CMM366A-ET
CLOUD MONITORING COMMUNICATION MODULE
USER MANUAL
Chinese trademark
English trademark
SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000 (overseas)
Fax: +86-371-67992952
Web: [Link]/
[Link]/
Email: sales@[Link]
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to SmartGen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.
Table 1 – Software Version
Date Version Note
2017-12-21 1.0 Original release.
2022-07-26 1.1 Update company logo and manual format.
CMM366A-ET Cloud Monitoring Communication Module User Manual Page 2 of 15
CONTENT
1 OVERVIEW ................................................................................................................................................. 4
2 PERFORMANCE AND CHARACTERISTICS.............................................................................................. 4
3 SPECIFICATION ........................................................................................................................................ 5
4 PANEL AND TERMINAL DESCRIPTION ................................................................................................... 6
4.1 PANEL INDICATOR AND BUTTONS ......................................................................................................... 6
4.2 ETHERNET ................................................................................................................................................ 7
4.3 RS485 ........................................................................................................................................................ 7
4.4 RS232 ........................................................................................................................................................ 7
4.5 LINK ........................................................................................................................................................... 8
4.6 USB HOST.................................................................................................................................................. 8
4.7 USB DEVICE ............................................................................................................................................... 8
4.8 TERMINAL ................................................................................................................................................. 9
5 PROGRAMMABLE PARAMETERS .......................................................................................................... 10
5.1 CONTENTS AND SCOPES OF PARAMETERS ........................................................................................ 10
5.2 PC CONFIGURATION INTERFACE .......................................................................................................... 12
6 SYSTEM DIAGRAM ................................................................................................................................. 13
7 CASE DIMENSION AND INSTALLATION ............................................................................................... 14
8 TROUBLESHOOTING .............................................................................................................................. 15
9 PACKING LIST ......................................................................................................................................... 15
CMM366A-ET Cloud Monitoring Communication Module User Manual Page 3 of 15
1 OVERVIEW
CMM366A-ET Cloud Monitoring Communication Module is an ETHERNET communication protocol
switch module which can achieve genset (with SCI) connect to Internet. After logging into cloud server,
module will receive corresponding genset controller communication protocol from cloud server. And
the module gains genset data via RS485 port, USB port, LINK port or RS232 port. Then the module
transmits the data to corresponding cloud server via wired ETHERNET for achieving user’s real-time
monitoring to running status and searching of running records via APP (IOS or Android) and pc terminal
devices.
CMM366A-ET module not only can achieve genset monitoring but also can insert some digital
alarm input/output signal to achieve monitoring of generator room entrance guard, guard against theft
and fire facilities.
2 PERFORMANCE AND CHARACTERISTICS
Connect to cloud server via wired ETHERNET, one to one monitoring;
Multiple ports for communication with genset control module: RS485, RS232, LINK and USB (Host);
can monitor great majority genset control modules of international first-class brands;
Widely power supply: DC (8~35)V, can direct use genset build-in starter battery;
With ARM-based 32-bit SCM, high integration of hardware and strong programming ability;
Include with GPS locate function to achieve gain location information and locate genset;
Take JSON network data communication protocol, upload real-time data variation and take
compression algorithm to vastly reduce network flow at the same time;
When alarm occurs it can upload data to server immediately;
2 auxiliary digital input ports which can receive external alarm signal;
1 auxiliary relay output ports which can output various of alarm signal;
Calendar and clock functions;
Power and multiple communication status indicators on front panel that working status is clear at
a glance;
Lamp test function;
Parameter adjust function: users can adjust parameters via USB port;
Take standard π-type 35mm guide-rail installation or screw-fixed installation that the module can
be installed in the genset control box;
Modular design, self extinguishing ABS plastic shell, light weight, compact structure with easy
installation.
CMM366-ET Cloud Monitoring Communication Module User Manual Page 4 of 15
3 SPECIFICATION
Table 2 – Technical Data
Items Contents
Operating Voltage DC 8.0V~35.0V, continuous power supply.
Standby: ≤2W
Power Consumption
Working: ≤5W
Digital Input Volt free digital Input
Relay Output 1A DC30V Volts free output
USB Host A-type USB female port
RS485 Isolated type
RS232 General type
LINK SmartGen exclusive port
USB Device B-type USB female port
ETHERNET RJ45 10/100Mbps self-adaption network interface
Case Dimensions 72.5mmx105mmx34mm
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-25~+70)°C
Weight 0.15kg
CMM366-ET Cloud Monitoring Communication Module User Manual Page 5 of 15
4 PANEL AND TERMINAL DESCRIPTION
4.1 PANEL INDICATOR AND BUTTONS
Fig.1 – CMM366A-ET Front Panel Diagram
Table 3 – Indicators Description
Icon Note
Green LED Light: Power supply normal indicator;
POWER/ALARM
Red LED Light: Common alarm indicator.
Normally Extinguish: RS485 disabled;
RS485(Red) Normally Light: Communication failure;
Blink: Communication normal.
Normally Extinguish: USB(Host) disabled;
USB(Red) Normally Light: Communication failure;
Blink: Communication normal.
Normally Extinguish: CMM366A-ET logins with server unsuccessfully;
ETHERNET(Red) Normally Light: Login with server successfully;
Blink: Real-time communication normal.
Normally Extinguish: Disabled;
LINK(Red) Normally Light: Communication failure;
Blink: Communication normal.
Normally Extinguish: RS232 disabled;
RS232(Red) Normally Light: Communication failure;
Blink: Communication normal.
Internal lamp test/reset key:
Press it for 1s, all the LEDs are illuminated; press it for 10s, reset the module to default and all the
LEDs blink for 3 times.
NOTE: After reset the module, parameters need to be re-configured via PC software. Please operate cautiously.
CMM366-ET Cloud Monitoring Communication Module User Manual Page 6 of 15
4.2 ETHERNET
CMM366A-ET EHTERNET port is automated negotiation 10/100Mbps working mode, which adopts
one to one cross-over cable connect with router as follows,
Fig.2 – ETHERNET Connet With Router
4.3 RS485
Receive genset data information by connecting module RS485 port with Genset Controller RS485
port.
If communication is abnormal, 120Ω terminal resistance is recommonded. One end of shield wire
hangs in the air and the other one connects with SCR.
Fig.3 – RS485 Connection
4.4 RS232
Receive genset data information by connecting module RS232 port with Genset Controller RS232
port.
Fig.4 – RS232 Connection
CMM366-ET Cloud Monitoring Communication Module User Manual Page 7 of 15
4.5 LINK
Receive genset data information by connecting module LINK port with Genset Controller LINK port.
Fig.5 – LINK Connection
4.6 USB HOST
Receive genset data information by connecting module A-type USB port (female port) with Genset
Controller USB port via USB cable.
Fig.6 – USB Host Connection
4.7 USB DEVICE
All the parameters can be configured and view CMM366A-ET ID&Login password by connecting
USB port with USB disk of PC software.
Fig.7 – USB Connect PC Device
CMM366-ET Cloud Monitoring Communication Module User Manual Page 8 of 15
4.8 TERMINAL
Table 4 – Terminals Description
No. Function Cable Size Note
2
1 B- 1.0mm Connected with negative of starter battery.
Connected with positive of starter battery. 3A
2 B+ 1.0mm2
fuse is recommended.
3 Digital Input 1 1.0mm2 Active when connect to B-.
2
4 Digital Input 2 1.0mm Active when connect to B-.
Normally
5 1.0mm2
Open
6 Relay Output Common 1.0mm2 Normally open output with 1A DC30V
Normally
7 1.0mm2
Close
8 RS485 B(-) 0.5mm2
Impedance-120Ω shielding wire is recommended,
9 RS485 A(+) 0.5mm2
its single-end earthed.
10 SCR 0.5mm2
11 RS232 RX 0.5mm2
12 RS232 TX 0.5mm2 RS232
13 RS232 GND 0.5mm2
CMM366-ET Cloud Monitoring Communication Module User Manual Page 9 of 15
5 PROGRAMMABLE PARAMETERS
5.1 CONTENTS AND SCOPES OF PARAMETERS
Table 5 – Parameter Content & Scope
No. Items Parameters Defaults Description
IP
0: Disabled 1: Enabled,
1 DHCP Enable (0-1) 1
obtain IP automatically
2 IP Address (0-255) [Link]
All changes of Ethernet (e.g. IP
3 Subnet Mask (0-255) [Link]
address, subnet mask) will
4 Default Gateway (0-255) [Link]
activate after repowering the
5 DNS Address (0-255) [Link]
module.
6 MAC Address (0-255) [Link].01.02.03
Gateway
20 Chinese characters, letters
1 Site Name (0-65535)
or numbers
2 Server URL (0-65535) [Link] 40 characters
3 Server Port (0-65535) 91
4 Security Code (0-65535) 123456 16 characters
GPS
Location
1 (0-1) 0 0: Disabled 1: Manual Input
Information
2 Longitude ((-180)-180)° 0.000000
GPS location, altitude
3 Latitude ((-90)-90)° 0.000000
information
4 Altitude ((-9999.9)-9999.9)m 100.0
Digital Input
Digital Input 1
1 Setting (0-9) 0 Default: Not used
0: Close to Activate
1: Open to Activate
2 Type (0-1) 0
See: Table 6 – Digital Input
Ports Content
3 Delay (0-20.0) 0.0 Action delay
Digital Input 2
1 Setting (0-9) 1 Default: Lamp test
0: Close to Activate
1: Open to Activate
2 Type (0-1) 0
See: Table 6 – Digital Input
Ports Content
3 Delay (0-20.0) 0.0 Action delay
Digital Output
Default: Not used
1 Setting (0-14) 0 See: Table 7 – Relay Output
Ports Content
CMM366-ET Cloud Monitoring Communication Module User Manual Page 10 of 15
NOTE: Configuration of monitoring genset controller model, communication port, communication baud rate, and
communication ID need to be set on the platform, and reboot the monitoring module after setting parameters.
Table 6 – Digital Input Ports Content
No. Item Description
0 Not Used Not used.
1 Lamp Test All the indicators are illuminated when input is active.
2 Remote Control Inhibit Cloud start/stop control is prohibited when input is active.
3 Access Alarm Input Access alarm is uploaded to server when input is active.
4 Fire Alarm Input Fire alarm is uploaded to server when input is active.
5 Alarm Input External alarm is uploaded to server when input is active.
6 Reserved
7 Reserved
8 Reserved
9 Factory Test Mode It is only used for factory test when active.
Table 7 – Relay Output Ports Content
No. Item Description
0 Not used Output port won’t output when this item is selected.
1 Digital Input 1 Active Output when auxiliary input 1 is active.
2 Digital Input 2 Active Output when auxiliary input 2 is active.
3 RS485 Comm. Failure Output when RS485 communication fails.
4 Network Comm. Failure Output when Network communication fails.
5 LINK Comm. Failure Output when LINK communication fails.
6 RS232 Comm. Failure Output when RS232 communication fails.
7 Common Alarm Output when there is an alarm.
Send remote control commands via cloud platform with fixed
8 Remote Control Output
output delay 20s.
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
CMM366-ET Cloud Monitoring Communication Module User Manual Page 11 of 15
5.2 PC CONFIGURATION INTERFACE
Connecting the USB port of CMM366A-ET communication module with PC USB port to configure
the parameters.
Fig.8 – IP Configuration
Through pressing “ping” key to test whether IP address is correct or not.
Fig.9 – Gateway Configuration
Fig.10 – Module Monitoring Interface
CMM366-ET Cloud Monitoring Communication Module User Manual Page 12 of 15
6 SYSTEM DIAGRAM
One CMM366A-ET module connects with one genset monitor module. It can be connected via
RS485 port, LINK port, RS232 port or USB port.
Fig.11 – CMM366A-ET System Diagram
CMM366-ET Cloud Monitoring Communication Module User Manual Page 13 of 15
7 CASE DIMENSION AND INSTALLATION
2 ways for installation: 35mm guide rail in box or screw (M4) installation as below:
Fig.12 – CMM366A-ET Case Dimension
Fig.13 – CMM366A-ET Guide Rail Installation
Fig.14 – CMM366A-ET Screw Installation
CMM366-ET Cloud Monitoring Communication Module User Manual Page 14 of 15
8 TROUBLESHOOTING
Table 8 – Troubleshooting
Symptoms Possible Solutions
Controller no response with Check power voltage;
power Check controller connection wirings.
Check Ethernet setting correct or not;
ETHERNET indicator off Check whether Ethernet socket indicator is blink or not;
Check cable connection.
Check connections;
Check RS485 port is enabled or not;
RS485 comm. abnormal
Check settings of genset ID and baud rate are correct or not;
Check RS485’s connections of A and B is reverse connect or not.
Check connections;
RS232 comm. abnormal Check RS232 port is enabled or not;
Check settings of genset ID and baud rate are correct or not.
Check connections;
LINK comm. abnormal Check LINK port is enabled or not;
Check settings of genset ID and baud rate are correct or not.
9 PACKING LIST
Table 9 – Packing List
No. Name Quantity Remark
1 CMM366A-ET 1
2 120Ω matched resistor 2
3 Certification 1
4 User manual 1
_________________________________
CMM366-ET Cloud Monitoring Communication Module User Manual Page 15 of 15