455 Rosemount 2051 Product Document

The document is a product data sheet for the Rosemount 2051 Pressure Transmitter from April 2013. It describes the transmitter's key features such as its Coplanar platform that enables integration of primary elements, manifolds, and remote seal solutions. It offers best in class performance with up to 0.05% high accuracy and protocols including HART, FOUNDATION fieldbus, PROFIBUS PA, and WirelessHART. The transmitter is available in differential, gage, and absolute pressure measurement types across various pressure ranges and with different output options.

Uploaded by

AJITH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
312 views84 pages

455 Rosemount 2051 Product Document

The document is a product data sheet for the Rosemount 2051 Pressure Transmitter from April 2013. It describes the transmitter's key features such as its Coplanar platform that enables integration of primary elements, manifolds, and remote seal solutions. It offers best in class performance with up to 0.05% high accuracy and protocols including HART, FOUNDATION fieldbus, PROFIBUS PA, and WirelessHART. The transmitter is available in differential, gage, and absolute pressure measurement types across various pressure ranges and with different output options.

Uploaded by

AJITH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Product Data Sheet

April 2013
00813-0100-4101, Rev JA

Rosemount 2051 Pressure Transmitter

 Coplanar™ platform enables integration of primary elements, manifolds, and remote seal solutions
 Best in Class performance with up to 0.05% high accuracy option
 IEC 62591 (WirelessHART™) Protocol enables cost effective installations

 Local Operator Interface (LOI) offers easy to use configuration capabilities at the transmitter

 Protocols available include HART® 4-20 mA, FOUNDATION™ fieldbus, PROFIBUS PA, HART 1-5 Vdc Low
Power

 Selectable HART Revision prepares your plant for the latest HART capabilities while ensuring seamless
integration with today's systems

 SIL2 safety certification to IEC 61508 is available with the full 4-20 mA HART offering to simplify
compliance
Rosemount 2051 April 2013

Rosemount 2051 Pressure Transmitter Product Offering


FOUNDATION of reliable measurement

Differential, gage, and absolute pressure measurement

Select from an extensive offering of DP Flowmeters, Liquid Level, Manifolds and


Flanges.

Available with variety of protocols and materials.

Industry leading capabilities extended to IEC 62591


(WirelessHART)

Cost effectively implement wireless on the industry's most proven platform

Optimize safety with the industry's only intrinsically safe Power Module

Eliminate wiring design and construction complexities to lower costs by 40-60%

Quickly deploy new pressure, level and flow measurements in 70% less time

Innovative, integrated DP Flowmeters

Fully assembled and leak tested for out-of-the-box installation

Reduce straight pipe requirements, lower permanent pressure loss, and achieve
accurate measurement in small line sizes

Up to 2.00% volumetric flow accuracy at 5:1 turndown

Proven, reliable, and innovative DP Level technologies

Connect to virtually any process with a comprehensive offering of process


connections, fill fluids, direct mount or capillary connections and materials

Quantify and optimize total system performance with QZ option

Optimize level measurement with cost efficient Tuned-System Assemblies

Instrument manifolds – quality, convenient, and easy

Designed and engineered for optimal performance with Rosemount transmitters

Save installation time and money with factory assembly

Offers a variety of styles, materials, and configurations

Table of Contents
Rosemount 2051C Coplanar Pressure Transmitter . 3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Rosemount 2051T In-Line Pressure Transmitter . . . 12 Product certifications . . . . . . . . . . . . . . . . . . . . . . . . .60
Rosemount 2051CF Flowmeters . . . . . . . . . . . . . . . . 19 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . .68
Rosemount 2051L Liquid Level Transmitter . . . . . . . 42

2 [Link]
April 2013 Rosemount 2051

Rosemount 2051C Coplanar Pressure Transmitter

Configuration Transmitter Output Code


4-20 mA HART®
2051 A
2051 with Selectable HART(1)
Lower Power
2051 M
(1)
2051 with Selectable HART
FOUNDATION Fieldbus F
Profibus W
Wireless X
2051C Coplanar
Pressure Transmitter (1) The 4-20mA with Selectable HART device can be ordered with Transmitter
Output option code A plus any of the following options codes: M4, QT, DZ,
CR, CS, CT, HR5, HR7.

Additional Information
Specifications: page 50
Certifications: page 60
Dimensional Drawings: page 68
Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Model Transmitter type

2051C Coplanar Pressure Transmitter

Measurement Type

Standard Standard

D Differential ★

G Gage ★

Pressure Range

Standard Standard

2051CD 2051CG
-25 to 25 inH2O (-62.2 to 62.2 ★
1 -25 to 25 inH2O (-62.2 to 62.2 mbar)
mbar)
-250 to 250 inH2O (-623 to 623 ★
2 -250 to 250 inH2O (-623 to 623 mbar)
mbar)
-1000 to 1000 inH2O (-2.5 to 2.5 ★
3 -393 to 1000 inH2O (-0.98 to 2.5 bar)
bar)
4 -300 to 300 psi (-20.7 to 20.7 bar) -14.2 to 300 psi (-0.98 to 20.7 bar) ★

-2000 to 2000 psi (-137.9 to 137.9 ★


5 -14.2 to 2000 psi (-0.98 to 137.9 bar)
bar)

[Link] 3
Rosemount 2051 April 2013

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Output

Standard Standard
(1) ★
A 4–20 mA with Digital Signal Based on HART Protocol
F FOUNDATION fieldbus Protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded

M Low-Power, 1–5 Vdc with Digital Signal Based on HART Protocol

Materials of Construction

Process Flange Type Flange Material Drain/Vent

Standard Standard

2 Coplanar SST SST ★

3(2) Coplanar Cast C-276 Alloy C-276 ★

5 Coplanar Plated CS SST ★


(2) ★
7 Coplanar SST Alloy C-276
8(2) Coplanar Plated CS Alloy C-276 ★

0 Alternate Process Connection ★

Isolating Diaphragm

Standard Standard

2(2) 316L SST ★


(2) ★
3 Alloy C-276
Expanded

5(3)(4) Tantalum

O-ring

Standard Standard

A Glass-filled PTFE ★

B Graphite-filled PTFE ★

Sensor Fill Fluid

Standard Standard

1 Silicone ★
(4) ★
2 Inert

4 [Link]
April 2013 Rosemount 2051

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Housing Material Conduit Entry Size

Standard Standard

A Aluminum ½–14 NPT ★

B Aluminum M20 × 1.5 ★

J SST ½–14 NPT ★


(5) ★
K SST M20 × 1.5
(6) ★
P Engineered Polymer No Conduit Entries

Expanded

D Aluminum G½
M(5) SST G½

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard

WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★

Antenna and SmartPower

Standard Standard

WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


PlantWeb Control Functionality

Standard Standard

A01 FOUNDATION fieldbus Advanced Control Function Block Suite ★

Alternate Flange(7)

Standard Standard

H2 Traditional Flange, 316 SST, SST Drain/Vent ★


(2) ★
H3 Traditional Flange, Cast C-276, Alloy C-276 Drain/Vent
H7(2) Traditional Flange, 316 SST, Alloy C-276 Drain/Vent ★

HJ DIN Compliant Traditional Flange, SST, 7/16 in. Adapter/Manifold Bolting ★

FA Level Flange, SST, 2 in., ANSI Class 150, Vertical Mount ★

FB Level Flange, SST, 2 in., ANSI Class 300, Vertical Mount ★

FC Level Flange, SST, 3 in., ANSI Class 150, Vertical Mount ★

FD Level Flange, SST, 3 in., ANSI Class 300, Vertical Mount ★

FP DIN Level Flange, SST, DN 50, PN 40, Vertical Mount ★

FQ DIN Level Flange, SST, DN 80, PN 40, Vertical Mount ★

[Link] 5
Rosemount 2051 April 2013

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Expanded

HK(8) DIN Compliant Traditional Flange, SST, 10 mm Adapter/Manifold Bolting


HL DIN Compliant Traditional Flange, SST, 12 mm Adapter/Manifold Bolting

Manifold Assembly(8)(9)

Standard Standard

S5 Assemble to Rosemount 305 Integral Manifold ★

S6 Assemble to Rosemount 304 Manifold or Connection System ★

Integral Mount Primary Element(8)(9)

Standard Standard

Assemble to Rosemount Annubar® Flowmeter or Rosemount ★


S4(10)
1195 Integral Orifice
S3 Assemble to Rosemount 405 Primary Element ★

Seal Assemblies(9)

Standard Standard

S1(11) Assemble to one Rosemount 1199 diaphragm seal ★

S2(12) Assemble to two Rosemount 1199 diaphragm seals ★

Mounting Brackets

Standard Standard

B1 Traditional Flange Bracket for 2-in. Pipe Mounting, CS Bolts ★

B2 Traditional Flange Bracket for Panel Mounting, CS Bolts ★

B3 Traditional Flange Flat Bracket for 2-in. Pipe Mounting, CS Bolts ★

B4 Coplanar Flange Bracket for 2-in. Pipe or Panel Mounting, all SST ★

B7 B1 Bracket with Series 300 SST Bolts ★

B8 B2 Bracket with Series 300 SST Bolts ★

B9 B3 Bracket with Series 300 SST Bolts ★

BA SST B1 Bracket with Series 300 SST Bolts ★

BC SST B3 Bracket with Series 300 SST Bolts ★

6 [Link]
April 2013 Rosemount 2051

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Product Certifications

Standard Standard

E1(5) ATEX Flameproof ★


(5) ★
E2 INMETRO Flameproof
E3(5) China Flameproof ★
(5) ★
E4 TIIS Flameproof
E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(5) ★
E7 IECEx Flameproof
EW India (CCOE) Flameproof Approval ★

I1(5) ATEX Intrinsic Safety ★


(5) ★
I2 INMETRO Intrinsically Safe
(5) ★
I3 China Intrinsic Safety
I4(5)(6) TIIS Intrinsic Safety ★

I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★

I7(5) IECEx Intrinsic Safety ★

IA(13) ATEX FISCO Intrinsic Safety ★

IE(14) FM FISCO Intrinsically Safe ★

IF(14) CSA FISCO Intrinsically Safe ★


(14) ★
IG IECEx FISCO Intrinsically Safe
(5) ★
IW India (CCOE) Intrinsically Safe
K1(5) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K2 INMETRO Flameproof and Intrinsic Safety ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★

K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★


(5) ★
K7 IECEx Flameproof, Intrinsic Safety, Type n and Dust
(5) ★
KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★
(5) ★
KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2
(5) ★
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe
N1(5) ATEX Type n ★

N7(5) IECEx Type n ★


(5) ★
ND ATEX Dust

Drinking Water Approval

Standard Standard

DW(15) NSF Drinking Water Approval ★

[Link] 7
Rosemount 2051 April 2013

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Shipboard Approvals

Standard Standard

SBS(4) American Bureau of Shipping (ABS) Type Approval ★


(4) ★
SBV Bureau Veritas (BV) Type Approval
SDN(4) Det Norske Veritas (DNV) Type Approval ★
(4) ★
SLL Lloyds Register (LR) Type Approval

Bolting Materials

Standard Standard

L4 Austenitic 316 SST Bolts ★

L5 ASTM A 193, Grade B7M Bolts ★

L6 Alloy K-500 Bolts ★

L8 ASTM A 193 Class 2, Grade B8M Bolts ★

Display and Interface Options

Standard Standard

M4(14) LCD Display with Local Operator Interface ★

M5 LCD display ★

Hardware Adjustments

Standard Standard

D4(16) Zero and Span Configuration Buttons ★

DZ(17) Digital Zero Trim ★

Flange Adapters

Standard Standard

DF(18) 1
/2-14 NPT Flange Adapters ★

Conduit Plug

Standard Standard

DO(4)(19) 316 SST Conduit Plug ★

RC 1/4 RC 1/2 Process Connection

Expanded

D9(20) RC 1/4 Flange with RC 1/2 Flange Adapter - SST

Ground Screw

Standard Standard

V5(4)(21) External Ground Screw Assembly ★

Performance

Standard Standard

P8(22) High Performance Option ★

8 [Link]
April 2013 Rosemount 2051

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transient Protection

Standard Standard

T1(4)(23) Transient Protection Terminal Block ★

Software Configuration

Standard Standard

Custom Software Configuration (Completed CDS 00806-0100-4101 or 00806-0100-4100 for Wireless ★


C1 (17)
required with order)
Alarm Limit

Standard Standard

C4(16)(24) NAMUR alarm and saturation levels, high alarm ★


(16)(24) ★
CN NAMUR alarm and saturation levels, high alarm
CR(16) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★
(16) ★
CS Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
(16) ★
CT Low Alarm (standard Rosemount alarm and saturation levels)

Pressure Testing

Expanded

P1 Hydrostatic testing with certificate

Cleaning Process Area

Expanded

P2 Cleaning for Special Service


P3 Cleaning for < 1 PPM Chlorine/Flourine
Maximum Static Line Pressure

Standard Standard

P9 4500 psig (310 bar) Static Pressure Limit (2051CD Ranges 2-5 only) ★

Calibration Certification

Standard Standard

Q4 Calibration Certificate ★

QG Calibration Certificate and GOST Verification Certificate ★

QP Calibration certification and tamper evident seal ★

Material Traceability Certification

Standard Standard

Q8 Material Traceability Certification per EN 10204 3.1 ★

[Link] 9
Rosemount 2051 April 2013

Table 1. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Quality Certification for Safety

Standard Standard

QS(25) Prior-use certificate of FMEDA data ★


(25) ★
QT Safety Certified to IEC 61508 with certificate of FMEDA

Surface Finish

Standard Standard

Q16 Surface finish certification for sanitary remote seals ★

Toolkit Total System Performance Reports

Standard Standard

QZ Remote Seal System Performance Calculation Report ★

Conduit Electrical Connection

Standard Standard

GE(4) M12, 4-pin, Male Connector (eurorast®) ★

GM(4) A size Mini, 4-pin, Male Connector (minifast®) ★

HART Revision Configuration

Standard Standard

HR5(16)(26) Configured for HART Revision 5 ★

HR7(16)(27) Configured for HART Revision 7 ★

Typical Model Number: 2051C D 2 A 2 2 A 1 A B4 M5

(1) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision
7 factory configured, add option code HR7.

(2) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(3) Available in Ranges 2-5 only.

(4) Not available with output code X.

(5) Not available with Low Power output code M.

(6) Only available with output code X.

(7) Requires 0 code in Materials of Construction for Alternate Process Connection.

(8) Not valid with optional code P9 for 4500 psi Static Pressure.

(9) “Assemble-to” items are specified separately and require a completed model number.

(10) Process Flange limited to Coplanar (codes 2, 3, 5, 7, 8) or Traditional (H2, H3, H7).

(11) Not valid with optional code D9 for RC1/2 Adaptors.

(12) Not valid with optional codes DF and D9 for Adaptors.

10 [Link]
April 2013 Rosemount 2051

(13) Only valid with FOUNDATION fieldbus output code F.

(14) Not available with FOUNDATION fieldbus output code F and Wireless Output Code X.

(15) Not available with Alloy C-276 isolator (3 code), tantalum isolator (5 code), all cast C-276 flanges, all plated CS flanges, all DIN flanges, all Level flanges, assemble-to
manifolds (S5 and S6 codes), assemble-to seals (S1 and S2 codes), assemble-to primary elements (S3 and S4 codes), surface finish certification (Q16 code), and remote
seal system report (QZ code).

(16) Only Available with HART 4-20 mA (output codes A and M).

(17) Only available with HART 4-20 mA Output (Output Codes A and M) and Wireless Output (Output Code X).

(18) Not valid with Alternate Process Connection options S3, S4, S5, S6.

(19) Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.

(20) Not available with Alternate Process Connection: DIN Flanges and Level Flanges.

(21) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(22) Available with 4-20 mA HART output code A, Wireless output code X, FOUNDATION fieldbus output code F, 2051C Ranges 2-5 or 2051T Ranges 1-4, SST diaphragms and
silicone fill fluid. High Performance Option includes 0.05% Reference Accuracy, 5 year stability and improved ambient temperature effect specifications. See
Performance specifications for details.

(23) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA and IE.

(24) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(25) Only available with HART 4-20 mA output (output code A).

(26) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(27) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.

[Link] 11
Rosemount 2051 April 2013

Rosemount 2051T In-Line Pressure Transmitter

Configuration Transmitter Output Code


4-20 mA HART®
2051 A
2051 with Selectable HART(1)
Lower Power
2051 M
(1)
2051 with Selectable HART
FOUNDATION Fieldbus F
2051T In-Line Profibus W
Wireless Pressure Transmitter Wireless X

(1) The 4-20mA with Selectable HART device can be ordered with Transmitter
Output option code A plus any of the following options codes: M4, QT, DZ,
CR, CS, CT, HR5, HR7.

Additional Information
Specifications: page 50
Certifications: page 60
Dimensional Drawings: page 68
20 Ordering Information

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Model Transmitter Type

Standard Standard
2051T In-Line Pressure Transmitter ★

Pressure Type

Standard Standard

G Gage ★
(1) ★
A Absolute

Pressure Range

Standard Standard
2051TG 2051TA ★

1 -14.7 to 30 psi (-1.0 to 2.1 bar) 0 to 30 psi (0 to 2.1 bar) ★

2 -14.7 to 150 psi (-1.0 to 10.3 bar) 0 to 150 psi (0 to 10.3 bar) ★

3 -14.7 to 800 psi (-1.0 to 55 bar) 0 to 800 psi (0 to 55 bar) ★

4 -14.7 to 4000 psi (-1.0 to 276 bar) 0 to 4000 psi (0 to 276 bar) ★

5 -14.7 to 10000 psi (-1.0 to 689 bar) 0 to 10000 psi (0 to 689 bar) ★

12 [Link]
April 2013 Rosemount 2051

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Output

Standard Standard
(2) ★
A 4–20 mA with Digital Signal Based on HART Protocol
F FOUNDATION fieldbus Protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded

M Low-Power, 1–5 Vdc with Digital Signal Based on HART Protocol

Process Connection Style

Standard Standard
2B 1
/2–14 NPT female ★

2C(3) G1/2 A DIN 16288 male (Available in SST for Range 1-4 only) ★

Expanded

2F(4) Coned and Threaded, Compatible with Autoclave Type F-250-C (Range 5 only)

Isolating Diaphragm Process Connection Wetted Parts Material

Standard Standard
2(5) 316L SST 316L SST ★
(5) ★
3 Alloy C-276 Alloy C-276

Sensor Fill Fluid

Standard Standard
1 Silicone ★
(4) ★
2 Inert
Housing Material Conduit Entry Size

Standard Standard
A Aluminum ½–14 NPT ★

B Aluminum M20 × 1.5 ★

J SST ½–14 NPT ★


(6) ★
K SST M20 × 1.5
P(7) Engineered Polymer No Conduit Entries ★

Expanded

D Aluminum G½
(6)
M SST G½

[Link] 13
Rosemount 2051 April 2013

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard

WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★

Antenna and SmartPower

Standard Standard

WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


PlantWeb Control Functionality

Standard Standard

A01 FOUNDATION fieldbus Advanced Control Function Block Suite ★★

Manifold Assemblies

Standard Standard

S5(8) Assemble to Rosemount 306 Integral Manifold ★★

Seal Assemblies

Standard Standard
(8) ★★
S1 Assemble to one Rosemount 1199 diaphragm seal

Mounting Bracket

Standard Standard

B4 Bracket for 2-in. Pipe or Panel Mounting, All SST ★★

14 [Link]
April 2013 Rosemount 2051

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Product Certifications

Standard Standard
(6) ★
E1 ATEX Flameproof
(6) ★
E2 INMETRO Flameproof
E3(6) China Flameproof ★
(6) ★
E4 TIIS Flameproof
E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(6) ★
E7 IECEx Flameproof
(6) ★
EW India (CCOE) Flameproof Approval
I1(6) ATEX Intrinsic Safety ★
(6) ★
I2 INMETRO Intrinsically Safe
(6) ★
I3 China Intrinsic Safety
I4(6)(7) TIIS Intrinsic Safety ★

I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★

I7(6) IECEx Intrinsic Safety ★


(10) ★
IA ATEX FISCO Intrinsic Safety
(10) ★
IE FM FISCO Intrinsically Safe
IF(10) CSA FISCO Intrinsically Safe ★
(10) ★
IG IECEx FISCO Intrinsically Safe
(6) ★
IW India (CCOE) Intrinsic Safety Approval
K1(6) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★

K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★

K7(6) IECEx Flameproof, Intrinsic Safety, Type n, Dust ★


(6) ★
KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★

KC(6) FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 ★


(6) ★
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe
(6) ★
N1 ATEX Type n
N7(6) IECEx Type n ★

ND(6) ATEX Dust ★

Drinking Water Approval

Standard Standard
DW(9) NSF Drinking Water Approval ★

[Link] 15
Rosemount 2051 April 2013

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Shipboard Approvals

Standard Standard
(4) ★
SBS American Bureau of Shipping (ABS) Type Approval
(4) ★
SBV Bureau Veritas (BV) Type Approval
SDN(4) Det Norske Veritas (DNV) Type Approval ★
(4) ★
SLL Lloyds Register (LR) Type Approval

Display and Interface Options

Standard Standard
(10) ★
M4 LCD Display with Local Operator Interface
M5 LCD display ★

Hardware Adjustments

Standard Standard
D4(11) Zero and Span Configuration Buttons ★

DZ(12) Digital Zero Trim ★

Wireless SST Sensor Module

Standard Standard
WSM(7) Wireless SST Sensor Module ★

Conduit Plug

Standard Standard
(4)(13) ★
DO 316 SST Conduit Plug

Ground Screw

Standard Standard
(4)(14) ★
V5 External Ground Screw Assembly

Performance

Standard Standard
P8(15) High Performance Option ★

Terminal Blocks

Standard Standard
(4)(16) ★
T1 Transient Protection Terminal Block

Software Configuration

Standard Standard
Custom Software Configuration (Completed CDS 00806-0100-4101 or 00806-0100-4100 for Wireless ★
C1(12)
required with order)

16 [Link]
April 2013 Rosemount 2051

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Alarm Limits

Standard Standard
(11)(17) ★
C4 Analog Output Levels Compliant with NAMUR Recommendation NE 43, Alarm High
(11)(18) ★
CN Analog Output Levels Compliant with NAMUR Recommendation NE 43, Alarm Low
CR(11) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★
(11) ★
CS Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
(11) ★
CT Low Alarm (standard Rosemount alarm and saturation levels)

Pressure Testing

Expanded

P1 Hydrostatic testing with certificate

Cleaning Process Area(19)

Expanded

P2 Cleaning for Special Service


P3 Cleaning for <1 PPM Chlorine/Fluorine

Calibration Certification

Standard Standard
Q4 Calibration Certificate ★

QG Calibration Certificate and GOST Verification Certificate ★

QP Calibration Certificate and tamper evident seal ★

Material Traceability Certification

Standard Standard
Q8 Material Traceability Certification per EN 10204 3.1 ★

Quality Certification for Safety

Standard Standard
QS(18) Prior-use certificate of FMEDA data ★
(18) ★
QT Safety Certified to IEC 61508 with certificate of FMEDA

Surface Finish

Standard Standard
Q16 Surface finish certification for sanitary remote seals ★

Toolkit Total System Performance Reports

Standard Standard
QZ Remote Seal System Performance Calculation Report ★

[Link] 17
Rosemount 2051 April 2013

Table 2. Rosemount 2051T In-Line Pressure Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Conduit Electrical Connector

Standard Standard
(4) ® ★
GE M12, 4-pin, Male Connector (eurofast )
(4) ® ★
GM A size Mini, 4-pin, Male Connector (minifast )

HART Revision Configuration

Standard Standard
(11)(20) ★
HR5 Configured for HART Revision 5
(11)(21) ★
HR7 Configured for HART Revision 7

Typical Model Number: 2051T G 3 A 2B 2 1 A B4 M5

(1) Wireless Output (code X) only available in absolute measurement type (code A) in range 1-5 with 1/2 14 NPT process connection (code 2B), and housing code (code
P)

(2) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART
Revision 7 factory configured, add option code HR7.

(3) Wireless output (code X) only available in G1/2 A DIN 16288 Male process connection (code 2C) with range 1-4, 316 SST isolating diaphragm (code 2), silicone fill
fluid (code 1), and housing code (code P).

(4) Not available with output code X.

(5) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(6) Not available with Low Power output code M.

(7) Only available with output code X.

(8) “Assemble-to” items are specified separately and require a completed model number.

(9) Not available with coned and threaded connection (2F code), assemble-to manifold (S5 code), assemble-to seal (S1 code), surface finish certification (Q16 code),
remote seal system report (QZ code).

(10) Not available with FOUNDATION fieldbus output code F or Wireless output code X

(11) Only Available with HART 4-20 mA (output codes A and M).

(12) Only available with HART 4-20 mA Output (output code A and M) and Wireless Output (output code X).

(13) Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.

(14) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(15) Available with 4-20 mA HART output code A, Wireless output code X, FOUNDATION fieldbus output code F, 2051C Ranges 2-5 or 2051T Ranges 1-4, SST diaphragms
and silicone fill fluid. High Performance Option includes 0.05% Reference Accuracy, 5 year stability and improved ambient temperature effect specifications. See
Performance Specifications for details.

(16) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA and IE.

(17) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(18) Only available with HART 4-20 mA output (output code A).

(19) Not valid with Alternate Process Connection S5.

(20) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(21) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
18 [Link]
April 2013 Rosemount 2051

Rosemount 2051CF Flowmeters

Configuration Transmitter Output Code


4-20 mA HART®
2051 A
2051 with Selectable HART(1)
Lower Power
2051 M
2051 with Selectable HART(1)
FOUNDATION Fieldbus F
Profibus W
Wireless X

(1) The 4-20 mA with Selectable HART device can be ordered with Transmitter
Output option code A plus any of the following options codes: M4, QT, DZ,
CR, CS, CT, HR5, HR7.

Additional Information
Specifications: page 50
Rosemount 2051CFA Annubar Certifications: page 60
Flowmeter
Dimensional Drawings: page 68

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Model Product Description


2051CFA Annubar Flowmeter
Measurement Type

Standard Standard

D Differential Pressure ★

Fluid Type

Standard Standard

L Liquid ★

G Gas ★

S Steam ★

[Link] 19
Rosemount 2051 April 2013

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Line Size

Standard Standard

020 2-in. (50 mm) ★

025 21/2-in. (63.5 mm) ★

030 3-in. (80 mm) ★


1 ★
035 3 /2-in. (89 mm)
040 4-in. (100 mm) ★

050 5-in. (125 mm) ★

060 6-in. (150 mm) ★


070 7-in. (175 mm) ★

080 8-in. (200 mm) ★

100 10-in. (250 mm) ★

120 12-in. (300 mm) ★

Pipe I.D. Range

Standard Standard

C Range C from the Pipe I.D. table ★

D Range D from the Pipe I.D. table ★

Expanded
A Range A from the Pipe I.D. table
B Range B from the Pipe I.D. table
E Range E from the Pipe I.D. table
Z Non-standard Pipe I.D. Range or Line Sizes greater than 12 in.
Pipe Material / Mounting Assembly Material

Standard Standard

C Carbon steel (A105) ★

S 316 Stainless Steel ★


(1)
0 No Mounting (Customer Supplied)
Expanded
G Chrome-Moly Grade F-11
N Chrome-Moly Grade F-22
J Chrome-Moly Grade F-91
Piping Orientation

Standard Standard

H Horizontal Piping ★

D Vertical Piping with Downwards Flow ★

U Vertical Piping with Upwards Flow ★

20 [Link]
April 2013 Rosemount 2051

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Annubar Type

Standard Standard

P Pak-Lok ★

F Flanged with opposite side support ★

Sensor Material

Standard Standard

S 316 Stainless Steel ★

Sensor Size

Standard Standard

1 Sensor size 1 — Line sizes 2-in. (50 mm) to 8-in. (200 mm) ★
2 Sensor size 2 — Line sizes 6-in. (150 mm) to 96-in. (2400 mm) ★

3 Sensor size 3 — Line sizes greater than 12-in. (300 mm) ★

Mounting Type

Standard Standard

T1 Compression or Threaded Connection ★


A1 150# RF ANSI ★

A3 300# RF ANSI ★

A6 600# RF ANSI ★
D1 DN PN16 Flange ★

D3 DN PN40 Flange ★
D6 DN PN100 Flange ★

Expanded
R1 150# RTJ Flange
R3 300# RTJ Flange
R6 600# RTJ Flange
Opposite Side Support or Packing Gland

Standard Standard

0 No opposite side support or packing gland (Required for Pak-Lok and Flange-Lok models) ★

Opposite Side Support – Required for Flanged Models


C NPT Threaded Opposite Support Assembly – Extended Tip ★

D Welded Opposite Support Assembly – Extended Tip ★

Isolation Valve for Flo-Tap Models

Standard Standard

0(1) Not Applicable or Customer Supplied ★

[Link] 21
Rosemount 2051 April 2013

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Temperature Measurement

Standard Standard

T Integral RTD – not available with Flanged model greater than class 600# ★
0 No Temperature Sensor ★

Expanded
R Remote Thermowell and RTD
Transmitter Connection Platform

Standard Standard

3 Direct-mount, Integral 3-valve Manifold– not available with Flanged model greater than class 600 ★

5 Direct -mount, 5-valve Manifold – not available with Flanged model greater than class 600 ★
1 ★
7 Remote-mount NPT Connections ( /2-in. FNPT)
Expanded
8 Remote-mount SW Connections (1/2-in.)
Differential Pressure Range

Standard Standard

1 0 to 25 in H2O (0 to 62,3 mbar) ★


2 0 to 250 in H2O (0 to 623 mbar) ★
3 0 to 1000 in H2O (0 to 2,5 bar) ★

Transmitter Output

Standard Standard

A(2) 4–20 mA with digital signal based on HART Protocol ★


F FOUNDATION fieldbus Protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded
M Low-Power, 1-5 Vdc with Digital Signal Based on HART Protocol
Transmitter Housing Material Conduit Entry Size

Standard Standard
1 ★
A Aluminum /2-14 NPT
B Aluminum M20 x 1.5 ★
1 ★
J SST /2-14 NPT
K(3) SST M20 x 1.5 ★

P(4) Engineered Polymer No Conduit Entries ★

Expanded
D Aluminum G1/2
M(3) SST G1/2

22 [Link]
April 2013 Rosemount 2051

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Performance Class

Standard Standard

1 2.0% flow rate accuracy, 5:1 flow turndown, 2-year stability ★

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard
WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★
Antenna and SmartPower

Standard Standard
WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


Pressure Testing

Expanded
P1(3)(5) Hydrostatic Testing with Certificate
(3)(5)
PX Extended Hydrostatic Testing
Special Cleaning

Expanded
P2(3) Cleaning for Special Services
PA(3) Cleaning per ASTM G93 Level D (Section 11.4)
Material Testing

Expanded
V1(3) Dye Penetrant Exam
Material Examination

Expanded
V2(3) Radiographic Examination
Special Inspection

Standard Standard

QC1(3) Visual & Dimensional Inspection with Certificate ★


(3) ★
QC7 Inspection & Performance Certificate
Surface Finish

Standard Standard

RL(3) Surface finish for Low Pipe Reynolds # in Gas & Steam ★
(3) ★
RH Surface finish for High Pipe Reynolds # in Liquid

[Link] 23
Rosemount 2051 April 2013

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Material Traceability Certification

Standard Standard

Q8(3)(6) Material Traceability Certification per EN 10474:2004 3.1 ★

Code Conformance

Expanded
J2 (3) ANSI/ASME B31.1
(3)
J3 ANSI/ASME B31.3
Materials Conformance

Expanded
J5(3)(7) NACE MR-0175 / ISO 15156
Country Certification

Standard Standard

J6(3) European Pressure Directive (PED) ★

Expanded
J1(3) Canadian Registration
Instrument Connections for Remote Mount Options

Standard Standard

G2(3) Needle Valves, Stainless Steel ★


G6(3) OS&Y Gate Valve, Stainless Steel ★

Expanded
G1(3) Needle Valves, Carbon Steel
(3)
G3 Needle Valves, Alloy C-276
G5(3) OS&Y Gate Valve, Carbon Steel
(3)
G7 OS&Y Gate Valve, Alloy C-276
Special Shipment

Standard Standard

Y1(3) Mounting Hardware Shipped Separately ★

24 [Link]
April 2013 Rosemount 2051

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Product Certifications

Standard Standard

E1(3) ATEX Flameproof ★

E2(3) INMETRO Flameproof ★


(3) ★
E3 China Flameproof
E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(3) ★
E7 IECEx Flameproof
(3) ★
I1 ATEX Intrinsic Safety
I2(3) INMETRO Intrinsically Safe ★
(3) ★
I3 China Intrinsic Safety
I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★


(3) ★
I7 IECEx Intrinsic Safety
(3)(8) ★
IA ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
IE(3)(8) FM FISCO Intrinsically Safe ★
(3)(8) ★
IF CSA FISCO Intrinsically Safe
(3)(8) ★
IG IECEx FISCO Intrinsically Safe
K1(3) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) ★


K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6) ★

K7(3) IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n (combination of E7, I7, and N7) ★
(3) ★
KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2
FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6,
KB ★
I5, and I6)
KC(3) FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 ★
(3) ★
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
N1(3) ATEX Type n ★
(3) ★
N7 IECEx Type n
(3) ★
ND ATEX Dust
Sensor Fill Fluid and O-ring Options

Standard Standard

L1(3)(9) Inert Sensor Fill Fluid ★


(3) ★
L2 Graphite-Filled (PTFE) O-ring
LA(3)(9) Inert Sensor Fill Fluid and Graphite-Filled (PTFE) O-ring ★

Display and Interface Options

Standard Standard

M4(3)(10) LCD Display with Local Operator Interface ★


(3) ★
M5 LCD display
[Link] 25
Rosemount 2051 April 2013

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Calibration Certification

Standard Standard

Q4(3) Calibration Certificate for Transmitter ★

Quality Certification for Safety

Standard Standard

QS(3)(11) Prior-use certificate of FMEDA data ★


(3)(11) ★
QT Safety Certified to IEC 61508 with certificate of FMEDA
Transient Protection

Standard Standard

T1(3)(9)(12) Transient terminal block ★

Manifold for Remote Mount Option

Standard Standard

F2(3) 3-Valve Manifold, Stainless Steel ★


(3) ★
F6 5-Valve Manifold, Stainless Steel
Expanded
F1(3) 3-Valve Manifold, Carbon Steel
F5(3) 5-Valve Manifold, Carbon Steel
PlantWeb Control Functionality

Standard Standard

A01(3)(8) FOUNDATION fieldbus Advanced Control Function Block Suite ★

Hardware Adjustments

Standard Standard

D4(3)(13) Zero and Span Hardware Adjustments ★


DZ(3)(14) Digital Zero Trim ★

Alarm Limit

Standard Standard

C4(3)(13)(15) NAMUR Alarm and Saturation Levels, High Alarm ★


(3)(13)(15) ★
CN NAMUR Alarm and Saturation Levels, Low Alarm
CR(3)(13) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★
(3)(13) ★
CS Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
CT(3)(13) Low Alarm (standard Rosemount alarm and saturation levels) ★

Ground Screw

Standard Standard

V5(3)(9)(16) External Ground Screw Assembly ★

26 [Link]
April 2013 Rosemount 2051

Table 3. Rosemount 2051CFA Annubar Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

HART Revision Configuration

Standard Standard

HR5(3)(13)(17) Configured for HART Revision 5 ★


(3)(13)(18) ★
HR7 Configured for HART Revision 7
Typical Model Number: 2051CFA D L 060 D C H P S 2 T1 0 0 0 3 2A A 1A 3

(1) Provide the “A” dimension for Flanged (page 77) and Pak-Lok (page 77).

(2) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART
Revision 7 factory configured, add option code HR7.

(3) Not available with Low Power Output Code M.

(4) Only available with output code X.

(5) Applies to assembled flowmeter only, mounting not tested.

(6) Instrument Connections for Remote Mount Options and Isolation Valves for Flo-tap Models are not included in the Material Traceability Certification.

(7) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply
to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(8) Only valid with FOUNDATION fieldbus Output Code F.

(9) Not available with output code X.

(10) Not available with FOUNDATION Fieldbus (Output Code F) or Wireless (Output Code X)

(11) Only available with 4-20 mA HART (Output Code A).

(12) Not available with Housing code 00, 5A or 7J. The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product
Certification code IA.

(13) Only available with 4-20 mA HART (output codes A and M).

(14) Only available with HART 4-20 mA Output (output codes A and M) and Wireless Output (output code X).

(15) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(16) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(17) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(18) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.

[Link] 27
Rosemount 2051 April 2013

Additional Information
Rosemount 2051CFC Compact Flowmeter Specifications: page 50
Certifications: page 60
Dimensional Drawings: page 68

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Model Product Description


2051CFC Compact Flowmeter
Measurement Type

Standard Standard

D Differential Pressure ★

Primary Element Technology

Standard Standard

C Conditioning Orifice Plate ★


P Orifice Plate ★

Material Type

Standard Standard

S 316 SST ★

Line Size

Standard Standard

005(1) 1
/2-in. (15 mm) ★

010(1) 1-in. (25 mm) ★


(1) 1 ★
015 1 /2-in. (40 mm)
020 2-in. (50 mm) ★

030 3-in. (80 mm) ★

040 4-in. (100 mm) ★

060 6-in. (150 mm) ★

080 8-in. (200 mm) ★

100 10-in. (250 mm) ★

120 12-in. (300 mm) ★

Primary Element Style

Standard Standard

N Square Edged ★

28 [Link]
April 2013 Rosemount 2051

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Primary Element Type

Standard Standard

040 0.40 Beta Ratio ★


(2) ★
065 0.65 Beta Ratio
Temperature Measurement

Standard Standard

0 No Temperature Sensor ★

Expanded
R Remote Thermowell and RTD
Transmitter Connection Platform

Standard Standard

3 Direct-mount, Integral 3-valve Manifold ★

7 Remote-mount, 1/4-in. NPT Connections ★

Differential Pressure Range

Standard Standard

1 0 to 25 in H2O (0 to 62,3 mbar) ★

2 0 to 250 in H2O (0 to 623 mbar) ★

3 0 to 1000 in H2O (0 to 2,5 bar) ★

Transmitter Output

Standard Standard

A(3) 4–20 mA with digital signal based on HART Protocol ★

F FOUNDATION fieldbus Protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded
M Low-Power, 1-5 Vdc with Digital Signal Based on HART Protocol
Transmitter Housing Material Conduit Entry Size

Standard Standard

A Aluminum 1
/2-14 NPT ★

B Aluminum M20 x 1.5 ★

J SST 1
/2-14 NPT ★

K(4) SST M20 x 1.5 ★

P(5) Engineered Polymer No Conduit Entries ★

Expanded
D Aluminum G1/2
(4)
M SST G1/2

[Link] 29
Rosemount 2051 April 2013

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Performance Class

Standard Standard

1 up to ±2.25% flow rate accuracy, 5:1 flow turndown, 2-year stability ★

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard
WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★
Antenna and SmartPower

Standard Standard
WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


Installation Accessories

Standard Standard

AB(4) ANSI Alignment Ring (150#) (Only required for 10-in. (250 mm) and 12-in. (300 mm) line sizes) ★
(4) ★
AC ANSI Alignment Ring (300#) (Only required for 10-in. (250 mm) and 12-in. (300 mm) line sizes)
AD (4) ANSI Alignment Ring (600#) (Only required for 10-in. (250 mm) and 12-in. (300 mm) line sizes) ★
(4) ★
DG DIN Alignment Ring (PN16)
(4) ★
DH DIN Alignment Ring (PN40)
DJ(4) DIN Alignment Ring (PN100) ★

Expanded
JB(4) JIS Alignment Ring (10K)
(4)
JR JIS Alignment Ring (20K)
JS(4) JIS Alignment Ring (40K)
Remote Adapters

Standard Standard

FE(4) Flange Adapters 316 SST (1/2-in NPT) ★

High Temperature Application

Expanded
HT(4) Graphite Valve Packing (Tmax = 850 °F)
Flow Calibration

Expanded
WC(4)(6) Flow Calibration Certification (3 point)
(4)(6)
WD Discharge Coefficient Verification (full 10 point)

30 [Link]
April 2013 Rosemount 2051

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Pressure Testing

Expanded
P1(4) Hydrostatic Testing with Certificate
Special Cleaning

Expanded
P2(4) Cleaning for Special Services
(4)
PA Cleaning per ASTM G93 Level D (Section 11.4)
Special Inspection

Standard Standard

QC1(4) Visual & Dimensional Inspection with Certificate ★

QC7(4) Inspection and Performance Certificate ★

Transmitter Calibration Certification

Standard Standard

Q4(4) Calibration Certificate for Transmitter ★

Quality Certification for Safety

Standard Standard

QS(4)(7) Prior-use certificate of FMEDA data ★

QT(4)(7) Safety Certified to IEC 61508 with certificate of FMEDA ★

Material Traceability Certification

Standard Standard

Q8(4) Material Traceability Certification per EN 10204:2004 3.1 ★

Code Conformance

Expanded
J2(4) ANSI/ASME B31.1
J3(4) ANSI/ASME B31.3
(4)
J4 ANSI/ASME B31.8
Materials Conformance

Expanded
J5(4)(8) NACE MR-0175 / ISO 15156
Country Certification

Expanded
J1(4) Canadian Registration

[Link] 31
Rosemount 2051 April 2013

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Product Certifications

Standard Standard

E1(4) ATEX Flameproof ★

E2(4) INMETRO Flameproof ★


(4) ★
E3 China Flameproof
E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(4) ★
E7 IECEx Flameproof
I1(4) ATEX Intrinsic Safety ★

I2(4) INMETRO Intrinsically Safe ★

I3(4) China Intrinsic Safety ★

I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★


(4) ★
I7 IECEx Intrinsic Safety
(4)(9) ★
IA ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
IE(4)(9) FM FISCO Intrinsically Safe ★
(4)(9) ★
IF CSA FISCO Intrinsically Safe
(4)(9) ★
IG IECEx FISCO Intrinsically Safe
K1(4) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) ★

K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6) ★

K7(4) IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n (combination of E7, I7, and N7) ★
(4) ★
KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2
FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, ★
KB
I5, and I6)
KC(4) FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 ★
(4) ★
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
N1(4) ATEX Type n ★
(4) ★
N7 IECEx Type n
(4) ★
ND ATEX Dust
Sensor Fill Fluid and O-ring Options

Standard Standard

L1(4)(10) Inert Sensor Fill Fluid ★


(4) ★
L2 Graphite-Filled (PTFE) O-ring
LA(4)(10) Inert Sensor Fill Fluid and Graphite-Filled (PTFE) O-ring ★

Display and Interface Options

Standard Standard

M4(4)(7) LCD Display with Local Operator Interface ★


(4) ★
M5 LCD Display
32 [Link]
April 2013 Rosemount 2051

Table 4. Rosemount 2051CFC Compact Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transient Protection

Standard Standard

T1(4)(10)(11) Transient terminal block ★

Manifold for Remote Mount Option

Standard Standard

F2(4) 3-Valve Manifold, Stainless Steel ★

F6(4) 5-Valve Manifold, Stainless Steel ★

Alarm Limit

Standard Standard

C4(4)(12)(13) NAMUR Alarm and Saturation Levels, High Alarm ★


(4)(12)(13) ★
CN NAMUR Alarm and Saturation Levels, Low Alarm
CR(4)(12) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★
(4)(12) ★
CS Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
(4)(12) ★
CT Low Alarm (standard Rosemount alarm and saturation levels)
PlantWeb Control Functionality

Standard Standard

A01(4)(9) FOUNDATION fieldbus Advanced Control Function Block Suite ★

Hardware Adjustments

Standard Standard

D4(4)(12) Zero and Span Hardware Adjustments ★

DZ(4)(14) Digital Zero Trim ★

Ground Screw

Standard Standard

V5(4)(10)(15) External Ground Screw Assembly ★

HART Revision Configuration

Standard Standard

HR5(4)(12)(16) Configured for HART Revision 5 ★

HR7(4)(12)(17) Configured for HART Revision 7 ★

Typical Model Number: 2051CFC D C S 060 N 065 0 3 2 A A 1 WC E5 M5

(1) Not available for Primary Element Technology C.

(2) For 2-in. (50 mm) line sizes the Primary Element Type is 0.6 for Primary Element Technology Code C.

(3) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART
Revision 7 factory configured, add option code HR7.

(4) Not available with Low Power Output Code M.

(5) Only available with output code X.

[Link] 33
Rosemount 2051 April 2013

(6) Not available with Primary Element Technology P.

(7) Not available with FOUNDATION Fieldbus (Output Code F) or Wireless (Output Code X).

(8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply
to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(9) Only valid with FOUNDATION fieldbus Output Code F.

(10) Not available with output code X.

(11) Not available with Housing code 00, 5A, or 7J. The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product
Certification code IA.

(12) Only available with 4-20 mA HART (output codes A and M).

(13) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(14) Only available with HART 4-20 mA (Output Codes A and M) and Wireless (Output Code X).

(15) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(16) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(17) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if 14 needed.

34 [Link]
April 2013 Rosemount 2051

Additional Information
Specifications: page 50
Rosemount 2051CFP Integral Certifications: page 60
Orifice Flowmeter
Dimensional Drawings: page 68

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Model Product Description


2051CFP Integral Orifice Flowmeter
Measurement Type

Standard Standard

D Differential Pressure ★

Material Type

Standard Standard

S 316 SST ★

Line Size

Standard Standard

005 1
/2-in. (15 mm) ★

010 1-in. (25 mm) ★

015 11/2-in. (40 mm) ★

Process Connection

Standard Standard

T1 NPT Female Body (Not Available with Remote Thermowell and RTD) ★

S1(1) Socket Weld Body (Not Available with Remote Thermowell and RTD) ★

P1 Pipe Ends: NPT Threaded ★

P2 Pipe ends: Beveled ★

D1 Pipe Ends: Flanged, DIN PN16, slip-on ★

D2 Pipe Ends: Flanged, DIN PN40, slip-on ★

D3 Pipe Ends: Flanged, DIN PN100, slip-on ★

W1 Pipe Ends: Flanged, RF, ANSI Class 150, weld-neck ★

W3 Pipe Ends: Flanged, RF, ANSI Class 300, weld-neck ★

W6 Pipe Ends: Flanged, RF, ANSI Class 600, weld-neck ★

[Link] 35
Rosemount 2051 April 2013

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Expanded
A1 Pipe Ends: Flanged, RF, ANSI Class 150, slip-on
A3 Pipe Ends: Flanged, RF, ANSI Class 300, slip-on
A6 Pipe Ends: Flanged, RF, ANSI Class 600, slip-on
R1 Pipe Ends: Flanged, RTJ, ANSI Class 150, slip-on
R3 Pipe Ends: Flanged, RTJ, ANSI Class 300, slip-on
R6 Pipe Ends: Flanged, RTJ, ANSI Class 600, slip-on
Orifice Plate Material

Standard Standard

S 316 SST ★

Bore Size Option

Standard Standard

0066 0.066-in. (1.68 mm) for 1/2-in. Pipe ★

0109 0.109-in. (2.77 mm) for 1/2-in. Pipe ★

0160 0.160-in. (4.06 mm) for 1/2-in. Pipe ★

0196 0.196-in. (4.98 mm) for 1/2-in. Pipe ★

0260 0.260-in. (6.60 mm) for 1/2-in. Pipe ★

0340 0.340-in. (8.64 mm) for 1/2-in. Pipe ★

0150 0.150-in. (3.81 mm) for 1-in. Pipe ★

0250 0.250-in. (6.35 mm) for 1-in. Pipe ★

0345 0.345-in. (8.76 mm) for 1-in. Pipe ★

0500 0.500-in. (12.70 mm) for 1-in. Pipe ★

0630 0.630-in. (16.00 mm) for 1-in. Pipe ★

0800 0.800-in. (20.32 mm) for 1-in. Pipe ★

0295 0.295-in. (7.49 mm) for 1 1/2-in. Pipe ★

0376 0.376-in. (9.55 mm) for 1 1/2-in. Pipe ★

0512 0.512-in. (13.00 mm) for 1 1/2-in. Pipe ★

0748 0.748-in. (19.00 mm) for 1 1/2-in. Pipe ★

1022 1.022-in. (25.96 mm) for 1 1/2-in. Pipe ★

1184 1.184-in. (30.07 mm) for 1 1/2-in. Pipe ★

Expanded
0010 0.010-in. (0.25 mm) for 1/2-in. Pipe
0014 0.014-in. (0.36 mm) for 1/2-in. Pipe
0020 0.020-in. (0.51 mm) for 1/2-in. Pipe
0034 0.034-in. (0.86 mm) for 1/2-in. Pipe

36 [Link]
April 2013 Rosemount 2051

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Transmitter Connection Platform

Standard Standard

D3 Direct-mount, 3-Valve Manifold, SST ★

D5 Direct-mount, 5-Valve Manifold, SST ★

R3 Remote-mount, 3-Valve Manifold, SST ★

R5 Remote-mount, 5-Valve Manifold, SST ★

Differential Pressure Ranges

Standard Standard

1 0 to 25 in H2O (0 to 62,3 mbar) ★

2 0 to 250 in H2O (0 to 623 mbar) ★

3 0 to 1000 in H2O (0 to 2,5 bar) ★

Transmitter Output

Standard Standard

A(2) 4–20 mA with digital signal based on HART protocol ★

F FOUNDATION fieldbus protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded
M Low-Power, 1-5 Vdc with Digital Signal Based on HART Protocol
Transmitter Housing Material Conduit Entry Size

Standard Standard

A Aluminum 1/2-14 NPT ★

B Aluminum M20 x 1.5 ★

J SST 1
/2-14 NPT ★
(3) ★
K SST M20 x 1.5
P(4) Engineered Polymer No Conduit Entries ★

Expanded
D Aluminum G1/2
M(3) SST G1/2
Transmitter Performance Class

Standard Standard

1 up to ±2.25% flow rate accuracy, 5:1 flow turndown, 2-year stability ★

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard
WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★
[Link] 37
Rosemount 2051 April 2013

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Antenna and SmartPower

Standard Standard
WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


Temperature Sensor

Expanded
RT(3)(5) Thermowell and RTD
Optional Connection

Standard Standard

G1(3) DIN 19213 Transmitter Connection ★

Pressure Testing

Expanded
P1(3)(6) Hydrostatic Testing with Certificate
Special Cleaning

Expanded
P2(3) Cleaning for Special Services
(3)
PA Cleaning per ASTM G93 Level D (Section 11.4)
Material Testing

Expanded
V1(3) Dye Penetrant Exam
Material Examination

Expanded
V2(3) Radiographic Examination
Flow Calibration

Expanded
WD(3)(7) Discharge Coefficient Verification
Special Inspection

Standard Standard

QC1(3) Visual & Dimensional Inspection with Certificate ★


(3) ★
QC7 Inspection and Performance Certificate
Material Traceability Certification

Standard Standard

Q8(3) Material Traceability Certification per EN 10204:2004 3.1 ★

38 [Link]
April 2013 Rosemount 2051

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Code Conformance

Expanded
J2(3)(8) ANSI/ASME B31.1
J3(3)(8) ANSI/ASME B31.3
(3)(8)
J4 ANSI/ASME B31.8
Materials Conformance

Expanded
J5(3)(9) NACE MR-0175 / ISO 15156
Country Certification

Standard Standard

J6(3) European Pressure Directive (PED) ★

Expanded
J1(3) Canadian Registration
Transmitter Calibration Certification

Standard Standard

Q4(3) Calibration Certificate for Transmitter ★

Quality Certification for Safety

Standard Standard

QS(3)(10) Prior-use certificate of FMEDA data ★


(3)(10) ★
QT Safety Certified to IEC 61508 with certificate of FMEDA
Product Certifications

Standard Standard

E1(3) ATEX Flameproof ★

E2(3) INMETRO Flameproof ★


(3) ★
E3 China Flameproof
E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(3) ★
E7 IECEx Flameproof
I1(3) ATEX Intrinsic Safety ★

I2(3) INMETRO Intrinsically Safe ★

I3(3) China Intrinsic Safety ★

I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★


(3) ★
I7 IECEx Intrinsic Safety

[Link] 39
Rosemount 2051 April 2013

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

IA(3)(11) ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only ★
(3)(11) ★
IE FM FISCO Intrinsically Safe
(3)(11) ★
IF CSA FISCO Intrinsically Safe
(3)(11) ★
IG IECEx FISCO Intrinsically Safe
K1(3)(11) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) ★

K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6) ★

K7(3) IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n (combination of E7, I7, and N7) ★

KA(3) ATEX and CSA Flameproof, Intrinsically Safe, Division 2 ★

FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, ★
KB
and I6)
KC(3) FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 ★
(3) ★
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
N1(3) ATEX Type n ★
(3) ★
N7 IECEx Type n
(3) ★
ND ATEX Dust
Sensor Fill Fluid and O-ring Options

Standard Standard

L1(3)(12) Inert Sensor Fill Fluid ★


(3) ★
L2 Graphite-Filled (PTFE) O-ring
(3)(12) ★
LA Inert Sensor Fill Fluid and Graphite-Filled (PTFE) O-ring
Display and Interface Options

Standard Standard

M4(3)(10) LCD Display with Local Operator Interface ★

M5(3) LCD display ★

Transient Protection

Standard Standard

T1(3)(12)(13) Transient terminal block ★

Alarm Limit

Standard Standard

C4(3)(14)(15) NAMUR Alarm and Saturation Levels, High Alarm ★


(3)(14)(15) ★
CN NAMUR Alarm and Saturation Levels, Low Alarm
CR(3)(14) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★
(3)(14) ★
CS Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
(3)(14) ★
CT Low Alarm (standard Rosemount alarm and saturation levels)
PlantWeb Control Functionality

Standard Standard

A01(3)(11) FOUNDATION fieldbus Advanced Control Function Block Suite ★

40 [Link]
April 2013 Rosemount 2051

Table 5. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.

Hardware Adjustments

Standard Standard

D4(3)(14) Zero and Span Hardware Adjustments ★

DZ(3)(16) Digital Zero Trim ★

Ground Screw

Standard Standard

V5(3)(12)(17) External Ground Screw Assembly ★

HART Revision Configuration

Standard Standard

HR5(3)(14)(18) Configured for HART Revision 5 ★

HR7(3)(14)(19) Configured for HART Revision 7 ★

Typical Model Number: 2051CFP D S 010 W1 S 0500 D3 2 A A 1 E5 M5

(1) To improve pipe perpendicularity for gasket sealing, socket diameter is smaller than standard pipe O.D.

(2) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision
7 factory configured, add option code HR7.

(3) Not available with Low Power Output Code M.

(4) Only available with output code X.

(5) Thermowell Material is the same as the body material.

(6) Does not apply to Process Connection codes T1 and S1.

(7) Not available for bore sizes 0010, 0014, 0020, or 0034.

(8) Not available with DIN Process Connection codes D1, D2, or D3.

(9) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

(10) Not available with FOUNDATION Fieldbus (Output Code F) or Wireless (Output Code X).

(11) Only valid with FOUNDATION fieldbus Output Code F.

(12) Not available with output code X.

(13) Not available with Housing code 00, 5A, or 7J. The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product
Certification code IA.

(14) Only available with 4-20 mA HART (output codes A and M).

(15) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(16) Only available with HART 4-10 mA (Output Codes A and M) and Wireless (Output Code X).

(17) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(18) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(19) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.

[Link] 41
Rosemount 2051 April 2013

Rosemount 2051L Liquid Level Transmitter


Configuration Transmitter Output Code
®
4-20 mA HART
2051 A
2051 with Selectable HART(1)
Lower Power
2051 M
(1)
2051 with Selectable HART
FOUNDATION Fieldbus F
Profibus W
2051L Liquid Level Wireless X
Transmitter

(1) The 4-20mA with Selectable HART device can be ordered with Transmitter
Output option code A plus any of the following options codes: M4, QT, DZ,
CR, CS, CT, HR5, HR7.

Additional Information
Specifications: page 50
Certifications: page 60
Dimensional Drawings: page 68
Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model Transmitter Type

Standard Standard

2051L Liquid Level Transmitter ★

Pressure Range

Standard Standard

2 –250 to 250 inH2O (–0,6 to 0,6 bar) ★

3 –1000 to 1000 inH2O (–2,5 to 2,5 bar) ★

4 –300 to 300 psi (–20,7 to 20,7 bar) ★

Transmitter Output

Standard Standard

A(1) 4–20 mA with Digital Signal Based on HART Protocol ★

F FOUNDATION fieldbus Protocol ★

W PROFIBUS PA Protocol ★

X Wireless ★

Expanded

M Low-Power, 1–5 V dc with Digital Signal Based on HART Protocol

42 [Link]
April 2013 Rosemount 2051

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Process Connection Size, Diaphragm Material (High Side)

Process Connection Size Diaphragm

Standard Standard
G(2) 2 in./DN 50 316L SST ★
(2) ★
H 2 in./DN 50 Alloy C-276
J 2 in./DN 50 Tantalum ★

A(2) 3 in./DN 80 316L SST ★


(2) ★
B 4 in./DN 100 316L SST
C(2) 3 in./DN 80 Alloy C-276 ★

D(2) 4 in./DN 100 Alloy C-276 ★

E 3 in./DN 80 Tantalum ★

F 4 in./DN 100 Tantalum ★

Extension Length (High Side)

Standard Standard

0 None, Flush Mount ★

2 2 in./50 mm ★

4 4 in./100 mm ★

6 6 in./150 mm ★

Mounting Flange Size, Rating, Material (High Side)

Size Rating Material

Standard Standard

M 2-in. ANSI/ASME B16.5 Class 150 CS ★

A 3-in. ANSI/ASME B16.5 Class 150 CS ★

B 4-in. ANSI/ASME B16.5 Class 150 CS ★

N 2-in. ANSI/ASME B16.5 Class 300 CS ★

C 3-in. ANSI/ASME B16.5 Class 300 CS ★

D 4-in. ANSI/ASME B16.5 Class 300 CS ★

X(2) 2-in. ANSI/ASME B16.5 Class 150 SST ★

F(2) 3-in. ANSI/ASME B16.5 Class 150 SST ★


(2) ★
G 4-in. ANSI/ASME B16.5 Class 150 SST
Y(2) Displayed ANSI/ASME B16.5 Class 300 SST ★

H(2) 3-in. ANSI/ASME B16.5 Class 300 SST ★

J(2) 4-in. ANSI/ASME B16.5 Class 300 SST ★

Q DN50 PN 10-40 per EN 1092-1 CS ★

R DN80 PN 40 per EN 1092-1 CS ★

K(2) DN50 PN 10-40 per EN 1092-1 SST ★

T(2) DN80 PN 40 per EN 1092-1 SST ★


[Link] 43
Rosemount 2051 April 2013

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Temperature Limits
Seal Fill Fluid (High Side) Specific Gravity (Ambient Temperature of 70
°F (21 °C))

Standard Standard

A Syltherm XLT 0.85 -102 to 293 °F (-75 to 145 °C) ★

C Silicone 704 1.07 32 to 401 °F (0 to 205 °C) ★

D Silicone 200 0.93 -49 to 401 °F (-45 to 205 °C) ★

H Inert (Halocarbon) 1.85 5 to 401 °F (-15 to 205 °C) ★

G Glycerin and Water 1.13 -49 to 320 °F (-45 to 160 °C) ★

N Neobee M-20 0.92 5 to 401 °F (-15 to 205 °C) ★

P Propylene Glycol and Water 1.02 5 to 203 °F (-15 to 95 °C) ★

Sensor Module Configuration, Flange Adapter (Low Side)

Configuration Flange Adapter

Standard Standard

1(2) Gage SST ★


(2) ★
2 Differential SST
Tuned-System with ★
3(2)(3) None
Remote Seal
Sensor Module Diaphragm Material, Sensor Fill Fluid (Low Side)

Diaphragm Material Sensor Fill Fluid

Standard Standard

1(2) 316L SST Silicone ★

Alloy C-276 (SST Valve ★


2(2) Silicone
Seat)
Alloy C-276 (Alloy ★
7(2) Silicone
C-276 Valve Seat)
A(2)(4) 316L SST Inert (Halocarbon) ★

Alloy C-276 (SST Valve ★


B(2)(4) Inert (Halocarbon)
Seat)
Alloy C-276 (Alloy ★
G(2)(4) Inert (Halocarbon)
C-276 Valve Seat)
O-ring

Standard Standard

A Glass-filled PTFE ★

44 [Link]
April 2013 Rosemount 2051

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Housing Material Conduit Entry Size

Standard Standard

A Aluminum ½–14 NPT ★

B Aluminum M20 × 1.5 ★

J SST ½–14 NPT ★

K(5) SST M20 × 1.5 ★

P(6) Engineered Polymer No Conduit Entries ★

Expanded

D Aluminum G½
(5)
M SST G½

Wireless options (Requires Wireless output code X and Engineered Polymer housing code P)
Wireless Transmit Rate, Operating Frequency and Protocol

Standard Standard

WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART ★

Antenna and SmartPower

Standard Standard

WP5 Internal Antenna, Compatible with Green Power Module (I.S. Power Module Sold Separately) ★

Options (Include with selected model number)


PlantWeb Control Functionality

Standard Standard

A01(7) FOUNDATION fieldbus Advanced Control Function Block Suite ★

Seal Assemblies

Standard Standard

S1(8) Assemble to One Rosemount 1199 Seal (Requires 1199M) ★

Product Certifications

Standard Standard

E1(5) ATEX Flameproof ★


(5) ★
E2 INMETRO Flameproof
(5) ★
E3 China Flameproof
E4 TIIS Flameproof ★

E5 FM Explosion-proof, Dust Ignition-proof ★

E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 ★


(5) ★
E7 IECEx Flameproof
EW(5) India (CCOE) Flameproof Approval ★

[Link] 45
Rosemount 2051 April 2013

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Standard Standard

I1(5) ATEX Intrinsic Safety ★


(5) ★
I2 INMETRO Intrinsically Safe
I3(5) China Intrinsic Safety ★

I4(5)(6) TIIS Intrinsic Safety ★

I5 FM Intrinsically Safe, Division 2 ★

I6 CSA Intrinsically Safe ★

I7(5) IECEx Intrinsic Safety ★


(7) ★
IA ATEX FISCO Intrinsic Safety
IE(7) FM FISCO Intrinsically Safe ★

IF(7) CSA FISCO Intrinsically Safe ★


(7) ★
IG IECEx FISCO Intrinsically Safe
IW(5) India (CCOE) Intrinsically Safety Approval ★

K1(5) ATEX Flameproof, Intrinsic Safety, Type n, Dust ★

K2 INMETRO Flameproof and Intrinsic Safety ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★

K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★


(5) ★
K7 IECEx Flameproof, Intrinsic Safety, Type n and Dust
KA(5) ATEX and CSA Flameproof, Intrinsically Safe, Division 2 ★

KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 ★


(5) ★
KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2
KD(5) FM, CSA, and ATEX Explosion-proof, Intrinsically Safe ★

N1(5) ATEX Type n ★


(5) ★
N7 IECEx Type n
(5) ★
ND ATEX Dust
Shipboard Approvals

Standard Standard

SBS(4) American Bureau of Shipping (ABS) Type Approval ★

SBV(4) Bureau Veritas (BV) Type Approval ★

SDN(4) Det Norske Veritas (DNV) Type Approval ★


(4) ★
SLL Lloyds Register (LR) Type Approval
Display and Interface Options

Standard Standard

M4(9) LCD Display with Local Operator Interface ★

M5 LCD display ★

46 [Link]
April 2013 Rosemount 2051

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Hardware Adjustments

Standard Standard

D4(10) Zero and Span Configuration Buttons ★

DZ(11) Digital Zero Trim ★

Flange Adapters

Standard Standard

DF(12) 1
/2-14 NPT Flange Adapters ★

Conduit Plug

Standard Standard

DO(4)(13) 316 SST Conduit Plug ★

Ground Screw

Standard Standard

V5(4)(14) External Ground Screw Assembly ★

Transient Protection

Standard Standard

T1(4)(15) Transient Terminal Block ★

Software Configuration

Standard Standard

C1(11) Custom Software Configuration (Requires completed Configuration Data Sheet) ★

Alarm Limit

Standard Standard

C4(10)(16) NAMUR alarm and saturation levels, high alarm ★

CN(10)(16) NAMUR alarm and saturation levels, low alarm ★

CR(10) Custom Alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet) ★

CS(10) Custom Alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet) ★

CT(10) Low Alarm (standard Rosemount alarm and saturation levels) ★

Calibration Certification

Standard Standard

Q4 Calibration Certificate ★

QG Calibration Certificate and GOST Verification Certificate ★

GP Calibration Certificate and tamper evident seal ★

[Link] 47
Rosemount 2051 April 2013

Table 6. Rosemount 2051L Liquid Level Transmitter Ordering Information


★ The Standard offering represents the most common options. The starred options (★) should be selected for
best delivery.
__The Expanded offering is subject to additional delivery lead time.
Material Traceability Certification

Standard Standard

Q8 Material Traceability Certification per EN 10204 3.1 ★

Quality Certification for Safety

Standard Standard

QS(17) Prior-use certificate of FMEDA data ★


(17) ★
QT Safety Certified to IEC 61508 with certificate of FMEDA

Toolkit Total System Performance Reports

Standard Standard

QZ Remote Seal System Performance Calculation Report ★

Conduit Electrical Connector

Standard Standard

GE(4) M12, 4-pin, Male Connector (eurofast®) ★


(4)
GM A size Mini, 4-pin, Male Connector (minifast®) ★

Lower Housing Flushing Connection Options

Ring Material Number Size (NPT)

Standard Standard

F1 316 SST 1 1
/4-18 NPT ★

F2 316 SST 2 1
/4-18 NPT ★

F3(18) Alloy C-276 1 1


/4-18 NPT ★
(18) 1 ★
F4 Alloy C-276 2 /4-18 NPT
F7 316 SST 1 1
/2-14 NPT ★

F8 316 SST 2 1
/2-14 NPT ★

F9 Alloy C-276 1 1
/2-14 NPT ★

F0 Alloy C-276 2 1
/2-14 NPT ★

HART Revision Configuration

Standard Standard

HR5(10)(19) Configured for HART Revision 5 ★


(10)(20) ★
HR7 Configured for HART Revision 7
Typical Model Number: 2051L 2 A A0 X D 21 A A B4 M5 F1

(1) HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART
Revision 7 factory configured, add option code HR7.

(2) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.

48 [Link]
April 2013 Rosemount 2051

(3) Requires option code S1.

(4) Not available with output code X.

(5) Not available with Low Power output code M.

(6) Only available with output code X.

(7) Only valid with FOUNDATION fieldbus output code F.

(8) “Assemble-to” items are specified separately and require a completed model number.

(9) Not valid with FOUNDATION fieldbus output code F and Wireless Output Code X.

(10) Only available with 4-20 mA HART (output codes A and M).

(11) Only available with HART 4-20 mA output (output codes A and M) and Wireless output (output code X).

(12) Not available with Remote Mount Seal Assembly option S1.

(13) Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.

(14) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

(15) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IE, IF, and IG.

(16) NAMUR-Compliant operation is pre-set at the factory.

(17) Only available with HART 4-20 mA output (output code A).

(18) Not available with Option Codes A0, B0, and G0.

(19) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.

(20) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.

[Link] 49
Rosemount 2051 April 2013

Specifications
Performance specifications
This product data sheet covers HART, Wireless, FOUNDATION fieldbus, and PROFIBUS PA protocols unless specified.

Conformance to specification (±3 (Sigma))


Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at least ±3.

Reference accuracy
Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability. For Wireless, FOUNDATION fieldbus, and PROFIBUS
PA devices, use calibrated range in place of span.

Models Standard High Performance Option, P8


2051C
±0.10% of span
For spans less than 15:1, accuracy =
Range 1
 0.025 + 0.005  --------------- % of Span
URL
 Span

High Accuracy Option, P8


±0.065% of span
±0.05% of span
For spans less than 10:1, accuracy =
For spans less than 10:1, accuracy =
Ranges 2-4 Ranges 2-4
 0.025 + 0.005  --------------- % of Span
URL
 0.015 + 0.005  --------------- % of Span
 Span URL
 Span

High Performance Option, P8


±0.075% of span
±0.065% of span
For spans less than 10:1, accuracy=
For spans less than 10:1, accuracy=
Range 5
 0.025 + 0.005  --------------- % of Span
Range 5 URL
 0.015 + 0.005  --------------- % of Span
 Span URL
 Span

High Accuracy Option, P8


±0.065% of span
±0.05% of span
2051T For spans less than 10:1, accuracy =
For spans less than 10:1, accuracy =
Ranges 1-4 Ranges 1-4
 0.0075  --------------- % of Span
URL
 0.0075  --------------- % of Span
 Span URL
 Span

±0.075% of span
For spans less than 10:1,
Range 5
accuracy =  0.075  --------------- % of Span
URL
 Span

±0.075% of span
2051L For spans less than 10:1, accuracy =
Ranges 2-4
 0.025 + 0.005  --------------- % of Span
URL
 Span

50 [Link]
April 2013 Rosemount 2051

Flow performance - Flow reference accuracy


2051CFA Annubar Flowmeter
Ranges 2-3 ±2.00% of Flow Rate at 5:1 flow turndown
2051CFC Compact Orifice Flowmeter – Conditioning Option C
 =0.4 ±2.25% of Flow Rate at 5:1 flow turndown
Ranges 2-3
 =0.65 ±2.45% of Flow Rate at 5:1 flow turndown
2051CFC Compact Orifice Flowmeter – Orifice Type Option P(1)
 =0.4 ±2.50% of Flow Rate at 5:1 flow turndown
Ranges 2-3
 =0.65 ±2.50% of Flow Rate at 5:1 flow turndown
2051CFP Integral Orifice Flowmeter
 <0.1 ±3.10% of Flow Rate at 5:1 flow turndown
0.1<  <0.2 ±2.75% of Flow Rate at 5:1 flow turndown
Ranges 2-3 0.2<  <0.6 ±2.25% of Flow Rate at 5:1 flow turndown
0.6<  <0.8 ±3.00% of Flow Rate at 5:1 flow turndown

(1) For smaller line sizes, see Rosemount Compact Orifice

Long term stability


± 50 °F (28 °C) temperature changes and up to 1000 psi (6,9 MPa) line pressure.
Models Standard High Performance Option, P8
2051C
Range 1 (CD) ±0.2% of URL for 1 year
Ranges 2-5 ±0.1% of URL for 2 years ±0.125% of URL for 5 years
2051T
Ranges 1-5 ±0.1% of URL for 2 years ±0.125% of URL for 5 years

Dynamic performance

4-20 mA HART(1) FOUNDATION fieldbus


Typical HART Transmitter Response
1-5 Vdc HART Low and PROFIBUS PA
Time
Power protocols (3)
Total Response Time (Td + Tc)(2):
2051C, Range 3-5: 115 ms 152 ms
Range 1: 270 ms 307 ms Transmitter Output vs. Time
Range 2: 130 ms 152 ms Pressure Released

2051T: 100 ms 152 ms Td = Dead Time


Td Tc
2051L: See Instrument Toolkit® See Instrument Toolkit 100%
Tc = Time Constant
Response Time = Td +Tc
Dead Time (Td) 60 ms (nominal) 97 ms
Update Rate(4) 22 times per second 22 times per second 36.8%
63.2% of Total
Step Change

0%
(1) Dead time and update rate apply to all models and ranges; analog output only Time
(2) Nominal total response time at 75 °F (24 °C) reference conditions.
(3) Transducer block response time, Analog Input block execution time not included.
(4) Does not apply to wireless (Output Code X). See “Wireless (Output Code X)” on page 55
for wireless update rate.

[Link] 51
Rosemount 2051 April 2013

Line pressure effect per 1000 psi (6,9 MPa)


For line pressures above 2000 psi (13,7 MPa) and Ranges 4-5, see user manual (Document number 00809-0100-4001 for HART,
00809-0100-4102 for WirelessHART, 00809-0100-4774 for FOUNDATION fieldbus, and 00809-0300-4101 for PROFIBUS PA)
Models Line Pressure Effect
2051CD, 2051CF Zero Error(1)
Range 1 ±0.25% of URL/1000 psi (68.9 bar)
Ranges 2-3 ±0.05% of URL/1000 psi (68.9 bar) for line pressures from 0 to 2000 psi (0 to 13.7 MPa)
Span Error
Range 1 ±0.4% of reading/1,000 psi (68.9 bar)
Ranges 2-3 ±0.1% of reading/1,000 psi (68.9 bar)

(1) Can be calibrated out at line pressure.

Ambient temperature effect per 50 °F (28 °C)

Models Ambient Temperature Effect High Performance Option, P8


2051C, 2051CF
±(0.025% URL + 0.125% span) from 1:1 to 5:1 ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1
Ranges 2-5
±(0.05% URL + 0.25% span) from 5:1 to 100:1 ±(0.025% URL + 0.125% span) from 5:1 to 100:1
Range 1 ±(0.1% URL + 0.25% span) from 1:1 to 30:1

2051T
±(0.05% URL + 0.25% span) from 1:1 to 30:1 ±(0.025% URL + 0.125% span) from 1:1 to 30:1
Range 2-4
±(0.07% URL + 0.25% span) from 30:1 to 100:1 ±(0.035% URL + 0.125% span) from 30:1 to 100:1
±(0.05% URL + 0.25% span) from 1:1 to 10:1 ±(0.025% URL + 0.125% span) from 1:1 to 10:1
Range 1
±(0.10% URL + 0.25% span) from 10:1 to 100:1 ±(0.05% URL + 0.125% span) from 10:1 to 100:1
Range 5 ±(0.1% URL + 0.15% span)
2051L See Instrument Toolkit

Mounting position effects

Models Mounting Position Effects


2051C Zero shifts up to ±1.25 inH2O (3.1 mbar), which can be calibrated out. No span effect.
2051T Zero shifts up to ±2.5 inH2O (6.2 mbar), which can be calibrated out. No span effect.
With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (2.49 mbar). With diaphragm in
2051L horizontal plane, zero shift of up to 5 inH2O (12.43 mbar) plus extension length on extended units. Zero
shifts can be calibrated out. No span effect.

Vibration effect Transient protection (Option Code T1)


Less than ±0.1% of URL when tested per the requirements of Meets IEEE C62.41, Category Location B
IEC60770-1 field or pipeline with high vibration level (10-60 Hz 6 kV crest (0.5 s - 100 kHz)
0.21mm displacement peak amplitude / 60-2000 Hz 3g). 3 kA crest (8 × 20 microseconds)
6 kV crest (1.2 × 50 microseconds)
Power supply effect
Less than ±0.005% of calibrated span per volt.(1)

Electromagnetic Compatibility (EMC)


Meets all relevant requirements of EN 61326 and NAMUR NE-21.(2)

(1) Does not apply to Wireless (Output Code X).

(2) NAMUR NE-21 does not apply to wireless output code X.

52 [Link]
April 2013 Rosemount 2051

Functional specifications
Range and Sensor limits

Table 7. Range and sensor limits


2051CD, 2051CF, 2051CG, 2051L
Range and Sensor Limits
Lower (LRL)
Range

Minimum Span 2051C Differential


Upper (URL)
2051CF 2051C Gage(1) 2051L Differential 2051L Gage(1)
Flowmeters
0.5 inH2O 25 inH2O –25 inH2O –25 inH2O
1 N/A N/A
(1.2 mbar) (62.3 mbar) (–62.1 mbar) (–62.1 mbar)
2.5 inH2O 250 inH2O –250 inH2O –250 inH2O –250 inH2O –250 inH2O
2
(6.2 mbar) (0.62 bar) (–0.62 bar) (–0.62 bar) (–0.62 bar) (–0.62 bar)
10 inH2O 1000 inH2O -1000 inH2O –393 inH2O –1000 inH2O –393 inH2O
3
(24.9 mbar) (2.49 bar) (-2.49 bar) (–979 mbar) (–2.49 bar) (–979 mbar)
3 psi 300 psi -300 psi –14.2 psig –300 psi –14.2 psig
4
(0.207 bar) (20.6 bar) (-20,6 bar) (–979 mbar) (–20.7 bar) (–979 mbar)
20 psi 2000 psi -2000 psi –14.2 psig
5 N/A N/A
(1.38 bar) (137.9 bar) (-137.9 bar) (–979 mbar)

(1) Assumes atmospheric pressure of 14.7 psig.

Table 8. Range and sensor limits


2051T
Range and Sensor Limits
Range

Minimum
Upper Lower Lower(1)
Span
(URL) (LRL) (Abs) (LRL) (Gage)
0.3 psi 30 psi 0 psia –14.7 psig
1
(20.6 mbar) (2.06 bar) (0 bar) (–1.01 bar)
1.5 psi 150 psi 0 psia –14.7 psig
2
(0.103 bar) (10.3 bar) (0 bar) (–1.01 bar)
8 psi 800 psi 0 psia –14.7 psig
3
(0.55 bar) (55.2 bar) (0 bar) (–1.01 bar)
40 psi 4000 psi 0 psia –14.7 psig
4
(2.76 bar) (275.8 bar) (0 bar) (–1.01 bar)
2,000 psi 10,000 psi 0 psia –14.7 psig
5
(137.9 bar) (689.4 bar) (0 bar) (–1.01 bar)

(1) Assumes atmospheric pressure of 14.7 psig.

Service
Liquid, gas, and vapor applications

[Link] 53
Rosemount 2051 April 2013

Protocols Local Operator Interface


The LOI utilizes a 2 button menu with internal and external
4–20 mA HART (Output Code A) configuration buttons. Internal buttons are always
Power supply configured for Local Operator Interface. External Buttons can
External power supply required. Standard transmitter be configured for either LOI, (option code M4), Analog Zero
operates on 10.5 to 42.4 Vdc with no load. and Span (option code D4) or Digital Zero Trim (option code
DZ). See 2051 with Selectable HART product manual
Load limitations
(00809-0100-4107) for LOI configuration menu.
Maximum loop resistance is determined by the
voltage level of the external power supply, as FOUNDATION fieldbus (Output code F)
described by:
Power supply
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
External power supply required; transmitters operate on 9.0 to
32.0 Vdc transmitter terminal voltage.
1387 Current draw
17.5 mA for all configurations (including LCD display option)
Load (s)

1000
Indication
500 Operating
Optional two line LCD display
Region
0 FOUNDATION fieldbus function block
10.5 20 30 Execution times
Voltage (Vdc) 42.4(1)
Communication requires a minimum Block Execution Time
loop resistance of 250 ohms. Resource -
(1) For CSA approval, power supply must not exceed 42.4 V. Transducer -
LCD Block -
Indication Analog Input 1, 2 30 milliseconds
Optional two line LCD/LOI Display PID 45 milliseconds
Zero and span adjustment requirements Input Selector 30 milliseconds
Zero and span values can be set anywhere within the range limits stated Arithmetic 35 milliseconds
in Table 7 and Table 8. Signal Characterizer 40 milliseconds
Integrator 35 milliseconds
Span must be greater than or equal to the minimum span stated
in Table 7 and Table 8. FOUNDATION fieldbus parameters
Output Schedule Entries 7 (max.)
Links 20 (max.)
Two-wire 4-20mA, user selectable for linear or square root
output. Digital process variable superimposed on 4-20 mA Virtual Communications Relationships
12 (max.)
(VCR)
signal, available to any host that conforms to HART protocol.
2051 Standard function blocks
Digital communications based on HART Revision 5 protocol. Resource block
2051 with selectable HART Contains hardware, electronics, and diagnostic
information.
The 2051 with Selectable HART comes with Selectable HART
Revisions. Digital communications based on HART Revision 5 Transducer block
(default) or Revision 7 (option code HR7) protocol can be Contains actual sensor measurement data including the
selected. The HART revision can be switched in the field using sensor diagnostics and the ability to trim the pressure
any HART based configuration tool or the optional local operator sensor or recall factory defaults.
interface (LOI). LCD block
Configures the local display.
2 Analog input blocks
Processes the measurements for input into other
function blocks. The output value is in engineering units
or custom and contains a status indicating
measurement quality.

54 [Link]
April 2013 Rosemount 2051

PID block Physical block


Contains all logic to perform PID control in the field The physical block defines the physical resources of the
including cascade and feedforward. device including type of memory, hardware,
electronics, and diagnostic information.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the Transducer block
current link master device fails or is removed from the segment. Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
Advanced control function block suite (Option Code A01) sensor or recall factory defaults.
Input selector block Indication
Selects between inputs and generates an output using
Optional two line LCD display.
specific selection strategies such as minimum,
maximum, midpoint, average or first “good.” Local Operator Interface
Arithmetic block Optional external configuration buttons.
Provides pre-defined application-based equations
including flow with partial density compensation, Wireless (Output Code X)
electronic remote seals, hydrostatic tank gauging, ratio Output
control, and others.
IEC 62591 (WirelessHART), 2.4 GHz DSSS
Signal characterizer block
Wireless radio (Internal Antenna, WP5 Option)
Characterizes or approximates any function that defines
an input/output relationship by configuring up to • Frequency: 2.400 - 2.485 GHz
twenty X, Y coordinates. The block interpolates an • Channels: 15
output value for a given input value using the curve • Modulation: IEEE 802.15.4 compliant DSSS
defined by the configured coordinates. • Transmission: Maximum of 10 dBm EIRP

Integrator block Local display


Compares the integrated or accumulated value from The optional 3-line, 7-digit LCD can display user-selectable
one or two variables to pre-trip and trip limits and information such as primary variable in engineering units, scaled
generates discrete output signals when the limits are variable, percent of range, sensor module temperature, and
reached. This block is useful for calculating total flow, electronics temperature. The display updates based on the
total mass, or volume over time. wireless update rate.

PROFIBUS PA (Output Code W) Digital zero trim


Digital Zero trim (option DZ) is an offset adjustment to
Profile version compensate for mounting position effects, up to 5% of URL.
3.02
Update rate
Power supply User selectable 1 sec. to 60 min.
External power supply required; transmitters operate on 9.0 to
Wireless sensor module for in-line transmitters
32.0 Vdc transmitter terminal voltage.
The 2051 Wireless transmitter requires the engineered polymer
Current draw housing to be selected. The standard sensor module will come
17.5 mA for all configurations (including LCD display option) with aluminum material. If stainless steel is required, the option
WSM must be selected.
Output update rate
Four times per second Power module
Field replaceable, keyed connection eliminates the risk of incorrect
Standard function blocks installation, Intrinsically Safe Lithium-thionyl chloride Power Module
with PBT/PC enclosure. Ten-year life at one minute update rate.(1)
Analog Input (AI Block)
The AI function block processes the measurements and
(1) Reference conditions are 70 °F (21 °C), and routing data for three
makes them available to the host device. The output additional network devices.
value from the AI block is in engineering units and Note: Continuous exposure to ambient temperature limits of -40 °F or
contains a status indicating the quality of the 185 °F (-40 °C or 85 °C) may reduce specified life by less than 20 per-
cent.
measurement.

[Link] 55
Rosemount 2051 April 2013

HART 1-5 Vdc Low Power (Output Code M) 2051L


Output Limit is flange rating or sensor rating, whichever is lower (Table
Three wire 1–5 Vdc output, user-selectable for linear 9 on page 56).
or square root output. Digital process variable Table 9. 2051L Flange Rating
superimposed on voltage signal, available to any host Standard Type CS Rating SST Rating
conforming to the HART protocol.
ANSI/ASME Class 150 285 psig 275 psig
2051 ANSI/ASME Class 300 740 psig 720 psig
Digital communications based on HART Revision 5 At 100 °F (38 °C), the rating decreases
protocol. with increasing temperature, per ANSI/ASME B16.5.
2051 with selectable HART DIN PN 10–40 40 bar 40 bar
The 2051 with Selectable HART comes with Selectable DIN PN 10/16 16 bar 16 bar
HART Revisions. Digital communications based on At 248 °F (120 °C), the rating decreases
HART Revision 5 (default) or Revision 7 (option code with increasing temperature, per DIN 2401.
HR7) protocol can be selected. The HART revision can
Static pressure limit
be switched in the field using any HART based
configuration tool or the optional local operator 2051CD, 2051CF
interface (LOI). • Operates within specifications between static line pressures of -14.2
Local Operator Interface psig (0.034 bar) and 3,626 psig (250 bar)
The LOI utilizes a 2 button menu with internal and •For Option Code P9, 4,500 psig (310,3 bar)
external configuration buttons. Internal buttons are • Range 1: 0.5 psia to 2,000 psig (34 mbar and 137,9 bar)
always configured for Local Operator Interface. Burst pressure limits
External Buttons can be configured for either LOI,
(option code M4), Analog Zero and Span (option code 2051C, 2051CF Coplanar or traditional process flange
D4) or Digital Zero Trim (option code DZ). See 2051 • 10,000 psig (689.5 bar)
with Selectable HART product manual
2051T in-line
(00809-0100-4107) for LOI configuration menu.
• Ranges 1–4: 11,000 psi (758.4 bar)
Power supply • Range 5: 26,000 psi (1792.6 bar)
External power supply required. Standard transmitter
operates on 9 to 28 Vdc with no load. Temperature limits
Ambient
Power consumption
–40 to 185 °F (–40 to 85 °C)
3.0 mA, 27–84 mW With LCD display(1) (2): –40 to 175 °F (–40 to 80 °C)
Output load
Storage(1)
100 k or greater (meter input impedance)
–50 to 230 °F (–46 to 110 °C)
Turn-On time With LCD display: –40 to 185 °F (–40 to 85 °C)
Performance within specifications less than 2.0 With Wireless Output: -40 °F to 185 °F (-40 °C to 85 °C)
seconds after power is applied to the transmitter.
Overpressure limits (1) 2051 LCD display may not be readable and LCD updates may be
slower at temperatures below -4 °F (-20 °C).
Transmitters withstand the following limits without damage:

2051C, 2051CF (2) Wireless LCD display may not be readable and LCD updates will be
slower at temperatures below -4 °F (-20 °C)
• Ranges 2–5: 3,626 psig (250 bar)
4,500 psig (310,3 bar) for option code P9
• Range 1: 2,000 psig (137,9 bar)

2051T
• Range 1: 750 psi (51,7 bar)
• Range 2: 1,500 psi (103,4 bar)
• Range 3: 1,600 psi (110,3 bar)
• Range 4: 6,000 psi (413,7 bar)
• Range 5: 15,000 psi (1034,2 bar)

56 [Link]
April 2013 Rosemount 2051

Process 2051
At atmospheric pressures and above. See Table 10. Analog output response to a step input change is
Table 10. Process Temperature Limits user-selectable from 0 to 36 seconds for one time
constant. This software damping is in addition to
2051C, 2051CF sensor module response time.
(1)
Silicone Fill Sensor
FOUNDATION fieldbus
with Coplanar Flange –40 to 250 °F (–40 to 121 °C)(2)
Transducer block: 0.4 seconds fixed
with Traditional Flange –40 to 300 °F (–40 to 149 °C)(2)(3)
AI Block: User configurable
with Level Flange –40 to 300 °F (–40 to 149 °C)(2)
with 305 Integral PROFIBUS PA
–40 to 300 °F (–40 to 149 °C)(2)
Manifold AI Block only: User configurable
Inert Fill Sensor(1) –40 to 185 °F (–40 to 85 °C)(3) Failure mode alarm
2051T (Process Fill Fluid)
Silicone Fill Sensor(1) -40 to 250 °F (-40 to 121 °C)(2) HART 4-20 mA (Output Code A)
Inert Fill Sensor(1) -22 to 250 °F (-30 to 121 °C)(2) If self-diagnostics detect a sensor or microprocessor failure, the
analog signal is driven either high or low to alert the user. High or
2051L Low-Side Temperature Limits
low failure mode is user-selectable with a jumper on the
Silicone Fill Sensor(1) –40 to 250 °F (–40 to 121 °C)(2) transmitter. The values to which the transmitter drives its
Inert Fill Sensor(1) -22 to 250 °F (-30 to 121 °C) (2) output in failure mode depend on whether it is
2051L High-Side Temperature Limits (Process Fill Fluid) factory-configured to standard or NAMUR-compliant operation.
Syltherm® XLT –100 to 300 °F (–73 to 149 °C) The values for each are as follows:
D.C. Silicone 704 ® 60 to 400 °F (15 to 205 °C) Standard Operation
D.C. Silicone 200 –40 to 400 °F (–40 to 205 °C) Output Code Linear Output Fail High Fail Low
Inert –50 to 350 °F (–45 to 177 °C) A 3.9  I  20.8 I  21.75 mA I  3.75 mA
Glycerin and Water 0 to 200 °F (–17 to 93 °C) M 0.97  V  5.2 V  5.4 V V  0.95 V
Neobee M-20 0 to 400 °F (–17 to 205 °C)
NAMUR-Compliant Operation
Propylene Glycol and
0 to 200 °F (–17 to 93 °C)
Water Output Code Linear Output Fail High Fail Low
A 3.8  I  20.5 I  22.5 mA I  3.6 mA
(1) Process temperatures above 185 °F (85 °C) require derating the ambient
limits by a 1.5:1 ratio. Output code F and X
If self-diagnostics detect a gross transmitter failure, that
(2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below information gets passed as a status along with the process
0.5 psia. variable.
(3) 160 °F (71 °C) limit in vacuum service.
Physical specifications
Humidity limits
0–100% relative humidity
Electrical connections
1
/2–14 NPT, G1/2, and M20 × 1.5 conduit.
Volumetric displacement
Less than 0.005 in3 (0.08 cm3)
Process connections
2051C
Damping • 1/4–18 NPT on 21/8-in. centers
• 1/2–14 NPT and RC 1/2 on 2-in.(50,8 mm), 21/8-in. (54,0 mm), or
4-20 mA HART 21/4-in. (57,2 mm) centers (process adapters)
2051 with selectable HART 2051T
Analog output response to a step input change is • 1/2–14 NPT female
user-enterable from 0.0 to 60 seconds for one time • G1/2 A DIN 16288 Male (available in SST for Range 1–4 transmitters
constant. This software damping is in addition to only)
sensor module response time. • Autoclave type F-250-C (Pressure relieved 9/16–18 gland thread; 1/4
OD high pressure tube 60° cone; available in SST for Range 5
transmitters only)

[Link] 57
Rosemount 2051 April 2013

2051L Paint for aluminum housing


• High pressure side: 2-in.(50,8 mm), 3-in. (72 mm), or 4-in. (102 Polyurethane
mm), ASME B 16.5 (ANSI) Class 150 or 300 flange;
50, 80, or 100 mm, DIN 2501 PN 40 or 10/16 flange Coplanar sensor module housing
• Low pressure side: 1/4–18 NPT on flange, 1/2–14 NPT on process CF-3M (Cast version of 316L SST)
adapter
Bolts
2051CF ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
• For 2051CFA wetted parts, see 00813-01000-4485 in the 485 ASTM F593G, Condition CW1 (Austenitic 316 SST)
section ASTM A193, Grade B7M (zinc plated alloy steel)
• For 2051CFC wetted parts, see 00813-01000-4485 in the 405 Alloy K-500
section
• For 2051CFP wetted parts, see 00813-01000-4485 in the 1195 Sensor module fill fluid
section Silicone or inert halocarbon
In-Line series uses Fluorinert® FC-43
2051C process wetted parts
Process fill fluid (2051L only)
Drain/Vent Valves Syltherm XLT, D.C. Silicone 704,
316 SST or Alloy C-276 D.C. Silicone 200, inert, glycerin and water, Neobee M-20, or
Process flanges and adapters propylene glycol and water
Plated carbon steel, SST CF-8M (cast version of 316 SST, material Cover O-rings
per ASTM-A743), or CW2M (cast version of Alloy C) Buna-N
Wetted O-rings Silicone (for wireless option code X)
Glass-filled PTFE or Graphite-filled PTFE Power module
Process isolating diaphragms Field replaceable, keyed connection eliminates the risk of
316L SST, Alloy C-276, or Tantalum incorrect installation, Intrinsically Safe Lithium-thionyl chloride
Power Module with PBT enclosure.
2051T process wetted parts
Shipping weights
Process connections Table 11. Transmitter weights without Options(1)
• 316L SST or Alloy C-276
Transmitter Standard 2051 In lb. (kg) Wireless In lb. (kg)
Process Isolating diaphragms 2051C 4.9 (2.2) 3.9 (1,8)
• 316L SST or Alloy C-276
2051L Table 12 below Table 12 below
2051L Process wetted parts 2051T 3.1 (1.4) 1.9 (0,86)

Flanged process connection (Transmitter high side) (1) Transmitter weights include the sensor module and housing only
Process diaphragms, Including process gasket surface (aluminum for standard 2051 and polymer for wireless).

•316L SST, Alloy C-276, or Tantalum


Extension
•CF-3M (Cast version of 316L SST, material per ASTM-A743), or
Cast C-276. Fits schedule 40 and 80 pipe.
Mounting flange
•Zinc-cobalt plated CS or SST

Reference process connection (Transmitter low side)


Isolating diaphragms
•316L SST or Alloy C-276
Reference flange and adapter
•CF-8M (Cast version of 316 SST, material per ASTM-A743)

Non-wetted parts for 2051C/T/L


Electronics housing
Low-copper aluminum or CF-8M (Cast version of 316 SST).
Enclosure Type 4X, IP 65, IP 66, IP68
Housing Material Code P: PBT/PC with NEMA 4X and IP66/67/68

58 [Link]
April 2013 Rosemount 2051

Table 12. 2051L Weights without Options


Flush 2-in. Ext. 4-in. Ext. 6-in. Ext.
Flange
lb. (kg) lb (kg) lb (kg) lb (kg)
2-in., 150 12.5 (5,7) — — —
3-in., 150 17.5 (7,9) 19.5 (8,8) 20.5 (9,3) 21.5 (9,7)
4-in., 150 23.5 (10,7) 26.5 (12,0) 28.5 (12,9) 30.5 (13,8)
2-in., 300 17.5 (7,9) — — —
3-in., 300 22.5 (10,2) 24.5 (11,1) 25.5 (11,6) 26.5 (12,0)
4-in., 300 32.5 (14,7) 35.5 (16,1) 37.5 (17,0) 39.5 (17,9)
DN 50/PN
13.8 (6,2) — — —
40
DN 80/PN
19.5 (8,8) 21.5 (9,7) 22.5 (10,2) 23.5 (10,6)
40
DN 100/
17.8 (8,1) 19.8 (9,0) 20.8 (9,5) 21.8 (9,9)
PN 10/16
DN 100/
23.2 (10,5) 25.2 (11,5) 26.2 (11,9) 27.2 (12,3)
PN 40

Table 13. Transmitter Options weights


Add
Code Option
lb (kg)
J, K, L, M Stainless Steel Housing 3.9 (1,8)
M5 LCD display for Aluminum Housing 0.5 (0,2)
M5 LCD Display for Wireless Output 0.1 (0,04)
SST Mounting Bracket for Coplanar
B4 1.0 (0,5)
Flange
Mounting Bracket for Traditional
B1 B2 B3 2.3 (1,0)
Flange
Mounting Bracket for Traditional
B7 B8 B9 2.3 (1,0)
Flange
BA, BC SST Bracket for Traditional Flange 2.3 (1,0)
H2 Traditional Flange 2.6 (1,2)
H3 Traditional Flange 3.0 (1,4)
H4 Traditional Flange 3.0 (1,4)
H7 Traditional Flange 2.7 (1,2)
FC Level Flange—3 in., 150 12.7 (5,8)
FD Level Flange—3 in., 300 15.9 (7,2)
FA Level Flange—2 in., 150 8.0 (3,6)
FB Level Flange—2 in., 300 8.4 (3,3)
FP DIN Level Flange, SST, DN 50, PN 40 7.8 (3,5)
FQ DIN Level Flange, SST, DN 80, PN 40 12.7 (5,8)
WSM SST Sensor Module 1.0 (0,45)
Power Module (701PGNKF) 0.4 (0,18)

[Link] 59
Rosemount 2051 April 2013

Product certifications
Approved manufacturing locations I5 Intrinsically-Safe and Non-incendive
Certificate No: 3033457
Rosemount Inc. — Chanhassen, Minnesota USA
Applicable Standards: FM Class 3600 – 1998, FM Class
Emerson Process Management GmbH & Co. — Wessling,
3610 – 2007, FM Class 3611 – 2004, FM Class 3810 – 2005
Germany
Markings: Intrinsically Safe for use in Class I, Division 1,
Emerson Process Management Asia Pacific
Groups A, B, C, and D; Class II, Divisions 1, Groups E, F, and
Private Limited — Singapore
G; Class III, Division 1; Class I, Zone 0, AEx ia IIC;
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China Nonincendive for use in Class I, Division 2, Groups A, B, C
Emerson Process Management LTDA — Sorocaba, Brazil and D; in accordance with Control Drawing 02051-1009
Emerson Process Management (India) Pvt. Ltd — Daman, India T4 (-50 °C to +70 °C) Enclosure Type 4X
Temperature Code:T4 (Ta = -50 °C to +70 °C),
European directive information
Enclosure Type 4X
The EC declaration of conformity for all applicable European directives
for this product can be found on the Rosemount website at
For input parameters see control drawing 02051-1009.
[Link]. A hard copy may be obtained by contacting an
Emerson Process Management representative. Special Conditions for Safe Use:

1. The Model 2051 transmitter housing contains


Ordinary location certification for Factory Mutual
aluminum and is considered a potential risk of ignition by
As standard, the transmitter has been examined and tested to
impact or friction. Care must be taken into account during
determine that the design meets basic electrical, mechanical,
installation and use to prevent impact and friction.
and fire protection requirements by FM, a nationally
recognized testing laboratory (NRTL) as accredited by the 2. The Model 2051 transmitter with the transient terminal
Federal Occupational Safety and Health Administration block (Option code T1) will not pass the 500Vrms
(OSHA). dielectric strength test and this must be taken into
account during installation.
HART Protocol
Canadian Standards Association (CSA)
Hazardous locations certifications All CSA hazardous approved transmitters are certified per ANSI/ISA
12.27.01-2003.
North American certifications
E6 Explosion-Proof, Dust Ignition Proof
FM Approvals Certificate No: 2041384
E5 Explosion-Proof and Dust-Ignition-Proof Applicable Standards: CSA Std. C22.2 No. 142 - M1987,
Certificate No: 3032938 CSA Std. C22.2 No. 30 - M1986, CSA Std. C22.2 No. 213 -
Applicable Standards: FM Class 3600 – 1998, FM Class M1987, CAN/CSA-E60079-0:07,
3615 – 2006, FM Class 3810 – 2005, ANSI/NEMA 250 – CAN/CSA-E60079-1:07
1991, ANSI/IEC 60529 – 2004 Markings: Explosion-Proof for Class I, Division 1, Groups B,
Markings: Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignitions Proof for Class II and Class III,
C, and D Division 1, Groups E, F, and G. Suitable for Class I, Division
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G; 2, Groups A, B, C, and D for indoor and outdoor hazardous
and Class III, Division 1. locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X,
T5 (Ta= -50 °C to +85 °C), Factory Sealed, Enclosure Type factory sealed. Single Seal.
4X I6 Intrinsically Safe
Certificate no.: 2041384
Applicable Standards: CSA Std. C22.2 No. 142 - M1987,
CSA Std. C22.2 No. 213 - M1987, CSA Std. C22.2 No. 157 -
92, CSA Std. C22.2 No. 213 - M1987, ANSI/ISA 12.27.01 -
2003, CAN/CSA-E60079-0:07, CAN/CSA-E60079-11:02
Markings: Intrinsically safe for Class I, Division 1, Groups A,
B, C, and D when connected in accordance with
Rosemount drawings 02051-1008. Temperature code
T3C. Class I Zone 1 Ex ia IIC T3C. Single Seal. Enclosure Type
4X.

60 [Link]
April 2013 Rosemount 2051

European Certifications 3. In case of repair, Contact Emerson Process Management


for information on the dimensions of flameproof joints.
I1 ATEX Intrinsic Safety
Certificate No: Baseefa08ATEX0129X ND ATEX Dust
Applicable Standards: EN60079-0:2012, Certification No. Baseefa08ATEX0182X
EN60079-11:2012 Applicable Standards: EN60079-0:2012, EN
Markings: II 1 G Ex ia IIC T4 Ga(–60 °C  Ta  +70 °C) 60079-31:2009
IP66 IP68 Markings: II 1 D Ex t IIIC T50 °C T500 60 °C Da
1180 IP66 IP68
Ui = 42.4 Vdc
Table 14. Input Parameters 1180
Ui = 30 V
Ii = 200 mA Special Conditions for Safe Use (X):
If the equipment is fitted with an optional 90 V transient
Pi = 1.0 W
suppressor, it is incapable of isolation from earth test and
Ci = 0.012 μF
this must be taken into account during installation.
Special Conditions for Safe Use (X): IECEx Certifications
When the optional transient protection terminal block is
installed, the apparatus is not capable of withstanding the I7 IECEx Intrinsic Safety
500 V insulation test required by Clause 6.3.12 of Certification No. IECExBAS08.0045X
EN60079-11. This must be taken into account when Applicable Standards: IEC60079-0:2011,
installing the apparatus.
IEC60079-11:2011
Ex ia IIC T4 Ga (–60 °C  Ta  +70 °C)
N1 ATEX Type n
Certification No. Baseefa08ATEX0130X Table 15. Input Parameters
Applicable Standards: EN60079-0:2012,
Ui = 30 V
EN60079-15:2010
Markings: II 3 G Ii = 200 mA
Ex nA IIC T4 Gc (–40 °C  Ta  +70 °C) Pi = 1.0 W
Ui = 42.4 Vdc max Ci = 0.012 μF
IP66
Special Conditions for Safe Use (X):
When the optional transient protection terminal block is
Special Conditions for Safe Use (X): installed, the apparatus is not capable of withstanding the
When the optional transient protection terminal block is 500V insulation test required by Clause 6.3.12 of
installed, the apparatus is not capable of withstanding a EN60079-11. This must be taken into account when
500 V r.m.s. test to case. This must be taken into account installing the apparatus.
on any installation in which it is used, for example by
assuring that the supply to the apparatus is galvanically E7 IECEx Flame-Proof
isolated. Certification No. IECEx KEM 08.0024X
Applicable Standards: IEC60079-0:2011,
E1 ATEX Flame-Proof IEC60079-1:2007-04, IEC60079-26:2006
Certification No. KEMA 08ATEX0090X Ex d IIC T6 Ga/Gb (–50 °C  Ta  65 °C)
Applicable Standards: EN60079-0:2009, IEC60079-0:2011, Ex d IIC T5 Ga/Gb (–50 °C  Ta  80 °C)
EN60079-1:2007, EN60079-26:2007 Ui = 42.4 Vdc
Markings II 1/2 G
Ex d IIC T6 Ga/Gb (–50 °C  Ta  65 °C) Special Conditions for Safe Use (X):
Ex d IIC T5 Ga/Gb (–50 °C  Ta  80 °C)
1. Appropriate ex d blanking plugs, cable glands, and
IP66
wiring needs to be suitable for a temperature of 90 °C.
1180
2. This device contains a thin wall diaphragm. Installation,
Ui = 42.4 Vdc
maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be
Special Conditions for Safe Use (X):
subjected. The manufacturer’s instructions for
1. Appropriate ex d blanking plugs, cable glands, and
wiring needs to be suitable for a temperature of 90 °C. maintenance shall be followed in detail to assure safety
2. This device contains a thin wall diaphragm. Installation, during its expected lifetime.
maintenance, and use shall take into account the 3. In case of repair, Contact Emerson Process Management
environmental conditions to which the diaphragm will for information on the dimensions of flameproof joints.
be subjected. The manufacturer’s instructions for
maintenance shall be followed in detail to assure safety
during its expected lifetime.
[Link] 61
Rosemount 2051 April 2013

N7 IECEx Type 'n' Combinations of Certifications


Certification No. IECExBAS08.0046X Stainless steel certification tag is provided when optional approval is
Applicable Standards: IEC60079-0: 2011, IEC60079-15: specified. Once a device labeled with multiple approval types is
2010 installed, it should not be reinstalled using any other approval types.
Ex nA IIC T4 Gc (–40 °C  Ta  +70 °C) Permanently mark the approval label to distinguish it from unused
Ui = 42.4 Vdc max approval types.

K1 E1, I1, N1, and ND combination


Special Conditions for Safe Use (X):
K2 E2 and I2 combination
When the optional transient protection terminal block is
K5 E5 and I5 combination
installed, the apparatus is not capable of withstanding a
500 V r.m.s. test to case. This must be taken into account K6 I6 and E6 combination
on any installation in which it is used, for example by K7 E7, I7, and N7 combination
assuring that the supply to the apparatus is galvanically
isolated. KA E1, I1, E6, and I6 combination
KB E5, I5, E6, and I6 combination
TIIS Certifications
KC E1, I1, E5, and I5 combination
E4 TIIS Flame-Proof
KD E1, I1, E5, I5, E6, and I6 combination
Ex d IIC T6

Inmetro Certifications

E3 Flame-Proof
NEPSI Certificate No: GYJ101321X
Applicable standards: GB3836.1-2000, GB3836.2-2000
Markings: Ex d II C T5/T6
T6 = -50 °C  Tamb  80 °C
T5 = -50 °C  Tamb  65 °C

I3 Intrinsic Safety
Certificate No: GYJ101320X
Applicable Standards: GB3836.1-2000, GB3836.4-2000
Markings: Ex ia IIC T4
T4: -60 °C  Tamb  70 °C
China (NEPSI) Certifications

E3 Flame-Proof
Ex d IIC T5/T6

I3 Intrinsic Safety
Ex ia IIC T4
CCOE Certifications

IW Intrinsic Safety
Ex ia IIC T4

EW Flame-Proof
Ex d IIC T5

62 [Link]
April 2013 Rosemount 2051

FOUNDATION FIELDBUS AND PROFIBUS PA PROTOCOLS


Hazardous Locations Certifications Markings: Intrinsically safe for Class I, Division 1, Groups A,
B, C, and D when connected in accordance with
North American Certifications
Rosemount drawings 02051-1008. Temperature code
FM Approvals T3C. Class I Zone 1 Ex ia IIC T3C. Single Seal. Enclosure Type
E5 Explosion-Proof and Dust-Ignition-Proof 4X.
Certificate No: 3032938 European Certifications
Applicable Standards: FM Class 3600 – 1998, FM Class I1 ATEX Intrinsic Safety
3615 – 2006, FM Class 3810 – 2005, ANSI/NEMA 250 – Certificate No: Baseefa08ATEX0129X
1991, ANSI/IEC 60529 – 2004 Applicable Standards: EN60079-0:2012,
Markings: Explosion-Proof for Class I, Division 1, Groups B, EN60079-11:2012
C, and D Markings: II 1 G Ex ia IIC T4 Ga(–60 °C  Ta  +70 °C)
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G; IP66 IP68
and Class III, Division 1. 1180
T5 (Ta= -50 °C to +85 °C), Factory Sealed, Enclosure Type
4X
Table 16. Input Parameters
IE/I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C
and D; Class II, Division 1, Groups E, F and G; Class III, Ui = 30 V
Division 1; Class I, Zone 0, AEx ia IIC; Nonincendive for use Ii = 300 mA
in Class I, Division 2, Groups A, B, C and D; in accordance Pi = 1.3 W
with Control Drawing 02051-1009. Ci = 0 μF

For FOUNDATION fieldbus and PROFIBUS PA, Temperature Special Conditions for Safe Use (X):
Code: T4 (Ta = -50 °C to +70 °C)
When the optional transient protection terminal block is
For FISCO, installed, the apparatus is not capable of withstanding the
Temperature Code: T4 (Ta = -50 °C to +60 °C) 500 V insulation test required by Clause 6.3.12 of
EN60079-11. This must be taken into account when
Enclosure Type 4X installing the apparatus.
For input parameters see control drawing 02051-1009.
IA ATEX FISCO Intrinsic Safety
Canadian Standards Association (CSA) Certificate No: Baseefa08ATEX0129X
Applicable Standards: EN60079-0:2012,
All CSA hazardous approved transmitters are certified per
EN60079-11:2012
ANSI/ISA 12.27.01-2003.
Markings: II 1 G Ex ia IIC T4 Ga(–60 °C  Ta  +60 °C)
E6 Explosion-Proof, Dust Ignition Proof IP66 IP68
Certificate No: 2041384 1180
Applicable Standards: CSA Std. C22.2 No. 142 - M1987,
CSA Std. C22.2 No. 30 - M1986, CSA Std. C22.2 No. 213 - Table 17. Input Parameters
M1987, CAN/CSA-E60079-0:07, Ui = 30 V
CAN/CSA-E60079-1:07 Ii = 200 mA
Pi = 1.0 W
Markings: Explosion-Proof for Class I, Division 1, Groups B,
Ci =  0.012 μF
C, and D. Dust-Ignitions Proof for Class II and Class III,
Division 1, Groups E, F, and G. Suitable for Class I, Division
Special Conditions for Safe Use (X):
2, Groups A, B, C, and D for indoor and outdoor hazardous
locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X, When the optional transient protection terminal block is
factory sealed. Single Seal. installed, the apparatus is not capable of withstanding the
500 V insulation test required by Clause 6.3.12 of
EN60079-11. This must be taken into account when
I6/IF Intrinsically Safe installing the apparatus.
Certificate no.: 2041384
Applicable Standards: CSA Std. C22.2 No. 142 - M1987,
CSA Std. C22.2 No. 213 - M1987, CSA Std. C22.2 No. 157 -
92, CSA Std. C22.2 No. 213 - M1987, ANSI/ISA 12.27.01 -
2003, CAN/CSA-E60079-0:07, CAN/CSA-E60079-11:02

[Link] 63
Rosemount 2051 April 2013

N1 ATEX Type n IECEx Certifications


Certification No. Baseefa08ATEX0130X I7 IECEx Intrinsic Safety
Applicable Standards: EN60079-0:2012, Certification No. IECExBAS08.0045X
EN60079-15:2010 Applicable Standards: IEC60079-0:2011,
Markings: II 3 G IEC60079-11:2011
Ex nA IIC T4 Gc (–40 °C  Ta  +70 °C) Ex ia IIC T4 Ga (–60 °C  Ta  +70 °C)
Ui = 42.4 Vdc max
IP66 Table 18. Input Parameters
Ui = 30 V
Special Conditions for Safe Use (X): Ii = 300 mA
When the optional transient protection terminal block is Pi = 1.3 W
installed, the apparatus is not capable of withstanding a Ci = 0 μF
500 V r.m.s. test to case. This must be taken into account
on any installation in which it is used, for example by Special Conditions for Safe Use (X):
assuring that the supply to the apparatus is galvanically
The device is not capable of withstanding the 500 V
isolated.
insulation test required by Clause 6.3.12 of IEC60079-11.
E1 ATEX Flame-Proof This must be taken into account when installing the
Certification No. KEMA 08ATEX0090X apparatus.
Applicable Standards: EN60079-0:2009,
IEC60079-0:2011, EN60079-1:2007, EN60079-26:2007
IG IECEx FISCO Intrinsic Safety
Markings II 1/2 G
Certification No. IECExBAS08.0045X
Ex d IIC T6 Ga/Gb (–50 °C  Ta  65 °C)
Applicable Standards: IEC60079-0:2011,
Ex d IIC T5 Ga/Gb (–50 °C  Ta  80 °C)
IEC60079-11:2011
IP66
Ex ia IIC T4 Ga (-60 °C  Ta  +70 °C)
1180
IP66
Ui = 32 Vdc
1180
Special Conditions for Safe Use (X):

1. Appropriate ex d blanking plugs, cable glands, and Table 19. Input Parameters
wiring needs to be suitable for a temperature of 90 °C. Ui = 17.5 V
2. This device contains a thin wall diaphragm. Installation, Ii = 380 mA
maintenance, and use shall take into account the Pi = 5.32 W
environmental conditions to which the diaphragm will be Ci =  5 μF
subjected. The manufacturer’s instructions for Li = 10 μH
maintenance shall be followed in detail to assure safety
during its expected lifetime. Special Conditions for Safe Use (X):

3. In case of repair, Contact Emerson Process Management The device is not capable of withstanding the 500 V
for information on the dimensions of flameproof joints. insulation test required by Clause 6.3.12 of IEC 60079-11.
This must be taken into account when installing the
ND ATEX Dust apparatus.
Certification No. Baseefa08ATEX0182X
Applicable Standards: EN60079-0:2012, EN E7 IECEx Flame-Proof
60079-31:2009 Certification No. IECEx KEM 08.0024X
Markings: II 1 D Ex t IIIC T50 °C T500 60 °C Da Applicable Standards: IEC60079-0:2011,
IP66 IP68 IEC60079-1:2007-04, IEC60079-26:2006
Ui = 42.4 Vdc Ex d IIC T6 Ga/Gb (–50 °C  Ta  65 °C)
1180 Ex d IIC T5 Ga/Gb (–50 °C  Ta  80 °C)
Ui = 32 Vdc
Special Conditions for Safe Use (X):

If the equipment is fitted with an optional 90 V transient


suppressor, it is incapable of isolation from earth test and
this must be taken into account during installation.

64 [Link]
April 2013 Rosemount 2051

Special Conditions for Safe Use (X): IB FISCO Intrinsic Safety


Certificate No: CEPEL 09.1768X
Appropriate ex d blanking plugs, cable glands, and wiring
Ex ia IIC T4 Ga (-60°C < Tamb < +60°C) IP66
needs to be suitable for a temperature of 90 °C.

This device contains a thin wall diaphragm. Installation, Combinations of Certifications


maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be Stainless steel certification tag is provided when optional
subjected. The manufacturer’s instructions for approval is specified. Once a device labeled with multiple
maintenance shall be followed in detail to assure safety approval types is installed, it should not be reinstalled using any
during its expected lifetime. other approval types. Permanently mark the approval label to
distinguish it from unused approval types.
In case of repair, Contact Emerson Process Management
for information on the dimensions of flameproof joints. K1 E1, I1, N1 and ND combination

N7 IECEx Type 'n' K2 E2 and I2 combination


Certification No. IECExBAS08.0046X
K5 E5 and I5 combination
Applicable Standards: IEC60079-0: 2011, IEC60079-15:
2010 K6 E6 and I6 combination
Ex nA IIC T4 Gc (–40 °C  Ta  +70 °C)
Ui = 42.4 Vdc max K7 E7, I7 and N7 combination

KA E1, I1 E6 and I6 combination


Special Conditions for Safe Use (X):
KB E5, I5, E6 and I6 combination
The device is not capable of withstanding the 500 V
insulation test required by Clause 6.8.1 of IEC60079-15. KC E1, I1, E5 and I5 combination
This must be taken into account when installing the
device. KD E1, I1, E5, I5, E6 and I6 combination

TIIS Certifications

E4 TIIS Flame-Proof
Ex d IIC T6

China (NEPSI) Certifications

E3 Flameproof
NEPSI Certificate No.: GYJ101321X
Applicable Standards: GB3836.1-2000, GB3836.2-2000
Markings: Ex d II C T5/T6
T5: –50 °C  Ta  +80 °C
T6: –50 °C  Ta  +65 °C

I3 Intrinsic Safety
NEPSI Certificate No.: GYJ101320X
Applicable Standards: GB3836.1-2000, GB3836.4-2000
Markings: Ex ia IIC T4
T4: –60 °C  Ta  +70 °C

Inmetro Certifications
E2 Flameproof
Certificate No: CEPEL 09.1767X
Ex d IIC T* Ga/Gb IP66
T6 = -50 °C < Tamb < 65 °C
T5 = -50 °C < Tamb < 80 °C

I2 Intrinsic Safety
Certificate No: CEPEL 09.1768X
Ex ia IIC T4 Ga (-60°C < Tamb < +70°C) IP66

[Link] 65
Rosemount 2051 April 2013

IEC 62591 (WirelessHART Protocol)


Approved manufacturing locations North American certifications
Rosemount Inc. — Chanhassen, Minnesota USA Factory Mutual (FM) approvals
Fisher-Rosemount GmbH & Co. — Wessling, Germany
Emerson Process Management Asia Pacific Private I5 FM Intrinsically Safe
Limited — Singapore Certificate No: 3045342
Beijing Rosemount Far East Instrument Co., LTD — Applicable Standards: Class 3600:2011, Class 3610:2010,
Beijing, China Class 3810: 2005
Markings: Intrinsically Safe for Class I, Division I, Groups A,
European directive information B, C, D
The most recent revision of the EC declaration of Zone Marking: Class I Zone 0, AEx ia IIC
conformity can be found at [Link]. T4 (-40 °C to 70 °C)
Intrinsically Safe when installed according to Rosemount
Telecommunication compliance Drawing 03031-1062
All wireless devices require certification to ensure that Enclosure Type 4X/IP66/IP68
they adhere to regulations regarding the use of the RF
spectrum. Nearly every country requires this type of Specific Conditions for Safe Use:
product certification. Emerson is working with The inline pressure sensor may contain more than 10%
governmental agencies around the world to supply aluminum and is considered a potential risk of ignition by
fully compliant products and remove the risk of impact or friction. Care must be taken into account during
violating country directives or laws governing wireless installation and use to prevent impact and friction.
device usage.
The surface resistivity of the transmitter is greater than
FCC and IC one gigaohm. To avoid electrostatic charge build-up, it
This device complies with Part 15 of the FCC Rules. must not be rubbed or cleaned with solvents or a dry cloth.
Operation is subject to the following conditions: This The Model 2051 Wireless pressure Transmitter shall only
device may not cause harmful interference. This be used with the 701PGNKF Rosemount Smartpower
device must accept any interference received, Battery Pack.
including interference that may cause undesired
operation. This device must be installed to ensure a CSA - Canadian Standards Association
minimum antenna separation distance of 20 cm from I6 CSA Intrinsically Safe
all persons. Certificate No: 2526009
Ordinary location certification for FM Applicable Standards: CSA C22.2 No. 0-M91, CSA C22.2
No. 159-92
As standard, the transmitter has been examined and Markings: Intrinsically Safe For Class I, Division I, Groups A,
tested to determine that the design meets basic B, C, D
electrical, mechanical, and fire protection T4 (-40 °C to 70 °C)
requirements by FM, a nationally recognized testing Intrinsically safe when installed according to Rosemount
laboratory (NRTL) as accredited by the Federal drawing 03031-1063
Occupational Safety and Health Administration Enclosure Type 4X/IP66/IP68
(OSHA).
European certifications

I1 ATEX Intrinsic Safety


Certificate No: Baseefa12ATEX0228X
Applicable Standards: EN60079-11:2012,
EN60079-0:2012
Markings: Ex ia IIC T4 Ga (-40 °C Ta 70 °C)
II 1G
IP66/68
1180

66 [Link]
April 2013 Rosemount 2051

Specific Conditions for Safe Use (X):

The plastic enclosure may constitute a potential


electrostatic ignition risk and must not be rubbed or
cleaned with a dry cloth.

For use with Rosemount 701PGNKF only

I7 IECEx Intrinsic Safety


Certificate No: IECEx BAS 12.0124X
Applicable Standards: IEC60079-11:2011,
IEC60079-0:2011
Markings: Ex ia IIC T4 Ga (-40 °C Ta 70 °C)
IP66/68

Specific Conditions for Safe Use:

The plastic enclosure may constitute a potential


electrostatic ignition risk and must not be rubbed or
cleaned with a dry cloth.

For Use with Rosemount 701PGNKF only

[Link] 67
Rosemount 2051 April 2013

Dimensional drawings
2051C Exploded View

Nameplate
Local Configuration Buttons(1)

Electronics Housing

Terminal Block
Cover O-ring

Cover
Electronics Board

Housing Rotation Set Screw


(180° Maximum Housing Rotation
without Further Disassembly)

Sensor Module

Coplanar Flange

Process O-Ring
Drain/Vent Valve

Flange Adapter O-Ring

Flange Alignment Screw (Not


Pressure Retaining)

Flange Adapters

Flange Bolts

1) Span and Zero Adjustment Buttons are optional with 4-20 mA and 1-5 Vdc HART protocol. Local Operator Interface buttons are
optional for PROFIBUS PA protocol. Local Configuration Buttons are not available with FOUNDATION fieldbus.

68 [Link]
April 2013 Rosemount 2051

2051C Coplanar Flange


5.66 (144)
3.85 (98) 5.20 (132)
4.36 (111)

Fieldbus
7.03 (179) Display Cover

HART Display
Terminal
Cover
Connections
Transmitter
Circuitry

6.40 (163)
2051 Wireless Housing with Coplanar Platform

[Link] 69
Rosemount 2051 April 2013

2051C Coplanar Flange


2051C Coplanar with Rosemount 305 3-Valve Coplanar Integral Manifold

5.66 (144)
3.85 (98) 5.20 (132)
4.36 (111)

Fieldbus
Display Cover
6.19
(157)
7.44 Terminal
HART Display
(189) Connections
Cover
Transmitter
Circuitry

Drain/ Vent Valve

5.00 (127) 9.20 (234)


Max Open Max Open

Dimensions are in inches (millimeters).

70 [Link]
April 2013 Rosemount 2051

Coplanar Flange Mounting Configurations with


Optional Bracket (B4) for 2-in. Pipe or Panel Mounting
2.82 4.36
(72) (111) 5/16 ⫻ 11/2 Bolts
2.18
for Panel Mounting
(55) 2.8 (71)
(Not Supplied)
PANEL MOUNTING

7.03
3/8–16 × 11/4 Bolts
(178)
for Mounting
to Transmitter

6.15
(156) 2.81
(71) 3.4 (85)

4.73
(120)

2-inch U-Bolt
for Pipe Mounting
PIPE MOUNTING

6.22
(158) 3.51
(89)

Dimensions are in inches (millimeters).

[Link] 71
Rosemount 2051 April 2013

2051C Coplanar with Traditional Flange

5.66 (144)
3.85 (98) 5.20 (132)
4.36 (111)

Fieldbus
Display Cover

Terminal
HART Display
7.76 Connections
Cover
(197)
1
/2 - 14 NPT Flange Transmitter
Adapter (optional) Circuitry

Drain/
Vent Valve
1.626
(41,3)

2.13
1.10 (28) 3.40 (86) 1.05 (27)
(54)

2051C Coplanar with Rosemount 305 3-Valve Traditional Integral Manifold


5.66 (144)
3.85 (98) 5.20 (132)
4.36 (111)

Fieldbus
Display Cover
6.19
(157) HART Display
1 Cover
/2 - 14 NPT Terminal
Flange Connections Transmitter
Adapter Circuitry
Drain/ (optional)
Vent Valve

1.626
(71)
3.75 (95)
Max Open

2.126
1.05 3.50 1.10 (54)
(27) (89) (28) 6.20 (158) 2.70 (69)
Max Open Max Open
8.90 (226)
Max Open
Dimensions are in inches (millimeters).

72 [Link]
April 2013 Rosemount 2051

Traditional Flange Mounting Configurations with


Optional Brackets for 2-in. Pipe or Panel Mounting
Panel Mount (Bracket Option B2/B8) Pipe Mount (Bracket Option B3/B9/BC)
9.18 (233)

2.62
(67)
6.19
(157)

1.94
(49) 11.51
(292)

3.56 (90)
5.32 Max Open
(135) 4.85
(123)

3.50 1.10
(89) (28)
6.19 (157)

Pipe Mount (Bracket Option B1 / B7 / BA)

3.56 (90)
6.76 (172) MAX OPEN

1.10 (28)

3.50 (89)

2.62 (67)

0.93
(24)

Dimensions are in inches (millimeters).

[Link] 73
Rosemount 2051 April 2013

2051T Dimensional Drawings


5.66 (144)
3.85 (98) 5.20 (132)
4.36 (111)

Fieldbus
Display Cover

HART Display
7.15 (182)
Cover
Terminal
Transmitter Connections
Circuitry

2051 Wireless Housing with Inline Platform

74 [Link]
April 2013 Rosemount 2051

2051T Dimensional Drawings


2051T with Rosemount 306 2-Valve Integral Manifold
5.66 (144)
3.85 (98)
5.20 (132)
4.36 (111)

Fieldbus
Display Cover

7.15
(182)
HART Display
Cover
Terminal
Connections
Transmitter
Circuitry

4.85 4.40
(123) (112)

6.25 (159)
Max Open

Dimensions are in inches (millimeters).

[Link] 75
Rosemount 2051 April 2013

2051T Typical Mounting Configurations with Optional Mounting Bracket


Pipe Mounting Panel Mounting
3.85
(98)

5.16 (131)

1.99 (51)

2.81 (71)
6.21
(158)
3.49
(89)
4.72
(120)
6.90
(175)

Dimensions are in inches (millimeters).

76 [Link]
April 2013 Rosemount 2051

Rosemount 2051CFA Pak-Lok Annubar Flowmeter(1)


Front View Side View Top View

B
C

(1) The Pak-Lok Annubar model is available up to 600# ANSI (1,440 psig at 100 °F (99 bar at 38 °C)).

Table 20. 2051CFA Pak-Lok Annubar Flowmeter Dimensional Data


Sensor Size A (Max) B (Max) C (Max) D (Max)
1 8.50 (215.9) 14.55 (369.6) 9.00 (228.6) 6.00 (152.4)
2 11.00 (279.4) 16.30 (414.0) 9.00 (228.6) 6.00 (152.4)
3 12.00 (304.8) 19.05 (483.9) 9.00 (228.6) 6.00 (152.4)
Dimensions are in inches (millimeters)

[Link] 77
Rosemount 2051 April 2013

Rosemount 2051CFC Compact Orifice Flowmeter


Orifice Plate Side View Orifice Plate Front View Orifice Plate Top View
(Primary Element Type code P)
Compact Orifice Plate

1.13-in. (28.7 mm)


wafer thickness
(Primary Element Type code C)
Conditioning Orifice Plate

Table 21. 2051CFC Dimensional drawings


Primary Transmitter
A B C D
Element Type Height
7.75 (197) - closed 6.00 (152) - closed
Type P and C 5.62 (143) Transmitter Height + A 6.27 (159)
8.25 (210) - open 6.25 (159) - open
Dimensions are in inches (millimeters).

78 [Link]
April 2013 Rosemount 2051

Rosemount 2051CFP Integral Orifice Flowmeter


Side View

Bottom View Front View

10.2
8.8 [223.46] [258.28]
6.2
[156.51]
5.3
[134.51]

Dimensions are in inches (millimeters).

Table 22. 2051CFP Dimensional Drawings


Line Size
Dimension 1/2-in. (15 mm) 1-in. (25 mm) 11/2-in. (40 mm)
J (Beveled/Threaded pipe ends) 12.54 (318.4) 20.24 (514.0) 28.44 (722.4)
J (RF slip-on, RTJ slip-on, RF-DIN slip on) 12.62 (320.4) 20.32 (516.0) 28.52 (724.4)
J (RF 150#, weld neck) 14.37 (364.9) 22.37 (568.1) 30.82 (782.9)
J (RF 300#, weld neck) 14.56 (369.8) 22.63 (574.7) 31.06 (789.0)
J (RF 600#, weld neck) 14.81 (376.0) 22.88 (581.0) 31.38 (797.1)
K (Beveled/Threaded pipe ends) 5.74 (145.7) 8.75 (222.2) 11.91 (302.6)
K (RF slip-on, RTJ slip-on, RF-DIN slip on)(1) 5.82 (147.8) 8.83 (224.2) 11.99 (304.6)
K (RF 150#, weld neck) 7.57 (192.3) 10.88 (276.3) 14.29 (363.1)
K (RF 300#, weld neck) 7.76 (197.1) 11.14 (282.9) 14.53 (369.2)
K (RF 600#, weld neck) 8.01 (203.4) 11.39 (289.2) 14.85 (377.2)
B.D. (Bore Diameter) 0.664 (16.87) 1.097 (27.86) 1.567 (39.80)
Dimensions are in inches (millimeters).

(1) Downstream length shown here includes plate thickness of 0.162-in. (4.11 mm).

[Link] 79
Rosemount 2051 April 2013

2051L Liquid Level


2-in. Flange Configuration
3- and 4-in. Flange Configuration
(Flush Mount Only)

3.85 3.85
(98) (98)

E
D

A 2-in., 4-in., or 6-in. A


H Extension H
(50.8, 101.6, 152.4)

Optional Flushing Connection Ring


(Lower Housing) 5.66 (144) Fieldbus HART
5.20 (132) Display Display
4.36 (111) Cover Cover
G

Terminal
Connections
6.60
F (68)

E 7.02
(178)
8.12
(206)

Flushing Connection
Diaphragm Assembly and
Mounting Flange

Transmitter
Circuitry
B C

Dimensions are in inches (millimeters).

80 [Link]
April 2013 Rosemount 2051

Table 23. 2051L Dimensional Specifications


Bolt Circle Outside Extension O.D.
Pipe Flange No. of Bolt Hole
Class(1) Diameter Diameter Diameter(1) Gasket
Size Thickness A Bolts Diameter
B C D Surface E
2 (51) 0.69 (18) 4.75 (121) 6.0 (152) 4 0.75 (19) NA 3.6 (92)
ASME B16.5 (ANSI) 150 3 (76) 0.88 (22) 6.0 (152) 7.5 (191) 4 0.75 (19) 2.58 (66) 5.0 (127)
4 (102) 0.88 (22) 7.5 (191) 9.0 (229) 8 0.75 (19) 3.5 (89) 6.2 (158)
2 (51) 0.82 (21) 5.0 (127) 6.5 (165) 8 0.75 (19) NA 3.6 (92)
ASME B16.5 (ANSI) 300 3 (76) 1.06 (27) 6.62 (168) 8.25 (210) 8 0.88 (22) 2.58 (66) 5.0 (127)
4 (102) 1.19 (30) 7.88 (200) 10.0 (254) 8 0.88 (22) 3.5 (89) 6.2 (158)
DIN 2501 PN 10–40 DN 50 20 mm 125 mm 165 mm 4 18 mm NA 4.0 (102)
DN 80 24 mm 160 mm 200 mm 8 18 mm 66 mm 5.4 (138)
DIN 2501 PN 25/40
DN 100 24 mm 190 mm 235 mm 8 22 mm 89 mm 6.2 (158)
Dimensions are in inches (millimeters).

Pipe Process Lower Housing G


Class(1) 1 1 H
Size Side F /4 NPT /2 NPT
2 (51) 2.12 (54) 0.97 (25) 1.31 (33) 5.65 (143)
ASME B16.5 (ANSI) 150 3 (76) 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)
4 (102) 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)
2 (51) 2.12 (54) 0.97 (25) 1.31 (33) 5.65 (143)
ASME B16.5 (ANSI) 300 3 (76) 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)
4 (102) 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)
DIN 2501 PN 10–40 DN 50 2.4 (61) 0.97 (25) 1.31 (33) 5.65 (143)
DN 80 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)
DIN 2501 PN 25/40
DN 100 3.6 (91) 0.97 (25) 1.31 (33) 5.65 (143)

(1) Tolerances are -0.020 and +0.040 (-0,51 and +1,02).

Options Custom Configuration(1)


If Option Code C1 is ordered, the customer may specify the
Standard Configuration following data in addition to the standard configuration
Unless otherwise specified, transmitter is shipped as follows: parameters.
• Output Information
ENGINEERING UNITS inH2O (Ranges 1, 2, and 3) • Transmitter Information
Differential/Gage psi (Ranges 4-5)
2051TA • LCD display Configuration
psi (all ranges)
• Hardware Selectable Information
• Signal Selection
4 mA (1 Vdc)(1): 0 (engineering units)
• Wireless Information
• Scaled Variable
20 mA (5 Vdc)(1): Upper range limit
• and more
Output: Linear
Refer to the “Rosemount 2051 Configuration Data Sheet”
Flange type: Specified model code option
document number 00806-0100-4101.
Flange material: Specified model code option
For Wireless refer to the “Rosemount 2051 Wireless
O-ring material: Specified model code option
Configuration Data Sheet” document number
Drain/vent: Specified model code option
00806-0100-4102.
LCD Display: Installed or none

Alarm(1): High
Software tag: (Blank)

(1) Not applicable to FOUNDATION fieldbus, PROFIBUS PA, or Wireless.


(1) Not applicable to FOUNDATION fieldbus or PROFIBUS PA protocols.

[Link] 81
Rosemount 2051 April 2013

Tagging (3 options available) Display and Interface Options


• Standard SST hardware tag is permanently affixed on transmitter. M4 Digital Display with Local Operator Interface (LOI)
Tag character height is 0.125 in. (3,18 mm), 84 characters • Available for 4-20 mA HART, 4-20 mA HART Low Power, and
maximum. PROFIBUS PA
• Tag may be wired to the transmitter nameplate upon request, 85 M5 Digital Display
characters maximum.
• 2-Line, 5-Digit LCD for 4-20 mA HART
Tag may be stored in transmitter memory. Character limit is
• 2-Line, 5-Digit LCD for 1-5 Vdc HART Low Power
dependent on protocol.
• 2-Line, 8-Digit LCD for FOUNDATION fieldbus and PROFIBUS PA
• HART Revision 5: 8 characters
• 3-Line, 7-Digit LCD for Wireless
• HART Revision 7 and Wireless: 32 characters
• Direct reading of digital data for higher accuracy
• FOUNDATION fieldbus: 32 characters
• Displays user-defined flow, level, volume, or pressure units
• Profibus PA: 32 characters
• Displays diagnostic messages for local troubleshooting
Commissioning tag(1) • 90-degree rotation capability for easy viewing
A temporary commissioning tag is attached to all transmitters.
Configuration buttons(1)
The tag indicates the device ID and allows an area for writing the
Rosemount 2051 Requires option D4 (Analog Zero and Span),
location.
DZ (Digital Trim), M4 (LOI) for local configuration buttons.
Optional Rosemount 304, 305, or 306 Integral
Transient protection
Manifolds
T1 Integral Transient Protection Terminal Block
Factory assembled to 2051C and 2051T transmitters. Refer to
Meets IEEE C62.41, Category Location B
Product Data Sheet (document number 00813-0100-4839 for
Rosemount 304 and 00813-0100-4733 for Rosemount 305 and 6 kV crest (0.5 s - 100 kHz)
306) for additional information. 3 kA crest (8 × 20 microseconds)
6 kV crest (1.2 × 50 microseconds)
Other seals
Refer to the Rosemount 1199 Seal Systems Product Data Sheet
Bolts for flanges and adapters
(document number 00813-0100-4016) for additional • Standard material is plated carbon steel per ASTM A449, Type 1
information. L4 Austenitic 316 Stainless Steel Bolts
L5 ASTM A 193, Grade B7M Bolts
Output information L6 Alloy K-500 Bolts
Output range points must be the same unit of measure. L8 ASTM A 193 Class 2, Grade B8M Bolts
Available units of measure include:
Conduit plug
Pressure DO 316 SST Conduit Plug
atm inH20@4 °C(1) g/cm2 psi • Single 316 SST conduit plug replaces carbon steel plug
mbar mmH2O kg/cm2 torr Rosemount 2051C Coplanar Flange and 2051T bracket
bar mmHg Pa cmH20@4 °C(1) option
inH20 mmH20@4 °C(1) kPa cmHG@0 °C(1) B4 Bracket for 2-in. Pipe or Panel Mounting
inHg ftH20 MPa (1)(2) ftH20@60 °F(1) • For use with the standard Coplanar flange configuration
hPa(1) inH20@60 °F(1) kg/SqM (1) mH20@4 °C(1) • Bracket for mounting of transmitter on 2-in. pipe or panel
mHg@0 °C(1) Psf(1) ftH2O@4C(1) • Stainless steel construction with stainless steel bolts
Flow(2)(3)
Rosemount 2051C traditional flange bracket options
bbl kg cm3 B1 Bracket for 2-in. Pipe Mounting
ft3 lb m3 • For use with the traditional flange option
gal L ton • Bracket for mounting on 2-in. pipe
Level(3) • Carbon steel construction with carbon
% ft cm steel bolts
• Coated with polyurethane paint
in mm
B2 Bracket for Panel Mounting
• For use with the traditional flange option
(1) Available with enhanced 2051 and Wireless.
• Bracket for mounting transmitter on wall
or panel
(2) Available on PROFIBUS PA.
• Carbon steel construction with carbon
steel bolts
(3) All flow units are available per second, minute, hour or day.
• Coated with polyurethane paint

(1) Only applicable to FOUNDATION fieldbus.

82 [Link]
April 2013 Rosemount 2051

B3 Flat Bracket for 2-in. Pipe Mounting


• For use with the traditional flange option
• Bracket for vertical mounting of transmitter on 2-in. pipe
• Carbon steel construction with carbon
steel bolts
• Coated with polyurethane paint
B7 B1 Bracket with SST Bolts
• Same bracket as the B1 option with Series 300 stainless steel bolts
B8 B2 Bracket with SST Bolts
• Same bracket as the B2 option with Series 300 stainless steel bolts
B9 B3 Bracket with SST Bolts
• Same bracket as the B3 option with Series 300 stainless steel bolts
BA Stainless Steel B1 Bracket with SST Bolts
• B1 bracket in stainless steel with Series 300 stainless steel bolts
BC Stainless Steel B3 Bracket with SST Bolts
• B3 bracket in stainless steel with Series 300 stainless steel bolts

[Link] 83
Rosemount 2051 Product Data Sheet
00813-0100-4101 Rev JA April 2013

Emerson Process Management Emerson Process Management


Rosemount Inc. Blegistrasse 23
8200 Market Boulevard P.O. Box 1046
Chanhassen, MN 55317 USA CH 6341 Baar
T (U.S.) 1-800-999-9307 Switzerland
T (International) (952) 906-8888 T +41 (0) 41 768 6111
F (952) 906-8889 F +41 (0) 41 768 6300
[Link] [Link]

Emerson Process Management Emerson Process Management


Asia Pacific Pte Ltd Latin America
1 Pandan Crescent 1300 Concord Terrace, Suite 400
Signapore 128461 Sunrise Florida 33323 USA
T +65 6777 8211 Tel + 1 954 846 5030
F +65 6777 0947
Service Support Hotline: +65 6770 8711
Email: Enquiries@[Link]
[Link]

Standard Terms and Conditions of Sale can be found at [Link]\terms_of_sale


The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
HART and WirelessHART are registered trademarks of the HART Communication Foundation
Modbus is a trademark of Modicon, Inc.
All other marks are the property of their respective owners.
© 2013 Rosemount Inc. All rights reserved.