Bedroom Electrical Layout Plan

1. The electrical works shall be done according to the Philippine Electrical Code and local laws and requirements. 2. Electrical power supply to the building should be single phase, 230 volts, 60 hertz, 3-wire alternating current. 3. The diagram shows the electrical layout including outlets, lights, and circuit numbers.

Uploaded by

Jenna Liza Layno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
92 views1 page

Bedroom Electrical Layout Plan

1. The electrical works shall be done according to the Philippine Electrical Code and local laws and requirements. 2. Electrical power supply to the building should be single phase, 230 volts, 60 hertz, 3-wire alternating current. 3. The diagram shows the electrical layout including outlets, lights, and circuit numbers.

Uploaded by

Jenna Liza Layno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ELECTRICAL NOTES

L E G E N D 1. THE ELECTRICAL WORKS HEREIN SHALL BE DONE IN


A R ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION
PINLIGHT PINLIGHT
OF THE PHILIPPINEELECTRICAL CODE, THE LAWS AND
M E T E R B A S E ORDINANCES OF THE LOCAL CODE , ENFORCING AUTHORITIES

S1 D
M M MO
N AND THE REQUIREMENTS OF THE LOCAL UTILITY COMPANY.
PINLIGHT PINLIGHT
S2 MF O

S1 O
S1 N
CL CL RH
F
D
N 6 2. ELECTRICAL POWER SUPPLY TO THE BUILDING SHOULD BE
CL N CKT DUPLEX CONVENIENCE OUTLET
CL CL
CL
( W I D E S E R I E S T Y P E ) SINGLE PHASE, 230VOLTS, 60 HERTZ, 3-WIRE ALTERNATIVE
2 H REF 5
CKT CKT 7 CURRENT.
M M PINLIGHT
Y Y CKT

PINLIGHT 3 PINLIGHT
3. ONLY ONE SERVICE DROP SHALL SERVE THE BUILDING.
LP PINLIGHT PINLIGHT
S2 AB LP WP
S1 E

E
CKT 4. WIRING INSTALLATION SHALL BE DONE IN THE FOLLOWING:
B S2 NG S3 YXR LOAD PANEL / PANEL BOARD
CL
PINLIGHT
G LP-
1 P P A. RIGID STEEL CONDUIT (RSC) POWER SERVICE ENTRANCE.
CKT
PINLIGHT
X TV TV
PINLIGHT PINLIGHT
N B. POLYVINYL CHLOURIDE PIPE (PVC)FOR BRANCH CIRCUIT
R H CL
8 RACEWAY AND ALL AUXILLARY SYSTEM LAYOUT.
CL
PINLIGHT CKT C I R C U I T H O M E R U N
CL
S1 R
Q 5. UNLESS OTHERWISE SPECIFIED IN THE PLAN, MINIMUM SIZE OF
S1H

S3WAY W
CL
S3 PCV Y Y V
#14 / OR 2.0 MM² THHN STRANDED CONDUCTORS SHALL BE 2.0 MM ² THHN STRANDED WIRE, 600
PINLIGHT
S3WAY W

W
PINLIGHT PINLIGHT 4 ACU WIRE CONVENIENCE OUTLET LINE VOLTS AND 20 MM Ø PVC CONDUITS.
S3 QPN

CKT
W CONCRETE CANOPY CONCRETE CANOPY
6. ALL MATERIAL S TO BE USED SHALL BE NEW AND APPROVED
S2 AB

P
CL
P P WP
P
UP

UP
CL

PINLIGHT PINLIGHT
PINLIGHT PINLIGHT TYPE FOR THE LOCATION AND PURPOSE INTENDED.
1-GANG REFRIGERATOR OUTLET 7. ALL CONDUIT PIPES SHALL BE CONCEALED UNLESS
A A
SUPL SUPL

C CONCRETE CANOPY CONCRETE CANOPY REF SPECIFICALL SHOWN AND NOTED OTHERWISE, EXPOSED
WML WML
B B WP
PINLIGHT CONDUIT RUNS SHALL BE INSTALLED PARALLEL OR
PERPENDICULAR WITH THE BUILDING LINE SUPPORTED BY
EITHER RANGE OR INDUCTION
CONDUIT CLAMPS EVERY 1000 MM.
R O U T L E T
8. PROVIDE GALVANIZE PULLING WIRE , GA. 16 FOR ALL EMPTY
SECOND FLOOR LIGHTING SECOND FLOOR CONVENIENCE CONDUITS.
9. PULL BOXES / SPLICE BOXES SHALL BE PROVIDED WHENEVER
O U T L E T L A Y - O U T O U T L E T L A Y - O U T WP
WEATHER PROOFED OUTLET
NECESSARYTO FACILITATE WIRING / PULLING EVEN IF THESE
SCALE 1:100 MTRS SCALE 1:100 MTRS
ARE NOT INDICATED ON THE PLANS.
10. ALL LIGHTING CONVINIENCE OUTLET CIRCUITS SHALL BE
L I G H T I N G O U T L E T
3-WIRE, 3.5MM² THHN AND 2.0MM² THHN FOR GROUNDING,
( P I N L I G H T )
2-14MM² THHN PL UNLESS OTHERWISE SPECIFIED ON THE PLANS.
1-8.0MM² THHN 11. ALL DUPLEX RECEPTACLE OUTLETS SHALL BE GROUNDING
25MMØ PVC TYPE WITH PARALLEL SLOTS, AND RATED 15A, 230 VOLTS.
E M E R G E N C Y L I G H T
METER BASE METER BASE 12 PROVIDE GROUND FAULT CIRCUIT INTERRUPTER
SERVICE ENTRANCE EL RECEPTACLES FOR OUTLET LOAD MARKED "GFCI" ON THE
220 VOLTS, 1-PHASE PLANS.
3-WIRE, 60 Hz GROUND FLOOR CONVENIENCE S1 1 - G A N G S W I T C H
13. LIGHT CONTROL WALL SWITCHES SHALL BE RATED 15A, 230
2 - G A N G S W I T C H VOLTS AC.
O U T L E T L A Y - O U T S2
14 ULESS OTHERWISE NOTED, MOUNTING HEIGHT FOR THE
GROUND FLOOR LIGHTING SCALE 1:100 MTRS
S3 3 - G A N G S W I T C H FOLLOWING DEVICES SHALL BE:
60 AT, 2P
O U T L E T L A Y - O U T S3WAY 3 W A Y S W I T C H
A. LIGHT CONTROL WALL SWITCHES.......................1400MM
SCALE 1:100 MTRS
15AT 15AT ABOVE FFL @ CENTER
TV C A B L E / T V
B. CONVINIENCE OUTLET........................................300MM ABOVE
LO 1 2 LO
2-14MM² THHN 15AT 20AT FFL. @ CENTER
1-8.0MM² THHN E X H A U S T F A N C. TELEPHONE OUTLET...........................................300MM ABOVE
LO 3 4 CO EF FFL. @ CENTER
25MMØ PVC 30AT 40AT
CENTER LAMP OUTLET D. CATV OUTLET.....................................................300MM ABOVE
MICROWAVE FFL. @ CENTER
REF 5 6 OVEN (EITHER DROP, PENDANT LAMP
M 20AT 20AT OR ROUND SURFACE TYPE E. INTERCOM OUTLET..............................................EQUIRED BY
60 AT, 2P CL L A M P ) FIELD CONDITIONS
N E M A 3 R C.O. 7 8 C.O. G. PANEL BOARD ..................................................REQUIRED BY
30AT 40AT AIR-CONDITIONING UNIT OULET FIELD CONDITIONS
EN CLOSU RE
ACU 1.5Hp ACU H. MANUAL STATION..............................................1400MM ABOVE
9 10 SPARE
30AT 30AT FFL. @ CENTER
I. BELL / BUZZER.................................................150MM BELOW
2-14MM² THHN SPARE 11 12 SPARE SURFACE TYPE PINLIGHT CEILING LINE
1-8.0MM² THHN SUPL J. KILLOWATT HOUR METER.................................. 1500MM TO
30AT
25MMØ PVC 1800 MM ABOVE FFL. @ CENTER.
DROP / PENDANT LAMP
GROUND DL 15. ALL ELECTRICAL EQUIPMENT S/ DEVICES SHALL BE
PROPERLY GROUNDED AND BOUNDED .
16. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE
SINGLE LINE DIAGRAM
NOT TO SCALE DIRECT SUPERVISION OF A DULY REGISTERED ELECTRICAL
ENGINEER OR PROFESSIONAL ELECTRICAL ENGINEER.

DRIP LOOP ( 24" )

THREADABLE RIGID
METAL CONDUIT(RMC)
NO ADAPTOR MUST BE THREADED
METER BASE
( NO MOUNTING BOARD AT THE BACK)
GROUNDING ON METER BASE

SAFETY SWITCH
.\2 STOREY SITE LOCATION ON GOOGLE.jpg

GROUNDING WIRE

20 %OF THE HEIGHT OF THE POLE

GROUNDING ROD ( HOT DIP GALVANIZED


STEEL ROD WITH MINIMUM DIMENSION
5
OF 8"Ø X 8 FEET LENGTH)

METER POST DETAIL


NOT TO SCALE
L O C A T I O N
NOT TO
M A P SCALE

LOGO ELECTRICAL ENGINEER PROJECT TITLE BUILDING OWNER NO R E V I S I O N S DATE SHEET CONTENTS SHEET NUMBER
LIGHTING OUTLET LAY-OU

ENGR. JENNA LIZA M. LAYNO P R O P O S E D O F T W O - S T O R E Y CONVENIENCE OUTLET LAY-OUT P-01


R E S I D E N T I A L B U I L D I N G MR. EDUARD JOSEPH M. DELA CRUZ SCHEDULE OF LOAD
PANEL BOARD ARRANGEMENT
LOCATION OF CONSTRUCTION PAGE
PRC: 14451 ADDRESS VICINITY MAP
PTR. 0000000 SINGLE LINE DIAGRAM
DATE : 01 - 03 - 24 A. H.BANZON ST., BALANGA CITY, BATAAN CATANING, BALANGA CITY, BATAAN LEGEND 01
PLACE: BALANGA CITY, BATAAN ELECTRICAL NOTES