Basic Electrical Engineering Units Guide
Basic Electrical Engineering Units Guide
ENGINEERING
PREPARED BY –
Introduction
1.1 SI Units
The system of units used in engineering and science is the
International System of units, usually abbreviated to SI units, and is based
on the metric system. This was introduced in 1960 and is now adopted by
the majority of countries as the official system of measurement.
The basic units in the SI system are listed with their symbols, in Table 1.1.
Table 1.1.
Quantity Unit
length metre, m
mass kilogram, kg
time second, s
electric current ampere, A
thermodynamic kelvin, K
temperature
luminous intensity candela, cd
amount of substance mole, mol
Derived SI units use combinations of basic units and there are many of
them. Two examples are:
1
SI units may be made larger or smaller by using prefixes which denote
multiplication or division by a particular amount. The six most common
multiplier, with their meaning, are listed in Table 1.2.
Table 1.2.
Prefix Name Meaning
M mega multiply by 1 000 000 x 106
k kilo multiply by 1000 x 103
m milli divide by 1 000 x 10-3
µ micro divide by 1 000 000 x 10-6
n nano divide by 1 000 00 0000 x 10-9
p pico divide by 1000 000 000 000 x 10-12
1.2 Charge
The unit of charge is coulomb (C) where one coulomb is one ampere
second. (1 coulomb = 6.24 x 10 18 electrons). The coulomb is defined as the
quantity of electricity which flows past a given point in an electric circuit
when a current of one ampere is maintained for one second. Thus,
Charge, Q = I t coulombs
where I is the current in amperes and t is the time in seconds.
1.3 Force
The unit of force is Newton (N) where one Newton is one kilogram metre
per second squared. The Newton is defined as the force which, when
applied to a mass of one kilogram, gives it an acceleration of one metre per
second squared. Thus,
Force, F = ma Newton
where m is the mass in kilograms and a is the acceleration in metres per
second squared. Gravitational force, or weight, is mg, where g = 9.81 m/s2
2
1.4 Work
The unit of work or energy is joule (J) where one joule is one Newton
metre. The joule is defined as the work done or energy transferred when a
force of one Newton is exerted through a distance of one metre in the
direction of the force. Thus
1.5 Power
The unit of power is watt (W) where one watt is one joule per second.
Power is defined as the rate of doing work or transferring energy. Thus,
W
Power, P watts
t
where W is the work done or energy transferred in joules and t is the time
in seconds. Thus
Energy, W Pt joules
1.6 Electrical potential and e.m.f.
The unit of electric potential is volt (V) where one volt is one joule
per coulomb. One volt is defined as the difference in potential between two
points in a conductor which, when carrying a current of one ampere,
dissipates a power of one watt, i.e.
3
1.7 Resistance and conductance
The unit of electric resistance is ohm (Ω) where one ohm is one volt
per ampere. It is defined as the resistance between two points in a
conductor when a constant electric potential of one volt applied at the two
points produces a current flow of one ampere in the conductor. Thus,
V
Resistance R ohms
I
where V is the potential difference across the two points in volts and I is
the current flowing between the two points in amperes.
The reciprocal of resistance is called conductance and is measured
in siemens (S) or Mho ( ). Thus,
1
Conductance, G Siemen
R
where R is the resistance in ohms.
Power, P = V I watts
Electrical energy = Power x time = VIt Joules
Although the unit of energy is joule, when dealing with large amounts of
energy, the unit used is the kilowatt hour (kWh) where
1 kWh = 1000 watt hour
= 1000 x 3600 watt seconds or joules
= 3 600 000 J
4
Table 1.3 Summary of terms, units and their symbols
Quantity Quantity Unit Unit
Symbol symbol
Length l metre m
Mass m kilogram kg
Time t second S
Velocity v metres per second m/s or m
s-1
Acceleration a metres per second m/s2 or m
squared s-2
Force F Newton N
Electrical charge Q coulomb C
Electric current I ampere A
Resistance R ohm Ω
Conductance G Siemen S
Electromotive force E volt V
Potential difference V volt V
Work W joule J
Energy E (or W) joule J
Power P watt W
Solved examples
Problem 1.
If a current of 5 A flows for 2 minutes, find the quantity of electricity
transferred.
Solution:
Quantity of electricity Q = I t coulombs
I=5A
t = 2 x 60 = 120 s
Q = 5 x 120 = 600 C
5
Problem 2.
A mass of 5000 g is accelerated at 2 m/s2 by a force. Determine the force
needed.
Solution:
Mass = 5000 g = 5 kg
Force = mass x acceleration
= 5 kg x 2 m/s2 = 10 kg m/s2 = 10 N
Problem 3.
Find the force acting vertically downwards on a mass of 200 g attached to a
wire.
Solution:
Mass = 200 g = 0.2 kg
Acceleration due to gravity, g = 9.81 m/s2
Force acting downwards = weight = mass x acceleration
=0.2 kg x 9.81 m/s2
=1.962 N
Problem 4.
A portable machine requires a force of 200 N to move it. How much work is
done if the machine is moved 20 m and what average power is utilized if the
movement takes 25 s?
Solution:
Force = 200 N
Distance = 20 m
Time taken = 25 s
Work done = force x distance
= 200 N x 20 m
= 4000 Nm or 4 kJ
6
Power = work done/time taken
= 4000 J/ 25 s
= 160 J/s = 160 W
Problem 5.
A mass of 1000 kg is raised through a height of 10 m in 20 s. What is (a) the
work done and (b) the power developed?
Solution:
Mass = 100 kg
Distance = 10 m
Time taken = 20 s
Acceleration due to gravity, g = 9.81 m/s2
(a) Work done = force x distance
Force = mass x acceleration
Work done = (1000 kg x 9.81 m/s2) x 10 m
= 98 100 Nm = 98.1 kNm or 98.1 kJ
work done
(b) Power =
time taken = 98100 J/20 s
= 4905 J/s = 4905 W or 4.905 kW
Problem 6.
Find the conductance of a conductor having a resistance of (a) 10 Ω, (b) 5
kΩ
Solution:
1
(a) Conductance G =
R
= 1/10 Siemen = 0.1 S
1
(b) Conductance G =
R
= 1/ (5 x 103) S = 0.2 x 10-3 S = 0.2 mS
7
Problem 7.
A source e.m.f. of 5 V supplies a current of 3 A for 10 minutes. How much
energy is delivered in this time?
Solution:
Voltage = 5 V
Current = 3 A
time = 10 m =10 x 60 s
Energy = power x time
Power = voltage x current.
Energy = V I t = 5 x 3 x (10 x 60)
= 9000 Ws or J= 9 kJ
EXERCISES
1. What force is required to give a mass of 20 kg an acceleration of 30
m/s2? [600 N]
2. Find the accelerating force when a car having a mass of 1.7 Mg
increases its speed with a constant acceleration of 3 m/s2 [5.1 kN]
3. A force of 40 N accelerates a mass at 5 m/s2. Determine the mass.
[8 kg]
4.. Determine the force acting downwards on a mass of 1500 g
suspended on a string. [14.72 N]
5. A force of 4 N moves an object 200 cm in the direction of the force.
What amount of work is done? [8 J]
6. A force of 2.5 kN is required to lift a load. How much work is done if
the load is lifted through 500 cm? [12.5 kJ]
7. An electromagnet exerts a force of 12 N and moves a soft iron
armature through a distance of 1.5 cm in 40 ms. Find the power
consumed. [4.5 W]
8. A mass of 500 kg is raised to a height of 6 m in 30 s. Find (a) the
work done and (b) the power developed. [(a) 29.43 kNm (b) 981 W]
9. In what time would a current of 1 A transfer a charge of 30 C? [30 s]
8
10. A current of 3 A flows for 5 minutes. What charge is transferred?
[900 C]
11. How long must a current of 0.1 A flow so as to transfer a charge of 30
C? [5 minutes]
12. Find the conductance of a resistor of resistance (a) 10Ώ (b) 2 kΏ (c) 2
mΏ [(a) 0.1 S (b) 0.5 mS (c) 500 S]
13. A conductor has a conductance of 50 µS. What is its resistance? [20
kΏ]
14. An e.m.f. of 250 V is connected across a resistance and the current
flowing through the resistance is 4 A. What is the power developed?
[1 kW]
15. 450 J of energy are converted into heat in 1 minute. What power is
dissipated? [7.5 W]
16. A current of 10 A flows through a conductor and 10 W is dissipated.
What p.d. exists across the ends of the conductor? [1 V]
17. A battery of e.m.f. 12 V supplies a current of 5 A for 2 minutes. How
much energy is supplied in this time? [7.2 kJ]
18. A dc electric motor consumes 36 MJ when connected to a 250 V
supply for 1 hour. Find the power rating of the motor and the current
taken from the supply. [10 kW, 40 A]
9
2 ELECTRIC CIRCUIT FUNDAMENTALS
Introduction
10
All atoms are bound together by powerful forces of attraction
existing between the nucleus and its electrons. Electrons in the outer shell
of an atom, however, are attracted to their nucleus less powerfully than are
electrons whose shells are nearer the nucleus.
It is possible for an atom to lose an electron; the atom, which is now
called an ion, is not now electrically balanced, but is positively charged and
is thus able to attract an electron to itself from another atom. Electrons that
move from one atom to another are called free electrons and such random
motion can continue indefinitely. However, if an electric pressure or
voltage is applied across any material there is a tendency for electrons to
move in a particular direction. This movement of free electrons, known as
drift, constitutes an electric current flow. Thus current is the rate of
movement of charge.
Conductors are materials that contain electrons that are loosely
connected to the nucleus and can easily move through the material from
one atom to another.
Insulators are materials whose electrons are held firmly to their
nucleus.
11
mobility of electrons within a material is known as electric conductivity.
Conductivity is determined by the types of atoms in a material (the number
of protons in each atom's nucleus, determining its chemical identity) and
how the atoms are linked together with one another. Materials with high
electron mobility (many free electrons) are called conductors, while
materials with low electron mobility (few or no free electrons) are called
insulators.
Here are a few common examples of conductors and insulators:
Conductors: silver, copper, gold, aluminum, iron steel, brass,
bronze, mercury, graphite, dirty water, concrete
Insulators: glass, rubber, oil, asphalt, porcelain, ceramic, quartz,
(dry) cotton, (dry) paper, (dry) wood, plastic, air,
diamond, pure water
12
2.5 Ohm’s law
Ohm’s law states that the applied voltage V across a circuit is
directly proportional to the current flowing I in the circuit provided the
temperature remains constant. Thus,
VI
V IR
where R is the constant of proportionality called resistance
V
I V
R or R
I
13
l
R
a
Where , - resistivity, in ohm-meters (Ω-m)
l - length, in meters (m)
a - cross-sectional area, in square meters (m2).
In the above equation the rho ( ) is the constant of proportionality
and is called the resistivity of the material. Resistivity is a physical property
of a material and is measured in ohm-meters (Ω-m) in the SI system.
change in current di
dt
Mathematically
di
V dt
di
L dt
14
The proportionality constant L is called the Inductance of the inductor. The
unit of Inductance is Henry [H].
15
W
P
t
Where P is power in watts, W is energy in joules and t is time in seconds
W W Q
P VI
t Q t
Power P in an electrical circuit is given by the product of potential
difference V and current I. The unit of power is the watt, W. Hence,
From Ohm’s law, V IR
P (IR) I
i.e. P I 2 watts
R P
Also, from Ohm’s I
law, V
P
PV
V
2
i.e. V
I watts
R
There are thus three possible formulae which may be used for calculating
Power can be measured using a device called a wattmeter.
16
Some practical applications of the effects of an electric current include:
17
Magnetic effect: bells, relays, motors, generators, transformers,
telephones, car-ignition and lifting magnets
Chemical effect: primary and secondary cells and electroplating
Heating effect: cookers, water heaters, electric fires, irons, furnaces, kettles
and soldering irons
2.10 Fuses
A fuse is used to prevent overloading of electrical circuits. The fuse,
which is made of material having a low melting point, utilizes the heating
effect of an electric current. A fuse is placed in an electrical circuit and if
the current becomes too large the fuse wire melts and so breaks the circuit.
Solved problems
Problem 1.
What current must flow if 0.24 coulombs is to be transferred in 15 ms?
Problem 2.
If a current of 10 A flows for four minutes, find the quantity of electricity
transferred.
Problem 3.
The current flowing through a resistor is 0.8 A when a p.d. of 20 V is
applied. Determine the value of the resistance.
V 200
From Ohm’s law, resistance R 20 25
I 0.8 8
18
Problem 4.
Determine the p.d. which must be applied to a 2 kΩ resistor in order that a
current of 10 mA flow through it.
Problem 5.
A coil has a current of 50 mA flowing through it when the applied voltage is
12 V. What is the resistance of the coil?
Resistance, V 12 103
R 12 12000 240
I 50 103 50 50
Problem 6.
A 100 V battery is connected across a resistor and causes a current of 5
mA to flow. Determine the resistance of the resistor. If the voltage is
reduced to 25 V, what will be the new value of the current flowing?
V 100 103
Resistance, R 100 20 103 20 k
I 5 103 5
Current when voltage is reduced to 25 V
V 25
I 25 103 1.25mA
R 20 10 3
20
Problem 7.
What is the resistance of a coil which draws a current of (a) 50 mA and (b)
200 µA from a 120 V supply?
a) Resistance R V 120
I 50 103
12000
120 2400 or 2.4k
0.05 5
19
b) Resistance 120 120
R 200 106 0.0002
1200000
600000 or 600k or 0.6M
2
Problem 8.
A 100 W electric light bulb is connected to a 250 V supply. Determine (a)
the current flowing in the bulb, and (b) the resistance of the bulb.
P
Power P = V I, from which, I
current V
a) Current 100 10 2
I 0.4 A
250 25 5
b) Resistance V
R 250 2500
I 0.4 4 625
Problem 9.
Calculate the power dissipated when a current of 4 mA flows through a
resistance of 5 kΩ
Power P I 2 R (4 103 )2 (5 103 )
16 106 5 103 80 103
= 0.08W or 80mV
Problem 10.
An electric kettle has a resistance of 30 Ω. What current will flow when it is
connected to a 240 V supply? Find also the power rating of the kettle.
V 240
Current, I 8A
R 30
Power, P VI 240 8 1920W 1.92kW
20
= power rating of kettle
21
Problem 11.
A current of 5 A flows in the winding of an electric motor, the resistance of
the winding is 100 Ω. Determine (a) the p.d. across the winding, and (b) the
power dissipated by the coil.
Problem 12.
The hot resistance of a 240 V filament lamp is 960 Ω. Find the current taken
by the lamp and its power rating.
V 240 24 1
From Ohm’s law, I A or 0.25A
current
R 960 96 4
Power rating 1
P VI (240) 60 W
4
Problem 13.
A 12 V battery is connected across a load having a resistance of 40 Ω.
Determine the current flowing in the load, the power consumed and the
energy dissipated in 2 minutes.
V 12
Current I 0.3A
R 40
Power consumed, P VI (12)(0.3) 3.6W
Energy dissipated = power time = (3.6W)(2 60 s) = 432 J
(since 1 J = 1 Ws)
Problem 14.
A source of e.m.f. of 15 V supplies a current of 2 A for six minutes. How
much energy is provided in this time?
22
Energy = power time and power = voltage current
Hence energy = VIt = 15 2 (6 60) = 10800 W or J = 10.8kJ
Problem 15.
An Electrical equipment in an office takes a current of 13 A from a 240 V
supply. Estimate the cost of electricity per week if the equipment is used
for 30 hours each week and 1 kWh of energy costs 7p
Problem 17.
Determine the power dissipated by the element of an electric fire of
resistance 20 when a current of 10 A flows through it. If the fire is on for 6
hours determine the energy used and the cost if 1 unit of electricity costs
7p.
Problem 18.
An office uses two 3 kW heater for an average of 20 hours each per week,
and six 150 W lights for 30 hours each per week. If the cost of electricity is
7p per unit, determine the weekly cost of electricity to the business.
Problem 19.
If 5 A, 10 A and 13 A fuses are available, state which is most appropriate for
the following appliances which are both connected to a 240 V supply (a)
Electric toaster having a power rating of 1 kW (b) Electric fire having a
power rating of 3 kW
24
EXERCISES
1. The current flowing through a heating element is 5 A when a p.d. of
35 V is applied across it. Find the resistance of the element. [7 ]
2. A 60 W electric light bulb is connected to a 240 V supply. Determine
(a) the current flowing in the bulb and (b) the resistance of the bulb.
[(a) 0.25 A (b) 960 Ω ]
4. The hot resistance of a 250 V filament lamp is 625Ω . Determine the
current taken by the lamp and its power rating. [0.4 A, 100 W]
5. Determine the resistance of a coil connected to a 150 V supply when
a current of (a) 75 mA (b) 300 µA flows through it. [(a) 2 k (b) 0.5 M]
6. Determine the resistance of an electric fire which takes a current of
12 A from a 240 V supply. Find also the power rating of the fire and
the energy used in 20 h. [20Ω , 2.88 kW, 57.6 kWh]
7. Determine the power dissipated when a current of 10 mA flows
through an appliance having a resistance of 8 k. [0.8 W]
8. 85.5 J of energy are converted into heat in nine seconds. What power
is dissipated? [9.5 W]
9. A current of 4 A flows through a conductor and 10 W is dissipated.
What p.d. exists across the ends of the conductor? [2.5 V]
10. Find the power dissipated when:
(a) a current of 5 mA flows through a resistance of 20 kΩ
(b) a voltage of 400 V is applied across a 120 kΩ resistor
(c) a voltage applied to a resistor is 10 kV and the current flow is 4
mA. [(a) 0.5 W (b) 113 W (c) 40 W]
10. A battery of e.m.f. 15 V supplies a current of 2 A for 5 min. How much
energy is supplied in this time? [9 kJ]
11. In a household during a particular week three 2 kW fires are used on
average 25 h each and eight 100 W light bulbs are used on average
35 h each. Determine the cost of electricity for the week if 1 unit of
electricity costs 7p. [Rs 12.46]
25
3 DC CIRCUITS
Introduction
This chapter introduces Kirchoff’s laws, resistances in series, parallel
reduction as well as star to delta and delta to star conversion. In addition to this,
independent and dependent voltage and current sources are analyzed with the
source transformation. Several typical problems related to Kirchoff’s laws are
solved in a simple manner.
Branch
A part of the network which connects the various points of the network
with one another is called a branch. A branch may contain one or more elements.
In the fig 3.3. AB, BC, BE and CF are the various branches
Figure 3.3
Junction point
1. Active or passive
2. Unilateral or bilateral
3. Linear or nonlinear
4. Lumped or distributed
3.3.1 Active and passive elements
Active element
The first one is called Kirchhoff’s current law, KCL and the second one is
Kirchhoff’s voltage law, KVL.
Kirchhoff’s currents law states that the algebraic sum of element current
meeting at a junction is zero.
Consider a junction P wherein four elements, carrying currents I1, I2, I3 and I4, are
meeting as shown in Fig. 3.4.
Figure 3.4 Currents meeting at a junction
Note that currents I1 and I4 are flowing out from the junction while the currents I2
and I3 are flowing into the junction. According to KCL,
I1 – I2 - I3 + I4 = 0
I1 + I4 = I2 + I3
KCL can also be stated as at a junction, the sum of element currents that
flows out is equal to the sum of element currents that flows in.
Kirchhoff’s voltage law states that the algebraic sum of element voltages
around a closed loop is zero.
Consider a closed loop in a circuit wherein four elements with voltages V1, V2, V3
and V4, are present as shown in Fig. 3.5
Assigning positive sign for voltage drop and negative sign for voltage rise, when
the loop is traced in clockwise direction, according to KVL
V1 - V2 - V3 + V4 = 0
V1 + V4 = V2 + V3
KVL can also be stated as, in a closed loop, the sum of voltage drops is
equal to the sum of voltage rises in that loop.
Two resistors are said to be connected in series when there is only one
common point between them and no other element is connected in that common
point. Resistors connected in series carry same current. Consider three resisters
R1, R2 and R3 connected in series as shown in Fig. 3.6. With the supply voltage of
E, voltages across the three resistors are V1, V2 and V3.
V1 = R1 I; V2 = R2 I ; V3 = R3 I
Applying KVL,
E = V1 + V2 + V3
= (R1 + R2 + R3) I = Re q I
E = Re q I
where E is the circuit voltage, I is the circuit current and Req is the equivalent
resistance. Here
Re q = R1 + R2 + R3
This is true when two are more resistors are connected in series. When n
numbers of resistors are connected in series, the equivalent resistance is given
by
Re q = R1 + R2 +.................+ Rn
V1 = R1 I ; V2 = R2 I
Total voltage of E is dropped in two resistors. Voltage across the resistors are
given by
R1
V1 = E and
R1 R
2
V2 = R2 E
R1 R 2
Two resistors are said to be connected in parallel when both are connected
across same pair of nodes. Voltages across resistors connected in parallel will be
equal. Consider two resistors R1 and R2 connected in parallel as shown in Fig.
3.8.
Figure 3.8 Resistors in parallel
I1 = E E
; I=
R1 2
R
2
where E is the circuit voltage, I is the circuit current and Re q is the equivalent
resistance. Here
1
1 1
Re q R R
1 2
1 R1 R 2
From the
above Re q R1 R 2
Thus , R1 R 2
Re q
R1 R 2
Referring to Fig. 3.8, it is noticed the total current gets divided as I1 and I2. The
branch currents are obtained as follows.
R1 R 2
E = I
R1 R 2
R2
I1 = I
R1 R 2
R1
I2 = I
R1 R 2
The circuits elements may be connected in star (Y) or Delta () connection.
In star connection, one end of the three elements are connected at one common
point. In delta connection, two ends of each element are connected to other two
elements.
Consider the star circuit (fig. 3.9 (a)). Circuit is not connected to any other
circuit. All the terminals are open.
Resistance between
terminals AB, R || (R R ) R1 (R2 R3 )
R
AB 3 2 3
R1 R2 R3
Resistance between
terminals
BC, R || (R R ) R3 (R1 R2 )
R
BC 3 1 2
R1 R2 R3
Resistance between terminals CA,
R R || (R R ) R2 (R1 R3 ) (ii)
CA 2 1 3
R1 R2 R3
Figure 3.9
R R R1 (R2 R3 ) R1 R2 R1 R3 (a)
R R R3 R1 R2 R3
A B
12
R R
R3 (R1 R2 ) R1 R3 R2 R3 (b)
R R R3 R1 R2 R3
B C
12
R R
R2 (R1 R3 ) R1 R2 R2 R3 (c)
R R R3 R1 R2 R3
C A
12
R R
R1 R2 R2 (d)
R
3
R R R3
A C
12
R1 R2 R1 R3 R1 R2 R2 R3
2R A R1 R2 R3
2R1 R2
R R R
1 2 3
R1 R2 (e)
R A
R1 R2 R3
Similarly,
R R1 R3 (f)
B
R1 R2 R3
R2 R3 (g)
R
C
R1 R2 R3
R1 (R1 R2 R3 )
= R1
(R1 R2 R3 )
Similarly,
RA RB RB RC RC R A
R2
RB
RA RB RB RC RC R A
R3
RA
Star (Y) to Delta ()
Figure 3.10
Where Ra Rb Rb Rc Rc Ra
R1
Rc
Ra Rb Rb Rc Rc Ra
R2
Rb
Ra Rb Rb Rc Rc Ra
R3
Ra
Figure 3.11
Where
R1 R2
R a
R1 R2 R3
R1 R3
R b
R1 R2 R3
R2 R3
R c
R1 R2 R3
Figure 3.12
Dependent voltage source
Controlled sources are very much useful in electronic circuits and
networks. There are two types of voltage controlled sources.
1. Voltage controlled voltage source (VCVS)
2. Current controlled voltage source (CCVS)
Voltage controlled voltage source (VCVS)
The output voltage across the interested component depends on some
other input voltage source.
Current controlled voltage source (CCVS)
The output voltage across the interested component depends on some
other input current source.
3.10.2 Current source
Independent current source
A current source has a specified value of current through it, independent of
the voltage appearing across it. Such a current source is designated as an
independent current source.
Fig 3.14 (a) A practical voltage source (b) A practical current source
Let us consider both sources are delivering same amount of current to the load
resistor RL.
Fig 3.14
I L VS
(1)
RX RL
Ry
I L IS (2)
Ry RL
Fig 3.14
If Rx = Ry = R
VS = ISR (or) IS VS
=
R
Fig 3.15(b)
The above circuit is having short circuited load terminals. Short circuited
line is having negligible resistance. Hence voltage drop across short circuited
output terminals is also negligible. Current through short circuited terminals is
same as that of I2. i.e I = I2.
Let consider the circuit given in fig 3.15 (c)
In the above circuit, the current is delivered by the voltage source Vin.
When current reaches the node ‘a’, it will follow the short circuited line since
short circuited line is having negligible resistance. No current will flow through
RL. So the circuit present after the short circuit will be omitted for analysis.
Consider the circuit given in fig 3.16 (a). Let us find the current in each
loop using mesh method.
(i) The given circuit consist of three individual loops, since it does not
have any crossovers
(ii) Current direction is marked in each loop.
First loop:
E1 11 R1 R4 (I1 I 2 )
Note: While writing loop equation for the first loop, go along the
direction of I1. If any current comes opposite to I1, take it as negative.
Hence the current in R4 is (I1-I2) with respect to first loop.
Second loop:
There is no voltage source in the second loop. Therefore the potential
rise in the second loop is zero.
0 I 2 R2 R5 (I 2 I 3 ) R4 (I 2 I1 )
0 I2 R4 (R2 R4 R5 ) I2 R5 (2)
I3
Note: While writing loop equation for second loop, go along the
direction of I2. If any current comes opposite to I2, take it as negative. If
any current flows in the same direction of I 2 then take it as positive.
Hence current through R5 is (I2+I3) and current through R4 is (I2+I1)
Third loop:
E2 13 R3 R5 (I 2 I 3 )
Note: While writing loop equation for third loop, go along the direction
of I3. If any current comes opposite to I3, take it as negative. If current
flows in the same direction I3, take it as positive. The current through R5
is (I2+I3) with respect to third loop.
R1 R4 R4 0
R R R R R
4 2 4 5 5
0 R5 R3 R5
E1 R4 0
0 R R R R
1
2 4 5 5
E 2 R5 R3 R5
R1 R4 E1 0
2 R4 0 R5
0 E2 R3 R5
R1 R4 R4 E1
3 R4 R2 R4 R
0
5
0 R5 E2
Steps
(i) Mark the nodes. Take one of the nodes as reference node. Assume the
voltages of other nodes as V1, V2, V3, ….etc. Also mark the current
directions in all the branches and name the currents as I1, I2 . . . etc.
Fig 3.17 (b)
(ii) At each node, write Kirchoff’s current law equations. The circuit
contains three nodes including the reference node (i.e. N = 3)
N – 1 = 3 – 1 = 2 equations have to be written
At node 1, by Kirchoff’s current law
I1 = I2 + I4
E1 V1 V1 V2 V1 0
R1 R2 R4
E1 V1 V1 V2 V1
R1 R1 R2 R2 R4
E1 V1 V1 V1 V2
R1 R1 R2 R4 R2
E1 1 1 1 V2
R R V1 R (1)
R
1 1 2 4 2
I2 = I3 + I5
V1
E2 V2 0
V2
V2 R5
R2 R3
V1 V2 E2 V2 V2
R2 R2 R3 R3 R5
E2 V1 V2 V2
V2
R3 R2 R2 R3 R5
E2 V1 1 1 1
R R V2 R R R (2)
3 2 2 3 5
1 1
1
E2
2
1
4
1 1 1 V2
R R2 R3 R3 5
3 R
1 1 1 1
R R R R2
1 2 4
1 1
1 1
R R2 R3 R
2
5
E1 1
1 R1 R2
E1 1 1 1
R R R R
3 2 3 5
1 1 1 E1
R R R R
2 2 2 4 1
1 E2
R R
2 3
Fig 3.18
Let V1 and V2 be the voltage at node 1 and 2,
V1 E
V2 V2
V2 R
R3 5
R2
E V2 V1 V2 V2
R3 R5 R2 R2 R3
E V1 1 1
1
R R R R R V 2 (2)
3 2 2 3 5
1 1 1
I R2 R4
R V
E 1 2 11
1 V 1
R 2
3 R R R R
2 2 3 5
1
1 1
R R
R2
2 4
1 1
1 1
R R2 R3 R
2 5
1
I
1 R2
E
R 1 1 1
R R R
3 2 3 5
1 1
R R I
2 2 4
R 1 E
R
2 3
Now, V1 1 ,V 2
2
Solved problems
Problem 1
In the given figure 3.19, calculate the load current IL, load voltage VL, and power
consumed by the load.
Fig 3.19
Solution:
Steps:
20 = 2 I1 + 2 (I1+ I2 )
20 = 4 I1 +2I2 (1)
Loop (2)
25 = 3 I2 + 2 (I1+ I2 )
25 = 2 I1 + 5I2 (2)
20 4 2 I1
25 2 5 I
2
20 2
1 100 50 50
25 5
4 20
2 100 40 60
2 25
1 50
I 3.125A
1
16
60
I 3.75A
2
16
2
By Kirchoff’s Current law
Problem 2
For a copper wire of 0.5km long and 0.5cm diameter, find the resistance. Assume
specific resistance of copper as 1.7 10-8 -m.
Solution:
Resistance R l
a
Where l = length in meter = 0.5 103m. d = diameter in m = 0.5 10-2m.
d
a = area in m2 = 2
(0.5 10 2 ) 2 1.9635 105 m 2
4 4
Problem 3
2F capacitor is charged to a voltage of 500V. Calculate the energy stored in the
electric field of the capacitor?
Solution:
Problem 4
By voltage divider rule, find the voltage across each resistance connected in
series (figure 3.20)
Solution:
50
= 20 25 50 100 52.62V
25
= 20 25 50 100 26.316V
20 Fig 3.20
= 20 25 50 100 21V
Problem 5
By current divider rule, find the current through each resistor in the circuit shown
in fig. 3.21.
Fig 3.21
Solution:
Req1 1 1
1.28
1 1 1 0.7823
3 4 5
I 2 1.28
100 39 A
2
1.28
Req2 1 1
1.053
1 1 1 0.95
2 4 5
I 4 0.9677
19.49 A
4 0.9677
Where
1 1 1 1
1.0833
Req 2 3 5
4
Req4 = 0.923
I 5 0.923
15.6 A
5 0.923
Problem 6
All the resistances in figure 3.22 are 1 each. Find the value of current I
Fig 3.22
Solution:
The total circuit is simplified into single resistance in series with 10V
source
10
Current I 5.714 A
1.75
Problem 7
Convert the following star circuit in (figure 3.24) into delta circuit
Fig 3.24
Solution:
544335
R1 15.67
3
544335
R2 9.4
5
544335
R3 11.75
4
Delta Circuit
Problem 8
Convert the following delta circuit (figure 3.25) into star circuit
Fig 3.25
Solution:
Ra 5 10
1.43
5 10
20
10 20
Rb 5.714
5 10
20
Rc 2.86
5 20
5 10
20
Star Circuit
Problem 9
Convert the following current source (figure 3.26) into equivalent voltage source
Fig 3.26
Vs = Is R = 10 5 = 50V
Problem 10
Convert the following voltage source (figure 3.27) into equivalent current source.
Fig 3.27
Problem 11
Solution:
= 6 || 3 = 2
Resistance of branch
ACD = 18 + 2 = 20
Problem 12
Calculate the values of different current for the circuit shown in figure 3.29. What
is the total value of conductance and resistance?
figure 3.29
Solution
II G1
G1 G2 G3
0.1
12 2A
0.6
I2 = 12 0.2/0.6 = 4A
1 1 1 1 1
25 1
GAC GAB GBC 0.4 0.6 6 S
1
R = 25/6 ohms
AC
GAC
Problem 13
figure 3.30
= 1.5 10 = 15V
VAB = 20 – 15 = 5V
I3R = 5 or (5/6) R = 5 or R = 6
Problem 14
If 20V is applied across AB shown in figure 3.31. Calculate the total current, the
power dissipated in each resistor and the value of the series resistance to have
the total current
figure 3.31
Solution:
Power Dissipation
P 2.252 6 30.4 W
g
Problem 15
Determine the branch currents in the network of figure 3.32, when the value of
each branch resistance is one ohm.
Solution:
Let the current directions be as shown in figure 3.32 (b), Apply Kirchhoff’s
second law to the closed circuit ABDA, we get
5 – x – z + y = 0 or x – y + z = 5 (i)
-(x-z) + 5 + (y + z) + z = 0 or x – y – 3z = 5 (ii)
x + 3y + z = 10 (iii)
x- y = 5 (iv)
x + 3y = 10 (v)
– 4y = -5 or y = 5/4 = 1.24A
Problem 16
(a) A rectangular carbon block has directions 1.0cm 1.0cm 50cm. What is the
resistance measure (i) between the two square ends? (ii) between two opposing
rectangular faces / resistivity of carbon at 20oC is 3.5 10-5 m.
(b) A current of 5A exists in a 10- resistance for 4 minutes (i) how many
coulombs and (ii) how many electrons pass through any section of the resistor in
this time “Charge of the electron = 1.6 x 10-19C
Solution:
(a) (i) R = l /A
Solution.
19 d2 / 4 = 19 (1.32 10-3)2 / 4 m2
Problem 18
What is the value of the unknown resistor R in figure 3.34, if the voltage drop
across the 500 resistor in 2.5 volts? All resistances are in ohm.
Fig 3.34
Solution:
Problem 19
Using mesh analysis, find mesh current in each loop given in fig 3.35
Fig 3.35
Solution
100 = 10 I1 + 20 I1 – 20I2
100 = 30 I1 – 20 I2 (1)
30 0
(iii) 20 20 30
70
0 30 45
100 20
0
1
0 70 30
150 30 45
= 100 (7045 – 30 30) + 20 (-15030)
30 100
2 0
20 0 30
150 45
0
= 100 (0 45 – 150 30) - 100 (-20 45)
30 20 100
3
20 70 0
30 150
0
= 30 (70 15 – 30 0) +20 (-20 150)+100(-2030)
2 45000
I 0.909 A
2 49500
3 195000 3.94 A
I 49500
3
(v) Verification of Answers:
Problem 20
In the circuit given in fig 3.36, obtain the load current I1, and power consumed by
RL.
Solution:
(ii) Current I L I 3
3
200 100 2
0 0 I1
100 0 3 I
4 4
2
0 0 4 5 10 4
I 3
100 2 0 0 I1
100 0 7
4I2
0 0 4 19 I 3
2 0 0
(iii)
7 4
0
4 19
0
2 0 100
3
0 7 100
4 0
0
= 2 (7 0 + 4 100) +100 (0) = 800
Power consumed by R I 2 R
L
L L
= 3.4182 10
= 116.9 watts
Problem 21
In the following circuit, find the values of E and I for the circuit shown in fig
3.37(a)
Fig 3.37(a)
Solution:
This problem is solved by applying nodal analysis. The circuit consists of
two nodes and one reference node. Assume node voltages as V 1 and V2 and also
assume the currents direction.
From circuit, V2 = 4 2 = 8V
By KCL,
At Node 1,
E V1 V2
1
V1 V 2
2 6
V1 V1 V1 V2
2 6 2 2
E 1 1 1 V2
V
1
2 2 6 2 2
0.5E = V1 (1.167) – 0.5V2 (1)
At Node 2,
V1 V2 V2 V2
2 4 2
V1 V2 V2 V1
0V 1 1 1
2 V
2
2 2 4 2 2
4 2
2
0 = -0.5V1 + 1.25V2 (2)
0 = -0.5 V1 + 1.25 8
0.5 V1 = 10
V1 = 20V
E = 38.68V
Current E 38.68 20
IV 2 9.34 A
1
2
Problem 22
Using nodal analysis, find all node voltages in the given fig 3.38
fig 3.38
Solution:
(i) No of nodes in the given circuit is 3 including reference node. Nodes are
marked as 1 and 2. Node voltages are assumed as V1 and V2. The
directions of branch currents are also assumed.
At node 1
100 V1 V1 V2
V1 20 20
10
100 V1 V1 V1 V2
10 10 20 20 20
V1 V1
10 V V2
1
10 20 20 20
At node 2
V1 150 V2
V2 V2 30
20 15
V1 V2 150 V2 V2
20 20 15 15 30
150 V1 V2 V2 V2
15 20 20 15 30
10 0.05
1 = 10 0.15 + 10 0.05 = 2.
10
0.15
0.2 10
2
0.05 = 0.2 10 + 10 0.05 = 2.5.
10
(v) The voltages are given as
1 2
V 72.73V ,V2 2.5 91V
1
0.0275 2
0.0275
Problem 23
Using nodal analysis, find all node voltages in the given fig 3.39
fig 3.39
Solution:
1 1 1
10 20 20
V1
10 1 1 20
11 V
2
20 20 30 15
0.1 0.05
(iii)
= 0.1 0.15 – 0.05 0.05 = 0.0125.
0.15
0.05
10 0.05
1 = 10 0.15 + 10 0.05 = 2.
10
0.15
0.1 10
2
0.05 = 0.1 10 + 10 0.05 = 1.5.
10
(iv) Voltages
1 2
V 160V 1.5 120V
2
1 0.0125 ,V2 0.0125
Exercise problems
Figure 3.40
Ans : 0.43A
3. The current in the 5H inductor varies at the rate of 3A/sec. What is the
value of the voltage across the inductor and the energy stored in the
magnetic field of the inductor. Ans : 22.5J
4. A 3F capacitor is charged to a voltage of 600V. Calculate the energy
stored in the electric field of the capacitor.
Ans: 0.54J
5. Using voltage divider rule, find the values of Va and Vb. (figure 3.41)
Figure 3.41
Figure 3.42
Ans: I1 = 12.8A, I2 = 15.96A, I3 = 21.3A
7. Find the equivalent resistance across A and B in the following circuit
Figure 3.43
Ans: 1.155
8. Using mesh analysis find loop currents in the circuit given in fig. 3.44
figure 3.44
Ans: 31.25 A, 12.5 A, 12.5 A
9. Using nodal method, find node voltages in the circuit given in fig 3.45
Also find all branch currents.
figure 3.45
Introduction
The knowledge of magnetic circuit is very important in the design,
analysis and applications of electromagnetic devices like transformer,
rotating electrical machines and electromagnetic relays. The basic concept
of magnetic circuit and electromagnetic induction are the main topics to be
explained in this chapter.
4.1 Introduction
Magnetism refers to a force that acts between magnets and magnetic
materials. We know, for example, that magnets attract pieces of iron,
deflect compass needles, attract or repel other magnets, and so on. This
force acts at a distance and without the need for direct physical contact.
The region where the force is felt is called the “field of the magnet” or
simply, magnetic field. Thus, a magnetic field is a force field.
The symbol for magnetic flux density is B. The unit of magnetic flux density
is the tesla, T, where 1 T = 1 Wb/m2 Hence
B webers / m2 or tesla
a
4.4 Magnetomotive force and magnetic field strength
Magnetomotive force (mmf) is the cause of the existence of a
magnetic flux in a magnetic circuit. It is obtained as the product of the
current (I amps) flowing through a coil of ‘N’ turns.
mmf NI ampere turns
NI
H l Ampere turns / metre
where l is the mean length of the flux path in metres.
Β/Η=µ0
Β/Η=µ0µr
µr varies with the type of magnetic material and, since it is a ratio of flux
densities, it has no unit.
From its definition, µr for a vacuum is 1. µ0µr =µ , called the absolute
permeability
Reluctance is the ‘magnetic resistance’ of a magnetic circuit to the
presence of magnetic flux. It is defined as the ratio of Magneto motive force
to flux. The unit is AT/Wb and is denoted by ‘S’.This is identical to
resistance of electrical circuits.
reluc tan ce NI
mmf
flux
Hl Hl
BA
lI l
B / H A 0 r A
Reluctance depends on
a) Nature of material
b) Length of magnetic path
c) Area of cross section of the material
4.6 Analogy between Magnetic circuit and Electric circuits
Leakage coefficient,
useful flux
Usually, leakage factor is greater than unity.
Magnetic field
NI
strength, H l
i.e NI
H
2Rm
we know that B=µ0µr
NI
0 r Wb / m 2
l
Flux, Ba
0 r aNI
l
NI MMF NI
S Figure 4.3 simple magnetic circuit:
l / 0 r reluc tan
a ce
S = (S1 + S2 + S3) + Sg
Total MMF= (S1 S 2 S3 ) Sg
l1 l 2 l 2l g
= a a
1 0 r12 0 r 23 0 r 3 0 g
a a
B1 B2 B3 Bg
= l 1+ l + l 3 + l
g
µ0 µr1 µ 0µ r2 2
µ 0µ r3 µ
0
= H1l1+H2 l2 +H3 l3 +Hg lg
MMF = S3 + 1 S1 (or)
S3 + 2 S2
Also MMF = H3 l
+ H1 l1 (or)
3
H3 l + H2 l 2
3
When the current is zero, the H value zero and hence B also zero. H
is increased by increasing the current then the flux density B also
increases until the point of maximum is reached (curve oa). The material is
saturated beyond this point. B will not increase with increase in H. Now H
is gradually decreased by decreasing current, it is found that B does not
decrease along ‘oa’, but follows the path ‘ab’. At point ‘b’, H is zero but B is
in the material is ‘ob’. It is called residual magnetism or residual flux
density. The power of retaining the residual magnetism is called Retentivity
of the material
To remove residual magnetism ob, the magnetizing force H is
reversed by reversing current. When H is gradually increased in reverse
direction, the B-H curve follows the path ‘bx’. So that when H=ox, B=0. The
value of H (to be applied in negative direction) required to remove the
residual magnetism is called coercive force. If H is further increased in the
negative direction, the material is again saturated at point c in the negative
direction. Reducing H to zero and then increasing it in positive direction
completes the curve cda. Thus, when an iron bar is subjected to a cycle of
magnetization, the B-H curve completes a closed loop (‘abxcda’). This loop
is called hysteresis loop.
4.12 Energy Losses in magnetic materials
When a magnetic material is subjected to a cycle of magnetization,
an energy loss (core loss) takes place. Core loss consist of two losses
namely hysteresis loss and eddy current loss.
4.12.1 Hysteresis loss
Hysteresis results in a dissipation of energy which appears as a
heating of the magnetic material. The energy loss associated with
hysteresis is proportional to the area of the hysteresis loop. The area of a
hysteresis loop varies with the type of material. The area, and thus the
energy loss, is much greater for hard materials than for soft materials. If
the energy per unit volume for a cycle is taken as Eh, then
If one complete cycle of magnetization, the energy loss per unit volume is
the area of hysteresis loop.
For AC-excited devices the hysteresis loop is repeated every cycle of
alternating current. Thus a hysteresis loop with a large area (as with hard
steel) is often unsuitable since the energy loss would be considerable. This
loss component of the core loss can be reduced by choosing a core of
electrical steel that has a narrow hysteresis loop. Hysteresis loss is
expressed by empirical formulae (given by steinmetz)
Wh = 1.6
Bma f V.
x
In this case, the coil is held stationary and the magnetic field is
varied. The self induced emf may be self induced or mutually induced.
Self induced emf
If a single coil carries a current, flux will be set up in it. If the current
changes, the flux will change. This change in flux will induce an emf in the
coil. This kind of emf is known as self induced emf. In other words, self
induced emf is the emf induced in a circuit when the magnetic flux linking it
changes because of the current changes in the same circuit. This
phenomenon is called self induction.
d
The magnitude of this self induced emf e N
dt
4.15.2.1 Self inductance (L)
Self inductance of a coil, L is the rate of change of flux linkages with
respect to the current in it. Its unit is Henry. Thus
d d Henry
L N
dI dI
= N2
Reluctance
and
The other part of the flux is called leakage flux represented by . When
ℓ1
coupling is always ≤ 1. If both the coils are far apart, then k = 0. On the other
hand if both the coils are wound over the same core, then k = 1.
Using energy criteria, it can be proved that M12 = M21 = M
d12 d21 d2 2 d11
Then M2 = N1 N2 = N1 N2 k
d I2 d I1 d I1
k
dI2
d11 d2 2
= k 2 N1 N2 = k2 L1 L2
d I1 dI
2
Thus M = k L1 L2
When the magnetic field, the current and the conductor are mutually at
right angles then:
Force F=BI l newtons
When the conductor and the field are at an angle to each other then
Force F BIl sin Newton
Since when the magnetic field, current and conductor are mutually at right
angles, F = BI l , the magnetic flux density B may be defined by B = F/I l ,
i.e. the flux density is 1 T if the force exerted on 1 m of a conductor
when the conductor carries a current of 1 A is 1 N.
Solved problems
Problem 1.
A magnetic pole face has a rectangular section having dimensions 200 mm
by 100 mm. If the total flux emerging from the pole is 150 µWb, calculate
the flux density.
2
Cross sectional area A = 200 100 = 20000 mm
= 20000 6 m2
150 6
Flux density B 6
A 20000
0.0075 Wb / m2
Problem 2.
A magnetizing force of 8000 A/m is applied to a circular magnetic circuit of
mean diameter 30 cm by passing a current through a coil wound on the
circuit. If the coil is uniformly
Problem 3.
A mild steel ring has a radius of 50 mm and a cross sectional area of 400
mm2. A current of 0.5 A flows in a coil wound uniformly around the ring
and the flux produced is 0.1 mWb. If the relative permeability at this value
of current is 200 find (a) the reluctance of the mild steel and (b) the number
of turns on the coil.
l 2r 2 3 m
A 400 6 m 2 ; I 0.5A; 0.13 Wb; 200
r
l 2 3
(a) Reluctance S =
0 A (47 ) 6 )
3.1256 AT / Wb
mmf
(b) S ; mmf S; NI S
S 3.1256 0.13
N
I 0.5
625 turns
Problem 4.
A section through a magnetic circuit of uniform cross-sectional area 2 cm 2
is shown in Figure 4.11. The cast steel core has a mean length of 25 cm.
The air gap is 1 mm wide and the coil has 5000 turns. Determine the current
in the coil to produce a flux density of 0.80 T in the air gap, assuming that
all the flux passes through both parts of the magnetic circuit.
S1 l1
0r A1
l1 l1 H
B
( )A BA 1
0 H 1
0
2 ) 750
Figure 4.11 0.8 2
1172000 AT / Wb
l2
S2 A lA
2
0 r 2 0 2
3
(47 ) 4 )
3979000 Wb / m2
Total reluc tan ce S1+S2=1172000+3979000
5151000 Wb / m2
Flux BA 0.80 2 4
1.6 4 Wb
mmf
S ; mmf S
Hence NI S
S
current 5151000 1.6 4
N 5000
0.165 A
Problem 5.
A toroidal air cored coil with 2000 turns has a mean radius of 25 cm.
Diameter of each turn is 6 cm. Current in the coil is 10 amps. Find (a) MMF
(b) Flux (c) Flux density. Find the magnetic field strength and verify B = H
relation is satisfied.
d 2 (6 10 )
2 2
a, area of cross section
= 2.8 103 m 2
4 4
= 0 r
= 4 x 10-7 x 1 (Air cured r =1)
S, Reluctance l 1.57
= = 4.46 108 AT / wb
4 10 2.8 103
7
a
MMF = NI = 2000 x 10 = 200000 AT
FLUX , MMF 200000 4.48 105 wb
= S 4.46 108
Flux Density , B 4.48 10
5
Problem 6.
A ring has mean diameter of 15cm, a cross section 1.7cm 2 and a radial gap
of 0.5 mm cut in it. It is uniformly wound with 1500 turns of insulated wire
and a current of 1 ampere produces a flux of 0.1 mwb at the gap. Calculate
relative permeability of iron. Assume no leakage.
B,
104 1 Tesla (wb/m2) = 0.588 tesla
= at air gap 4
a 1.7 10 1.7
H, at air gap B 1
4.681105 AT / m
= 1.7 4 10 7
0
At required at air gap = H. l g
= (4.681 x 105) x (0.5 x 10-3)
= 234.1
Total MMF or ampere turns = NI = 1500 x 1 = 1500
Problem 7.
An iron rod of 1cm radius is bent to a ring of mean diameter 30cm and
wound with 250 turns of wire. Assume relative permeability of iron as 800.
An air gap of 0.1cm is cut across the bent ring. Calculate the current
required to produce a useful flux of 20,000 lines. Assume leakage factor of
1.1. Also find the magnetizing current.
0 a
=
0 r a 0.001
4 107 ( 110 4 )
= 2533029.59 AT/wb.
Useful flux is available at the air gap = 20000 lines = 20000 x 10-8 wb.
Problem 8.
The magnetic circuit shown in figure 4.12 is made up of cast steel bar of
cross section 5 sq cm. The middle link has 200 turns of wire wound over it.
The flux path in the central link is 20 cm long. The flux path in the other
link sections on the LHS and RHS to central limb is 50 cm each. Find the
current required to produce a flux of 2m wb. Take relative permeability of
the material as 1000.
Figure 4.12
0 r a
0.2
= 5 104 4 107 1000
= 318309.9 AT/wb
reluctance in any side limb, S2 = l 2
0 r a
= 0.5
4 107 1000 5 104
= 795774.72 AT/wb
Effective reluctance, S =
S S2
1
+
2
= 716197.25
MMF = S = (2 x 10 ) (716197.25)
-3
= 1432.4 AT
Magnetising current MMF NI 1432.4 7.162 Amps.
= Turns N 200
Problem 9.
A coil of resistance 150 ohms is placed in a magnetic field of flux 0.1 mwb.
The coil has 500 turns. A galvanometer of 450 ohms resistance is
connected in series with it. The coil is moved in 0.1 seconds from the
given field to another field of 0.3 mwb. Find the average induced emf and
the average current through the coil.
Problem 10.
A conductor 10 cm long and carrying a current of 60A lies perpendicular to
a field of strength 1000 AT/m. Calculate (a) the force acting on the
conductor (b) mechanical power required to move the conductor against
the force with a speed of 1 m / sec. (c) emf induced in the conductor (d)
electrical power developed.
Force, F = BI l Newton
& B = 0H (because magnetic field is in the air / free space)
= 4 x 10-7 x 1000
= 4 x 10-4
F = 4 x 10-4 x 60 x 0.1 = 7.5 x 10-3 x 1
= 7.5 x 10-3 Newton.
Mechanical Power required, P = force x velocity = 7.5 x 10-3 x 1
= 7.5 x 10-3 watts
Emf induced, e = B l v = 4 x 10-4 x 0.1 x 1 = 4 x 10-5
Power developed, P = e x I = 4 x 10-5 x 60
=7.5 x 10-3 watts
Problem 11.
An air cored toroidal coil has 480 turns. Its mean length is 30cm. Cross
sectional area = 5cm2. Find (a) self inductance of the coil (b) average emf
induced if a current of 4A is reversed in 60 milli secs.
N 2
N
L= (Another formula is L = )
S I
l l
S= (because air cored coil & hence = 1)
0 r a 0 a r
emf induced, e = di 8
= 483 x 10-6 x
L dt 60 103
= 0.064 V
Problem 12.
Self inductance of a coil of 500 turns is 0.25 H. If 60% of the flux is linked
with a second coil of 10500 turns, calculate (i) mutual inductance between
the two coils, (ii) emf induced in second coil when the current in the first
coil is changed at the rate of 100A/sec.
em21 d1i
=M
dt
63.75 = M (2 0)
2 103
M = 63.75mH
we know that M = K L1 L2
63.75 = 0.75 37.5 L2
L2 = 193mH
Initially when 1 = 0.3 mwb 🡪 2 = K 1 = 0.75 x 0.3 = 0.225 mwb
When current is made zero 1 = 0 🡪 2 = 0
d2 = (0.225 – 0) = 0.225 mwb
d2 3
e =N N 2 0.225 10
m21 dt 2 103
N2 = 567 turns
EXERCISES
1. Find the ampere turns required to produce a flux of 0.4 mwb in
the air gap of a magnetic circuit which has an air gap of 0.5mm.
The iron ring has 4 cm 2 cross section and 63 cm mean length.
Take r = 1800 and leakage coefficient = 1.15 (Ans : 718)
2. A coil is wound uniformly with 300 turns over an iron ring having
a mean circumference of 400 mm and a cross section of 500 mm 2.
If the coil has a resistance of 8 and is connected across a 20V
DC supply, calculate.
a) the mmf of the coil
b) magnetic field strength
c) total flux
d) reluctance of the ring
Assume r = 900
Introduction
In ac circuits, voltage and current vary sinusoidally. The passive
parameters of AC circuits are resistance R, inductance L and capacitance
C. The aim of this chapter is to discuss the effect of each passive
parameter, series and parallel AC circuit and resonance circuits.
Fig 5.1
1
f
(Hz)
T
Instantaneous values
Instantaneous values are the values of the alternating quantities at
any instant of time. They are represented by small letters, i, v, etc.
Peak value
The largest value reached in a half cycle is called the peak value or
the maximum value or the crest value or the amplitude of the waveform.
Such values are represented by Vm , Im . Peak-to-peak value is measured
between minimum and maximum peaks.
Fig 5.6
Consider the phasor line of length Vm shown in Figure 5.7 (a). (It is
the phasor). The vertical projection of this line (indicated in dotted) is
Vm sin α. Now, assume that the phasor rotates at angular velocity of ω rad/s
in the counterclockwise direction. Then, α = ωt, and its vertical projection is
Vm sinαt. . If we designate this projection (height) as v, we get v= Vm sinωt,
which is the familiar sinusoidal voltage equation.
A sinusoidal waveform can be created by plotting the vertical
projection of a phasor that rotates in the counterclockwise direction at
constant angular velocity ω. If the phasor has a length of Vm, the waveform
represents voltage; if the phasor has a length of Im, it represents current.
Note carefully: Phasors apply only to sinusoidal waveforms.
Iav = i1 i2 i3 .....in
n
A better way of finding the average value is to find the area over the
curve for a small interval of time and integrate over the curve and divide it
by ‘T’
1 T
Iav = i dt
T0
Also, Iav = Area under the curve over one complete cycle
Base ( period )
IRMS =2 i 2 i 2 in2
i123
n
A better way of finding it is to find the area over the squared curve
for a small interval of time, and integrate over the curve and divide it by ‘T’
and take square root of the whole.
1T
IRMS =
T
∫ i 2 (t)dt
0
∫ 0
2
= ∫ (I
0
m sin )2 d
2
= I2 sin 2 d
∫ 1 cos
m
0
2 2
m 2
= I2 d
0
sin 2 2
= Im2
2 2 0
Im2
= 2 0
2
= I2
m
Im2 I
IRMS = = m
2 2
For sine quantities RMS value 1
times or 0.707 time maximum value
is 2
RMS value can be found by considering only one half cycle for
symmetrical waveforms.
Since voltage and current waveforms coincide, their phasors also coincide
as in Figure 5.9 (b)
5.9.1 Power
Vm Im
Average power over a P Sin2 d
cycle, 0
∫
V I
= m m
(1 cos 2
) 2 0∫
V I Sin2
= m
m
2 2
0
V I
= m m [ ]
2
Vm I m V I
= 2 m2 m2
= V I watts
Vm
= ( cost)
L
= Im sin (t-/2)
Vm
Where Im = & L = XL inductive reactance in ohms
L
In a purely inductive circuit the opposition to the flow of alternating current
is called the inductive reactance, XL
VL
X
L
IL
XL L 2fL
Hence for v = Vm sint in a pure inductive circuit, we get i = Im sin (t - /2)
i.e. i lags behind v by /2 radians in pure ‘L’ circuit
where Im = Vm
Vm i.e. Xc = 1/c 🡪 capacitive reactance in ohms
1/ c X
c
In a purely capacitive circuit the opposition to the flow of alternating
current is called the capacitive reactance
V
X C
C
IC
1 1
X
C
C 2fC
So, for given v = Vm sint in a pure capacitive circuit i = Im sin (t + 90o), the
current is leading voltage by /2 radians in a pure capacitive circuit.
(a) circuit (b) Phasor diagram (c) Voltage triangle (d) Impedance triangle
In any a.c. series circuit the current is common to each component and is
thus taken as the reference phasor.
From the phasor diagram of Figure 5.12 (b), the ‘voltage triangle’ is derived.
If each side of the voltage triangle in Figure 5.12 (c) is divided by current I ,
then the ‘impedance triangle’ is derived.
current I leads the applied voltage by an angle lying between 0° and 90°
(depending on the values of
and VC ), shown as angle .
VR
(a) circuit (b) Phasor diagram (c) Voltage triangle (d) Impedance
From the phasor diagram of Figure 5.13 (b), the ‘voltage triangle’ is derived.
If each side of the voltage triangle in Figure 5.13 (c) is divided by current I ,
then the ‘impedance triangle’ is derived.
(see Figure 5.14). and VC are anti-phase, i.e. displaced by 180°, and there
VL
are three phasor diagrams possible—each depending on the relative values
of VL and VC
and (XL XC )
tan R
When, XC XL (Figure 5.14(c)), Z R2 (XCL X )2
and (XC XL )
tan R
(a) circuit (b) XL XC (c) XC XL (d) XC = XL
When XL =XC , (Figure 5.14(d)), the applied voltage V and the current are in
Circuit V Z P.F
Assuming Z = R + jX
1
1 R jX R jX
Z R R2 X
2 Z2
jX
R X
= j
2 2
Z Z
=G–jB
R
where G is called conductance and =
Z2
X
& B is called susceptance and =
Z2
i.e Z = R + jX ⇒ Y = G – jB
Similarly Z = R – jX ⇒ Y = G + jB
i.e Inductive reactance is expressed as +jX and inductive susceptance as
–jB and capacitive reactance is expressed as –jX and capacitive
susceptance as +jB
i.e. Z = R jX ⇒ Y = G jB
consider 3 impedances Z1, Z2 & Z3 in parallel and let ‘Z’ be its equivalent
then 1 1 1 1
Z Z1 Z 2 Z 3
i.e Y = Y1 + Y2 + Y3
i.e when two or more impedances (say of the form R+jX)are in parallel, their
equivalent admittance is sum of the individual admittances
Y = Y1 + Y2 + Y3
= (G1 – jB1) + (G2 – jB2) + (G3 – jB3)
= (G1 + G2 + G3) – J (B1 + B2 + B3)
= G – jB
i.e. sum of individual conductance of parallel branches is equal to
equivalent conductance and sum of individual susceptance of parallel
branches is equal to equivalent susceptance. Admittance triangle for
G – jB is as below.
Power Factor
G
Cos =
Y
Admittance triangle for G + jB is as below.
V
=Z
1
= V1
Similarly I2 = VY2 & I3 = VY3 etc.
I = I1 + I2 + I3 = V (Y1 + Y2 + Y3)
= VY
i.e Total current through the circuit is the product of voltage applied and
equivalent admittance. Also power factor of various parallel branches are
cos 1 = G1 / Y1, cos 2 = G2 / Y2, cos 3 = G3 / Y3 and
Power factor of overall circuit is cos = G / Y
Figure 5.17
Power factor
It is defined as the cosine of the angle between the voltage and
current. If is the angle between voltage and current, p.f = cos. The lagging
power factor occurs for inductive load and leading power factor occurs for
capacitive load.
Active or Real or True Power
The product of r.m.s value of voltage and current with the cosine of
the angle between them is called the real power P. Mathematically
P = VrIr cos
Its unit is watt (W)
Reactive Power
The product of r.m.s value of voltage and current with the sine of the
angle between them is called the reactive power Q. Mathematically
Q = VrIr sin
Its unit is reactive volt amperes (var)
Apparent Power
The product of r.m.s value of voltage and current is called apparent power
S.
S = VrIr
Powerfactor
True Power P VIcos
Apparent Power S VI
R
Powerfactor cos
(from impedance triangle)
Z
5
Z = 5 53.1o is polar form.
Examples:
1) 10 30o + 8 60o
10 30o = 8.66 + j5
8 60o = 4 + j6.93
1030o + 8 60o = 12.66 + j11.93 = 17.4 43.3o
2) (8+j6) (3 – j4)
= 1036.9 5 -53.1
= (10 5) (36.9 + (-53.1))
= 50-16.2
= (48 – j14)
5.19 Resonance
CV 2 CI
2
I m2 L
2
sin 2 t cos 2 t
2
I L I2L
m
[1] m
2 2
Energy dissipated per cycle
= I2RT
where I = I m
= RMS value of current
2
T = 1/f = Time period for one cycle
Z R j( X L X C ) R 2 ( X
LC X
)2 R2 R2
2R 2 2R
Current in RLC circuit at half power frequencies,
V V
i V
Z 2R2 0.707R
V 2 1 V 2
V
Power P I 2 R R R
2R 2R 2 R
2
In fig 5.21,
f1 = Lower half power frequency.
f2 = Upper half power frequency
The range of frequency between f2 and f1 is called bandwidth of RLC
circuit. Current response is appreciable over the bandwidth. The current
value varies from 0.707 V/R to V/R. Sharpness of the tuning of RLC circuit is
decided by the bandwidth (f2 – f1).
At lower cut off frequency,
XL – XC = R (At lower frequencies XC > XL)
1 2 LC
1 L 1
1C R
⇒ 1
1C
LC 1 RC
2
1 1
2 LC RC 1 0
1 1
f1 fr f2
RC (RC) 2 4 LC
1
2LC
RC R 2C 2 4LC
2LC 4L2C 24L2C 2
R
R2 1
2L 4L2LC
R 2 1
2f1 R
2L 2L LC
R 1
R 2 1
4L 2
2L LC
Similarly at upper half power frequency,
XL – XC = R (At upper frequencies XL > XC)
1
2 L R
2C
2 LC 1
2
R
2C
2 LC 1 RC
2 2
2 LC RC 1 0
2 2
RC (RC) 2 4LC
2
2LC
RC R 2C 2 4LC
2LC 4L2C 24L2C
2
R
R2 1
2L LC
R 4L2
R 2 1
2f 2
2L 2L LC
f 2 R 1 R
2
1
4L 2 2L LC
Bandwidth ( f 2 R 2 2
f1 ) 1 R 1R 1 R 1
4L 2 2L LC4L 2 2L LC
2R
4L
(f2 R
f1 )
2L
The ratio of resonance frequency fr to bandwidth ( f2 f1) is called the
quality factor of coil Q.
fr
Q
f 2 f1
fr
R
2L
2fr L
R
1
L
r L LC
Q 1 L
R R R C
5.21 Selectivity
r L 1 1 1
⇒2 ⇒
r C r LC r LC
1 1
2fr ⇒ f
LC r 2LC
Problem 1.
Find the average value, rms value, peak factor and form factor of the
following waveforms
(a) Unsymmetrical Saw Tooth
(b) Unsymmetrical rectangular
(c) Symmetrical rectangular
(d) Symmetrical Trapesoidal Waveform
(e) Half Wave Rectified sine wave
(f) Full wave rectified sine wave
Average value of I
5
= 2.5amps
2 Figure 5.23
Peak factor 5
peak value 1.732
=
rms value 2.887
25T
== T 25 volts
(ii) Area under one cycle of
squared curve
= 1002 x T/2+(-50)2xT/2
12500T
= 2
Period or base =T
RMS value
12500T Figure 5.24
= 2 79.06 volts
Average value
100T / 2
= 100 volts
T/2
(ii) Area under one cycle =
1002 x T/2
1002 T /
RMS value of V 100 volts
2
=
T/2
Form factor RMS 100
= Average 100 1
Figure 5.26
2/3 2
Average value of V Vm volts
Vm 3
=
0.745V
Form factor m
1.11
= 2 / 3Vm
Vm 1.342
Peak factor = 0.745V
m
(e) Half Wave Rectified sine wave
= ∫ I m sin d ∫ 0 d
0
= I m (cos )
0
= Im (-cos + cos 0) Figure 5.27
= Im (1+1)
= 2Im
Period or base = 2
Average value 2I m
= Im /
2
sin 2
2
= I m
2 2 0
= I m sin 2 0 sin 2 0
2
2 2 2
I 2
= m
2
Period or base = 2
Im2
2 I m2 Im
RMS value = =
= 2 4 2
= ∫I
0
m sin d
= I m (cos ) 0
= 2Im
Period or base =
Figure 5.28
Average value
2I
= m 2I m /
= I 2 sin 2 d
0
1 cos 2
= I2 d
m
0 2
sin 2
2
= I m
2 2 0
= I m sin 2 0 sin 2 0
2
2 2 2
I 2
= m
2
Period or base =
I m2
2 I m2 Im
RMS value = =
= 2
2
RMS value Im /
Form factor 1.11
Average value 2
=
2I m / 2 2
Peak factor Peak value Im
= RMS value I m /2 2
Problem 2
For a series RL circuit (Fig. 5.29), determine the source voltage and phase
angle if the voltage across the resistance is 50V and the voltage across the
inductor is 30V.
Figure 5.29
Solution:
Given : VR = 50V, VL = 30V
Source voltage VS = VR + jVL = 50 + j30 = 58.3 30.96oV
Phase angle between source voltage VS and source current Is is
tan 1
VL
tan 1 30
VR 50
30.96 o
Problem 3
In an AC circuit, resistor R and inductor L are connected in series. Voltage
and current equations are given as e(t) = 200 sin 314t and i(t) = 20 sin (314t –
30o). Calculate
(i) RMS value of the voltage and current
(ii) Frequency
(iii) The power factor
(iv) Power
(v) Values of R and L
Solution:
Given:
e(t) = 200 sin 314t
i(t) = 20 sin (314t – 30o)
(i) Peak value of the voltage, Vm = 200V
Peak value of the current, Im = 20A
Impedance Z V 141.42
I 14.142 10
Z R 2 XL 2
10 8.662 XL2
Figure 5.30
Solution:
Impedance Z = R –jXc
Where 1
Xc 1 1 1.591k
2fC 2 50 2
C 106
Z (2 j1.591)k
Current V
I 100 (30.62 j24.36)mA
Z (2 j1.591) 103
= 39.1238.492omA
Phase angle between source voltage and source current i(t) is
= 38.492o
Voltage across resistor R,
VR = I R = 39.12 10-3 2 103 = 78.24V
Voltage across capacitor,
I Xc = 39.12 10-3 1.591 103 = 62.23V
Problem 5
In an a.c circuit, resistor R and capacitor C are connected in series.
Voltage and current equations are given as e(t) = 100 sin (100t – 30o)V and i(t)
= 10 sin (1000t + 10o)A. Calculate (a) RMS value of the voltage and current
(b) frequency (c) the power factor (d) power (e) values of R and C.
Solution:
a) Peak value of the voltage, Vm = 100V
Peak value of the current, Im = 10A
Vm 100
RMS value of the voltage, Vrm
s 70.71V 2
2
RMS value of the I
current, I rms m 10 7.071V
2 2
b) Frequency
Given, = 2f = 1000 rad / sec.
1000
f 159Hz(or)Cycles / sec.
2
c) Phase angle between e(t) and i(t)
The phasor diagram for the given RC circuit is shown in figure
Figure 5.31
Xc = 6.43
1
X
C
C
1
6.43
1000 C
1
C 0.1555mF
1000 6.43
Problem 6
Find the current through impedance Z of the following circuit (figure 5.32)
connected to the a.c voltage source.
Figure 5.32
Solution:
V
Current I
Z
Impedance Z = R+j (XL – XC)
R = Resistance = 50
XL = Reactance of the inductor
= L = 2fL = 2 505010-3=15.7
1
1 1 63.66
XC 2fC 2 50 50
C
106
Now, Z = 50 + j (15.7-63.66)
Z = (50-47.96j)
V
I 100 (1.042 0.999 j) A
Z (50 j47.96
j)
= 1.443 43.8oA
Problem 7
For the following fig 5.33, determine total impedance Z, source current I
and phase angle
Figure 5.33
Solution:
Total current I = IR + IL
Current through resistor
R,
V
I 100
R 2A
R 50
Current through inductor
I L V 100 j5 A
jX L j20
Total current I = (2-5j) A = 5.385 -68.19oA
Impedance Z V 100 (6.896 17.24 j) 18.5968.19o
I (2 5 j)
The phase angle difference between source voltage V and current I is
= 68.19o
Problem 8
For the following circuit in figure 5.34, determine total current IT, phase
angle and total impedance Z in the circuit.
Figure 5.34
Solution:
Total current IT = IR + IC
Current through resistance V
I 50 / 20 2.5A
R, R
R
V
Current through capacitor IC
C, jX C
Capacitive reactance 1 1
XC 795.77
2fC 2 2 10 0.110
3 6
Now,
IC 50
0.063 jA
j795.77
Total current IT = (2.5 + 0.063j) A = 2.5 1.443oA
The phase angle difference between source voltage V and source current I
is = 1.443o
Total impedance Z V 50
2.51.443o 20 1.443
o
IT
= (19.99-0.5j)
Problem 9
In the given figure 5.35, find the value of current under resonance and also
find resonant frequency, power, voltage drops across R, L and C.
Figure 5.35
Solution:
At resonance impedance Z = R
Current E E 100
I A
Z R 50
1 1
Resonant frequency f r 80Hz
2LC 240 103 100 106
Problem 10
In the given circuit figure 5.36, find frequency, current and voltages across
R, L and C. Also find the quality factor (Q) and bandwidth at resonance.
Figure 5.36
Solution
1
Resonance fr
frequency 2LC
1
1.838 kHz
2 15 103 0.5 106
At resonance, impedance Z =R.
V V 250
Current I 12.5 A
Z R 20
Voltage across
R1 , ER IR 12.5 20 250 V
Voltage across L, EL = IL = I (2 f) L
= 12.5 2 1.838 103 15 10-3
= 2165 V
1 1
Voltage across C, EC = I XC = I
C I 2fC
1
12.5
2 1.838 10 0.5 10
3 6
= 2165 V
L 2 1.838 103 5 103
Quality factor Q 2fL
R R 20
= 8.66
Quality factor Q fr
f 2 f1
fr
1.838 10 212.2 Hz
3
Bandwidth (f – f ),
2 Q 8.66
Problem 11
A RLC circuit consists of R = 10, L = 10mH and C = 2.5F. Calculate the
value of half power frequencies and also bandwidth.
Solution:
1 R R 2 1
Lower cut off f1
frequency, 2 2L 2L LC
2
1 10 10 1
2 10 103 10 103 2.5 106
2 2 10 103
1
500 (500) 0.04 10
2 9
2
= 930Hz 1 R
R 2 1
Upper cut off frequency f 2
2L LC
2 2L
1 10
2
10 1
2 2 10 103 2 10 103 10 103 2.5 106
= 1089Hz
Problem 12
In figure 5.37, determine the value of RC for resonance.
Figure 5.37
Solution:
1 1
Admittance Y
Z1 Z2
1 1 1 (2 2 j) 1 RC 3 j
22j RC 3 j 2 2 j (2 2 RC 3 j RC 3 j
j)
22j RC 3 2 2 j RC 3 j
j
22 j 2 22 R 2C j 2 44 R2 9
2
3
j
82 R R2 C 9 R 23 9 28
C
C C
RC 3 1.732
Problem 13
In figure 5.38, determine the value of C under resonance frequency 1000
rad/secs (
RC 4 ).
Figure 5.38
Solution:
1 1
Admittance Y
Z1 Z2
1 1 1 (4 j4) 1 4 jX C
4 j4 4 jX C 4 j4 (4 j4) 4 jX C 4 jX C
4 j4 4 jX 4 j4 4 jX C
C
42 j 2 42 42 j 2 X 2C 32 4 X2
4 4 X 4 C
j C
32 4 X 2 32
C
4 X C
2 2
X C 8 64 4 16
2 4
Radian frequency = 1000 rad/sec
1 1
X 4⇒ 4
C
C 1000 C
1
C 0.25F
4000
Problem 14
In the circuit given in figure 5.39, determine the value of L under resonance
frequency 160Hz.
Solution :
1 1
Admittance Y
Z1 Z2
1 1 1 3 jX L1 1 44j
3 jX L1 4 4 j 3 jX L1 3 jX L1 4 4 j 4 4 j
3 jX L1 44j 3 jX L1 44j
32 j 2 X 2 42 j 2 42 9 jX 2 42 j 2 42
L L
3 jX L1 4 4 j 3 4 4 X L1
j
9X 2
32 9X 2
32 32 9 X 2
L1 L1 L1
4 X L1 1 X L1
32 0⇒
9X 2 8 9X2
L L
9 8X
2
X 2L L
8X 9 0 (i)
XL L
Solving eqn (i),
X L1 8 64 4 8 28 6.646(or)1.354
9 2
2
when XL1 = 6.646,
X L1
L
6.646
2 160 6.61mH
when XL1 = 1.354,
X L1
L 1.354
2 160 1.347mH
Exercise problems
Figure 5.40
Figure 5.41
Figure 5.42
Figure 5.43
Introduction
Basics of single phase AC circuits have been discussed in chapter 5.
Different types of three phase ac circuits and power measurements for ac three
phase circuits are main topics in this chapter
i) For a given frame size, the power rating of three phase motor or
three phase generator is more than single phase motor or generator.
ii) Three phase motors are self starting but single phase motors are not
self starting
iii) For the transmission of same power, three phase circuits require
less conductor material than single phase circuit.
iv) Single phase motor produces pulsating torque but three phase
motor produces uniform torque.
Three phase system has three independent voltage sources. Three voltage
sources may be connected in star or delta connection. Each independent voltage
source form separate phase. They are named as R-phase, Y-phase and B-phase
EMF generated by each source is represented as follows.
VR = Vm sint
Vy = Vm sin (t - 120o)
VB = Vm sin (t – 240o)
Fig 6.1(a) Three phase star connected system Fig 6.1(b) Three phase delta connected system
Fig 6.3 (a) RYB Phase sequence Fig 6.3 (b) RBY Phase sequence
A balanced star connected 3-phase system is given in fig 6.4 and phasor
representation of its 3-phase voltages is also shown in fig 6.5
RN | V
VRN VYN | V|2 |2 2 | V
YN
|| V| cos 60o
RNYN
VL V
1
3VPh
22 2
V 2V
2
phph ph
In delta connected system, line voltage between any two lines is equal to
phase voltage. A delta connected system is shown in fig 6.6
In fig 6.9
Line current IL1 = phasor difference of IYR and IRB
= IYR - IRB
= IYR + (-IRB)
I YRRBYR
2 I 2 2IIcos 60o
RB
Where = 60 ➔ phase difference between IYR and –IRB and
o
Now, I
P3 L
cos 3VL I cos
VL L
3
VBY V 120o
I V 120o
Z 2 2 Z 2 2 Z2
BY
2
VYR
V 240 V 240o
o
I
Z3
Z 33 Z33
YR 3
Total power (P) consumed by the 3 phase load is equal to algebraic sum of
the average power consumed by each load.
Now,
P = W1 + W2 + W3 = VRN IR cos + VYN IY cos + VBN IB cos
= Vph Iph cos + Vph Iph cos + Vph Iph cos = 3Vph Iph cos
6.9.2 Two wattmeter method
Let consider the circuit, measuring power in balanced three phase star
connected load using two wattmeters.
Fig 6.13 Power measurement using two wattmeters
In each wattmeter, pressure coils are connected between two lines. Hence
line voltage is applied across pressure coils. The relation between line voltages
and line currents are given in phasor diagram in fig 6.14.
Wattmeter will indicate down scale reading when phase angle between line
voltage and line current is greater than 90o. To get upscale reading either current
coil connection or voltage coil connection is interchanged. Reading taken from
particular wattmeter is taken as negative after reversal of coil connection.
Power factor:
Power factor is calculated for 3-phase circuit from the reading of the two
wattmeters. Power factor is cosine of phase angle between phase voltage and
phase current. For a balanced load each phase has same power factor. But
power factor of every phase differs in case of unbalanced 3 phase load.
From two wattmeters reading.
W1 W2 3VL I L cos
W1 W2 VL I L cos(30 ) VL I L cos(30 ) VL I L cos(30 ) cos(30 )
VL I L (cos 30 cos sin 30 sin cos 30 cos sin 30 sin )
VL I L 1 1
(sin 30 sin sin 30 sin ) sin sin
VL I 2
L
2
VL I L sin
Now, W1 W2 VL I L sin 1
tan
3VL I L cos
W1 W2 3
tan 1 3 W1 W2
W1 W2
Power factor = cos
If we multiply this value with 3 , we will get total reactive power in 3-phase load.
Solved Problems
Problem 1
Each phase of a 3 phase star connected alternator produces a voltage of 11000V
and current of 1000A at power factor 0.9. Find line voltage, line current and total
capacity of the alternator.
Solution
For star connected system,
Line voltage VL 3V ph 3 11000 19053V
= 29.7 Mwatts
Problem 2
Each phase of 3 phase delta connected alternator produces a voltage of 11000V
and current of 1000A at power factor 0.9. Find line voltage, line current and total
capacity of the alternator.
Solution:
For delta connected system.
Line voltage VL Vph 11000 V
Problem 3
A 3-phase, 440V, star connected alternator is connected to a balanced star
connected load. Each phase having load of (10+j10). Find (a) Active power (b)
Reactive power (c) Apparent power.
Solution:
Given: VL 440V , Z ph (10 j10)
Vph VL 440
254V
3
3
I ph Vph 254
(12.7 12.7 j) A 17.96 45o A
Z ph (10
j10)
Fig 6.16
Problem 4
A 3-phase, 440V, delta connected alternator is connected to three phase load.
Each phase is having load impedance (20+j20). Find (i) Active power (ii) Reactive
power (iii) Apparent power.
Solution:
Given:
VL 440V , Z ph 20 20 j
Phase voltage Vph = VL = 440V
Vph 400
Phase current I 11 11 j 15.56 45o A
ph
Z ph (20 j20)
Fig 6.17
a) Active power = 3 Vph Iph cos = 3 400 15.56 cos 45o
= 14.523 K watts
b) Reactive power = 3 Vph Iph sin
= 14.523 KVAR
c) Apparent power = 3 Vph Iph = 3 400 15.56 = 20.539 KVA
Problem 5
In two wattmeter method, for three phase load, the wattmeter readings are 500W
and 40W. Calculate (i) Active power (ii) Phase lag (iii) Power factor (iv) Reactive
power
Solution:
(i) Active power = W1 W2 500 40 460 Watts
W W
(ii) Phase lag tan 1
3 1 2
tan 500 (40) o
1 3 63.8
W W 500 40
1 2
W1 – W2 = 3.355kW (2)
From (i) and (ii),
W1 + W2 = 12 103
W1 – W2 = 3.355 103
2W1 = 15.355 103
W1 =7.6775 103 watts
From (i) ➔ W2 = 12 103 – 7.677 103
W2 = 4.322 kW
Exercise problems
3. In two wattmeter method, for three phase load, the wattmeter readings are
600W and -60W. Calculate (i) Active power (ii) Phase lag , (iii) Power
factor (iv) Reactive power
Ans: 540W, 64.7o, 0.427, 1143 VAR.
4. A three phase load consumes power of 10kW at 0.8 pf. If two wattmeter
method is applied to measure the power, what are the individual readings
of the wattmeter?
Ans: 7165W, 2835W.
7 ELECTRICAL MACHINES
Introduction
In this chapter construction and principles of operation of ac and dc
electromechanical energy conversion devices such as dc generator, motor,
transformer and ac machines, with their applications will be discussed in details.
7.1 DC machines
DC machines are broadly classified as DC generators and DC motors.
Generator converts mechanical energy into electrical energy and motors vice
versa. Electrical Machines work on the principle of Faraday’s law of
electromagnetic induction. The basic requirements are a magnetic field,
conductor and relative motion between them. In DC machines the field is
stationary and the conductors are revolving. So is produced an induced emf
directly proportional to rate of change of flux.
7.2 DC Generator
7.2.1 Working principle of DC Generator
The dc generator is rotating electrical machine which converts
mechanical energy into electrical energy. The generator is usually driven by a
steam turbine or water turbine which is called as prime mover.
The dc generator operates on the principle based on the Faraday’s Law
of electromagnetic induction. The generator should have (i) magnetic field (ii)
conductors capable of carrying current (iii) movement of conductors in the
magnetic field. Necessary magnetic field is produced by field coil. The set of
conductors is called the armature.
Imagine an elementary set up with just two poles ‘N’ and ‘S’ and a single
turn coil placed in between them on a rotor. When the rotor with the coil (called
armature) is rotated, the two conductors, i.e. coil sides, ‘aa’ and ‘bb’ will come
under the influence of north pole and south pole alternatively. So the emf
induced in each conductor will be reversing when coming under N and S poles
repeatedly. If we terminate each conductor i.e coil side on a separate ring and
collect the current through brushes touching the two rings the current collected
would be alternating (a.c).
To make the current collected unidirectional or D.C. the coil sides are
soldered to split copper blocks as shown. Now the currents coming out of
brushes will be unidirectional (d.c) because the brushes alternately contact
different coil sides. Such an arrangement of split copper block is called
commutator that helps getting D.C. outside.
So we need to have three main parts namely field system (poles & pole
winding or field winding), armature and commutator.
= flux/pole in weber
Z = total number of armature conductors = No. of slots x No. of conductors/slot
P = No. of generator poles
A = No. of parallel paths in armature
N = armature rotation in revolutions per minute (r.p.m)
E = e.m.f induced in any parallel path in armature
Generated e.m.f Eg = e.m.f generated in any one of the parallel paths i.e E.
Average e.m.f generated /conductor = d/dt volt (n=1)
Now, flux cut/conductor in one revolution d = P
Wb No. of revolutions/second = N/60
Time for one revolution, dt = 60/N second
d PN
dt 60
PN Z ZPN
volt
60 2 120
For a simplex lap-wound generator
PN Z ZN
volt
60 P 120
PN P
Eg 60 A volt
Where A = 2 - for simplex wave-winding
= P - for simplex lap-winding
Armature current Ia = IL
Terminal voltage V = Eg – Ia Ra
Electric power developed = EgIa
2
Power delivered to load = EgIa – I
a
= Ia (Eg-IaRa) = VIa
Figure 7.2
(ii) Self-Excited DC. Generators
A DC. Generator whose field magnet winding is supplied current from the
output of the generator itself is called a self-excited generator. There are three
types of self-excited generators depending upon the manner in which the field
winding is connected to the armature, namely;
(a) Series generator;
(b) Shunt generator;
(c) Compound generator
(a) Series generator
In a series wound generator, the field winding is connected in series with
armature winding so that whole armature current flows through the field winding
as well as the load. Fig. (7.3) shows the connections of a series wound generator.
Since the field winding carries the whole of load current, it has a few turns of
thick wire having low resistance. Series generators are rarely used except for
special purposes e.g., as boosters.
= EgIa – Iaaseag
2(R +R )=I [E – I(Rase+R )]
= VIa or VIa
Figure 7.3
Figure 7.4
Figure 7.5
The dc motor is rotating electrical machine which converts electrical energy into
mechanical energy. Construction of dc motor is exactly similar to dc generator.
In a dc motor, both the armature and the field windings are connected
to a dc supply. Thus, we have current carrying armature conductors placed in a
stationary magnetic field. Due to electromagnetic torque exerted on the armature
conductors, the armature starts revolving. Thus, electrical energy is converted
into mechanical energy in the armature.
Since same flux is linking both the primary and secondary coils
f =frequency of supply
Figure 7.10
Figure 7.10 shows the variation of flux in the core. Since is zero at t=0 and =m at
T 1
t , i.e t .
4 4f
m
Therefore, average rate of change of flux 4 volt
f
m
1/ 4 f
rms value of emf induced in the primary winding, E 4.44 f N 4.44 fN B A volt
1 m 1 1 m
rms value of emf induced in the sec ondary winding, E 4.44 f N 4.44 fN B A volt
2 m 2 2 m
E 1 N1
E2 N
2
Thus,
(i) If N1 N2, E1 E2, it is called step down transformer. i.e., secondary
voltage less as compared to primary voltage
(ii) If N1 N2, E1 E2, it is called step up transformer. i.e., secondary
voltage greater as compared to primary voltage
E1
Voltage ratio N1
E2 N2
E 1 I1 = E 2 I2
I1
Then the current ratio
I 2 E2 N2
E1 N1
K = V2 / V1 = E2 / E1 = I1/ I2
Laminated Core:
Laminated silicon steel core is made up of ‘L’, ‘E’ & ‘I’ shaped stampings
depending on the type of transformer. Silicon steel ensures reduced hysteresis
loss and laminated core results in reduction of eddy current loss.
Winding:
The primary and secondary windings of copper are placed on the vertical
limbs of the core. They are electrically isolated and magnetically linked through
core.
Transformer Tank:
The transformer assembly with core and windings is placed in an
aluminum tank. This tank acts as an enclosure and cooling surface.
Transformer oil:
This is mineral oil obtained by refining crude petroleum. This is filled in the
tank. It serves two purposes.
a) acts as a cooling medium
b) acts as an insulator between tank and transformer assembly.
Conservator:
This is a cylindrical tank placed over the main tank. It is connected
through pipe to transformer tank. The transformer tank is filled with the oil while
conservator is partially filled. It acts as a reservoir to take in and let out oil as the
oil in the main tank expands or contracts with increase or decrease in load.
Breather:
As the oil expands the level in the conservator raises and the air is
released. Air is breathed in when the level goes down. This breathing in and out
of air by conservator is through breather. Breather is a small vessel containing
drying agent ‘silica gel’. This ensures presence of only dry air devoid of moisture.
Buchholz Relay:
Moisture ingress affects the insulating property of oil and hence is
detrimental. Buchholz relay is provided to sense this condition and protect
transformer by taking it out of service.
7.4.6 Application of transformers
The field rotates at the synchronous speed, Ns 120 f where ‘f’ is the frequency of
= P
supply and ‘P’ is the number of poles for which the stator is wound.
This rotating magnetic field cuts across the stationery rotor conductors
and emf is induced. By keeping the rotor winding internally closed circuit, current
flows through it. Now the current carrying rotor conductors placed in magnetic
field experience a force. As per Lenz’s law the direction of induced emf, current
and force is in such direction as to oppose the cause of producing it, which in
this case is relative speed between rotating magnetic field and stationery
conductors. Hence the force produced rotates the rotor in the direction of
rotating magnetic field so as to reduce relative velocity. The rotor, however
cannot catch up and rotate at synchronous speed of field, because if it does so,
the relative speed would become zero and then there is no induced emf, no
current and hence no torque. The rotor therefore runs at a speed, N, slightly less
Stator:
Stator is the stationary part of the motor. The stator cores consist of high
grade, low loss electrical sheet-steel stampings assembled in the frame. Slots are
provided on the inner periphery of the stator to accommodate the stator
conductors. Required numbers of stator conductors are housed in the slots.
These conductors are arranged to form a balanced three phase winding. The
stator winding may be connected in star or delta.
Rotor:
Figure 7.14 (a) Squirrel cage rotor of three phase induction motor
7.6 Alternator
Alternator is an ac generator. It works on the principle of electromagnetic
induction. Unlike DC generator there is no need for commutator. Another major
difference is that unlike DC machines alternator has stator as armature and rotor
as filed. This is to facilitate lighter field winding on rotating mass and ease of
tapping 3 phase supply from stationery armature winding.
The rotor winding is energized from the DC exciter and alternate N and S
poles are developed on the rotor. When the rotor is rotated in anti-clockwise
direction by a prime mover, the stator or armature conductors are cut by the
magnetic flux of rotor poles. Consequently, e.m.f. is induced in the armature
conductors due to electromagnetic induction. The induced e.m.f. is alternating
since N and S poles of rotor alternately pass the armature conductors. The
direction of induced e.m.f. can be found by Fleming’s right hand rule and
frequency is given by
PN
f 120 ; where P = number of poles & N = speed of rotor in rpm.
The magnitude of the voltage induced in each phase depends upon the
rotor flux, the number and position of the conductors in the phase and the speed
of the rotor.
Figure 7.17
Fig. (7.17(i)) shows star-connected armature winding and d.c. field winding.
When the rotor is rotated, a 3-phase voltage is induced in the armature winding.
The magnitude of induced e.m.f. depends upon the speed of rotation and the d.c.
exciting current. The magnitude of e.m.f. in each phase of the armature winding is
the same. However, they differ in phase by 120°electrical as shown in the phasor
diagram in Fig. (7.15 (ii)).
7.6.3 Application of alternator:
The centrifugal switch disconnects the capacitor and auxiliary winding as the
rotor accelerates.
Problem 1
A 220-V d.c machine has on armature resistance of 0.5. If the full-load armature
current is 20A, find the induced emf when the machine acts as (i) generator (ii)
motor.
Figure 7.21
Solution:
Problem 3
A 250V, 4-pole, wave-wound dc series motor has 782 conductors on its armature.
It has armature and series field resistance of 0.75 ohm. The motor takes a current
of 40A. Estimate its speed and gross torque developed if it has a flux per pole of
25 mWb.
Problem 4
The maximum flux density in the core of a 250/3000 volts, 50Hz single – phase
transformer is 1.2 Wb/m2. If the emf per turn is 8 volt, determine (i) primary
and secondary turns (ii) area of the core
Solution
(i) E1 = N1 emf induced / turn
N1 = 250/8 = 32, N2 = 3000/8 = 375
(ii) We may use E2 = 4.44 f N2 Bm A
3000 = 4.44 50 375 1.2
A A = 0.03 m2 .
Problem 5
A 25kVA transformer has 500 turns on the primary and 50 turns on the secondary
winding. The primary is connected to 3000-V, 50Hz supply. Find the full-load
primary and secondary currents, the secondary emf and the maximum flux in the
core. Neglect leakage drops and no-load primary current
Solution:
N
K = 50 1
2
500 10
N1
Problem 6
A 25kVA single-phase transformer has 250 turns on the primary and 40 turns on
the secondary winding. The primary is connected to 1500 volt, 50Hz mains.
Calculate (i) Primary and Secondary currents on full-load (ii) Secondary emf (iii)
maximum flux in the core.
Solution: (i) If V2 = Secondary voltage rating = secondary emf
V2 40
, given V2 = 240 volts
250
1500
(ii) Primary current = 25000/1500 = 16.67 amp
m = 0.027 Wb or 27mWb.
Problem 7
An 8 pole dc shunt generator with 778 wave connected armature conductors and
running at 500 rpm supplies a load of 12.5 resistance at terminal voltage of 50V.
The armature resistance is 0.24 and the field resistance is 250. Find the
armature current, the induced emf and the flux per pole
Figure 7.22
Introduction
The main objective of this chapter is to explore the electrical
measurement and measuring instruments. Different types of these
instruments have been discussed in details
8.1 Introduction
Tests and measurements are important in designing, evaluating,
maintaining and servicing electrical circuits and equipment. In order to
detect electrical quantities such as current, voltage, resistance or power, it
is necessary to transform an electrical quantity or condition into a visible
indication. This is done with the aid of instruments (or meters) that indicate
the magnitude of quantities either by the position of a pointer moving over
a graduated scale (called an analogue instrument) or in the form of a
decimal number (called a digital instrument).
Figure 8.1 (a) Construction of PMMC Figure 8.1 (b) Spring control
instrument
Fig. 8.1(a) shows the basic construction of a PMMC instrument. A
moving coil instrument consists basically of a permanent magnet to
provide a magnetic field and a small light weight coil is wound on a
rectangular soft iron core that is free to rotate around its vertical axis.
When a current is passed through the coil windings, a torque is developed
on the coil by the interaction of the magnetic field and the field set up by
the current in the coil. The aluminum pointer attached to rotating coil and
the pointer moves around the calibrated scale indicating the deflection of
the coil. To reduce parallax error a mirror is usually placed along with the
scale. A balance weight is also attached to the pointer to counteract its
weight (see Fig. 8.1(b)). To use PMMC device as a meter, two problems
must be solved. First, a way must be found to return the coil to its original
position when there is no current through the coil. Second, a method is
needed to indicate the amount of coil movement. The first problem is
solved by the use of hairsprings attached to each end of the coil as shown
in Fig. 8.1(a). These hairsprings are not only supplying a restoring torque
but also provide an electric connection to the rotating coil. With the use of
hairsprings, the coil will return to its initial position when no current is
flowing though the coil. The springs will also resist the movement of coil
when there is current through coil. When the developing force between the
magnetic fields (from permanent magnet and electro magnet) is exactly
equal to the force of the springs, the coil rotation will stop. The coil set up
is supported on jeweled bearings in order to achieve free movement. Two
other features are considered to increase the accuracy and efficiency of
this meter movement. First, an iron core is placed inside the coil to
concentrate the magnetic fields. Second, the curved pole faces ensure that
the turning force on the coil increases as the current increases.
It is assumed that the coil sides are situated in a uniform radial
magnetic field of flux densityB ( wb/m2 ) , let the length of a coil side (within
the magnetic field) be l (meter), and the distance from each coil side to the
axis be r (meter).
Principle of operation: It has been mentioned that the interaction between
the induced field and the field produced by the permanent magnet causes a
deflecting torque, which results in rotation of the coil.
This instrument consists of a few soft iron discs (B) that are fixed to
the spindle (D), pivoted in jeweled bearings. The spindle (D) also carries a
pointer (P), a balance weight (W), a controlling weight (W) and a damping
piston (E), which moves in a curved fixed cylinder (F). The special shape of
the moving-iron discs is for obtaining a scale of suitable form.
Basic principle of operation
In moving iron instruments the movable system consists of one or more
pieces of specially-shaped soft iron, which are so pivoted as to be acted
upon by the magnetic field produced by the current in coil.
The brief description of different components of a moving-iron
instrument is given below.
Moving element: a small piece of soft iron in the form of a vane or
rod
Coil: to produce the magnetic field due to current flowing through it
and also to magnetize the iron pieces.
In repulsion type, a fixed vane or rod is also used and magnetized
with the same polarity.
Control torque is provided by spring or weight (gravity)
Damping torque is normally pneumatic, the damping device
consisting of an air chamber and a moving vane attached to the instrument
spindle.
Deflecting torque produces a movement on an aluminum pointer over a
graduated scale.
Advantages:
1. The instruments are suitable for use in ac and dc circuits.
2. The instruments are robust, owing to the simple construction of the
moving parts.
3. The stationary parts of the instruments are also simple.
4. Instrument is low cost compared to moving coil instrument.
5. Torque/weight ratio is high, thus less frictional error.
Errors:
1. Errors due to temperature variation.
2. Errors due to friction is quite small as torque-weight ratio is high in
moving-iron instruments.
3. Stray fields cause relatively low values of magnetizing force
produced by the coil. Efficient magnetic screening is essential to
reduce this effect.
4. Error due to variation of frequency causes change of reactance of
the coil and also changes the eddy currents induced in neighboring
metal.
5. Deflecting torque is not exactly proportional to the square of the
current due to non-linear characteristics of iron material.
Fixed coil: The magnetic field is produced by the fixed coil which is
divided into two sections to give more uniform field near the centre and to
allow passage of the instrument shaft.
Moving coil: The moving coil is wound either as a self-sustaining coil
or else on a non-magnetic former. A metallic former cannot be used, as
eddy currents would be induced in it by alternating field. Light but rigid
construction is used for the moving coil. It should be noted that both fixed
and moving coils are air cored.
Springs: The controlling torque is provided by two control springs.
These hairsprings also act as leads of current to the moving coil.
Dampers: Air friction damping is employed for these instruments
and is provided by a pair of Aluminum-vanes attached to the spindle at the
bottom. These vanes move in a sector shaped chamber.
Shielding: Since the magnetic field produced by fixed coils is weaker
than that in other types of instruments, these meters need a special
magnetic shielding. Electro-dynamic instruments are effectively shielded
from the effects of external magnetic fields by enclosing the mechanism in
a laminated iron hollow cylinder with closed ends.
Operating Principle
Let us consider the currents in the fixed and moving coils are if and im
respectively. The action of electrodynamic instrument depends upon the
force exerted between fixed and moving coils. The flux density B ( wb/m2 )
produced by the fixed coil is proportional to if (fixed coil current). The force
on the conductors of the moving coil, for a given strength field, will be
proportional to im (moving coil current) and the number of turns ‘N’ of the
moving coil. In case of ammeter and voltmeter fixed and moving coils are
connected in series and the developed torque is due to the interaction of
the magnetic fields produced by currents in the fixed and moving coils and
thus it will be proportional to i2 (if = im =i). Thus, dynamic instruments can
be used for dc and ac measurements.
A.C operation: The dynamometer instrument is used to measure
alternating current or voltage, the moving coil due to its inertia takes up a
position where the average deflecting torque over a complete cycle is
balanced by the restoring torque of the spiral spring. The deflecting torque
is proportional to the mean value of the square of the current or voltage
(note both coils are connected in series for ammeters or voltmeters), and
the instrument scale can therefore be calibrated to read rms values of
alternating current or voltage.
Basic operation
Induction instruments operate in alternating-current circuits and they
are useful only when the frequency and the supply voltage are
approximately constant. The most commonly used technique is the shaded
pole induction watt-hour meter, shown in fig.8.5 (b).
ii) second flux (2) interacting with the eddy currents (Ie1) induced
by the first flux (1).
In the induction type single phase energy meter, the flux produced by
shunt magnet (pressure or voltage coil current) sh lags behind the applied
voltage V by almost 90°. The flux is produced by the load current I and
se
is in the direction of I
se
Introduction
In this chapter, different types of wiring used for domestic
applications along with wiring accessories and materials are discussed.
Additionally, different types of gas discharged lamps and earthing are also
introduced in details.
9.1 House wiring
House wiring deals with the distribution system arranged within the
domestic premises. Wiring requirement varies with customer to customer.
House wiring generally done on either 230 V single phase or 440 V three
phase supply. In the latter case, total load is divided among the three
phases. An earth wire will also run connecting all the power plugs from
where large quantity of electrical energy is tapped by using electrical
appliances like heater, electric iron, hot plate, air conditioner etc.
Cleat Wiring: This type of wiring is not used practically for permanent
wiring and is only suitable for temporary wiring purposes such as for
marriages with advantages of saving in labour and overall cost. The
porcelain or wooden cleats are very easy to erect and fixed at a distance of
4.5 cm to 15 cm apart. V.I.R or P.V.C wires are normally used in this
system, though T.R.S wires can also be installed in special cleats for
certain types of installations.
C.T.S. (T.R.S) wiring (Batten Wiring): The wires used in such a wiring are
sheathed in tough rubber of P.V.C. wires and they are carried on wooden
batten with clips. This wiring is suitable for damp climate, but cannot
withstand much heat and so is not suitable for places of very hot weather
and there is also danger of mechanical damage and fire hazard. C.T.S wires
are not suitable for outdoor use. Therefore they should not be exposed to
direct sunlight and where there are corrosive acids fumes. At such places,
now P.V.C. wires can be easily used.
Casing and capping wiring: This is most common type of wiring used for
indoor and domestic installations. This system was introduced 60 years
ago when it was considered necessary to provide some protection to
conductors. V.I.R. wires are carried in two or triple channel of wooden
casing and closed by wooden capping.
The obvious objections to the wooden casing and capping system
are that wood is very inflammable, even though with a coating of paints of
shellac varnish, it is not damp-proof. This type of wiring should not be
used where there is danger of mechanical damage or fire hazards
according to I.E Rules. Due to defects in wood and high cost of wood now-
a-days P.V.C. casing capping is used. These are cheaper in cost and easy
to handle. The wiring look is also fine-looking and no paint coating is
required.
Conduit Wiring: In this system V.I.R. wires or P.V.C wires are carried
through steel or iron pipes giving protection from mechanical injury or fire
risks. For workshops and public buildings, this is the best and most
desirable system of wiring. It gives very good appearance when concealed.
Now-a-days, P.V.C. conduit pipes are also available which do not require
any threading. These are flexible and can be bent easily. For concealed
wiring, the pipes are directly buried in the wall and roofs and then wires are
drawn through them.
The tube is filled with argon gas and a drop of mercury. Oxide
coated tungsten filaments are used as electrodes at the two ends of the
long tube. The circuit is completed through choke or ballast and a starter
as shown in figure 9.4. Glow starters are commonly used. It is a voltage
operated device and has two bi metallic contacts (electrodes) enclosed in a
glass tube filled with argon or mixture of helium and hydrogen.
When the supply voltage is applied, discharge takes place in the
glow starter as their electrodes are closer. The gas inside gets heated and
this closes the bi metallic contacts. Current flows through the closed
circuit of choke, main electrodes and starter and the main electrodes are
heated with this current. Now with closed contacts in the glow starter, no
more voltage exists between the bi metallic contacts and the discharge
ceases. The gas cools down and the contacts open. The circuit is now
open and the current does not flow. This making and breaking of circuit
momentarily induces high voltage of the order of 1000 volts in the choke
which added with supply voltage initiates discharge between the main
electrodes through argon gas and the fluorescent lamp starts giving light.
Once the discharge is initiated a much lower voltage than normal voltage is
sufficient to maintain the discharge. Thereafter the choke acts only to
reduce voltage available across the main electrodes. The capacitor
connected across the starter helps to suppress electromagnetic waves
generated at the gap due to sparking which may have radio interference
with other device connected.
Fluorescent lamp produces white light. The average life is 7500
hours. The light output is 70 lumens per watt. They have poor colour
rendering especially for red colour.
When the supply is switched on, the lamp would not start as the
supply voltage is too low to start the discharge. The leak transformer
connected across the mains produces a starting voltage of about 400V.
The neon gas starts the discharge, and afterwards the sodium vapourises
and the discharge continues. The discharge in neon gas gives red-orange
glow. Once the metallic sodium vapourises, it produces mono-chromatic
yellow light. The lamp will come up to its rated light output in
approximately 15 minutes.
The power factor is very low, about 0.3; hence a capacitor is used to
raise it. The efficiency is approximately 75 lumens per watt and the lamp
has an average life of 6000 hrs.
The lamp must be operated horizontally, or nearly so, to keep the
sodium well spread out along the tube.
The major application of this type of lamp is for high way and general
out door lighting where colour discrimination is not required, such as
street lighting, parks, railway yards, storage yards etc. They have very
poor colour rendering characteristic.
When the supply is switched on, the supply voltage is applied across
the electrodes, but is not sufficient enough to cause discharge between the
two main electrodes. But this voltage is high enough for initiating a
discharge over the very short distance between the main electrode and the
auxiliary electrode. This discharge then spreads rapidly and sets up
discharge between the main electrodes. The argon initiates the discharge,
vapourises the mercury and after some time the mercury vapourises and
the discharge continues.
The choke is provided to limit the current to a safe value. This choke
lowers the power factor. So a capacitor is connected across the circuit to
improve power factor. The lamp gives greenish blue colour light. It takes 3
to 4 minutes for the full light output to appear. When the supply is
interrupted, the lamp must cool down and the vapour pressure be reduced
for it to be restarted.
The efficiency of mercury vapour lamp is about 40 lumens per watt.
These lamps must be operated vertically, since if they are used
horizontally convection will cause the discharge to touch the glass bulb,
which will fail. Lamps of this type are used for general industrial lighting,
railway yards, ports, work areas, shopping centres etc. They are used flood
lights to improve the architectural beauty of buildings, hoardings etc.
9.10 Earthing
A wire coming from the ground 2.5 to 3 meters deep from an
electrode is called earthing.
The earth’s potential is always taken as zero for all purposes. The
electrical appliances or machines when connected with earth attain zero
potential and are said to be earthed.
All metal bodies of electrical equipments like motors, water heaters
etc are to be connected to earth. By earthing we mean a metallic
connection (by copper or GI wire) of the body to the earth mass for the
safety of the human being from electric shock. Earth is considered to be at
zero potential and it is a low resistance path. This low resistance path
allows the current from the supply line to flow through it whenever there is
risk of some live wire accidentally coming into contact with the body. Thus
the user is protected in case of any accidental touch with such facility
equipment.
9.10.1 Objective of earthing
1. To save human life from danger or shock or death by
blowing fuse of any apparatus which becomes leaky.
2. To protect large buildings from atmospheric lightning.
3. To protect all machines fed from O.H lines through
lighting arresters.
4. To maintain the line voltage constant ( neutral of every
alternator, transformer is earthed)
9.10.2 Good earthing
Good earthing is that earthing which gives very low resistance to the
flow of heavy current (short circuit current) of a circuit. The earth
resistance for copper wire is 1 ohm and for G.I wire it should not be more
than 3 ohms.
Steps should be taken to reduce earth resistance
1. By pouring water
2. Increase in plate area
3. Increase in depth
4. Electrodes in parallel
The contact surface area of G.I pipe with soil is more in comparison
to the plate because of its circular sections and hence can take up heavy
leakage current for the same electrode size. The earth wire connection with
the G.I. pipe being above the ground level can be checked for carrying out
continuity test as and when desired while in plate earthing it is difficult also
It is an advantage over the plate earthing.
Introduction
Present day three phase generator used to generate 3-phase power are
called alternator (synchronous generators). An alternator has a balanced
three phase winding on the stator and called the armature. The three coils
are so placed in space that their axes are mutually 120° apart as shown in
figure 10.1. From the terminals of the armature, 3-phase power is obtained.
Rotor houses a field coil which is being excited by D.C. The field coil
produces flux and electromagnetic poles on the rotor surface. If the rotor is
driven by an external agency, the flux linkages with three stator coils
become sinusoidal function of time and sinusoidal voltage is induced in
them. However, the induced voltages in the three coils (or phases) will
differ in phase by 120° because the present value of flux linkage with R-
phase coil will take place after 120°with Y-phase coil and further 120°after,
with B-phase coil. A salient pole alternator has projected poles as shown in
figure 10.1(a). It has non uniform air gap and is generally used where speed
is low. On the other hand a non salient pole alternator has uniform air gap
(figure 10.1(b)) and used when speed is high.
Frequency, voltage & interconnected system
The frequency of the generated emf for a p polar generator is given
p p
f=
b where n is speed of the generator in rps or f= n when n is in
n2 120