Endress+Hauser 33
Operation Proline Prosonic Flow 91
4 Operation
1
+48.25 xx/yy
+3702.6 x
Esc
- + E
2 3
a0001141
34 Endress+Hauser
Proline Prosonic Flow 91 Operation
Esc
- + E
p
Esc Esc >3s
m E – + – +
o
E E E E E
Esc
– +
n +
–
A0001142
Endress+Hauser 35
Operation Proline Prosonic Flow 91
! Note!
• The transmitter continues to measure while data entry is in progress, i.e. the current measured
values are output via the signal outputs in the normal way.
• If the power supply fails all preset and configured values remain safely stored in the EEPROM.
" Caution!
Changing certain sensor specific parameters may influence characteristics of numerous functions of
the entire measuring device, particularly measuring accuracy.
This type of parameters may not be changed! Please contact Endress+Hauser if you have any
questions.
36 Endress+Hauser
Proline Prosonic Flow 91 Operation
4.3 Communication
In addition to local operation, the measuring device can also be configured and measured values
obtained by means of the HART protocol. Digital communication takes place using the 4–20 mA
current output HART ä 31.
The HART protocol allows the transfer of measuring and device data between the HART master and
the field devices for configuration and diagnostics purposes.
The HART masters, e.g. a handheld terminal or PC-based operating programs (such as FieldCare),
require device description (DD) files which are used to access all the information in a HART device.
Information is exclusively transferred using so-called "commands". There are three different
command groups:
• Universal commands:
All HART devices support and use universal commands.
The following functionalities are linked to them:
– Recognizing HART devices
– Reading digital measured values (volume flow, totalizer, etc.)
• Common practice commands:
Common practice commands offer functions which are supported and can be executed by most
but not all field devices.
• Device-specific commands:
These commands allow access to device-specific functions which are not HART standard. Such
commands access individual field device information, (among other things), such as empty-pipe/
full-pipe adjustment values, low flow settings etc.
! Note!
The measuring device has access to all three command classes. A list of all the "Universal
commands" and "Common Practice Commands" can be found on ä 39.
! Note!
In the CURRENT SPAN function, the HART protocol demands the setting "4 to 20 mA HART" or
"4-20 mA (25 mA) HART".
HART write protection can be disabled or enabled by means of a jumper on the I/O board.
Endress+Hauser 37
Operation Proline Prosonic Flow 91
Handheld terminal Field Xpert SFX100 Use update function of handheld terminal
Fieldcheck Update via FieldCare using the Flow Device FXA193/291 DTM in the
Fieldflash module
! Note!
The Fieldcheck tester/simulator is used for testing flowmeters in the field. When used in
conjunction with the "FieldCare" software package, test results can be imported into a database,
printed and used for official certification. Contact your Endress+Hauser representative for more
information.
30 Volume flow
250 Totalizer 1
Process variables:
At the factory, the process variables are assigned to the following device variables:
• Primary process variable (PV) Volume flow
• Second process variable (SV) Totalizer
38 Endress+Hauser
Proline Prosonic Flow 91 Operation
Universal Commands
0 Read unique device identifier none Device identification delivers information on the device
Access type = Read and the manufacturer. It cannot be changed.
The response consists of a 12-byte device ID:
– Byte 0: fixed value 254
– Byte 1: manufacturer ID, 17 = E+H
– Byte 2: device type ID, 98 = Prosonic Flow 91
– Byte 3: number of preambles
– Byte 4: universal commands rev. no.
– Byte 5: device-specific commands rev. no.
– Byte 6: software revision
– Byte 7: hardware revision
– Byte 8: additional device information
– Byte 9-11: device identification
1 Read primary process variable none – Byte 0: HART unit code of the primary process
Access type = Read variable
– Bytes 1-4: primary process variable
Factory setting: primary process variable = Volume flow
! Note!
• You can set or change the assignment of device
variables to process variables using Command 51.
• Manufacturer-specific units are represented using
the HART unit code "240".
2 Read the primary process variable none – Byte 0-3: current current of the primary process
as current in mA and percentage variable in mA
of the set measuring range – Byte 4-7: %- value of the set measuring range
Access type = Read
Factory setting: primary process variable = Volume flow
! Note!
You can set or change the assignment of device
variables to process variables using Command 51.
3 Read the primary process variable none 24 bytes are sent as a response:
as current in mA and four (preset – Bytes 0-3: primary process variable current in mA
using Command 51) dynamic – Byte 4: HART unit code of the primary process
process variables variable
Access type = Read – Bytes 5-8: primary process variable
– Byte 9: HART unit code of the secondary process
variable
– Bytes 10-13: second process variable
– Byte 14: HART unit code of the third process
variable
– Bytes 15-18: third process variable
– Byte 19: HART unit code of the fourth process
variable
– Bytes 20-23: fourth process variable
Factory setting:
• Primary process variable = Volume flow
• Secondary process variable = Totalizer
• Third process variable = Sound velocity
• Fourth process variable = Flow velocity
! Note!
• Manufacturer-specific units are represented using
the HART unit code "240".
Endress+Hauser 39
Operation Proline Prosonic Flow 91
6 Set HART shortform address Byte 0: desired address (0 to 15) Byte 0: active address
Access type = Write Factory setting: 0
! Note!
With an address > 0 (multidrop mode), the current
output of the primary process variable is set to 4 mA.
11 Read unique device identification Bytes 0-5: TAG Device identification delivers information on the device
using the TAG (measuring point and the manufacturer. It cannot be changed.
designation)
The response consists of a 12-byte device ID if the
Access type = Read given TAG agrees with the one saved in the device:
– Byte 0: fixed value 254
– Byte 1: manufacturer ID, 17 = E+H
– Byte 2: device type ID, 98 = Prosonic Flow 91
– Byte 3: number of preambles
– Byte 4: universal commands rev. no.
– Byte 5: device-specific commands rev. no.
– Byte 6: software revision
– Byte 7: hardware revision
– Byte 8: additional device information
– Byte 9-11: device identification
! Note!
You can write the TAG, TAG descriptor and date using
Command 18.
! Note!
• The data relate to the primary process variable
(= volume flow).
• Manufacturer-specific units are represented using
the HART unit code "240".
40 Endress+Hauser
Proline Prosonic Flow 91 Operation
! Note!
• Manufacturer-specific units are represented using
the HART unit code "240".
17 Write user message Any 32-character long text can be saved in the device Displays the current user message in the device:
Access = Write under this parameter: Bytes 0-23: current user message in the device
Bytes 0-23: desired user message
18 Write TAG, TAG descriptor and With this parameter, you can store an 8-character Displays the current information in the device:
date TAG, a 16-character TAG description and a date: – Bytes 0-5: TAG
Access = Write – Bytes 0-5: TAG – Byte 6-17: TAG description
– Byte 6-17: TAG description – Bytes 18-20: date
– Bytes 18-20: date
19 Write the device production Bytes 0-2: production number Bytes 0-2: production number
number
Access = Write
Endress+Hauser 41
Operation Proline Prosonic Flow 91
The following table contains all the common practice commands supported by the
device.
34 Write damping value for primary Byte 0-3: damping value of the primary process Displays the current attenuation constant in the
process variable variable in seconds device:
Access = Write Factory setting: Bytes 0-3: attenuation constant in seconds
Primary process variable = Volume flow
35 Write measuring range of primary Write the desired measuring range: The currently set measuring range is shown as the
process variable – Byte 0: HART unit code for the primary process response:
Access = Write variable – Byte 0: HART unit code for the set measuring range
– Byte 1-4: end of measuring range, value for 20 mA of the primary process variable
– Bytes 5-8: start of measuring range, value for 4 mA – Byte 1-4: end of measuring range, value for 20 mA
– Bytes 5-8: start of measuring range, value for 4 mA
Factory setting:
Primary process variable = Volume flow ! Note!
! Note!
• If the HART unit code is not the correct one for the
Manufacturer-specific units are represented using the
HART unit code "240".
process variable, the device will continue with the
last valid unit.
40 Simulate output current of Simulation of the desired output current of the primary The momentary output current of the primary process
primary process variable process variable. An entry value of 0 exits the variable is displayed as a response:
Access = Write simulation mode: Byte 0-3: output current in mA
Byte 0-3: output current in mA
Factory setting:
Primary process variable = Volume flow
44 Write unit of primary process Specify the unit of the primary process variable. Only The current unit code of the primary process variable
variable units which are suitable for the process variable are is displayed as a response:
Access = Write accepted by the device: Byte 0: HART unit code
Byte 0: HART unit code
Factory setting:
! Note!
Manufacturer-specific units are represented using the
Primary process variable = Volume flow HART unit code "240".
! Note!
• If the written HART unit code is not the correct one
for the process variable, the device will continue
with the last valid unit.
• A change of the unit of the primary process variable
has a direct impact on the system units.
48 Read extended device status none The current device status is displayed in extended
Access = Read form as the response:
Encoding: see Table ä 44.
42 Endress+Hauser
Proline Prosonic Flow 91 Operation
50 Read assignment of the device none Display of the current variable assignment of the
variables to the four process process variables:
variables – Byte 0: device variable code for the primary
Access = Read process variable
– Byte 1: device variable code for the second
process variable
– Byte 2: device variable code for the third
process variable
– Byte 3: device variable code for the fourth
process variable
Factory setting:
• Primary process variable: code 30 for
volume flow
• Secondary process variable: code 250 for
totalizer
• Third process variable: code 40 for sound
velocity
• Fourth process variable: code 49 for flow
velocity
53 Write device variable unit This command sets the unit of the given device The current unit of the device variables is displayed in
Access = Write variables. Only those units which suit the device the device as a response:
variable are transferred: – Byte 0: device variable code
– Byte 0: device variable code – Byte 1: HART unit code
– Byte 1: HART unit code
Code of the supported device variables:
! Note!
Manufacturer-specific units are represented using the
See data ä 38 HART unit code "240".
! Note!
• If the written unit is not the correct one for the
device variable, the device will continue with the
last valid unit.
• A change of the unit of the primary process variable
has a direct impact on the system units.
59 Set number of preambles in This parameter sets the number of preambles which As a response, the current number of the preambles is
message responses are inserted in the message responses: displayed in the response message:
Access = Write Byte 0: number of preambles (2 to 20) Byte 0: number of preambles
Endress+Hauser 43
Operation Proline Prosonic Flow 91
! Note!
• For detailed information on the device status/diagnosis messages and how they are rectified
ä 56
• Bits and bytes not listed are not assigned.
5 C - 281 Initialization
4 C - 411 Upload/download
0
3 F - 001 Device fault
2 F - 282 Data storage
5 C - 431 Calibration
2 - -
3 - -
3
4 - -
5 - -
6 - -
7 - -
44 Endress+Hauser
Proline Prosonic Flow 91 Commissioning
5 Commissioning
PROSONIC FLOW 91
Startup message
STARTING. . .
DEVICE SOFTWARE
Current software is displayed (example)
V X.XX.XX
SYSTEM OK
Beginning of standard measuring mode
OPERATION
Normal measuring mode commences as soon as startup completes. Various measured value and/or
status variables appear on the display (HOME position).
! Note!
If startup fails, an error message indicating the cause is displayed.
Endress+Hauser 45
Commissioning Proline Prosonic Flow 91
For sensor installation with the configuration program "FieldCare" any "Quick Setup" menus which
correspond to the local operation exist.
Other methods (see table) are available for determining the relevant values for sensor distance, wire
length, etc. The procedure is illustrated in detail on ä 46.
Sensor type Required values for the sensor Local display FieldCare Applicator
installation procedure
clamp-on Position sensor x x x
version
Wire length x x x
Sensor distance x x x
1)Conditions that must be met before determining the values via the local display using the "Sensor" Sensor Setup
( ä 78):
• Transmitter installed ( ä 30)
• Transmitter connected to power supply ( ä 30)
2)
FieldCare is a configuration software package for flowmeters in the field. Conditions that must be met before
determining the values via "FieldCare":
• Transmitter installed ( ä 30)
• Transmitter connected to power supply ( ä 30)
• "FieldCare" configuration package installed on a notebook/PC
• Connection made between notebook/PC and device via the FXA291 service interface ( ä 30)
3)
Applicator is software for selecting and configuring flowmeters. The values required can be determined without having
to connect the transmitter beforehand.
The "Applicator" can be downloaded from the Internet ( www.applicator.com) or ordered on
CD-ROM for installation on a local PC.
! Note!
Enter a valid release code to allow that device parameters can be changed or activated. The code
(factory setting = 91) is entered by means of the corresponding matrix cell.
"Clamp-on" sensor installation
46 Endress+Hauser
Proline Prosonic Flow 91 Commissioning
! Note!
A detailed description of all the functions can be found on ä 75
5.3.2 Commissioning
Additionally to the settings for the sensor installation ( ä 46) the following functions have to be
configured for the standard application:
• System units
• Outputs
Endress+Hauser 47
Commissioning Proline Prosonic Flow 91
! Hinweis!
For information on installing and removing the T-DAT ä 61
F O
XXX.XXX.XX
Quick Setup
Esc
- + E
HOME N
POSITION
T-DAT
SAVE/LOAD
LOAD P SAVE
P CANCEL
F F
YES
P NO YES
P NO
F F F F
Restart of the Input is
measuring device saved
a0001221-en
! Hinweis!
• Any settings already saved on the EEPROM are deleted.
• This option is only available, if the T-DAT contains valid data.
• This option can only be executed if the software version of the T-DAT is the same or newer than
that of the EEPROM. Otherwise, the error message "TRANSM. SW-DAT" appears after restarting
and the LOAD function is then no longer available.
SAVE:
Data are transferred from the EEPROM to the T-DAT
48 Endress+Hauser
Proline Prosonic Flow 91 Commissioning
" Caution!
• If the fluid is very difficult to measure (e.g. containing entrained solids or gas) it may prove
impossible to obtain a stable zero point despite repeated zero point adjustments. In instances of
this nature, please contact your Endress+Hauser service center.
• You can view the currently valid zero point value using the "ZERO POINT" function ( ä 104).
Esc
- + E
a0005820
Endress+Hauser 49
Commissioning Proline Prosonic Flow 91
5. Using the local display, select the "ZERO POINT ADJUSTMENT" function in the function
matrix:
HOME F R PROCESS PARAMETER
PROCESS PARAMETER F R ZERO POINT ADJ.
6. When you press OS you are automatically prompted to enter the code if the function matrix is
still disabled. Enter the code.
7. Use OS to select START and press F to confirm.
Select YES at the prompt and press F again to confirm. Zero point adjustment now starts.
– The message "ZEROPOINT ADJUST RUNNING" appears on the display for 30 to 60 seconds
while adjustment is in progress.
– If the fluid velocity in the pipe exceeds 0.1 m/s, the following error message appears on the
display: ZERO ADJUST NOT POSSIBLE.
– When the zero point adjustment is completed, the "ZERO ADJUST." function reappears on
the display.
8. Back to the HOME position
– Press and hold down Esc key (X) for more than 3 seconds
– Repeatedly press and release the Esc key (X).
50 Endress+Hauser
Proline Prosonic Flow 91 Maintenance
6 Maintenance
No special maintenance work is required.
! Note!
If too much coupling fluid is applied, signal transmission is reduced by up to 10 dB.
a0005750
! Note!
• Avoid to use a thick layer of the coupling fluid (less is more).
• Clean and reapply new coupling fluid when sensor is removed from the pipe.
• On rough pipe surfaces e.g. GRP pipes ensure that the gaps are filled. Apply suffizienet copling
fluid.
• A change in the signal strength might indicate a dotorration of the coupling fluid. No action is
required as long as the signal strength is higher than 50 dB.
Endress+Hauser 51
Accessories Proline Prosonic Flow 91
7 Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor. Your Endress+Hauser service organization can provide detailed
information on the order code in question.
Sensor W DN 15 to 65, –20 to +80 °C (½" to 2½ ", –4 to +176 °F), 5.0 MHz
(DN 15 to 65, (½" to 2½") • IP 67 / NEMA 4X DK9WS - 1*
Clamp-on version • IP 68 / NEMA 6P DK9WS - 3*
DN 15 to 65, 0 to +55 °C (½" to 2½ ", 32 to +212 °F), 5.0 MHz
DK9WS - 2*
• IP 67 / NEMA 4X
• IP 68 / NEMA 6P DK9WS - 4*
DN 100 to 4000, 0 to +130 °C (4" to 160", +32 to +266 °F), 1.0 MHz
• IP 67 / NEMA 4X DK9WS - P*
DN 100 to 4000, 0 to +130 °C (4" to 160", +32 to +266 °F) 0.5 MHz
• IP 67 / NEMA 4X DK9WS - R*
• IP 68 / NEMA 6P DK9WS - T*
52 Endress+Hauser
Proline Prosonic Flow 91 Accessories
Fieldgate FXA520 Gateway for remote interrogation of HART sensors and actuators FXA520 – ****
via Web browser:
• Web server for remote monitoring of up to 30 measuring points
• Intrinsically safe version [EEx ia]IIC for applications in hazardous
areas
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in Web browser and/or WAP
cellular phone
• Limit value monitoring with alarm by e-mail or SMS
• Synchronized time stamping of all measured values
• Remote diagnosis and remote configuration of connected HART
devices
Endress+Hauser 53
Accessories Proline Prosonic Flow 91
54 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
8 Troubleshooting
Endress+Hauser 55
Troubleshooting Proline Prosonic Flow 91
56 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
message.
C 461 Current adjustment is active. End current adjustment. Alarm
Signal output (–)
C 481 The measuring device is being checked – Notice
Diagnosis active on site via the test and simulation device. (–)
C 482 Simulation current output active Switch off simulation Notice
Simulation outp. (–)
Simulation frequency output active
Endress+Hauser 57
Troubleshooting Proline Prosonic Flow 91
"A changeCaution!
of the sensor configuration is
required if the measuring device
indicates zero or low flow.
S 461 Current output: – Change the upper or lower limit setting, as applicable. Notice
Signal output The current flow is outside the set range. – Increase or reduce flow, as applicable. (–)
Pulse output: 1. Increase the setting for pulse weighting.
Pulse output frequency is out of range.
2. When entering the pulse width, select a value that can still be
processed by an external totalizer (e.g. mechanical totalizer,
PLC, etc.).
Example:
The maximum input frequency of the connected totalizer is
10 Hz. The pulse width to be entered is:
1 - = 50 ms
---------------------
2 10 Hz
3. Reduce flow
58 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
! Note!
You may have to change or correct settings in certain functions in the matrix in order to rectify faults.
Measured value reading fluctuates 1. Check the fluid for presence of gas bubbles.
even though flow is steady.
2. "TIME CONSTANT" function (current output) Increase value
3. "FLOW DAMPING" function (system parameter) Increase value
There are differences between the This symptom is due primarily to backflow in the piping, because the pulse output cannot subtract in the "STANDARD or
flowmeter's internal totalizer and the SYMMETRY" measuring modes.
external metering device.
Measured value reading shown on 1. Check the fluid for presence of gas bubbles.
display, even though the fluid is at a 2. Activate the "ON-VALUE LOW FLOW CUT OFF" function, i.e. enter or increase the value for the switching point.
standstill and the measuring tube is
full.
The current output signal is always 1. Set the "FIELDBUS ADDRESS" function to "0".
4 mA, irrespective of the flow signal at
2. Low flow too high. Reduce value in the "ON-VALUE LOW FLOW CUT OFF" function.
any given time.
The fault cannot be rectified or some The following options are available for tackling problems of this nature:
other fault not described above has
Request the services of an Endress+Hauser service technician
occurred. If you contact our service organization to have a service technician sent out, please be ready with the following
information:
In these instances, please contact your
– Brief description of the fault
Endress+Hauser service organization. – Nameplate specifications ( ä 7): ordering code and serial number
Returning devices to Endress+Hauser
The necessary procedures must be carried out before you return a flowmeter requiring repair or calibration to
Endress+Hauser ( ä 65).
In all cases, enclose a fully completed "Declaration of contamination" form with the flowmeter. A copy of the "Dangerous
Goods Sheet" can be found at the end of these Operating Instructions.
Replace transmitter electronics
Components in the electronics defective Order spare part ä 61.
Endress+Hauser 59
Troubleshooting Proline Prosonic Flow 91
MAXIMUM VALUE
4–20 mA (25 mA) 25mA
4–20 mA NAMUR 22.6 mA
4–20 mA US 22.6 mA
4–20 mA (25 mA) HART 25 mA
4–20 mA HART NAMUR 22.6 mA
4–20 mA HART US 22.6 mA
ACTUAL VALUE
Fault is ignored, i.e. standard measured value output on the basis of ongoing flow
measurement (not recommended).
Pulse output MINIMUM/MAXIMUM VALUE FALLBACK VALUE Output signal corresponds to "zero flow"
Signal output No pulses
ACTUAL VALUE
Fault is ignored, i.e. standard measured value output on the basis of ongoing flow
measurement.
Status output In the event of fault or power supply failure: status output Non-conductive No effect on status output
60 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
Troubleshooting can entail replacing defective components with tested spare parts. The illustration
below shows the available scope of spare parts.
! Note!
You can order spare parts directly from your Endress+Hauser service organization by quoting the
serial number printed on the transmitter nameplate ä 7.
1. Choose the Endress+Hauser Device Viewer via web browser:
www.endress.com/deviceviewer
2. Enter the serial number of the device into the W@M Device Viewer.
3. The list of the available spare parts for the device is displayed.
Es
c
a0005821
Endress+Hauser 61
Troubleshooting Proline Prosonic Flow 91
# Warning!
• Risk of electric shock.
Exposed components carry dangerous voltages. Make sure that the power supply is switched off
before you remove the cover of the electronics compartment.
• Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface,
purpose-built for electrostatically sensitive devices!
• If the dielectric strength of the device cannot be guaranteed maintained in the following steps,
then an appropriate inspection must be carried out in accordance with the manufacturer’s
specifications.
" Caution!
Use only genuine Endress+Hauser parts.
62 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
Es
c
b
a
2
c
d
e
f
3
g
h
4 i
k
a0005831
Endress+Hauser 63
Troubleshooting Proline Prosonic Flow 91
" Caution!
Use only genuine Endress+Hauser parts.
a0005832
64 Endress+Hauser
Proline Prosonic Flow 91 Troubleshooting
8.8 Return
" Caution!
Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused through
plastic.
Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be charged
to the owner-operator.
The following steps must be taken before returning a flow measuring device to Endress+Hauser,
e.g. for repair or calibration:
• Always enclose a duly completed "Declaration of contamination" form. Only then can
Endress+Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per
EC REACH Regulation No. 1907/2006.
• Remove all residues. Pay special attention to the grooves for seals and crevices which could
contain residues. This is particularly important if the substance is hazardous to health, e.g.
flammable, toxic, caustic, carcinogenic, etc.
! Note!
You will find a preprinted "Declaration of contamination" form at the back of these Operating
Instructions.
8.9 Disposal
Observe the regulations applicable in your country!
! Note!
An upload or download between the individual software versions is only possible with a special
service software.
Endress+Hauser 65
Technical data Proline Prosonic Flow 91
9 Technical data
9.1.1 Application
Measuring principle Prosonic Flow operates on the principle of transit time difference.
9.1.3 Input
66 Endress+Hauser
Proline Prosonic Flow 91 Technical data
9.1.4 Output
Signal on alarm • Current output, pulse output Failsafe mode can be selected ä 109
• Status output "Not conductive" in the event of fault or power supply failure
Low flow cut off Low flow cut off Switch-on point can be selected as required
Galvanic isolation All circuits for inputs, outputs and power supply are galvanically isolated from each other.
Endress+Hauser 67
Technical data Proline Prosonic Flow 91
a0016008
Fig. 43: Cable gland for one multicore connecting cable (1 ר 8 mm / 0.31 in) per cable entry
A0008152
Fig. 44: Cable gland for two connecting cables (2 × Ø 4 mm / 0.16 in) per cable entry
68 Endress+Hauser
Proline Prosonic Flow 91 Technical data
Prosonic Flow
• Cable material:
– Prosonic Flow 91W (DN 50 to 4000 / 2 to 160"): PVC (standard) or
– Prosonic Flow 91W (DN 15 to 65 / ½ to 2½"): TPE-V
• Cable length:
– For use in a non-hazardous zone: 5 to 60 m (16.4 to 196.8 ft)
– For use in a hazardous zone: 5 to 30 m (16.4 to 98.4 ft)
! Note!
To ensure correct measuring results, route the connecting cable well clear of electrical machines
and switching elements.
Endress+Hauser 69
Technical data Proline Prosonic Flow 91
%
3.5
c
2.0
0.5
a
0 2 4 6 8 10 12 m/s
A0011347
Fig. 45: Example of the measured error in a pipe with a nominal diameter DN > 200
a Measured error of the device (0.5 % o.r. ± 3 mm/s)
b Measured error due to installation conditions (typically 1.5 % o.r.)
c Measured error at the measuring point: 0.5 % o.r. ± 3 mm/s + 1.5 % o.r. = 2 % o.r. ± 3 mm/s
o.r. = of reading
70 Endress+Hauser
Proline Prosonic Flow 91 Technical data
Measurement Report
If required, the device can be supplied with a measurement report. To certify the performance of
the device, a measurement is performed under reference conditions. Here, the sensors are mounted
on a pipe with a nominal diameter of DN 15 (½"), DN 25 (1"), DN 40 (1½"), DN 50 (2") or
DN 100 (4") respectively.
The measurement report guarantees the following error limits of the device
[at a flow velocity > 0.3 m/s (1 ft/s) and a Reynolds number > 10000]:
o.r. = of reading
Repeatability Max. ± 0.3% for flow velocities > 0.3 m/s (0.98 ft/s)
Length of connecting cable Shielded cables are offered in the following lengths:
5 m, 10 m, 15 m, 30 m
60 m only available for sensors DN50...4000
15 feet, 30 feet, 45 feet, 90 feet
180 feet only available for sensors DN 2" to 160"
Route the cable well clear of electrical machines and switching elements.
Endress+Hauser 71
Technical data Proline Prosonic Flow 91
Sensor
–20 to +80 °C (–4 to +176 °F)
Optional: 0 to +130 °C (–32 to +265 °F)
It is permitted to insulate the sensors mounted on the pipe.
! Note!
• It is permitted to insulate the sensors mounted on the pipes.
• Mount the transmitter in a shady location and avoid direct sunlight, particularly in warm climatic
regions.
Storage temperature The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors and the corresponding sensor cable (see above).
Sensors
IP 67 (NEMA 4X)
Optional: IP 68 (NEMA 6P)
Medium pressure range Perfect measurement requires that the static fluid pressure is higher than vapor pressure, to avoid
(nominal pressure) outgasing.
72 Endress+Hauser
Proline Prosonic Flow 91 Technical data
Design, dimensions The dimensions and lengths of the sensor and transmitter can be found in the "Technical
Information" document for the device in question. This can be downloaded as a PDF file from
www.endress.com. A list of the "Technical Information" documents available is provided in Section
"Documentation" on ä 74.
Materials Transmitter
Wall-mounted housing: powder-coated die-cast aluminum
Sensor
Prosonic Flow W clamp-on version
• Sensor holder: stainless steel 1.4308/CF-8
• Sensor housing: stainless steel 1.4301/304
• Strapping bands/bracket: stainless steel 1.4301/304
• Sensor contact surfaces: chemically stable plastic
Display elements • Liquid crystal display: illuminated, two lines with 16 characters per line
• Custom configurations for presenting different measured value and status variables
• 1 totalizer
Endress+Hauser 73
Technical data Proline Prosonic Flow 91
Ex approval Information about currently available Ex versions (FM, CSA) can be supplied by your
Endress+Hauser Sales Center on request. All explosion protection data are given in a separate
documentation which is available upon request.
CE mark The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
C-tick mark The measuring system meets the EMC requirements of the Australian Communication and Media
Authority (ACMA).
9.1.14 Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor ä 52.
Your Endress+Hauser service organization can provide detailed information on the order codes in
question.
9.1.15 Documentation
• Flow Measurement (FA005D/06)
• Technical Information Prosonic Flow 91W (TI105D/06)
• Supplementary documentation on Ex-ratings: ATEX, FM, CSA
74 Endress+Hauser
▼
Function groups Functions
MEASURING VALUES VOLUME FLOW SOUND VELOCITY FLOW VELOCITY SIGNAL STRENGTH
▼
( ä 77) ( ä 77) ( ä 77) ( ä 77) ( ä 77)
Endress+Hauser
SENSOR SETUP SETUP
▼
( ä 78) ( ä 78)
Proline Prosonic Flow 91
SYSTEM UNITS UNIT VOLUME FLOW UNIT VOLUME UNIT TEMPERATURE UNIT VELOCITY UNIT VISCOSITY UNIT LENGTH
▼
( ä 79) ( ä 79) ( ä 79) ( ä 80) ( ä 80) ( ä 80) ( ä 80)
▼
( ä 81) ( ä 81) ( ä 81) ( ä 81) ( ä 82)
10
10.1
▼
( ä 83) ( ä 83) ( ä 83) ( ä 83)
▼
( ä 84) ( ä 84) ( ä 84) ( ä 84)
▼
( ä 85) ( ä 85) ( ä 86) ( ä 86)
PULSE/STAT. OUT. OPERATION MODE PULSE VALUE PULSE WIDTH OUTPUT SIGNAL ASSIGN STATUS SWITCH-ON POINT
▼
( ä 87) ( ä 87) ( ä 87) ( ä 87) ( ä 88) ( ä 88) ( ä 88)
SWITCH-OFF POINT
( ä 89)
COMMUNICATION TAG NAME TAG DESCRIPTION FIELDBUS ADDRESS WRITE PROTECT MANUFACTURER ID DEVICE ID
▼
( ä 92) ( ä 92) ( ä 92) ( ä 92) ( ä 92) ( ä 92) ( ä 92)
▼
( ä 93) ( ä 93) MENT ( ä 94) ( ä 94)
Illustration of the function matrix
PIPE DATA PIPE MATERIAL SOUND VEL.PIPE CIRCUMFERENCE PIPE DIAMETER WALL THICKNESS
▼
( ä 95) ( ä 95) ( ä 95) ( ä 95) ( ä 96) ( ä 97)
Description of device functions
▼
( ä 98) ( ä 98) ( ä 98) ( ä 98)
LIQUID DATA LIQUID TEMPERATURE SOUND VELOCITY VISCOSITY SOUND VEL. NEG. SOUND VEL. POS.
▼
( ä 99) ( ä 99) ( ä 99) LIQUID ( ä 100) ( ä 100) ( ä 100) ( ä 101)
75
Description of device functions
76
▼
Function groups Functions
CONFIG. CHANNEL SENSOR TYPE SENSOR CONFIG. CABLE LENGTH POS.SENSOR WIRE LENGTH SENSOR DISTANCE
▼
( ä 102) ( ä 102) ( ä 102) ( ä 102) ( ä 103) ( ä 103) ( ä 103)
CALIBRATION DATA CAL. FACTOR ZERO POINT ZEROPOINT STAT. CORR. FACTOR
▼
( ä 104) ( ä 104) ( ä 104) ( ä 104) ( ä 104)
SYSTEM PARAMETER INSTL. DIR. SENSOR MEASURING MODE POS. ZERO RETURN FLOW DAMPING
▼
( ä 105) ( ä 105) ( ä 106) ( ä 108) ( ä 108)
Description of device functions
SUPERVISION FAILSAFE MODE ACTUAL SYS. COND PREV. SYST. COND ALARM DELAY SYSTEM RESET
▼
( ä 109) ( ä 109) ( ä 109) ( ä 109) ( ä 110) ( ä 110)
▼
( ä 111) ( ä 111) ( ä 111) ( ä 111)
▼
( ä 112) ( ä 112)
▼
( ä 112) ( ä 112)
Endress+Hauser
Proline Prosonic Flow 91
Proline Prosonic Flow 91 Description of device functions
! Note!
• The engineering unit of the measured variable displayed here can be set in the SYSTEM UNITS group,
( ä 79).
• If the fluid in the pipe flows backwards, a negative sign prefixes the flow reading on the display.
VOLUME FLOW The volume flow currently measured appears on the display.
Display:
5-digit floating-point number, including unit and sign
(e.g. 5.5445 dm3/min; 1.4359 m3/h; –731.63 gal/d; etc.)
SOUND VELOCITY The current measured sound velocity in the liquid appears on the display.
Display:
5-digit fixed-point number, incl. unit
(e.g. 1400.0 m/s, 5249.3 ft/s)
FLOW VELOCITY The flow velocity currently measured appears on the display.
Display:
5-digit floating-point number, including unit and sign
(e.g. 8.0000 m/s, 26.247 ft/s)
Display:
4-digit fixed-point number
(e.g. 80.0 dB)
! Note!
To ensure reliable measurement takes place, Prosonic Flow requires a signal strength of
> 30 dB.
Endress+Hauser 77
Description of device functions Proline Prosonic Flow 91
78 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
Use this function group to select the unit required and displayed for the measured variable.
UNIT VOLUME FLOW Use this function to select the unit for displaying the volume flow.
The unit you select here is also valid for:
• Volume flow display
• Current output
• Switch points (limit value for volume flow, flow direction)
• Low flow
Options:
Metric:
Cubic centimeter cm3/s; cm3/min; cm3/h; cm3/day
Cubic decimeter dm3/s; dm3/min; dm3/h; dm3/day
Cubic meter m3/s; m3/min; m3/h; m3/day
Milliliter ml/s; ml/min; ml/h; ml/day
Liter l/s; l/min; l/h; l/day
Hectoliter hl/s; hl/min; hl/h; hl/day
Megaliter Ml/s; Ml/min; Ml/h; Ml/day
US:
Cubic centimeter cc/s; cc/min; cc/h; cc/day
Acre foot af/s; af/min; af/h; af/day
Cubic foot ft3/s; ft3/min; ft3/h; ft3/day
Fluid ounce oz f/s; oz f/min; oz f/h; oz f/day
Gallon gal/s; gal/min; gal/h; gal/day
Kilo gallons Kgal/s; Kgal/min; Kgal/h: Kgal/day
Million gallons Mgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (normal fluids: 31.5 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Barrel (beer: 31.0 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 42.0 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Barrel (filling tanks: 55.0 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Imperial:
Gallon gal/s; gal/min; gal/h; gal/day
Mega gallon Mgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (beer: 36.0 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 34.97 gal/bbl) bbl/s; bbl/min; bbl/h; bbl/day
Factory setting:
Depends on nominal diameter and country
(dm3/min to m3/h or US-gal/min),
corresponding to the full scale value unit factory setting ä 113
UNIT VOLUME Use this function to select the unit for displaying the volume.
The unit you select here is also valid for:
• Totalizer status display
• Unit totalizer
• Pulse value (e.g. m3/p)
Options:
Metric cm3; dm3; m3; ml; l; hl; Ml
US cc; af; ft3; oz f; gal; Kgal; Mgal; bbl (normal fluids); bbl (beer); bbl (petrochemicals);
bbl (filling tanks)
Imperial gal; Mgal; bbl (beer); bbl (petrochemicals)
Factory setting:
Depends on nominal diameter and country (dm3 to m3 or US-gal), corresponds to the
totalizer unit factory setting ä 113
Endress+Hauser 79
Description of device functions Proline Prosonic Flow 91
UNIT Use this function to select the unit for the liquid temperature.
TEMPERATURE
! Note!
The liquid temperature is entered in the function TEMPERATURE ( ä 99).
Options:
°C (Celsius)
K (Kelvin)
°F (Fahrenheit)
°R (Rankine)
Factory setting:
°C
UNIT VELOCITY Use this function to select the unit for velocity.
The unit you select here is also valid for:
• Sound velocity
• Flow velocity
Options:
m/s
ft/s
Factory setting:
m/s
UNIT VISCOSITY Use this function to select the unit for liquid viscosity.
Options:
mm2/s
cSt
St
Factory setting:
mm2/s
UNIT LENGTH Use this function to select the unit for the measure of length.
The unit you select here is also valid for:
• Nominal diameter
• Diameter
• Wall thickness
• Liner thickness
• Wire length
• Sensor distance
Options:
MILLIMETER
INCH
Factory setting:
MILLIMETER
80 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
LANGUAGE Use this function to select the language for all texts, parameters and messages shown on
the local display.
Options:
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
ITALIANO
Factory setting:
Depends on country, see factory setting ä 113 ff.
! Note!
If you press the OS keys simultaneously at startup, the language defaults to "ENGLISH".
ACCESS CODE All data of the measuring system are protected against inadvertent change.
Programming is disabled and the settings cannot be changed until a code is entered in this
function. If you press the P keys in any function, the measuring system automatically goes
to this function and the prompt to enter the code appears on the display (when
programming is disabled).
You can activate programming by entering your private code (factory setting = 91, see
also the subsequent DEFINE PRIVATE CODE function)
User input:
Max. 4-digit number: 0 to 9999
! Note!
• The programming levels are disabled if you do not press a key within 60 seconds
following automatic return to the HOME position.
• You can also disable programming in this function by entering any number (other than
the defined private code).
• The Endress+Hauser service organization can be of assistance if you mislay your
personal code.
DEF.PRIVATE CODE Use this function to enter a personal code to enable programming.
User input:
0 to 9999 (max. 4-digit number)
Factory setting:
91
! Note!
• This function only appears if the private code was entered in the ACCESS CODE
function.
• Programming is always enabled with the code "0".
• Programming has to be enabled before this code can be changed.
When programming is disabled this function is not available, thus preventing others
from accessing your personal code.
Endress+Hauser 81
Description of device functions Proline Prosonic Flow 91
T-DAT SAVE/LOAD In this function, the configuration/settings of the transmitter can be saved to a
transmitter DAT (T-DAT) or uploading a configuration from the T-DAT to the EEPROM
can be activated (manual back-up function).
Application examples:
• After commissioning, the current measuring point parameters can be saved to the
T-DAT (backup).
• When exchanging the transmitter, the data can be loaded from the T-DAT to the new
transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT to the EEPROM)
Factory setting:
CANCEL
! Note!
• If the target device has an older software version, the message "TRANSM. SWDAT" is
displayed during startup. Then only the SAVE function is available.
• LOAD
This function is only possible if the target device has the same software version as, or a
more recent software version than, the source device.
• SAVE
This function is always available.
82 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
FORMAT Use this function to define the maximum number of places after the decimal point
displayed for the reading in the main line.
Options:
XXXXX.
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Factory setting:
X.XXXX
! Note!
• Note that this setting only affects the reading as it appears on the display, it has no
influence on the accuracy of the system's calculations.
• The places after the decimal point as computed by the measuring device cannot always
be displayed, depending on this setting and the engineering unit. In such instances an
arrow appears on the display between the measuring value and the engineering unit
(e.g. 1.2 l/h), indicating that the measuring system is computing with more decimal
places than can be shown on the display.
CONTRAST LCD Use this function to optimize display contrast to suit local operating conditions.
User input:
10 to 100%
Factory setting:
50%
TEST DISPLAY Use this function to test the operability of the local display and its pixels.
Options:
OFF
ON
Factory setting:
OFF
Test sequence:
1. Start the test by selecting ON.
2. All pixels of the main line and additional line are darkened for at least 0.75 seconds.
3. The main line and additional line show an "8" in each field for at least 0.75 seconds.
4. The main line and additional line show a "0" in each field for at least 0.75 seconds.
5. The main line and additional line show nothing (blank display) for at least
0.75 seconds.
When the test completes the local display returns to its initial state and the setting changes
to "OFF".
Endress+Hauser 83
Description of device functions Proline Prosonic Flow 91
SUM The total for the totalizer's measured variable aggregated since measuring commenced
appears on the display.
This value can be positive or negative, depending on:
• Flow direction
and/or
• Setting in the MEASURING MODE function ä 106
Display:
Max. 6-digit floating-point number, incl. sign and unit (e.g. 15467.4 m3)
! Note!
• The totalizer's response to faults is defined in the central "FAILSAFE MODE" function
ä 109.
• The unit of the totalizer is defined in the UNIT VOLUME function ä 79.
OVERFLOW The total for the totalizer's overflow aggregated since measuring commenced appears on
the display.
Total flow quantity is represented by a floating-point number consisting of max. 6 digits.
You can use this function to view higher numerical values (>9,999,999) as overflows. The
effective quantity is thus the total of the OVERFLOW function plus the value displayed in
the SUM function.
Example:
Reading for 2 overflows: 2 E7 dm3 (= 20,000,000 dm3)
The value displayed in the function "SUM" = 196,845 dm3
Effective total quantity = 20,196,845 dm3
Display:
Integer with exponent, including sign and unit, e.g. 2 E7 dm3
RESET TOTALIZER Use this function to reset the sum and the overflow of the totalizer to "zero" (= RESET).
Options:
NO
YES
Factory setting:
NO
84 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
! Note!
The functions of the CURRENT OUTPUT group are only available if the "0" value was entered in the BUS
ADDRESS function ä 92.
CURRENT RANGE Use this function to specify the current range. You can configure the current output either
in accordance with the NAMUR recommendation (max. 20.5 mA) or for a maximum
drive of 25 mA.
Options:
OFF
4-20 mA (25 mA)
4-20 mA (25 mA) HART
4-20 mA NAMUR
4-20 mA HART NAMUR
4-20 mA US
4-20 mA HART US
Factory setting:
4-20 mA (25 mA) HART NAMUR
I [mA]
o
20
n
0
Q
p
A m n o
OFF 4 mA - -
4-20 mA (25 mA) 4 - 24 mA 2 25
4-20 mA (25 mA) HART 4 - 24 mA 2 25
4-20 mA NAMUR 3,8 - 20,5 mA 3,5 22,6
4-20 mA HART NAMUR 3,8 - 20,5 mA 3,5 22,6
4-20 mA US 3,9 - 20,8 mA 3,75 22,6
4-20 mA HART US 3,9 - 20,8 mA 3,75 22,6
a0005392
A = Work range
m = Work range
n = Lower signal on alarm level
o = Upper signal on alarm level
p = Scaled full scale value
Q = Flow
! Note!
• If the measured value is outside the measuring range (defined in the VALUE 20 mA
function ä 86), a notice message is generated.
• The current output's response to faults is defined in the central FAILSAFE MODE
function ä 109.
Endress+Hauser 85
Description of device functions Proline Prosonic Flow 91
VALUE 20 mA Use this function to assign the 20 mA current a full scale value. Positive and negative
values are permissible. The required measuring range is defined by defining the VALUE
20 mA .
In the SYMMETRY measuring mode ä 106, the value assigned applies to both flow
directions; in the STANDARD measuring mode it applies only to the flow direction
selected.
User input:
5-digit floating-point number, with sign
Factory setting:
Depends on nominal diameter and country, [value] / / [dm3 to m3 or US-gal to US-Mgal]
Corresponds to the factory setting for the full scale value ä 113.
! Note!
• The appropriate unit is taken from the SYSTEM UNITS group ä 79.
• The value for 4 mA always corresponds to the zero flow (0 [unit]).
This value is fixed and cannot be edited.
TIME CONSTANT Use this function to enter a time constant defining how the current output signal reacts to
severely fluctuating measured variables, either very quickly (enter a low time constant) or
with damping (enter a high time constant).
User input:
Fixed point number 0.01 to 100.00 s
Factory setting:
1.00 s
86 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
OPERATION MODE Configuration of the output as a pulse or status output. The functions available in this
function group vary, depending on which option you select here.
Options:
OFF
PULSE
STATUS
Factory setting:
PULSE
! Note!
The appropriate unit is taken from the SYSTEM UNITS group.
transistor transistor
B B< P B B= P
conducting conducting
nonconducting nonconducting
P t P t
a0001233-en
" Caution!
Buffering (pulse memory) takes place if the number of pulses is too large to output the
pulses with the selected pulse width (see PULSE VALUE function on ä 87). The
system error message RANGE PULSE is displayed if more pulses are in the pulse memory
than can be output in 4 seconds.
! Note!
• When entering the pulse width, select a value that can still be processed by an external
totalizer (e.g. mechanical totalizer, PLC, etc.).
• The pulse output's response to faults is defined in the central FAILSAFE MODE function
ä 109.
Endress+Hauser 87
Description of device functions Proline Prosonic Flow 91
Options:
PASSIVE - POSITIVE
PASSIVE - NEGATIVE
Factory setting:
PASSIVE - NEGATIVE
ASSIGN STATUS
OUTPUT
! Note!
This function is not available unless the STATUS setting was selected in the OPERATING
MODE function.
Configuration of the status output.
Options:
ON (operation)
ALARM
NOTICE MESSAGE
ALARM or NOTICE MESSAGE
FLOW DIRECTION
VOLUME FLOW LIMIT VALUE
Factory setting:
ALARM
! Note!
• The behavior of the status output is a normally closed behavior, in other words the
output is closed (transistor conductive) when normal, error-free measuring is in
progress.
• It is very important to read and comply with the information on the switching
characteristics of the status output ä 91.
User input:
5-digit floating-point number, [unit]
Factory setting:
0 [unit]
! Note!
• The appropriate unit is taken from the SYSTEM UNITS group.
• Only the switch-on point is available for flow direction output (no switch-off point). If
you enter a value not equal to the zero flow (e.g. 5 ), the difference between the zero
flow and the value entered corresponds to half the switchover hysteresis.
88 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
User input:
5-digit floating-point number, [unit]
Factory setting:
0 [unit]
! Note!
• The appropriate unit is taken from the SYSTEM UNITS group.
• If SYMMETRY is selected in the MEASURING MODE function and values with
different signs are entered for the switch-on and switch-off points, the notice message
"INPUT RANGE EXCEEDED" appears.
Endress+Hauser 89
Description of device functions Proline Prosonic Flow 91
General
If you have configured the status output for "LIMIT VALUE" or "FLOW DIRECTION", you can
configure the requisite switch points in the SWITCH-ON POINT and SWITCH-OFF POINT
functions. When the measured variable in question reaches these predefined values, the status
output switches as shown in the illustrations below.
-Q Q
-1 0 +1 a
b
a0001236
The value entered in the function ON-VALUE defines the switch point for the positive and negative
directions of flow. If, for example, the switch point entered is = 1 m3/h, the status output switches
off at –1 m3/h (not conductive) and switches on again at +1 m3/h (conductive). Set the switch
point to 0 if your process calls for direct switchover (no switching hysteresis). If low flow cut off is
used, it is advisable to set hysteresis to a value greater than or equal to the low flow.
A B C
m n n
m m n
o o o
t
a0001235
• A = Maximum safety:
m SWITCH-OFF POINT n SWITCH-ON POINT
• B = Minimum safety:
m SWITCH-OFF POINT n SWITCH-ON POINT
• C = Minimum safety:
m SWITCH-OFF POINT = n SWITCH-ON POINT (this configuration should be avoided)
• o = Relay de-energized
90 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
Esc
- + E
A0001237
Esc
- + E
A0001237
Esc
- + E
A0001237
A0001237
A0001237
a0001241
A0001239
a0001242
A0001237
a0001243
a0001244
Endress+Hauser 91
Description of device functions Proline Prosonic Flow 91
! Note!
The communication group is only visible if the HART option was selected in the CURRENT RANGE function.
TAG NAME Use this function to enter a tag name for the measuring device. You can edit and read this
tag name via the local display or the HART protocol.
User input:
Max. 8-character text, permitted characters are: A-Z, 0-9, +,-, underscore, space, period
Factory setting:
"_ _ _ _ _ _ _ _" (without text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device. You can edit and read
this tag description at the local display or via the HART protocol.
User input:
Max. 16-character text, permitted characters are: A-Z, 0-9, +,-, underscore, space, period
Factory setting:
"_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _" (without text)
FIELDBUS ADDRESS Use this function to define the address for the exchange of data with the HART protocol.
User input:
0 to 15
Factory setting:
0
! Note!
Addresses 1 to 15: a constant 4 mA current is applied.
Options:
OFF = function can be edited/read via the HART protocol
ON = HART protocol write-protected (only readable)
Factory setting:
OFF
MANUFACTURER ID Use this function to view the manufacturer number in decimal numerical format.
Display:
– Endress+Hauser
– 17 ( 11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display:
62 hex ( 98 dez) for Prosonic Flow 91
92 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
ON-VALUE LOW Use this function to enter the switch-on point for low flow cut off.
FLOW CUT OFF Low flow cut off is active if the value entered is not equal to 0. The sign of the flow value
is highlighted on the display to indicate that low flow cut off is active.
User input:
5-digit floating-point number, [unit]
Factory setting:
Depends on nominal diameter and country, [value] / [dm3 to m3 or US-gal]
Corresponds to the factory setting for the low flow ä 113.
! Note!
The appropriate unit is taken from the SYSTEM UNITS group.
The switch-off point is specified as a positive hysteresis from the switch-on point with
50%.
2 2
b
H
a
1 1
c c t
a0001245
Q Flow [volume/time]
t Time
H Hysteresis
a SWITCH-ON POINT LOW FLOW CUT OFF = 200 dm3/h
b Low flow switch-off point = 50%
c Low flow cut off active
1 Low flow cut off is switched on at 200 dm3/h
2 Low flow cut off is switched off at 300 dm3/h
Endress+Hauser 93
Description of device functions Proline Prosonic Flow 91
ZERO POINT Use this function to start zero point adjustment automatically. The new zero point
ADJUSTMENT determined by the measuring system is adopted by the ZERO POINT function.
Options:
CANCEL
START
Factory setting:
CANCEL
! Note!
• Zero point adjustment must only be carried out if the sensors have been replaced. The
value determined should not be over 3 ns. If the value is overshot, check whether the
pipe actually has zero flow. For example, sunshine can partially warm the pipe and the
resulting movement in liquid is measured as flow.
• Programming is locked during zero point adjustment The message "ZEROPOINT
ADJUST RUNNING" appears on the display.
• If the zero point adjustment is not possible, (e.g. if v > 0.1 m/s), or has been canceled,
then the alarm message "ZERO ADJUST NOT POSSIBLE" is shown on the display.
ZERO POINT Use this function to display the zero point correction value for the measuring pipe and the
measuring sensors.
Display:
Max. 5-digit number
Factory setting:
0 ns
94 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
PIPE MATERIAL Use this function to display the pipe material. This is specified by the option selected in the
function PIPE STANDARD. If you edit the predetermined value, the pipe standard will be
reset to the option OTHER and the function NOMINAL DIAMETER does not appear.
The pipe material must be selected if the option OTHER was selected in the function PIPE
STANDARD and thus a pipe standard is not defined.
Options:
CARBON STEEL
DUCTILE IRON
STAINLESS STEEL
ALLOY C
PVC
GRP*
ASBESTOS CEMENT
PE
LDPE
HDPE
PVDF
PTFE
PA
PP
GLASS PYREX
OTHER
Factory setting:
STAINLESS STEEL
! Note!
*GRP not recomende!
SOUND VELOCITY Use this function to display the sound velocity in the pipe material.
PIPE The sound velocity in the pipe must be specified.
User input:
Fixed-point number 800 to 6500 m/s
Factory setting:
3120 m/s
User input:
Fixed point number 31.4 to 15,700.0 mm
Factory setting:
279.3 mm
Endress+Hauser 95
Description of device functions Proline Prosonic Flow 91
PIPE DIAMETER Use this function to display the pipe outer diameter.
The pipe outer diameter or the pipe circumference must be specified.
User input:
Fixed-point number 10.0 to 5000.0 mm
Factory setting:
33,7 mm für DN 15 to 65
88,9 mm für DN 50 to 4000
96 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
WALL THICKNESS Use this function to display the wall thickness of the pipe.
The wall thickness must be entered.
User input:
Fixed point number 0.1 to max. 1000 mm (depends on nominal diameter)
Factory setting:
3.2 mm
Endress+Hauser 97
Description of device functions Proline Prosonic Flow 91
LINER MATERIAL Use this function to display the liner material of the pipe.
The liner material must be specified if a liner is present.
Options:
LINER NONE
MORTAR
RUBBER
TAR EPOXY
OTHER
Factory setting:
LINER NONE
SOUND VELOCITY Use this function to display the sound velocity of the liner. This is specified by the option
LINER selected in the function LINER MATERIAL. If you edit the predetermined value the liner
material will be reset to the option OTHERS.
The sound velocity of the liner must be entered if the option OTHER was selected in the
function LINER MATERIAL.
User input:
Fixed-point number 800 to 6500 m/s
Factory setting:
Depends on the setting selected in the function LINER MATERIAL
LINER THICKNESS Use this function to enter the thickness of the liner.
User input:
Fixed-point number 0.0 to 99.9 mm
Factory setting:
0 mm
98 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
Options:
WATER
SEA WATER
DISTILLED WATER
AMMONIA
ALCOHOL
BENZENE
BROMIDE
ETHANOL
GLYCOL
KEROSENE
MILK
METHANOL
TOLUOL
LUBE OIL
FUEL OIL
PETROL
OTHER
Factory setting:
WATER
! Note!
The selection specifies the values for the sound velocity and viscosity. If OTHER is
selected, these must be entered via the SOUND VELOCITY LIQUID and VISCOSITY
functions.
TEMPERATURE Use this function to enter the process temperature of the liquid. Via the sound velocity,
the value influences the determination of the sensor distance. Enter the process
temperature at normal operating conditions to achieve an optimum configuration of the
measuring system.
User input:
Fixed-point number –273.15 °C to 726.85 °C
Factory setting:
20 °C
Endress+Hauser 99
Description of device functions Proline Prosonic Flow 91
SOUND VELOCITY Use this function to display the sound velocity of the liquid. This is determined via the
LIQUID values of the functions LIQUID and TEMPERATURE. If you edit the predetermined value,
the function LIQUID will be reset to the option OTHER.
The sound velocity of the liquid must be entered if the liquid is not available for selection
in the function LIQUID and the option OTHER was selected here.
! Note!
We recommend you select a smaller search range in the event of unfavorable signal
conditions (signal strength < 50%).
0-1000 0-1000
v [m/s]
2 3
1
a0001246
User input:
Fixed-point number 400 to 3000 m/s
Factory setting:
1487.4 m/s
VISCOSITY This function displays the viscosity of the liquid. This is determined via the values of the
LIQUID and TEMPERATURE functions. If you edit the predetermined value the function
LIQUID will be reset to the option OTHER. The viscosity must be entered if the liquid is
not available for selection in the function LIQUID and the option OTHER was selected
here.
User input:
Fixed-point number 0.0 to 5000.0 mm2/s
Factory setting:
1 mm2/s
SOUND VELOCITY Use this function to specify the lower search range for the sound velocity of the liquid.
NEGATIVE
User input:
Fixed-point number 0 to 1000 m/s
Factory setting:
500 m/s
! Note!
Pay particular attention to the information in the function SOUND VELOCITY LIQUID.
100 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
SOUND VELOCITY Use this function to specify the upper search range for the sound velocity of the liquid.
POSITIVE
User input:
Fixed-point number 0 to 1000 m/s
Factory setting:
500 m/s
! Note!
Pay particular attention to the information in the function SOUND VELOCITY LIQUID.
Endress+Hauser 101
Description of device functions Proline Prosonic Flow 91
SENSOR Use this function to select the configuration for the ultrasonic clamp-on sensors.
CONFIGURATION
Options:
NO. TRAVERSE: 1
NO. TRAVERSE: 2
NO. TRAVERSE: 4
Factory setting:
NO. TRAVERSE: 2
! Note!
• 1 traverse for nominal diameters larger than DN 600, for certain plastic pipes with a
wall thickness greater than 4 mm or if the signal strength is not sufficient in other
arrangements.
• 2 traverses is the recommended configuration for pipes smaller than DN 600.
• 4 traverses can only be used for DN 50 in exceptional circumstances. The
recommended configuration is 1 traverse.
CABLE LENGTH Use this function to select the length of the sensor cable.
Options:
LENGTH 5 m/15 feet
LENGTH 10 m/30 feet
LENGTH 15 m/45 feet
LENGTH 30 m/90 feet
LENGTH 60 m/180 feet
Factory setting:
LENGTH 5 m/15 feet
! Note!
The influence on the flow measurement caused by the cable length is minimal with
nominal diameters under DN 80. For larger nominal diameters, the result is negligible.
102 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
POSITION SENSOR Use this function to view the position of both sensors on the rail.
Display:
4-digit number combination
! Note!
This function is only available if the number of traverses is 2 or 4 (see function SENSOR
CONFIGURATION).
WIRE LENGTH The wire length for assembling the sensors at the correct distance apart appears on the
display.
Display:
max. 4-digit number, including unit (e.g. 200 mm)
! Note!
This function is only available if the number of traverses is 1 (see function SENSOR
CONFIGURATION).
SENSOR DISTANCE The distance between sensor 1 and sensor 2 appears on the display.
Display:
max. 5-digit number, including unit (e.g. 200 mm)
! Note!
2 traverses cannot be used if the sensor distance is <180 mm.
Endress+Hauser 103
Description of device functions Proline Prosonic Flow 91
CAL. FACTOR Use this function to call up the calibration factor currently used.
Data indicated:
5-digit floating-point number (typically 1.000)
ZERO POINT Use this function to call up the zero point correction currently used.
Data indicated:
5-digit floating-point number with sign (e.g. +0200.0)
ZEROPOINT STAT. Use this function to call up or manually change the static zero point correction currently
being used.
User input:
5-digit floating-point number, including unit and sign (e.g. +0010.0 ns)
CORR. FACTOR Use this function to enter a correction factor at the client's site.
User input:
5-digit floating-point number between 0.5 and 2.
Factory setting:
1.000 (no correction)
104 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
ISTALLATION Use this function to reverse the sign of the flow quantity, if necessary.
DIRECTION SENSOR
Options:
FORWARDS (flow as indicated by the arrow)
BACKWARDS (flow opposite to direction indicated by the arrow)
Factory setting:
NORMAL
Endress+Hauser 105
Description of device functions Proline Prosonic Flow 91
MEASURING MODE Use this function to select the measuring mode for all outputs and for the internal totalizer.
Options:
STANDARD
SYMMETRY
Factory setting:
STANDARD
The responses of the individual outputs and the internal totalizer in each of the measuring
modes are described in detail on the following pages:
Current output
STANDARD
Only the flow components for the selected flow direction are output, (positive or negative
full scale value n = flow direction). Flow components in the opposite direction are not
taken into account (suppression).
I [mA]
20
4
0 Q
m n
a0001248
SYMMETRY
The output signals of the current output are independent of the direction of flow (absolute
amount of the measured variable). The "VALUE 20mA" o (e.g. backflow) corresponds to
the mirrored VALUE 20 mA n (e.g. flow). Positive and negative flow components are
taken into account.
mA
20
4
0 Q
o m n
a0001249
! Note!
The direction of flow can be output via the configurable status output.
106 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
SYMMETRY
The absolute value of the positive and negative flow components is taken into account.
Status output
! Note!
The information is only applicable if LIMIT VALUE was selected in the function ASSIGN
STATUS OUTPUT.
STANDARD
The status output signal switches at the defined switch points.
SYMMETRY
The status output signal switches at the defined switch points, irrespective of the sign. In
other words, if you define a switch point with a positive sign, the status output signal
switches as soon as the value is reached in the negative direction (negative sign), (see
illustration).
Q
10
0
t
-4
- 10
➀ ➁ ➀ ➁ ➀
A0001247
Totalizer
STANDARD
Only positive flow components are output.
Negative components are not taken into account.
SYMMETRY
The positive and negative flow components are balanced.
In other words, net flow in the flow direction is registered.
Endress+Hauser 107
Description of device functions Proline Prosonic Flow 91
Options:
OFF
ON Signal output is set to the "ZERO FLOW" value.
Factory setting:
OFF
FLOW Use this function to set the filter depth of the digital filter.
DAMPING The sensitivity of the measurement signal can be reduced with respect to interference
peaks (e.g. in the event of a high solid content, gas bubbles in the fluid etc.).
The reaction time of the measuring system increases with the filter setting.
User input:
0 to 60 s
Factory setting:
2s
! Note!
• The system damping acts on all functions and outputs of the measuring device.
• The higher the value set, the stronger the damping (higher response time).
108 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
FAILSAFE MODE The dictates of safety render it advisable to ensure that the device signal processing
assumes a predefined state in the event of an alarm. The setting you select here is valid for:
• Current output
• Pulse output
• Totalizer
! Note!
This has no effect on the display.
Options:
MINIMUM VALUE
MAXIMUM VALUE
CURRENT VALUE (not recommended)
Factory setting:
MINIMUM VALUE
The response of the individual outputs and the totalizer is listed below.
Current output:
MINIMUM VALUE
The current output adopts the value of the lower signal on alarm level (as defined in the
CURRENT SPAN function on ä 85).
MAXIMUM VALUE
The current output adopts the value of the upper signal on alarm level (as defined in the
CURRENT SPAN function on ä 85).
ACTUAL VALUE
Measuring value output based on the actual flow measurement (alarm is ignored).
Pulse output:
MINIMUM or MAXIMUM VALUE
Output is zero pulse
ACTUAL VALUE
Measuring value output based on the actual flow measurement (alarm is ignored).
Totalizer:
MINIMUM or MAXIMUM VALUE
The totalizer is paused while an alarm is present.
ACTUAL VALUE
The totalizer continues to count on the basis of the current flow value.
The fault is ignored.
ACTUAL SYSTEM Use this function to check the current system condition.
CONDITION
Display:
"SYSTEM OK" or the diagnosis message with the highest priority.
PREVIOUS SYSTEM Use this function to view the 20 most recent diagnosis messages since measuring last
CONDITIONS started.
Display:
The last 20 diagnosis messages.
Endress+Hauser 109
Description of device functions Proline Prosonic Flow 91
ALARM DELAY Use this function to define a time span in which the criteria for an error have to be satisfied
without interruption before an error or notice message is generated.
Depending on the setting and the type of error, this suppression acts on the:
• Display
• Current output
• Pulse/status output
User input:
0 to 100 s (in steps of one second)
Factory setting:
0s
" Caution!
If this function is activated error and notice messages are delayed by the time
corresponding to the setting before being forwarded to the higher-order controller (process
controller, etc.). It is therefore imperative to check in advance in order to make sure
whether a delay of this nature could affect the safety requirements of the process.
If error and notice messages cannot be suppressed, a value of 0 seconds must be entered
here.
SYSTEM RESET Use this function to perform a reset of the measuring system.
Options:
NO
RESTART SYSTEM (restart without interrupting power supply)
MEASURING PIPE DATA (restore the original calibration data)
! Note!
The T-DAT has to be present for the original calibration data to be restored successfully
when the MEASURING PIPE DATA option is selected. If this is not the case, the error
message DATA STORAGE appears.
Factory setting:
MEASURING PIPE DATA
110 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
SIMULATION Use this function to set all outputs and the totalizer to their defined failsafe modes, in order
FAILSAFE MODE to check whether they respond correctly.
During this time, the words "SIMULATION FAILSAFE MODE" appear on the display.
Options:
ON
OFF
Factory setting:
OFF
SIMULATION Use this function to set all outputs and the totalizer to their defined flow-response modes,
MEASURAND in order to check whether they respond correctly.
During this time, the words "SIMULATION MEASURAND" appear on the display.
Options:
OFF
VOLUME FLOW
Factory setting:
OFF
! Note!
• The measuring device cannot be used for measuring while this simulation is in progress.
• The setting is not saved if the power supply fails.
VALUE SIMULATION
MEASURAND
! Note!
This function is not available unless the SIMULATION MEASURAND function is active
(= VOLUME FLOW).
Use this function to define a freely selectable value (e.g. 12 m3/s).
This is used to test downstream devices and the measuring device itself.
User input:
5-digit floating-point number [unit], with sign
Factory setting:
0 [unit]
" Caution!
The setting is not saved if the power supply fails.
! Note!
The appropriate unit is taken from the SYSTEM UNITS group.
Endress+Hauser 111
Description of device functions Proline Prosonic Flow 91
SERIAL NUMBER Use this function to view the serial number of the measuring system.
SOFTWARE REVISION Use this function to view the software revision number of the electronics board.
NUMBER
112 Endress+Hauser
Proline Prosonic Flow 91 Description of device functions
10.22.1 SI units
10.22.3 Language
Country Language
Australia English
Belgium English
Canada English
China English
Denmark English
Germany Deutsch
England English
Finland English
France Francais
Holland English
Hong Kong English
India English
Indonesia English
International Instruments English
Italy Italiano
Japan English
Malaysia English
Norway English
Poland English
Portugal English
Austria Deutsch
Russia English
Sweden English
Switzerland Deutsch
Singapore English
Spain Espanol
South Africa English
Thailand English
Endress+Hauser 113
Proline Prosonic Flow 91 Index
Index
A E
ACCESS CODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Electrical connection
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Sensor connecting cable . . . . . . . . . . . . . . . . . . . . . . . 27
ACTUAL SYSTEM CONDITION . . . . . . . . . . . . . . . . . . 109 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
ALARM DELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Electromagnetic compatibility (EMC) . . . . . . . . . . . . . 29, 72
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . 72 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Applicator (selection and configuration software) . . . . . . . 54 F
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 74 FAILSAFE MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
ASSIGN STATUS OUTPUT . . . . . . . . . . . . . . . . . . . . . . . 88 Field Xpert SFX100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
C Fieldcheck (tester and simulator). . . . . . . . . . . . . . . . . . . . 54
CABLE LENGTH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 FLOW DAMPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Cable specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 28–29 FLOW VELOCITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
CAL. FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Calibration factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Function matrix
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Brief guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
CE mark (Declaration of Conformity) . . . . . . . . . . . . . . . . . 9 Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Certificates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 74 FXA195 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
CIRCUMFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Cleaning (external cleaning) . . . . . . . . . . . . . . . . . . . . . . . 51
Code entry (function matrix) . . . . . . . . . . . . . . . . . . . . . . 36 G
Commissioning Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Group
Commubox FXA 195 (electrical connection) . . . . . . . . . . . 53 AMPLIFIER VERSION . . . . . . . . . . . . . . . . . . . . . . . . 112
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 CALIBRATION DATA . . . . . . . . . . . . . . . . . . . . . . . . 104
Connection COMMUNICATION. . . . . . . . . . . . . . . . . . . . . . . . . . 92
HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 CONFIG. CHANNEL . . . . . . . . . . . . . . . . . . . . . . . . 102
See Electrical connection CURRENT OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Terminal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 LINER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 LIQUID DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
CONTRAST LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 MEASURING VALUES . . . . . . . . . . . . . . . . . . . . . . . . 77
Control OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Field Xpert HART Communicator . . . . . . . . . . . . . . . . 37 PIPE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
CORR. FACTOR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 PROCESS PARAMETER . . . . . . . . . . . . . . . . . . . . . . . 93
Coupling fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 PULSE/STATUS OUTPUT . . . . . . . . . . . . . . . . . . . . . 87
C-tick mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 74 SENSOR SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
CURRENT RANGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 SENSOR VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . 112
SIMULATION SYSTEM. . . . . . . . . . . . . . . . . . . . . . . 111
D SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Data back-up (of device data with T-DAT) . . . . . . . . . . . . 48 SYSTEM PARAMETER . . . . . . . . . . . . . . . . . . . . . . . 105
Declaration of Conformity (CE mark) . . . . . . . . . . . . . . . . . 9 SYSTEM UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
DEF.PRIVATE CODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 TOTALIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Degree of protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Device description files . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 H
DEVICE ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 HART
Device variable using the HART protocol . . . . . . . . . . . . . 38 Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Diagnosis messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Device status/diagnosis messages . . . . . . . . . . . . . . . . 44
Display Field Xpert HART Communicator . . . . . . . . . . . . . . . . 37
Display and operating elements . . . . . . . . . . . . . . . . . . 34 Hazardous substances . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 65
Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 73 HOME position (operating mode) . . . . . . . . . . . . . . . . . . . 34
Rotating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
See Display I
Temporary (for blind version) . . . . . . . . . . . . . . . . . . . 25 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Inlet/outlet runs
Clamp-on version . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
114 Endress+Hauser
Proline Prosonic Flow 91 Index
Endress+Hauser 115
Proline Prosonic Flow 91 Index
T
TAG DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
TAG NAME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
T-DAT (HistoROM)
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Save/load (data back-up, e.g. for replacing devices) . . . 48
T-DAT SAVE/LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Technical data at a glance . . . . . . . . . . . . . . . . . . . . . . . . . 66
TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
116 Endress+Hauser
Declaration of Contamination
Erklärung zur Kontamination
Because of legal regulations and for the safety of our employees and operating equipment, we need the "declaration of
contamination", with your signature, before your order can be handled. Please make absolutely sure to include it with
the shipping documents, or - even better - attach it to the outside of the packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die
unterschriebene "Erklärung zur Kontamination", bevor Ihr Auftrag bearbeitet werden kann. Legen Sie diese unbedingt den
Versandpapieren bei oder bringen Sie sie idealerweise außen an der Verpackung an.
harmful/
Medium /concentration Identification flammable toxic corrosive irritant other * harmless
Medium /Konzentration CAS No. entzündlich giftig ätzend gesundheits- sonstiges* unbedenklich
schädlich/
reizend
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv
Please tick should one of the above be applicable, include security sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
_____________________________________________ ______________________________________________
(place, date / Ort, Datum) (Company stamp and legally binding signature)
(Firmenstempel und rechtsverbindliche Unterschrift)
www.endress.com/worldwide
BA00100D/06/EN/13.11
71130013
FM+SGML6.0 ProMoDo