DIMM - DUAL INPUT MONITOR MODULE
SPECIFICATIONS
Operating Voltage 17~41 VDC
Average Current Consumption 600µA(Typical)
Alarm Current 30mA
Dimensons 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
Max. Humidity 90% RH, non-condensing
Mounting 4" square electrical box
DESCRIPTION
STANDARD FEATURES
The Hochiki Dual Monitor Module (DIMM) is designed
• Fast, reliable contact monitoring utilizing the for use on the FireNET analog addressable system.
Hochiki DCP (Digital Communications Protocol) It provides two independent contact monitoring cir-
• 127 devices can be used per DCP loop cuits while only utilizing one address on the SLC loop.
• Bi-colored indicating LED provides module status Up to 127 devices can be placed on a single SLC
loop. The device address is uniquely stored on an
• Dual input contact monitor
onboard EEPROM. The module can be programmed
• Can be programmed to monitor Normally Open to monitor normally open (NO) or normally closed
(NO) or Normally Closed (NC) contacts (NC) contact fire alarm and supervisory devices. The
• Operates on Class A or Class B SLC loop interrupt driven Digital Communication Protocol (DCP)
• Accepts up to 14 AWG wire combines maximum communication reliability and
• Mounts to 4" square gang box fast response to emergency conditions. The module
has a single bi-colored LED to indicate device sta-
tus. It fits into a standard 4" square or double gang
electrical back box.
PRODUCT LISTINGS
Underwriters Laboratories: S5694
CSFM #: 7300-0410:150
Specifications subject to change without notice. Continued on back.
Hochiki America Corporation Find latest revision at www.hochiki.com
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or
[email protected] F0003 11/2005
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DIMM. The modules shall be UL listed and compatible with the Hochiki FireNET fire alarm control panel.
The device address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate
device status.
Back Side of a DIMM
WIRING DIAGRAM
U.L. LISTED
E.O.L. DEVICE 22K DCP-DIMM OUT TO NEXT MODULE
PART NUMBER Dual Input Monitor Module
0400-01000 TB2
TYPICAL WIRING FOR N/O CONTACTS ONLY
SER. NO. XXXXXXXXX -
+ +
TB1
Input A
E.O.L. DEVICE 22K
PART NUMBER
0400-01000 - S + + U.L. LISTED
COMPATIBLE
+ SC - - FIRE CONTROL
ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE
DEVICES MAY BE USED . Input B PANEL
-
TYPICAL WIRING FOR N/C CONTACTS ONLY
S5694
SIGNALING DEVICE AND INHERENTLY POWER LIMITED.
U.L. LISTED ISSUE NO. AU-6031
E.O.L. DEVICE 22K
E.O.L. DEVICE 22K PART NUMBER
PART NUMBER 0400-01000
0400-01000
CAUTION!
DO NOT CONNECT MORE
THAN ONE N/C CONTACT
TO AN INPUT!
Hochiki America Corporation DIMM Specifications subject to change without notice.