C Multivalve® Assemblies
Caution Notice
Installation, usage, and maintenance of all ECII® products must
Do not use any product contained in this catalog with any be in compliance with all Engineered Controls International,
service commodity other than LP-Gas or NH3. If you have Inc. instructions as well as requirements and provisions of
a need for use of another application, contact Engineered NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, state, provincial and local standards, codes, regulations, and
(336) 449-7707 before proceeding. laws.
Proper application, installation and maintenance of products Inspection and maintenance on a periodic basis is essential.
in this catalog are essential. Users of these products Installation and maintenance should be performed only by
should obtain further information if there are any doubts or qualified personnel.
questions.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
1960 to 1985 — Two-Letter Date Code Second letter in date code is the year
R — 1960 A — 1969 J — 1978
First letter in date code is the month S — 1961 B — 1970 K — 1979
A — January G — July T — 1962 C — 1971 L — 1980
B — February H — August U — 1963 D — 1972 M— 1981
C — March I — September V — 1964 E — 1973 N — 1982
D — April J — October W— 1965 F — 1974 O — 1983
E — May K — November X — 1966 G — 1975 P — 1984
F — June L — December Y — 1967 H — 1976 Q — 1985
Relief valves used on ASME tanks carry a numerical code Z — 1968 I — 1977
indicatingmonth and year such as 1-75 means January, 1975. EXAMPLE: DL = April of 1980
From 1985 to 1990 — Digit Date Code Second 2 digits in date code are the year
86 — 1986 89 — 1989
First digit in date code is the month 87 — 1987 90 — 1990
1 — January 7 — July 88 — 1988
2 — February 8 — August EXAMPLE: 5-87 = May of 1987
3 — March 9 — September
4 — April 10 — October
5 — May 11 — November
6 — June 12 — December
After 1990 — Digit-Letter-Digit Date Code Letter in date code is the week Second 2 digits in date code are the year
A — 1st week 91 — 1991 97 — 1997
First digit in date code is the month B — 2nd week 92 — 1992 98 — 1998
1 — January 7 — July C — 3rd week 93 — 1993 99 — 1999
2 — February 8 — August D — 4th week 94 — 1994 00 — 2000
3 — March 9 — September E — 5th week 95 — 1995 01 — 2001
4 — April 10 — October 96 — 1996 02 — 2002
5 — May 11 — November 03 — 2003 etcetera. . .
6 — June 12 — December EXAMPLE: 6A92 = First week of June, 1992
Classic Gold — Indicates a single stage regulator that is designed to be used alone in single stage systems.
Brilliant Red — Denotes a first stage high pressure regulator, normally used in two-stage applications
in conjunction with a select brown second stage regulator.
Select Brown — Signifies second stage low pressure regulators, designed for use in two-stage systems in
conjunction with a brilliant red high pressure regulator — also signifies integral twin stage regulators
designed to provide benefits of two-stage regulation in one compact unit.
Select Blue — Indicates a second stage 2 PSIG delivery pressure regulator and a line pressure regulator downstream
to reduce 2 PSIG to appliance pressure
Green — High pressure pounds to pounds anhydrous amonia regulator.
Section Description
A Regulators and Accessories
C Multivalve® Assemblies
Section A
A A
A1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO® Regulator Color Coding
RegO® domestic first stage, second stage, single stage, and integral twin stage LP-Gas regulators are easy to
identify. In addition to a standard part number marking, each regulator is color coded to indicate the proper application
and to help minimize misapplication in the field that can lead to accidents and costly service callbacks. The color
coding system is standard on all 404, LV404, 2302, LV2302, 2403, 2503, LV4403, and LV5503 series domestic
LP-Gas regulators manufactured after May of 1986.
Select Brown - Regulators with Low Pressure delivery range. Select Brown color is found on both:
• Integral Twin Stage Regulators. Designed to provide benefits of two-stage regulation in one compact unit.
Select Blue - Second Stage Regulators for 2 PSIG Systems. Designed to reduce first stage pressure down to 2 PSIG.
Normally used in conjunction with a first stage high pressure regulator.
Classic Gold - Single Stage Regulators. Designed to use alone in Single Stage Systems.
Except as expressly set forth above, and subject to the limitation of liability
below, ECII MAKES NO OTHER WARRANTY, EXPRESS OR IMPLIED,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, with
respect to its products and parts, whether used alone or in combination
with others. ECII disclaims all warranties not stated herein.
A2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
Warning installation, operation and service.
A3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO® Regulator Dependability
When RegO® LP-Gas Regulators are properly installed, safe, precise, All give you a product that provides accurate gas delivery under
trouble-free service is the result. varying pressure ranges and load conditions.
Dependability is built into every regulator ... the result of rigid standards RegO® LP-Gas Regulators are UL listed and comply with applicable
of quality control and close tolerance machining. And this has been code requirements.
true for more than 60 years. RegO® Products offer a complete line of LP-Gas Regulators with
RegO® Products are manufactured from the finest materials, and capacities for almost every application.
assembled and tested using procedures second to none.
Second Stage in a 2
9
PSIG System 2,200,000 LV5503Y6/Y8 8
200,000 LV404B23/29 Series 7
15 PSIG Inlet 50 PSIG Inlet
25 PSIG Inlet
Integral Twin Stage 525,000 LV404B4/B9 Series
A 800,000 LV404Y9 CFH/hr. 100 200 300 400 500 600 700 800 900 1000
BTU/hr. 500,000 1,000,000 1,500,000 2,000,000 2,500,000
Automatic 200,000 7525B23 Series
Changeover 450,000 7525B4 Series Example for a Second Stage Regulator
1. Assume load of 250,000 BTU’s per hour.
* See catalog page for inlet and delivery specifications.
2. Assume a minimum delivery pressure of 10” w.c.
Now determine which regulator in the Series would be most suitable.
Turn to the individual product pages and refer to the Performance 3. Assume a minimum inlet pressure of 10 psig.
Curves. Check the performance of the regulator with your actual load 4. For these conditions, refer to chart for the LV4403B Series,
conditions at the minimum LP-Gas inlet pressure for the regulator. Second Stage Regulator, shown below.
Use the pressure corresponding to your lowest winter temperatures 5. Find the line on the chart corresponding to the anticipated inlet
shown in the chart below or refer to the delivery pressure of your first pressure.
6. Draw a vertical line upward from the point of assumed load
Approx. Approx. Pressure (250,000 BTU’s per hour) to intersect with the line corresponding
Temperature Temperature
Pressure (PSIG) (PSIG) to the lowest inlet pressure.
°F °C Propane Butane °F °C Propane Butane 7. Read horizontally from the intersection of these lines to the
delivery pressure at the left side of the chart. In this example the
-40 -40 3.6 40 4 72 3.0
delivery pressure will read 10.6” w.c. Since the delivery pressure
-30 -34 8 50 10 86 6.9 will be 10.6” w.c. at the maximum load condition and lowest
anticipated inlet pressure, the regulator is sized properly for the
-20 -29 13.5 60 16 102 12
demand.
-10 -23 23.3 70 21 127 17
0 -18 28 80 27 140 23
10 -12 37 90 32 165 29 LV4403B Series Second Stage Regulator
20 -7 47 100 38 196 36
Inches of Water Column
13
stage regulator. 12
15 PSIG Inlet
Example for a First Stage Regulator 11
10
1. Assume a load of 500,000 BTU’s per hour.
9
2. Assume a minimum delivery pressure of 9.5 psig. 5 PSIG Inlet 8 PSIG Inlet 10 PSIG Inlet
3. Assume a minimum tank pressure of 15 psig. CFH/hr. 0 50 100 150 200 250 300 350 400 450 500
4. For these conditions, refer to chart for the LV4403TR Series, First BTU/hr. 250,000 500,000 750,000 1,000,000 1,250,000
A4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Safety Warnings
Purpose
In its continuing quest for safety, Engineered Controls International, Inc. publishes a series of bulletins explaining
the hazards associated with the use, misuse, and aging of LP-Gas valves and regulators. It is hoped that these
factual bulletins will make clear to LP-Gas dealer managers and service personnel, that the utmost care and
attention must be used in the installation, inspection, and maintenance of these products, or problems could
occur which would result in injuries and property damage.
The National Fire Protection Association Pamphlet #58 - 2004 Edition, “Liquified Petroleum Gas Code” states in
Section 1.5 that, “persons who transfer liquid LP-Gas, who are employed to transport LP-Gas, or whose primary
duties fall within the scope of this code shall be trained in proper handling procedures. Refresher training shall
be provided at least every three years. The training shall be documented.” These “ECII® Safety Warnings”
may be useful in training new employees and reminding older employees of hazards that can occur. It is
recommended that all employees be furnished with a copy of NPGA Safety Pamphlet 306, “LP-Gas Regulator
and Valve Inspection and Maintenance.”
Nature of Warnings
It is recognized that warnings should be as brief as possible, but
the factors involved in regulator failures are not simple. They need The Causes of High Pressure Gas in a System are:
to be fully understood so that proper maintenance programs can be
established. If there is a simple warning, it would be: 1. Regulator vents that are clogged or obstructed.
Vents must be clear and fully open at all times.
Inspect regulators regularly as outlined in this safety warning and
Many regulators are equipped with a pressure relief valve which
replace as required per these recommendations. When all of these
discharges to atmosphere through the vent. Ice, snow drifts, dirt,
recommendations are followed, the recommended service life of
bugs, paint, or other foreign material can clog the vents.
an ECII/RegO® regulator (except single stage) manufactured after
1995 is 25 years. The recommended service life of all other ECII/ An obstructed vent may prevent the pressure relief valve from
RegO® regulators is 15 years. operating properly.
LP-Gas Regulators
A6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Loss of Pressure Underground Installations
Freeze-up inside the regulator. Special hazards can occur if regulators are not properly installed in
underground systems. Water, dirt, mud and insects can get into the
regulator if the bonnet cap is not tightly in place and the vent is not
protected with a proper vent tube, opening above any potential water
level.
Most problems occur because the waterproof dome on the buried
storage tank does not extend above the ground level sufficiently to
keep out water and mud.
Ice Refer to NPGA No. 401.
A7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Advantages of Two-Stage Regulation
A8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Two-Stage LP-Gas Systems ...
Require First Stage Regulators with Built-in Relief Valves
Resulting in sudden pressure surge due to flashing into vapor here! 80° F. 140 PSIG 50° F. 86 PSIG
First stage relief can prevent liquid from forming in first stage piping 90° F. 165 PSIG 60° F. 102 PSIG
during periods with no gas demand! ! !
200
Pressure PSIG
150
Propane
100
50
Butane
The Problem
Many modern LP-Gas appliances are equipped with pilotless ignition stage regulator will not relieve the pressure in first stage piping.
systems. Water heaters and older appliances use pilot lights, but it The rapid vaporization of the liquid may cause a rapid pressure surge
has become a common practice for energy conscious homeowners to that could seriously damage critical components of the appliance and
shut-off the pilot when leaving home for extended periods of time. In furnace controls.
each instance, there is no gas demand at all for extended periods.
A fire or explosion could occur as a consequence.
The Consequences
If the first stage regulator fails to lock-up tight, usually as a result The Solution
of a worn seat disc or foreign material lodged between nozzle and RegO® LV4403 Series First Stage Regulators with Built-In Relief
seat disc, pressure will build-up in the first stage piping – possibly Valves reduce the possibility of this serious hazard in two stage
to a level that approaches tank pressure. Combining this with warm applications. The built-in relief valve is designed to vent as needed
ambient temperatures and cool ground, propane liquid may form in and reduce the possibility of first stage piping pressure from becoming
the first stage piping. high enough to form liquid.
When gas demand resumes, this liquid may pass through the second
stage regulator into the appliances and furnace. NOTE – the second
A9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pipe and Tubing Selection Guide
Use the following simple method to assure the selection of the correct sizes of piping and tubing for LP-Gas vapor systems. Piping between first and second stage
regulators is considered, as well as low pressure (inches water column) piping between second stage, single stage, or integral twin stage regulators and appliances.
Instructions:
1. Determine the total gas demand for the system by adding up the BTU/hr input
from the appliance nameplates and adding demand as appropriate for future
appliances.
2. For second stage or integral twin stage piping:
A. Measure length of piping required from outlet of regulator to the appliance
furthest away. No other length is necessary to do the sizing.
B. Make a simple sketch of the piping, as shown.
C. Determine the capacity to be handled by each section of piping. For
example, the capacity of the line between a and b must handle the total
demand of appliances A, B, and C; the capacity of the line from c to d must
handle only appliance B, etc.
D. Using Table 3 select proper size of tubing or pipe for each section of piping,
using values in BTU/hr for the length determined from step #2-A. If exact
length is not on chart, use next longer length. Do not use any other length
for this purpose! Simply select the size that shows at least as much capacity
as needed for each piping section.
3. For piping between first and second stage regulators
A. For a simple system with only one second stage regulator, merely measure
length of piping required between outlet of first stage regulator and inlet of
second stage regulator. Select piping or tubing required from Table 1.
B. For systems with multiple second stage regulators, measure length of piping
required to reach the second stage regulator that is furthest away. Make a
simple sketch, and size each leg of piping using Table 1, 2, or 3 using values
shown in column corresponding to the length as measured above, same as
when handling second stage piping.
Example 1 Example 2.
Determine the sizes of piping or tubing required for the twin-stage LP-Gas Determine the sizes of piping or tubing required for the two-stage LP-Gas
installation shown. installation shown.
A10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pipe and Tubing Selection Guide
Example 3
Determine the sizes of piping or tubing required for the 2 PSI LP-Gas installation shown.
Total first stage piping length = 26 feet; first stage regulator setting is 10psig (use Table 1 or 2 @ 30 feet)
Total 2 PSI Piping Length = 19 ft. (use Table 4 @ 20 ft. or Table 6 @ 20 ft.)
From aa to a, demand= 338,000 BTU
use 3/8” CSST or 1/2” copper tubing or 1/2” pipe
From Regulator a to each appliance:
From a to b, demand= 65,000 BTU; length = 25 ft. (Table 5),
use 1/2” CSST
From a to c, demand= 200,000 BTU; length = 30 ft. (Table 5)
use 3/4” CSST
From a to d, demand= 38,000 BTU; length = 21 ft.* (Table 5)
use 3/8” CSST *use 25 ft. column Furnace
Range
From a to e, demand= 35,000 BTU; length = 40 ft. (Table 5)
65,000 200,000
use 1/2” CSST First Stage c
26 30
Regulator 19 Water
Feet b Feet
Feet Heater
25 21
Feet 38,000
a Feet
d
aa 12
Table 1 – First Stage Pipe Sizing (Between First and Second Stage Regulators) 10 PSIG Inlet with a 1 PSIG Pressure Drop Maximum capacity of pipe or tubing, in thousands of BTU/hr or LP-Gas
Table 2 – First Stage Plastic Tubing Sizing 10 PSIG Inlet with a 1 PSIG Pressure Drop Maximum capacity of plastic tubing in thousands of BTU/hr of LP-Gas
Table 4-Maximum Capacity of CSST In Thousands of BTU per hour of undiluted LP-Gases Pressure of 2 psi and a pressure drop of 1 psi (Based on a 1.52 Specific Gravity Gas)*
A
**EHD –– Equivalent Hydraulic Diameter –– A measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
Table 5-Maximum Capacity of CSST In Thousands of BTU per hour of undiluted LP-Gases Pressure of 11 Inch Water Column and a Pressure Drop of 0.5 Inch Water Column (Based on a 1.52 Specific Gravity Gas)*
Table 6 – Copper Tube Sizing or Schedule 40 Pipe Sizing* In Thousands of BTU per hour of undiluted LP-Gases 2 PSIG inlet with a 1PSIG pressure drop (Between 2 PSIG service regulator & line pressure regulator).
A12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO® Regulator Designs
Typical of the LV4403 Low Pressure Regulators and
LV4403 High Pressure Regulators. Molded Diaphragm Assembly
RegO® LP-Gas Regulators have been designed to Twin layers of molded synthetic rubber sandwich a
tough, flexible fabric to give super sensitive response
give outstanding performance and dependability with a in a temperature range of -40º to +165ºF. Molded
minimum of maintenance. diaphragm seals in a groove between the body and
Nozzle Orifice bonnet.
Replaceable and precision machined to prevent scoring of the
seat disc. Diaphragm Plate
Rigid diaphragm plate transmits pressure variations to
Seat Disc control linkage.
Replaceable, resilient construction gives sure closing at lock up
pressure. Straight line seat disc to nozzle operation provides Relief Valve
even seat disc wear and positive lock up. It is built in and tamper resistant. Large bonnet vent
allows high capacity relief on second stage regulators.
Pivot Pin
Fully enclosed in regulator body. Bonnet Cap
Bonnet cap incorporates travel stop to help control
Control Linkage downstream pressure in the unlikely event of a
Provides quick response to diaphragm movement; moves directly regulator malfunction.
perpendicular to nozzle orifice to meter gas flow, give positive
closure and reduce seat disc wear. Large Bonnet Vent
Large vent is equipped with protective screen and
Built-In Pressure Tap threaded for 3⁄4” F. NPT vent piping. Large vent helps
Provides a convenient way to check downstream pressure on prevent ice from building up and blocking the vent
both high and low pressure models. during inclement weather. The regulator should be
Body & Bonnet installed with vent down and the vent protected
Painted, heavy-duty zinc resists corrosion and gives long-life against blockage.
protection, even under “salty air” conditions.
A
Connections
Machined and threaded into the body casting; also
includes 1⁄4” NPT pressure gauge ports.
Seat Disc
Synthetic rubber assembly attached directly to the
yoke assembly to ensure proper movement and
regulation.
Integral O-Ring
Minimizes tendency to
vibrate or hum under
extreme loads.
Sensitivity
In those cases where there is a choice of delivery pressure ranges,
the lowest spring range which will fulfill your requirements is
recommended because the sensitivity of a regulator decreases as the
Relief Valves
range of the adjusting spring increases.
Most high pressure regulators are not equipped with integral relief
valves. For certain applications where it is desirable to protect
equipment downstream of the regulator, relief valves must be installed
in the line.
A13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Compact First Stage Regulators
LV3403TR
Application Materials
Ideal for use as a first stage regulator on any domestic size ASME or Body............................................................................................... Zinc
DOT container in propane gas installations requiring up to 1,500,000 Bonnet............................................................................................ Zinc
BTU’s per hour. The regulator is factory set to reduce container Spring............................................................................................ Steel
pressure to an intermediatepressure of approximately 10 PSIG. Seat Disc.....................................................................Resilient Rubber
Diaphragm.............................. Integrated Fabric and Synthetic Rubber
Features
• Compact design can be connected to a service valve using either
a POL adapter or a RegO product pigtail.
• Non Adjustable
• Design provides for good flow regulation at both high and low
container pressures.
• Built in relief valve and travel stop comply with NFPA 58 over
pressure requirements.
• Body and bonnet are assembled in the USA using the unique,
patented RegUlok seal system.
Initial Setting
• Fully painted in brilliant red for complete corrosion protection. 11
• Mounting bracket available as an accessory: part number 2302-31. 150 PSIG INLET
DELIVERY PRESSURE PSIG
50 PSIG INLET
9
25 PSIG INLET
3.865” CFH/hr.
BTU/hr.
100
250,000
200
500,000
300
750,000
400
1,000,000
500
1,250,000
600
1,500,000
750
1,750,000
FLOW PROPANE
PRODU
10
O
G
CT
RE
S
10
Y
NT
3.56” E
Y
AR A
WA R R
Ordering Information
Factory
Delivery Vapor Capacity BTU/hr
Part Number Inlet Connection Outlet Connection Orifice Size Pressure Bonnet Vent Position Propane*
LV3403TR Over Outlet
¼” [Link] ½” [Link] ¼” 10 PSIG 1,500,000
LV3403TRV9 9:00
* Maximum flow based on inlet pressure 20 PSIG higher than the regulator setting and delivery pressure 20% lower than the regulator setting and delivery pressure 20% lower than the setting.
A14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
High Pressure First Stage Regulators
LV4403SR and TR Series
Application Materials
Provides accurate first stage regulation in two-stage bulk tank Body ............................................................................... Die Cast Zinc
systems. Reduce tank pressure to an intermediate pressure of 5 to 10 Bonnet ............................................................................ Die Cast Zinc
PSIG. Also used to supply high pressure burners for applications like Nozzle Orifice ............................................................................. Brass
industrial furnaces or boilers. Also incorporated in multiple cylinder Spring .......................................................................................... Steel
installations. Valve Seat Disc ......................................................... Resilient Rubber
Diaphragm ............................ Integrated Fabric and Synthetic Rubber
Features
• Incorporate integral relief valves for added system protection.
LV4403 Series
• Large vent helps prevent blockage and has 3⁄4” [Link] thread for
vent piping. UL
®
LV4403SR
150 PSIG Inlet 41⁄2"
Initial Setting 125 PSIG Inlet 51⁄4"
Delivery Pr essure
5
4
50 PSIG Inlet
3
10 PSIG Inlet 25 PSIG Inle
t
CFH/hr. 100 200 300 400 500 600 700 800 900 1000
BTU/hr. 500,000 1,000,000 1,500,000 2,000,000 2,500,000
37⁄8" 11⁄2"
LV4403TR
150 PSIG Inlet
12 Initial Setting 125 PSIG Inlet
PRODU
Delivery Pr essure
11
10
100 PSIG Inlet O
10
G
CT
PSIG
RE
9
S
8
10
7
15 PSIG Inlet 50 PSIG Inlet
NT
25 PSIG Inlet E
Y
AR A
WA R R
CFH/hr. 100 200 300 400 500 600 700 800 900 1000
BTU/hr. 500,000 1,000,000 1,500,000 2,000,000 2,500,000
Ordering Information
Outlet Orifice Factory Delivery Adjustment Range* Integral Relief Vapor Capacity BTU/hr
Part Number Inlet Connection Connection Size Pressure (PSIG) Included Propane**
LV4403SR4 5 1-5
½” F. NPT
LV4403TR4 10 5-10
½” F. NPT
LV4403SR9 5 1-5
¼” Yes 2,500,000
LV4403TR9 10 5-10
F. POL
LV4403SR96 5 1-5
¾” [Link]
LV4403TR96 10 5-10
* When used for final stage pressure control, must either incorporate integral relief valve or separate relief valve should be specified in accordance
with NFPA Pamphlet 58.
** Maximum flow based on inlet pressure 20 PSIG higher than the regulator setting and delivery pressure 20% lower than the setting.
A15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Low Pressure Second Stage Regulators
LV4403B Series
Application Materials
Designed to reduce first stage pressure of 5 to 20 PSIG down to Body ............................................................................... Die Cast Zinc
burner pressure, normally 11” w.c. Ideal for medium commercial Bonnet ............................................................................ Die Cast Zinc
installations, multiple cylinder installations and normal domestic Nozzle Orifice ............................................................................. Brass
loads. Spring .......................................................................................... Steel
Valve Seat Disc ......................................................... Resilient Rubber
Diaphragm ............................ Integrated Fabric and Synthetic Rubber
Features
• Large vent helps prevent blockage and has 3⁄4" [Link] for vent
piping.
LV4403B Series
• With 15 PSIG inlet pressure, regulator is designed to not pass
more than 2 PSIG with the seat disc removed.
• Built in pressure tap has plugged 1⁄8" [Link] outlet. Plug can be
removed with a 3⁄16" hex allen wrench.
Backmount Design
A Mounts directly to house line piping. Eliminates need for union joints,
elbows, and mounting brackets. Quick and easy to install.
11⁄2" 33⁄16"
41⁄2" Outlet
71⁄8"
51⁄4"
Dia.
75⁄32"
21⁄4" PRODU
10
Approx. O
G
CT
RE
17⁄16" 313⁄16"
LV4403B
10
Y
NT
E
Y
LV4403BR AR A
WA R R
Ordering Information
Outlet Orifice Factory Delivery Bonnet Vent Vapor Capacity BTU/
Part Number Inlet Connection Connection Size Pressure Adjustment Range Position hr. Propane**
LV4403B4 1½”
LV4403B46 ½” F. NPT
LV4403B46R* 11” w.c. at 10 PSIG
#28 Drill 9” to 13” w.c. Over Inlet 935,000
¾” F. NPT Inlet
LV4403B66
¾” F. NPT
LV4403B66R*
* Backmount design
** Maximum flow based on 10 PSIG inlet and 9” w.c. delivery pressure.
A16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Low Pressure Second Stage Regulators
LV4403B66RA Series
Application Materials
Designed to reduce first stage pressure of 5 to 20 PSIG down to Body ...................................................................... Die Cast Aluminum
burner pressure, normally 11” w.c. Ideal for medium commercial Bonnet ............................................................................ Die Cast Zinc
installations, vapor meter installations and normal domestic loads. Nozzle Orifice ............................................................................. Brass
Spring .......................................................................................... Steel
Valve Seat Disc ......................................................... Resilient Rubber
Features Diaphragm ............................ Integrated Fabric and Synthetic Rubber
• 90 degree right angle inlet to outer connection for meter or
standard installations.
• Large vent helps to prevent blockage and has ¾” F. NPT for vent
piping.
A
Can mount directly to vapor meter. It is also suitable for mounting w/ Mounting Bracket
directly to the house piping. It will retrofit into existing installations that
are currently using a 90 degree, right angle regulator.
51⁄4"
71⁄4"
PRODU
10
O
G
CT
RE
90°
S
10
Y
NT
2 3/16" E
Y
AR A
WA R R
Ordering Information
Outlet Orifice Factory Delivery Adjustment Bonnet Vent Vapor Capacity BTU/
Part Number Inlet Connection Connection Size Pressure Range Position hr. Propane*
LV4403B66RA
11” w.c. at 10
¾” F. NPT ¾” F. NPT 3/16” 9” to 13” w.c. Over Inlet 1,000,000
LV4403B66RAB** PSIG Inlet
A17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Low Pressure Second Stage Regulators
LV5503B Series
Application Materials
Designed to reduce first stage pressure of 5 to 20 PSIG down to Body (LV5503B Series ......................................... Die Cast Aluminum
burner pressure,normally 11” w.c. Ideal for larger commercial and Bonnet (LV5503B Series) ..................................... Die Cast Aluminum
industrial applications, multiple cylinder installations and large Nozzle Orifice ............................................................................ Brass
domestic systems. Spring ......................................................................................... Steel
Valve Seat Disc ........................................................ Resilient Rubber
Diaphragm ........................... Integrated Fabric and Synthetic Rubber
Features
• Incorporates integral relief valve.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Factory
Inlet Outlet Delivery Adjustment Vapor Capacity BTU/hr.
Part Number Connection Connection Orifice Size Pressure Range Bonnet Vent Position Propane
LV5503B4 ½” F. NPT
¾” F. NPT ¼” 11” w.c. at 10 1,600,000
LV5503B6 9” - 13” w.c. Over Inlet
¾” F. NPT PSIG Inlet
LV5503B8 1” F. NPT 9/32 ” 2,300,000
Maximum flow is based on 10 PSIG inlet and 9” w.c. delivery pressure.
A18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Second Stage Regulators for 2 PSI Systems
LV4403Y and LV5503Y Series
Application Materials
Designed to reduce first stage pressure of 10 PSIG down to 2 PSIG. Body (LV4403Y Series).................................................. Die Cast Zinc
A line pressure regulator is required downstream to reduce the 2 Body (LV5503Y Series ......................................... Die Cast Aluminum
PSIG to a nominal 11” W.C. Bonnet (LV4403Y Series)............................................... Die Cast Zinc
Bonnet (LV5503Y Series) ..................................... Die Cast Aluminum
Nozzle Orifice ............................................................................ Brass
Features Spring ......................................................................................... Steel
Valve Seat Disc ........................................................ Resilient Rubber
• Large vent helps prevent blockage and has ¾” [Link] for vent piping. Diaphragm ........................... Integrated Fabric and Synthetic Rubber
• With 15 PSIG inlet pressure, regulator is designed to not pass
more than 5 PSIG with the seat disc removed.
LV5503Y8
2.20
Initial Setting
2.00
15 PSIG Inlet
1.80
5 PSIG Inlet 10 PSIG Inlet
1.60
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
5,000,000 1,250,000 2,000,000
LV5503Y6
2.20
Initial Setting
2.00
1.80
15 PSIG Inlet PRODU
10
O
5 PSIG Inlet
G
CT
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
500,000 1,250,000 2,000,000
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Bonnet Vent Vapor Capacity BTU/hr.
Part Number Inlet Connection Outlet Connection Orifice Size Adjustment Range
Position Propane***
LV4403Y4 1/2” F. NPT 1/2” F. NPT 1/4” 2 PSIG @ 10 PSIG Inlet Over Inlet 1,000,000
LV4403Y46R* 1/2” F. NPT 3/4” F. NPT 1/4” 2 PSIG @ 10 PSIG Inlet Over Inlet 1,000,000
LV5503Y6 3/4” F. NPT 3/4” F. NPT 1/4” 2 PSIG @ 10 PSIG Inlet Over Inlet 2,200,000
LV5503Y8 3/4” F. NPT 1” F. NPT 9/32” 2 PSIG @ 10 PSIG Inlet Over Inlet 2,200,000
Maximum flow is based on 10 PSIG inlet pressure and 1.5 PSIG delivery pressure.
A19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Low Pressure Second Stage Tobacco Barn Regulator
LV5503G4 Series
Application Materials
Especially developed for drying barns in the tobacco industry. The
LV5503G4 regulator will supply a steady and constant flow of fuel to as Body...................................................................... Die Cast Aluminum
many as 12 to 20 burners throughout the barn. Bonnet................................................................... Die Cast Aluminum
Nozzle Orifice ............................................................................ Brass
Spring ......................................................................................... Steel
Features Valve Seat Disc ........................................................ Resilient Rubber
Diaphragm ........................... Integrated Fabric and Synthetic Rubber
• Similar to construction of the LV5503B Series. Provides the
same stability, low lock-up, and sensitive performance.
LV5503G4 Series
• Equipped with integral relief valve.
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
UL ®
Ordering Information
Inlet Outlet Orifice Adjustment Bonnet Vent Vapor Capacity BTU/
A
Part Number Connection Connection Size Factory Delivery Pressure Range Position hr. Propane*
LV5503G4 ½” F. NPT ¾” F. NPT ¼” 15” w.c. at 15 PSIG Inlet 8” - 18” w.c. Above Inlet 1,750,000
Maximum flow is based on 15 PSIG inlet pressure and 13” w.c. delivery pressure.
* Maximum flow is based on 15 PSIG inlet and 12” w.c. delivery pressure.
Large Capacity Second Stage Regulators
LV6503B Series
Application
These regulators are designed to reduce gas pressure from the first
stage regulator down to appliance pressure, normally 11” w.c. They
are for use in LP-Gas applications.
Features
• Tee style inlet and outlet connections – made from ductile iron.
• Incorporate integral large 2” [Link] relief vents.
• Built in pressure taps for both inlet and outlet pressure.
• Full capacity relief at 10 psig inlet will keep the down stream
pressure at less than 2 PSIG per NFPA 58.
PRODU Materials
10
O
UL
G
CT
RE
®
Inlet Body............................................................................ Ductile Iron
10
Y
NT
E
Body............................................................................ Cast Aluminum
Y
AR A
WA R R
Ordering Information Bonnet ........................................................................ Cast Aluminum
Inlet Outlet Factory Delivery Adjustment Bonnet Vent Vapor Capacity BTU/hr.
Part Number Connection Connection Orifice Size Pressure Range Position Propane
LV6503B14 1½” F. NPT 1½” F. NPT 8,000,000
11” w.c. at 10 PSIG
⅝” 8½” - 14” w.c. Over Inlet
LV6503B16 2” F. NPT 2” F. NPT Inlet 9,750,000
* Maximum flow is based on 10 PSIG inlet and 20% droop.
A20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Compact Twin Stage Regulators
LV404B4 and LV404B9 Series
Application Materials
This compact two-stage regulator is designed to reduce container Body (First Stage)...................................................................... Brass
pressure down to 11” w.c. delivery pressure. It is ideal for “on-site” Body (Second Stage) .................................................... Die Cast Zinc
cylinder applications, mobile homes and average domestic service Nozzle Orifice ............................................................................ Brass
including small ASME and 100 to 420 pound DOT cylinders. Spring ......................................................................................... Steel
Valve Seat Disc ........................................................ Resilient Rubber
Diaphragm ........................... Integrated Fabric and Synthetic Rubber
Features
• Incorporates integral relief valves.
• Large vent helps prevent blockage and has 3⁄4” F. NPT for vent
piping.
• Built in pressure taps on both first and second stage regulators have
plugged 1⁄8” [Link] outlets. Plugs can be removed with a 3⁄16”
hex allen wrench.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Bonnet Bonnet Accessories
Factory Adjustment Vent Vent Capacity
Inlet Outlet Orifice Delivery Range 2nd Position Position BTU/hr. 1st Stage Vent
Part Number Connection Connection Size Pressure Stage 1st Stage 2nd Stage Propane* Pipe-Away
LV404B4 Down Over Outlet
½” F. NPT
LV404B4V9 9 o’clock 9 o’clock
¼” F. NPT
LV404B46 Down Over Outlet
¾” F. NPT
LV404B46V9 11” w.c. at 100 9 o’clock 9 o’clock
.219 9” - 13” w.c. 525,000 404PE
LV404B9 PSIG Inlet Down Over Outlet
½” F. NPT
LV404B9V9 9 o’clock 9 o’clock
F. POL
LV404B96 Down Over Outlet
¾” F. NPT
LV404B96V9 9 o’clock 9 o’clock
Maximum flow is based on 25 PSIG inlet pressure and 9” w.c. delivery pressure.
A21
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Compact Twin Stage Regulators
LV404B23 and LV404B29 Series
Application Materials
The LV404B23 and LV404B29 Series Regulators are designed for Body (First Stage).......................................................... Die Cast Zinc
small domestic applications with flow requirements up to 200,000 Body (Second Stage) .................................................... Die Cast Zinc
BTU’s/hr. These regulators are ideal for mobile homes, cottages and Bonnet LV404B23, First Stage ...................................... Die Cast Zinc
“on-site” cylinder applications. These regulators can also be used in Bonnet LV404B29, First Stage .................................................. Brass
RV applications if a protective Bonnet, Second Stage .................................................. Die Cast Zinc
cover is also supplied. Diaphragms ......................... Integrated Fabric and Synthetic Rubber
Springs ....................................................................................... Steel
Valve Seat Discs ...................................................... Resilient Rubber
Features
• Provides all the benefits of two-stage regulation in one compact unit
(for small size loads) at a reasonable cost. LV404B23 LV404B23V9 LV404B29
• Incorporates integral relief valve in second stage.
• Full size vents on the first and second stage are both tapped 1⁄8”
[Link].
• Built in pressure taps on both first and second stage regulators have
plugged 1⁄8” [Link] outlet. Plugs can be removed with a 3⁄16” hex
allen wrench.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Accessories
Bonnet
Factory Adjustment Vent Bonnet Vent Capacity 1st Stage
Part Inlet Outlet Orifice Delivery Range 2nd Position 1st Position BTU/hr Vent 2nd Stage
Number Connection Connection Size Pressure Stage Stage 2nd Stage Propane* Pipe-Away Vinyl Cover Bracket
LV404B23 ¼” F. NPT
11” w.c. at Rear Over Outlet
LV404B29 F. POL
½” F. NPT .100 100 PSIG 9-13” w.c. 200,000 404PE 2302-55 2302-31
LV404B23V9 ¼” F. NPT Inlet Left 9 o’clock
LV404B29V9 F. POL
* Maximum flow based on 25 PSIG inlet pressure and 9” w.c. delivery pressure.
A22
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Twin Stage Automatic Changeover Regulators
7525B Series
Application Materials
These combination automatic changeover, two stage regulators are Body (First Stage).......................................................... Die Cast Zinc
especially suitable for homes, mobile homes, cottages, construction Body (Second Stage) .................................................... Die Cast Zinc
and other portable two cylinder installations. Empty containers may Bonnet First Stage . ....................................................... Die Cast Zinc
be replaced without interrupting customer’s gas service. Bonnet, Second Stage .................................................. Die Cast Zinc
First Stage Nozzle Orrifice ........................................................ Brass
Springs ....................................................................................... Steel
Features Valve Seat Discs ...................................................... Resilient Rubber
Diaphragms ......................... Integrated Fabric and Synthetic Rubber
• Automatic changeover switches from “service” to “reserve” cylinder
automatically without interrupting service.
• The Second Stage Incorporates wide bonnet drip lip vent to guard
against freeze-up when properly installed.
UL ®
• With 15 PSIG inlet pressure the second stage, regulator is designed 7525B23
to not pass more than 2 PSIG with the seat disc removed.
7525B4
• Allows “reserve” cylinder to supplement the flow of gas from the
“service” cylinder during extreme load or severe cold conditions.
• Change over knob and indicator are integral to the first stage.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
Ordering Information WA R R
A23
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Two PSIG Delivery Pressure Twin-Stage Regulator
LV404Y9
Application
SPECIAL 2 PSIG DELIVERY pressure twin stage regulator is
designed to reduce container pressure down to 2 PSIG. A line
pressure regulator is required downstream to reduce the 2 PSIG to a
nominal 11” W.C.
UL
®
Features
• Incorporates integral relief valve in the 2 PSIG stage portion of the
regulator.
• Designed to pass not more than 5 PSIG with the seat disc
removed.
• Large vent helps prevent blockage and has a ¾” [Link] for vent
piping.
• Built in pressure taps for both the 10 PSIG regulator and 2 PSIG
regulator, Plugs can be removed with a 3/16” hex Allen wrench.
LV404Y9
• Select Blue Finish to designate 2 PSIG delivery pressure for 2-
pound systems.
Materials
Body (First Stage).......................................................... Die Cast Zinc
Body (2 PSIG Stage) ..................................................... Die Cast Zinc
A Bonnet First Stage . ................................................................... Brass
Bonnet, Second Stage .................................................. Die Cast Zinc
Diaphragms ......................... Integrated Fabric and Synthetic Rubber
Springs ....................................................... Steel and Stainless Steel
Valve Discs ............................................................... Resilient Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Factory
Bonnet Vent
Inlet Outlet Delivery Adjustment 2 PSIG Bonnet Capacity
Part Number Orifice Size Position 1st
Connection Connection Pressure Range (PSIG) Vent Position BTU/HR*
Stage
(PSIG)
LV404Y9 [Link]
½” [Link] .219 2 1.8 to 2.5 Down Outlet 800,000
(CGA 510)
Maximum flow is based on 25 PSIG inlet pressure and 1.5 PSIG delivery pressure.
A24
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Two Stage Regulator Outfits 5807, 5808, 5820 Series
Application LV4403TR9
LV4403B Series
These outfits contain the equipment required to provide two-
stage regulation.
UL
®
Features PRODU
10
O
CT
• Includes a new pigtail. This helps ensure that a new pigtail is
RE
S
installed along with the regulator.
10
Y
NT
E
Y
AR A
WA R R
Features
• Includes a new pigtail. This helps ensure that a new pigtail is installed along
with the regulator.
PRODU
10
O
A
G
CT
RE
E
Y
AR A
WA R R
Ordering Information
2503-22
Twin Stage Pigtails Capacity BTU / hr.
Kit Number Regulator Included Inlet F. NPT Outlet F. NPT Included Propane
912JS12
5828 LV404B4 525,000
¼” ½” 912JS12
5832 LV404B23V9 200,000
regulation.
7525B23
Features PROD U
10
O
G
CT
RE
Y
NT
E
Y
AR A
Features
• All metal, die cast construction.
Materials
Body............................................................................... Die Cast Zinc
Bonnet ........................................................................... Die Cast Zinc
Springs ....................................................................................... Steel
Valve Seat Discs ...................................................... Resilient Rubber
Diaphragms ................................................ Molded Synthetic Rubber
302V
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Factory Vapor Capacity
Part Outlet Orifice Adjustment Bonnet Vent
Type Inlet Connection Delivery BTU/hr.
Number Connection Size Range Position
Pressure Propane*
302 ¼” F. NPT Small Vent Above
302S Soft M. POL w/60 DMS orifice Inlet
11” w.c. at
302V Single 3/8” F. No. 50 Drip Lip Above
¼” F. NPT 100 PSIG 9-13” w.c. 125,000
Stage NPT Drill Inlet
inlet
302V9 ¼” F. NPT Drip Lip at 9
302V9LS Soft POL w/o orifice o’clock
Maximum flow is based on 25 PSIG inlet pressure and 9” w.c. delivery pressure.
A26
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Low Pressure Single Stage Regulators
LV2302 Series
Application
A compact, sturdy regulator incorporating many of the quality features
found in larger domestic regulators. Ideal for outdoor LP-Gas grills.
The regulator reduces cylinder pressure down to burner pressure, UL
normally 11” w.c. It is intended for use on small portable appliances ®
that use 100,000 BTU’s/hr. or less. It may not be used on fixed pipe
systems per NFPA 58, 1995 edition.
Features
• Compact size with large capacity rating.
• Unique bonnet vent profile minimizes vent freeze over when properly
installed.
A
Materials
Body............................................................................... Die Cast Zinc
Bonnet ........................................................................... Die Cast Zinc
Springs ....................................................................................... Steel
Valve Seat Discs ...................................................... Resilient Rubber
Diaphragms ......................... Integrated Fabric and Synthetic Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Inlet Outlet Factory Delivery Adjustment Bonnet Vent Vapor Capacity BTU/hr.
Orifice Size
Number Connection Connection Pressure Range Position Propane*
LV2302A2 ¼” F. NPT 11” w.c. at 100
3/8” F. NPT No. 49 Drill 9”-13” w.c. Over Outlet 150,000
LV2302P M. POL PSIG Inlet
Maximum flow is based on 10 PSIG inlet pressure and 9” w.c. delivery pressure.
A27
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
High Pressure Industrial / Commercial Pounds-to-Pounds Regulators
597F Series
Application
Designed to reduce propane gas container pressure down to
between 3 and 100 PSIG. Ideal for liquid or vapor service, they
can be used in a variety of applications including salamander
heaters, weed burning torches, fish cookers, tar pot heaters, and
other industrial type services.
Features
• Provides high capacity performance at a reasonable price.
• Can be readily fitted with a pressure gauge in the 1/4” [Link] port.
Materials
• Molded diaphragm provides an o-ring like seal between the body Body............................................................................................. Zinc
and the bonnet. Bonnet ......................................................................................... Zinc
Springs ....................................................................................... Steel
• Fully painted in brilliant red for complete corrosion protection. Valve Seat Discs ...................................................... Resilient Rubber
A Diaphragms ......................... Integrated Fabric and Synthetic Rubber
• Available in four adjustable ranges for maximum performance. Adjusting Screw.......................................................................... Brass
• Bonnet and body are assembled in the USA using the unique,
patented RegULokSM Seal System.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Adjustment Outlet Recommended Delivery Capacity Determined at Capacity BTU/hr.
Inlet Connection
Number Method Connection Pressure Range (PSIG) Set Pressure of PSIG* Propane**
597FA 1-15 10 1,750,000
597FB 10-30 20 3,000,000
Tee Handle 1/4” NPT 1/4” NPT
597FC 20-45 30 3,500,000
597FD 40-100 40 4,500,000
* Set pressure established at 100 PSIG inlet and a flow of 250,000 BTU/hr.
** Capacity determined at actual delivery pressure 20% less than set pressure with inlet pressure 20 PSIG higher than the set pressure.
A28
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
High Pressure Industrial / Commercial Pounds-to-Pounds Regulators
1580M Series and AA1580M Series
Application
UL
®
Designed to reduce LP-Gas and anhydrous ammonia container
pressures to between 3 and 125 PSIG. Precision-built with a multi-
million BTU capacity, the 1580M series is perfect for such big, tough
jobs as crop dryers, asphalt batch mixing plants, road building “tar
wagons”, heat treating and other large industrial and commercial
loads. It’s also ideal as a first stage regulator in large multiple
operations. The AA1580M series is ideal for use in anhydrous
ammonia applications such as blue print machines and heat treating.
Features
• Large nozzle and straight through flow provides high capacity and
resistance to freeze-up.
Materials
PRODU
10
O
Body........................................................................ Forged Aluminum
G
CT
RE
E
Y
AR A
WA R R
Valve Seat Discs ...................................................... Resilient Rubber
Diaphragms ......................... Integrated Fabric and Synthetic Rubber
Ordering Information
Recommended Capacity
A
Delivery Determined at
Part Adjustment Inlet & Outlet Pressure Range B Height Set Pressure of
Number Service Method Connections (PSIG) A Width (max.) PSIG Capacity**
AA1582MW Tee Handle
3-25 20 2,100 CFH NH3
AA1582MK Hex Head ¼”
NH3 2 3
16 ” 4⅛”
AA1582ML F. NPT 20-50 30 2,400 CFH NH3
AA1582MH 45-125 60 2,600 CFH NH3
7,000,000
3-30 20
1584MN BTU/hr. LPG
7,500,000
LP-Gas 25-50 30
1584ML BTU/hr. LPG
½” 8,000,000
45-125 2 15
16 ” 4⅞” 60
1584MH F. NPT BTU/hr. LPG
AA1584MW 3-25 20 4,500 CFH NH3
AA1584ML NH3 20-50 30 4,800 CFH NH3
AA1584MH 45-125 60 5,100 CFH NH3
11,000,000
3-30 20
1586MN BTU/hr. LPG
Tee Handle
12,000,000
LP-Gas 25-50 30
1586ML BTU/hr. LPG
¾” 14,000,000
F. NPT 45-125 60
1586MH BTU/hr. LPG
AA1586MW 3-25 20 7,000 CFH NH3
AA1586ML NH3 20-50 3 ½” 7” 30 7,700 CFH NH3
AA1586MH 45-125 60 8,900 CFH NH3
11,000,000
3-30 20
1588MN BTU/hr. LPG
1” 12,000,000
LP-Gas 25-50 30
1588ML F. NPT BTU/hr. LPG
14,000,000
45-125 60
1588MH BTU/hr. LPG
* Set pressure is established with 100 PSIG inlet pressure and a flow of 500,000 BTU/hr. propane for 1580M Series, 90 CFH/hr. NH3 for
AA1582M Series and 180 CFH/hr. NH3 for AA1584M and AA1586M Series.
** Capacities determined at actual delivery pressure 20% less than set pressure with inlet pressure 20 PSIG higher than set pressure.
NOTE: Care must be taken to prevent re-liquification of propane at normal temperatures by heat tracing or other effective means. Use of a relief valve
upstream or downstream of these regulators is recommended in accordance with NFPA 58.
A29
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
High Pressure / High Temperature Industrial / Commercial Pounds-to-
Pounds Regulators X1584M, X1586M Series
Application
Designed to reduce LP-Gas container pressures to between 3 and
50 PSIG. Ideal for crop drying, heat treating, asphalt batch mixing UL
®
Features
• Special diaphragm and seat materials are suitable for up to 300ºF.
temperatures.
• Large nozzle and straight through flow provides high capacity and
resistance to freeze ups.
10
O
G
CT
E
Y
AR A
Backup Seal ....................... High Temperature Resilient Composition WA R R
Ordering Information
Inlet & Outlet Recommended Delivery Capacity Determined at Capacity BTU/hr.
Part Number Service Adjustment Method
Connections Pressure Range (PSIG) Set Pressure of PSIG* Propane**
X1584MN 3-30 20 7,000,000
½” F. NPT
X1584ML 25-50 30 7,500,000
X1586MN 3-30 20 11,000,000
LP-Gas Tee Handle ¾” F. NPT
X1586ML 25-50 30 12,000,000
X1588MN 3-30 20 11,000,000
1” F. NPT
X1588ML0 25-50 30 12,000,000
* Set pressure is established with 100 PSIG inlet pressure and a flow of 500,000 BTU/hr. propane.
** Capacities determined at actual delivery pressure 20% less than set pressure with inlet pressure 20 PSIG higher than set pressure.
NOTE: Care must be taken to prevent re-liquification of propane at normal temperatures by heat tracing or other effective means. Use of a relief valve upstream or downstream of these regulators is
recommended in accordance with NFPA 58.
A30
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Vapor Relief Valves
3139 Series
Application
Designed for use as a relief valve on first stage regulators that comply
with the NFPA 58 [Link] exception: “first stage regulators with a
rated capacity of more than 500,000 BTU/hr. shall be permitted to
have a seperate relief valve.
Features
• Pop-action design keeps product loss to a minimum. UL
®
PRODU
10
G O
CT
RE
S
10
Y
E NT
Y
AR A
WA R R
3139-18 3139-26 3139-39
Flow Capacity
at 120% of Set
Part Number Set Pressure Regulator Settings Connection Size Height Width
Pressure
(SCFH Propane)
3139-18 18 PSIG 10 PSIG 1357*
3139-26 26 PSIG 15 PSIG ¼” M. NPT 2 27/32” 1 1/16” 1725**
3139-38 38-PSIG 20 PSIG 2304***
* Flow recorded at 21.6 PSI inlet pressure for this valve.
** Flow recorded at 31.2 PSI inlet pressure for this valve.
*** Flow recorded at 45.6 PSI inlet pressure for this valve.
A31
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Copper Pigtails
912 and 913 Series
Straight Pigtails Ordering Information Application
Part Number
¼” Tube ⅜” Tube Pigtails are available in a variety of connections, sizes and styles.
Care should always be taken in selecting the proper pigtail for a
Approximate ⅞” Hex 1⅛” Hex ⅞” Hex
particular application.
Connections Length Short Nipple Long Nipple Short Nipple
5” - ½” 913JS05 Note: Engineered Controls International, Inc. recommends a new
12” 912PS12 - 913PS12
pigtail be installed with every new and replaced regulator.
[Link] x 20” 912PS20 912PA20 913PS20
[Link] 30”
36”
912PS30
912PS36
-
912PA36
913PS30
913PS36
Features
48” 912PS48 912PA48 913PS48 • Heavy duty construction.
12” 912FS12 - - • Individually soldered connections to the copper tubing.
¼” Inverted 20” 912FS20 912FA20 - • Each pigtail is individually tested prior to shipment.
Flare x [Link] 30” 912FS30 - -
36” 912FS36 - -
5” - - 913JS05 Materials
¼” [Link] x 12” 912JS12 - - Tubing...................................................................................... Copper
[Link] 20” 912JS20 - - Connection ................................................................................ Brass
36” 912JS36 - - 913PS12
½” [Link] x UL
12” - - 913LS12
[Link]
®
10
O
¼” M. NPT x
G
CT
913JS05A
RE
M. POL 5” 90°
10
913PS05A
NT
E
Y
AR A
WA R R
M. POL x 913PS12G 270° Right Hand
913JS05A 913PS12G 913PS05A M. POL 12” 913PS12H 270° Left Hand
A 913PS12S 360°
Inlet Fittings
These inlet fittings are available for assembly into either first stage
of single stage regulators. All have 1⁄4” M. NPT connections and are
machined from brass.
90 210
R
612-PG 30 270
612-PG 60 240
60 240
0 300
30 270 30
0
270
300
POL (CGA 510)
POL (CGA 510)
0 300
1/4” NPT
POL (CGA 510)
... ECII
MA ...
R
A32
Flat Blade Screw Slot Flat Blade Screw Slot
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Brackets
RegO® Brackets are especially designed for use in installing RegO®
PRODU
Regulators in applications requiring the use of a bracket.
10
O
CT
RE
S
10
Y
Part
NT
E
Y
AR A
WA R R
Number Material For Use With Regulator Model:
2302-31 Cadmium 2302 Series/404B23
2503-22 Plated Steel
LV404 Series, 2503 Series LV4403 Series
2503-19 Aluminum
2503-19 2503-22 2302-31
Manifolds
Application
For use in systems that require uninterrupted gas service during
cylinder exchange. Especially for summer cottages, mobile homes
and single appliance loads.
1350R
• Floating disc check minimizes discharge of gas to the atmosphere
when empty cylinder is being replaced.
Features
• Floating disc check minimizes discharge of gas to the atmosphere
when empty cylinder is being replaced.
Materials A
Body............................................................................... Forged Brass
Seat Discs ................................................................ Resilient Rubber
CT
RE
Y
NT
E
Y
AR A
WA R R
Application
Use with suitable pigtails to connect multiple cylinders together. Ideal
for loads that require more than one cylinder to be in service at a
time. UL
®
Features
• Provides a three-way tee function without an internal disc check. 1350E
Materials
Body............................................................................... Forged Brass
10
O
1450R
G
CT
Y
NT
E
Y
AR
WA R RA
A33
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Test Kits
PRODU
10
O
G
Low Pressure Test Set
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
2434A Series
1328 Adapter
10
O
1212 Kit
CT
RE
A
S
Application
10
Y
NT
E
Y
AR A
WA R R
The water manometer kit is especially suited for use with low pressure
LP-Gas systems. It is ideal for pressure checks downstream of the
low pressure regulator and at the appliances.
Features
• Flexible tube rolls up for convenient storage with accessories in
compact carry case.
• Magnetic clips allow easy attachment to metal surfaces.
• Flexible spring steel scale is calibrated in inches of water column for
reading to 16” w.c.
• Molded nylon tubing connectors incorporate a rapid shut-off design
in an unbreakable molded top.
• Rapid pressure safety trap prevents loss of fluid due to pressure
surges on both columns.
• Scale is center mounted between columns to eliminate parallax
error and has a full two-inch sliding zero adjustment.
Contents
1—Rubber tubing adapter and 7⁄16” spud. 1212 KIT Flexible Tube Water Manometer Kit
A34
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Accessories
10
O
CT
2962
RE
S
10
Y
NT
E
Y
AR A
WA R R
Designed for testing high pressure lines. Adapter has 0 to 300 PSIG
gauge. A bleeder valve allows you to bleed down to correct pressure
during pressure tests.
2962
Part
Number Description
LV4403-400 Adhesive Warning Label
A35
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Accessories
Warning Notice
A36
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
B B
Section B
Cylinder and Service Valves
B1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
LIMITED 10 YEAR WARRANTY AND LIMITATION OF LIABILITY liability below, ECII MAKES NO OTHER WARRANTY, EXPRESS
OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
LIMITED 10 YEAR WARRANTY WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, with respect to its products and parts,
Engineered Controls International, Inc. (“ECII”) warrants to the original whether used alone or in combination with others. ECII disclaims all
purchasers the products and repair kits manufactured by it to be free warranties not stated herein.
from defects in materials and workmanship under normal use and
service for a period of 10 years from the date of manufacture. If within
thirty days after buyer’s discovery of what buyer believes is a defect,
buyer notifies in writing and ships the product to ECII at 100 Rego LIMITATION OF LIABILITY
Drive, Elon, NC 27244, ECII, at its option, and within forty-five days of
receipt , will repair, replace F.O.B. point of manufacture, or refund the
purchase price of that part or product found by ECII to be defective.
Failure of buyer to give such written notice and ship the product within NOTICE TO USERS OF PRODUCTS
thirty days shall be deemed an absolute and unconditional waiver of
any and all claims of buyer arising out of such defect. The Limited Warranty stated above is a factory warranty to the first
purchasers of ECII products. Since most users have purchased
This warranty does not extend to any product or part that is not these products from ECII distributors, the user must within thirty (30)
installed and used continuously after installation in accordance with days after the user’s discovery of what user believes is a defect,
ECII’s printed instructions, all applicable state and local regulations, notify in writing and return the product to the distributor from whom
and all applicable national standards, such as those promulgated by he purchased the product/part. The distributor may or may not at
NFPA, DOT and ANSI. This warranty does not extend to any product the distributor’s option choose to submit the product/parts to ECII,
or part that has been damaged by accident, misuse, abuse, failure to pursuant to this Limited Warranty. Failure by buyer to give such
maintain, or neglect, nor does it extend to any product or part which written notice within thirty (30) days shall be deemed an absolute and
has been modified, altered, disassembled, or repaired in the field. unconditional waiver of buyer’s claim for such defects. Acceptance
This warranty does not cover any cosmetic issues, such as scratches, of any alleged defective product/parts by ECII’s distributor for
dents, marring, fading of colors or discoloration. replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
Except as expressly set forth above, and subject to the limitation of
B2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
B
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Cross Reference by Part Number.................................... B20
Cylinder Valves................................................................... B9
Design Features of RegO® Cylinder Valves...................... B8
Safety Warnings................................................................. B4
Service Valves.................................................................. B15
Warnings and Labels........................................................ B18
B3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Cylinder and Service Valves
Safety Warnings Purpose
In its continuing quest for safety, Engineered Controls International, Inc. publishes a series of bulletins explaining
the hazards associated with the use, misuse, and aging of LP-Gas valves and regulators. It is hoped that these
factual bulletins will make clear to LP-Gas dealer managers and service personnel, that the utmost care and
attention must be used in the installation, inspection, and maintenance of these products, or problems could
occur which would result in injuries and property damage.
The National Fire Protection Association Pamphlet #58 - 2004 Edition, “Liquified Petroleum Gas Code” states in
Section 1.5 that, “persons who transfer liquid LP-Gas, who are employed to transport LP-Gas, or whose primary
duties fall within the scope of this code shall be trained in proper handling procedures. Refresher training shall
be provided at least every three years. The training shall be documented.” These “ECII® Safety Warnings”
may be useful in training new employees and reminding older employees of hazards that can occur. It is
recommended that all employees be furnished with a copy of NPGA Safety Pamphlet 306, “LP-Gas Regulator
and Valve Inspection and Maintenance.”
Important Factors:
Check cylinder valves for leaking components every time cylinders 1. Installation: It should not be necessary to remind the readers that
are filled. cylinder valves must be installed and used in strict conformance with
NFPA Pamphlet 58, and all other applicable codes and regulations.
Codes, regulations and manufacturers’ recommendations have been
developed by experts with many years of experience in the LP-
The bulletin is not intended to be an exhaustive treatment of the Gas industry in the interest of safety for users of LP-Gas and all
subject of cylinder valves and certainly does not cover all safety personnel
B4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Cylinder and Service Valves
5. The liquid service shut-off valve, with excess flow valve provided
on some cylinder valves, is also of critical importance. The excess
flow valve must be periodically tested for proper performance, in
addition to the inspection of the shut-off valve.
6. The fixed liquid level gauge on a cylinder valve is, when present,
essential to prevent overfilling the cylinder. The gauging valve must
operate freely, venting vapor when loosened, and sealing gas-tight
easily when tightened with the fingers. Gauge valves meant for
use with a socket key or screwdriver must also seal easily without
excessive torque. The fixed liquid level gauge diptube must be of
the proper length, and be in proper position. Periodic test should be
conducted by weighing the cylinder after filling, to determine that it
does not contain more than the allowable amount of LP-Gas. This At the very minimum, it is desirable that these customers:
check should be done periodically, and any time there is suspicion
that the gauge diptube may be damaged or broken. 1. Know the odor of LP-Gas and what to do in case they smell gas.
Use of the NPGA “Scratch ’n Sniff” leaflet could be productive.
The environment and conditions of use will determine the safe service
life of these products. Periodic inspection and maintenance are
essential. Because ECII® Products have a long and proven record
of quality and service, LP-Gas dealers may forget the hazards that
Since cylinders are often used by consumers without previous can occur because a cylinder valve is used beyond its safe service
knowledge of the hazards of LP-Gases and the LP-Gas dealers life. Life of a cylinder valve is determined by the environment in which
are the only ones who have direct contact with the consumers, it it “lives”. The LP-Gas dealers know better than anyone what this
is the dealers’ responsibility to make sure that his customers environment is. NOTE: There is a developing trend in state legislation
are properly instructed in safety matters relating to their and in proposed national legislation to make the owners of products
installation. responsible for replacing products before they reach the end of their
safe useful life. LPGas dealers should be aware of legislation which
could affect them.
B5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Thread Specifications
Cylinder Valve Threads Because of the many thread forms available on equipment used in
the LP-Gas industry today, the maze of letters, numbers and symbols
which make up various thread specifications becomes confusing. To
help eliminate some of this confusion, a brief explanation of some of
the more widely used thread specifications is shown below.
Outlet Connections
CGA Outlets
The CGA (Compressed Gas Association) outlets are standard for use
with various compressed gases. The relation of one of these outlets Copper Tubing
Cylinder
Valve
to another is fixed so as to minimize undesirable connections. They Nut
Outlet
have been so designed to prevent the interchange of connections
which may result in a hazard.
CGA 182, or SAE Flare
This connection assures a leak-tight joining of copper tubing to brass
3/8”-18 NPT Thread Connection
parts without need for brazing or silver soldering. The common size
This connection also is used for vapor or liquid withdrawal. It has a
B 3⁄8” diameter thread, and 18 threads per inch, National Pipe Taper
used on LP-Gas valves and fittings is 3⁄8” SAE (Society of Automotive
Engineers) flare. Although this connection is referred to as a 3⁄8”,
Outlet form.
because 3⁄8” OD tubing is used, the thread actually measures 5⁄8”.
The specifications are .625 – 18 UNF – 2A – RH – EXT, which means
Cylinder Valve Outlet .625” diameter thread, 18 threads per inch, Unified Fine Series Class
2 Tolerances, right-hand, external thread.
Nipple
Nut
CGA 555
CGA 555 is the standard cylinder valve outlet connection for liquid
withdrawal of butane and/or propane. Thread specification is .903” –
14 NGO – LH – EXT, which means .903” diameter thread, 14 threads Cylinder
Nipple Valve
per inch, National Gas Outlet form, left-hand external thread. Nut Outlet
Type I Outlet
This connection is designed to mate with either a 15⁄16” Female
ACME or a Male POL (CGA510). It complies with the ANSI Z21.58
Standard for Outdoor Cooking Appliances and the Can/CGA-1.6
Standard for Container Connections. A back check assembly in the
outlet is designed to prevent gas flow until a leak free connection is
made with an inlet adapter. These standards apply to barbecue grill
cylinders manufactured after October 1994.
B6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Cylinder and Service Valves
Heavy-Duty Valve Stem Seals
General Information ECII®/RegO® Cylinder Valves utilize seat discs and stem seals which
The wide acceptance of ECII®/RegO® Cylinder Valves is based on resist deterioration and provide the kind of reliable service required
their reliable performance as well as their reputation for engineering for LP-Gas utilization. Diaphragm or O-Ring stem seals are available.
and manufacturing excellence. Together with thorough testing, these Valves with diaphragm stem seals are recognized for their heavy-
efforts result in years of trouble-free service. ECII®/RegO® Cylinder duty body design and are suitable for use in cylinders up to 200
Valves are listed by Underwriters’ Laboratories and approved by the lbs. propane capacity. O-Ring type stem seals are the most widely
Bureau of Explosives for pressure relief valve operation, wherever accepted in the industry. The simple, economical and long life design
applicable. See section on relief valves for important information. features a tapered and confined nylon seat disc which provides
positive, hand-tight closings, and a faster filling cylinder valve.
Instructions for the Proper Use and Applications 2. Do not use excessive force in opening or closing the valves. The
of ECII®/RegO® Cylinder Valves seat disc and diaphragm materials permit the valves to be opened
and closed easily by hand. Never use a wrench on wheel handle
1. Containers and pipe line should be cleaned thoroughly before valves. B
valves are installed. Large particles of solid foreign matter can cut the
seating surface of any resilient seat disc, causing the valve to leak. 3. When the design of the piping installation allows liquid to be locked
Care must be exercised in inserting valves into lines or containers to between two valves, a hydrostatic relief valve must be installed in the
avoid damaging or exerting pressure against pressure relief valves line between the two valves. The pressures which can develop due
and outlet connections. Use a minimum amount of a suitable luting to temperature increase in a liquid full line are tremendous and can
compound on the cylinder valve threads only. Excess amounts of cause rupture of the line or damage to the valves.
luting compound can foul the operating parts of the valves.
4. The valves are designed to withstand normal atmospheric
temperatures. They should not, however, be subjected to abnormally
high temperatures.
B7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Design Features of ECII® / RegO® Cylinder Valves
Valve Stems On 901, 903, 9101 and Back Seat On 901, 9101 and
9103 Valves 9103 Valves
Are machined with a double lead thread Is metal-to-metal seating to provide
for quick opening and closing as well as added protection against leakage
high lift. whilethe valve is open. Back seat the
valve while in operation.
Seat Disc
Tapered Seat Openings Is a tapered nylon in a fully confined
On 9101 and 9103 Valves seat to ensure easy, leak-free, positive
Permit increased flow rates shutoffs. Seat disc also provides a
resulting in faster charging. separate swivel action to minimize
scoring by impurities.
B8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Heavy-Duty Cylinder Valves for Vapor Withdrawal
9103 Series
Application
This heavy duty cylinder valve is designed for vapor withdrawal of
DOT cylinders up to 100 lbs. propane capacity. It is used in domestic
hookups, and industrial commercial installations.
Features
• Equipped with a fast filling throat and high lift, o-ring stem seal
design.
Materials
Body............................................................................... Forged Brass
Handwheel.......................................................................... Aluminum 9103D
Stem........................................................................................... Brass
O-Rings..................................................................... Resilient Rubber
Seat Disc.................................................................................... Nylon
Relief Spring................................................................ Stainless Steel
PRODU B
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Fixed For Use in Approximate Filling Rate Liquid Flow, GPM Accessories
Pressure
Liquid Dip Tube Cylinders
Part Container Service Relief Pressure Drop Across Valves
Level Vent Length w/ w/Propane
Number Connection Connection Valve POL Plug
Valve Deflector Capacity
Setting 10 PSIG 25 PSIG 50 PSIG 100 PSIG
Style Up To:
9103D10.6 F. POL 10.6”
3/4” M NGT Knurled 375 PSIG 100 lbs. 12.7 20.3 29.0 41.3 N970P
9103D11.6 (CGA 510) 11.6”
IMPORTANT: 1⁄4” O.D. pigtails or POL connections for 1⁄4” O.D. pigtails should not be used with these valves.
NOTES: To ensure proper functioning and maximum protection from excess flow valves, the cylinder valve should be fully opened
and backseated when in use. These valves incorporate an excess flow valve. Refer to L-500 / Section F, for complete information
regarding selection, operation and testing of excess flow valves.
B9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Tamper-Resistant Cylinder Valve with Outlet Check
for Vapor Withdrawal 9103T9F
Application
UL
®
Features
• Minimizes the risk of unauthorized persons withdrawing propane
from cylinders not in service. It is necessary to install a male POL
connection to open the outlet check to withdraw vapor from the
valve.
• Ball type excess flow located in the valve inlet protects against
excessive discharge if the cylinder is tipped or the hose ruptures.
Closing flow is 200 SCFH at 100 PSIG.
• Outlet seal plug on a heavy duty chain prevents dirt from entering
POL when not in use.
B
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast
Stem........................................................................................... Brass
O-Rings..................................................................... Resilient Rubber
Seat Disc.................................................................................... Nylon
Relief Spring................................................................ Stainless Steel
Plug............................................................................................ Brass
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Approximate Filling Rate Liquid Flow, GPM
Fixed Liquid Pressure
Part Container Service For Use in Cylinders w/
Level Vent Relief Valve Pressure Drop Across Valves
Number Connection Connection Propane Capacity Up To:
Valve Style Setting
10 PSIG 25 PSIG 50 PSIG 100 PSIG
¾” F. POL 375
9103T9F None 100 lbs. 5.0 7.6 10.7 14.9
M. NGT (CGA 510) PSIG
B10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cylinder Valve for RV and Small ASME System Vapor Withdrawal
9106CO
Application
Designed especially for vapor withdrawal service in small ASME
containers with surface area up to 23.8 square feet. UL flow capacity
is 645 SCFM/air.
Features
• One-piece relief valve is shielded from tampering and damage.
UL
®
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast
Stem........................................................................................... Brass
Seat Disc.................................................................................... Nylon
Relief Spring................................................................ Stainless Steel
10
O
Approx.
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Container Service Fixed Liquid Level Pressure Relief Valve For Use In Cylinders w/ Propane Flow Capacity
Part Number
Connection Connection Vent Valve Style Setting Capacity Up To SCFM/Air
¾” F. POL 312 ASME
9106CO none 645
M. NGT (CGA 510) PSIG Tanks*
* Surface area up to 23.8 square feet.
B11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cylinder Valve for Liquid Withdrawal
9107K8A
Application
Equipped with excess flow valves and liquid withdrawal tubes, they
are designed for liquid withdrawal of DOT cylinders up to 100 lbs.
propane capacity. They are most often used with heavy BTU loads
found in industrial uses.
Features
• O-ring stem seal design.
Materials
Body............................................................................... Forged Brass
B Handwheel............................................................ Aluminum Die Cast
Seat Disc.................................................................................... Nylon
O-Rings..................................................................... Resilient Rubber
Relief Spring................................................................ Stainless Steel
Stem........................................................................................... Brass
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Container Fixed Liquid Level Vent Valve Dip Tube Length w/
Part Number Service Connection Liquid Withdrawl Tube Length
Connection Style Deflector
¾”
9107K8A CGA 555 Knurled 11.6” 44”
M. NGT
B12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
“Dual” Cylinder Valve for Simultaneous Liquid and Vapor Withdrawal
8556
Application
UL
®
This dual cylinder valve was designed especially for industrial uses.
It increases the cylinder’s flexibility by permitting DOT cylinders
up to 100 lbs. propane capacity to be used interchangeably or
simultaneously for either liquid or vapor withdrawal.
Features
• Two separate flow channels in the body permit vapor and/or liquid
withdrawal alternately, or simultaneously.
• Furnished with a 3⁄8” O.D. stainless steel liquid withdrawal tube with
a “T” dimension of 44”.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast B
Stem........................................................................................... Brass
Seat Disc.................................................................................... Nylon
O-Rings..................................................................... Resilient Rubber
Relief Spring................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Container Service Connection
Part Number Fixed Liquid Level Vent Valve Style Liquid Withdrawl Tube Length
Connection Vapor Liquid
*
To ensure proper functioning and maximum protection from integral excess flow valves, the cylinder valve should be fully opened and backseated when in use.
NOTE: These valves incorporate an excess flow valve. Refer to L-500/Section F, for complete information regarding selection, operation and testing of excess flow valves.
B13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Service Valves for ASME and DOT Containers or Fuel Line Applications
901C1, 9101C, 9101D, and 9101R Series
UL
Application ®
Features
• O-Ring stem seal design provides positive seal.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast
Stem........................................................................................... Brass
B O-Rings..................................................... Resilient Synthetic Rubber
Seat Disc.................................................................................... Nylon 9101R1
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
9101D
Ordering Information
Approximate Filling Rate Liquid Flow, GPM
Fixed Liquid Pressure Drop Across Valve
Container Service Level Vent
Part Number Bonnet Style Connection Connection Valve 10 PSIG 25 PSIG 50 PSIG 100 PSIG
901C1 5.3 8.2 10.8 14.2
No
9101C1 8.8 12.4 15.8 21.7
Standard
9101D11.1
F. POL Yes 8.6 12.7 16.3 22.3
9101D11.7 ¾” M. NGT
CGA 510
9101R1 No
9101R11.1 MultiBonnet 7.6 11.7 15.2 20.6
Yes
9101R11.7
Note Since these valves have no integral pressure relief valve, they can be used on any container with an independant relief device sufficient for that tank’s capacity.
B14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Service Valves for ASME Motor Fuel Containers
901C, 9101H, and 9101Y Series
Application
Designed specifically for vapor or liquid withdrawal service on ASME
UL
®
The integral excess flow valve found in all these service valves helps
prevent excessive product loss in the event of fuel line rupture.
Features
• Incorporates integral excess flow valve and shut-off valve in one
unit. 9101H5
B
• Metal-to-metal back seat provides added protection against leakage
while the valve is open.
• 9101H6 equipped with a 1⁄4” NPT internal thread for the addition of
a liquid withdrawal tube.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast
Stem........................................................................................... Brass
O-Rings..................................................... Resilient Synthetic Rubber
Seat Disc.................................................................................... Nylon
9101Y5H
Ordering Information
Closing Flow (LP Gas)
Liquid Vapor
Container Service Withdrawal
Part Number Connection Connection Connection 25 PSIG Inlet (SCFH) 100 PSIG Inlet (SCFH) Liquid GPM
901C3 350*** 605*** 1.5***
F. POL CGA 510
901C5 None 550*** 1050*** 2.6***
9101H5* 765** 1300** 3.6**
¾”M. NGT ⅜” SAE Flare
9101H6* ¼” NPT 550**** 1050**** 2.6****
60° Angle
9101Y5H* None 550** 1050** 3.6**
⅜” SAE Flare
* Heavy-duty models PRODU
10
O
** Based on 3⁄8” O.D. pigtail, 20” long or less, connected to valve outlet. For greater lengths, the pigtail must have a larger O.D.
G
CT
RE
*** Same as (**). In addition, 1⁄4” O.D. pigtails or POL connections for 1⁄4” O.D. should not be used with this valve.
**** Based on 3⁄8” O.D. pigtail; 20: long or less, connected to valve outlet. Also based on 1⁄4” pipe size dip tube, 42” long or less, attached to special inlet
10
Y
NT
E
connection. For longer pigtail lengths, the diameter of the pigtail must be increased.
Y
AR
WA R R
A
NOTE: These valves incorporate an excess flow valve. Refer to L-500/Section F, for complete information regarding selection, operation and testing of excess flow valves.
B15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Service Valves for DOT Fork Lift Containers
9101P5 and 9101P6 Series
Application
Designed specifically for vapor or liquid withdrawal service on DOT
fork lift containers. Valves with 1.5 GPM closing flow are for use in
small and medium size lift truck applications, while those with 2.6
GPM closing flow are for large lift trucks. Since none of these valves
have an integral pressure relief valve, they may only be used as an
accessory valve on containers that have an independent pressure
relief valve sufficient for that cylinders capacity.
The integral excess flow valve found in all these service valves helps
prevent excessive product loss in the event of fuel line rupture.
When installed for liquid withdrawal, the 9101P6 Series has provisions
for attachment of a liquid withdrawal tube. The 9101P5 Series must
be installed in containers that have provisions for a separate liquid
withdrawal.
• 9101P6 Series equipped with a 1⁄4” NPT internal thread for the
addition of a liquid withdrawal tube.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast 9101P6 PRODU
10
O
Stem........................................................................................... Brass 9101P6H
G
CT
RE
Y
NT
E
Y
AR A
WA R R
Ordering Information
Approximate Filling Rate Liquid
Closing Flow (LP-Gas) Flow, GPM Accessories
B16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Adhesive Warning Labels
901-400 and 903-400
B
DO NOT REMOVE, DEFACE OR OBLITERATE THIS LABEL—DO NOT FILL THIS CONTAINER UNLESS THIS LABEL IS READABLE.
ADDITIONAL SAFETY INFORMATION
IS AVAILABLE FROM: Engineer ed Cont ro ls
® International, Inc. Printed in U.S.A. 04-0994-1189 Part No. 901-400
100 RegO Drive PO Box 247 Elon College, NC 27244 USA Phone (336) 449-7707 Fax (336) 449-6594 www .regoproducts.c om
DO NOT REMOVE, DEFACE OR OBLITERATE THIS LABEL—DO NOT FILL THIS CYLINDER UNLESS THIS LABEL IS READABLE.
ADDITIONAL SAFETY INFORMATION 100 RegO Drive PO Box 247 Elon College, NC 27244 USA Printed in U.S.A. 05-0994-1086
IS AVAILABLE FROM: Phone (336) 449-7707 Fax (336) 449-6594 [Link] Warning No. 903-400
B17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Warning Notice
B18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cross Reference by Part Number
8556................................................................................................B13 9101P5H.........................................................................................B16
901-400...........................................................................................B17 9101P6............................................................................................B16
901C1.............................................................................................B14 9101P6H.........................................................................................B16
901C3.............................................................................................B15 9101R1...........................................................................................B14
901C5.............................................................................................B15 9101R11.1.......................................................................................B14
903-400...........................................................................................B17 9101R11.7.......................................................................................B14
9101C1...........................................................................................B14 9101Y5H.........................................................................................B15
9101D11.1.......................................................................................B14 9103D10.6........................................................................................B9
9101D11.7.......................................................................................B14 9103D11.6.........................................................................................B9
9101H5...........................................................................................B15 9103T9F..........................................................................................B10
9101H6...........................................................................................B15 9106CO........................................................................................... B11
9101P5............................................................................................B16 9107K8A.........................................................................................B12
B19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
B
B20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
C C
Section C
Multivalve® Assemblies
C1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
LIMITED 10 YEAR WARRANTY AND LIMITATION OF LIABILITY liability below, ECII MAKES NO OTHER WARRANTY, EXPRESS
OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
LIMITED 10 YEAR WARRANTY WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, with respect to its products and parts,
Engineered Controls International, Inc. (“ECII”) warrants to the original whether used alone or in combination with others. ECII disclaims all
purchasers the products and repair kits manufactured by it to be free warranties not stated herein.
from defects in materials and workmanship under normal use and
service for a period of 10 years from the date of manufacture. If within
thirty days after buyer’s discovery of what buyer believes is a defect,
buyer notifies in writing and ships the product to ECII at 100 Rego LIMITATION OF LIABILITY
Drive, Elon, NC 27244, ECII, at its option, and within forty-five days of
receipt , will repair, replace F.O.B. point of manufacture, or refund the
purchase price of that part or product found by ECII to be defective.
Failure of buyer to give such written notice and ship the product within NOTICE TO USERS OF PRODUCTS
thirty days shall be deemed an absolute and unconditional waiver of
any and all claims of buyer arising out of such defect. The Limited Warranty stated above is a factory warranty to the first
purchasers of ECII products. Since most users have purchased
This warranty does not extend to any product or part that is not these products from ECII distributors, the user must within thirty (30)
installed and used continuously after installation in accordance with days after the user’s discovery of what user believes is a defect,
ECII’s printed instructions, all applicable state and local regulations, notify in writing and return the product to the distributor from whom
and all applicable national standards, such as those promulgated by he purchased the product/part. The distributor may or may not at
NFPA, DOT and ANSI. This warranty does not extend to any product the distributor’s option choose to submit the product/parts to ECII,
or part that has been damaged by accident, misuse, abuse, failure to pursuant to this Limited Warranty. Failure by buyer to give such
maintain, or neglect, nor does it extend to any product or part which written notice within thirty (30) days shall be deemed an absolute and
has been modified, altered, disassembled, or repaired in the field. unconditional waiver of buyer’s claim for such defects. Acceptance
This warranty does not cover any cosmetic issues, such as scratches, of any alleged defective product/parts by ECII’s distributor for
dents, marring, fading of colors or discoloration. replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
Except as expressly set forth above, and subject to the limitation of
C2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
C
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Cross Reference by Part Number................................................. C12
Multivalve® Assemblies................................................................... C4
Warnings....................................................................................... C12
C3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO Multivalve® Assemblies
General Information Comprehensive Testing —
RegO Multivalves were pioneered in the 1930’s. By combining several
® • Every Multivalve® must pass a stringent underwater leakage test
valve functions in one unit, Multivalves® made possible new and more prior to shipment.
practical tank designs (fewer openings and smaller, less cumbersome • Multivalves® with pressure relief valves are individually tested and
protective hoods). They received immediate acceptance. adjusted to assure proper pressure settings.
The Multivalve® design has kept pace with changing industry needs • Those equipped with excess flow checks are tested for compliance
over the years. They are as popular as ever; still keeping fabricating with published closing specifications and for leakage after closing.
costs down and reducing operating expenses for the LP-Gas dealer. Pressure Relief Valves and Other Devices —
RegO Multivalves® Reduce the Cost of Fabrication by • Multivalves® equipped with integral pressure relief devices employ
• Combining several valve functions in one less expensive body. full-capacity, “pop-action” reliefs with set pressures of 250 psig for
ASME use and 375 psig for DOT cylinders.
• Reducing the number of threaded openings in ASME containers.
Double Back-Check Filler Valves —
• Diminishing the size and cost of protective hoods.
• Multivalves® with filling connections have double backcheck safety.
• Providing generous sized wrenching bosses for quick, easy
If the upper check ceases to function, the lower stand-by check will
installation.
continue to protect the filling connection from excessive leakage.
RegO Multivalves® Reduce LPG Dealer Expenses by
Ease of Maintenance —
• Permitting on-site filling of 100 lb. to 420 lb. DOT cylinders, thus
• Standardization of parts makes it possible for one repair kit to
eliminating cylinder return and interrupted customer service.
maintain the bonnet assemblies of RegO® cylinder valves, service
• Providing well-placed hose connections for easy filling. valves, motor fuel valves, and Multivalves®.
• Allowing ample space for secure attachment and easy removal of RegO Multivalves® fit every LP-Gas need.
the regulator.
• Wide selection of Multivalves® for domestic, commercial, and
• Providing substantial savings of bonnet repairs on valves with the industrial needs are available.
MultiBonnet.®
• Multivalves® may be ordered with pressure relief, liquid level tube,
RegO Multivalves® Satisfy Customer Demands for Tough, Safe filler valve, vapor equalizing valve, internal pipe connections, liquid
Equipment with These Features filling and withdrawal connections, and 1⁄4” NPT tapped opening for
Heavy-Duty Valve Stem Seals — pressure gauge with or without steel plug.
• Tapered nylon disc in a fully confined seat resist deterioration and
provide hand-tight closings over a long service life.
Seal Cap
Molded from tough, resilient
plastic to protect threads
and internal working parts.
Designed to protect the filler UL Shear Point
opening against dirt and other Provides for a shear just
foreign materials. Also acts below the ACME threads to
as a secondary pressure seal. protect the container in case
of a pullaway while the hose
Long Wearing Gasket is connected. The ACME
Permits leak-free, hand-tight connection should shear off
connection of the hose on an angle pull, leaving the
coupling to the filler valve. body and check assembly of
the valve still in place.
Forged Brass Body
Filler Seat Disc
Fabricated of special
synthetic composition and
made extra thick for
longer life.
MultiBonnet®
Designed to allow quick and Valve Guide
easy repair of bonnet pack- A precision machined “stem”
ings on Multivalves® on to assure positive alignment
active propane systems.
“Pop Action” Pressure Relief
Provides quick release of
excess pressure. Relief seat
disc is special resilient
composition rubber designed
to resist bonding to the
valve seat even after years
of service.
C4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO Multibonnet® Assemblies
Handwheel
Aluminum die cast handwheel.
Non-Rising Stem
Designed to allow easy backseating and long
service life.
Internal O-ring
External O-ring
Nameplate C
Provides easy identification of the RegO
MultiBonnet®.
Teflon Backseat
Provides for upper packing isolation when valve
is fully open.
Application
The MultiBonnet® is designed to allow quick and easy repair of bonnet • Available on certain new Multivalves® and service valves as well as
packings in certain Multivalves® and service valves on active propane repair assemblies for many existing RegO® valves.
systems. It allows you to repair valve bonnet stem o-ring leaks in • UL listed as a component of valve assembly.
minutes, without interrupting gas service to your customers.
Here’s How The MultiBonnet® Works
• Eliminates the need to evacuate tanks or cylinders to repair the
• When the valve is fully open, only the lower stem will rise and
MultiBonnet® packing.
backseat against the teflon washer which isolates the upper
• Two section design allows repair of MultiBonnet® assemblies on packing.
active propane systems without interruption in gas service or
• This allows you to remove the upper packing nut, which contains
shutting off appliances downstream. This helps to prevent time
the o-rings, and replace it while the valve is fully open and gas
consuming relighting of pilots, special appointments, and call
service not interrupted.
backs.
• Cost of replacing the MultiBonnet® packing is only 1/3 as much as
replacing a complete bonnet assembly—not including time cost
savings, which can be substantial.
C5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ASME Multivalves® for Vapor Withdrawal
G8475R Series
Application
These Multivalves® are designed for use in single opening UL
ASME containers equipped with a 21⁄2” M. NPT riser. They ®
• Designed for installation of a 1/8” FNPT pressure gauge With the service valve closed the pressure port will be
or pressure gauge connection. The pressure test port will isolated from the container. This will allow a high pressure leak
communicate to the downstream side of the service valve. test to be conducted without disconnecting the pigtail from the
service valve.
• Double back check filler valve has filling capacities matched to the
high capacity pumps and meters on modern delivery trucks.
10
O
G
CT
G8475RV
10
Y
NT
E
42 72 98 125
Y
AR A
WA R R
G8475RW
Ordering Information
Vapor Equalizing Fixed Pressure Relief Valve
Connection Float Liquid For use in
Dip
Part Container Service Filling UL Guage Level Flow Capacity conatiners
Tube
Number Connection Connection Connection Listed Flange Vent Part w/ surface are
Size Length Setting
Closing Opening Valve Number up to:
UL ASME
Flow Style
83 sq ft.
2020 1939 above ground
G8475RV M3131G SCFM, SCFM, 276 sq. ft.
air air under
4200
1 1/4” Fits ground
2 1/2” F. POL 1 3/4” CFH 250
M. “JUNIOR” Knurled 30”*
F. NPT (CGA 510) M. ACME @ 100 PSIG 192 sq. ft.
ACME size
PSIG above ground
3995
G8475RW MV3132G SCFM, n/a 639 sq. ft
air under
ground
*Dip tube not installed, may be cut by customer to desired length.
C6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ASME Multivalves® for Vapor Withdrawal
8593AR
Application
These Multivalves® provide vapor withdrawal and filling of ASME
containers. A separate pressure relief valve is required in addition to
this valve. The MultiBonnet® is standard on this valve.
Features
• Combines double back check filler valve, service valve, vapor
UL ®
equalizing valve with excess flow, fixed liquid level gauge and
plugged pressure gauge opening in one unit.
• “Y” shape configuration allows for ease of operation with all valves
and gauges easily accessible at all times.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast 8593AR
Valve Stem................................................................................. Brass
O-Ring....................................................................... Resilient Rubber
Seat Disc (shut-off valve)........................................................... Nylon
Seat Discs (other)...................................................... Resilient Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Vapor Equalizing Connection Fixed Liquid Dip
Part Container Service Filling Level Vent Tube For Use In Containers
Number Connection Connection Connection Connection Size UL Listed Closing Flow Valve Style Length w/ Surface Area Up To:
1½” F. POL 1¾” 1¼”
8593AR16.0 4200 CFH at 100 PSIG Knurled 16”* **
M. NPT (CGA 510) M. ACME M. ACME
*Dip tube not installed, may be cut by customer to desired length.
**Since these Multivalves® have no integral pressure relief valves, they can be used on any ASME container with an independent relief device sufficient for that tank’s capacity.
C7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
DOT Multivalve® for Liquid Withdrawal
8555DL
Application
These Multivalves® permit liquid withdrawal from DOT cylinders with
up to 100 lbs. propane capacity. They eliminate unnecessary cylinder
handling when servicing high volume loads and allow on-site filling
into the vapor space without interrupting gas service.
Features UL
®
• Furnished with 44” long, 1⁄2” O.D. brass liquid withdrawal tube.
Materials
8555DL
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast
Valve Stems................................................................................ Brass
O-Rings..................................................................... Resilient Rubber
Seat Disc (shut-off valve)........................................................... Nylon
C Seat Disc (others)...................................................... Resilient Rubber
Relief Spring................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
For Use In
Fixed Liquid Dip Tube Liquid Pressure Cylinders Liquid Closing
Container Service Filling Level Vent Length w/ Withdrawal Tube Relief Valve w/Propane Flow
Part Number Connection Connection Connection Valve Style Deflector Length Setting Capacity Up To: (LP-Gas)***
¾” CGA 1¾” 375
8555DL11.6 Knurled 11.6” 44” 100 lbs. ** 1.7 GPM
M. NGT 555* M. ACME PSIG
* Use adapter 12982 to connect to pipe threads.
** Per CGA Pamphlet S-1.1.
*** To ensure proper functioning and maximum protection from integral excess flow valves, the cylinder valve should be fully opened and backseated when in use.
C8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
DOT Multivalves® for Vapor Withdrawal
6555R, 8555D and 8555R Series
Application
These Multivalves® permit vapor withdrawal. They allow for container
filling without interrupting gas service.
The 8555D and 8555R Series are designed for DOT cylinders with up UL
®
to 200 lbs. propane capacity.
Features
• Incorporates service valve, high capacity filler valve with integral
back-check, fixed liquid level gauge and pressure relief valve in
one single unit.
• Heavy duty O-ring stem seal provides positive leak proof seal.
• Tapered nylon shut-off seat disc in fully confined seat ensures easy,
leak-free, positive shut-off.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast C
Valve Stems................................................................................ Brass
O-Rings..................................................................... Resilient Rubber
Seat Disc (shut-off valve)........................................................... Nylon
Seat Disc (others)...................................................... Resilient Rubber
Relief Spring................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
For Use In Pressure Relief Valve
Containers Dip Tube Fixed Liquid Flow Capacity*
Part with Size Up Length Container Service Filling Level Vent
Number Bonnet Style Application To: w/Deflector Connection Connection Connection Valve Style Setting UL Listing ASME
2
6555R10.6 MultiBonnet® 25 ft surface 10.6”
6555R11.6 MultiBonnet® ASME area or 60 11.6” 250 793 700
Containers gallons water PSIG SCFM, air SCFM, air
6555R12.0 MultiBonnet® capacity 12.0”
¾” F. POL 1¾”
8555D10.6 Standard Knurled
10.6” M. NGT (CGA 510) M. ACME
8555R10.6 MultiBonnet® DOT 200 lbs. 375
n/a n/a
8555D11.6 Standard Cylinders Propane ** PSIG
11.6”
8555R11.6 MultiBonnet®
*Per CGA Pamphlet S-1.1.
C9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
DOT and ASME Multivalves® for Vapor Withdrawal
6532, 6533, 6542 and 6543 Series
Application
These Multivalves® permit vapor withdrawal from ASME containers
up to 50 sq. ft. surface area and DOT containers up to 420 lbs.
propane capacity. They allow on-site cylinder filling without interrupting
gas service.
• Similar but smaller than the 6542 and 6543, these are generally
used for replacement on existing containers with 3⁄4” NGT
openings.
• Secondary back check placed in the body of the valve to help PRODU
10
O
minimize reverse flow in the event the upper back check shears
UL
G
CT
RE
Y
NT
E
Y
AR A
WA R R
• The MultiBonnet® option allows quick and easy repair of bonnet.
Ordering Information
For Use In For Use In
Fixed Pressure Cylinders Containers
Liquid Dip Tube Relief w/Propane w/Surface
Part Container Service Filling Level Vent Length with Valve Capacity Area Up
Number Bonnet Style Application Connection Connection Connection Valve Style Deflector Setting Up To:** To:***
6532A12.0 Standard
¾” M. NGT 43 sq. ft.
6532R12.0 MultiBonnet® 250
ASME* 12.0” -
6542A12.0 Standard PSIG
1” M. NGT 53 sq ft.
6542R12.0 MultiBonnet®
6533A10.5 Standard
10.5”
6533R10.5 MultiBonnet® F. POL 1¾”
¾” M. NGT Knurled
6533A11.7 Standard (CGA 510) M. ACME
11.7”
6533R11.7 MultiBonnet® 375 420 lbs.
DOT -
6543A11.1 Standard PSIG Propane
11.1”
6543R11.1 MultiBonnet®
1” M. NGT
6543A11.7 Standard
11.7”
6543R11.7 MultiBonnet®
* UL rated flow capacities are: 6532A12.0-1180 SCFM/air, 6542A12.0-1530 SCFM/air.
** Per CGA Pamphlet S-1.1.
*** From NFPA, Appendix D.
C10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ASME Multivalves® for Vapor Withdrawal
7556R
Application
These compact Multivalves® are especially suited for vapor
withdrawal of ASME containers where compact groupings of
components are necessary. Separate filler valves and pressure relief
valves are required.
Features
• Combines service valve, vapor equalizing valve with excess flow,
fixed liquid level gauge and plugged pressure gauge opening in
one unit.
7556R
• Rugged, 1” wrenching boss on center column minimizes possible
damage during installation. UL ®
• “Y” shape configuration allows for ease of operation with all valves New Style 7556R Series with ⅛” FNPT pressure test port.
and gauges easily accessible at all times.
• Designed for installation of a ⅛” FNPT pressure gauge or pressure gauge ⅛” F-NPT Pressure Test Port is isolated from the container when
connection. The pressure test port will communicate to the downstream the service valve is closed.
side of the service valve.
Materials
Body............................................................................... Forged Brass
Handwheel............................................................ Aluminum Die Cast C
Valve Stems................................................................................ Brass
O-Rings..................................................................... Resilient Rubber
Seat Disc (shut-off valve)........................................................... Nylon
Seat Disc (others)...................................................... Resilient Rubber
With the service valve closed the pressure test port will be
isolated from the container. This will allow a high-pressure leak
test to be conducted without disconnecting the pigtail from the
service valve.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Vapor Equalization Connection Fixed Liquid Dip For Use In
Container Service Level Vent Valve Tube Containers w/
Part Number Connection Connection Connection Size UL Listed Closing Flow Style Length Surface Area Up To:
F. POL
7556R12.0 ¾” M. NGT 1¼” M. ACME 4200 CFH @ 100 PSIG Knurled 12”** *
(CGA 510)
* Since these Multivalves® have no integral pressure relief valves, they can be used on any ASME container with an independant
relief device sufficent for that tank’s capacity.
** Other tube lengths available.
C11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Warning Notice
The following warning information, Part Number 903-500, is included
with each shipment of cylinder valves and service valves to the first
purchaser of the product from the factory.
C12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section D
D D
D1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
LIMITED 10 YEAR WARRANTY AND LIMITATION OF LIABILITY Except as expressly set forth above, and subject to the limitation of
liability below, ECII MAKES NO OTHER WARRANTY, EXPRESS
LIMITED 10 YEAR WARRANTY OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
Engineered Controls International, Inc. (“ECII”) warrants to the original PARTICULAR PURPOSE, with respect to its products and parts,
purchasers the products and repair kits manufactured by it to be free whether used alone or in combination with others. ECII disclaims all
from defects in materials and workmanship under normal use and warranties not stated herein.
service for a period of 10 years from the date of manufacture. If within
thirty days after buyer’s discovery of what buyer believes is a defect,
buyer notifies in writing and ships the product to ECII at 100 Rego
Drive, Elon, NC 27244, ECII, at its option, and within forty-five days of LIMITATION OF LIABILITY
receipt , will repair, replace F.O.B. point of manufacture, or refund the
purchase price of that part or product found by ECII to be defective.
Failure of buyer to give such written notice and ship the product within
thirty days shall be deemed an absolute and unconditional waiver of NOTICE TO USERS OF PRODUCTS
any and all claims of buyer arising out of such defect.
The Limited Warranty stated above is a factory warranty to the first
This warranty does not extend to any product or part that is not purchasers of ECII products. Since most users have purchased
installed and used continuously after installation in accordance with these products from ECII distributors, the user must within thirty (30)
ECII’s printed instructions, all applicable state and local regulations, days after the user’s discovery of what user believes is a defect,
and all applicable national standards, such as those promulgated by notify in writing and return the product to the distributor from whom
NFPA, DOT and ANSI. This warranty does not extend to any product he purchased the product/part. The distributor may or may not at
or part that has been damaged by accident, misuse, abuse, failure to the distributor’s option choose to submit the product/parts to ECII,
maintain, or neglect, nor does it extend to any product or part which pursuant to this Limited Warranty. Failure by buyer to give such
has been modified, altered, disassembled, or repaired in the field. written notice within thirty (30) days shall be deemed an absolute and
This warranty does not cover any cosmetic issues, such as scratches, unconditional waiver of buyer’s claim for such defects. Acceptance
dents, marring, fading of colors or discoloration. of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
D2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
D
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Cross Reference by Part Number........................................... D20
Duoport® Assemblies.............................................................. D17
General Information................................................................... D6
Hydrostatic Relief Valves......................................................... D16
Multiport™ Assemblies............................................................ D18
“Pop-Action” Relief Valves....................................................... D10
Saftey Warning.......................................................................... D4
Warnings................................................................................. D20
D3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Safety Warning — LP-Gas Pressure Relief Valves
Purpose
! WARNING
International, Inc. is publishing safety warning bulletins
explaining the hazards associated with the use, misuse and
aging of ECII®/ RegO® Products. LP-Gas dealer managers
and service personnel must realize that the failure to exercise
the utmost care and attention in the installation, inspection
and maintenance of these products can result in personal
injury and property damage.
Scope
D4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Inspect Regularly
A pressure relief valve discharges when some extraordinary 4. Physical damage. Ice accumulations and improper
circumstance causes an over pressure condition in installation could cause mechanical damage. IF THERE ARE
the container. If a pressure relief valve is known to have ANY INDICATIONS OF DAMAGE, REPLACE THE VALVE.
discharged, the relief valve, as well as the entire system,
should be immediately and thoroughly inspected to determine
5. Tampering or readjustment. Pressure relief valves
the reason for the discharge. In the case of discharge due to
are factory set to discharge at specified pressures. IF
fire, the valve should be removed from service and replaced.
THERE ARE ANY INDICATIONS OF TAMPERING OR
READJUSTMENT, REPLACE THE VALVE.
Relief valves should be inspected each time the container is 6. Seat leakage. Check for leaks in the seating area using
filled but no less than once a year. If there is any doubt about a noncorrosive leak detection solution. REPLACE THE
the condition of the valve, it must be replaced. VALVE IF THERE IS ANY INDICATION OF LEAKAGE.
Never force a relief valve closed and continue to leave it
Eye protection must be worn when performing inspection on in service. This could result in damage to the valve and
relief valves under pressure. Never look directly into a relief possible rupture of the container or piping on which the
valve under pressure or place any part of your body where valve is installed.
the relief valve discharge could impact it. In some cases a
flashlight and a small mirror are suggested to assist when 7. Corrosion and contamination. REPLACE THE VALVE
making visual inspections. IF THERE ARE ANY SIGNS OF CORROSION OR
CONTAMINATION ON THE VALVE.
To Properly Inspect A Pressure Relief Valve, Check For:
1. A rain cap. Check protective cap located in valve or at end 8. Moisture, foreign particles or contaminants in the valve.
of pipeaway for a secure fit. Protective caps help protect Foreign material such as paint, tar or ice in relief valve
the relief valve against possible malfunction caused by parts can impair the proper functioning of the valves.
rain, sleet, snow, ice, sand, dirt , pebbles, insects, other Grease placed in the valve body may harden over time
debris and contamination. REPLACE DAMAGED OR or collect contaminants, thereby impairing the proper
MISSING CAPS AT ONCE AND KEEP A CAP IN PLACE operation of the relief valve. DO NOT PLACE GREASE
AT ALL TIMES IN THE VALVE BODY, REPLACE THE VALVE IF THERE
ARE ANY INDICATIONS OF MOISTURE OR FOREIGN
2. Open weep holes. Dirt, ice, paint and other foreign MATTER IN THE VALVE.
particles can prevent proper drainage from the valve
body. IF THE WEEP HOLES CANNOT BE CLEARED, 9. Corrosion or leakage at container connection. Check
REPLACE THE VALVE. container to valve connection with a non-corrosive leak D
detection solution. REPLACE THE VALVE IF THERE IS
3. Deterioration and corrosion on relief valve ANY INDICATION OF CORROSION OR LEAKAGE AT THE
spring. Exposure to high concentrations of water, CONNECTION BETWEEN THE VALVE AND CONTAINER.
salt, industrial pollutants, chemicals and roadway
contaminants could cause metal parts to fail. IF CAUTION: Never plug the outlet of a pressure relief valve. Any
THE COATING ON THE RELIEF VALVE SPRING IS device used to stop the flow of a properly operating pressure
CRACKED OR CHIPPED, REPLACE THE VALVE. relief valve that is venting an overfilled or overpressurized
container - raises serious safety concerns!
Predicting the safe useful life of a relief valve obviously is not an 1. CGA Pamphlet S-1.1 Pressure Relief Standards - Cylinders, Section
exact science. The conditions to which the valve is subjected 9.1.1.
will vary widely and will determine its useful life. In matters of 2. ECII® Catalog L-500.
this kind, only basic guidelines can be suggested. For example,
the Compressed Gas Association Pamphlet S-1.1 Pressure 3. ECII® Warning # 8545-500.
Relief Device Standards — Cylinders, section 9.1.1 requires
all cylinders used in industrial motor fuel service to have the 4. NPGA Safety Pamphlet 306 “LP-Gas Regulator and Valve
cylinder’s pressure relief valves replaced by new or unused Inspection and Maintenance” and “LP-Gas Training Guidebooks”.
relief valves within twelve years of the date of manufacture
of cylinder and within each ten years thereafter. The LP-Gas 5. NFPA # 58, “Storage and Handling of Liquefied Petroleum Gases”.
dealer must observe and determine the safe useful life of relief
6. NFPA # 59, “LP-Gases at Utility Gas Plants”.
valves in his territory. The valve manufacturer can only make
recommendations for the continuing safety of the industry. 7. ANSI K61.1 Safety Requirements for Storage and Handling of
Anhydrous Ammonia.
D5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO® Pressure Relief Valves
Requirements for Pressure Relief Valves The reasons for this are two-fold:
Every container used for storing or hauling LP-Gas and anhydrous ● If the relief valve is called upon to open, the resulting
ammonia must be protected by a pressure relief valve. These discharge produces an increased vaporization of the
valves must guard against the development of hazardous product in the container with the result that the liquid cools
conditions which might be created by any of the following: to a certain extent and the vapor pressure drops. A reading
taken at this time would obviously not indicate what the
● Hydrostatic pressures due to overfilling or the trapping of pressure was when the relief valve opened.
liquid between two points.
● High pressures resulting from exposure of the container to ● The pressure gauges usually on most containers provide
excessive external heat. somewhat approximate readings and are not intended to
provide an indication of pressure sufficiently accurate to
● High pressures due to the use of incorrect fuel.
judge the setting of the relief valve.
● High pressures due to improper purging of the container.
Repair and Testing
Consult NFPA Pamphlet #58 for LP-Gas and ANSI #K61.1 for RegO® Pressure Relief Valves are tested and listed by
anhydrous ammonia, and/or any applicable regulations governing Underwriters Laboratories, Inc., in accordance with NFPA
the application and use of pressure relief valves. Pamphlet #58. Construction and performance of RegO®
Pressure Relief Valves are constantly checked at the factory
Operation of Pressure Relief Valves by U.L. inspectors. Therefore, testing of RegO® Pressure
Pressure relief valves are set and sealed by the manufacturer to function
at a specific “start-to-discharge” pressure in accordance with regulations.
Relief Valves in the field is not necessary.
This set pressure, marked on the relief valve, depends on the design
requirement of the container to be protected by the relief valve. If the Any pressure relief valve which shows evidence of leakage, other
container pressure reaches the start-to-discharge pressure, the relief valve improper operation or is suspect as to its performance must be
will open a slight amount as the seat disc begins to move slightly away replaced immediately using approved procedures.
from the seat. If the pressure continues to rise despite the initial discharge
through the relief valve, the seat disc will move to a full open position with Pipe-Away Adapters
a sudden “pop”. This sharp popping sound is from which the term “pop-
action” is derived. Pipe-away adapters are available for most RegO® Pressure
D Whether the relief valve opens a slight amount or pops wide open, it will
Relief Valves, where it is required or desirable to pipe the
discharge above or away from the container. Each adapter
start to close if the pressure in the container diminishes. After the pressure is designed to sever if excessive stress is applied to the vent
has decreased sufficiently, the relief valve spring will force the seat disc
piping – thus leaving the relief valve fully operative.
against the seat tightly enough to prevent any further escape of product.
The pressure at which the valve closes tightly is referred to as the “re-seal”
or “blow-down” pressure. Generally, the re-seal pressure will be lower than Weep hole deflectors are available on larger relief valves.
the start-to-discharge [Link] re-seal pressure can be, and in most These deflectors provide protection against flame impinging
cases is, adversely affected by the presence of dirt, rust, scale or other on adjacent containers which could occur from ignition of
foreign particles lodging between the seat and disc. They interfere with LP-Gas escaping through the relief valve drain hole when the
the proper mating of the seat and disc and the pressure in the container valve is discharging.
will usually have to decrease to a lower pressure before the spring force
embeds foreign particles into the resilient seat disc material and seals Selection of RegO® Pressure Relief Valves For ASME
leak-tight. The degree by which the presence of dirt decreases the re-seal Containers
pressure, is, of course, dependent on the size of the interfering particles.
The rate of discharge required for a given container is
Once particles have been trapped between the disc and seat, the start-
to-discharge pressure is also affected. For example, the pressure relief
determined by the calculation of the surface area of the
valve will start-to-discharge at some pressure lower than its original start- container as shown in “Chart A” for LP-Gas and “Chart B” for
to-discharge pressure. Again, the pressure at which the valve will start to anhydrous ammonia. See page D9.
discharge is dependent on the size of the foreign particles.
Setting - The set pressure of a pressure relief valve depends
In the case of a pressure relief valve that has opened very slightly due upon the design pressure of the container. Refer to NFPA
to a pressure beyond its start-to-discharge setting, the chances of Pamphlet #58 for more information.
foreign material lodging between the seat and disc is negligible although
the possibility is always present. If the relief valve continues to leak at
Selection of RegO® Pressure Relief Valves for DOT
pressures below its start-to-discharge setting it must be replaced.
Containers
Relief valves which have “popped” wide open must also be
checked for foreign material lodged between the seat and disc, To determine the proper relief valve required for a given
as well as for proper reseating of the seat and disc. Continued DOT container, refer to the information shown with each
leakage at pressures below the start-to-discharge setting indicate pressure relief valve in the catalog. This information will give
the relief valve must be replaced. the maximum size (pounds water capacity) DOT container for
which the relief valve has been approved.
The pressure at which a pressure relief valve will start to discharge
should never be judged by the reading of the pressure gauge Setting - The standard relief valve setting for use on DOT
normally furnished on the container. cylinders is 375 PSIG.
D6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
RegO® Pressure Relief Valves
Ordering RegO® Pressure Relief Valves Part Number Explanation
When ordering RegO® Pressure Relief Valves, be sure you are Products carrying an “A” or “AA” prefix contain no brass parts and
certain that it will sufficiently protect the container as specified in are suitable for NH3. Hydrostatic relief valves carrying an “SS”
the forewording information, NFPA Pamphlet #58 and any other prefix are of stainless steel construction and are suitable for use
applicable standards or specifications. with NH3. The products are also suitable for use with LP-Gas
service except relief valves carrying an “AA” prefix. These are
All adapters, protective caps and deflectors must be ordered of partial aluminum construction and are listed by U.L. for NH3
separately, unless specified otherwise. service only.
Unfortunately many of the above problems may not be easily Collection of debris would be prevented. Contamination caused by
observed because of the compact nature of some relief valve corrosive atmospheres would be reduced. Water collection in the
designs. valves would be eliminated. Relief valves protected with caps
from the time of installation in the container would obviously have
a much longer safe useful life, but they still should be replaced at
A casual visual inspection of a relief valve may not necessarily disclose some time because of the gradual deterioration of the rubber seat
a potential hazard. On the other hand, a visual inspection will often disc due to age alone.
disclose leakage, corrosion, damage, plugging and contamination.
In the event a relief valve has been used without the required
cap, the relief valve should be thoroughly inspected and the
Eye protection must be used when examining relief valves under required cap placed on the relief valve. If damage is noted to
pressure.
the relief valve, it should be replaced and the replacement valve
Smaller Relief Valves should be capped. Relief valves with pipe-away adapters or
deflectors used on lift truck containers have been found choked
The industry’s requirement for a small full-flow safety relief valve with debris. Inspection of relief valves with deflectors can only be
challenged design engineers some years ago: accomplished by removing the deflector.
Surface area =Total outside surface area of container in square feet. Flow Rate SCFM Air = Required flow capacity in cubic feet per minute
When the surface area is not stamped on the name plate or when the of air at standard conditions, 60ºF. and atmospheric pressure (14.7 psia).
marking is not legible, the area can be calculated by using one of the The rate of discharge may be interpolated for intermediate values of
following formulas: surface area. For containers with total outside surface area greater than
1. Cylindrical container with hemispherical heads. Area (in sq. ft.) = 2000 square feet, the required flow rate can be calculated using the
overall length (ft.) x outside diameter (ft.) x 3.1416. formula, Flow Rate—SCFM Air = 53.632 A0.82. Where A = total outside
surface area of the container in square feet.
2. Cylindrical container with semi-ellipsoidal heads. Area (in sq. ft.) =
overall length (ft.) + .3 outside diameter (ft.) x outside diameter (ft.) x
3.1416.
3. Spherical container. Area (in sq. ft.) = outside diameter (ft.) squared x
3.1416.
D
Chart B — Minimum Required Rate of Discharge for Anhydrous Ammonia Pressure Relief
Valves Used on ASME Containers
Minimum required rate of discharge in cubic feet per minute of air at 120% of the maximum permitted start-
From ANSI K61.1-1981, Appendix A (1981). to-discharge pressure for pressure relief valves to be used on containers other than those constructed in
accordance with United States Department of Transportation cylinder specifications.
Surface area = Total outside surface area of container in square feet. Flow Rate SCFM Air = Required flow capacity in cubic feet per minute of
When the surface area is not stamped on the name plate or when the air at standard conditions, 60°F. and atmospheric pressure (14.7 psia).
marking is not legible, the area can be calculated by using one of the The rate of discharge may be interpolated for intermediate values of
following formulas: surface area. For containers with total outside surface area greater than
1. Cylindrical container with hemispherical heads. Area (in sq. ft.) = overall 2,500 square feet, the required flow rate can be calculated using the
length (ft.) x outside diameter (ft.) x 3.146. formula, Flow Rate—SCFM Air = 22.11 A0.82 where A = outside surface area
of the container in square feet.
2. Cylindrical container with other than hemispherical heads. Area (in sq.
ft.) = overall length (ft.) + .3 outside diameter (ft.) x outside diameter (ft.) Conversion Factor
x 3.1416. ft2 x 0.092 903 = m2
3. Spherical container. Area (in sq. ft.) = outside diameter (ft.) squared x SCFM x 0.028 317 = m3/min
3.1416. ft x 0.304 8 =m
D9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
“Pop-Action” Pressure Relief Valves
General Information Relief Valves in this catalog are only intended
The “Pop-Action” design permits the RegO® Pressure Relief Valve to open slightly to relieve
for use in LP-Gas or anhydrous ammonia
moderately excessive pressure in the container. When pressure increases beyond a predetermined
service. Do not use any other service
point, the valve is designed to “pop” open to its full discharge capacity, reducing excess pressure
commodity. If you have an application other
quickly. This is a distinct advantage over ordinary valves which open gradually over their entire
than conventional LP-Gas or anhydrous
range, allowing excessive pressure to develop before the relief valve is fully open. All RegO® internal,
ammonia service, contact Engineered
semiinternal, and external relief valves incorporate this “Pop-Action” design.
Controls International, Inc before proceeding.
Application
Designed specifically for use as a primary relief valve in ASME
transports and delivery trucks with 2” and 3” NPT couplings.
Features
• Low profile design assures maximum protection against sheering
or distortion.
• All functioning parts are located below the level of the container
connection to reduce the possibility of damage or tampering.
D • Use of two different materials for stem and guide minimizes the
possibility of stem seizure which may occur when similar materials
are used.
A8434-SERIES
Materials
PRODU
Body............................................................................ Stainless Steel
10
O
G
Y
NT
AR A
WA R R
Ordering Information
Start To A B C UL
Part Discharge Container Overall Height Height Above (At 120% of Set ASME (At 120% Suitable for Tanks with Protective Cap
Number Setting PSIG Connection (Approx.) Coupling (Approx.) Pressure) of Set Pressure) Surface Area Up To:* (Included)
A8434N 265 3659
2” M. NPT 9 1/16” ½” 3700 175 Sq. Ft. A8434-11B
A8434G 250 3456
A8436N 265 9839
3” M. NPT 17 ⅞” ¾” 10210 602 Sq. Ft. A8436-11B
A8436G 250 9598
* Per NFPA Pamphlet #58, Appendix D. Area shown is for UL or ASME flow rating—whichever is larger.
D10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Fully Internal “Pop-Action” Pressure Relief Valves for
Motor Fuel Containers 8543 and 8544 Series
Application
8543 Series relief valves are designed for use as a primary relief
valve in larger ASME motor fuel containers such as on buses, trucks
and construction equipment.
8544 Series relief valves are designed for use as a primary relief
valve in smaller ASME and DOT motor fuel containers such as on
tractors, lift trucks, cars and taxicabs.
Features
• Assure minimum product loss due to “pop-action” design. 7543-10
7544-11A
• Recessed design minimizes possibility of damage and tampering.
• ASME rated for use with LP-Gas (except 8544K which meets DOT
requirements). D
Materials A
Body........................................................................................... Brass
UL D
Spring (8543)............................................................... Stainless Steel ®
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
8544
Ordering Information
Flow Capacity SCFM/Air****
A B C D Accessories
Start To Container Overall Height Above Hex UL ASME Protective
Part Container Discharge Connection Height Coupling Wrenching (At 120% of (At 120% of Cap Pipeaway
Number Type Setting PSIG M. NPT (Approx.) (Approx.) Section Set Pressure) Set Pressure) (Included) Adapter
8544G 1” 1 5 16 ” 1020 936 7544-41 7544-11A*
250
8543G 1¼” 111 16 ” 1465 1400 7543-40C 7543-10**
ASME 5
8544T 1” 5 7
16 ” ⅞” 1 16 ” 1282 1158 7544-41 7544-11A
312
8543T 1¼” 1 16 ”
11
1990 1731 7543-40C 7543-10**
8544K DOT/ASME 375 1” 1 5 16 ” 1545*** - 7544-41 7544-11A
D11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Fully Internal “Pop-Action” Pressure Relief Valve
for DOT Fork Lift Cylinders 8545AK
Application
Designed specifically for use as a primary relief valve on forklift
cylinders, the 8545AK reduces the possibility of improper functioning
of the relief mechanism due to foreign material build up. All guides,
springs, stem and adjusting components are located inside the
cylinder - removed from the direct exposure of foreign materials and
debris from the atmosphere.
Features UL
®
• Internal stem guide eliminates the need for a close fit between the
body and poppet, which lessens the chance of clogging due to
foreign material.
Materials
Body........................................................................................... Brass
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel
Poppet........................................................................................ Brass
Guide.......................................................................................... Brass
Seat Disc................................................................... Resilient Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Accessories (Order Separately)
Flow Capacity SCFM/Air**
Deflectors***
Part Container Start To Discharge Container Protective
Number Type Setting PSIG Connection M. NPT (ECII® Rated at 480 PSIG Cap 45° Elbow 90° Elbow
8545AK Dot 375 ¾” 400* 7545-40 7545-14 7545-12
* Classified by U.L. in accordance with Compressed Gas Association Pamphlet S-1.1 Pressure Device Standards for Cylinders.
Meets requirements for use on DOT containers with 262 pounds or less weight of water or 109 pounds or less of LP-Gas.
** Flow rates are shown for bare relief valves. Adapters and pipeaways will reduce flow as discussed in forewording information.
*** Order protective cap #8545-41 or 7545-40.
D12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Semi-Internal “Pop-Action” Pressure Relief Valves for ASME
Containers 7583, 8684 and 8685 Series
Application
Designed for use as a primary relief valve on ASME containers such UL
®
Features PRODU
10
O
CT
RE
• Constructed of non-corrosive materials.
S
10
Y
NT
E
• “Pop-action” design keeps product loss at a minimum.
Y
AR A
WA R R
• Request RegO® Relief Valves on all your original equipment ASME Materials
containers for reliable performance.
Body........................................................................................... Brass
Spring.......................................................................................... Steel
Stem............................................................................ Stainless Steel
Seat Disc................................................................... Resilient Rubber
Ordering Information
Flow Capacity SCFM/Air
A B C D
Start To Container Overall Height Above Wrench Suitable for
Part Discharge Connection Height Coupling Hex UL (At 120% of Set ASME (At 120% of Tanks w/Surface Protective
Number Setting PSIG M. NPT (Approx.) (Approx.) Section Pressure) Set Pressure) Area Up To:* Cap (Included)
7583G ¾” 8 316” 1716 ” 1¾” 1980 1806 80 Sq. Ft. 7583-40X
8684G 250 1” 9 3 8” 1916” 1 7 8” 2620 2565 113 Sq. Ft. 8684-40
8685G 1¼” 11116 ” 11116” 2 3 8”
* Per NFPA Pamphlet #58, Appendix D. Area shown is for UL or ASME flow rating—whichever is larger.
4385 4035 212 Sq. Ft. 7585-40X
D
Application
Designed especially for use as a primary relief valve on large
stationary storage containers, these low profile relief valves are
generally mounted in half couplings. However, they are designed so
UL ®
that the inlet ports clear the bottom of a full 2” coupling. This assures
that the relief valve should always be capable of maximum flow
under emergency conditions.
Features PRODU
10
O
G
CT
RE
Y
NT
E
Y
AR A
WA R R
• Built-in spring stop limits the rise of the seat in full open position
and prevents the spring from going “solid”.
D13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
External “Pop-Action” Pressure Relief Valves for ASME Containers and Bulk Plant
Installations AA3126, AA3130, 3131, 3132, 3133, 3135, AA3135, and A3149 Series
Application
3135-10
Designed for use as a primary relief valve on ASME above ground
and underground containers, bulk plant installations and skid tanks.
The 3131 Series may also be used as a primary or secondary
relief valve on DOT cylinders, or as a hydrostatic relief valve. All
working components of these relief valves are outside the container
connection, so the valves must be protected from physical damage.
Features
UL
• “Pop-action” design keeps product loss at a minimum. ®
• Relief valve designed to automatically reseat firmly after discharge. 3135 A3149
• Most are ASME rated for use with LP-Gas and anhydrous
ammonia.
AA3135 W3132G
Materials
D Description 3131, 3132, 3133, 3135 AA3126 AA3130 AA3135 A3149 PRODU
10
O
Body Brass Aluminum Rod* Upper Cold Rolled Steel Lower Ductile Iron
CT
RE
S
Liner None Stainless Steel
10
Y
Spring Guide Brass Aluminum Stainless Steel
NT
E
Y
AR A
Spring Corrosion Resisant Steel Stainless Steel Stainless Steel or Coated Steel WA R R
Ordering Information
Flow Capacity SCFM/Air (a) Accessories
Start To A B C UL Suitable
Discharge Container Overall Wrench (At 120% ASME for Tanks
Setting Connection Height Hex of Set (At 120% of w/Surface Area Weep Hole
Part Number PSIG M. NPT (Approx.) Section Pressure) Set Pressure) Up To: (e) Protective Cap Part Number Outlet Size Deflector
AA3126L030 30 ½” 2⅜” ⅞” (b) - - 7545-40 AA3126-10 ½” M. NPT -
A3149L050 50 2600(c) - 113 Sq. Ft.
2½” 10½” 4⅛” 3149-40 (h) Included (j)
A3149L200 200 8770 (c) - 500 Sq. Ft.
AA3126L250 ½” 2⅜” ⅞” 277 (c) - 23 Sq. Ft. (f) 7545-40 AA3126-10 ½” M. NPT
3131G 7 2060 1939 85 Sq. Ft. 3131-40 (g) - -
¾” 3 16 ” 1¾”
AA3130UA250 2045 1838 249 Sq. Ft. (f) AA3130-40P AA3131-10 1” F. NPT
W3132G 1” 3340 - 154 Sq. Ft. 3132-10 1¼” F. NPT
3132G 1 4130 - 200 Sq. Ft. -
6 32 ” 2⅜” 3132-54 (g)
T3132G 3790 - 180 Sq. Ft. 3132-10 1¼” F. NPT
250
MV3132G 3995 - 190 Sq. Ft. -
1¼” 3133-11
3135G 5
21
32 ” 5770 - 300 Sq. Ft. 3135-54 (g) 3135-10
11
2 ”
16
AA3135-0PR
AA3135UA250 6 13 32” 6430 6341 1010 Sq. Ft. (f) AA3135-10 2” F. NPT
15
3133G 1½” 5 16 ” 3⅛” 6080 - 320 Sq. Ft. 3133-40 (g) 3133-10
A3149G 2½” 10½” 4⅛” 10390 9153 613 Sq. Ft. 3149-40 (h) Included (j)
7
AA3130UA265 ¾” 3 16 ” 1¾” 2125 1912 261 Sq. Ft. (f) AA3130-40P AA3131-10 1” F. NPT -
265 AA3135-
AA3135UA265
11
1¼” 6 13 32” 2 ”
16 6615 6703 1045 Sq. Ft. (f) AA3135-10 2” F. NPT 3133-11
40PR
AA3126L312 312 ½” 2⅜” ⅞” 330 (c) - 27 Sq. Ft. (f) 7545-40 AA3126-10 ½” M. NPT -
(a) Flow rates shown are for bare relief valves. Adapters and pipeaways will (f) Per ANSI K61.1-1972, Appendix A.
reduce flow as discussed in forewording information. (g) Cap supplied with chain.
(b) Not UL or ASME rated. .059 square inch effective area. (h) Outlet 31⁄2-8N (F) thread, will accept 3” M. NPT pipe thread.
(c) Not UL or ASME rated. ECII® rated at 120% of set pressure. (j) Weep hole deflector is Part No. A3134-11B.
(e) Per NFPA Pamphlet #58, Appendix D. Area shown is for UL or ASME
flow rating—whichever is larger.
D14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
External “Pop-Action” Supplementary Pressure Relief Valves for
Small ASME Containers and DOT Cylinders 3127 and 3129 Series
Application
Designed for use as a supplementary relief valve on small ASME
above ground and underground containers. They may also be used 3129-10 Pipe Away Adapter
as a primary or secondary relief device on DOT cylinders, or as
hydrostatic relief valves.
3127 Series
• “Pop-action” design keeps product loss at a minimum.
Materials
Body........................................................................................... Brass
Spring.......................................................................... Stainless Steel
Seat Disc................................................................... Resilient Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Accessories
Flow Capacity SCFM/
Air Pipeaway Adapter
Start To A B C UL
Discharge Container Overall Wrench (At 120% ECII® Rated Suitable for
Container Setting Connection Height Hex of Set at 480 Tanks w/Surface Protective
Part Number Type PSIG M. NPT (Approx.) Section Pressure) PSIG*** Area Up To:* Cap Part Number Outlet Size
3127G ¼” 1 31 32” ⅞” 295 -
ASME 250 - -
3129G ½” 2 19 32 ” 1⅛” 465 3129-10 ½” F. NPT
7545-40
3127K ¼” 1 31 32 ” ⅞” 450 100 lbs./Propane -
DOT 375 -
3129K ½” 219 32 ” 1⅛” 780 200 lbs./Propane 3129-10 ½” F. NPT
* Flow rates shown are for bare relief valves. Adapters and pipeaways will reduce flow as discussed in forewording information.
** Not UL or ASME rated. ECII® rated at 480 PSIG.
*** Meets DOT requirements.
D15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
External Hydrostatic Relief Valves 3125, 3127, 3129, SS8001,
SS8002, SS8021 and SS8022 Series
Application
Designed especially for the protection of piping and shut-off valves
where there is a possibility of trapping liquid LP-Gas or anhydrous
ammonia. They may be installed in pipelines and hoses located
between shut-off valves or in the side boss of RegO® shut-off
valves.
Features
• Relief valve designed to automatically reseat firmly after discharge.
Materials
Body (3125, 3127, 3129)............................................................ Brass
Body (SS8001, SS8002, SS8021, SS8022)................ Stainless Steel
Spring.......................................................................... Stainless Steel
Seat Disc................................................................... Resilient Rubber
3125 Series (.161 Orifice)
3127 Series (.274 Orifice) UL PRODU
Ordering Information
®
10
O
3129 Series (.386)
CT
RE
S
Accessories
10
Y
NT
E
Y
AR A
A C WA R R
Pipeaway
Start To Container B Wrench
Part Discharge Valve Body Connection Height Hex Protective Adapter or
Number Setting PSIG Material M. NPT (Approx.) Section Cap Threads
SS8001G ¼” 11
16 ”
⅞” -
SS8002G Stainless ½” ⅞”
-
SS8021G Steel ¼” 11
16 ” ¼” NPSM Thrds
250 1⅜”
SS8022G ½” ⅜” NPT Thrds
⅞”
3127G ¼” 131 32” -
3129G ½” 219 32” 1⅛” 3129-10*
3127H ¼” 131 32” ⅞” -
275 Brass 7545-40
3129H ½” 219 32” 1⅛” 3129-10*
3127P ¼” 131 32” 1⅛” -
3129P 300 219 32” 1⅛” 3129-10*
½”
SS8022P Stainless Steel 1⅜” ⅞” - ⅜” NPT Thrds
3127J ¼” 131 32” ⅞” -
Brass 7545-40
3129J ½” 219 32” 1⅛” 3129-10*
SS8001J ¼” 11
16 ”
350 ⅞” -
SS8002J Stainless ½” ⅞”
-
SS8021J Steel ¼” 11
16 ” ¼” NPSM Thrds
1⅜” SS8022G
SS8022J ½” ⅜” NPT Thrds
⅞”
3127K ¼” 1 32”
31
-
375 19 7545-40
3129K ½” 2 32” 1⅛” 3129-10*
3125L Brass 1 9 16” ⅝” Included
¼” 31 -
3127L 1 32” ⅞” 7545-40
3129L ½” 219 32” 1⅛” 3129-40P 3129-10*
SS8001L 400 ¼” 11
16 ”
⅞” -
SS8002L Stainless ½” ⅞”
-
SS8021L Steel ¼” 11
16 ” ¼” NPSM Thrds
1⅜”
SS8022L ½” ⅜” NPT Thrds
⅞”
3127U ¼” 131 32” -
Brass 7545-40
3129U ½” 2 19 32” 1⅛” 3129-10*
SS8001U ¼” 11
16 ”
450 ⅞” -
SS8002U Stainless ½” ⅞”
-
SS8021U Steel ¼” 11
16 ” ¼” NPSM Thrds (.156 Orifice)
1”
SS8022U ½” ⅞” ⅜” NPT Thrds
(.156 Orifice)
* 1⁄2” F. NPT outlet connection.
D16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
DuoPort® Pressure Relief Valve Manifolds for Small Storage Containers
8542 Series
Application
Designed especially for use as a primary relief device on smaller
stationary storage containers, with 2” NPT threaded couplings.
These manifolds allow servicing or replacement of either of the two
PRODU
relief valves without evacuating the container or loss of service. The
10
O
CT
operating lever selectively closes off the entrance port to the relief
RE
S
valve being removed while the remaining valve provides protection
for the container and its contents. The rating of each manifold is
10
Y
NT
based on actual flow through the manifold and a single pressure relief E
Y
AR A
valve, taking friction loss into account. It is not merely the rating of the WA R R
relief valve alone.
Features
• Allows for relief valve removal and replacement on a periodic basis
without shutting down and evacuating the container.
Manifold Materials
Body.................................................................................. Ductile Iron ?
Clapper Disc................................................................ Stainless Steel
Bleeder Valve.............................................................. Stainless Steel
Seat Disc.................................................................................... Teflon
Packing............................................................................ Polyethylene
Ordering Information
Flow Capacity SCFM/Air**
Relief Valve Included
Start to Application (at 120% of set pressure)
Container
Discharge
Part Number Connection UL Rating
Setting Inlet Accessory ASME Rating
M. NPT (at 120%
PSIG Quantity Part Number Connection (at 120% of
LP- Pipeaway of set
NH3 M. NPT set Pressure)
Gas Adaptors Pressure)
8542G Yes No 3135MG 3135-10* 5250 (1) NA
250
AA8542UA250 2” 2 AA3135MUA250 1¼” AA3135- 6430 (1) 6341 (1)
No Yes
AA8542UA265 265 AA3135MUA265 10* 6615 (1) 6703 (1)
D17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
MultiportTM Pressure Relief Valve Manifold Assemblies
for Large Storage Containers A8560, A8570 and AA8570 Series
Application
Designed especially for use as a primary relief device on large
stationary pressurized storage containers with flanged openings.
These manifolds incorporate an additional relief valve, not included
A8560
in the flow rating, allowing for servicing or replacement of any one of
the relief valves without evacuating the container. The handwheel on
A8570
the manifold selectively closes off the entrance port to the relief valve
being removed while the remaining relief valves provide protection for
the container and its contents. All manifold flow ratings are based on
flow through the relief valves after one has been removed for service
or replacement.
Features
• Allows for relief valve removal and replacement on a periodic basis
without shutting down and evacuating the container.
D • Relief valves are ASME rated for use with LP-Gas and anhydrous
ammonia.
Materials
Body.................................................................................. Ductile Iron
Resilient Parts............................................................................ Teflon
Clapper Disc................................................................ Stainless Steel
Bleeder Valve.............................................................. Stainless Steel
10
O
Liner Stainless Steel
G
CT
RE
E
Y
*A special coating is applied to the inlet threads to minimize possibility of electrolytic action. AR A
WA R R
D18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Typical RegO Multiport™ Pressure Relief Valve Manifold
10
O
(4” Port Dia) Flat Faced.
G
Gasket
CT
RE
E
Y
AR A
AA8570 300#
1/16” Raised Faced.
7565-48 WA R R gasket furnished with each manifold
assembly.
Ordering Information
Application Relief Valve
Flow Capacity SCFM/Air**
Accessories At 120% of Set Pressure
Start To Container Inlet
Discharge Flange Connection Pipeaway
Part Number Setting PSIG LP-Gas NH3 Connection Quantity Part Number M. NPT Adapters UL Rating ASME Rating
A8563G 3 18,500 (2)
3”-300#*
A8564G 4 27,750 (3) Not
A3149MG
A8573G 3 18,500 (2) Applicable
4”-300#
A8574G 4 27,750 (3)
250 Yes Yes 2½” ****
A8563AG 3 18,300 (2)
3”-300#*
A8564AG 4 Not 27,400 (3)
A3149G
A8573AG 3 Applicable 18,300 (2)
4”-300#
A8574AG 4 27,400 (3)
* For use with modified 300# ANSI flange with 4” port. *** 2” F. NPT outlet connection.
** Flow rating based on number of relief valves indicated in parenthesis ( ). **** Outlet 31⁄2-8N (F) thread, will accept 3” M. NPT pipe thread.
Flow rates shown are for bare relief valves. Adapters and pipeaways will
reduce flow rates as discussed in forewording information.
D19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ECII® Warning Notice
The following warning information, Part Number 8545-500, is included
with each shipment of pressure relief valves and relief valve manifolds
to the first purchaser of the product from the factory.
D20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section E
E E
E1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
LIMITED 10 YEAR WARRANTY AND LIMITATION OF LIABILITY Except as expressly set forth above, and subject to the limitation of
liability below, ECII MAKES NO OTHER WARRANTY, EXPRESS
LIMITED 10 YEAR WARRANTY OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
Engineered Controls International, Inc. (“ECII”) warrants to the original PARTICULAR PURPOSE, with respect to its products and parts,
purchasers the products and repair kits manufactured by it to be free whether used alone or in combination with others. ECII disclaims all
from defects in materials and workmanship under normal use and warranties not stated herein.
service for a period of 10 years from the date of manufacture. If within
thirty days after buyer’s discovery of what buyer believes is a defect,
buyer notifies in writing and ships the product to ECII at 100 Rego
Drive, Elon, NC 27244, ECII, at its option, and within forty-five days of LIMITATION OF LIABILITY
receipt , will repair, replace F.O.B. point of manufacture, or refund the
purchase price of that part or product found by ECII to be defective.
Failure of buyer to give such written notice and ship the product within
thirty days shall be deemed an absolute and unconditional waiver of NOTICE TO USERS OF PRODUCTS
any and all claims of buyer arising out of such defect.
The Limited Warranty stated above is a factory warranty to the first
This warranty does not extend to any product or part that is not purchasers of ECII products. Since most users have purchased
installed and used continuously after installation in accordance with these products from ECII distributors, the user must within thirty (30)
ECII’s printed instructions, all applicable state and local regulations, days after the user’s discovery of what user believes is a defect,
and all applicable national standards, such as those promulgated by notify in writing and return the product to the distributor from whom
NFPA, DOT and ANSI. This warranty does not extend to any product he purchased the product/part. The distributor may or may not at
or part that has been damaged by accident, misuse, abuse, failure to the distributor’s option choose to submit the product/parts to ECII,
maintain, or neglect, nor does it extend to any product or part which pursuant to this Limited Warranty. Failure by buyer to give such
has been modified, altered, disassembled, or repaired in the field. written notice within thirty (30) days shall be deemed an absolute and
This warranty does not cover any cosmetic issues, such as scratches, unconditional waiver of buyer’s claim for such defects. Acceptance
dents, marring, fading of colors or discoloration. of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
E2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
E
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Cross Reference by Part Number.............................................E20
Flange Seal Valves....................................................................E12
Hose-End Filling Valve Safety Warning.......................................E4
Multipurpose Valves..................................................................E16
Quick-Acting Horse End Valves...................................................E6
Quick-Acting Minimum Loss Valves............................................E5
Quick-Acting Valves.....................................................................E7
Tank Car Valve..........................................................................E15
Vapor Head Manifold.................................................................E14
“V”-Ring Seal Valves...................................................................E9
Warnings...................................................................................E20
E3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Hose-End Filling Valves (With ACME Connectors)
Safety Warnings Purpose
In its continuing quest for safety, Engineered Controls International, Inc. publishes a series of bulletins explaining
the hazards associated with the use, misuse, and aging of LP-Gas valves and regulators. It is hoped that these
factual bulletins will make clear to LP-Gas dealer managers and service personnel, that the utmost care and
attention must be used in the installation, inspection, and maintenance of these products, or problems could
occur which would result in injuries and property damage.
The National Fire Protection Association Pamphlet #58 - 2004 Edition, “Liquified Petroleum Gas Code” states
that, “persons who transfer liquid LP-Gas, who are employed to transport LP-Gas, or whose primary duties fall
within the scope of this code shall be trained in proper handling procedures. Refresher training shall be provided
at least every three years. The training shall be documented.” These “ECII® Safety Warnings” may be useful in
training new employees and reminding older employees of hazards that can occur. It is recommended that all
employees be furnished with a copy of NPGA Safety Pamphlet 306-88, “LP-Gas Regulator and Valve Inspection
and Maintenance.”
Nature of Warnings
It is recognized that warnings should be as brief as possible, but
factors involved in filler valve and filling valves failure are not simple.
They need to be fully understood so that proper procedures and
maintenance can be used to prevent accidents. If there is a simple
warning, it would be:
● Make sure the ACME connector spins on easily by hand. Larger Filler and Filling Valves
● If leak is noticed when filling is started, stop the operation and For 2¼” and 3¼” valves with ACME connections, use only the special
correct the leaking condition. wrenches designed for the purpose.
● After filling, bleed the gas trapped between the filler valve Do not use pipe wrenches or hammers to tighten the connections. All
and hose-end valve by using the vent on the hose-end valve of the previous warnings about the smaller valves also apply here.
or by slightly loosening coupling nut to vent the gas before
disconnecting. General Warning
All ECII® products are mechanical devices that will eventually
If gas does not stop venting, then filler valve or hose-end become inoperative due to wear, contaminants, corrosion and aging
valve is leaking. Do not disconnect filling connector. This is a components made of materials such as rubber and metal. The
hazardous situation and your company procedure for handling environment and conditions of use will determine the safe service
this problem must be carefully followed. life of these products. Periodic inspection and maintenance are
essential. Because ECII® products have a long and proven record of
Make sure your company has such a procedure. Inspection of quality and service, LP-Gas dealers may forget the hazards that can
Filling Valves with Handwheel occur because a filler valve or a filling valve is used beyond its safe
● Valves should be inspected at least once a month to be sure the service life. Life of these valves is determined by the environment
valve handle is tight and not damaged, that the stem is not bent and in which they “live.” The LP-Gas dealer knows better than anyone
that there is no “play” in the threads in the bonnet. “Play” will normally what this environment is. Note: There is a developing trend in state
not be noticed if the valve is under pressure. legislation and in proposed national legislation to make the owner of
products responsible for replacing products before they reach the
● The ACME threads should be examined for wear, dents or nicks and end of their safe useful life. LP-Gas dealers should be aware of the
the seating area should be clean and smooth. legislation which could affect them.
E4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Quick-Acting Minimum Loss Hose-End Valves for Bobtail Delivery Trucks
and Dispensing Stations A7793A and A7797A
Application
Designed to vastly reduce the amount of product vented when
disconnecting bobtail delivery trucks, dispensing systems and
anhydrous ammonia nurse tanks.
These valves provide instant, full-on flow at the flip of a handle. Shut-
off is instant and the handle locks for added protection. This “top of UL
®
the line” hose-end valve is a fully contained unit that does not require
additional filling adapters or connectors.
Features
• Minimizes product venting loss, when disconnecting, instantly by
housing the seat disc at the bottom of the built-in ACME filling
connector.
E
Materials
Body.................................................................................. Ductile Iron
“V”-Ring...................................................................................... Teflon
Stem............................................................................ Stainless Steel
Seat Disc............................................................. Synthetic Elastomer
ACME Connector.......................................... Aluminum w/Steel Insert
Seal Housing............................................................... Stainless Steel
Lever........................................................................... Stainless Steel
Bonnet............................................................. Cadmium Plated Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Flow at 1 PSIG (Cv) Pressure Drop*
Part Number Inlet Connection (F. NPT) Outlet Connection (F. ACME) Locking Handle
(GPM/Propane)
A7793A ¾” 1 ¾” Yes 16.0
A7797A 1” 1 ¾” Yes 16.0
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square root of pressure drop. Example: A7797 @ 9 PSIG = 16.0 x 9 = 48.0 GPM/propane. For NH3 flow,
multiply propane flow by .90.
E5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Quick-Acting Hose-End Valves for Bobtail Delivery Trucks and Dispensing
Stations A7707L and A7708L
Application
Designed especially for safe operator handling of LP-Gas in bobtail
delivery truck, dispensing systems and anhydrous ammonia nurse
tank service.
These valves provide instant, full-on flow at the flip of the handle
and provide instant positive shut-off with a handle lock for added
protection.
Features
• “V”-ring spring-loaded pressure stem seal provides for leak-proof
operation. No packing to retighten or replace.
• Full swivel handle rotates 360° so the valve can be operated from
any angle.
• Swivel seat disc minimizes grinding on the body seat and assures
longer service life.
E
Materials
Body.................................................................................. Ductile Iron
“V”-Ring...................................................................................... Teflon A7708L
Stem............................................................................ Stainless Steel
Seat Disc............................................................. Synthetic Elastomer
Valve Lever.................................................................. Stainless Steel
Seal Housing............................................................... Stainless Steel
Bonnet............................................................. Cadmium Plated Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Accessories
Filling Connectors**
Extended Compact
Inlet & Outlet Locking Flow at 1 PSIG Pressure Drop
Part Number Body Design Connection (F. NPT) Handle (Cv) (GPM/Propane)** Steel Brass Steel
A7707L Globe 18.0
1” Yes A7575L4 3175A A3175A
A7708L Angle 22.0
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square root of pressure drop.
Example: A7708L @ 9 PSIG = 22.0 x 9 = 66.0 GPM/propane. For NH3 flow, multiply propane flow by .90.
* * See appropriate catalog section for additional information.
E6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Quick-Acting Valves for Crop Driers and Charging Manifold Hoses
7554 Series
Application
7554S Series valves provide instant shut-off and fast opening control
on LP-Gas crop driers. They are also ideal for charging manifold
hoses, stationary fuel transfer hoses and other applications requiring
quick, positive shut-off. They are not for use with delivery truck hoses
because the handle could snag on the ground and open the valve as
the hose is reeled back to the truck.
Both valve series must be installed so that flow through the valve is
opposite to that of a conventional globe valve. This allows the inlet
flow to assist in closing the valve and prevents the valve from being 7554S
opened by high pump pressures.
Features
• Quick-acting design speeds transfer operations, permitting rapid, UL
one-handed opening and closing. ®
• Swivel seat disc minimizes grinding on the body seat and assures
longer service life.
Materials
Body.................................................................................. Ductile Iron
Bonnet........................................................................................ Brass
“V”-Ring...................................................................................... Teflon
Stem............................................................................ Stainless Steel 7554LV
Seat Disc............................................................. Synthetic Elastomer
ACME Connector.......................................... Aluminum w/Steel Insert
Seal Housing............................................................... Stainless Steel
Lever........................................................................... Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Inlet & Outlet Connection (F. NPT) Locking Handle Flow At 1 PSIG (Cv) Pressure Drop* (GPM/Propane)
7554SAV No
½” 7.3
7554LAV Yes
7554SV No
¾” 11.3
7554LV Yes
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table
by square root of pressure drop. Example: 7554LV @ 9 PSIG = 11.5 X 9 = 34.5 GPM/
propane.
E7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Quick-Acting Valves for Cylinder Charging Hoses
7053T, A7553A, and 7901T Series
Application
Designed primarily for use on cylinder charging hoses to provide fast,
convenient shut-off and fast opening.
Features
A7553A
• Quick-acting design speeds transfer operations.
UL
• Permits easy, one-handed opening and closing of the valve. ®
Materials
Body (7053T, 7901)........................................................ Forged Brass
Body (A7553).................................................................... Ductile Iron
E O-Ring....................................................... Resilient Synthetic Rubber 7901TA
Bonnet Assembly (7053T, 7901)................................................ Brass
Bonnet Assembly (A7553)............................................................ Steel
Seat Disc.................................................... Resilient Synthetic Rubber
Handle (7053T, 7901).................................................................. Brass
Handle (A7553)............................................................................ Steel
Springs.......................................................................... Stainless Steel
PRODU
10
O
G
CT
RE
7053T
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Inlet Connection (F. NPT) Outlet Connection (F. NPT) Body Material Flow At 1 PSIG (CV) Pressure Drop* (GPM/Propane)
7901T Brass
¼” ¼”
A7553A Ductile Iron
7901TA ⅜” ⅜”
1.95
7901TB ¼”
Brass
7901TC ½”
½”
7053T
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square
root of pressure drop. Example: 7901T @ 9 PSIG = 1.95 x 9 = 5.85 GPM/propane. For NH3 flow,
multiply propane flow by .90.
E8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
“V”-Ring Seal Globe and Angle Valves
General Information Installation and Operation Note
RegO® Globe and Angle Valves are designed and manufactured Containers and pipe lines should be thoroughly cleaned before globe
especially to meet the rigid requirements of the LP-Gas industry. The and angle valves are installed. Large particles of solid foreign matter
high quality construction and wide variety of sizes and styles also can permanently damage the seating surface in the valve body,
make them highly suited to many other industries such as anhydrous causing the valve to leak. Use a minimum amount of a suitable pipe
ammonia, chemical and petrochemical. dope on the male connecting threads as excess amounts may fall off
and be carried into the valve, causing damage to the seat or other
These ductile iron valves are available in both threaded and flanged operating parts.
connections. Threaded connections are available in 1⁄2” F. NPT to 3”
F. NPT sizes. Flanged connections are available in 11⁄2”, 2” and 3”
It is totally unnecessary to use excess force in opening or closing
pipe sizes.
RegO® valves. The type of seat disc material used and the general
The ductile iron used in these valves has a 60,000 PSIG tensile design of these valves permits them to be opened and closed easily.
strength which closely approaches that of steel castings. Its yield Proper valve operation insures unusually long life.
strength of 45,000 PSIG and elongation of 15% is also comparable
to that of steel castings. These material features assure the ability of Wrenches must never be used to operate valves equipped with
the valve body to withstand impact, wrenching stresses and thermal handwheels and designed for hand operation.
shock. This ductile iron conforms to ASTM specification A395.
Downstream Accessory Boss
RegO® globe and angle valves are designed for working pressures
These RegO® valves incorporate a plugged 1⁄4” F. NPT boss on
up to 400 PSIG WOG and for operating temperatures from -40° F. to
the downstream side of the body for attaching either a hydrostatic
+160° F.
relief valve or vent valve. Boss size on the 2” and 3” valves has been
increased to allow a ¾” drilling for accommodation of a standard by-
“V”-Ring pass valve or jumper lines.
Stem Seal Hydrostatic Relief—When the design of the piping installation
is such that liquid may be locked between two shut-off valves,
a hydrostatic relief valve should be installed in the lines
between the valves. The pressures which can develop due to
The “V”-ring spring-loaded pressure seal used in these RegO® globe temperature increase in a liquidfull line are tremendous and
and angle valves is the most effective stem seal yet developed. It can easily damage the valves or piping unless a hydrostatic
should not be confused with conventional valve stem packing where
relief valve is installed.
the seal is obtained by compressing the packing around the stem by
means of a packing gland with resultant hard operation and frequent
packing replacement.
Vent Valve—If the globe or angle valve is used as a shut-off
valve on a loading hose, a vent valve should be installed in the
E
The wax like surface of the teflon “V”-ring seal and consequent low
friction assures leak-tight performance for an indefinite period where downstream boss to allow liquid trapped beyond the shut-off
periodic retightening of the packing is not required and the seal valve to be vented before disconnecting the hose coupling.
provides extra long service life.
General Features
Heavy Duty Handwheel
Teflon “V”-Ring
provides easy operation.
Spring-Loaded Pressure
Seal for leak-proof
O-Ring Wiper keeps sand operation. No packing to
and grit away from pressure adjust or replace.
seal and stem threads.
E9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
“V”-Ring Seal Globe and Angle Valves for Bulk Storage Containers,
Transports, Bobtails and Plant Piping A7500 Series and TA7500 Series
Application
Specifically designed to assure positive shut-off and long,
maintenancefree service life in liquid or vapor service on bulk storage
containers, transports, bobtails, cylinder filling plants and plant
piping.
The high quality construction and wide variety of sizes make them
highly suited for use with LP-Gas, anhydrous ammonia and in the
chemical and petrochemical industries.
TA7034
Features UL
®
• Swivel seat disc assembly minimizes the seat disc from grinding on
the body seat. The seat disc stops rotating as soon as it touches
the body seat. This feature provides for good seat alignment and
A7505AP
assures long seat life.
• 1⁄4” F. NPT plugged boss on the downstream side of the valve body A7514AP
allows attachment of a hydrostatic relief valve or vent valve.
• Heavy duty rolled ACME stem threads provide quick action and long
service life. A7513AP
E
Materials
Body.................................................................................. Ductile Iron
Bonnet (7034, 7505-7508).......................................................... Steel
Bonnet (7509-7518).......................................................... Ductile Iron
Valve Stem.................................................................. Stainless Steel
Wiper Ring................................................................ Synthetic Rubber A7517AP
Seat Disc.............................................................. See Ordering Chart PRODU A7517FP
10
O
“V”-Rings.................................................................................... Teflon
G
CT
RE
E
Y
AR A
WA R R
Ordering Information
Part Number Flow at 1 PSIG Pressure Accessories
Drop (Cv) (GPM/
Buna N Seat Discs Teflon Seat Discs* Propane)***
Inlet and Outlet Port Hydrostatic
Globe Angle Globe Angle Connection Diameter Globe Angle Relief Valve Vent Valve
- - TA7034P TA7034LP ½” F. NPT 10.0 14.8
¾”
A7505AP A7506AP TA7505AP TA7506AP ¾” F. NPT 12.0 17.7
A7507AP A7508AP TA7507AP - 1” F. NPT 1” 17.8 22.0
A7509BP A7510BP TA7509BP TA7510BP 1¼” F. NPT 1¼” 36.5 54.0
A7511AP A7512AP TA7511AP TA7512AP 1½” F. NPT 43.0 55.5
1½” SS8001U TSS3169
A7511FP - TA7511FP 1½” Flange** 46.0 -
-
A7513AP A7514AP TA7513AP 2” F. NPT 75.0 88.5
2”
A7513FP A7514FP TA7513FP TA7614FP 2” Flange** 78.0 133.0
A7517AP A7518AP TA7517AP - 3” F. NPT
3⅛” 197.0 303.0
A7517AP A7518FP TA7517FP - 3” Flange**
E10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Globe and Angle Valve Dimensions
Dimensions
Flanges
Valve Number
Drawing (A or TA Prefix) Inlet & Outlet Port Diameter A B C D E F G
7034P ½” F. NPT
¾” 311⁄16”
7505AP ¾” F. NPT -
A
7511AP 1½” F. NPT 1½” 6 ⁄ ”
13 16 53⁄16” -
- - - -
7513AP 2” F. NPT 2” 73⁄16” 5⅞”
A
-
D
B
7518FP 3” Flange 3⅛” 11¾” 6¼” 8¼” 1⅛” 5” 9”
E
D B
F
NOTE: Regarding 7505AP through 7510BP — the thread used for assembling the bonnet to the body of the valve is a left hand thread. We advise our customers to be cognizant of this assembly
design in attempting to remove the bonnets of these valves in order to avoid serious damage to the valves.
Flange Dimensions
Valve Number (A or TA
Prefix) Size Flange Drilling D E F H
* Reducing screwed flanges are available for reducing 11⁄2” flange to 1 or 11⁄4” pipe thread and 3” flange to 21⁄2” pipe thread. Order from your local piping supplier.
E11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Flange Seal Globe and Angle Valves
Nylon bearing
General Features surrounds stem to
Rugged quick-acting prevent galling.
Acme threads on stem.
Threads are under flange Rubber flange ring
ring . . . dust, sand and grit stem seal effectively
can’t reach them. prevents gas escape.
The higher the
Swivel seat cannot pressure, the tighter
grind during valve the seal.
opening or closing.
Metal to metal back
Synthetic Rubber seat permits
E Seat Disc replacement of
flange ring with
valve in service.
E12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Flange Seal Globe and Angle Valves for Bulk Storage Containers, Filling
Hoses and Plant Piping 7704, 7705 and 7706 Series
Application
Designed to assure positive shut-off and long maintenance-free
service life in liquid or vapor service. Ideally suited for use on cylinder
charging manifolds, truck filling hoses, bulk storage containers and
plant piping.
The high quality construction and wide variety of sizes make them
highly suited for use with LP-Gas, anhydrous ammonia and in the
chemical and petrochemical industries.
UL
®
• Swivel seat disc minimizes grinding on the body seat and assures
longer service life. E
• “Dropped seat” body design of the angle valve provides high flow
capacity.
Materials
Body.................................................................................. Ductile Iron A7706 P 7704 LP
Bonnet (7704, 05, 06)................................................................. Brass A7704 LP
Bonnet (7704, 05, 06).................................................................. Steel 7706 P
Stem (7704, 05, 06).................................................................. Bronze A7706 P
Stem (7704, 05, 06)..................................................... Stainless Steel
Flange Ring.............................................................. Synthetic Rubber
Seat Disc.................................................................. Synthetic Rubber
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Flow at 1 PSIG Pressure Drop (Cv) (GPM/Propane)* Accessories
Globe Angle Inlet & Outlet Connection (F. NPT) Globe Angle Hydrostatic Relief Valve Vent Valve
7704P 7704LP
½” 7.3 12.3
A7704P A7704LP
SS8001J or SS8001L TSS3169
7705P 7706P
¾” 11.5 17.7
A7705P A7706P
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square root of pressure drop. Example: A7704LP @ 9 PSIG =12.3 x 9 = 36.9 GPM/propane. For NH3 flow,
multiply propane flow by .90.
E13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Flange Seal Liquid Transfer Angle Valves for Bulk Storage Containers
7550 and 7551 Series
Application
Designed especially for liquid transfer of LP-Gas from consumer bulk
storage containers when used with a Chek-Lok® or equipped with
an integral excess flow valve. May also be used for vapor LP-Gas
service.
are not met. Refer to the Warning Bulletin in the Excess Flow Valve
Section of this catalog.
Features
• Flange seal stem design provides for leak-proof operation. No
packing to retighten or replace.
• Resilient swivel seat disc assures longer seat life and easy, positive
shut-off.
Materials
Body (7750, 51).......................................................................... Brass
Body (A7750, 51).................................. Cadmium Plated Ductile Iron
Bonnet (7750, 51)....................................................................... Brass
Body (A7750, 51)........................................................................ Steel
PRODU
Stem (7750, 51)........................................................................ Bronze
10
O
G
CT
E
Y
AR A
WA R R
Ordering Information
Flow at 1 PSIG Excess Flow Accessories
(Cv) Pressure Approximate
Inlet Connection Outlet Connection Integral Excess Drop* Closing Flow** Hydrostatic Relief
Part Number (F. NPT) (F. NPT) Flow (GPM/Propane) (GPM/Propane) Valve Vent Valve
7550P 3127U 3165
No 13.3 -
A7550P SS8001J TSS3169
¾”
7550PX 3127U 3165
¾” Yes - 16.0
A7550PX SS8001J TSS3169
7551P 3127U 3165
½” No 8.9 -
A7551P SS8001J TSS3169
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square root of pressure drop. Example: 7550P @ 9 PSIG = 13.3 x 9 = 39.9 GPM/propane. For NH3 flow, multiple propane flow by .90.
* * For NH3 flow, multiply propane flow by .90.
E14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Tank Car Angle Valves for Railroad Tank Cars
TA7894P
Features
• “V”-ring spring-loaded pressure seal design provides dependable,
leak-free operation. No packing to retighten or replace.
• Wiper o-ring eliminates entrance of dirt and grit into stem area that
can prohibit smooth operation.
• Heavy duty ACME stem threads give quick action and are
hardened for long service life.
• Full diameter seat provides greater flow capacity and low pressure
drop.
51⁄4"
Materials
Body.................................................................................... Ductile Iron
“V”-Rings......................................................................................Teflon
O-Ring........................................................................Synthetic Rubber 103⁄8"
Stem.............................................................................. Stainless Steel Approx.
Bonnet................................................................................. Ductile Iron
Seat Disc......................................................................................Teflon
Handwheel.............................................. Cadmium Plated Ductile Iron
311⁄16"
Approx.
PRODU
10
O
8"
G
CT
RE
Approx.
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Accessories
Outlet Connection Flow At 1 PSIG (Cv) Hydrostatic Relief
Part Number Inlet Connection ([Link]) Pressure Drop Valve Vent Valve
TA7894P Tank Car Flange 2” 112 SS8001U TSS3169
* To obtain approximate flow at other than 1 PSIG pressure drop, multiply flow in table by square root of pressure drop. Example: TA7894P @ 9 PSIG = 112 x 9 = 336 GPM/propane. For NH3 flow,
multiply propane flow by .90.
E15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Multipurpose Valve for Filling of NH3 Containers
A8016DBC
Application
Designed specifically for use as a manual filler valve on anhydrous
ammonia applicator tanks. This valve incorporates an integral back
check valve.
Features
• Positive seating back check valve opens for maximum flow at
minimum pressure drop when filling — regardless of the type of
coupling in which the valve is installed.
• Back Check seat is fully contained in the tank coupling for maximum
protection in the event of external damage to the valve.
E
Materials
Body.................................................................................. Ductile Iron
Bonnet......................................................................................... Steel
“V”-Rings.................................................................................... Teflon
Stem............................................................................ Stainless Steel
Seat Disc.................................................. Resillient Synthetic Rubber
Back Check Valve........... Stainless Steel, Steel and Synthetic Rubber
Springs........................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Filling Capacity at 20 PSIG Accessories
Part Number Inlet Connection Filling Connection
Pressure Drop GPM/NH3 Hydrostatic Relief Valve Vent Valve
A8016DBC 1 1/4” 1 3/4” 95 SS8001J TSS3169
* Determined at 9.5 to 12 PSIG differential.
* * Determined at 100 PSIG inlet.
E16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Multipurpose Valve for Filling of NH3 Containers
A8016DP
Application
Designed specifically for use as a manual valve or vapor equalizing
valve on anhydrous ammonia applicator and nurse tanks.
Features UL
®
• Excess flow seat is fully contained in the tank coupling for maximum
protection in the event of external damage to the valve.
• Resilient seat disc assembly is fully contained on three sides for A8016DP
bubble-tight shut-off and long service life.
Materials
Body.................................................................................. Ductile Iron
Bonnet......................................................................................... Steel
“V”-Rings.................................................................................... Teflon
Stem............................................................................ Stainless Steel
Seat Disc................................................... Resilient Synthetic Rubber
Excess Flow Valve.................................... Stainless Steel--Steel Body
Springs........................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Approximate Excess Flow
Closing Flows Accessories
Inlet Connection Filling Connection Filling Capacity At 20 PSIG Liquid* Vapor** Hydrostatic
Part Number (M. NPT) (M. ACME) Pressure Drop GPM/NH3 GPM/NH3 CFH/NH3 Relief Valve Vent Valve
A8016DP 1¼” 1¾” 95 44 24,000 SS8001J TSS3169
* Determined at 9.5 to 12 PSIG differential.
* * Determined at 100 PSIG inlet.
E17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Multipurpose Valves for Liquid Withdrawal of LP-Gas and NH3 Containers
A8017D & A8020D
Application
Designed especially for use as a high capacity liquid withdrawal valve
on LP-Gas and anhydrous ammonia containers.
Features A8017DP
• Excess flow seat is fully contained in the tank coupling for maximum
protection in the event of external damage to the valve.
• A8017DH has two plugged 1⁄4” NPT ports, one on the top and the
other on the side, accommodate either a vent valve or hydrostatic
relief valve.
Materials
Body.................................................................................. Ductile Iron
Bonnet......................................................................................... Steel
Stem............................................................................ Stainless Steel
A8020D
Seat Disc.................................................. Resillient Synthetic Rubber PRODU
10
O
“V”-Rings.................................................................................... Teflon
G
CT
RE
E
Y
AR A
WA R R
Ordering Information
Accessories
Part Inlet Connection Outlet Connection Approximate Excess Flow Liquid Closing Flow** Hydrostatic Relief
Number (M. NPT) (F. NPT) (GPM/Propane) Valve Vent Valve
A8017DH 49 Not Required
1”
A8017DP 1¼” 55 TSS3169
SS8001J
A8017DLP ¾” 49
A8020D 1¼” 1” 78 SS8001J TSS3169
E18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Multipurpose Valve for Filling and Liquid Transfer of NH3 Containers
A8018DP
Application
Designed primarily for use as a combination filler and liquid withdrawal
valve on three-opening applicator tanks or on nurse tanks.
Features
• Functions as both a filler valve and liquid transfer valve, in one unit.
• Triple guide filler valve check provides for dependable shut-off A8018DP
performance when filling ceases.
Materials
Body.................................................................................. Ductile Iron
Bonnet......................................................................................... Steel
Stem............................................................................ Stainless Steel
Seat Discs................................................. Synthetic Resilient Rubber
“V”-Rings.................................................................................... Teflon
Excess Flow Valve................................... Stainless Steel - Steel Body
Springs........................................................................ Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Filling Capacity At Approximate Accessories
Inlet Outlet Filling 20 PSIG Excess Flow
Part Connection Connection Connection Pressure Drop Liquid Closing Hydrostatic
Number (M. NPT) (F. NPT) ([Link]) GPM/NH3 Flow GPM/NH3 Relief Valve Vent Valve
A8018DP 1¼” 1” 1¾” 74 50 SS8001J TSS3169
* Determined at 9 to 12 PSIG differential.
E19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Warning Notice
The following warning information, Part Number 903-500, is included
with each shipment of Quick-Acting and Tank Car Valves to the first
purchaser of the product from the factory.
E20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section F
F F
F1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
This warranty does not extend to any product or part that is not The Limited Warranty stated above is a factory warranty to the first
installed and used continuously after installation in accordance with purchasers of ECII products. Since most users have purchased
ECII’s printed instructions, all applicable state and local regulations, these products from ECII distributors, the user must within thirty (30)
and all applicable national standards, such as those promulgated by days after the user’s discovery of what user believes is a defect,
NFPA, DOT and ANSI. This warranty does not extend to any product notify in writing and return the product to the distributor from whom
or part that has been damaged by accident, misuse, abuse, failure to he purchased the product/part. The distributor may or may not at
maintain, or neglect, nor does it extend to any product or part which the distributor’s option choose to submit the product/parts to ECII,
has been modified, altered, disassembled, or repaired in the field. pursuant to this Limited Warranty. Failure by buyer to give such
This warranty does not cover any cosmetic issues, such as scratches, written notice within thirty (30) days shall be deemed an absolute and
dents, marring, fading of colors or discoloration. unconditional waiver of buyer’s claim for such defects. Acceptance
of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
F2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
F
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Back Pressure Check Valves ..................................................... F25
Chek-Lok® Excess Flow Valves . ............................................... F18
Chek-Lok® Operation . ............................................................... F17
Cross Reference by Part Number .............................................. F28
Double Check Filler Valves ........................................................ F20
Excess Flow Valves . .................................................................... F8
Limitations of Excess Flows ......................................................... F7
Safety Warning for Excess Flows . ............................................... F4
Testing of Excess Flows ............................................................... F7
Troubleshooting of Excess Flows . ............................................... F6
Vapor Equalizing Valves ............................................................. F23
Warnings and Labels . ................................................................ F27
F3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Excess Flow Valves
Safety Warnings Purpose
In its continuing quest for safety, Engineered Controls International, Inc. publishes a series of bulletins explaining
the hazards associated with the use, misuse, and aging of LP-Gas valves and regulators. It is hoped that these
factual bulletins will make clear to LP-Gas dealer managers and service personnel, that the utmost care and
attention must be used in the installation, inspection, and maintenance of these products, or problems could
occur which would result in injuries and property damage.
The National Fire Protection Association Pamphlet #58 - 2004 Edition, “Liquified Petroleum Gas Code” states
that, “persons who transfer liquid LP-Gas, who are employed to transport LP-Gas, or whose primary duties fall
within the scope of this code shall be trained in proper handling procedures. Refresher training shall be provided
at least every three years. The training shall be documented.” These “ECII® Safety Warnings” may be useful in
training new employees and reminding older employees of hazards that can occur. It is recommended that all
employees be furnished with a copy of NPGA Safety Pamphlet 306-88, “LP-Gas Regulator and Valve Inspection
and Maintenance.”
Nature of Warnings Engineered Controls International, Inc. provides excess flow valves
It is recognized that warnings should be as brief as possible, but with a number of closing ratings. Engineered Controls International,
the factors involved in excess flow valve failures to perform are not Inc. obviously can take no responsibility for the proper selection or
simple. They need to be fully understood. If there is a simple warning, correct installation of any valve.
it would be:
Excess flow valves do not provide complete shut-off because there is
Make sure that the excess flow valve really closes when a bleed at the check to permit pressure equalization.
the flow exceeds normal transfer flow.
Causes of Failure to Close
This bulletin is not intended to be an exhaustive treatment of excess
Installers, LP-Gas plant managers and service personnel should be
flow valves, and certainly does not cover all safety practices that
aware that the excess flow valves may not close if these conditions
should be followed in installation, operation and maintenance of LP-
are present.
Gas systems which include excess flow valves.
1. The piping system restrictions (due to pipe length, branches,
Selection and Installation reduction in pipe size or number of other valves) decrease the
The selection of a given closing rating of an excess flow valve flow rate to less than the valve’s closing flow.
involves an analysis of the complete piping system and is beyond the
scope of this bulletin.
F
F4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Excess Flow Valves
2. The break or damage to the downstream line is not Because of these limitations, it is good industry practice to NOT
large enough to allow enough flow to close the valve. rely entirely on excess flow valves for protection. Installation of
emergency shut-off valves with remote controls is recommended in
addition to excess flow valves.
Testing
The National Propane Gas Association Safety Bulletin #113-78
states:
In general, most testing makes use of the fact that excess flow valves
are “surge sensitive” and will close quicker under a sudden flow surge
than under steady flow. A sufficient surge can often be created by
using a quick open/close valve to control sudden, momentary flow
into a tank or piping section containing very low pressure. An audible
click from the excess flow valve (and corresponding stoppage of flow)
indicates its closure.
Any test of any excess flow valve will not prove that the valve will
close in an emergency situation, due to reasons cited before. This
test will only check the valve’s condition, and the flow rate sizing for
those test conditions.”
F
General Warning
4. LP-Gas pressure upstream of the excess flow valve,
particularly due to low temperature, is not high All ECII® products are mechanical devices that will eventually
enough to produce a closing flow rate. become inoperative due to wear, contaminants, corrosion and aging
of components made of materials such as metal and rubber.
The environment and conditions of use will determine the safe service
life of these products. Periodic testing at least once a year when tank
pressures are low and maintenance, as required, are essential.
F5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Troubleshooting Excess Flow Valve Installations
Periodical Inspections for Excess Flow Valves 2. Line Restriction Too Great
An excess flow valve installed
Excess flow valves should be tested and proven at the time of in a tank outlet will not close if
installation and at periodic intervals not to exceed one year. the line beyond it is reduced or
CAUTION: Testing an excess flow valve in the summer when if the flow is otherwise restricted
tank pressures are high will not prove that the same valve will by too many fittings or too
also function under low pressure conditions in the winter. Once long a run because the line is
a year testing should be conducted during the winter. incapable of passing the amount
of LP-Gas necessary to create
The test should include a simulated break in the line by the quick an “excess” flow. This condition
opening of a shut-off valve at the farthest point in the piping that should be corrected when testing
the excess flow valve is intended to protect. If the excess flow valve a system by simulating a break
closes under these conditions, it is reasonable to assume that it will at the farthest possible point and
close in the event of accidental breakage (clean break) of the piping replacing any restrictive hose,
at any point closer to the excess flow valve. pipe or fittings.
The National Propane Gas Association Safety Bulletin Number 113- 3. Improper Operating Practice
78 states:
A restriction can also be imposed
In order to test an excess flow valve in a piping system, the upon the excess flow valve by an
flow through the valve must be made to exceed the valve’s improperly opened valve at the
closing rating. This testing should only be attempted by trained tank outlet. The shutoff valve
personnel familiar with the process. If no one at the facility should be either fully opened
has experience in proper testing, outside expert help should or fully closed. If “throttled,” the
be obtained. The exact procedure used may vary with the valve could reduce the amount
installation, advisability of gas discharge and availability of of LP-Gas passing through the
equipment. excess flow valve in a sufficient
amount to keep it from closing.
In general, most testing makes use of the fact that excess flow valves Throttling operations should not
are “surge sensitive” and will close quicker under sudden flow surge be performed in the lines being
than under steady flow. A sufficient surge can often be created by protected by excess flow valves.
using a quick open/close valve to control sudden, momentary flow
F into a tank or piping section containing very low pressure. An audible
4. Improper Selection
click from the excess flow valve (and corresponding stoppage of flow) The many types of excess flow
indicates its closure. valves available are designed for
specific jobs. The excess flow
A test involving venting gas to the atmosphere is hazardous valve selected should remain
and may be impractical or illegal. open during normal flow but close
Any test of any excess flow valve will not prove that the valve will at “excess” flow. An inspection
close in an emergency situation, due to reasons cited before. This which simulates a line break
test will only check the valve’s condition and the flow rate sizing for prior to start-up operations will
those test conditions. determine if the proper valve has
been selected.
What prevents excess flow valves from closing when the line
breaks? 5. Tampering with Excess Flow Valves
F6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
The Limitations of Excess Check Valves for LP-Gas
Excess flow check valves have been of help in limiting gas loss in Where excess flow valves are installed, they should be checked
many incidents involving breakage of hoses and transfer piping. to see that:
Thus, they do provide a useful safety function in LP-Gas systems.
However, there have also been transfer system accidents where 1. They are installed in the correct direction — the arrow on the
excess flow valves have been ineffective in controlling gas loss due to valve indicates the shut-off direction.
a variety of conditions and to the inherent limitations of these valves.
This bulletin explains what protection excess flow valves can offer, 2. The flow rating on the valve is proper for the installation. The
points out conditions which can interfere with that protection, and rating must be above the normal system flow, but not higher than
offers suggestions for effective excess flow valve installation. necessary to prevent “nuisance” closing in normal conditions. If
the manufacturer’s catalog information is not sufficient, the valve
An excess flow valve is a protective device to help control the suppliers can provide sizing assistance.
discharge of product in the event of complete breakage of pipe lines
or hose rupture. However, an excess flow valve can only offer limited 3. In-line excess flow valves are installed so likely piping damage
protection from gas discharge, because it will only close under those will occur downstream of the valve and will not separate the
conditions which cause the flow through the valve to exceed its rated
valve from the upstream piping.
closing flow, and even when closed it necessarily allows some “bleed”
past the valve. When the excess flow valves can be examined separate from the
line (before the installation or if removed for system maintenance),
An excess flow valve is not designed to close and thus may not they should be checked to see that the parts are in good condition
provide protection, if any of the following conditions are present: and that the poppet can be pushed fully closed.
1. The piping system restrictions (due to pipe length, branches,
Testing of Excess Flow Valves
reduction in pipe size, or number of other valves) decrease the
flow rate to less than the valve’s closing flow. (Valve should be
In order to test an excess flow valve in a piping system, the flow
selected by closing flow rating — not just by pipe size). through the valve must be made to exceed the valve’s closing
rating.
2. The break or damage to the downstream line is not large enough to This testing should only be attempted by trained personnel
allow enough flow to close the valve. familiar with the process. If no one at the facility has experience
in proper testing, outside expert help should be obtained. The
3. A shut-off valve in the line is only partially open and will not allow exact procedure used may vary with the installation, advisability
enough flow to close the excess flow valve. of gas discharge, and availability of equipment.
4. LP-Gas pressure upstream of the excess flow valve, particularly In general, most testing makes use of the fact that excess flow
due to low temperature, is not high enough to produce a closing valves are “surge sensitive” and will close quicker under a sudden F
flow rate. flow surge than under steady flow. A sufficient surge can often
be created by using a quick-closing valve to control sudden,
5. Foreign matter (such as welding slag) is lodged in the valve and momentary flow into a tank or piping section containing very
prevents its closing. low pressure. An audible click from the excess flow valve (and
corresponding stoppage of flow) indicates its closure.
6. A buildup of process material (sludge), which may be found in
LPGas, may occur over a period of time and cause the valve to A test involving venting gas to the atmosphere is hazardous and
stick open. may be impractical, or illegal.
7. The piping break or damage occurs upstream of an in-line excess Any test of any excess flow valve will not prove that the valve
flow valve, so the escaping product is not passing through the will close in an emergency situation, due to reasons cited before.
valve. This test will only check the valve’s condition, and the flow rate
sizing for those test conditions.
8. The flow through the valve is in the wrong direction. (Excess flow
For additional information on excess flow valves and other means
valves only respond to flow in one direction.)
of
shut-off protection, contact Engineered Controls International,
[Link] excess flow valve has been damaged, or is otherwise not in
Inc. and refer to NFPA 58.
operating condition.
Because of these limitations of excess flow valves, they should not Prepared by
be relied upon as the only means of controlling the escape of product NATIONAL PROPANE GAS ASSOCIATION
in the event of piping damage. When possible, shut-off protection by The purpose of this bulletin is to set forth general safety practices for
quick closing valves, with shut-off controls accessible in spite of likely the installation, operation, and maintenance of LP-Gas equipment.
line damage, should be provided in addition to, or instead of excess It is not intended to be an exhaustive treatment of the subject, and
flow valves. should not be interpreted as precluding other procedures which
would enhance safe LP-Gas operations. The National Propane Gas
Association assumes no liability for reliance on the contents of this
bulletin.
F7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves
Spring retainer.
Precision machining.
F8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves for Liquid or Vapor Service
1519C Series
Application
Designed for top mounting in storage tank manhole covers for liquid
or vapor applications. The tapped inlet allows for an optional 1” NPT
dip pipe connection to withdraw liquid from the top of the tank.
Features
• Precision machined
Materials
1519C2 1519C2
Body........................................................................................... Brass UL
®
PRODU 1519C4
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information Typical Installation
Features
• Precision machined.
Materials
1519A Series and 1519B Series
Body........................................................................................... Brass
Valve Poppet w/Stem................................................................. Brass 1519A2, 1519A3, 1519A4, 1519B4,
Spring.......................................................................... Stainless Steel A1519A2, A1519A4, A1519B4
Guide.......................................................................................... Brass UL
®
A1519 Series
Body................................................................ Cadmium Plated Steel
Valve Disc........................................................ Cadmium Plated Steel
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel
F Guide................................................................................. Ductile Iron
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
A1519A6
F10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves for Liquid or Vapor 3272 Series, 3282 Series, 3292
Series, A3272 Series, A3282 Series, A3292 Series, 7574 and 12472
Application
Designed for liquid or vapor use for filling, withdrawal and vapor
equalizing in container or line applications. They are intended for long
lines or branch piping where tank-mounted excess flow valves are
inadequate.
Features
• Precision machined.
UL
Materials
®
Typical Installation
Series 3272, 3282, 3292, 7574, 12472
Body........................................................................................... Brass
Seat Disc.................................................................................... Brass
Stem........................................................................................... Brass
Spring.......................................................................... Stainless Steel
Guide (12472 ONLY)................................................................. Plastic
10
A3272G
E 200 A3292B O
C - 7574
G
20
CT
RE
D
S
P ro p a ne F lo w (G P M )
P ro p a ne F lo w (G P M )
C
100
10
Y
10 90
NT
9 80 B
8 B 70 C
E
Y
7 AR A
WA R R
6 60 A
5 50
4
40
3
A
30
2 20
1
.07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 910 10
Drop Across Valve (PSI) .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10
Drop Across Valve (PSI)
Ordering Information NOTE: Multiply flow rate by .94 to determine liquid butane flow and by .90 to determine liquid anhydrous ammonia flow.
F11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves for Container Service
A7537 Series, A7539 Series, A8523 and A8525
Application
Designed for mounting in threaded full or half couplings in container
installations. They may be used for filling, withdrawal or vapor
equalizing applications. The exceptionally low pressure drop makes
them ideal for pump suction lines. If a riser pipe to the vapor space is
used with these valves, the minimum inside diameter of the riser pipe
must be at least two times the valve thread size in order not to restrict
flow to the side inlet ports.
Features
• Precision machined.
• Separate models for installation in either half or full couplings. Typical Installation
Materials UL®
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
NOTE: Multiply flow rate by .94 to determine liquid butane flow and by .90 to determine liquid anhydrous ammonia flow.
Ordering Information
B Approximate Closing Flow*
For Use With A Outlet C D
Vapor SCFH (Propane)
Part This Type Inlet Connection Connection Wrench Hex Effective Length Liquid (GPM
Number Coupling M. NPT NPT Flats (Approx.) Propane) 25 PSIG Inlet 100 PSIG Inlet
A8523 Half ¾” ¾” Male 1⅛” 1¾” 15 5,170 8,800
A8525 Half 1¼” 1¼” Male 1¾” 2⅛” 35 12,540 21,560
A7537L4 Half
75 13,000 25,600
A7537L4F Full
A7537N4 Half 2” Male
2” and 2⅝“ 2½” 125 25,000 42,500
A7537N4F Full 1¼” Female
A7537P4 Half
150 30,500 52,000
A7537P4F Full
A7539R6 Half
150 32,100 55,500
A7539R6F Full
A7539T6 Half 3” Male
3” and 3¾” 3⅛” 200 39,400 68,300
A7539T6F Full 2” Female
A7539V6 Half
250 51,100 88,700
A7539V6F Full
* Based on horizontal installation of excess flow valve. Flows are slightly more when valves are installed with outlet up; slightly less when installed with outlet down.
F12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves for Vapor or Liquid
A2137 Series and 2139 Series
Application
UL®
Features
• Precision machined.
Materials
A2137 Series
Body................................................................ Cadmium Plated Steel
Disc.................................................................. Cadmium Plated Steel Container Service Pipe Line Service
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel F
Guide............................................................... Cadmium Plated Steel
2139 Series
Body........................................................................................... Brass
Disc............................................................................................. Brass
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel
Guide.......................................................................................... Brass
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
NOTE: Multiply flow rate by .94 to determine liquid butane flow
and by .90 to determine liquid anhydrous ammonia flow.
Ordering Information
Approximate Closing Flows***
A B D Vapor SCFH (Propane)
Inlet Connection Outlet Connection C Effective Length Liquid
Part Number NPT F. NPT Wrench Hex Flats (Approx.) (GPM Propane) 25 PSIG Inlet 100 PSIG Inlet
A2137 2” Male and 1¼” 50 10,000 17,000
2”* 27⁄16” 19⁄16”
A2137A Female 70 14,000 25,000
2139 3” Male and 2” 125 26,500 46,000
3”** 3½” 15⁄16”
2139A Female 160 32,700 57,200
F13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valves for Flange Mounting in Container Service
A3500 Series and A4500 Series
Application
Designed for mounting in flanged tank connections with internal
UL®
If a riser pipe to the vapor space is used with these excess flow
valves, the minimum inside diameter of the riser pipe must be at least
two times the valve thread size in order not to restrict flow to the side
inlet ports.
Features
• Precision machined.
• Generous flow channels provide low pressure drop minimizing
cavitation in pump suction lines.
• Cotter pin prevents loss of spring retainer due to vibration in
service.
• Stainless steel spring provides consistent closing flow and long
service life.
Materials
Body................................................................ Cadmium Plated Steel
F Seat Disc......................................................... Cadmium Plated Steel
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel PRODU
10
O
CT
RE
S
10
Y
Flanged Installation In Container
NT
E
Y
AR A
WA R R
The valve is screwed into this opening by fitting a 1⁄4” flat metal piece
into the slot and turning until hand tight. A lubricant may be used, but
a luting compound is not necessary since this joint does not have to
be gas tight.
service. These valves are designed especially for use with RegO®
globe and angle valves.
Features
• 2723C provides a 3⁄4” dip pipe inlet connection for top-mounted
liquid or bottom-mounted vapor requirements.
• Precision machined.
Materials A8013D
A8013D Series
Body................................................................ Cadmium Plated Steel
Disc.............................................................................. Stainless Steel
Stem............................................................................ Stainless Steel
Spring.......................................................................... Stainless Steel
Guide............................................................... Cadmium Plated Steel
Insert........................................................................... Stainless Steel
F
2723C
Body........................................................................................... Brass
Valve Poppet.............................................................................. Brass
Retainer...................................................................................... Brass
Spring.......................................................................... Stainless Steel
2723C
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
A. B. D. Approximate Closing Flow**
Inlet Outlet C. Effective E.
Vapor SCFH (Propane)
Connection Connection Wrench Hex Length Threaded Liquid
Part Number M. NPT NPT Flats (Approx.) End To Port (GPM Propane) 25 PSIG Inlet 100 PSIG Inlet
A8013D ¾” ⁄ ”
9 16 39
8,700 14,700
A8013DA 1¼” 1” 1⅞” 21⁄32” - 44
A8013DB 1¼” 11⁄16” 55 10,900 19,300
2723C 1¼” ¾” 111⁄16” 11⁄4” 33⁄16” 20 3,900 6,900
* 3⁄4” F. NPT Dip Pipe Connection
** Based on horizontal installation of excess flow valve. Flows are slightly more when valves are installed with outlet up; slightly less when installed with outlet down.
NOTE: Multiply flow rate by .94 to determine liquid butane flow and by .90 to determine liquid anhydrous ammonia flow.
F15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Excess Flow Valve for Pressure Gauges
2884D
Application
Designed for container use in pressure gauge installations to minimize
UL
®
Features D
C
• Precision machined.
2884D B
• Suitable for use with all ¼” [Link] pressure gauges.
Materials PRODU
10
O
CT
RE
Body........................................................................................... Brass
S
Valve . ........................................................................................ Brass
10
Y
NT
E
Spring.......................................................................... Stainless Steel
Y
AR A
Ordering Information WA R R
Pin............................................................................... Stainless Steel
* Based on horizontal installation of excess flow valve. Flows are slightly more when valves are installed with outlet up; slightly less when installed with outlet down.
NOTE: Multiply flow rate by .94 to determine liquid butane flow.
3199W
Features
• Integral ball check design.
D
• Machined groove designed to break-off and allow excess flow valve Groove
ball to close.
PRODU
10
O
G
CT
RE
Typical Installation
S
Materials
10
Y
NT
E
Y
AR A
WA RR
Body........................................................................................... Brass NOTE:
Nut.............................................................................................. Brass No protection is afforded should break-off occur downstream of the
Bell.............................................................................. Stainless Steel groove. Also, restrictions introduced by the regulator may prevent
Spring.......................................................................... Stainless Steel closing of the valve due to limited flow capacity. The valve’s purpose
Retainer Spring........................................................... Stainless Steel is to protect the cylinder valve outlet should the regulator be broken
Retainer...................................................................................... Brass off of its connection (at the groove), in which case it will close. It must
not be depended upon to protect against breaks downstream of the
Ordering Information regulator.
F16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Chek-Lok® Excess Flow Valves
Designed to provide a convenient means of withdrawing liquid from The Chek-Lok® permits one transfer shut-off valve with an adapter to
stationary containers prior to moving the container. be used interchangeably on a number of tanks. With a Chek-Lok® on
each tank and a high capacity RegO® 7550P Series transfer valve
NFPA Pamphlet 58 standards require: 1) containers with 125 gallons
and adapter on all your service and delivery trucks – the need for
water capacity, or more, have a connection for liquid evacuation which
individual transfer valves is eliminated. This provides a substantial
is at least 3/4” NPT, and 2) containers designed for stationary use, have
savings without sacrificing safety.
no more propane than 5% of their water capacity in liquid form during
transportation. These rules apply to containers manufactured after
July 1, 1961.
Chek-Lok® Operation
Instructions to Open Chek-Lok® Connecting the
1 Loosen cap to vent any accumulated LP-Gas from the Chek-Lok. 7590U or 7591U
After venting stops, remove the cap. If venting does not stop,
retighten the cap and use other approved means to withdraw liquid Chek-Lok®
from the container.
NOTE: Use a suitable size wrench when removing the cap and
adapter from the Chek-Lok. Do not allow the Chek-Lok to un- 7550P Angle Valve
thread from the tank during removal. When necessary, use a
second wrench to secure the Chek-Lok in position.
4 Check the coupling nut and adapter assembly for leaks using a Connecting the
suitable leak detection solution.
7572FC or 7580FC F
If the Chek-Lok fails to open after following this procedure, the
pressure downstream of the shut-off valve should be increased Chek-Lok®
to equalize pressure in the Chek-Lok. It is simple to equalize
pressures using vapor from either the vapor return valve or service
valve, or from a hose end valve connected to the delivery truck. 7550P Angle Valve
2 Open shut-off valve fully. Liquid discharging to the atmosphere 7572-14A Adapter
should cause the excess flow feature of the Chek-Lok to close,
provided tank pressure is 35 PSIG or more.
If, for any reason, the excess flow valve does not close, the shut-
off valve must be closed immediately and must not be removed
until the system can be evacuated and the unit repaired. 7572FC or 7580FC Chek-Lok®
3 After the excess flow valve closes, remove the Adapter and Shut-
Off Valve Assembly.
In the absence of a 7550P transfer valve, a 3⁄4” A7505A Globe Valve
or A7506AP Angle Valve may be used. Follow the above procedures
4 Clean face of Chek-Lok and install the Cap with a gasket.
using the 7572C-15A adapter instead of the 7572C-14A. Use an ECII
IMPORTANT: Only use the proper Chek-Lok Cap. Do not use a
standard pipe cap. 7550P without an adapter in an emergency only.
CAUTION: Always wear approved protective gloves when working with the Chek-Lok®.Do not vent LP-Gas near possible source of ignition.
Chek-Lok® Mounting
Chek-Lok® Valves may be either top mounted with a dip tube
or bottom mounted. For bottom mounting, it is preferable to
position the coupling in the head or slightly off of the bottom.
This helps prevent the accumulation of sludge, etc. around the
valve which could affect the proper operation of the excess
flow valve.
F17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Chek-Lok® Excess Flow Valves
7590U and 7591U Series
Application 7590U with Cap
10
O
means of withdrawing liquid from stationary containers prior to moving
CT
RE
the container. The Chek-Lok® permits one transfer shut-off valve with
S
an adapter to be used interchangeably on a number of tanks. UL
10
Y
NT
® E
Y
AR A
WA R R
The 7590U and 7591U Chek-Loks® are also designed for use on
permanent installations provided the excess flow valve is sized
properly for the system and piping. NOTE: In some cases, it may
be necessary to use an in-line excess flow valve to protect the
downstream piping. This valve is not recommended for use as a liquid Cap C
source for pumps. Gasket
Features
B
• Extra strength connection between body and adapter provides Chek-Lok ®
increased strength. A
• Heavy duty brass cap requires at least 31/2 full turns for removal.
Materials
• O-ring seal on adapter provides a gas tight seal before the adapter
opens the equalizing stem. Body........................................................................................... Brass
Stem........................................................................................... Brass
• Eliminates need for individual transfer valves at each container. Spring.......................................................................... Stainless Steel
Seals....................................................................... Sunthetic Rubber
• UL listed. Valve Poppet.............................................................................. Brass
Gasket........................................................................................ Nylon
F C.
Body Wrench Hex
B.
Approximate
C.
Cap Wrench Hex
Approximate Closing
Flow, Liquid
Chek-Lok® Number Inlet Connection Outlet Connection Flats Effective Length Flats GPM (Propane)*
7590U ¾” M. NPT 115⁄8” 17⁄16” 20
15⁄8” UNF 15⁄16”
7591U 1¼” M. NPT 1¾” 111⁄16” 35
* Based on horizontal installation of excess flow valve. Flows are slightly more when valves are installed with outlet up, and slightly less when installed with outlet down.
Note: Multiply flow rate by .94 to determine liquid butane flow.
Features
• Built in nylon gasket provides a gas tight seal.
• Design eliminates the need to slug excess flow feature of Chek- PRODU
10
O
Lok® when removing the adapter.
G
CT
RE
S
10
A
• Built in bleeder valve allows controlled discharge of liquid before
NT
E
Y
AR A
WA R R
removing the adapter.
Ordering Information
Adapter Number Inlet Connection Outlet Connection A Wrench Hex Flats B Approximate Length
7590U-20 1⅝” F. NPT ¾” F. NPT 1¾” F. NPT 4⅛” F. NPT
F18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Union Style Adapters for 7590U and 7591U Valves
UL
PRODU
10
O
CT
RE
S
®
10
Y
NT
E
Y
AR
WA R RA
Ordering Information
Adapter Inlet Outlet A. Wrench Hex B. Approximate
Number Connection Connection Flats Length
7590U-10 1⅝” UNF ¾” F. NPT 1¾” 113⁄16” 7590U-10
10
O
G
CT
RE
UL
10
Y
NT
E
Y
AR A
WA R R ®
Ordering Information F
B.
Approximate
7572C-15A
Adapter Inlet Outlet A. Wrench Hex Effective
For Globe and
Number Connection Connection Flats Length
Angle Valves
7572C-14A ¾” F. NPT 1”
¾” M. NPT 1⅜”
7572C-15A ¾” M. NPT ¼”
F19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Double-Check Filler Valves
General Information
RegO® Double-Check Filler Valves incorporate a resilient upper
check valve, normally designated as a filler valve, and a lower check
valve, commonly called a back pressure check valve. Available in a Seal cap made of tough, resilient
range of sizes to cover virtually all LP-Gas storage containers, these molded plastic. Protects threads
valves are UL listed and meet NFPA standards, as well as other and internal working parts. Caps
safety requirements. are designed to contain normal tank
pressures, and must be kept on valves
Flow of liquid into the storage container opens both check valves. at all times.
When flow stops, they both are designed to close automatically to Long-wearing gasket permits hand-tight
permit the operator to disconnect the hose coupling. The automatic connection of cap and hose coupling.
closing action also helps prevent the discharge of container contents
in the event of hose failure. The lower back pressure check affords Safety groove is designed to shear
extra protection by restricting the discharge if the upper check fails to below the ACME thread, leaving the
function properly due to accidents or other causes. valve seats closed and unaffected if the
delivery truck pulls away with the hose
connected.
The double back check construction allows emergency inspection, Seat disc of special synthetic
repair, or replacement of the upper fill assembly without removing composition is extra thick for longer
product from the container. When the upper filler valve body is life.
removed, the lower back check valve provides a seal, permitting only Valve guide is precision machined to
some leakage, allowing a new upper filler valve body to be installed. assure positive seal.
Spare Gasket Ordering Information Exclusive swing-away lower back check
valve for extra fast filling is provided on
ACME Part Number
Models 6579 and 6587. Differs from
1¼” A2797-20R conventional design by swiveling to a
1¾” A2697-20R vertical position when opened.
2¼” A3184-8R
3¼” A3194-8R
Double-Check Filler Valves for Large Motor Fuel and ASME Tanks
6579 Series and 7579 Series
F Application Materials
Designed to provide fast filling of large motor fuel and ASME domestic Upper Body................................................................................ Brass
tanks. The 6579 Series incorporates a swing-away lower check which Lower Body................................................................................ Brass
greatly reduces pressure drop across the valve. This lower pressure Springs........................................................................ Stainless Steel
drop promotes faster filling rates and greater efficiency resulting in Washer and Seat Disc.............................................. Synthetic Rubber
more profitable operations. Cap............................................................................................ Plastic
UL
PRODU
10
O
Features
G
CT
7579P A
RE
®
10
Y
NT
E
Y
AR A
WA R R
• Double back check provides added system protection. A D C
• Both checks are spring actuated for quick, precise closure when
flow into the valve stops or reverses. B 7579
• 6579 Series swing-away check promotes faster filling for more 6579
profitable operations.
6579
Ordering Information
Part Number A. B. D. Propane Liquid Capacity at Various Differential Pressures (GPM)
C.
ACME Tank Effective
Wrench 5 PSIG 10 PSIG 25 PSIG 50 PSIG 75 PSIG
Cap Only Cap, Chain and Ring Hose Connection Length
Hex Flats
Connection M. NPT (Approx.)
7579 7579C 1¼” 50 70 111 157 192
7579P - 1¼” 37 52 82 116 142
1¾” 1⅞”
6579** 6579C** 1¼” 78 110 174 246 301
F20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Double Check Filler Valves for Forklift, Motor Fuel and RV Tanks
7647 Series
Application
Designed to provide fast filling of forklift, motor fuel, and recreational UL
®
Features
• Resilient seat disc in lower check designed to provide a gas tight
seal without leakage.
• Large 13⁄4” wrench flats on 7647SC allow use of socket wrench for
easy installation.
• Specify RegO® Filler Valves on all your original tank purchases to 7647SC
insure quality and dependable performance.
Materials UL
®
7647SA
7647DC
UL
®
PRODU
10
O
G
CT
RE
7647HF
10
Y
NT
E
Y
AR A
WA R R
7647H
Ordering Information
Part Number Propane Liquid Capacity at Various Differential Pressures (GPM)***
A B C D
w/Lanyard Hose Tank Connection Wrench Effective Length
Basic and Cap Connection M. NPT Flats (Approx.) 10 PSIG 20 PSIG 30 PSIG 40 PSIG 50 PSIG
7647H - ½” F. NPT 27⁄16”
7647HF - ½” SAE Flare 2⅝”
1¾” ACME & 1½”
- 7647DC ¾” 3” 14 20 24 27 50
F. POL
- 7647SA** 31⁄16”
1¾” ACME
- 7647SC* 1¾” 2¼”*
* Large 13⁄4” hex wrench flats.
** 30˚ angle on 1-1/4” ACME hose connection.
*** Multiply flow rate by .94 to determine liquid butane capacity.
F21
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Double Check Filler Valves for Delivery Truck Tanks and
Large Storage Containers 7579S, 6587EC and 3197C
Application
UL
Designed to provide fast filling of bobtails, transports and large bulk ®
storage tanks.
Features
• Double back check provides added system protection.
• Both checks are spring actuated for quick, precise closure when
flow into the valve stops or reverses.
F Materials
Upper Body................................................................................ Brass
Lower Body (7579S and 6587EC).............................................. Brass 6587EC
Lower Body (3197C).................................................................. Brass
Springs........................................................................ Stainless Steel
Washer and Seat Discs............................................ Synthetic Rubber
Cap (6587EC and 3197C).......................................................... Brass
Cap (7579S).............................................................................. Plastic
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
3197C
Ordering Information
A. B. D. Propane Liquid Capacity at Various Differential Pressures (GPM)
C.
Part ACME Tank Effective
Wrench 5 10 25 50 75
Number Hose Connection Length
Hex Flats PSIG PSIG PSIG PSIG PSIG
Connection M. NPT (Approx.)
7579S 1¾” 1½” 2” 211⁄16” 44 62 98 139 170
6587EC* 2¼“ 2” 2⅞” 4⁄”
38 92 130 206 291 356
3197C 3¼” 3” 4” 61⁄2” 148 210 332 470 575
* Swing-away lower back check valve design for higher filling rates.
NOTE: Multiply flow rate by .94 to determine liquid butane capacity.
F22
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Single Check Filler Valves for Storage Tanks with Supplementary
Back Check Valves 3174C, 3194C and 6584C
Application
Designed for use with RegO® Back Check Valves to provide
fast filling of bulk storage tanks. Also may be used as a spare or
replacement part.
These single check filler valves must never be installed directly into
container couplings. They must be used with the appropriate back
check valve to comply with NFPA Pamphlet #58.
Features
• Specifically for use with RegO® Back Check Valves.
3174C
• 6584C stem assembly reduces turbulence during filling and
promotes higher filling rates.
Materials
Upper Body................................................................................ Brass
Lower Body ............................................................................... Brass
Springs........................................................................ Stainless Steel
Washer and Seat Discs............................................ Synthetic Rubber
Cap (3194C, 6584C).................................................................. Brass
Cap (3174C).............................................................................. Plastic
PRODU
10 F
O
G
CT
RE
UL
10
Y
NT
E
Y
AR A
WA R R ®
3194C, 6584C
Ordering Information
Propane Liquid Capacity at Various
Differential Pressures (GPM)
Outlet For Use With
ACME Hose Connection M. Wrench Hex Back Check
Part Number Connection NPT Flats 5 PSIG 10 PSIG 25 PSIG 50 PSIG Valve:
3174C 1¾” 1¼” 1¾” 23 33 52 74 3176
6584C* 2¼” 2” 2⅜” 156 220 348 492 A3186
3194C 3¼” 3” 3½” 147 208 329 465 A3196
F23
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Double Check Vapor Equalizing Valves for ASME and DOT
Containers 7573 Series and 3183AC
Application
Designed to facilitate loading operations by providing equalization of
pressures in the supply and storage containers. The supplementary PRODU
10
O
excess flow valve closes when the flow from the container being filled
CT
RE
S
exceeds a predetermined rate.
10
Y
NT
E
Y
AR A
WA R R
The 7573 Series is designed for use in bulk delivery systems and
motor fuel containers. The 3183AC is designed for use in delivery
trucks and other large containers.
Features UL ®
• Upper back check valve can be easily replaced without evacuating 7573 Series
the container Materials
• Specify RegO® Vapor Equalizing Valves on all your original tank Body ........................................................................................... Brass
purchases to insure quality and dependable performance.
Spring .......................................................................... Stainless Steel
Upper Check Seat Disc .............................................Synthetic Rubber
Seals ........................................................................ Synthetic Rubber
Cap ............................................................................................ Plastic
Ordering Information
Part Number B. Approx. Closing Flow
A. D.
Tank C. at 100 PSIG Inlet
ACME Hose Effective Length
Basic W/ Chain & Cap Connection M. Wrench Hex Flats (Approx.)
Pressure
Connection
NPT (SCFH/Propane)
7573D 7573DC 1¼” ¾” 1¼” 21⁄16” 4,100
- 3183AC 1¾” 1¼” 2” 3⁄ ”
1 16
10,000
F
Single Check Vapor Equalizing Valves for ASME and DOT
Containers with Supplementary Excess Flow Valves
Application
Designed for use with RegO® Excess Flow Valves to facilitate loading
operations by providing equalization of pressures in the supply and
storage containers. Also may be used as a spare or replacement part.
These vapor equalizing valves must never be installed directly into
container couplings. They must be used with the appropriate excess
flow valve to comply with NFPA Pamphlet #58.
Features
• Specifically for use with RegO® Excess Flow Valves.
Materials
PRODU
10
O
Body............................................................................................ Brass 3170
G
CT
RE
UL
NT
E
Y
AR A
Seal............................................................................Synthetic Rubber ® WA R R
Cap..............................................................................................Plastic
Ordering Information
Part Number A. B. C. D.
Inlet Outlet Wrench Hex Effective Length Approximate Closing Flow at 100 PSIG For Use With Excess
Basic With Cap & Chain Connection Connection Flats (Approx.) Inlet Pressure (SCFH/Propane Vapor) Flow Valve:
3170 - 1¼” ¾” 1¼” 19⁄16” 7.600 3272E
- 3180C 1¾” 1¼” 1¾” 111⁄16” 10,000 3282A
F24
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Back Pressure Check Valves
General Information Metal-to-metal seats will allow slight leakage after closure. These
valves will restrict the escape of container contents in the event of
RegO® Back Pressure Check Valves are designed to allow flow in accidental breakage of the piping or fittings.
one direction only. The check, normally held in the closed position by
a spring, precludes the possibility of flow out of the container. When
flow starts into the container, the pressure overcomes the force of
the spring to open the check. When the flow stops or reverses, the
check closes.
When used with the appropriate single check filler valve, the
combination forms a double check filler valve suitable for use in filling
of bulk storage tanks.
Features
• Generous flow channels for low pressure drop.
• Soft seat valves have synthetic rubber seat disc for positive seals.
3146 Series, 3176 Series, A3186, A3196
Materials
Body (3146, 3146S, 3176) ...................................................... Brass
Body (all others) ............................................ Cadmium Plated Steel
Disc (3146, 3146S, 3176) . ...................................................... Brass
F
Disc (all others) ............................................. Cadmium Plated Steel
Stem (3146, 3146S, 3176) ...................................................... Brass
Stem (A3146, A3196, A3276BC) ............................... Stainless Steel
Stem (A3176, A3186) .................................... Cadmium Plated Steel
Spring ........................................................................ Stainless Steel
Seat Disc (3146S, A3276BC) ................................ Synthetic Rubber
UL
®
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Features
PRODU
10
G O
CT
• Swing-away check design offers faster flow rates.
RE
S
10
Y
E NT
Y
AR A
• Heavy-duty construction for long service life. WA R R
6586D
Ordering Information
Part Number Propane Liquid Capacity at Various Differential Pressures (GPM)
A. B. C. D.
Inlet Connection Outlet Connection Wrench Effective Length
Brass Steel F. NPT M. NPT Hex Flats (Approx.) 5 PSIG 10 PSIG 25 PSIG 50 PSIG
6586D A6586D 2” 2” 2⅞” 27⁄16” 190 270 420 600
NOTE: Multiply flow rate by .94 to determine liquid butane capacity.
F
Back Pressure Check Valves for Flanged Installation
A3400L4 and A3400L6
Application
Designed to provide high flow capacity and allow more efficient tank
filling than conventional designs. The unobstructed throat area
reduces flow turbulence through the valve, thereby reducing pressure
drop. Large flow channels and spacious side ports assure ample
capacity for the most demanding high capacity filling operations.
Features
• Speeds up filling operations in bulk tanks.
• All steel and stainless steel construction assures long service life.
Materials A3400L6
10
O
Stem ............................................................................ Stainless Steel
G
CT
RE
UL
S
E
Y
AR A
WA R R
Guide ............................................................................ Stainless Steel
Roll Pin ........................................................................ Stainless Steel
Ordering Information
A. B. D. Propane Liquid Capacity at Various Differential Pressures (GPM)
Flange Connection Wrench Hex C. Threaded End
Part Number M. NPT Flats Overall Length To Port 5 PSIG 10 PSIG 25 PSIG 50 PSIG
A3400L4 2” 5¼” 15⁄16” 223 316 500 707
Slotted
A3400L6 3” 59⁄32” 19⁄16” 424 600 949 1342
NOTE: For installation in flange tank connections with internal threads, see the “Flanged Installation in Container” section under “Excess Flow Valves.”
Multiply flow rate by .94 to determine liquid butane capacity and by .90 for liquid anhydrous ammonia capacity.
F26
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Warning Notice
The following warning information, Part Number 903-500, is included These adhesive warning labels are intended for application as close
with each shipment of Excess Flow, Check, Filler and Vapor as possible to the Chek-Lok® once the Chek-Lok® is installed.
Equalizing Valves to the first purchaser of the product from the
factory. The basic information contained on the label is intended for the
benefit of the user of the Chek-Lok® and is not intended to be an “all-
This information is intended to be forwarded throughout the product inclusive” product warning.
distribution chain. Additional copies are available from Engineered
Controls International, Inc. and Authorized Product Distributors. This label is printed on a heavy duty material with pressure sensitive
adhesive backing. The ultra-violet ink stands up well when exposed
to the environment.
DANGER WARNING
LP-GAS IS EXTREMELY
F
FLAMMABLE AND EXPLOSIVE
AVOID SERIOUS INJURY AND PROPERTY DAMAGE. IF YOU SEE, SMELL,
OR HEAR ESCAPING GAS... EVACUATE AREA IMMEDIATELY! CALL YOUR
LOCAL FIRE DEPARTMENT! DO NOT ATTEMPT TO REPAIR. DO NOT
STORE IN BUILDING OR ENCLOSED AREA. DO NOT USE ON HOT AIR
BALLOONS OR AIRCRAFT.
CAUTION!
Use this CHECK-LOK ® connection only for liquid evacuation before moving
tank in accordance with NFPA Pamphlet 58, which is the law in many states.
This publication is available from NFPA, Batterymarch Park, Quincy, MA
02269. Read and follow ECII ® product instruction number 7572FA-301.
DO NOT REMOVE, DEFACE OR OBLITERATE THIS LABEL.
DO NOT FILL THIS CONTAINER UNLESS THIS LABEL IS READABLE.
ADDITIONAL SAFETY INFORMATION IS AVAILABLE FROM
F27
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cross Reference by Part Number
12472................................................................................................ F11 A3292C............................................................................................... F11
A1519A2..............................................................................................F10 A3400L4..............................................................................................F26
1519A2..............................................................................................F10 A3400L6..............................................................................................F26
1519A3..............................................................................................F10 A3500L4..............................................................................................F14
A1519A4..............................................................................................F10 A3500N4.............................................................................................F14
1519A4..............................................................................................F10 A3500P4..............................................................................................F14
A1519A6..............................................................................................F10 A3500R6.............................................................................................F14
A1519B4..............................................................................................F10 A3500T6..............................................................................................F14
1519B4..............................................................................................F10 A3500V6..............................................................................................F14
1519C2...............................................................................................F9 6579..................................................................................................F20
1519C4...............................................................................................F9 6584C...............................................................................................F23
A2137..................................................................................................F13 A6586D...............................................................................................F26
A2137A................................................................................................F13 6586D...............................................................................................F26
2139..................................................................................................F13 6587EC.............................................................................................F22
2139A................................................................................................F13 A7537L4..............................................................................................F12
A2697-20R..........................................................................................F20 A7537L4F............................................................................................F12
A2697-20R..........................................................................................F23 A7537N4.............................................................................................F12
2723C...............................................................................................F15 A7537N4F ..........................................................................................F12
A2797-20R..........................................................................................F20 A7537P4 ............................................................................................F12
A2797-20R..........................................................................................F23 A7537P4F ..........................................................................................F12
2884D...............................................................................................F16 A7539R6 ............................................................................................F12
3146..................................................................................................F25 A7539R6F...........................................................................................F12
A3146..................................................................................................F25 A7539T6..............................................................................................F12
3146S................................................................................................F25 A7539T6F ..........................................................................................F12
3170..................................................................................................F24 A7539V6 ............................................................................................F12
3174C...............................................................................................F23 A7539V6F ..........................................................................................F12
3176..................................................................................................F25 7572-400...........................................................................................F27
A3176..................................................................................................F25 7572C-14A........................................................................................F19
3180C...............................................................................................F24 7572C-15A........................................................................................F19
3183AC.............................................................................................F24 7573D...............................................................................................F24
A3184-8R............................................................................................F20 7573DC.............................................................................................F24
A3186..................................................................................................F25 7574.................................................................................................. F11
A3194-8R............................................................................................F20 7574L................................................................................................ F11
3194C...............................................................................................F23 7579..................................................................................................F20
A3196..................................................................................................F25 7579P................................................................................................F20
F 3197C...............................................................................................F22 7579S................................................................................................F22
3199W...............................................................................................F16 7590U...............................................................................................F18
3272E................................................................................................ F11 7590U-10..........................................................................................F19
3272F................................................................................................ F11 7590U-20..........................................................................................F18
A3272G............................................................................................... F11 7591U...............................................................................................F18
3272G............................................................................................... F11 7647DC.............................................................................................F21
A3276BC.............................................................................................F25 7647H...............................................................................................F21
3282A................................................................................................ F11 7647HF.............................................................................................F21
3282B................................................................................................ F11 7647SA.............................................................................................F21
A3282C............................................................................................... F11 7647SC.............................................................................................F21
3282C............................................................................................... F11 A8013D...............................................................................................F15
A3292A................................................................................................ F11 A8013DA.............................................................................................F15
3292A................................................................................................ F11 A8013DB.............................................................................................F15
A3292B................................................................................................ F11 A8523..................................................................................................F12
3292B................................................................................................ F11 A8525..................................................................................................F12
F28
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section G
G G
G1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
This warranty does not extend to any product or part that is not The Limited Warranty stated above is a factory warranty to the first
installed and used continuously after installation in accordance with purchasers of ECII products. Since most users have purchased
ECII’s printed instructions, all applicable state and local regulations, these products from ECII distributors, the user must within thirty (30)
and all applicable national standards, such as those promulgated by days after the user’s discovery of what user believes is a defect,
NFPA, DOT and ANSI. This warranty does not extend to any product notify in writing and return the product to the distributor from whom
or part that has been damaged by accident, misuse, abuse, failure to he purchased the product/part. The distributor may or may not at
maintain, or neglect, nor does it extend to any product or part which the distributor’s option choose to submit the product/parts to ECII,
has been modified, altered, disassembled, or repaired in the field. pursuant to this Limited Warranty. Failure by buyer to give such
This warranty does not cover any cosmetic issues, such as scratches, written notice within thirty (30) days shall be deemed an absolute and
dents, marring, fading of colors or discoloration. unconditional waiver of buyer’s claim for such defects. Acceptance
of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
G2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
G
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Cross Reference by Part Number............................................... G23
Flomatic® Service Guide............................................................ G19
Flomatic® Valves......................................................................... G17
General Information-Flomatic®................................................... G16
General Information-Manual Valves.............................................. G6
Manual Valves—1¼” Threaded..................................................... G8
Manual Valves—3” Threaded...................................................... G14
Manual Valves—2” Threaded...................................................... G15
Manual Valves—3” Flanged........................................................ G10
Manual Valves—4” Flanged.........................................................G11
Pump System Troubleshooting................................................... G23
Remote Cable Controls............................................................... G13
Remote Thermal Release........................................................... G13
Safety Warning.............................................................................. G4
G3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Warnings
Purpose
In its continuing quest for safety, Engineered Controls International, Inc. publishes a series of bulletins
explaining the hazards associated with the use, misuse, and aging of LP-Gas valves and regulators. It is hoped
that these factual bulletins will make clear to LP-Gas dealer managers and service personnel, that the utmost
care and attention must be used in the installation, inspection, and maintenance of these products, or problems
could occur which would result in injuries and property damage.
The National Fire Protection Association Pamphlet #58, “Storage and Handling of Liquified Petroleum Gases’’
states in section 1-6 that “In the interest of safety, all persons employed in handling LP-Gases shall be trained
in proper handling and operating procedures’’. These “ECII® Safety Warnings’’ may be useful in training new
employees and reminding older employees of hazards that can occur.
It is recommended that all employees be furnished with a copy of NPGA Safety Pamphlet 306-88 “LPGas
Regulator and Valve Inspection and Maintenance, 111-81 Limitations of Excess Flow Check Valves for LP-Gas,
and 113-78 Safety Considerations in Bobtail Deliveries.’’
Nature of Warnings
It is recognized that warnings should be as brief as possible, but the
factors involved in internal valve and excess flow valve failures to
perform are not simple. They need to be fully understood. If there is
a simple
Make sure that the internal valve’s excess flow feature really
closes when the flow exceeds rated closing flow, and that the
valve will shut-off.
G4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pressure Differential Internal Valves (Flomatics)
Pressure differential valves (Flomatics) open by pump pressure and
close when the pump stops.
These valves must never be locked open by means of wires, chains,
pegs or other devices.
Testing
General Warning
All ECII® Products are mechanical devices that will eventually
become inoperative due to wear, contaminants, corrosion and aging
of components made of materials such as metal and rubber. G
The environment and conditions of use will determine the safe service
life of these products. Periodic testing at least once a year when tank
pressures are low and maintenance, as required, are essential.
G5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Manual Internal Valves
A3200 Series
General Information
These valves must remain in the closed position except during
product transfer. A line break downstream of the pump may fail to
Manual Internal Valves are designed for a variety of uses in LP-Gas
actuate the excess flow valve as the pump may limit flow. If break
and anhydrous ammonia service. In addition, accessories allow most
occurs in the system, or the excess flow closes, immediately shut
of them to be actuated manually, by cable or with air.
down the system.
Installation, usage and maintenance of this product must be
Inspection and maintenance on a periodic basis is essential.
in compliance with all Engineered Controls International, Inc.
Installation and maintenance must be performed only by qualified
instructions, as well as requirements and provisions of NFPA # 58,
personnel.
DOT, ANSI, and all applicable federal, state, provincial, and local
Be sure all instructions are read and understood before installation
standards, codes, regulations and laws.
and operation of these valves.
How The Valves Work 5. Always keep valve closed except during product transfer.
Refer to the drawings. View “A’’ shows the valve held closed without 6. Completely open all valves during pumping. Partially closed or
leakage by tank pressure and the valve’s closing spring. Actuation throttle type valves may prevent excess flow valve from closing when
of the operating handle alone does not open the valve, it only allows required, even in a properly designed piping system.
pressure to equalize between the inlet and outlet of the valve by rapid
bleeding of the product downstream. This equalized pressure then 7. All personnel must be aware of remote closure locations and their
allows the valve to open via the internal spring. operation in case of emergency. They must also be aware of the
equalizing opening through which bleeding can occur after the excess
The valve opens by moving the handle to mid-point, see view “B’’. flow valve closes. If this bleed is not stopped by closing a downstream
This position allows the actuator to put the equalizing portion of valve, a hazard may occur.
the valve stem in the pilot opening, allowing more product to bleed
downstream than if the handle was fully open. 8. Never, under any circumstances, permanently wire open the
operating handle of the internal valve.
In a few seconds, the tank and downstream pressure will be nearly
equal. The excess flow spring will push the main poppet to the open
position, see view “C’’, the handle should then be moved to the fully
Cable Control System
open position.
The cable control system employed must meet the requirements
and be in accordance with the provisions of NFPA #58, DOT,
If at first, the handle is quickly moved to the fully opened position, the
pilot valve allows a small amount of bleed downstream, but much less ANSI, and all applicable federal, state, provincial and local
than during rapid bleed (view “B’’). This results in a longer pressure codes.
G equalizing time before the main valve can open.
Troubleshooting
NOTE: The main poppet will not open until outlet pressure
approximates tank pressure! 1. Internal Valve Will Not Open. Causes may be excess leakage
downstream, pump engaged too quickly, excessive wear of valve, or
Once the main poppet is open, flow greater than the excess flow ice freezing of poppet.
rating, or a sufficient surge in flow, forces the main poppet closed When there is excessive volume downstream, a greater amount of
against the excess flow spring, as seen in view “D’’. The pilot valve in time is required to equalize tank and downstream pressure.
this position is open and allows a small amount of bleed downstream, To determine if the pilot seat is opening, install a pressure gauge
but much less than during rapid bleed (view “B’’). downstream of valve outlet, open any hand valves between valve and
pressure gauge, and open valve. Pilot seat is not opening if pressure
When the operating handle is moved to the closed position, the valve does not build up to tank pressure. Perform this test with pump off. A
closes and a leak-tight seal is re-established as seen in view “A”. broken internal part may cause pilot seat not to open.
If operating handle rotates past the full open position, there is internal
NOTE: To provide excess flow protection, the flow rating of the pump, malfunctioning, and the valve must be disassembled and repaired.
piping, valves, fittings, and hose on the inlet and outlet sides of the
2. Premature Valve Closure.
valve must be greater than the flow rating of the valve. Any restrictions
that reduce the flow to less than the excess flow valve rating will result First, check to see that operating lever is properly connected and fully
in the excess flow valve not operating when required. opens valve. Premature closure may also be a result of engaging
pump too quickly, sudden line surges, an underrated excess flow
Valve Operation and Precautions spring or an obstructed inlet port.
3. Valve Will Not Close.
1. Valve must be opened before starting pump, and before opening Usually a result of faulty or sticking actuator. First, check the actuator
valve on pump outlet. to see that it works freely by disconnecting it from valve handle and
cycling it several times. Also, operate valve handle manually. If it
2. Leave pumping system “wet’’ to avoid drying of seals and to reduce sticks in the open position, replace the packing and bushings. This
time involved in opening valve. Drain piping only when required by should free the operating mechanism providing the valve has no
codes or safe operating practices. internal damage.
3. When piping is dry or at lower pressure than the tank, open valve
4. Low Flow Capacity
half-way for a few seconds to allow line pressure to equalize before
Downstream piping may be too small and/or long, screen or strainer
fully opening the valve handle. The main poppet may not open
immediately if the handle is placed in the open position too quickly. may be plugged, possible restriction downstream, or a bypass valve
stuck in the open position are causes of low flow. Also, the bypass
4. Flow surges may close the built-in excess flow valve and should valve may be set too low and prematurely opening. Check for high
be avoided. If the valve slams shut, immediately stop the pump, close differential pressure across the bypass valve. If bypass valve is open,
the nearest downstream valve, and move handle to midpoint position the differential across the valve should not exceed 5 to 6 psig.
to equalize pressure until valve reopens with a click, then restart
pump and open downstream valve slowly.
G6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Maintenance
Potential problems may be eliminated with preventive internal valve 3. Inspect, clean and oil all operating controls. Check controls to see
maintenance. Perform the following steps once a month: that they open fully, but do not overtravel the valve operating lever.
See that they work freely to close the valve. Worn parts should be
1. Check to see that the operating lever moves freely and smoothly. replaced.
There should be no leakage around the lower stem or seal housing.
Leakage requires replacement of the seal housing packing. A sticking 4. Remove valve if the tank is to be steam cleaned. Heat may
lever indicates trapped foreign material or mechanism wear. damage the valve’s seals.
2. Check both seat discs for tight closure. Close valve and exhaust 5. Valve is not designed for water service. After tank is hydrostatically
downstream pressure. Be sure piping is warmed to an ambient tested, immediately remove all water and allow tank to thoroughly dry
temperature. Close the first downstream valve and note pressure out before installing valve.
buildup between the closed valves with a pressure gauge. If leakage
occurs, replace both seat discs.
G7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
1¼” Threaded Internal Valve for Small Capacity Pumping Systems
and Bobtail Vapor Equalization A3209D & A3209DT Series
Application We have redesigned our A3209R Series internal valves; the new part
number will be A3209D Series the list price will not change.
Designed primarily for use with LP-Gas and anhydrous ammonia as a
main valve on small capacity pumping systems, NH3 nurse tanks and Your orders for the A3209R050 and A3209R080 will be changed to
in-line installations. It may also be installed in the vapor equalizing the new part number for orders scheduled as follows:
opening on bobtail delivery trucks. Installation is quick and easy, and
it fits in both full and half couplings, as well as, in-line applications. A3209R050 to A3209D050: your orders scheduled for delivery after
The valve may be actuated manually by hand or cable.
UL
®
June 2007.
• Return spring forces the valve to the closed position when the
lever is released.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Inlet Outlet Closing Flow LP-Gas Vapor Capacity** (SCFH/Propane) Accessories
Part
Connection Connection
Number LP-Gas NH3 25 PSIG 100 PSIG Thermal Latch Pneumatic Actuators
M. NPT F. NPT
A3209D050 1¼” 1¼” 50 45 13,300 22,900
A3209D080 1¼” 1¼” 80 72 15,700 26,700 A3209PA
A3209TL
A3209DT050 1¼” 1¼” 50 45 13,300 22,900 A3209PAF
G8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
3” Flanged Internal Valve for Bobtail Delivery Trucks, Transports,
and Large Stationary Storage Tanks A3217 Series
Application
Designed primarily for LP-Gas and anhydrous ammonia filling and/ UL
®
Features
Provides More Efficient Operation
• Flow passages designed to allow substantially higher without
cavitation or loss of efficiency--saving time and money.
• Strainer sits on the top flange of the valve’s seat insert, making
removal of the valve easier. It completely covers the top of the G
valve to help keep out sediment and foreign material.
• Heavy duty rod wiper helps minimize dirt and foreign material from
A3217FR & FL Series
entering operating shaft and hampering operation.
Single Flange
Durable Construction A3217DFR & DFL Series
• Cadmium plating helps resist corrosion during storage and use. Double Flange
• Main disc retaining screws are installed from the top down to help
minimize the chance of loose screws entering and damaging the
pump.
PRODU
10
O
• All ferrous materials with a temperature range of -40° F. to +130°
G
CT
E
Y
AR A
• Built-in excess flow valve. WA R R
Ordering Information
Part Closing Flow
Number GPM Accessories
Operating
Single Flange Double Flange Lever Inlet Outlet Pneumatic
Body Body Position Connection Connection LP-Gas NH3 Actuator
A3217FR160 A3217DFR160 Right Side A3217FPA
160 145
A3217FL160 A3217DFL160 Left Side A3217FLPA
A3217FR210 A3217DFR210 Right Side 3” 300# A3217FPA
3” 300# 210 190
A3217FL210 A3217DFL210 Left Side ANSI RF A3217FLPA
ANSI RF
A3217FR260 A3217DFR260 Right Side Modified A3217FPA
Flange 260 236
A3217FL260 A3217DFL260 Left Side Flange** A3217FLPA
A3217FR410 A3217DFR410 Right Side A3217FPA
410 372
A3217FL410 A3217DFL410 Left Side A3217FLPA
* Valve supplied with 16 nuts and 8 studs for mounting. **Modified bore = 4 ⁄8” diameter with 5 ⁄4” diameter raised face.
5 3
G9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
3” Flanged Internal Valves for Bobtail Delivery Trucks,
Transports, and Large Stationary Storage Tanks
A3217FPA and A3217FLPA Pneumatic Actuators
These Pneumatic Actuators are designed specifically for use with the
A3217 Series 3” Internal Valves. The diaphragm design provides a
UL
®
Features
• Diaphragm type–no seals to leak.
Materials
Body and Valve Cage.......................... Cadmium Plated Ductile Iron
Seat....................................................... Nickel Chrome Plated Steel
Strainer...................................................................... Stainless Steel
Shaft.......................................................................... Stainless Steel
Pilot Valve Stem........................................................ Stainless Steel
Springs...................................................................... Stainless Steel
Actuator Cam............................................................ Stainless Steel
Lever................................................ Cadmium Plated Carbon Steel
G Seat Disc................................................. Resilient Synthetic Rubber
G10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
4” Flanged Internal Valve for Transports and Large Stationary
Storage Tanks A3219 Series
Application
Designed primarily for LP-Gas and anhydrous ammonia service on UL ®
Features
Provides More Efficient Operation
• Flow passages designed to allow higher pumping rates without
cavitation or loss of efficiency–-saves time and money.
• Strainer completely covers the top of the valve to help keep out
sediment and foreign material.
• Stainer seats at the top flange of the valve’s seat insert, making
removal of the valve easier.
Durable Construction
• Cadmium plating helps resist corrosion during storage and use.
• Taper pin lock secures the operating shaft to provide for more
precise,trouble-free actuation.
Materials
• Built-in excess flow valve and thermal protection.
PLOT GENERATED 8/08/2002 AT 15:15
10
O
Pilot Valve Plug.......................................................... Stainless Steel
G
CT
RE
Y
NT
E
Y
A
AR
WA R R Lever Assembly................................ Cadmium Plated Carbon Steel
Seat Disc................................................. Resilient Synthetic Rubber
Ordering Information
Closing Flow GPM Accessories
Part Number* Inlet Connection Outlet Connection Pneumatic Remote Thermal
LP-Gas NH3
Actuator Release
A3219FA400L 4” 300# ANSI RF 4” 300# ANSI RF 400 360
A3219FPA A3219RT (2)
A3219FA600L Modified Flange** Flange 600 540
* Valve supplied with 16 nuts and 8 studs for moutning.
** Modified bore = 5 7/8” diameter with 7” diameter raised face.
G11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
4” Flanged Internal Valves for Transports and Large Stationary
Storage Tanks
Application
UL
A3219FPA Pneumatic Actuator
®
Features
• Diaphragm type–no seals to leak.
G12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Remote Thermal Release for DOT MC331 Pressure Vessel
A3219RT
Application
Designed especially for use with Internal Valves installed in DOT
UL
®
PRODU
10
O
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
G
Remote Cable Controls for Internal Valves 3200C and 3200L
Application
UL
The 3200C Remote Cable Kit is designed especially for use with the ®
10
O
G
CT
Y
NT
E
Y
AR A
• Provides necessary remote closure system for bobtails required WA R R
by DOT regulation on MC330/MC331 tanks and NFPA #58.
Ordering Information
Part Materials
Number Description Contents
100 Foot Cable, 6 Cable Clamps, Quick Body...................................................................... Galvanized Steel
3200C Remote Cable Kit
Link, Sign, Fuse Link, Steel Nut and Bolt
Springs...................................................................... Stainless Steel
3200L Operating Lever Lever Assembly
G13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Threaded Internal Valves For Bobtail Delivery Trucks, Transports
and Stationary Storage Tanks A3213R Series
Application Seat disc fully retained and field replaceable.
Excess flow spring is independent from
Designed primarily for use with LP-Gas and anhydrous ammonia
return spring operation
for liquid withdrawal; vapor transfer or vapor equalization of bobtail
delivery trucks, transports, stationary storage tanks, and in-line
installations. The valve may be operated manually by cable or
pneumatically.
Features
• May be installed in full and half couplings.
• All critical operating components are located in the valve body inside
the container coupling for maximum protection against physical
damage.
A3213R
• Built in excess flow valve.
Cam attached with Allen head fastener which is
• Return spring returns the valve to the closed position when the accessed from the ¼” pipe plug on side of the body
handle is released.
• Specify RegO® Internal Valves on your next new tank body or when
your tank is rebuilt.
A3213RT
PRODU
10
O
Cam attached with Allen head fastener
G
CT
RE
E
Y
AR A
WA R R
Ordering Information
Closing Closing
LP-Gas Vapor
Flow Half Flow Full
Capacity (SCFH/ Accessories
Inlet Outlet Coupling Coupling
Part Propane)
Connection Connections (GPM) (GPM) A B C D E F
Number
M-NPT F-NPT 25 100
Pneumatic Thermal
LPG NH3 LPG NH3 PSIG PSIG
Actuator Latch
Inlet Inlet
A3213R150 150 135 125 113 - -
A3213R200 200 180 160 144 44,100 75,100
11⁄2” 57⁄8” 41⁄4” - - 71⁄8”
A3213R300 300 270 250 225 57,900 90,500
A3213R400 400 360 325 293 71,400 121,300
3” 3” A3213PA A3213TL
A3213RT150 150 135 125 113 - -
A3213RT200 200 180 160 144 44,100 75,100
11⁄2” 715⁄16” 41⁄4” 37⁄8” 41⁄2” 31⁄2”
A3213RT300 300 270 250 225 57,900 90,500
A3213RT400 400 360 325 293 71,400 121,300
G14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Threaded Internal Valves For Bobtail Delivery Trucks, Transports
and Stationary Storage Tanks A3212 Series
Application
Designed primarily for use with LP-Gas and anhydrous ammonia PRODU
10
O
for liquid withdrawal; vapor transfer or vapor equalization of bobtail
CT
RE
S
delivery trucks, transports, stationary storage tanks, and in-line
10
Y
installations. The valve may be operated manually by cable or
NT
E
Y
AR A
pneumatically. WA R R
Features
• May be installed in full and half couplings.
• Nylon bearing supported operating shaft provides smooth, easy
operation.
• Simple operating lever facilitates easy adaptation of all cable
controls. UL
• Midway stem position allows for quicker pressure equalization.
®
Materials
A3212R Series
Body............................................................................... Ductile Iron
Operating Lever............................................. Cadmium Plated Steel
Stem.......................................................................... Stainless Steel
Springs...................................................................... Stainless Steel
G
Seat Disc................................................ Resilient Synthetic Rubber
Shaft Bearing........................................................................... Nylon
A3212RT Series
Ordering Information
Closing Flow (GPM) Closing Flow (GPM)
Inlet Outlet Accessories
Part Half Coupling Full Coupling
Connection Connection
Number
M. NPT F. NPT LP-Gas NH3 LP-Gas NH3 Thermal Latch Pneumatic Actuator
A3212R105
105 95 65 59
A3212RT105
A3212R175
2” 2” 175 158 100 90 A3213TL A3213PA
A3212RT175
A3212R250
250 225 130 117
A3212RT250
G15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Flomatic® Internal Valve Operation
General Information
RegO® piston type Flomatic® Internal Valves are normally closed
and use pressure differential to provide completely automatic service.
Mounted directly between the tank body and pump, the Flomatic®
uses the pressure differential developed by the pump to open the
valve and it closes automatically when the differential no longer
exists.
This means the RegO® Flomatic® opens when the pump is on and
closes when the pump is shut off – fully automatic.
G16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Flomatic® Internal Valves for Bobtail Delivery Trucks, Transports
and Large Stationary Storage Tanks A7883FK and A7884FK
Application
Designed primarily for LP-Gas and anhydrous ammonia liquid UL
®
Features
Fully Automatic
• Operates on pressure differential from the pump to open and
close.
• Automatically closes should downstream line rupture causing loss
of pump differential pressure required to keep the valve open.
• Problems of improperly sized excess flow valves slugging shut
during liquid transfer are eliminated.
Faster Unloading
• Straight through flow design provides minimum pressure drop and
large flow capacity to the pump, resulting in higher flow rates and
greater pump efficiency.
• Unloading is quicker and turn-around faster to provide more
A7883FK
profitable operation.
Greater Protection
• Fully automatic operation virtually eliminates operator errors such
as forgetting to close the valve after product transfer.
• Fully internal design reduces possibility of spillage that may result
from a collision.
• Built-in visual indicator lets the operator know whether the valve
seat is in the open or closed position.
• Never a cable problem. These valves must NEVER be held open
by wire or any other means as the valve will not close as expected
when the pump is shut-off.
G
Less Maintenance
• Easily replaceable, high efficiency external filter removes
contaminant’s as small as 20 microns. Filter virtually eliminates
orifice clogging, excessive internal filter maintenance and service
downtime.
• No need to check or replace air lines, cables or cable
connections.
Economical
• Completely equipped with mounting bolts, flange gaskets, quick
acting valve and filter - all in one purchase price.
• No need to purchase additional mounting equipment or actuating
accessories.
• Specify RegO® Internal Valves on your next new tank body or
when your tank is rebuilt.
Materials
Body................................................................................ Cast Steel PRODU
10
Valve Stem............................................................... Stainless Steel O
G
CT
Piston............................................................................... Aluminum
Cylinder.................................................................... Stainless Steel
10
Y
NT
AR A
Seats...................................................... Resilient Synthetic Rubber WA R R
Ordering Information
Accessories (included with Flomatic®)
Part Inlet Connection Outlet Connection Strainer Base Overall Height Height from Indicator
Number ANSI Flange ANSI Flange Width Width (Approx.) to Base Filter 3-Way Valve
A7883FK 3”-300#** 3”-300# 4¾” 8¼” 10⅞” 413⁄16”
A7884-201 A7853A
A7884FK 4”-300#*** 4”-300# 5¾” 10” 11¼” 415⁄16”
* Supplied with A7853A 3-way valve, A7884-201 filter, studs, nuts and gaskets.
** With 413⁄16” diameter bore.
*** With 513⁄16” diameter bore.
G17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
¼” Three-Way Quick-Acting Valve
A7853A
UL
®
Tank Flange
Flomatic filter
Tank Gasket Flange
(To Pump Station
¼” Vent Line
¼“ High Tee
G Pressure
Hose
Pump
Control Cable
(with Fuse link
and return spring)
A7853PA
A7853A Three Way Valve
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Accessories
Overall Height from
(included with Flomatic®)
Inlet Connection ANSI Outlet Connection Strainer Base Height Indicator to
Part Number Flange ANSI Flange Width Width (Approx.) Base Filter 3-Way Valve
13
A7883FK 3”-300#** 3”-300# 4¾” 8¼” 10⅞” 4 16”
15 A7884-201 A7853A/A7853PA
A7884FK 4”-300#*** 4”-300# 5¾” 10” 11¼” 4 16”
* Supplied with A7853A 3-way valve, A7884-201 filter, studs, nuts and gaskets.
** With 413⁄16” diameter bore.
*** With 513⁄16” diameter bore.
G18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
On The Job Service Guide for the Flomatic® Valve
Introduction
Efficient, profitable transport and delivery truck operations depend on
keeping the equipment working safely and efficiently under changing
conditions. It is important to know how to eliminate expensive delays
by handling unloading problems as they arise.
The transport or delivery truck tank pressure may be higher than the
storage tank pressure when you are ready to unload (Figure 4). This
G
is because your rig may have been freshly loaded at the terminal or
bulk plant without a vapor equalizing line and hasn’t had time to get
back to normal. Also, the storage tank pressure tends to drop when a
lot of LPGas is being used.
But, let’s say you do these things, start the pump and the liquid
doesn’t move. Now, how do you find out what is wrong?
G19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
On The Job Service Guide for the Flomatic® Valve
Step 1 6. Ice in the system may prevent proper operation, as will a
Immediately shut down the pump so you don’t cause possible collapsed or kinked sensing line or a clogged sensing line filter.
damage to the seals or valves. Next: If you found the trouble within STEP 1, just start the pump and
continue unloading, If not, proceed accordingly.
1. Check all manual valves in the system to make certain they
are open or closed as required for proper operation. a. New Models with T-handle: To adjust to the proper
position, push in the end of the valve stem and tighten the
2. Check the liquid level in the transport or delivery tank. If the needle valve clockwise until it seats. Then, turn
level is low, it may slow the transfer rate. counterclockwise 1½ turns.
3. Check to assure that the pump rotates normally when power b. Old Models with Plug: To adjust to the proper position,
is applied. If not, inspect and repair as needed the power takeoff, carefully remove the plug. A small amount of liquid
universal joints, drive shaft and clutch, etc. LP-Gas may be discharged when plug is loosened. Insert
a small screwdriver and tighten the needle valve
4. Make sure the lever is straight out on the ¼” operating valve clockwise until it seats. Then turn it counterclockwise
in the line between the pump discharge line and the Flomatic® 1 turn only. CAUTION: Do not open needle valve
valve (Figure 5). If is isn’t, the Flomatic® valve will remain closed. more than 1 turn as it might blow out!
5. Make certain the priming valve on the side of the Flomatic® c. Threaded Models with Internal Priming Channel. The
valve is open (Figure 6). internal priming channel normally self-actuates. To be sure
the system is primed, remove the plastic hood and push
the travel indicator up about 1⁄8” and hold for at least 15 seconds.
G20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
On The Job Service Guide for the Flomatic® Valve
G21
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
On The Job Service Guide for the Flomatic® Valve
USE EXTREME CARE AT ALL TIMES WHEN WORKING AROUND YOUR VEHICLE!
Watch out for drive shafts and moving parts. It is common knowledge that serious injury
can result if any part of one’s body or clothing is caught in moving machinery.
If you manually open the Flomatic® valve, you are responsible for safely unloading the
liquid and closing the valve when you’re through. If this procedure is being followed,
under no circumstances must the valve be left unattended. The valve must never be
permanently held in the open position.
If you are not able to cause the Flomatic® valve indicating shaft to
move to the open position after completing the preceding steps, a
complete detailed diagnosis will have to be made.
In any event, if you haven’t solved the problem and the unit still
doesn’t operate properly, immediately take it out of service, have a
complete analysis made and repair as needed.
G
Be sure to obtain and keep available for quick referral the
Manufacturers’ Operation and Service Manuals for the valves,
pump, meter and all operating equipment in the system.
G22
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pumping System Troubleshooting Guide
Introduction
Most LP-Gas and anhydrous ammonia systems use pumps to This would allow pressure gauges to be put in easily without
move liquid from one location to another. Unloading transport trailer removing the LP-Gas or anhydrous ammonia from the system
tanks into plant storage, loading delivery trucks, filling bulk tanks, at the time trouble occurs, saving a lot of time and unnecessary
engine fuel tanks, portable cylinders, etc. and pressurizing LP-Gas expense. Pressure gauges should be installed temporarily at the
vaporizers are only a few of many such applications. A well-designed time the system is first installed, and pressure readings recorded
and properly installed pumping system will perform well for some while the system is working properly. Then, in many cases,
time, but eventually problems occur requiring attention. merely comparing pressures with original readings may tell what
the trouble is.
Finding out what is wrong, and getting it working again, can be a
timeconsuming and confusing experience, unless one knows clearly NOTE: The figure below shows where pressure gauges should
how to proceed. be installed. Pressure gauge readings from the original tests
should be recorded for each gauge.
The purpose for this technical guide is to provide simple, step-by-step
guidelines for correcting LP-Gas and anhydrous ammonia pumping It is recommended that the pressure gauges not be used
difficulties. continuously, because vibrations and the ravages of weather
cause their damage or ruin. Therefore, as soon as the initial
The procedure includes a preliminary checklist to help find out if tests are complete, it is best to (1) close the shutoff valves, (2)
the difficulty can be corrected without taking anything apart. Then, remove the gauges, (3) plug the valves and (4) keep the gauges
it shows how to zero in on more serious problems by using a few in a safe place, ready for troubleshooting when really needed.
pressure gauges to pinpoint the cause. It is easier to diagnose a problem if the original test results are
available, but don’t panic if they aren’t. You can still solve the
It is recommended that the pumping system be equipped for easy problem without this information, but it requires more time and
pressure gauge installation before trouble occurs. Small manual effort.
shutoff valves can be installed at proper locations, with plugs inserted
in the outlets.
G23
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pumping System Troubleshooting Guide
Be sure to obtain and keep available for quick referral the the other hand, if you have done all of this and still haven’t worked
Manufacturer’s Operation and Service Manuals for the valves, pump, out your problem. feel free to call your local distributor or Engineered
meter and all operating equipment in the system. Controls International, Inc.
To avoid delays, maintain a complete stock of recommended spare direct. We will do our best to help. Perhaps, between us, we will be
parts on hand for quick repairs. able to solve your problem and add something new to the procedure
which could help everyone in the future.
Follow the steps as shown. Don’t assume the answer is known
beforehand, or skip any applicable steps. Rather, be thorough and
methodical and in most instances, you will solve the problem. On
G24
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cross Reference by Part Number
A3213RT200....................................................................................... G14
3200C............................................................................................... G13 A3213RT300....................................................................................... G14
3200L................................................................................................ G13 A3213RT400....................................................................................... G14
A3209D050........................................................................................... G8 A3217FAL160........................................................................................ G9
A3209D080........................................................................................... G8 A3217FAL210........................................................................................ G9
A3209DT050......................................................................................... G8 A3217FAL260........................................................................................ G9
A3209DT080......................................................................................... G8 A3217FAL410........................................................................................ G9
A3212R105......................................................................................... G15 A3217FAR160....................................................................................... G9
A3212R175......................................................................................... G15 A3217FAR210....................................................................................... G9
A3212R250......................................................................................... G15 A3217FAR260....................................................................................... G9
A3212RT105....................................................................................... G15 A3217FAR410....................................................................................... G9
A3212RT175....................................................................................... G15 A3219FA400L...................................................................................... G11
A3212RT250....................................................................................... G15 A3219FA600L...................................................................................... G11
A3213R150......................................................................................... G14 A3219RT............................................................................................. G13
A3213R200......................................................................................... G14 A7883FK............................................................................................. G17
A3213R300......................................................................................... G14 A7883FK............................................................................................. G18
A3213R400......................................................................................... G14 A7884FK............................................................................................. G17
A3213RT150....................................................................................... G14 A7884FK............................................................................................. G18
G25
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
G
G26
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section H
H H
H1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
This warranty does not extend to any product or part that is not The Limited Warranty stated above is a factory warranty to the first
installed and used continuously after installation in accordance with purchasers of ECII products. Since most users have purchased
ECII’s printed instructions, all applicable state and local regulations, these products from ECII distributors, the user must within thirty (30)
and all applicable national standards, such as those promulgated by days after the user’s discovery of what user believes is a defect,
NFPA, DOT and ANSI. This warranty does not extend to any product notify in writing and return the product to the distributor from whom
or part that has been damaged by accident, misuse, abuse, failure to he purchased the product/part. The distributor may or may not at
maintain, or neglect, nor does it extend to any product or part which the distributor’s option choose to submit the product/parts to ECII,
has been modified, altered, disassembled, or repaired in the field. pursuant to this Limited Warranty. Failure by buyer to give such
This warranty does not cover any cosmetic issues, such as scratches, written notice within thirty (30) days shall be deemed an absolute and
dents, marring, fading of colors or discoloration. unconditional waiver of buyer’s claim for such defects. Acceptance
of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
H2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
H
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
ACME Adapters....................................................................... H9 Pigtails..................................................................................... H8
ACME Check Connectors....................................................... H6 POL Adapters........................................................................ H11
ACME Plugs............................................................................ H7 POL Plugs............................................................................... H7
Caps and Reducers................................................................. H8 Pressure Gauge Adapter....................................................... H11
Cross Reference by Part Number......................................... H13 Short Type Hose Couplings..................................................... H5
Extended Type Hose Couplings.............................................. H4 Swivel Adapters..................................................................... H10
Filler Hose Adapters................................................................ H7 Unloading Adapters................................................................. H6
Miscellaneous Adapters.........................................................H11
H3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Extended Type Hose Couplings for Vapor and Liquid Service
A7571 and A7575 Series
Application
Designed especially for liquid filling and vapor equalization of LP-
Gas and anhydrous ammonia. The limited travel of the handle on the
tailpiece minimizes spin-off, encouraging cautious removal to properly
bleed off trapped product to assure closure of the filler valve and
hose end valve. The ACME threads are machined on a rugged steel
insert which is permanently cast in the aluminum handle, providing for
durability under repeated use.
UL
®
Features
• Lightweight aluminum handle is contoured and ribbed for added
comfort, easy handling allows for easy make-up.
• Free swivel action between tailpiece and handle allows for easy
make-up.
A7571 Series
Materials
Handle................................................................................. Aluminium
ACME Threads.................................................................... Steel Inlet
H Restraining Ring.......................................................... Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
A7575 Series
Ordering Information
A. B. C.
Part Type Hose Connection Coupling Connection Approx.
Number of Service (M. NPT) (F. ACME) Length
A7575L2* ½”
A7575L3 ¾”
Liquid 1¾”
A7575L4 1”
7”
A7575L5** 1¼”
A7571LA ½”
Vapor 1¼”
A7571LB ¾”
* Includes 7199-33 adapter, shipped loose.
** Includes A7575L5-1 adapter, shipped loose.
H4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Short Type Hose Couplings for Vapor and Liquid Service
3171, 3175, 3181, 3185 and 3195 Series
3175 Series
A3185 Series
Style A Style B
For Liquid Filling For Liquid Filling
UL ®
Style C Style D
For Vapor Equalizing For Vapor Equalizing
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
A. B. C. D. E.
Part Hose Connection Coupling Connection Tailpiece Hose End Overall
Number Material Style (M. NPT) (F. ACME) Bore To Nut Length
3175B ½” ⁄ ”
35 64
H5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ACME Check Connectors for Lift Trucks 7141F and 7141M
Application
These brass connectors are especially designed to join the carburetor
fuel line to the service valve on lift truck cylinders. Sturdy, long lasting
ACME threads allow quick, hand-tight assembly that provides for
quick and simple cylinder replacement. Back checks automatically
close in each connector when disconnected.
The 7141M couples directly to the service valve. An integral O-ring is 7141M 7141F
designed to seal before the internal check opens, aiding in product
loss prevention. A gasket at the ACME thread is a secondary seal
when the connectors are tightened together. The connector fits
RegO® lift truck cylinder filling adapters for fast, convenient filling.
The 7141F accepts fuel line adapter and couples directly to the
7141M. The O-ring seal in the 7141M is designed to seal before the
internal check opens to allow product to pass through the connection.
The knurled coupling eases threading and the ACME threads provide
rapid effortless make-up, even against LP-Gas pressure. PRODU
10
O
CT
RE
S
NOTE: Refer to the “Cylinder and Service Valves” section of the
UL
10
Y
NT
E
L-500 catalog for additional information.
Y
AR A
WA R R ®
Ordering Information
Protective Cap*
A. B.
Part Number Application Inlet Outlet Rubber Brass
7141M Service Valve ⅜” F. NPT 1¼” M. ACME 7141M-40 7141FP
7141F Fuel Line 1¼” F. ACME ¼” F. NPT - -
* Recommended to minimize foreign material entering valves which could result in leakage.
Features 3119A
• Built-in vent valve provides for a controlled release of gas which 3120
may be trapped within the unit after use and also helps to indicate
closure of the Filler Valve.
10
O
UL
G
CT
RE
®
10
Y
NT
Materials
Y
AR
WA R RA
Body............................................................................... Brass
Plunger............................................................................ Steel
H6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Filler Hose Adapters 3179A and 7577V
These adapters are designed with minimal flow restriction and
recommended for use on the outlet of the LP-Gas delivery truck filler
hose. If the controlled bleed off of the connection indicates the filler
valve on the tank being filled has failed to close, the hose adapter
should be left in place on the filler valve and disconnection should
be made at the regular filler hose coupling. (Repair of the filler valve
must be made as soon as possible). An integral check valve in these
adapters helps prevent further loss of product. The standard filler
3179B valve cap should be attached to these adapters when left on the
container.
PRODU
10
O
CT
RE
UL
S
10
Y
NT
® E
Y
AR A
WA R R
Ordering Information
Built-in Vent A Filler Valve B Hose
Part Number
Valve Connection Connection
7577V Yes
1¾” F. ACME 1¾” M. ACME
3179B No
7577V
ACME Plugs
Specifically designed to withstand the everyday abuse given hose
C5763N
end valves on delivery trucks and hose end couplings on risers in
bulk plants. These rugged plugs protect the coupling tip as well as
prevent the entrance of dirt, dust, snow and rain. They also prevent
possible gas contamination from these same sources. The heavily
ribbed outer surface permits hand-tight make-up.
H
These plugs are available in a choice of four sizes which may be
used with liquid as well as vapor type couplings. As a convenience,
the nylon plugs have a retaining chain and ring to prevent loss during Ordering Information
a transfer operation. A
Part Number Material (M. ACME) Chain & Ring Fits Pipe Size Up To:
All are suitable for LPG or anhydrous ammonia service except the C5763N 1¼” ¾”
brass 5765PR, which is for LP-Gas only. Nylon
C5765N 1¼”
PRODU
1¾”
UL 10
O
5765PR Brass Not Applicable
G
CT
RE
®
C5767N 2¼” 1¼”
10
Y
NT
E
Nylon
Y
AR A
WA R R
C5769N 3¼” 2”
POL Plugs
PRODU
10
O
G
CT
RE
UL
10
Y
NT
E
Y
AR A ®
WA R R
10538P
(Has hole for attaching
wire to prevent loss of
plug) 3705RC
N970P W/Chain & Ring
Highly recommended for installation in LP-Gas cylinder valve POL Ordering Information
outlets whenever the service line is disconnected or when the cylinder
Part
is being transported.
Number Material Connection
When properly installed, the POL plug is designed to prevent N970P Cycolac
M. POL
contamination of the valve outlet and guards against product leakage 10538P
Brass (CGA 510)
if the cylinder valve is accidentally opened. 3705RC
H7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Caps and Reducers
Ordering Information
Cap With Chain & Ring
Part Ring Fits Pipe Cap Only Part Thread
Number Size Up To: Number Material Connection 907FP
A5776
3144-91 3144-9P 1¼” F. ACME Reducer Coupling
¾” 7141FP Cap Plug
3174-91 Cycolac
3174-9P
3174-93 1¾” F. ACME
1¼”
A8016-93 A8016-9P Nylon
1708 ¾” F. POL (CGA 510)
7141FP 1¼” F. ACME
1¼” -
3175P 1¾” F. ACME
Brass 1708C POL Cap
3184-90 2” 2¼” F. ACME
3194-90 3” 3194-9 CGA 510
3¼” F. ACME
- - 5776* 3194-90G ACME Cap with
A3184-90 2” 2¼” F. ACME Stainless Steel Flange
-
A3194-90 3” Steel
3¼” F. ACME
- - A5776*
907FP 1” - Brass 115 16 ” F. ACME
* Reduces to 13⁄4” M. ACME
PRODU
10
O
G
CT
3144-91
RE
Y
NT
E
Y
Copper Pigtails
612J Series Gauge Tail 0-300 PSIG
PRODU
Pressure Gauge
10
O
Features UL
G
CT
RE
150 150
120 180 120 180
10
90 210
R
® 90 210
R
NT
E 612-PG 612-PG
Y
AR A 60 240 60 240
WA R R
30 270
0 300 0 300
1/4” NPT
• Individually soldered connections to the copper tubing. POL (CGA 510)
• Each pigtail is individually tested prior to shipment.
H
Materials
Fully Retained Bleeder Valve
Flat Blade Screw Slot
Tubing...................................................................................... Copper
Connections............................................................................... Brass 0-300 PSIG
612P Series Gauge Tail Pressure Gauge
150
120 180
912JS12 90 210
R
612-PG
60 240
30 270
0 300
Straight Pigtails
R
MA
Ordering Information
Fully Retained Bleeder Valve
Part Number Flat Blade Screw Slot
¼” Tube ⅜” Tube
⅞” Hex
Approximate ⅞” Hex 1⅛” Hex Short
Connections Length Short Nipple Long Nipple Nipple
5” - ½” 913JS05
12” 912PS12 - 913PS12
[Link] x 20” 912PS20 912PA20 913PS20 913JS05A
[Link] 30” 912PS30 - 913PS30 913PS05A
36” 912PS36 912PA36 913PS36
Bent Pigtails
48” 912PS48 912PA48 913PS48
12” 912FS12 - - Ordering Information 913PS12G
H8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ACME Adapters
Ordering Information
PRODU
For Spare
10
O
UL
CT
RE
D Gasket
S
®
Part A B C Overall E Order
10
Y
NT
E
Y
AR A
Number Material M. ACME MNPT Hex Length Diameter Part No. WA R R
5764A ¼” 1½” D
5764B ⅜”
A2697-
5764C 1¾” ½” 1¾” ¾”
1⅞” 20R
5764D ¾”
5764E 1”
Brass
5766E 1” A B C
2¼” 2¼” 2 5
16 ” 1⅜” A3184-8R E
5766F 1¼”
5768G 1½”
5768H 3¼” 2” 3½” 3⅝” 2⅛” A3194-8R
5768J 2½”
A5764D ¾” A2697- Gasket (Furnished with adapter)
1¾” 1¾” 2 3 16 ” ¾”
A5764E Steel 1” 20R
ACME x Female NPT
A5768H 3¼” 2” 3¼” 3¼” 1 13 16 ” A3194-8R
Ordering Information
For Spare
D Gasket
Part A B C Overall E Order
Number Material M. ACME F. NPT Hex Length Diameter Part No.
5763D 1¼” ¾” 1¼” 1¾” 7
16 ” A2797-20R
5765D ¾” 1⅞” 11
16 ” D
5765E 1¾” 1” 1¾” A2697-20R
2⅛” ¾”
5765F 1¼”
5767F 1¼” 1 3 16”
Brass 2¼” 2 5
16 ”
5767G 2¼” 1½” 1⅜” A3184-8R
A E B C
5767H 2” 2⅜” 2 7 16 ” 1 25 64”
5769H
5769J 3¼”
2”
2½”
3⅜”
3¼”
2⅞”
3½”
1⅞”
A3194-8R
H
2⅛”
5769K 3” 3½” 3⅝”
A5765C ½” 17
32 ”
Gasket (Furnished with adapter)
A5765D ¾” 11
16 ”
1¾” 1¾” 2 3
” A2697-20R
ACME x Male NPT
16
A5765E 1” ⅞”
A5765F Steel 1¼” ”
15
16
C
Ordering Information
For Spare
Gasket
Part A B C D Order A D A B
Number Material M. ACME F. NPT Hex Diameter Part No.
5765M 1¾” 1¾” 2 1 16 ” ⅞” A2697-20R
5767M Brass 2¼” 2¼” 2 5 16 ” 1 25 64” A3184-8R
5769M 3¼” 3¼” 2¾” 2⅛” A3194-8R
Gasket (Furnished with adapter)
ACME x ACME
Ordering Information C
For Spare
Gasket
Part A B C D Order
Number Material M. ACME F. NPT Hex Diameter Part No.
D B A
A5764W Steel 1¾” ⅜”* 1¼” 1 11 16 ” 2697-20
* 3⁄8” -16 UNC Thread.
ACME x Miscellaneous
(Recommended for securing
hose-end valve when not in use).
H9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Male POL Swivel Adapters
D PRODU D
10
O
UL
CT
RE
S
®
10
Y
NT
E
Y
A
B
AR
WA R R C B
C
A A
970 (CGA 510) POL
970S (CGA 510) POL
Hard Nose POL Soft Nose POL w/60 DMS Orifice
D
D
3188 Series
C B B
C
50-70
Micron
A Filter
(CGA 510) POL A
970AXS
Soft Nose POL w/Excess Flow D 3199W (CGA 510) POL
Heavy Duty Hard Nose POL w/Excess Flow
D
D
C B
C B
C B
A
A 970AW (CGA 510) POL A
970HT (CGA 510) POL
970AX (CGA 510) POL 970JR
Soft Nose POL w/Handwheel
Hard Nose POL w/Excess Flow Hard Nose POL w/Hose Barb Connection
H Ordering Information
Part A B C D Vapor at 100 PSIG Liquid
Number Material Outlet Thread Hex Drill Overall Length Inlet (SCFH) (GPM)
970 ⁄ ”
5 16 2⅜”
- -
970S ⁄ ”
3 16 23⁄32”
970AX ⅞”
¼” 25⁄64” 404 1.10
970AXS
M. NPT ⁄ ”
5 16
3199W 2⁄ ”7 16 450 0.95
970AW
Brass 1⅜” 22⁄32”
970HT ⁄ ”
3 16
- -
¼”
970JR ⅞” ⁄ ”
5 32 2⅝”
Hose Barb
3188A 350 .95
½”
3188B 1⅛” ⁄ ”
5 16 2½” 700 1.9
M. NPT
3188C 1180 2.9
Note: All nipples incorporate wrench hex section.
A
PRODU
10
O
Part A B C D B
G
CT
C
RE
Y
NT
®
12982 ¼” M. NPT E
Y
AR A
WA R R
Brass 1¼” ⁄ ”
3 16 1 ⁄ ”
15 16
12982G 9⁄16” -18NF
D
CGA 555
H10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
POL Adapters
PRODU
B
10
B O
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
D A C D C
CGA 510 D
A C
(POL) CGA 510 D
(POL) A C Female POL x Male NPT
Ordering Information
Ordering Information
A B C D
Part A B C D Part Number Material Hex Diameter
H
Number Material Hex Diameter
5761A ¼” 3
16 ”
5760Z ⅛” 5
”
16 5761B ⅜” 13
32 ”
5760A ¼” 13
32 ”
Brass 1⅝” 1⅛”
1⅝” 1⅛” 5761C ½” 7
5760B ⅜” 35
64 ”
16 ”
Brass 5761D ¾”
43
5760C ½” 64 ”
11⁄8” B
⁄”
78
Hose
Adapter Ordering Information
For use with fuel Part A B
gases (LP-Gas, 1⁄4” ⁄ ” Hex.
9 16
Number Material
5⁄8”
Acetylene). Hex.
Female
15774-1 Brass ¼” M. NPT Inverted
A B Flare
A
Ordering Information Female Inverted Flare
x Male NPT
Part A B B
Number Material
1300 Brass 9
16 ”-18NF (L.H.) ¼” M. NPT
D
23⁄16”
B A
C
Pressure E
Gauge Adapter
11⁄4”
Hex.
A
C
F
Ordering Information Ordering Information
Part Part
Number Material A B C Number Material A B C D E F
1494-1 Brass ½” F. NPT ¼” F. NPT ½” M. NPT 1328 ⅝” - 18 UNF ⅝” - 18 UNF ¼”
13
”
16 2” 1½”
1331 Brass ¾” - 16 UNF ¾” - 16 UNF Hose 15
16 ” 2⅛”
Barb 1¾”
1332 ⅞” - 14 UNF ⅞” - 14 UNF 1 1 16 ” 2½”
H11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Hose End Valve Adapter
7576
Application
No gas flow is allowed when this adapter is not connected to the 1¾”
ACME connection of a filler valve, it also acts as a back check.
UL ®
Features
• Designed to be installed on the outlet connection of LP-Gas hose
end valve; no flow is allowed until the 7576 adapter female ACME
connection is engaged on to the male ACME threads on the filler
valve.
• Incorporates a back check that will stop flow out of a filler valve that
fails to close, when the 7576 adapter remains connected to the
filler valve.
• Bleeder valve is designed to vent gas between the hose end valve
connection and 7576 hose end adapter.
7576
Materials
H
Body........................................................................................... Brass
Inlet Connection......................................................................... Brass
Outlet Connection....................................................................... Brass
ACME Swivel....................................................................... Aluminum
Spring.......................................................................... Stainless Steel
Seat Disc.................................................................. Synthetic Rubber
O-Rings.................................................................... Synthetic Rubber
4.0
PRODU 4.1
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Filler Connection Hose End Valve Connection Propane Liquid Capacity @
Part Number Vent Valve
80 PSID
7576 Yes 1¾” F. ACME 1¾” M. ACME 57 GPM
H12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cross Reference by Part Number
12982..............................................................................................H10 5765D...............................................................................................H9
10538P..............................................................................................H7 A5765E................................................................................................H9
1300................................................................................................H11 5765E................................................................................................H9
1328................................................................................................H11 A5765F................................................................................................H9
1331................................................................................................H11 5765M...............................................................................................H9
1332................................................................................................H11 C5765N...............................................................................................H7
1494-1.............................................................................................H11 5765PR.............................................................................................H7
15774-1...........................................................................................H11 5765F................................................................................................H9
1708..................................................................................................H8 5766E................................................................................................H9
2906A..............................................................................................H11 5766F................................................................................................H9
2906D.............................................................................................H11 A5767F................................................................................................H9
2906E..............................................................................................H11 5767F................................................................................................H9
2906F..............................................................................................H11 5767G...............................................................................................H9
2906G.............................................................................................H11 5767H...............................................................................................H9
3119A................................................................................................H6 5767M...............................................................................................H9
3120..................................................................................................H6 C5767N.............................................................................................H7
3121..................................................................................................H6 5768G...............................................................................................H9
3144-91.............................................................................................H8 A5768H...............................................................................................H9
3144-9P............................................................................................H8 5768H...............................................................................................H9
3171..................................................................................................H5 5768J................................................................................................H9
3171A................................................................................................H5 A5769H...............................................................................................H9
3174-91.............................................................................................H8 5769H...............................................................................................H9
3174-93.............................................................................................H8 5769J................................................................................................H9
3174-9P............................................................................................H8 A5769K................................................................................................H9
3175..................................................................................................H5 5769K................................................................................................H9
A3175..................................................................................................H5 5769M...............................................................................................H9
A3175A................................................................................................H5 C5769N...............................................................................................H7
3175A................................................................................................H5 5776..................................................................................................H8
3175B................................................................................................H5 A5776..................................................................................................H8
3175P................................................................................................H8 7141FP.............................................................................................H8
3179B................................................................................................H7 A7571LA..............................................................................................H4
3181..................................................................................................H5 A7571LB..............................................................................................H4
3181A................................................................................................H5 A7575L2..............................................................................................H4
A3184-90..............................................................................................H8 A7575L3..............................................................................................H4
3184-90..............................................................................................H8 A7575L4..............................................................................................H4
3185...................................................................................................H5
A3185..................................................................................................H5
A7575L5..............................................................................................H4
7576................................................................................................H12 H
3188A..............................................................................................H10 7577V................................................................................................H7
3188B..............................................................................................H10 A8016-93.............................................................................................H8
3188C.............................................................................................H10 A8016-9P............................................................................................H8
3191..................................................................................................H5 907FP...............................................................................................H8
3194-9...............................................................................................H8 912FA20............................................................................................H8
A3194-90.............................................................................................H8 912FS12...........................................................................................H8
3194-90.............................................................................................H8 912FS20...........................................................................................H8
3195..................................................................................................H5 912FS30...........................................................................................H8
A3195..................................................................................................H5 912FS36...........................................................................................H8
3199W.............................................................................................H10 912JS12............................................................................................H8
3705RC.............................................................................................H7 912JS20............................................................................................H8
5760A..............................................................................................H11 912JS36............................................................................................H8
5760B..............................................................................................H11 912PA20...........................................................................................H8
5760C.............................................................................................H11 912PA36...........................................................................................H8
5760D.............................................................................................H11 912PA48...........................................................................................H8
5760S..............................................................................................H11 912PS12...........................................................................................H8
5760Z..............................................................................................H11 912PS20...........................................................................................H8
5761A..............................................................................................H11 912PS30...........................................................................................H8
5761B..............................................................................................H11 912PS36...........................................................................................H8
5761C.............................................................................................H11 912PS48...........................................................................................H8
5761D.............................................................................................H11 913JS05A..........................................................................................H8
5763D...............................................................................................H9 913PS05A.........................................................................................H8
C5763N...............................................................................................H7 913PS12G........................................................................................H8
5764A................................................................................................H9 913PS12H.........................................................................................H8
5764B................................................................................................H9 913PS12S.........................................................................................H8
5764C...............................................................................................H9 970..................................................................................................H10
A5764D...............................................................................................H9 970AW............................................................................................H10
5764D...............................................................................................H9 970AX.............................................................................................H10
A5764E................................................................................................H9 970AXS...........................................................................................H10
5764E................................................................................................H9 970HT.............................................................................................H10
A5764W...............................................................................................H9 970JR..............................................................................................H10
A5765C...............................................................................................H9 N970P.................................................................................................H7
A5765D...............................................................................................H9 970S................................................................................................H10
H13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
H
H14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas & Anhydrous Ammonia Equipment
Section J
J J
Miscellaneous Equipment
(Including Rotogages and ESVs)
J1
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Limited Warranty and Limitation of Liability
This warranty does not extend to any product or part that is not The Limited Warranty stated above is a factory warranty to the first
installed and used continuously after installation in accordance with purchasers of ECII products. Since most users have purchased
ECII’s printed instructions, all applicable state and local regulations, these products from ECII distributors, the user must within thirty (30)
and all applicable national standards, such as those promulgated by days after the user’s discovery of what user believes is a defect,
NFPA, DOT and ANSI. This warranty does not extend to any product notify in writing and return the product to the distributor from whom
or part that has been damaged by accident, misuse, abuse, failure to he purchased the product/part. The distributor may or may not at
maintain, or neglect, nor does it extend to any product or part which the distributor’s option choose to submit the product/parts to ECII,
has been modified, altered, disassembled, or repaired in the field. pursuant to this Limited Warranty. Failure by buyer to give such
This warranty does not cover any cosmetic issues, such as scratches, written notice within thirty (30) days shall be deemed an absolute and
dents, marring, fading of colors or discoloration. unconditional waiver of buyer’s claim for such defects. Acceptance
of any alleged defective product/parts by ECII’s distributor for
replacement or repairs under the terms of ECII’s Limited Warranty in
no way determines ECII’s obligations under this Limited Warranty.
J2
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Foreword
This catalog describes a complete line of equipment available from Engineered Controls International, Inc. for use with LP-Gas and
anhydrous ammonia (NH3). The following points are important to know for proper use of the catalog:
1. Illustrations and drawings of individual products are representative of “product groups” and all products within a product group
are similar in construction.
2. Materials used for construction of products in this catalog are suitable for rated service pressure at temperatures of -40° F.
to +165° F., unless otherwise specified.
3. Products in this catalog are only intended for use in LP-Gas and/or anhydrous ammonia service as follows.
a. “A” or “AA” prefix — Products with this prefix are suitable for NH3 service (i.e., contain no brass parts).
b. “AA” prefix on relief valves — These valves are NOT suitable for use with LP-Gas service. These are of partial aluminum
materials and are listed by Underwriters Laboratories (UL) for NH3 service only.
c. All other products are suitable for use with LP-Gas service.
d. “SS” prefix—Hydrostatic relief valve with this prefix are suitable for NH3 service (i.e., they have stainless steel materials).
Caution Notice
Do not use any product contained in this catalog with any Installation, usage, and maintenance of all ECII® products must
service commodity other than LP-Gas or NH3. If you have be in compliance with all Engineered Controls International,
a need for use of another application, contact Engineered Inc. instructions as well as requirements and provisions of
Controls International, Inc., 100 RegO Drive, Elon, NC 27244, NFPA #54, NFPA#58, DOT, ANSI, and all applicable federal,
(336) 449-7707 before proceeding. state, provincial and local standards, codes, regulations, and
laws.
Proper application, installation and maintenance of products
in this catalog are essential. Users of these products Inspection and maintenance on a periodic basis is essential.
should obtain further information if there are any doubts or Installation and maintenance should be performed only by
questions. qualified personnel.
Be sure all instructions are read and understood before
installation, operation and service.
Warning
All ECII ® products are mechanical devices that will
eventually become inoperative due to wear, corrosion and Filters
aging of components made of materials such as rubber.
The environment and conditions of use will determine the ECII® LP-Gas equipment is designed to operate in a system
J
safe service life of these products. Periodic inspection free from contamination. A variety of in-line filters are
and maintenance are essential to avoid serious injury and commercially available to the LP-Gas industry for installation
property damage. in domestic systems.
The use of an in-line filter should be considered when
Many ECII® products are manufactured for storage, transport, other system components may be unclean and the system
transfer and use of toxic flammable and dangerous liquids and contaminated by rust, scale, dirt, debris or other foreign
gases. Such substances should be handled by experienced material.
and trained personnel only, using accepted governmental
and industrial safety procedures. Never vent LP-Gas near any
possible source of ignition.
Contents Page
Combination Valve.................................................................. J17 Needle Valves......................................................................... J20
Cross Reference by Part Number.......................................... J21 Pressure Gauges................................................................... J19
Cylinder Filling Systems......................................................... J15 Pull-Away Valves...................................................................... J7
Emergency Shut-Off Valves (ESVs)...................................J8/J11 Quick Connect POL Filling Adapters...................................... J19
ESV Accessories.................................................................... J12 Rotogages®.........................................................................J4/J6
Fixed Liquid Level Gauges..................................................... J18 Sight Flow Indicators.............................................................. J16
Gas Alarms and Detectors..................................................... J20 Spanner Wrench..................................................................... J22
Gritrol Filters........................................................................... J17 Vent Valves............................................................................. J21
Hose-End Adapters..........................................................J15/J16
J3
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
1” Rotogages® for Large Mobile and Stationary Containers
9090 and AA9090 Series
Application
Rotogages® are designed to provide an accurate determination of
LPGas or anhydrous ammonia container contents. They mount in a
standard 1” NPT coupling on large mobile or stationary containers.
To operate the Rotogages®, the vent valve is opened and the dip
tube rotated slowly from the container vapor space to the liquid
space. The difference in appearance of the discharge indicates when
the liquid level is reached. Dial readings then indicate the percentage
of product in the container.
Features
• Supported design (TS Models) eliminates whipping and the need
for internal support hangers.
Materials
J Body............................................................................................ Steel
Stem............................................................................................ Steel
Dip Tube..................................................................... Seamless Steel
Indicator......................................................................... Malleable Iron
Dial Plate............................................................................. Aluminium
Vent Stem.................................................................... Stainless Steel
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
A9091-18LX
UL
®
Rotogage® Dials
Ordering Information
Part Number Service Container Size
A9091-18L LP-Gas All Sizes
A9091-18LX* LP-Gas Over 1200 U.S. gallons
A9091-18N NH3 All Sizes
* Dial permits higher filling level, as per NFPA 58, (1983) Par. 4-5.2.1, Table 4-5.2.1
J4
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
1” Rotogages® for Large Mobile and Stationary Containers
UL ®
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
For Container Inside Diameter
Part Number
J5
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
¾” Rotogages® for Small Stationary and Mobile LP-Gas Containers
2070 Series
Application
Rotogages® are designed to provide accurate determination of
LP-Gas container contents. They may be end or side mounted in
a standard ¾” NPT coupling on stationary or mobile containers.
UL®
Features
• Provides long, trouble-free performance and ease of operation.
Materials
Body........................................................................................... Brass
Stem............................................................................... Brass Tubing
Dip Tube........................................................ Seamless Brass Tubing
Dial Plate............................................................................. Aluminium
Indicator......................................................................... Malleable Iron
PRODU
10
O
J
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number
For Containers with Inside
Rotogage® Dip Tube Diameter Tank Connection Valve Seat Orifice
2071-L25.7 Up to 40” No. 54
2070CO ¾ M. NPT
2071-L39.7 Up to 60” Drill Size
NOTE: The dip tube must be cut to the required length (1⁄2 of container inside diameter minus
1⁄2”), when mounted on center line of tank.
J6
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Pull-Away Valves for Transfer Operations
A2141 Series
Application
Designed especially to provide pull-away protection for LP-Gas and Materials
anhydrous ammonia transfer operations including transport and
delivery truck loading and unloading, engine fuel container filling and Body (¾”, 1”)................................................... Cadmium Plated Steel
miscellaneous cylinder filling operations. When properly fastened to Body (1¼”, 2”)..................................................................... Aluminum
the inlet end of the discharge hose, the valve is designed to stop gas Seals.......................................................................... Buna-N Rubber
escape from both upstream and downstream lines in the event of a Cables.............................................. Nylon Coated, Galvanized Steel
pull-away. An excessive tension pull causes the valve to automatically
separate, closing two internal back pressure checks. Only a few cubic
centimeters of gas escape at the instant of separation.
Features
J
• Heavy-duty construction for long service life.
PRODU
10
O
G
CT
RE
UL
S
10
®
NT
E
Y
AR A
WA R R
Ordering Information
LP-Gas Liquid Flow Capacity at Various Differential Pressures
Inlet/Outlet Disconnect Reconnect (GPM)*
Length Of
Part Number Connections Force Force
Valve
NPT F. Approx-lbs Approx-lbs 5 PSIG 10 PSIG 25 PSIG 50 PSIG
A2141A6
¾” 130 80 37⁄8” 11 16 25 36
A2141A6L**
A2141A8
1” 75 50 49⁄16” 21 30 47 67
A2141A8L**
A2141A10 1¼” 160 25 55⁄8” 52 75 120 170
A2141A16 2” 300 50 145⁄16”” 250 350 550 750
* To Determine NH liquid flow capacity, multiply by .90.
3
J7
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Emergency Shut-Off Valves (ESV’s)
Why and how they should be used for Bobtail Filling Section 2-4.5.4 Emergency shutoff valves shall be approved and
and Transport Unloading. incorporate all the following means of closing:
General Information (a) Automatic shutoff through thermal (fire) actuation. When fusible
The primary purpose of Emergency Shut-Off Valves in bobtail filling elements are used they shall have a melting point not exceeding 250°
and transport unloading is to allow quick shut-off of liquid and vapor F. (121° C).
flow in the event there is an accidental pull-away of a truck or a hose
rupture, both of which could cause a fire. (b) Manual shutoff from a remote location.
A system using Emergency Shut-Off Valves will not prevent some (c) Manual shutoff at the installed location.
spillage of liquid and vapor, but the total system should be constructed
so this spillage will be kept to a minimum. This provision sets for the basic criteria for the emergency shutoff
valve, a key valve in the protection of many liquid transfer operations.
Actuating means for remote control may be electrical, mechanical or
This can be accomplished either by making possible, quick action pneumatic.
by the driver or plant personnel in closing the valves by manual
remote or pneumatic remote actuation; or in case of a pull-away, by Many systems use a pneumatic system where the tubing itself acts
automatic closing of the liquid valve by means of a cable connected as a fusible element releasing the pressure holding the valve open.
to the liquid hose. With respect to the feature of manual shutoff at the installed location,
it is recommended that this valve be operated occasionally. Also, the
By minimizing the presence of liquid and vapor, the chance of a fire or system should be tested periodically to determine that it will function
explosion will be reduced. In case of a fire, thermal links at the valves properly.
or at other appropriate locations could close the valves and prevent
further release of liquid and vapor. Section 3-2.7.9 on new installations, and by December 31, 1980
on existing installations, (1) stationary single container systems of
The valve closing systems will be discussed later in this section. The over 4,000 gal. (15.1 m3) water capacity, or (2) stationary multiple
user should decide which system is most appropriate, depending on container systems with an aggregate water capacity of more than
the piping configuration and the general layout of the filling/-unloading 4,000 gal. (15.1 m3) utilizing a common or manifolded liquid transfer
area. line, shall comply with 3-2.7.9 (a) and (b).
ESV Application for Bobtail Loading and Transport Unloading (a) When a hose or swivel type piping 11⁄2” or larger is used for liquid
transfer or a 11⁄4” or larger vapor hose or swivel type piping is used
A very important function of the typical LP-Gas storage plant is to in this service (excluding flexible connectors in such liquid and vapor
transfer LP-Gas into bobtails for delivery to customers. How efficiently piping), and emergency shutoff valve complying with 2-4.5.4 shall be
and rapidly these bobtails can be filled often determines the number installed in the fixed piping of the transfer system within 20 ft (6m) of
of customers that can be served each day, as well as how many lineal pipe from the nearest end of the hose or swivel type piping to
J bobtails are required to satisfactorily serve all customers. Therefore,
the selection of an ESV for the bobtail liquid loading line should be
which the hose or swivel type piping is connected. The preceding
sizes are nominal. Where the flow is only in one direction, a backflow
done with care so as to maximize efficiency in filling and have year- check valve may be used in lieu of an emergency shutoff valve if
round dependability. installed in the fixed piping down-stream of the hose or swivel type
piping, provided the backflow check valve has a metal-to-metal seat
The RegO® 2” liquid ESV (7605B) has a full open port so that the or a primary resilient seat with a secondary metal seat not hinged
restrictions of flow would be no more than you would expect through with combustible material. When either a liquid or vapor line has two
an equivalent length of 2” schedule 80 pipe. To improve the overall or more hoses or swivel type piping of the sizes designated, either an
efficiency of the system, the valve was also designed as an operating emergency shutoff valve or a backflow check valve shall be installed
valve so it could replace an existing globe or angle valve already in each leg of the piping.
installed at the end of the fixed piping. Thus, installing a RegO® ESV
could actually result in a more efficient pumping operation than the (1) Emergency shutoff valves shall be installed so that the temperature
existing system. sensitive element in the valve, or a supplemental temperature
sensitive element [250° F. (121° C) maximum] connected to actuate
Equally important in the consideration of an ESV is its performance in the valve, is not more than 5 ft. (1.5 m) from the nearest end of the
an emergency, especially bobtail pull-aways. According to the NPGA, hose or swivel type piping connected to the line in which the valve is
it is the bobtail filling transfer process that produces almost 99% of all installed.
bulk plant accidents and fires. Therefore, when selecting the proper
ESV for bobtail filling, also consider the dependability of performance, (b) The emergency shutoff valve(s) or backflow check valve(s)
and simplicity of operation and maintenance. specified in 3-2.7.9 (a) shall be installed in the plant piping so that any
break resulting from a pull will occur on the hose or swivel type piping
The RegO® ESV clearly indicates to the operator its open or closed side of the connection while retaining intact the valves and piping on
position. It allows full manual control by the operator and provides the plant side of the connection. This may be accomplished by use
means for remote operation in emergencies from either in front of the of concrete bulkheads or equivalent anchorage or by the use of a
valve or in the rear. weakness or shear fitting. Such anchorage is not required for tank
car unloading.
No complicated systems of pulleys and cables are necessary since
direct, straight pulls will close the valve. Means are even provided
to secure a length of cable to the transfer hose so as to produce These provisions have been interpreted by the National Propane Gas
an automatic closing in the event the driver pulls away without Association as to how bobtail filling and transport unloading stations
disconnecting the hose. should be configured. The diagrams shown here are in essential
conformance with NPGA Bulletin 128-77.
NFPA Provisions (1986)
J8
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
LP-Gas Emergency Shut-Off Valves (ESV’s)
To this point, our comments have been principally concerned with Remote Control Systems
ESV protection of the liquid line at bulk plants because this is the
area of greatest potential danger in the event of a pull-away or hose Usually in transfer loading operations, the valve handles and cables
rupture. are located in close proximity to the area of greatest potential danger
during an emergency. Therefore, each bobtail filling system or
However, regulations also require an ESV in the vapor transfer line transport unloading system should have installed in it at least one
when the vapor hose is 11⁄4” or larger. A helpful rule of thumb in readily accessible, alternate remote operating device.
determining whether or not an ESV control valve is required in your
Figure 2
RegO® ESV’s with Remote Pneumatic
and Transfer Hose Cable Release
Systems Typical Installation
J9
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
2” & 3” Swing-Check ESVs for Bulk Plants
6016 Series and 6024 Series
Application UL
®
• Straight through design allows for a liquid flow of 150 GPM (LPG)
with only a 1 psig drop.
• Valve has only two moving parts, stem and close/thermal trigger.
• Stem seals are spring loaded for leak free performance at low
temperatures/pressures.
Materials
Body............................................................... Ductile Iron Cad Plated
Stem............................................................................ Stainless Steel
Seat............................................................................. Stainless Steel
Seat Disc (6016)............................................. High Temperature Viton
Seat Disc (AA6016).................................................. Synthetic Rubber
Springs........................................................................ Stainless Steel
Gaskets...................................................................................... Teflon
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number For Use With: Inlet and Outlet Connections Liquid Flow Capacity at 10 PSIG Drop (GPM)
6016 LP-Gas 2” F-NPT 711 (LP-Gas)
AA6016 NH3 2” F-NPT 640 (NH3)
6024 LP-Gas 3” F-NPT 1325 (LP-Gas)
AA6024 NH3 3” F-NPT 1173 (NH3)
J10
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
1¼” Swing-Check ESV for Bulk Plants
6010 and AA6010
Application
Designed for installation in liquid or vapor transfer lines at LP-Gas or
Anhydrous Ammonia bulk plants to provide for quick shut-off of liquid
or vapor flow in the event of an accidental pull-away, line break, or
hose rupture.
Features
Meets NFPA 58 and UL requirements
• Valve has only two moving parts, stem and close/thermal trigger.
J
5.2
• Stem seals are spring loaded for leak free performance at low
temperatures/pressures.
9.9 5.7
Materials
Body.............................................................. Ductile Iron Clad Plated
3.4
Stem............................................................................ Stainless Steel
Seat............................................................................. Stainless Steel 5.2
Seat Disc..................................... High Temperature Viton (6010 only)
Seat Disc.......................................... Synthetic Rubber (AA6010 only)
PRODU
10
Springs........................................................................ Stainless Steel O
G
CT
Gaskets...................................................................................... Teflon
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Inlet and Outlet Accessories Liquid Flow Capacity @ 10 PSIG
Part Number For Use With Pressure Drop (GPM)
Connections Remote Pneumatic Close Remote Pneumatic Open/Close
6010 LP-Gas 1¼” F. NPT 259
6016-60D 6016-60C
AA6010 NH3 1¼” F. NPT 233
J11
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
ESV Pneumatic Controls
Application UL
®
Features
Convenience 6016 with 6016-60D Remote Close Actuator
Reliability
Security
PRODU
10
O
G
CT
RE
Y
NT
E
Y
Ordering Information
Part Number Description
7781AFPN-1 Cylinder assembly kit to convert 7781AF ESVs to pneumatic shutdown.
6016-60D Cylinder assembly kit to convert 6016 ESVs to pneumatic shutdown.
7605PN-50 Pneumatic remote shutdown system kit, complete with 100’ of tubing, fittings, 1 charging valve assembly and 1 remote shutdown valve assembly
7605APN-8A Extra shutdown valve assembly
7605A-BT 100’ roll of ¼” pneumatic tubing.
7605AP-16 ¼” tubing tee, with nuts.
7605AP-15 ⅛” NPT x ¼” tubing, straight connector.
J12
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Hydraulic Automatic Cylinder Filling System
7194MD and 7194HD
Application
Hydraulic self-contained system.
Designed to provide accurate, economical filling of LP-Gas DOT and No external power required.
fork lift cylinders by weight. Filling stops automatically as the total
weight of the cylinder reaches the amount pre-set on the scale. One
individual can efficiently handle up to four cylinder filling operations
simultaneously, to maximize profits, increase efficiency and allow Shut-off Valve
servicing of more customers.
1
The RegO® automatic cylinder filling system is designed for use with
these scales only: LP-Gas Supply
6 Strainer Hydrostatic Relief Valve
FAIRBANKS-MORSE SCALES
New Style - 1280A Double Beam Scale or Single Beam Scales 3
1124A and 1174A. 7
Old Style - 1280 Double Beam Scale or Single Beam Scale 1123
with or without Howe No. 12108 “Over or Under’’ Indicator. 8 Open
HOWE SCALES
(with or without Howe No. 8325 Balance Indicator)
—No. 54X Wood Pillar and Shelf Scale.
—No. 57 Steel Pillar and Shelf Scale (single beam).
2
—No. 57X Steel Pillar and Shelf Scale (double beam).
Features Closed
4 A,B
to the cylinder valve, and the lever on the master cylinder is moved
to the vertical position. When the quick-acting valve on the loading
hose is opened, the cylinder will rapidly fill. The master cylinder lever PRODU
10
O
is designed to trip, move to a horizontal position and automatically G
CT
RE
S
shut off the control valve as soon as the scale reaches the pre-set
filled weight.
10
Y
NT
E
Y
AR A
Components may be ordered separately with piping done by the WA R R
installer. Two completely assembled manifold configurations are also
available.
Key
No. Description Size Part No.
Assembly for Fairbanks-Morse. Includes items 1 thru 8 below. 7194MD
Assembly for Howe. Includes items 1 thru 8 7194HD
1 Propane Control Valve ½” NPT Female, with ⅛” NPT Female Hydraulic Connection 7177
2 Master Cylinder, with Actuator Lever ⅛” NPT Hydraulic Connection 7188
3 Hydraulic Hose Assembly ⁄ ” I.D. with ⅛” NPT Male Ends, 43½” Overall Length
3 16 7194-1
1-3 Valve, Cylinder and Hose Assembly for Fairbanks-Morse Scales - 7188MS
1-3 Valve, Cylinder and Hose Assembly for Howe Scales - 7188HS
Bracket Kit for Fairbanks Morse Scales, Complete with Screws, Washers, Nuts
4A - 7194M-3A
and Instructions
Bracket Kit for Howe Scales, Complete with Screws, Washers, Nuts and
4B - 7194H-3
Instructions
5 Can of Hydraulic Fluid, Complete with Filling Spout 1½ ounce 7188-21
6 Propane Filling Hose Assembly ½” I.D., with ½” NPT Male Ends. 50½” Overall Length 7193D
7 Quick-acting Shut Off Valve ½” NPT INlet X ¼” NPT Outlet 7901TB
8* Soft Nose Cylinder Connector ¼” NPT Male X POL Male 7193D-10
J13
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Sight Flow Indicators for Bulk Plants
A7794 and A7796
Application UL
®
Features
• Durable ductile iron body assures long, trouble-free operation with
design working pressure of 400 PSIG.
Materials
Body.................................................................................. Ductile Iron
Swing Check............................................................... Stainless Steel
Check Seat Disc........................................ Resilient Synthetic Rubber
Glass............................................... Polished, Ground and Tempered
Tested to 2,500 PSIG.
PRODU
10
O
G
CT
RE
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
A
Inlet/Outlet B
Part Number Connections Length
A7794 2” F. NPT 5¾”
A7796 3” F. NPT 7⅜”
J14
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Hose End Adapters for DOT Cylinder Filling
7193D-10 and 7193U-10
Application
Designed to provide quick and easy filling of DOT cylinders with POL
UL ®
PRODU
7193D-10
10
O
CT
RE
S
10
Y
NT
E
7193U-10
Y
AR A
WA R R
Application
The 7193T-10 Connector is designed for use on the 7193D-10 Filling
Adapters. Connector allows quick connection to the Type I 15⁄16 M.
ACME threads for operators that fill both POL and Type I valves.
PRODU
10
O
7193T-10
G
CT
UL
RE
®
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Applications Inlet Connection Outlet Connection Materials
7193T-10 Converts 7193D-10 Adapters from POL to a Type 1 Connection M. POL CGA 510 Type 1 Connection (15⁄16” M. ACME) Brass
J15
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Hose End Adapter for Lift Truck Cylinder Filling
7193L-10A
Application
The 7193L-10A is designed to provide quick and easy attachment of
the filling hose to DOT cylinders equipped with RegO® 7141M check
connectors.
10
O
G
CT
RE
UL
S
®
10
Y
NT
E ⁄ ” NPT
14
Y
AR A
WA R R
Ordering Information
Accessories
Body
Part Number Application Inlet Connection Outlet Connection Material Adapter
7193L-10A Filling of Fork Lift Cylinders* ¼” M. NPT 1¼” F. ACME Brass 5760A
Lever Operated Hose End Adapter for Fork Lift Cylinder Filling
7193K-10B
Application
Designed to drastically reduce labor and time when continuously
UL®
10
O
check closes when disconnected, eliminating the need to close any
G
CT
RE
Y
NT
E
hose. The shut-off valve on the container must be closed after filling. Quick
Y
AR A
WA R R
⁄ ” NPT
14 Disconnect
Yoke
Because a leak-tight seal is formed before the checks close, product
loss is kept to an absolute minimum when connecting or disconnecting
the loading hose.
18 1⁄4”
Ordering Information Approx.
J16
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Combination Valve for Bulk Storage Containers
A2805C
Application
Designed for installation on bulk storage containers, this valve
combines a pressure gauge mounting and provision for a fixed tube
UL
®
The shut-off valve prevents the pressure gauge from being subjected
to constant pressure, thereby prolonging its life and accuracy. The PRODU
10
O
valve may be closed, and the vent valve opened to vent pressure
CT
RE
S
from the gauge to permit replacement.
10
Y
NT
E
Y
AR A
WA R R
For fixed liquid level gauging, the valve can be mounted at the
maximum permitted filling level. When equipped with a dip tube
threaded 1⁄8” [Link], it can be installed at any convenient level.
Materials A2805C
Ordering Information
J
Part Number Contianer Connection Service Connection Liquid Level Vent
A2805C ¾” M. NPT ¼” F. NPT for Gauge Mounting Knurled*
* Has 1⁄8” F. NPT opening for installing separate dip tube.
Application
Designed especially for use in liquid motor fuel lines to trap foreign
material which otherwise may damage precision components in the
LP-Gas carburetion system. These filters incorporate an integral
sintered metal filter element in a straight through design.
12802
PRODU
10
O
UL
G
CT
RE
®
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Inlet Connection Outlet Connection
12802 ¼” F. NPT ¼” M. NPT
J17
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Vent Valves 3165C, 3165S and TSS3169
Application
Especially designed to bleed off liquid or vapor pressures trapped
in transfer lines. When installed in the downstream boss of RegO®
globe and angle valves used at the end of a liquid transfer hose,
the bleeder valve allows for the controlled venting of the product
and indicates to the operator that the valves are closed and he can
disconnect the coupling. They may also be used as a fixed liquid level
gauge where the dip tube is part of the container.
3165C 3165S TSS3169
All these valves incorporate a No. 54 drill size orifice.
10
O
1 1⁄8”
G
CT
RE
Materials UL
S
1 1⁄8”
10
Y
NT
E
⁄”
34
Y
AR A
® WA R R
Ordering Information
Accessories
Part Number Service Connection Actuation Warning Plate Kit
3165C Knurled
LP-Gas Only
3165S ¼” M. NPT Slotted 2550-40P
TSS3169 LP-Gas & NH3 Tee Handle
10
O
UL 1 1⁄8”
G
CT
RE
®
10
Y
NT
E
Y
AR A
WA R R
⁄ ” NPT
14
1⁄4 ”
NPT
1⁄4 ”
NPT
v = 12”
v = 12”
v = 12”
3165SF12.0 TA3169F12.0
Ordering Information
Accessories
Part
Number Service Connection Actuation Dip Tube Length Warning Plate Kit
3165CF* *
Knurled
3165CF12.0 LP-Gas Only
¼” M. NPT 2550-40P
3165SF12.0 Slotted 12”
TA3169F12.0 LP-Gas & NH3 Tee Handle
J18
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Spanner Wrench for ACME Connectors
3195-50
Application
This aluminum spanner wrench is especially designed for use with
21⁄4” and 31⁄4” ACME couplings, adapters and caps.
PRODU
3195-50
10
O
UL
G
CT
RE
®
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number For Use With ACME Connector Size
3195-50 2¼” & 3¼”
Pressure Gauges
Application
Especially designed in a variety of sizes and construction for the LP-
Gas and anhydrous ammonia industry.
PRODU
10
O
G
CT
UL
RE
®
10
Y
NT
E
Y
AR A
WA R R
Ordering Information
Part Number Service Case Material Maximum Pressure Case Size Increment Divisions
2434A-2* 35” w.c. and 1” w.c. and
2½”
2434-2** Steel 20 oz. (Dual) 1 oz.
3226A-3
30 PSIG ½ PSI
2411
Brass
5575
60 PSIG 2” 1 PSI
5547 Steel
LP-Gas
5576 Brass
Only
1286 Steel 100 PSIG 2 PSI
1178 2½”
948 Brass
612** 300 PSIG 2” 5 PSI
948B Steel
1183 Brass 500 PSIG 20 PSI
A8060 60 PSIG
NH3 and 2½”
A8150 Steel 150 PSIG 5 lb.
LP-Gas
A8400 400 PSIG
* 1/4” Hose Connection
** 1/8” M. NPT Connection
J19
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Needle Valves 1224, 1316 and 1318
Application
These valves are high quality, “true’’ throttling valves. Unlike most
socalled needle valves, both the body seat and stem are tapered to
provide fine, precise control over a wide range of adjustment without UL
stem galling. ®
The 1316 and 1318 provide taper pipe thread by left hand hose
connection threads and are useful in a wide range of torch and fuel
burner applications where an accurate throttling action is required.
1224
PRODU
10
O C
G
CT
B
RE
A
S
10
Y
NT
E
Y
AR A
WA R R
Ordering Information D
10
O
Features
G
CT
RE
S
100-HGD
10
Y
• Available in attractive high impact plastic housing.
NT
E
Y
AR A
WA R R
• Early warning: a high pitched audio alarm and red light visual
alarm is activated when propane fumes reach a level of only ¼ the
danger level.
to ensure maximum sensitivity, reliability and accuracy. From Floor For Propane
• Supplied with CSA approved converter for use with standard 110 Typical
volt outlets. Installation
Converter PlugsPlugs
Converter Into
Unit Specifications Standardinto
110Standard
Volt Outlet
110 Volt Outlet
Height . . . . . . . . . . . . 3¾”
Width . . . . . . . . . . . . . 5¾”
Depth . . . . . . . . . . . . . 1⅜”
UL
®
Ordering Information
Part Number Description
100-HGD Household Propane Gas Alarm
J20
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
Cross Reference by Part Number
12802................................................................................................ J17 7193D-10.......................................................................................... J15
100-HGD........................................................................................... J20 7193K-10B........................................................................................ J16
1178.................................................................................................. J19 7193L-10A......................................................................................... J16
1183.................................................................................................. J19 7193T-10........................................................................................... J15
1286.................................................................................................. J19 7193U-10.......................................................................................... J15
1316WA............................................................................................. J20 7194-1............................................................................................... J13
2070CO............................................................................................... J6 7194H-3K.......................................................................................... J13
2071-L25.7.......................................................................................... J6 7194HD............................................................................................. J13
2071-L39.7.......................................................................................... J6 7194M-3K......................................................................................... J13
A2141A10.............................................................................................. J7 7194MD............................................................................................ J13
A2141A16.............................................................................................. J7 7605A-BT.......................................................................................... J12
A2141A6................................................................................................ J7 7605AP-15........................................................................................ J12
A2141A6L.............................................................................................. J7 7605AP-16........................................................................................ J12
A2141A8................................................................................................ J7 7605APN-8A..................................................................................... J12
A2141A8L.............................................................................................. J7 7605PN-50........................................................................................ J12
2411.................................................................................................. J19 7781AFPN-1..................................................................................... J12
2434-2............................................................................................... J19 A7794.................................................................................................. J14
2434A-2............................................................................................ J19 A7796.................................................................................................. J14
A2805C............................................................................................... J17 7901TB............................................................................................. J13
3165C............................................................................................... J18 A8060.................................................................................................. J19
3165CF.............................................................................................. J18 A8150.................................................................................................. J19
3165CF12.0...................................................................................... J18 A8400.................................................................................................. J19
3165S................................................................................................ J18 A9091-18L............................................................................................. J4
3165SF12.0...................................................................................... J18 A9091-18LX.......................................................................................... J4
TA3169F12.0.......................................................................................... J18 A9091-18N............................................................................................ J4
3195-50............................................................................................. J19 AA9091RM24.......................................................................................... J5
3226A-3............................................................................................ J19 9091RM24.......................................................................................... J5
5547.................................................................................................. J19 AA9092RM36........................................................................................... J5
5575.................................................................................................. J19 9092RM36.......................................................................................... J5
5576.................................................................................................. J19 AA9093RSM48......................................................................................... J5
6010...................................................................................................J11 9093RSM48........................................................................................ J5
AA6010....................................................................................................J11 AA9093TSM48......................................................................................... J5
6016.................................................................................................. J10 9093TSM48........................................................................................ J5
AA6016................................................................................................... J10 AA9094RSM60......................................................................................... J5
6016-60D.......................................................................................... J12 9094RSM60........................................................................................ J5
6024.................................................................................................. J10
AA6024................................................................................................... J10
AA9094TSM60......................................................................................... J5
9094TSM60........................................................................................ J5
J
612.................................................................................................... J19 AA9095RSM72......................................................................................... J5
7177.................................................................................................. J13 9095RSM72........................................................................................ J5
7188.................................................................................................. J13 AA9095TSM72......................................................................................... J5
7188-21............................................................................................. J13 9095TSM72........................................................................................ J5
7188HS............................................................................................. J13 948.................................................................................................... J19
7188MS............................................................................................. J13 948B.................................................................................................. J19
7193-4............................................................................................... J13 TSS3169................................................................................................ J18
7193D-10.......................................................................................... J13
J21
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
J
J22
Engineered Controls International, Inc.100 RegO Dr. P.O. Box 247 Elon, NC 27244 USA [Link] Phone (336) 449-7707 Fax (336) 449-6594
[Link]
Catalog L-500
100 RegO Drive PO Box 247 Elon, NC 27244 USA Telephone (336) 449-7707 Fax (336) 449-6594