ABB Utilities GmbH RTU560
Remote Terminal Unit
Data Sheet
Analog Output 23AA20
Application
Analog control outputs for sequential- - or closed- - The microcontroller on the board handles the dialog
loop control, display instruments, measurand re- on the RTU560 system bus. All configuration data
corders etc. can be connected to the RTU560 by the and processing parameters are loaded from the
analog output board 23AA20. The 23AA20 board communication unit via the RTU560 system bus.
has two output channels which are potential isolated
and can be configured to different output current The module executes a number of tests during initial-
ranges. The output format, unipolar, bipolar or live ization and operation. If an error occurs the central
zero (4...20 mA) will be configured by software pa- control unit is notified. All error statuses which could
rameter. affect the function of the module are displayed by a
light emitting diode (ST) as a common disturbance
The following output current ranges can be config- on the front panel. A failure of the module is detected
ured by plug- -in jumpers, independent per channel: by the communication unit.
V ± 2,5 mA
V ± 5 mA
D +
V ± 10 mA I011
memory
output
V ± 20 mA (4...20 mA)
I010
opto- - A --
coupler
B
Characteristics U
adjustment
S DC/DC current range
Each output has a digital to analog converter (DAC) converter
M
which converts the digital value present in the output
O
memory into an analog signal. The DAC has a reso- D +
lution of 11 bit plus sign. A received output value D I021
memory
output
keeps stored until a new value is received. The out- U
I020
put channels are set to 0% after power up or reset of L
opto- -
coupler
A --
the board. E
adjustment
The outputs of the analog output module 23AA20 DC/DC
converter current range
are potentially isolated between the channels and
from the RTU560 power supply.
ST
The module is equipped with both a serial and a par-
allel interface to the RTU560 system bus. Therefore
the board can be configured in the extension sub- Fig. 1: Block diagram
rack. Analog output board 23AA20
Doc.- -No.: 1KGT 150 401 V000 1 9
ABB Utilities GmbH
Data Sheet Analog Output 23AA20 RTU560
Technical Data
In addition to the RTU560 general technical data, the following applies:
Output Channels Mechanical Layout
Outputs: 2 Printed circuit 3HE, Euro- -card format
board: (160 x 100 mm)
Potential isolation: from one another and
against power supply Front panel: 4R, 1 slot (20 mm)
Output current: ± 2,5 mA Weight: approx. 0.3 kg
± 5 mA
± 10 mA Connection Type
± 20 mA (4...20 mA)
Connector: indirect, 48 pole
Range selection: per channel by Type F DIN 41612
plug- -in jumpers
Load impedance: max.1000 Ω (±2,5...±10 mA) Test Voltages
max. 500 Ω (± 20 mA) AC test voltage: 2,5 kV 50 Hz / VDE 804
Resolution: 11 bit + sign safety electrical isolation
Adjustment: 2000 Digit = 100%
factory- -adjusted Impulse voltage 5 kV (1.2/50)
withstand test: IEC 255- -4 (class III)
Errors (Reference: 25 ˚C)
Gain error: typ. (%) max. (%) Electromagnetic Compatibility
± 20 mA 0,01 0,02 Electrical fast 2 kV
± 10 mA 0,01 0,01 transient test: IEC 801- -4 (class 4)
± 5 mA / ± 2,5 mA 0,03 0,2
Offset error: typ. (%) max. (%) High frequency 1 / 2.5 kV (1MHz)
± 20 mA / ± 5 mA 0,03 0,1 disturbance test: IEC 255- -4 (class III)
± 10 mA / ± 2,5 mA 0,06 0,2
Environmental Conditions
Temperature drift: (Range: 0...70 _C)
Gain typ. (ppm/˚C) max. (ppm/˚C) Temperature: 0 ... 70 _C
± 20 mA / ± 5 mA 100 200 Relative humidity: 5 ... 95%
± 10 mA / ± 2,5 mA 100 200 (non condensing)
Offset
± 20 mA / ± 5 mA 60 300
± 10 mA / ± 2,5 mA 120 600 Ordering Information
Front plate plastic: light beige
Power Supply 23AA20R5101 1KGT004100R5101
Supply: 5 V / 650 mA
ABB Utilities GmbH
Kallstadter Straße 1
68309 Mannheim (Germany)
Telephone +49 (0) 621 381- -7592
Telefax +49 (0) 621 381- -7622 03/2001 Subject to alteration