Fanuc AC Servo Amplifier Manual
Fanuc AC Servo Amplifier Manual
Descriptions Manual
2.2
ORDERING
INFORMATION
2.2.1
200–V Input Series
(1) Power Supply Module (PSM)
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
PSM–15 A06B–6087–H115
PSM–37 A06B–6087–H137
See Chapter 3 for details of how to select the power supply module.
NOTE
PSM–11 and PSM–45 require forced air cooling from the outside. See (7) in Section 2.2.3 and
Chapter 7.
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
NOTE
For the PSMR, a regenerative discharge unit is required. See (8) in Section 2.2.3, Section
3.4.5, and Section 8.1.7.
14
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM1–12 A06B–6079–H101
38060172
SVM1–20 A06B–6079–H102
SVM1–40S A06B–6079–H103
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM1–12 A06B–6096–H101
38060172
SVM1–20 A06B–6096–H102
SVM1–40S A06B–6096–H103
NOTE
1 For the SVM1–130, forced air cooling may be required depending on the motor used. See (7)
in Section 2.2.3 and Chapter 7.
2 A dynamic brake module (DBM) is required whenever the SVM1–240 or SVM1–360 is used.
In the event of an emergency stop, for example, the dynamic brake module stops the motor
immediately by short–circuiting the power line of the motor without PWM control. SVMs other
than SVM1–240 and SVM1–360 have the dynamic brake function built in.
15
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM2–12/12 A06B–6079–H201
SVM2–20/20 A06B–6079–H203
SVM2–12/40 A06B–6079–H204
SVM2–40/40 A06B–6079–H206
SVM2–40/80 A06B–6079–H207
SVM2–40L/40L A06B–6079–H209
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM2–12/12 A06B–6096–H201
SVM2–20/20 A06B–6096–H203
SVM2–12/40 A06B–6096–H204
SVM2–40/40 A06B–6096–H206
SVM2–40/80 A06B–6096–H207
SVM2–40L/40L A06B–6096–H209
16
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM3–12/12/12 A06B–6079–H301
SVM3–12/12/20 A06B–6079–H302
38060172
SVM3–12/20/20 A06B–6079–H303
SVM3–12/12/40 A06B–6079–H305
SVM3–20/20/40 A06B–6079–H307
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM3–12/12/12 A06B–6080–H301
SVM3–12/12/20 A06B–6080–H302
38090172
SVM3–12/20/20 A06B–6080–H303
SVM3–12/12/40 A06B–6080–H305
SVM3–20/20/40 A06B–6080–H307
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM3–12/12/12 A06B–6096–H301
SVM3–12/12/20 A06B–6096–H302
38090172
SVM3–12/20/20 A06B–6096–H303
SVM3–12/12/40 A06B–6096–H305
SVM3–20/20/40 A06B–6096–H307
17
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–15 A06B–6088–H215#H500
Standard
SPM–22 A06B–6088–H222#H500
380150307
SPM–26 A06B–6088–H226#H500
SPM–30 A06B–6088–H230#H500
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–15 A06B–6088–H315#H500
Standard
SPM–22 A06B–6088–H322#H500
380150307
SPM–26 A06B–6088–H326#H500
SPM–30 A06B–6088–H330#H500
18
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
(c) Type 3 (specifications for spindle switching control or differential speed control)
Applicable detectors :
1. Spindle switching control
(switching the speed only, or switching both the speed and position)
2. Differential speed control (input circuit for position coder signals)
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–11 A06B–6078–H411#H500
SPM–15 A06B–6078–H415#H500
SPM–30 A06B–6078–H430#H500
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–5.5 A06B–6078–H106#H500
38090307
SPM–11 A06B–6078–H111#H500 (Note)
SPM–15 A06B–6088–H115#H500
Standard
SPM–22 A06B–6088–H122#H500
380150307
SPM–26 A06B–6088–H126#H500
SPM–30 A06B–6088–H130#H500
NOTE
SPM–11 (except type 3) and SPM–45 require forced air cooling from the outside. See (7) in
Section 2.2.3 and Chapter 7.
19
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPMC–5.5 A06B–6082–H206#H512
38090307
SPMC–11 A06B–6082–H211#H512 (Note)
Standard
SPMC–15 A06B–6082–H215#H512
SPMC–26 A06B–6082–H226#H512
NOTE
SPMC–11 requires forced air cooling from the outside. See (7) in Section 2.2.3 and Chapter
7.
2.2.2
400–V Input Series
(1) Power supply module (PSM–HV)
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
NOTE
1 The PSM–HV requires a capacitor module (PSMC–HV). Specify an appropriate capacitor
module for the PSM–HV being used, according to (2) in Section 2.2.2.
2 The PSM–75HV requires forced air cooling from the outside. See (7) in Section 2.2.3 and
Chapter 7.
20
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
NOTE
No capacitor module (PSMC–HV) is required.
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM1–20HV A06B–6085–H102
SVM1–60HV A06B–6085–H104
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM1–20HV A06B–6097–H102
SVM1–60HV A06B–6097–H104
21
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM2–20/20HV A06B–6085–H201
SVM2–20/40HV A06B–6085–H202
SVM2–20/60HV A06B–6085–H203
Standard 38090307
SVM2–40/40HV A06B–6085–H204
SVM2–40/60HV A06B–6085–H205
SVM2–60/60HV A06B–6085–H206
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SVM2–20/20HV A06B–6097–H201
SVM2–20/40HV A06B–6097–H202
SVM2–20/60HV A06B–6097–H203
Standard 38090307
SVM2–40/40HV A06B–6097–H204
SVM2–40/60HV A06B–6097–H205
SVM2–60/60HV A06B–6097–H206
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–15HV A06B–6092–H215#H500
SPM–45HV A06B–6092–H245#H500
22
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–15HV A06B–6092–H315#H500
SPM–45HV A06B–6092–H345#H500
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
External dimensions
Category Name Ordering number Remarks
(H x W x D mm)
SPM–15HV A06B–6092–H115#H500
SPM–45HV A06B–6092–H145#H500
NOTE
SPM–11HV and SPM–75HV require forced air cooling from the outside. See (7) in Section
2.2.3 and Chapter 7.
23
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
2.2.3
Others
(1) AC reactor
For PSM–5.5 or
A81L–0001–0122
PSM–11
PSM–18HV,
A81L–0001–0127
30HV, 45HV
24
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
25
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
NOTE
1 Connectors are classified into either the press–mount type or solder type, depending on the
method used for attaching a cable to a connector. When a connector is specified, therefore,
care is necessary.
2 When attaching a cable to a press–mount type connector, use the special tools prepared by
the manufacturer of the connector. For the tool specifications, see ”Connection tools”
described later.
– Connector configuration
Configuration of A06B–6071–K203
26
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
NOTE
1 Type A interface
2 Type B interface
Configuration of A06B–6073–K215
27
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
Use: For the M sensor, MZ sensor, BZ sensor, high–resolution position coder, or high–resolution magnetic pulse coder
α C series: For the speed meter, analog override, or motor overheat
28
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
Configuration of A06B–6098–K200
– Connection tools
Manufacturers of press–mount type connectors provide special tools for attaching the connectors to cables.
(b) Connectors manufactured by Honda Tsushin Kogyo Co., Ltd. (press–mount type connectors only)
(5) Fuses
Fuses are specified as spare parts of the fuses used in modules. The ordering drawing number of the fuses
required for each module and the fuse configuration are shown below.
29
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
– Fuse configuration
Configuration of A06B–6073–K250
Configuration of A06B–6073–K252
Configuration of A06B–6077–K250
Configuration of A06B–6081–K250
Configuration of A06B–6098–K250
NOTE
For the AC reactor unit
30
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
For PSMR–3
A80L–0024–0006
(at 2kw output)
For PSMR–3
A80L–0026–0003
(at 3kw output)
For PSM–5.5
For PSMR–5.5 A06B–6052–J001
Power Primary 380/415/460VAC
(at 5.5kw output)
transformer Secondary 200VAC
Optional
O tional
Power Primary 380/415/460VAC
For PSM–11
transformer Secondary 200VAC
For PSMR–5.5 A06B–6044–J006
(at 7.5kw output)
31
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
380/415/460VAC
Rated primary voltage 230VAC (The secondary is used as an autotransformer.)
+10% –15%, 50/60"1Hz, 3Φ
15A (at 380V) 30A (at 380V) 46A (at 380V) 68A (at 380V) 97A (at 380V)
Rated primary current 14A (at 415V) 28A (at 415V) 42A (at 415V) 63A (at 415V) 89A (at 415V)
13A (at 460V) 25A (at 460V) 38A (at 460V) 56A (at 460V) 80A (at 460V)
Weight Max. 61kg Max. 115kg Max. 165kg Max. 260kg Max. 375kg
Outline drawing Fig. 8.1.5 (a) Fig. 8.1.5 (b) Fig. 8.1.5 (c) Fig. 8.1.5 (d) Fig. 8.1.5 (f)
32
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
380/415/460VAC
200/220/230/240VAC, ∆ connection
230VAC (The secondary is used as an auto-
Rated primary voltage 380/415/460/480/550VAC, Y connection
transformer.)
"15%, 50/60Hz"2Hz; 3Φ
+10% –15%, 50/60"1Hz, 3Φ
Class B Class H
Insulation
(maximum allowable temperature: 130°C) (maximum allowable temperature: 180°C)
Outline drawing Fig. 8.1.5 (e) Fig. 8.1.5 (a) Fig. 8.1.5 (b) Connection diagram
200V
(Neutral point)
Connection diagram
(Primary) (Secondary)
33
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
AC380V R – 6, S – 14, T – 22
AC400V R – 4, S – 12, T – 20
AC415V R – 4, S – 12, T – 20
Make 8–16 and 16–24 connections by
y using
g supplied
cables.
AC440V R – 3, S – 11, T – 19
AC460V R – 3, S – 11, T – 19
AC480V R – 2, S – 10, T – 18
Cable A660–8001–T532 2
Cable A660–8004–T926 2
Bolt A30L–0001–0021 4
(b) Connection points of power transformers for PSMR–5.5, PSM–5.5, PSM–11, PSM–15, PSM–26,
PSM–30, PSM–37, and PSM–45
34
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
200VAC +10%
–15%
380VAC
400VAC
415VAC
440VAC
460VAC
480VAC
AC input voltage (V)
NOTE
1 When installing a transformer in a cabinet, be careful to
ensure that the transformer does not thermally affect other
equipment. For example, separate the transformer from the
other equipment.
2 When installing a transformer outside the cabinet, make
sure that the transformer is not directly exposed to cutting
chips or coolant.
3 If there is a possibility of the transformer falling, secure the
transformer with bolts or similar.
PSM–45, SPM–45,
A06B–6078–K003 (Note)
PSM–75HV, SPM–75HV
NOTE
SVM1–130 requires forced air cooling only when it is being used to drive the α22/3000,
α30/3000, α40/2000 (with a fan), αL25/3000, αL50/2000, or αM40/3000.
35
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
See Section 8.1.7, ”SELECTING A REGENERATIVE DISCHARGE UNIT” for details of selection.
(9) Cables
Applicable terminal–to–termi-
Category Name Between terminals Ordering number
nal distance
NOTE
K823 to K830 are used for 300–mm–wide modules.
36
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
A06B–6078–K809 150mm
A06B–6078–K810 100mm
Cable for connection
Optional
O tional
of modules (Note 2)
A06B–6082–K808 200mm
A06B–6082–K809 150mm
A06B–6082–K810 100mm
NOTE
1 The following three cables are supplied together. The ordering drawing number differs
depending on the cable length.
K4: For 200–VAC power supply for cooling fan (between CX1B and CX1A)
K5: For 24–VDC control power supply (between CX2B and CX2A)
K8: For interface between modules (between JX1B and JX1A)
2 The following two cables are supplied together. The ordering drawing number differs
depending on the cable length.
K5: For 24–VDC control power supply (between CX2B and CX2A)
K8: For interface between modules (between JX1B and JX1A)
NOTE
Each cable is 7 m long.
37
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
A66L–6001–0023#L150R0 15cm
Internal optical cables
(Note 1)
A66L–6001–0023#L300R0 30cm
A66L–6001–0026#L1R003 1m
A66L–6001–0026#L5R003 5m
FSSB inter-
Optional A66L–6001–0026#L7R003 7m
face cables
External optical cables
A66L–6001–0026#L10R03 10m
(Note 2)
A66L–6001–0026#L20R03 20m
A66L–6001–0026#L30R03 30m
A66L–6001–0026#L50R03 50m
NOTE
1 Optical cables for connecting SVMs.
SVM (COP10A) – SVM(COP10B)
2 Optical cables for connecting the CNC and SVM.
CNC (COP10A) – SVM (COP10B)
38
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
NOTE
1 For the installation positions of the circuit breakers and magnetic contactor, see Section 2.1.
2 Circuit breakers 1 and 2 must have a rated voltage of 200VAC or higher.
3 The current and voltage of the operation coil of the magnetic contactor must be within the rating
of the internal contact [CX3 (MCC)] of the PSM. For details, see (6) in Section 9.2.1.
4 When PSMR–5.5 is used with a rated output capacity of 5.5 kW
5 When PSMR–5.5 is used with a rated output capacity of 7.5 kW
PSM name Circuit breaker 1 Circuit breaker 2 Circuit breaker 2 Magnetic contactor Remarks
PSMV–11HV – 5A 5A 60A
NOTE
1 For the installation positions of the circuit breakers and magnetic contactor, see Section 2.1.
2 Circuit breakers 1 and 3 must have a rated voltage of 400VAC or higher.
3 Circuit breaker 2 must have a rated voltage of 200VAC or higher.
4 The current and voltage of the operation coil of the magnetic contactor must be within the
ratings of the internal contact [CX3 (MCC)] of the PSM. For details, see (6) in Section 9.2.1.
39
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
PSMR–5.5,
PSM–5.5 A06B–6077–K102 8–1–9–(b) Fuji Electric EA103B/50 Fuji Electric BZ–TB20B–3
PSM–18HV
PSM–15,
A06B–6077–K104 8–1–9–(d) Fuji Electric EA103B/75 Fuji Electric BZ–TB20B–3
PSM–30HV
For control
A06B–6077–K106 8–1–9–(j) Fuji Electric EA33/5 Fuji Electric BZ–TB10B–503
power supply
PSMR–5.5,
PSM–5.5 A06B–6077–K122 8–1–10–(b) Fuji Electric SC–1N Fuji Electric SZ–1N/T
PSM–18HV
PSM–11,
PSM–30HV A06B–6077–K123 8–1–10–(b) Fuji Electric SC–2N Fuji Electric SZ–1N/T
PSMV–11HV
Optional PSM–15 A06B–6077–K124 8–1–10–(c) Fuji Electric SC–2SN Fuji Electric SZ–2SN/T
PSM–26,
A06B–6077–K125 8–1–10–(d) Fuji Electric SC–4N Fuji Electric SZ–4N/T
PSM–45HV
PSM–37,
A06B–6077–K128 8–1–10–(g) Fuji Electric SC–7N Fuji Electric SZ–5N/T
PSM–75HV
NOTE
The coil voltage specification of the magnetic contactor is 200VAC.
40
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
– Recommended parts
Parts manufactured by Fuji Electric Co., Ltd.
PSM name Circuit breaker 1 Circuit breaker 2 Circuit breaker 2 Magnetic contactor Remarks
NOTE
For details, see the brochures available from Fujitsu Electric Co., Ltd. Note that the
specification of the coil voltage of a magnetic contactor may differ depending on the supply
voltage and frequency used.
To protect equipment from surge voltages caused by lightning, install a lightning surge protector between lines and
between a line and ground. For how to install protectors, see Appendix A. For the outline drawings of lightning surge
protectors, see Section 8.1.11.
41
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
NOTE
1 For the 200–V input series main power supply and control power supply, and the 400–V input
series control power supply
2 For the 400–V input series main power supply
3 Tûv approved products
– Recommended products
HF3005C–TMA 5A
HF3010C–TMA 10A
HF3015C–TMA 15A
HF3020C–TMA 20A
HF3030C–TMA 30A
HF3040C–TMA 40A
Leakage current:
HF3050C–TMA 50A AC460V 5.3 mA max
at 460VAC
460VAC, 60 Hz
HF3060C–TMA 60A
HF3080C–TMA 80A
HF3100C–TMA 100A
HF3150C–TMA 150A
HF3200C–TMA 200A
HF3250C–TMA 250A
For details, refer to the brochures supplied by SOSHIN ELECTRIC CO., LTD.
42
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
3SUP–AH series and 3SUP–DH series manufactured by Okaya Electric Industries Co., Ltd.
Part number (Okaya Electric Industries) Rated current Rated voltage Remarks
3SUP–D75H–ER–4 75A
Leakage current:
3SUP–D100H–ER–4 100A 4 mA max
AC500V at 500VAC
500VAC, 60 Hz
3SUP–D150H–ER–4 150A
3SUP–D200H–ER–4 200A
For details, refer to the brochures supplied by Okaya Electric Industries Co., Ltd.
NF3020C–TX 20A
NF3030C–TX 30A
NF3050C–TX 50A
Leakage
g current:
250 mA max
NF3080C–TX 80A AC460V
at 460VAC,, 60 Hz
NF3100C–TX 100A (Note)
NF3150C–TX 150A
NF3200C–TX 200A
For details, refer to the brochures supplied by SOSHIN ELECTRIC CO., LTD.
FN258–7 7A
FN258–16 16A
FN258–30 30A
FN258–42 42A
Leakage
g current:
150 mA max
FN258–55 55A AC480V
at 250VAC,, 50 Hz
FN258–75 75A (Note)
FN258–100 100A
FN258–130 130A
FN258–180 180A
43
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
NOTE
The NF3000C–TX series manufactured by SOSHIN ELECTRIC CO., LTD. and the FN258
series manufactured by SCHAFFNER have a large line–to–ground capacitor capacitance,
allowing a very high leakage current. Therefore, they can be used only for neutral grounding
type power supplies.
(13) Detectors
α position coder
BZ sensor
44
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
Type V, 20,000min–1
Magnetic sensor RIP A57L–0001–0037#RIP
Water–proof connector specification
Type X, 15,000min–1
Magnetic sensor U2IP A57L–0001–0037#U2IP
Water–proof connector specification
45
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
(14) Others
NOTE
These parts are required when the interface with the CNC is type B or FSSB, and
absolute–position detection is performed. The battery for the absolute pulse coder can be
connected using one of following two methods:
Connection method 1: A special lithium battery is installed in the α amplifier.
– Use A06B–6073–K001.
Connection method 2: A battery case (A06B–6050–K060) is used.
– Use A06B–6050–K061 or a commercially available size–D battery.
– A cable (A06B–6093–K810) is required.
46
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
2.1 The FANUC series consists of the following units and parts:
CONFIGURATION
2.1.1
200–V Input Series
(1) Power supply module (PSM) (Basic)
(2) Power supply module (register discharge type) (PSMR) (Basic)
(3) Servo amplifier module (SVM) (Basic)
(4) Spindle amplifier module (SPM) (Basic)
(5) Spindle amplifier module (SPMC) (Basic)
(6) AC reactor (Basic)
(7) Connectors (for connection cables) (Basic)
(8) Fuses (Basic)
(9) Power transformer (Optional)
(10) Fan adaptor (Optional)
(11) AC line filter (Basic)
(12) Regenerative discharge unit (Basic)
(13) Dynamic brake module (DBM) (Basic)
8
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
ÃÃ ÃÃ Ã ÃÃ
Power supply Spindle amplifier Servo amplifier Servo amplifier
module module module (2–axes) module (2–axes)
ÃÃ
ÃÃ
L+
L–
ÃÃ
ÃÃ ÃÃ ÃÃ
ÃÃÃÃÃÃÃ ÃÃ
AC input
for control PSM
ÃÃÃÃÃÃÃ
DC link (300VDC)
ÃÃ
supply SPMC
200R,
ÃÃ ÃÃ ÃÃ
200S
ÃÃ ÃÃ Ã
ÃÃ ÃÃ
Circuit 1φ
UL VL WL UL VL WL
breaker 2 L1 L2 L3 UVW UM VM WM UM VM WM
Fan
motor
Lightening surge
absorbers
: Basic
: Optional
: Units prepared by the machine tool builder
NOTE
1 See Chapter 3 for details of how to combine the power supply module, servo amplifier modules,
and spindle amplifier modules.
2 A magnetic contactor, AC reactor, and circuit breakers are always required.
3 To protect the unit from surge currents caused by lightning, connect surge absorbers between
lines, and between the lines and ground, at the power inlet of the power magnetics cabinet.
See APPENDIX A for details.
9
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
ÃÃ Ã ÃÃ
Power supply Spindle amplifier Servo amplifier
module module module (2–axes)
ÃÃ
L+
ÃÃ ÃÃ
ÃÃÃÃÃÃÃÃÃ
L–
ÃÃ
AC input
ÃÃ ÃÃÃÃÃÃÃ DC link (300VDC)
ÃÃ
for control PSMR SPM SVM
power SPMC
supply 200R,
ÃÃ Ã ÃÃ
200S,
1φ RE1 RE2
ÃÃ Ã ÃÃ Ã
TH1 TH2 UL VL WL
RST UVW UM VM WM
ÃÃÃ
(400VAC) 3φ
motor
(460VAC)
ÃÃÃ 1φ
ÃÃÃ Servo
ÃÃÃ
motor
3φ 3φ
Circuit Lightening surge Spindle motor
breaker 2 absorbers
: Basic
: Optional
: Units prepared by the machine tool builder
NOTE
1 See Chapter 3 for details of how to combine the power supply module, servo amplifier modules,
and spindle amplifier modules.
2 A magnetic contactor, AC line filter, regenerative discharge unit, and circuit breakers are always
required.
3 To protect the unit from surge currents caused by lightning, connect surge absorbers between
lines, and between the lines and ground, at the power inlet of the power magnetics cabinet.
See APPENDIX A for details.
4 When an insulating transformer is installed, high–frequency noise to the power supply is
reduced, so the AC line filter is not required. If the insulating transformer is installed outside
the power magnetics cabinet, and the cable connecting the amplifier is exposed, the cable must
be covered with a grounded metal duct, or an AC line filter must be installed.
10
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
2.1.2
400–V Input Series
11
2. CONFIGURATION AND ORDERING INFORMATION B–65162E/03
ÃÃ ÃÃ ÃÃ ÃÃ
module module module module (2–axes)
ÃÃ
L+
ÃÃ
ÃÃ ÃÃ
L–
DC link
ÃÃ ÃÃ
ÃÃ ÃÃ
Control power supply (DC600V)
(AC200V)
AC input
(AC230V) PSM–HV PSMC–HV SPM–HV SVM–HV
1φ
ÃÃ
200R
ÃÃ
Circuit 200S,
ÃÃ Ã
ÃÃ
breaker 2
ÃÃ ÃÃ
Lightning surge UL VL WL
L1 L2 L3 UVW UM VM WM
protector
Circuit Magnetic AC
(AC400V) breaker 1 contactor reactor
(AC460V) Fan
motor Servo
3φ motor
3φ
Circuit
breaker 3 Spindle motor Servo
Lightening surge motor
protector
: Basic configuration
: Equipment to be prepared by the user
NOTE
1 For the control power supply, single–phase 200VAC is required.
2 Install circuit breakers, a magnetic contactor, and AC reactor.
3 At the power supply inlet of the power magnetics cabinet, install lightning surge protectors
between the lines and between a line and ground to protect the equipment from surge voltages
caused by lightning. For details, see Appendix A.
4 Note that when PSM–75HV is used, the position of the PSMC–HV differs from the above
diagram. For the position of the PSMC–HV, see (5) in Section 5.1.
5 Measures must be taken to detect the operation (trip) of circuit breaker 3.
12
B–65162E/03 2. CONFIGURATION AND ORDERING INFORMATION
ÃÃ ÃÃ Ã ÃÃ
module module module (2–axes) module (2–axes)
ÃÃ
L+
ÃÃ
L– ÃÃ
ÃÃ ÃÃ ÃÃ
ÃÃ
DC link (DC300V)
(AC200V)
(AC230V) PSMV–HV PMS SVM SVM
1φ 1φ
ÃÃ SPMC
ÃÃ
200R
Circuit 200S,
ÃÃ ÃÃ ÃÃ
ÃÃ
breaker 2
400R,400S
ÃÃ ÃÃ ÃÃ
Lightning surge 400T UL VL WL UL VL WL
protector L1 L2 L3 UVW UM VM WM UM VM WM
Magnetic
(AC400V) contactor
(AC460V)
Fan
motor Servo Servo
3φ motor motor
AC reactor unit
: Basic configuration
: Equipment to be prepared by the user
NOTE
1 For the control power supply, single–phase 200VAC is required.
2 Install a magnetic contactor and AC reactor. Always connect the magnetic contactor closer to
the input power supply than the AC reactor unit.
3 At the power supply inlet of the power magnetics cabinet, install lightning surge protectors
between the lines and between a line and ground to protect the equipment from surge voltages
caused by lightning. For details, see Appendix A.
4 Measures must be taken to detect the operation (trip) of circuit breaker 3.
13