ACU-802S Air Conditioning Unit Manual
ACU-802S Air Conditioning Unit Manual
ne
CHAPTER 1
rli
Ai
an
ic
er
General Information
Am
an
ic
er
Am
of
ty
er
op
Pr
Creation:05-04-2012 1-1-2
1. Description
1.A. Unit Description
(See Figure 1)
The ACU-802S Air Conditioning and Heating Units are self-contained truck or trailer mounted, diesel
engine driven units. The ACU-802S Air Conditioning and Heating Units are designed to provide
passenger comfort in all single, double, or triple connection cooled aircraft, in any climate or season.
Major assemblies of the ACU-802S Air Conditioning and Heating Units are: a heavy-duty four cycle
diesel industrial engine with power take off; a fully regulated 115 ton capacity rotary screw compressor;
s
condenser coil; twin condensing fans; ASME receiver tank; evaporator coil; and centrifugal blower.
ne
Model number 802S-CUP, 802S-H-CUP each designates a trailer mounted unit with a 17,000 lb. (7,711
kg.) capacity fifth wheel trailer assembly. The rear axle is equipped with dual wheels and drum type
rli
brakes actuated by an Orscheln type lever mounted at the front of the unit adjacent to the tow bar.
Ai
Model number 802S-CUS, 802S-H-CUS each designates a truck mounted module. The module is
designed to be mounted on any suitable truck chassis. Refer to Chapter 2, Section 3, for module
installation instructions.
an
The operator’s station is located on the right side of the unit forward of the engine compartment. All
normal operating controls and monitoring equipment are installed on the instrument panel. The panel is
ic
illuminated to permit nighttime operation. An integral safety control circuit is provided to protect the
engine and refrigeration system from potentially damaging conditions. Monitored functions include the
er
following:
Am
• Engine Faults
• Low coolant level
• Low oil pressure
• High coolant temperature
Low fuel level option
of
•
• Refrigeration System Faults
• High/low compressor pressures
ty
This chapter contains operating instructions for the ACU-802S Air Conditioning Unit. The information
presented herein provides a physical and functional description of the unit and its components provides
operating procedures, unit specifications, dimensions, and shipping and storage instructions.
op
Maintenance, overhaul, and parts information are contained in Chapter 2, 3, and 4. Manufacturer’s
data covering component assemblies are contained in Chapter 5. For the purpose of unit identification,
Pr
a nameplate stamped with the unit model, serial number, and unit weight is installed in on the unit near
the instrument panel.
5 6
of
ty
er
Creation:05-04-2012 1-1-4
5
s
ne
rli
Ai
an
ic 4
er
Am
3
of
2 1
ty
er
s
1.C. Major Component Description
ne
For purposes of discussion and component location, unit orientation is properly established as follows:
the tow bar or truck cab shall be considered to be at the front end of the unit. Right and left are
rli
determined by (facing the rear of the unit) facing the condenser coil. The instrument panel is located on
the right side of the unit. Left is opposite the instrument panel.
Ai
1.C.i. R-134a Refrigeration System
an
The refrigeration system comprises the following components: a rotary screw compressor; an oil
separator tank; an oil filter assembly; a reversing valve; an outside coil assembly; a liquid
refrigerant receiver tank; a filter/drier assembly; expansion valve; main thermal expansion
ic
solenoid valve; the inside coil assembly; an optional defrost system; compressor load and unload
er
solenoid valve; compressor liquid injection temperature pilot valve; compressor vapor injection
thermal expansion valve; vapor injection filter; compressor suction strainer; vibration eliminators;
relief valves; check valves; shut-off valves; refrigerant condition sight glass; service access ports;
Am
service connection angle valves; and control pressure switches. Each of the above components
is discussed in detail in the following paragraphs. System operation is explained below.
.
1.C.i.a. RefrigerationCycle
of
Refrigeration is the transfer of heat from a place where it is not wanted to a place where it
is unnoticeable. Heat is a form of energy. It is not a solid, liquid or gas, and therefore is
ty
temperature, solidifies, or condenses it. Refrigeration effect depends upon changing the
state of a refrigerant from a liquid to a gas and back to a liquid.
op
For any particular weight of liquid refrigerant at saturation conditions, a specific amount of
heat is required to change that liquid into the gaseous state at the same conditions.
Though no temperature or pressure change occurred, heat was absorbed by the
refrigerant. This heat is called the latent heat. Obviously, to change gaseous refrigerant
at saturation conditions to a liquid at the same saturation conditions, the latent heat must
be rejected.
Creation:05-04-2012 1-1-6
°F PSIG °F PSIG °F PSIG °F PSIG
-40 *14.77 -2 5.3 30 25.6 90 104.2
-35 *12.4 0 6.3 32 27.3 95 113.9
-30 *9.8 2 7.2 34 29.1 100 124.3
-28 *8.7 4 8.3 36 30.8 105 135.2
-26 *7.6 6 9.4 38 32.6 110 146.8
-24 *6.4 8 10.5 40 34.5 115 159.0
-22 *5.1 10 11.6 45 39.5 120 171.9
s
-20 *3.8 12 12.8 50 44.9 125 185.5
ne
-18 *2.4 14 14.0 55 50.7 130 199.8
-16 *1.0 16 15.3 60 56.9 135 218.8
rli
-14 0.2 18 16.7 65 63.6 140 230.5
Ai
-12 1.0 20 18.0 70 70.7 145 247.0
-10 1.8 22 19.4 75 78.3 150 264.4
an
-8 2.6 24 20.9 80 86.4 155 282.5
-6 3.5 26 22.4 ic 85 95.0 160 301.5
-4 4.4 28 24.0
er
*Vacuum in. HG based on atmospheric pressure of 14.696 PSIA
NOTE: Use the following formula to convert to degrees centigrade: (°F - 32) X 5/9
Am
A basic refrigeration system is a closed loop. One half of the loop is at a high pressure,
the other half is at a low pressure. The high pressure half is divided from the low pressure
half by the compressor and the expansion valve (see figure 2 (1 of 2)). Two heat
ty
exchangers complete the system. The heat exchanger on the high pressure side of the
system is the condenser. The heat exchanger on the low pressure side of the system is
er
the evaporator.
Liquid refrigerant absorbs heat and changes into a gas in the evaporator. Because the
op
compressor’s pumping maintains the evaporator at a low pressure, and the evaporating
process is at saturation conditions, the evaporator temperature is at a correspondingly low
temperature.
Pr
The compressor compresses the gas returning from the evaporator into a high pressure
gas and delivers it to the condenser. The high pressure gas rejects its heat and changes
into a liquid. This condensing process is at saturation conditions and takes place at a high
temperature corresponding to the high pressure. Liquid leaving the condenser is at a high
pressure. Upon passing through the expansion valve, the pressure drops to the
evaporator pressure.
s
ne
EXPANSION
VALVE
3
rli
Ai
an
ic
HEAT MOVES HEAT MOVES
INSIDE
er
FROM SUPPLY OUTSIDE COIL FROM
COIL
AIR TO 2 REFRIGERANT
REFRIGERANT 4 TO OUTSIDE AIR
Am
of
ty
COMPRESSOR
er
1
op
Pr
Creation:05-04-2012 1-1-8
1.C.i.a.1. Cooling Cycle – air conditioning and heating units
The refrigerant gas leaves the compressor (C2), through the oil separator (C14),
reversing valve (heating option only) (V1), outside coil (C5), check valve (heating
option only) (V25), valve (V42), and into receiver (C3), from receiver (C3) to shutoff
valve (V17), filter drier (F3), sight glass (G11), expansion valve (V6), check valve
(V39), distributor, inside coil (C4), check valve (V35), and back to compressor (C2).
For cooling, the inside coil (C4) is the evaporator. The mostly liquid refrigerant is fed
through a distributor into the lower rows of tubes. The refrigerant gas leaves the coil
through the top manifold and returns to the compressor (C2).
s
Heat from the supply air is absorbed in the inside coil (C4) as the liquid refrigerant
ne
evaporates at a low temperature. The compressor (C2) pumps the gaseous
refrigerant to the outside coil (C5).
rli
Refrigerant gas, from the compressor (C2), flows into the top refrigerant manifold of
the outside coil (C5). Heat from the gaseous refrigerant is rejected to the ambient
Ai
as the refrigerant condenses to a liquid at a high temperature. Liquid refrigerant
from the outside coil (C5) flows to the receiver (C3).
an
ic
er
Am
of
ty
er
op
Pr
REVERSING
VALVE V1
s
DISTRIBUTOR (OPTIONAL)
ne
rli
V35
Ai
OUTSIDE
COIL
DIESEL C5
COMPRESSOR
ENGINE
an
C2
C1
C14
OIL
SEPARATOR
ic FANS
V39 SOLENOID
er
VALVE L4 V17 V42
G11 F3
V22 V25
RECEIVER
Am
EXPANSION FILTER C3
VALVE V6 DRIER
COOLING MODE
FIGURE 2 (2 OF 2)
ty
er
op
Pr
Creation:05-04-2012 1-1-10
1.C.i.a.2. Heating Cycle (Optional) – Air Conditioning and Heating Units (See Figure 3)
The refrigerant gas leaves the compressor (C2), through the oil separator, reversing
valve (V1), inside coil (C4), check valve (V38), valve (V42), and into receiver (C3),
from receiver (C3) to shutoff valve (V17), filter drier (F3), sight glass (G11),
expansion valve (V6), check valve (V40), outside coil (C5), check valve (V35), and
compressor (C2).
For heating, the outside coil (C5) is the evaporator. The liquid refrigerant is fed into
the lower manifold. The refrigerant gas leaves the coil through the top manifold and
returns to the compressor (C2).
Heat from the ambient air is absorbed in the outside coil (C5) as the liquid
refrigerant evaporates at a low temperature. The compressor (C2) pumps the
gaseous refrigerant to the inside coil (C4).
s
Refrigerant gas, from the compressor (C2), flows into the top refrigerant manifold of
ne
the inside coil (C4). Heat from the gaseous refrigerant is rejected to the supply air
as the refrigerant condenses to a liquid at a high temperature. Liquid refrigerant
from the inside coil (C4) flows to the receiver.
rli
Ai
an
ic
er
Am
of
ty
er
op
Pr
EXPANSION
VALVE
3
s
ne
rli
Ai
HEAT MOVES HEAT MOVES
FROM OUTSIDE
OUTSIDE COIL INSIDE COIL FROM
an
AIR TO 2 REFRIGERANT TO
4
REFRIGERANT SUPPLY AIR
ic
er
Am
COMPRESSOR
1
of
ty
er
op
Pr
Creation:05-04-2012 1-1-12
INSIDE COIL
C4
s
REVERSING
VALVE V1
ne
DISTRIBUTOR
(OPTIONAL)
V38 V40
rli
V35
Ai
OUTSIDE
COIL
an
DIESEL C5
COMPRESSOR
ENGINE
C2
C1
C14
OIL
ic
SEPARATOR FANS
er
V39 SOLENOID
VALVE L4 V17 V42
Am
G11 F3
V22 V25
RECEIVER
EXPANSION FILTER C3
VALVE V6 DRIER
of
FIGURE 3 (2 OF 2)
er
op
Pr
The compressor (C2) is directly driven by the engine power take off shaft through a disc
coupling. The power take off is of the clutchless type, the compressor therefore operates
whenever the engine is turning.
The compressor is of the positive displacement rotary screw type with a fixed volume
ratio. The volume ratio is selected to provide optimum efficiency for this application
without over compressing the refrigerant. The compressor is a flooded unit, which means
that oil is injected into the inlet gas to make a seal between rotors. The flooded screw
compressor is dependable, efficient, and not harmed by some liquid slugging.
The compressor has a hydraulically actuated slide valve for step-less capacity control.
s
The compressor can be unloaded to 25% of full load capacity.
ne
1.C.i.b.1. Capacity Control (See Figures 5-1 & 5-2)
rli
Regulating compressor capacity is required to maintain the desired supply air
temperature in varying ambient weather conditions. During hot and humid days,
Ai
more heat must be removed from the ambient air than in dry cool conditions. The
capacity control system regulates compressor output in response to changing
requirements.
an
Load regulation controls the amount of refrigerant compressed per compressor
revolution. A hydraulically actuated slide valve controls the volume of refrigerant
ic
vapor delivered to the rotors. Slide valve position is controlled by a loading and
unloading 2-coil direct acting solenoid valve (L1 and L2) controlling compressor oil
er
flow to the slide valve cylinder. The coils are energized or de-energized by the
onboard programmable logic controller (PLC) (E1) in response to inside coil
Am
In probe-less cooling mode, the PLC defaults to maintain an inside coil pressure of
28 psig. If the operator commands the unit for warmer air, the PLC will increase the
inside coil pressure as needed by unloading the compressor partially allowing the
of
In probe-less heating mode (optional), the PLC defaults to an inside coil pressure of
ty
215 psig to deliver very warm air to the aircraft. If the operator commands the unit
for cooler air, the PLC will decrease the inside coil pressure as needed by unloading
er
In probe mode, the PLC varies the inside coil pressure as needed to maintain cabin
comfort automatically.
Pr
The PLC (E1) sends power to load and unload solenoid, energizing the load coil
(L1). Oil then flows from the solenoid valve through needle valve (V9) to
compressor port “2” where it enters the load side of the slide valve piston. This
equalizes the force on the slide valve piston and discharge pressure on the slide
valve area loads the compressor.
Creation:05-04-2012 1-1-14
1.C.i.b.3. Compressor Unloading
The PLC (E1) sends power to load and unload solenoid, energizing the load coil
(L2). This allows oil to flow from the compressor port “2” through the needle valve
(V9) to the solenoid valve. This allows discharge pressure on the slide valve piston
to unload the slide valve as the piston moves outward.
(L1/L2)
LOAD/UNLOAD
SOLENOID
V9
L1/L2
NEEDLE
s
VALVE
ne
rli
Ai
ENERGIZE COIL “b” (L1) TO LOAD
ENERGIZE COIL “a” (L2) TO UNLOAD
an
1.C.i.b.4. Compressor Hold ic
When the refrigeration system stabilizes at a constant inside coil pressure, the
compressor unload piston is held in a stationary position. In hold position, both “a”
er
(L2) and “b” (L1) coils are de-energized. This blocks oil flow to and from the load
and unload solenoid. With the slide valve stationary, the compressor rate is
Am
constant.
direct acting solenoid valves. This is an integral part of the compressor. The
manifold is ported to load or unload the compressor on demand.
ty
The compressor is supplied with a 5” check valve on the inlet, the valve is spring
loaded and prevents backflow from the compressor into the suction line. The pin
op
holding the flapper is in the vertical position to ensure the weight of the flapper does
not keep the valve open.
Pr
s
ne
2
rli
3
Ai
6
an
4
ic
er
7
Am
8
of
Creation:05-04-2012 1-1-16
COMPRESSOR
C
B A
A. MALE ROTOR
B. FEMALE ROTOR
s
C. CYLINDER
ne
rli
Ai
CAPACITY CONTROL SLIDE VALVE
an
ic
er
Am
of
ty
er
op
CAPACITY CONTROL
FIGURE 5
(1 OF 2)
SLIDE VALVE
CAPACITY CONTROL
ty
FIGURE 5
(2 OF 2)
er
op
Pr
Creation:05-04-2012 1-1-18
1.C.i.c. Oil Separator (C14) (See Figure 6)
The oil separator removes oil from the refrigerant vapor discharged from the compressor
through centrifugal force. The separator serves as a reservoir for compressor lubricating
oil collected during the separation process. The oil functions to lubricate the moving parts
of the compressor and to seal the rotors. The rotors are precisely machined, but require
an oil film to seal the small clearances that must exist between the lobes of the male rotor
and female rotor flutes to permit rotation. Oil is swept along with high velocity refrigerant
vapor forced from the compressor discharge outlet. The refrigerant transports the
suspended oil to the separator tank where it is removed centrifugally.
Hot, high pressure refrigerant vapor enters the separator through a port located on the
s
side of the vessel. The compressor discharge outlet is connected to the inlet through
ne
sweat soldered copper pipe, a flexible vibration eliminator, and inlet coupling. The oil
laden vapor is fed into the vessel through a curved deflector that diverts the flow of
refrigerant toward the cylinder shell, starting the centrifugal motion. Entering refrigerant is
rli
fed through a mesh basket that acts as a sieve, collecting the heavier, more viscous oil
particles without impeding the flow of refrigerant vapor. The oil separated by the basket
Ai
falls as droplets through the mesh to the bottom of the vessel. The impact of high velocity,
oil bearing refrigerant against the cylinder shell causes the oil to separate and trickle down
the sides of the shell to the sump where it pools and is collected. A mesh screen in the
an
sump damps oil velocity, calming the oil supply. A suction line pick up tube extends into
the reservoir sump from the outlet coupling. The dip tube permits only refrigerant-free,
non-turbulent oil to be supplied to the compressor oil inlet. The swirling refrigerant gas
ic
rises and exits the columnar vessel through the dome outlet coupling. A mesh screen
surrounding the outlet coupling disperses any remaining oil carried by the high velocity
er
gas. Sight glass indicators are positioned on the vessel to indicate minimum and high oil
levels. A manual shut-off valve is installed at the oil outlet. An angle access valve and
Am
relief valve are installed in couplings located on the vessel domed cap. The relief valve
relieves vessel pressure at 375 psig. An additional angle access valve is installed on the
lower side of the vessel sump cap.
The separator tank is a cylindrical, columnar pressure vessel of welded construction with a
of
domed cap and sump; a 3 in. inlet with deflector and strainer basket; a 3 in. vertical
screened outlet; 1-1/4 in., NPT oil outlet with dip tube; oil shut-off valve; 1-1/4 in., NPT oil
level sight glasses; ¾ in., NPT drain connection; and ½ in., NPT safety valve and service
ty
port connections. The tank is a 12-3/4 in. diameter pressure vessel 32 inches long. Tank
weight is 220 lbs. Maximum operating pressure is 400 psi. The tank, welded in
er
accordance with AWS specification A2.4 and A3.0, meets the requirements of the ASME
Boiler and Pressure Vessel Code Section VIII, and is National Board certified.
op
Pr
1
3
15
s
ne
14
4
rli
13
Ai
12 5
an
11
ic
10 6
er
Am
7
of
ty
er
Creation:05-04-2012 1-1-20
1.C.i.d. Refrigerant Oil
The compressor is lubricated with synthetic ester based lubricating oil, Solest 68. The oil
is fully miscible with and soluble in refrigerant R-134a. The oil lubricates the moving parts
of the compressor, seals the revolving parts during operation, and operates the
compressor load/unload slide valve. Use only Solest 68 compressor oil from CPI
engineering services. This ester based oil is not a health or safety hazard under
conditions of normal use and contains no known carcinogens. No special identification or
warning labels are required. The oil flash point is 511°F (266°C), and the specific gravity
is 0.835. The oil is insoluble in water and should be extinguished with CO2 foam or a dry
chemical type of fire extinguisher in the event of fire. Direct exposure should be limited
and normal precautions relating to handling and storage should be taken. Solest 68
s
refrigerant oil reacts unfavorably with strong oxidants, producing carbon monoxide as a
ne
decomposition product. No hazardous polymerization occurs on decomposition. The oil is
non-toxic under conditions of ordinary use with adequate ventilation.
rli
1.C.i.e. R-134a Refrigerant
Ai
The characteristics of R-134a refrigerant medium allow it to absorb large quantities of heat
from the heat load and dissipate the heat gain to the atmosphere. The boiling point of R-
134a refrigerant is -15°F (-26°C) at atmospheric pressure. The saturation temperature
an
and pressure range of this refrigerant make it a good heat exchange medium for use in
ground support air conditioning. The stability and predictability of R-134a, a
hydrofluorocarbon (HFC), in addition to its thermodynamic and physical properties, make it
ic
a suitable refrigerant for high, medium, and low temperature applications.
Hydrofluorocarbon (HFC) refrigerant compounds do not pose any threat to the
er
atmospheric ozone.
Am
While toxicity of R-134a refrigerant during normal conditions of use is low at acceptable
exposure limits (1,000 ppm) over an 8 to 12 hour period, thermal decomposition resulting
from exposure of the refrigerant to a source of combustion may produce hydrogen
fluoride, hydrochloric, and hydrofluoric acids. These toxic and irritating compounds are
noxious and produce pungent odors. An acceptable exposure limit (AEL) is an airborne
of
134a vapor may cause central nervous system depression, and may result in dizziness or
loss of coordination. Continued exposure to high concentrations may result in an irregular
er
WARNING:
Pr
WARNING:
BLINDNESS MAY RESULT FROM LIQUID REFRIGERANT
CONTACTING THE EYES. FROST BITE MAY RESULT FROM
CONTACT WITH THE SKIN. IN ALL CASES OF EXPOSURE TO
LIQUID REFRIGERANT OR HIGH CONCENTRATIONS OF
s
VAPOR, SEEK IMMEDIATE MEDICAL AID.
ne
At room temperature and pressure, physical contact with normal concentrations of R-134a
rli
vapors is not hazardous. In liquid form, however, R-134a refrigerant can freeze skin and
eye tissue on contact. If skin exposure occurs, the exposed area should be soaked in
Ai
lukewarm water until thawed, and then the application of a non-medicated ointment such
as white petroleum jelly should be done. Seek medical treatment if skin remains grey in
color. In case of eye contact, flush the eyes with water for 15 minutes; then apply a light
an
bandage, and seek medical treatment.
ic
WARNING:
er
NEVER HANDLE REFRIGERANT CONTAINERS WITH BARE
Am
OCCURS.
er
air and R-134a may form when liquid R-134a refrigerant is pumped into a closed vessel if
the initial air pressure is greater than one atmosphere and the final pressure is over 300
psig.
Creation:05-04-2012 1-1-22
WARNING:
NEVER LEAK TEST WITH A PRESSURIZED MIXTURE OF R-
134a REFRIGERANT AND AIR. R-134a REFRIGERANT MAY BE
SAFELY PRESSURIZED WITH DRY NITROGEN. NEVER WELD
OR STEAM CLEAN ON OR NEAR AN AIR CONDITIONING
SYSTEM. NEVER EXPOSE REFRIGERANT CONTAINERS TO
o
EXCESSIVE HEAT (OVER 120°F) (49 C). ALWAYS COVER
CONNECTIONS WITH A CLOTH TO PREVENT REFRIGERANT
FROM SPRAYING ONTO THE SKIN OR INTO THE EYES.
s
ne
Observe all of the safety precautions recommended by the product manufacturer for
handling and transporting R-134a refrigerant. See Chapter 5 of this manual for further
rli
information.
Ai
Leak detection may be accomplished using various non-selective, halogen-selective, and
compound-selective instruments or with fluorescent dye. Instruments that are sensitive to
CFCs and HCFCs may have low sensitivity to or not read HFC refrigerant levels due to the
an
difference in ionization of these compounds. The compatibility of dye with R-134a
refrigerant should be tested before use. The requirements of pin-point leak detectors are
markedly different from those of area monitors. Selectivity is far more important to area
ic
monitors that must differentiate R-134a from other compounds that may be present in the
air.
er
1.C.i.f. Compressor Lubrication Oil Line Filter (F7) (See Figure 7)
Am
A single element, full flow internal cartridge type filter is installed in the lubricating oil line at
the compressor oil injection port. The filter has a 25 micron rating and will have a 6 psi
drop at 20 gpm flow, based on ISO SSU oil. The filter has pop-up alarm, which indicates
a 25 psig restriction. Once activated there is continuous indication of a bypass or clogged
of
condition even following equipment shutdown. The signal will not change until it is
manually reset. There is a bypass valve inside the filter that will start bypass at 30 psi. If
the pressure drop limitation of the bypass valve is exceeded unfiltered lubricating oil will be
ty
A four-way, two position reversing valve in placed in the refrigeration system in such a way
to swap the outside and inside coil functions. The reversing valve is made of steel. Each
spool is a hone fit with its own body; therefore spools are not interchangeable with
Pr
different bodies.
With the valve in the de-energized position high pressure gas is being directed to end “A”
of the valve through the slave pilot and remote pilot. If the remote pilot valve is then
energized, end “B” of the main valve will open to suction and move the slave pilot piston to
its opposite seat, thereby pressurizing “A”. Additional high pressure gas will flow into that
end and will accelerate the shift of the spool toward end “B”.
The valve pilot solenoid valve is energized during the cooling mode and de-energized in
the heating mode.
Creation: 05-04-2012 1-1-23
1, 2
s
ne
rli
Ai
OUT
an
7
ic
er
Am
6
3
of
5 .....Steel bowl
6 .....Cartridge, filter
op
Creation:05-04-2012 1-1-24
s
ne
rli
(a) (b)
Ai
INSIDE COIL
an
COMPRESSOR
DISCHARGE
ic
er
Am
of
ty
er
op
COMPRESSOR
SUCTION
Pr
OUTSIDE COIL
The outside coil is an air-cooled type heat exchanger, constructed of copper tubes and
aluminum fins. The tubes are staggered to obtain maximum heat transfer and are
enclosed in a galvanized steel casing. On engine drive units, seven rows of the coil are
used for refrigerant and one row is used for engine coolant heat exchanging. The rows
used for refrigerant are inner fin construction (tube within a tube with fins between the
inside and outside tubes) that provide approximately 50% better heat transfer over plain
tubes.
s
ne
rli
Ai
an
ic
er
Am
of
ty
1
er
op
Creation:05-04-2012 1-1-26
1.C.i.i. Inside Coil (C4) (See Figure 10)
The inside coil is an air cooled type of heat exchanger constructed of staggered rows of
copper tubes and aluminum fins. The aluminum fins on the tubing increase the heat
transfer efficiency. The evaporator is a direct expansion type of coil in which refrigerant is
fed directly into the cooling coil through the expansion valve. The various circuits through
the coil are fed through distributors to equalize the flow of refrigerant to each circuit in
order to maintain high evaporator efficiency. The coil is mounted inside a partitioned
metal enclosure connected to the blower housing and to the air outlets. The blower
provides the mass air flow to accomplish the heat transfer function. The evaporator is that
part of the low pressure side of the refrigeration system in which the refrigerant
evaporates, absorbing heat as it changes to a vapor. The evaporator performs the
s
primary function of the refrigeration system, the cooling of the supply air. Heat is
ne
absorbed by the cool, low pressure refrigerant from the ambient air forced through the coil
by the blower fan.
rli
INSIDE COIL (C4)
Ai
TOP DIFFUSER BOTTOM
DIFFUSER
an
INSIDE COIL
ENCLOSURE
ic
er
Am
of
ty
er
AIR FROM
op
BLOWER
Pr
AIR OUTLET
HOSE 1
The main thermal expansion valve regulates the rate of refrigerant flow to the main
evaporator coil to maintain a set superheat. Superheat is the temperature
difference between the actual temperature and the saturated temperature at the
evaporator outlet. The minimum superheat is 6°F (3.3°C ). Lower superheat
setting may result in liquid carry over to the compressor. The liquid, upon coming in
contact with the warm coil, will flash into gas. The superheat adjustment is located
externally on the valve body. Two complete turns will raise or lower the actuating
superheat approximately 1 °F (0.6 °C ) (superheat range 6 °F -15 °F ) (3.3 °C - 8
°C ). Turning the stem right (clockwise) decreases flow, and raises superheat.
s
Turning the stem left (counterclockwise) increases flow and lowers superheat.
ne
The assembly is designed to operate in all ambient temperatures where the unit
normally operates. The assembly is charged with a selective charge, see vendor’s
rli
literature.
This assembly employs an external equalizer, which compensates for pressure drop
Ai
through the evaporator, allowing the TXV to maintain a correct superheat no matter
the load.
an
1.C.i.j.2. Vapor Injection Thermal Expansion Valve (V7)
This expansion valve regulates the flow of refrigerant to the vapor injection coil. The
ic
vapor injection coil consists of three independent rows in the evaporator.
er
Vapor injection provides more cooling capacity from the compressor. Vapor at a
higher pressure than suction is injected into the transition stage of the rotor
Am
operation. This “supercharges” the compressor and provides the unit with more
cooling capacity.
In the refrigeration system after liquid refrigerant has passed trough the filter drier, a
portion of it is pulled off for vapor injection through expansion valve (V7). The
of
Creation:05-04-2012 1-1-28
1
s
ne
rli
Ai
INLET
3
an
4
ic
er
Am
2
of
OUTLET
ty
er
1..... Diaphragm
2..... Superheat spring
op
A normally closed solenoid valve (V24) is installed in the liquid line between receiver and
the liquid injection port on the compressor. The valve is controlled by its coil (L7) which is
energized by the PLC (E1) to maintain a discharge temperature, and consequentially, oil
temperature, around 190 °F when the compressor is under heavy load.
A storage reservoir is provided in the refrigeration system to collect the refrigerant charge
during periods of inactivity or during service procedures, and to provide an adequate
supply of refrigerant to the evaporator to meet the varying demands of the heat load. The
s
receiver is sized based on the operating charge required for all system components,
ne
including the liquid lines. Liquid refrigerant capacity is 24 gallons. The receiver tank is a
horizontal vessel constructed of high strength steel with a maximum working pressure of
400 psig at 450°F (232oC). The vessel is designed and manufactured in accordance with
rli
Section VIII of ASME Code and is National Board certified. The vessel is equipped with a
liquid level float gauge; inlet and outlet connections with rotolock shut-off valves; access
Ai
valve; and safety pressure relief valve. The outlet incorporates a dip tube that permits
suction of only liquid refrigerant from the tank. The shut-off valves installed on the tank
are horizontal style valves with 1-3/8 in. I.D. sweat soldered connections and 1-3/4-12
an
UNF coupling connection. The valve is provided with a Teflon and organic fiber seal; a
side gauge port; and reinforced zinc plated steel stem cap.
ic
[Link] Filtration
er
1.C.i.m.1. General
Am
flow and separate suspended or emulsified water from the refrigerant charge.
Refrigerant is a hygroscopic medium that readily absorbs water. Water reacts
chemically with R-134a refrigerant, a halogenated hydrocarbon, to form hydrochloric
ty
process is not interrupted, they produce pin-hole leaks that reduce system effectivity
and degrade the cooling capacity of the unit.
Pr
All water vapor is extracted from refrigerant during manufacture. System moisture
results from leaks, condensation, defective seals, or improperly made connections.
The oxidation process resulting from water contamination produces compounds that
reduce the heat transfer capability of the refrigerant medium. The unit is equipped
with a liquid line filter/drier assembly, a suction line filter, and a vapor injection
suction line filter.
The dehydrator contains a desiccant material that absorbs and entrains moisture
assimilated by the refrigerant medium. Insolubles are mechanically retained by the
filter element strainer, a pleated 100 mesh monel cloth material fitted to a perforated
Creation:05-04-2012 1-1-30
metal core. The dehydrator element does not provide bulk filtration of the entire
volume of refrigerant on each pass through the circuit. Approximately 10 percent of
the refrigerant medium passes through the activated medium each pass through the
circuit. This level of filtration provides effective moisture removal and does not
restrict refrigerant flow, avoiding a large pressure drop through the filter.
The filter/drier is responsible for protecting the main thermal expansion valve from
solids that could block or restrict its small orifice and from ice formation. Either
condition could stop or hinder the refrigeration process and result in a compressor
fault condition. The filter also removes oleoresins (sludge and varnish) resulting
from compressor oil decomposition. Organic acid results from oil decomposition.
Trace amounts of compressor oil not removed in the oil separator are transported
throughout the system. Excessive heat or air in the system may result in the
s
formation of oil contaminants. Catalytic metals such as iron and copper contribute
ne
to the decomposition process. Access valves are provided at each filter for the
purpose of monitoring pressure drop across the filter.
rli
1.C.i.m.2. Filter/drier Assembly (F3) (See Figure 13)
Ai
The filter/dehydrator assembly installed in the liquid line comprises a steel shell
fitted with 1 5/8 in. ODS sweat soldered connections; an aluminum cover plate with
gasket; a strainer; a mesh filter element; strainer end cap; desiccant cartridge; and
an
cover plate fasteners. The filter is a compound unit consisting of a dehydrator and a
filter assembly. The shell has a working pressure rating of 500 psig. Nominal
capacity is 40 tons. The cover plate gasket is a neoprene material with organic
ic
fiber. The mesh filter is an epoxy resin bonded assembly incorporating a perforated
metal center core; metal end caps; 1.0 in., NPT male end fitting; and pleated 100
er
mesh monel filter medium backed with 16 mesh tinned steel wire cloth. Filter rated
capacity is 10 gpm. Pressure drop across the filter is approximately 0.3 psi (2 kPa).
Am
The filter operates at temperatures from 60°F to 250°F (15 °C to 121 °C ). The
filter may be cleaned and reused. The desiccant cartridge comprises a monel
basket filled with activated desiccant media, and then sealed. The basket is
fabricated from 30 mesh monel screen. The desiccant is ¼ in. mesh size Grade F-1
granular activated alumina with a minimum surface area of 210 sq. in. m/gram. The
of
primary element (92 percent) of the desiccant compound is aluminum oxide with a
16 percent minimum water absorption capacity. Specific gravity of the material is
3.0 - 3.7 gm/cm3. The alumina is oven heated to between 375 °F (190 °C ) and
ty
425°F (218 °C ) for a minimum of 8 hours and immediately sealed in an air tight
container until ready for use. Moisture collected by the desiccant is not absorbed, or
er
taken into the material’s inner molecular structure. It is absorbed, building up on the
surface of the desiccant. The irregular surface area of the desiccant increases its
op
In contrast to the liquid line filter/drier which protects the system control devices, the
suction line filters protect the compressor from ingestion of contaminants. A filter is
installed in the vapor injection circuit to clean refrigerant delivered to the
compressor. The filter shells are of one-piece, all-brass construction with brass cap,
and corrosion resistant bronze fasteners. A ¼-inch 45 degree SAE flare access
valve is installed in the cap to permit reading pressure drop across the filter. The
vapor injection line filter is equipped with 1-5/8 in. ODS connections and a type “F”
Creation: 05-04-2012 1-1-31
115 sq. in. replaceable pleated media filter element. Maximum capacity is 15.8 tons
at 40°F (4oC) evaporator temperature.
s
ne
7
rli
6
Ai
5
an
12
3 ic
2
er
1
Am
of
ty
8
er
9
op
11 10
Pr
Creation:05-04-2012 1-1-32
s
ne
rli
Ai
8
9
an
7
ic
er
6
Am
3 4
of
1
2
ty
er
op
A sight glass assembly incorporating a moisture indicator is installed in the high pressure
liquid line following the filter/dehydrator assembly. The sight glass incorporates a litmus
paper element that provides a visual indication of filter condition. Whenever the color-
coded sight glass moisture element indicates a high level of water contamination (red or
orange color), the dehydrator cartridge is probably saturated and should be promptly
replaced to ensure satisfactory system operation. Primarily, the sight glass allows the
operator/technician to observe the flow of refrigerant through the circuit. Bubbles or
foaming indicate insufficient refrigerant charge, or, possibly, a restriction in the liquid line
that is adversely affecting system operation. Flash gas observed in the liquid line
indicates inadequate subcooling of the refrigerant.
s
ne
rli
Ai
an
ic
er
Am
CAUTION
of
ty
er
op
DRY WET
Pr
Creation:05-04-2012 1-1-34
1.C.i.o. Solenoid Valve Main Expansion Valve (L4) (See Flow Diagram)
The expansion valve balance line is connected to a solenoid valve (L4), that is controlled
by the PLC (E1) that acts as both a liquid line shut-off valve and an expansion valve
controller. The expansion valve solenoid (L4) provides external balances to suction
pressure when energized. When de-energized it provides discharge pressure to the
power assembly to shut off the expansion valve and stop refrigerant flow to the evaporator
coil. The expansion valve shut-off solenoid valve (L4) is energized during normal
operation.
s
Flexible metallic tube assemblies are installed in the refrigerant circuit to dampen noise
ne
and vibration resulting from engine; power take off, and compressor operation.
Eliminators are installed in the compressor suction line, discharge line, and vapor injection
suction line. The vibration eliminator consists of a deep pitched corrugated stainless steel
rli
tube covered with high tensile stainless steel wire braid. The vibration eliminators are
installed through sweat-soldered connections to refrigeration system piping. Ferrule joints
Ai
are brazed with high temperature alloys to prevent separation during installation.
an
The refrigerant circuit is equipped with general purpose service valves to permit
connection of instrumentation to test points throughout the system. The angle valves
ic
incorporate a shut off feature that isolates the gauge port from the system to prevent
refrigerant loss or entry of contaminants and air during gauge connection.
er
1.C.i.q.1. Packed Angle Valves (V4, V23, V31, V32) (See Figure 16)
Am
Service valves installed in the high and low pressure side of the system are
equipped with a 3/8 in., NPTM bottom inlet; 3/8 in., flare outlet connection; packed
angle valve with forged brass body and manual stem; seal cap; and nylon gasket.
of
ty
er
op
Pr
PACKED ANGLE VALVE (V4, V23, V31, V32) (See Flow Diagram)
(Shown in the Open Position)
FIGURE 16
Creation:05-04-2012 1-1-36
1.C.i.q.2. Self-Sealing Access Valves (See Figure 16A)
The schraeder type access valve, of similar design to the type of valve used to fill
pneumatic tires, provides a means for conveniently checking system pressures
without disturbing system operation. An adapter fitting is required to permit gauge
connections to this type of service access valve. The access valve is equipped with
a 1/8 in. or ¼ in., NPTM base and ¼ in., 45 degree flare tube connection, self-
sealing valve core; brass body; and half union. The valve conforms to the
requirements of ARI specification 720-76.
s
ne
rli
Ai
an
ic
er
1..... Pin
2..... Valve
Am
2
of
1
ty
er
op
Pr
ACCESS VALVE
FIGURE 16A
CAUTION:
ALWAYS BACKSEAT THE VALVE BEFORE ATTEMPTING TO
s
REMOVE TEST EQUIPMENT OR INSTRUMENTS FROM THE
ne
SERVICE VALVES. FAILURE TO FOLLOW THIS PROCEDURE
WILL RESULT IN LOSS OF REFRIGERANT.
rli
1.C.i.q.4. Relief Valves (V15, V18) (See Figure 18)
Ai
All system pressure vessels installed in the refrigeration circuit are equipped with a
safety relief valve conforming to ANSI/ASHRAE 15 Standard Safety Code for
an
Mechanical Refrigeration. Flow ratings are National Board certified. The valves are
Teflon seated to permit their use in either high or low pressure applications. The
relief valves are equipped with ½ in., NPTM inlet; 5/8 in. SAE flare outlet; 375 psig
ic
fixed relief valve setting; angle-type brass body; and 9/32 in. port size. Since the
valves are not intended to regulate overload or cutout pressures, the relief valve
er
discharge pressure setting corresponds to the maximum working pressure rating of
the vessel.
Am
CAUTION:
THE RELIEF VALVES SHOULD NEVER BE DISCHARGED
of
Check valves are installed in the refrigerant and compressor oil circuits to prevent
reverse migration of flow during an off cycle or during a change of operating cycle.
The check valves incorporate a spring-biased valve that permits unidirectional flow.
Pr
Check valves are installed in the vapor injection line to the compressor, the oil
injection line to the compressor and also the liquid injection line to the compressor.
Creation:05-04-2012 1-1-38
s
ne
rli
Ai
an
A
ic
er
FRONT-SEATED (ALL FLOW SHUT OFF)
Am
B
of
C
Pr
Ai
an
ic
er
Am
4
of
ty
er
2......Seat valve
3......Piston valve
4......Spring 2
Pr
5......Outlet fitting
Creation:05-04-2012 1-1-40
s
ne
rli
Ai
an
2
ic
3
er
Am
4
1
of
5
ty
er
2 .....Bonnet
3 .....Bolt
4 .....Spring, valve
Pr
5 .....Gasket
6 .....Piston, valve 6
A charge of air is forced into the cylinders by the turbocharger compressor that evacuates
all of the burned gases resulting from fuel combustion through the exhaust valve ports.
s
This dense charge of intake air cools the exhaust valves and internal engine parts. Clean,
ne
relatively unrestricted air flow is supplied through the air filter assembly for this purpose.
The air filter assembly installed on the unit is a single-stage with 99% cleaning efficiency.
The paper pleats are permanently locked in place in the self-contained housing. A
rli
pressure indicator is mounted on the ducting between the filter and the turbo-inlet to
monitor filter restriction.
Ai
[Link] Air Cooler
an
A charge air cooler (CAC)(C31) is required to cool the air leaving the turbo-charger before
it is introduced into the engine intake manifold. This is an air to air heat exchanger,
ambient air is blown across the CAC to cool the pressurized engine intake air running
ic
through it. The CAC is sized to bring the charged high-temperature air from the CAC
er
down to the specified temperature for engine ingestion.
discharges exhaust gases to the atmosphere through a vertical outlet pipe fitted with a rain
cap. The primary function of the exhaust system is to capture the gases which result from
the combustion of the fuel/air mixture in the engine and to vent them with low flow
ty
resistance into the atmosphere. The silencer damps exhaust sounds and removes carbon
particles and other particulate matter from the exhaust gas stream. Collected solids need
er
NOTE:
Pr
Creation:05-04-2012 1-1-42
s
ne
rli
Ai
an
ic
er
Am
of
ty
3….Alternator
4….Turbo discharge to CAC
op
5….Turbo inlet
6….Turbo exhaust
7….Oil filter
Pr
8….Starter motor
9….Coolant conditioner element
3….Oil dipstick
4….Oil fill
op
5….Oil Pan
6….ECM
Pr
Creation:05-04-2012 1-1-44
[Link] System (See Figure 21)
The diesel engine is water cooled through a 50% solution of anti-freeze concentrate
and pure, demineralized water that is circulated through a coolant loop in the
condenser coil where forced air heat exchange occurs during fan operation. An
ethylene-glycol base antifreeze is used in the engine cooling system. The antifreeze
raises the boiling point of the coolant mixture. The coolant system comprises a 10
psi filler cap, an expansion tank, a 6 quart overflow recovery tank, and one row of
the condenser coil. The engine coolant loop portion of the condenser coil is located
away from the coil to prevent interference with the refrigeration process.
s
ne
Coolant is drawn by the centrifugal water pump on the engine from the condenser
coil and forced through the engine oil cooler into the cylinder block. The coolant
then circulates through the block into the cylinder heads. When the coolant is below
rli
operating temperature 180 °F (87°C ), coolant flow is blocked at the thermostat. A
bypass return allows the coolant to circulate within the engine during warm up.
Ai
Once operating temperature is reached, the thermostat opens and coolant flow is
bypassed to the condenser coil. The thermostat functions to bypass coolant flow
when operating temperature is reached and to regulate engine coolant temperature.
an
The thermostat prevents coolant temperature fluctuation caused by variations in
engine loads and speed. Unregulated engine temperature would result in
incomplete fuel combustion and resulting dilution of lubrication oil, excessive engine
ic
wear, and sludge formation in the crankcase due to overcooling.
er
The function of the coolant is to absorb the heat generated by the combustion
process and remove the heat absorbed by the engine oil. The expansion tank
Am
deaerates the cooling system via small dearation hoses placed within the cooling
system. The upper portion of the chamber acts as a reservoir for the collected air.
During engine operation, as coolant temperature increases and expansion occurs,
the filler cap acts as a relief valve, opening at 10 psi to release air and expanded
coolant into the overflow recovery bottle. After engine shutdown, coolant in the
of
system cools and contracts, lowering internal pressure below atmospheric pressure.
The resulting partial vacuum draws coolant from the overflow recovery bottle back
into the system through the pressure filler cap. A coolant level sensor is installed in
ty
the expansion tank to ensure engine operation with too low of a coolant level does
not occur.
er
The heat boost circuit functions to increase supply air temperature at the air outlet in
the heating mode of unit operation. The heat boost coolant circuit consists of a
Pr
normally-closed, two-way 24 VDC solenoid valve, a 2-row, 18 circuit tube and fin
EGW heat exchanger, interconnecting hose and clamps installed in parallel with the
conventional engine coolant circuit.
The solenoid valve is installed in the coolant line from the heat exchanger coil to the
coolant expansion tank. The heat boost coil is mounted in the air outlet chamber
inside the evaporator coil box. The coil assembly is a forced air heat exchanger
comprised of staggered circuits of finned copper tubing enclosed in a galvanized
steel casing with inlet and outlet header pipe manifolds. The solenoid valve controls
coolant flow through the secondary heat boost circuit. The engine coolant, a heat
Creation: 05-04-2012 1-1-45
transfer solution comprising 50% ethylene glycol antifreeze concentrate and 50%
demineralized water, transports the waste heat rejected by the engine during fuel
combustion to the heat exchanger coil where the heat is transferred to the air
supply. The coolant is circulated through the engine and plumbing circuit by the
engine water pump. The heat boost coil dissipates the heat gain absorbed by the
engine coolant, applying finish heat to the supply air at the inside coil box air outlet.
The EGW heat exchanger provides up to 40 °F (4,000 Btu/min.) of additional heat
in the heating mode of unit operation.
NOTE:
Heat boost coil (C29) and Heat boost solenoid (L7) are
s
only supplied with optional heat unit.
ne
SOLENOID (L7)
rli
Ai
HEAT BOOST EXPANSION
COIL (C29) TANK (C9)
an
INSIDE COIL (C4)
ic
er
Am
RECLAIM
TANK
of
PTO (C26)
ty
er
op
DIESEL ENGINE
(C1)
Pr
SHUT OFF
VALVE (V41)
Creation:05-04-2012 1-1-46
[Link].e. Fuel System
The fuel system is comprised of the following components: a 130 gallon (492 liter)
capacity vented fuel tank; a fuel level sender; a filler cap; outlet check valve; fuel suction
filter; fuel pump; fuel injectors; and the necessary interconnecting fuel lines and fittings. A
pressure regulator installed in the return fuel manifold maintains system pressure.
Fuel is drawn from the fuel supply tank through a fuel filter/water separator and enters a
fuel transfer pump. The transfer pump delivers fuel to the secondary filter mounted on the
engine. The fuel is then further pressurized by an on engine high pressure pump, and is
then delivered to the high pressure fuel rail which supplies fuel to the injectors. The fuel is
filtered through elements in the injectors and atomized through the spray tip orifices into
the combustion chamber. Surplus fuel is delivered to the interconnecting fuel lines back to
s
the fuel tank.
ne
[Link].f. ECM (Electronic Engine Control Module) (See Figure 20)
rli
The ECM controls the speed of the engine. It fulfils all the functions of the mechanical
controller plus other functions. The main components of the ECM are the sensors, the
Ai
control unit and the actuator. Engine-side and unit-side equipment is connected to the
ECM control unit by way of separate-prefabricated wiring harnesses. The unit-side wiring
is installed by the unit manufacturer. Further information about the ECM may be found in
an
Chapter 5.
[Link] System
ic
[Link].g.1. Alternator (G1) (See Figure 20)
er
A 24 VDC alternator provides the electrical current required to maintain the storage
Am
output current.
Two 12 VDC lead acid batteries are installed in series in the unit electrical system to
er
provide 24 VDC operating power. The flooded electrolyte wet cell batteries are
rated at 1,000 cold cranking amps, 200 minutes reserve capacity. The batteries are
op
equipped with SAE type A top post terminals. The batteries conform to BCI group
size 31.
Pr
s
ne
rli
7
Ai
an
ic
er
6
Am
of
5
ty
4
er
4. ....Tow bar
5. ....Parking brake
6 .....Carrier, front axle 1
7. ....Rear axle assembly 2
8. ....Carrier, rear axle
Creation:05-04-2012 1-1-48
[Link]. Trailer Running Gear (See Figure 23)
The trailer running gear comprises a front axle, carrier, carrier support, leaf springs, and towbar;
a single rear axle, carrier, and leaf springs; six wheel and tire assemblies; and mechanical
parking brakes. Running gear capacity is 17,000 lbs (7,711 kg). The running gear utilizes a fifth
wheel design front axle that allows the unit to be turned in a radius equal to its length. Leaf
spring suspension permits smooth towing over irregular surfaces. The rear axle dual wheels
provide increased carrying capacity to accommodate unit front to rear weight distribution. Front
axle capacity is 6,000 lbs (2,722 kg). Rear axle capacity is 11,000 lbs (4,989 kg)
The mechanically actuated parking brakes are automotive type assemblies with internal
expanding shoe, backing plate, and drum. The brakes are designed to lock the wheels and skid
s
the trailer when subjected to a sufficient towing force applied in either a forward or reverse
ne
direction. The parking brakes will maintain trailer position, under full load, on a 11.5 degree
grade. The parking brake is the only means of holding the trailer in a stationary position when
the tow bar is disconnected from the towing vehicle. Dead man or run-away braking is optional.
rli
A gravity latch retains the tow bar in the elevated position. The latch may be actuated at any
Ai
degree of steering angle. Raising the tow bar does not apply the parking brake. A 4 in. I.D.
heavy-duty forged steel lunette eye is welded to the towbar. The towbar is a heavy-duty
assembly of open channel steel construction. The towbar hinge pin is 1.0 inch in diameter.
an
The parking brake lever is an over-center assembly incorporating a handle with knurled
adjustment knob, heat treated alloy steel load link, pins, fasteners, and side-mount brackets.
ic
The lever has two end positions, “over center” and “off,” which are approximately 90 degrees
apart. To compensate for cable travel, brake lining wear, and to allow setting apply tension, the
er
brake lever incorporates an adjustment knob, providing approximately 1.5 inches total
adjustment and infinite positioning within that range. An optional setscrew prevents unauthorized
Am
Since the parking brake system combines a linear, rigid control rod with adjustable linkage,
“mechanical advantage” describes the braking action provided. Movement of the lever operates
a control rod connected to a trailer cross shaft. Adjustable linkage interconnects the brake
of
backing plates with pivot brackets installed on the cross shaft. The pivot brackets, which rotate
on the cross shaft, actuate the linkage when the brake lever is moved to the over-center position.
The turnbuckle assemblies are connected to a control lever on the brake backing plate. A
ty
wedge secured to the lever by a clamping bolt expands the brake shoes against the machined
surface of the drum. The output end of the load link is connected to an SAE 3/8-24 UNF control
er
rod clevis. The parking brake is equipped with 9-inch diameter, 2-inch wide shoe and lining
assemblies and matching drums.
op
The front axle is manufactured from square mechanical steel tube and includes welded steering
and wheel hub spindles. The axle track is 22-1/2 inches (57cm). Front leaf springs are 23
Pr
inches (58 cm)long eye-to-center of slipper with four leaves. Nylon bushings are installed in the
spring eyes. The springs, two inches wide, are attached through U-bolts to the axle and through
hardened steel fasteners to the fifth wheel steering arm.
The rear axle is manufactured from deep section rectangular mechanical steel tube and includes
welded wheel hub spindles. The axle track is 73 inches (185 cm). Rear leaf springs are 27-1/2
inches (70 cm) long eye-to-center of slipper with eight leaves. Nylon bushings are installed in the
spring eyes. The springs are attached through U-bolts to the axle and through hardened steel
fasteners to shackles welded to the rear carrier assembly. The rear axle is equipped with 2 in. X
9 in. drum type parking brakes and dual hubs.
Creation: 05-04-2012 1-1-49
The running gear wheels and hubs are designed to permit towing the trailer over various ramp
surfaces in all weather conditions. The wheels are steel single-piece assemblies 10 inches (25
cm) in diameter with 5 bolt holes on 5.5 inch (14 cm) bolt circle. Wheel width is 5.5 inches (14
cm). Wheel bolts are ½-20 UNF size with helical, split lock washers and hex nuts. The rims are
5 degree flat base wheels with “F” contour. Valve hole location is one-inch offset. The hole
accommodates a standard TR-135 tube valve stem. The valve stem is equipped with a .305-32
cap thread. Load range “E” (10 PR) 7.50-10 highway trailer tires are mounted on the rims.
Tire design section width is 8.0 inches and 25.46 inches overall diameter. The load rating over
paved roads at 10 mph (16 km) is 2,860 lbs (1,297 kg). capacity at 85 psi inflation pressure. The
hub assembly is a conventional cantilever mounted cast iron assembly, equipped with grease
seal, tapered roller bearings, press-fit bearing races, keyed washers, castellated nut, cotter pin,
and dust cover. The cantilever type hub is a full-float assembly installed on the trailer front and
s
rear axle spindle.
ne
[Link]. Power Take Off (C26) (See Figure 24)
A heavy-duty power take off is installed on the engine flywheel housing to transmit engine power
rli
to the compressor and supply air blower. The power take off combines a direct in-line drive for
running the compressor and a side-loaded drive for operation of the blower. The in-line drive
Ai
incorporates an overload type coupling assembly. The side-loaded drive incorporates multi-
sheave pulleys and a poly v-band drive belt.
an
The power take off is designed to fit an SAE #2 housing and is of the clutchless variety. The
power take off is of suitable capacity for either side-load or in-line applications. It consists of a
cast housing, tapered roller main bearing supported drive shaft, ball pilot bearing, bearing
ic
retainer, torsional flywheel coupling, and fasteners. The torsional flywheel coupling is bolted
directly to the flywheel. The flywheel coupler is directly mounted on the drive shaft.
er
The power take off housing is bolted to the flywheel housing on the engine. The rear of the
Am
driveshaft is supported by main roller bearing assemblies contained in the housing. The shaft
pilot extension is supported by a ball bearing pressed into the flywheel. The cross shaft bearings
are grease lubricated through fittings provided on the housing.
Engine horsepower is transmitted to the compressor and supply air blower through a
er
power take off assembly, a multi-ribbed v-belt, drive coupling, quick-disconnect shaft
mounted sheave assemblies, and taper-lock bushings. The power take off driveshaft is
connected in-line with the input shaft of the compressor through an overload drive
op
coupling.
Pr
The blower is belt driven from a multi-sheave pulley installed on the power take off
driveshaft in front of the drive coupling and a matching pulley on the blower input shaft.
The blower input shaft is mounted on the blower drive frame, supported by pillow block
bearings. The blower fan is connected to the input shaft through a hub, setscrews, end
plate, shaft key, eight cap screw fasteners, and center bolt. All fasteners are cross-drilled
and safety wired. The only side loading occurs from the overhung load imposed from the
torque transmitted by the belt drive.
The bushing may be installed either on the outside or inside of the pulley. The screws are
installed through tapped holes in the pulley hub when the bushing is located inside. The
attaching screws are always located on the outside where they are easily accessible.
When the bushing flange is facing toward the component, the tapped holes in the bushing
flange are aligned with drilled holes in the sheave hub. When the bushing flange is away
s
from the component, the drilled holes in the bushing flange are aligned with the tapped
ne
holes in the sheave hub. Industry standard size “SF” and “SK” bushings are installed on
the indirect belt drive system
rli
The compressor drive coupling is a rigid assembly consisting of a 2-1/2 inch I.D. PTO
shaft coupling half; a 2.802/2.805 in. I.D. compressor shaft coupling half; a 2” diameter
Ai
compressor shaft bushing; a 10-1/4 inch long center spool; spacer links, fasteners, and
calibrated overload disc packs. The disc packs are designed to relieve the shearing
stress caused by shock load torque.
an
The drive belt is a multi-segment banded v-belt assembly consisting of five double-
wrapped “BP” section ribs. The ribs are wrapped with a cotton polyester fabric cover
ic
impregnated with synthetic neoprene rubber compound. The belts comprise a tension
section of rubber compounds that stretch as the belt bends, a rubber compression
er
section, and polyester and aramid fiber cords that carry the horsepower loads. The multi-
segment belt design multiplies belt strength and load carrying capacity and eliminates belt
Am
The belt is 81 inches (205.7 cm) overall outside length. “BP” section belts are 21/32 inch
wide at the top with 7/16 inch high sides. Wrapped v-belts eliminate static electricity
through the cover. Belt drive alignment is critical, with pulley angular misalignment to a
of
maximum of .33 degree resulting in 4-13 percent reduced life span. The belting tolerates
up to .005 in./inch parallel misalignment. Maximum static tension for a new belt is 45 lb. ft.
per rib and 15 lb. ft. per rib for a used belt. Drive pulleys must be replaced when
ty
excessive wear allows the pulley rib tip to contact the belt rib root. The poly-rib belt
requires less energy to operate than conventional v-belts.
er
The sides of the belt should wedge the belt in the groove. The belt grips the pulley. If the
op
pulley is excessively worn, allowing the belt to ride on the bottom of the groove, the belt
will be forced away from the sides, reducing belt grip and drive performance. A screw
adjusted belt tensioner pulley assembly is mounted on the blower frame. All belt drives
Pr
an
ic
er
1
Am
3
of
ty
er
3. ....Overload coupling
4. ....Drive pulley
Pr
Creation:05-04-2012 1-1-52
1.C.v.b. Engine Fan Drive
The engine fan drive assembly provides the mass air flow required to accomplish heat
transfer in the outside condenser coil. The compressor delivers hot, dense high pressure
refrigerant vapor to the condenser. The cooler ambient air flow forced through the coil by
the fans causes the hot high pressure vapor to condense to a liquid as the heat carried by
the refrigerant dissipates. This heat transfer rejects the heat absorbed by the refrigerant
in the evaporator coil when in cooling mode.
The fan drive assembly consists of twin, 42” diameter, propellers with (C11, C30 – see
flow diagram) 1-1/4 inch tapered bushing; 2 pair of conventional heavy-duty “BP” section
v-belts ; quick-disconnect shaft mounted pulleys; tensioner pulleys; taper-lock bushings;
s
spacers; engine stubshaft; and pillow block bearings. The fan drive pulleys are belt driven
ne
from a multi-sheave crankshaft pulley installed on the engine stubshaft. Each drive pulley
is driven by a matched pair of v-belts. Fan input shafts are supported by pillow block
bearings mounted on the venturi frame. The fan venturi ensures that air flow through the
rli
condenser coil is symmetrical.
Ai
an
ic
er
Am
of
ty
er
op
Pr
4
1
s
ne
rli
Ai
5
an
6
7, 8
ic
er
Am
of
ty
er
Creation:05-04-2012 1-1-54
[Link]. Supply Air System (See Figure 25)
The supply air circuit consists of a centrifugal fan wheel; a power take off belt drive; mechanical
drive components; the blower housing with washable inlet filter; inside evaporator coil assembly;
the coil enclosure; hose outlet assemblies; and supply air delivery hose(s). The supply air
system provides controlled conditioned air flow, adjustable to meet individual cooling
requirements depending on variable conditions such as heat and electrical load, passenger load,
and ambient temperature.
Ambient air is drawn through a 3/8-inch thick open pore polyurethane foam filter at the blower
inlet. The cleaned air is compressed by the blower and forced through the evaporator coil where
heat transfer occurs. The supply air compressed by the blower fan is forced through a diffuser
s
on the top of the evaporator, and through the lower diffuser, into the evaporator chamber where
ne
moisture separates from the air and collects in a drainage tray. From the lower chamber, the air
enters the outlet assemblies that contain the air delivery dampers. The air delivery dampers
rotate 90 degrees from the fully closed to the fully open position. A rubber seal in each damper
rli
shuts off air flow in the closed position. The conditioned air is then supplied through the delivery
hose to the aircraft.
Ai
an
ic
er
Am
of
ty
er
op
Pr
s
ne
rli
Ai
an
ic
er
1 6
7
Am
4
5
of
ty
er
Creation:05-04-2012 1-1-56
[Link].a. Blower Assembly (C6) (See Figure 26)
The blower assembly consists of the centrifugal fan wheel, of aluminum construction, and
a steel blower shroud with diffuser. The centrifugal fan wheel has blades that are flat and
backward inclined, leaning away from the direction of the wheel’s rotation. This type of fan
is efficient and designed to operate at high speeds. A rotating blower wheel draws air in
through the inlet, increases its velocity, and discharges the air from the housing outlet.
The purpose of the housing is to convert the high velocity pressure produced by the fan
blades to static pressure at the housing outlet. The conversion process is dynamic. Total
air pressure includes both velocity and static elements. Pressure conversion is improved
s
by the diffuser, which acts to straighten the flow. Flow rate and static pressure at the
ne
blower outlet increase as the diffuser angle increases. By providing a gradual increase in
the flow area, a diffuser gradually decreases the air velocity and produces a higher static
outlet pressure. Static pressure identifies the pressure required to overcome the system’s
rli
resistance to air flow expressed in inches of water. Static pressure, which exists in air at
rest or in motion, represents potential energy.
Ai
Two types of losses are associated with pressure conversion: loss due to friction and loss
due to flow separation. Static pressures must equal the sum of the pressure losses in the
an
system at the required flow rate. Static efficiency is the ratio of total air horsepower output
to impeller horsepower. Total air horsepower output consists of static and velocity
elements. Maximum static efficiency falls at the top of the performance curve before the
ic
stall recession. In an efficient air delivery system, air delivery duct static pressure losses
must be made up by the pressure generated by the blower. Velocity pressure, expressed
er
in inches of water, is produced by the velocity of air flow and represents kinetic energy.
Total pressure in the air moving system is the sum of static and velocity pressure. Total
Am
absolute pressure at any point is the sum of total pressure and atmospheric pressure.
The total required velocity pressure at any point in a system is fixed by the rate of air flow
that must be maintained.
Any fan adds kinetic energy to the air in an air moving circuit. Part of this kinetic energy is
of
converted to potential energy or static pressure. Static pressure is equal in all directions in
still air. In moving air, static pressure can be accurately measured with a manometer
connected to a pressure tap flush with the inner wall of the duct. Total pressure is
ty
measured by an open-ended probe (pitot tube) facing directly into the air flow. The
difference in liquid levels in the manometer records the total pressure value. Velocity
er
Resistance to air flow in an air delivery system is caused by the combined effect of duct
friction and the energy dissipating effect of turbulence. Total system resistance can then
be expressed as the overall static pressure loss that corresponds to air velocity and
Pr
velocity pressure. The total energy discharged by the fan is a product of flow rate (cfm)
and total pressure. Static pressure decreases as the flow rate increases. The point of
operation in an air delivery system is the intersection of flow rate and static pressure at a
given fan speed. Air horsepower is the energy delivered by the fan to an air moving
system. When the fan discharges into a plenum chamber, the velocity head is dissipated
in turbulence.
The performance of all fans and blowers is governed by rules of physics referred to as
Fan Laws. Air volume flow rate (cfm), rotation speed (rpm), static pressure (sp), and
horsepower (hp) required to drive a blower fan. When volumetric air flow rate changes, all
the other values change.
Delivered air volume varies directly with the speed ratio and is not affected by changes in
air density. Static pressure varies with the square of the speed ratio and varies directly
with the density ratio. Horsepower varies with the cube of the speed ratio and varies
directly with the density ratio. The performance requirements at a new air flow rate are
calculated by finding the ratio of the new flow rate to the existing flow rate. The new rpm
s
required is found by multiplying the ratio by the existing rpm. Static pressure is found by
ne
multiplying the ratio by itself and the result by the existing static pressure. To determine
the new horsepower requirement, multiply the ratio by itself twice, then by the existing
horsepower. Finally, calculate the percent of change required by comparing existing
rli
conditions with new performance requirements.
Ai
[Link].b. Air Intake Filter (F11)
The two-piece air intake filter-silencer removes dirt, dust, pollen, and other foreign
an
materials from the ambient air. It is mounted on the blower inlet and is easily removable.
The filter dampens sound and provides sufficient element area to maintain adequate air
velocity.
ic
[Link].c. Hose Outlet Chamber
er
T
he outlet chamber(s) directs the supply air into the delivery duct hose connected to the
Am
aircraft conditioned air inlet. The hose outlet assembly consists of a single or optional
double hose connector rings, damper gate plates, gate shafts, bushings, damper handles,
and mounting brackets. The connector rings accommodate 12-inch I.D. duct hose. Gate
plate fasteners are safety wired for security. On standard units equipped with a single
hose connection, the optional hose connection is blocked by an insulated cover plate.
of
ty
er
op
Pr
Creation:05-04-2012 1-1-58
1
2
3
s
ne
4
rli
Ai
5
an
9
ic
er
Am
of
6
8 7
ty
er
op
The air delivery hose assembly includes a male coupler ring for attachment to the
conditioned air outlet chamber through turn catch latches; a round or an optional lay flat
12-inch I.D. flat or wire reinforced duct hose with scuff strip, and transition section to 8-
inch I.D. cuff; hose clamps; and quick connect/disconnect hose coupler assembly.
Standard hoses are supplied non-insulated. Insulated hoses are optional. Hoses are
available in various lengths and sizes to meet customer requirements. Hoses may be
connected through aluminum sleeves in multiple lengths. All materials used in hose
construction are fire resistant. The duct is designed for outdoor use in all types of weather
including damp, salt-laden air for extended periods of time. The hose may be handled in
s
any direction with a minimum crimping of fabric. The helical stiffener core in wire-
ne
reinforced hose prevents transverse collapse and excessive area reduction during sharp
bends. The internal surface of the duct is constructed to minimize air friction losses and
leakage. This type of hose may be retracted to 20 percent of its full length to permit
rli
compact storage. The hose may be stored without damage in ambient temperatures
ranging from -80°F (-62°C) to 160°F (71.1°C). The duct hose resists exposure to salt-fog
Ai
atmosphere, fungus growth, ultraviolet light, ozone, and rain. The hose is capable of
withstanding internal temperatures to 250°F (121°C); internal operating pressures of 3
psig; and tensile pulls to 600 lbs. (12 in. size) without rupture or separation. The exterior
an
hose fabric is non-permeable, highly resistant to abrasion, and is repairable. The fabric
and scuff strip are lock stitched to prevent unraveling if broken. Hose weight is
approximately 1.8 lbs./ft.
ic
The hose-to-aircraft coupler clamped to the end of the hose is a quick connect/disconnect
er
assembly of all stainless steel construction matching the industry standard specifications
(MS33562) for aircraft 8-inch conditioned air connectors. The coupling consists of a
Am
stainless steel body and sliding ring, opposed loop handles, adjustable hook latches,
locking levers, and compression springs. The handles aid pushing the coupling steel
hooks into the slots on the aircraft connector ring. The slots are located 180 degrees
apart on 9-1/8 in. centers. The coupler is twisted ¼-turn to engage the connector ring;
then clamped into position tightly using the spring-loaded locking levers. A replaceable
of
Creation:05-04-2012 1-1-60
s
ne
rli
Ai
an
ic
3
er
Am
of
1
ty
er
op
2
1 .....Hose
2 .....Hose coupler SEE VIEW A
Pr
AIRCRAFT COUPLER
s
ne
rli
Ai
ACE-277-004
an
ic
er
Am
of
P/N 1003414-6
ty
er
op
ACE-277-804
Pr
Creation:05-04-2012 1-1-62
[Link]. Electronic Control System
The unit is equipped with a ‘smart’ control system that allows the unit to operate at maximum
efficiency under all operating conditions. Operator interaction with the control system occurs at
the unit operating panel. The control system consists of a PLC (E1), an HMI display, various
pushbuttons on the unit control panel, and various sensors mounted in the unit.
The electronic control system may be operated in two modes, a ‘closed loop’ mode, where a
cabin temperature feedback probe is deployed, or an ‘open loop’ mode of operation where the
unit calculates a best guess for the needed output to satisfy the aircraft.
In the closed loop mode, the PLC in the unit will directly read the aircraft cabin temperature.
s
From this temperature, it will automatically control the unit fully, including mode of operation.
ne
The engine speed, and therefore blower speed will be regulated to supply sufficient air to heat or
cool the cabin as needed, with the compressor being automatically loaded and unload to keep
the delivered air temperature correctly for the aircraft demand. This mode is automatically
rli
enabled when the optional aircraft temperature probe is connected to the unit.
Ai
In the open loop mode, the PLC will calculate a ‘best guess’ for aircraft requirements. The
operator will also need to select the unit mode of operation before starting the engine. The unit
will operate at a fixed output pressure and temperature to satisfy the aircraft for a given ambient
an
temperature. This mode of operation is automatically selected when the optional aircraft probe is
not connected, or a fault occurs with the probe or its circuit.
ic
In either mode of operation, the operator can ‘bias’ the output of the unit, that is, make it warmer
or cooler. There is a range of -10 to 10 on the bias value, and is the only operator influence on
er
the unit’s operation.
Am
The programmable logic controller (PLC) is the ‘brain’ of the electronic control system
employed on the unit. It directly controls the speed of the engine, and the operation of
every valve, solenoid, and relay on the unit. All lamps, beacons, and other accessories
of
The software in the PLC analyzes values of various sensors within the unit, and based
upon their values, calculates the best action for the unit to operate as efficiently as
er
possible. The PLC will automatically load or unload the compressor, and will regulate
engine speed to deliver the proper quantity and temperature of air to the aircraft to satisfy
its heating or cooling requirements.
op
The PLC software also contains a large library of aircraft and their heat transfer
characteristics for open loop operation. The software is also aware of the maximum
Pr
allowed pressures for aircraft and will never exceed them, no matter the cooling or heating
demand.
The PLC also acts as the unit main safety device. Whenever a sensor or safety switch is
actuated, the PLC will immediately stop the engine to prevent damage to the unit, or to
personnel near the unit.
The PLC to engine interface consists of a J1939 CAN (Controller Area Network) bus and
the keyswitch power input to the ECM. The keyswitch power input is used to enable or
disable engine operation, while the J1939 commands the engine operating speed.
Creation: 05-04-2012 1-1-63
[Link].b. HMI Display (E2)
The HMI display is the link between the operator and the PLC. It allows the user to pick
the aircraft being serviced, displays the fuel level in the fuel tank (if equipped), choose the
mode of operation, and bias the unit output.
In the event of a fault condition, the unit will display a fault code number on the display in a
dedicated screen. This fault number can be used to assist in further diagnosis of the
issue.
There is a hidden menu availble to assist in servicing, testing, and maintaining the unit.
This menu allows the unit to be operated manually, allows every input value to the PLC to
s
be read, every output from the PLC to be actuated, and allows the fault and warning code
ne
history of the unit to be read. Unit options are also configured in this menu.
rli
This sensor is deployed into the cabin of the aircraft for closed loop operation. Once
Ai
connected, the unit automatically will operate in closed loop mode until the sensor is
disconnected. The sensor connector is located to the left of the unit operator’s station and
extension cables are used to connect the unit to the sensor in the cabin. This sensor is of
an
a the 4-20mA type, unaffected by cable length. No fault code exists for the loss of this
sensor, the unit will automatically revert to open loop cooling mode when the sensor
connection fails.
ic
er
Am
of
This sensor is installed above the air intake of the blower. This sensor measures the
temperature of the air ingested by the blower as the ambient temperature the unit, and
er
therefore, the aircraft are in. This data is used to in the computation of the aircraft
flow/pressure requirements in open loop mode. A fault with this sensor or circuit will
op
Creation:05-04-2012 1-1-64
[Link].e. Compressor Slide Valve Position Sensor (B3)
This sensor is mounted in the compressor. It is attached the slide valve and senses the
position of the slide valve in the compressor. A 4-20mA signal is generated and used by
the PLC to determine when the compressor is operating at full capacity. A fault code 02
will be displayed when a fault exists in this sensor or its circuit.
This sensor is mounted in the discharge plumbing of the compressor in a thermowell. The
thermowell is brazed into the plumbing, allowing the sensor to be replaced if ever
necessary without removal or loss of refrigerant from the refrigeration system.
s
ne
The temperature of the discharge gas from the compressor is measured by this sensor.
The PLC will use this information to turn on and off the liquid injection solenoid as needed
to keep the discharge gas temperature at 190 °F ( 88 °C) or less to ensure oil temperature
rli
is maintained at 190 °F ( 88 °C ) or less.
Ai
A second function of this sensor is to act as the discharge temperature safety for the unit.
A fault code 08 indicates excessively high discharge temperature, while a fault 03 will be
displayed when a fault exists in this sensor or circuit.
an
[Link].g. Inside Coil Pressure Transducer (B5)
ic
This sensor is mounted in the plumbing adjacent to the inside coil. A 4-20mA signal is
generated by this sensor in the range of 0-363 PSIG ( 0-25 bar).
er
This sensor is used by the PLC to determine the inside coil pressure, and control the load
Am
and unload solenoid valves as needed to keep the inside coil pressure as desired.
This normally closed switch monitors the pressure of the compressor suction and
ty
discharge as a safety. If the suction pressure becomes too low or the discharge pressure
is too high, the switch will open and the PLC will shut off the unit. This switch is set suring
er
the initial startup and setup of the unit and should never need adjustment for the life of the
unit.
op
A fault code 11 indicates that this switch has tripped, or there is an issue with the circuit
containing this switch.
Pr
an
2
1
4
ic
er
Am
of
5
ty
er
op
Creation:05-04-2012 1-1-66
[Link].i. Delivered air pressure (B6) and temperature (B7) sensors
These two sensors are mounted in the coilbox of the unit, near the hose outlet assembly.
The pressure and temperature of the air leaving the unit to the aircraft are monitored by
these two sensors and converted to 4-20mA signals for the PLC to read.
The outlet air pressure sensor is used by the PLC to control the engine speed to achieve a
desired outlet air pressure to the aircraft. The temperature sensor is used to regulate the
load and unload solenoids by the PLC as needed to ensure no coil freezeup occurs in the
unit. Fault codes 03 and 04 are assigned to these two sensors for troubles with the
sensor or the circuitry going to the sensors.
s
ne
rli
Ai
an
ic
er
B7
Am
B6
of
ty
er
op
Pr
This sensor is mounted to the side of the compressor assembly. It measures the position
of the slide valve in the compressor and converts that to a 4-20mA signal for the PLC to
read. The PLC uses this signal to determine when to increase the outlet pressure to affect
more cooling or heating when needed in the closed loop cycle.
A fault 02 will be set when there is a problem with this sensor or the circuit containing it.
s
ne
rli
Ai
an
ic
er
Am
of
ty
er
op
Pr
Creation:05-04-2012 1-1-68
2. Operation
2.A. Environmental Considerations
WARNING:
POSITION THE UNIT TO AVOID EXHAUST FUMES OR
s
COMBUSTIBLE VAPOR INTAKE INTO THE BLOWER. FAILURE
ne
TO DO SO MAY CAUSE EXHAUST FUMES OR VAPORS TO BE
BLOWN INTO THE AIRCRAFT!
rli
Unit performance is affected by local ambient air condition. Factors that contribute to the heat
load carried by ambient air are the heat absorbed from other equipment, buildings and other
Ai
structures, fencing, and prevailing wind. Position the unit where a continuous supply of fresh
ambient air is available. Unit performance and capability will decrease if the unit is positioned
where it will receive hot, contaminated intake air.
an
The unit will operate satisfactorily when ambient air is highly contaminated providing that the
blower filter and outside condenser coil are kept clean.
ic
er
The unit may be operated on a slight incline, but optimum performance is attained when the unit
is level, ensuring proper compressor lubrication.
Am
For any given resistance, the volume of air delivered by the unit’s fans and blower is not affected
by changes in air density. However, delivery pressure and mass flow rate will vary directly with
ty
air density.
er
Normal cold climate operation should not affect unit performance and reliability. Consult TLD for
extreme cold weather operation. Cold weather starting kits are available options to improve
engine cold weather starting capability.
Pr
WARNING:
IMPROPER OPERATION MAY CAUSE PROPERTY DAMAGE,
RESULT IN PERSONAL INJURY OR DEATH.
READ AND UNDERSTAND THE OPERATING INSTRUCTIONS
THOROUGHLY BEFORE ATTEMPTING TO OPERATE THE UNIT.
Preparation for use includes instructions for redeployment of the unit following shipment or storage;
s
preparation for normal use; and preparation for use in temperature extremes.
ne
2.B.i. First Use or Preparation for Use Following Shipment
rli
Before starting or operating the unit for the first time or after shipment, perform the following:
Apply the parking brake and chock the wheels.
Ai
Remove the blocking, banding, and tie down restraints securing the unit to the shipping vehicle.
Open all access doors and remove interior packing materials.
Remove interior and exterior sealing materials.
an
Close all drain valves.
Connect the battery cables and check battery charge condition using the panel mounted
voltmeter. ic
2.B.i.a. Inspection
er
Inspect the unit thoroughly prior to use. Perform the following checks:
Am
Inspect the exterior for shipping damage, broken lights, bent sheet metal, or other external
damage. Check for visible evidence of engine fuel, coolant and oil leaks; refrigerant leaks;
and compressor oil leaks.
Creation:05-04-2012 1-2-2
2.B.i.c. Engine Coolant Level
CAUTION:
ENSURE THAT THE COOLANT SOLUTION WILL PREVENT
FREEZING AT THE LOWEST EXPECTED TEMPERATURE.
NOTE:
s
If the engine coolant has been drained for shipment, refill the
ne
cooling system with ethylene-glycol antifreeze concentrate
mixed with fresh water in the recommended proportions.
A 50 percent EGW solution will provide protection to -34°F
rli
(-37°C).
Ai
Check coolant level. The recovery bottle should be half-full for normal operation.
an
2.B.i.d. Fuel Level
Fill the fuel tank as required with fresh, clean low sulfur (0.05% max.) diesel fuel meeting
ic
the requirements of ASTM designation D975 No. 2. Refer to the engine operation manual
contained in Chapter 5 for fuel specifications.
er
CAUTION:
Am
2.B.i.e. Fasteners
ty
Check for loose fasteners and clamps, missing service port caps, loose wires or hoses,
er
and missing anti-chafe guards. Tighten fasteners to the correct torque value. Replace
missing caps. Install the required wire and hose supports.
op
2.B.i.f. Tires
Check tire pressure and inflate as necessary. Correct tire pressure is 85 psi (cold).
Pr
Ensure that all lubrication fittings have been serviced. Refer to Chapter 2, Section 1,
Paragraph [Link] 1.B. for lubrication points and recommended lubricants.
Check compressor and blower alignment. Refer to Chapter 3, Section 4, Paragraph 7 for
alignment procedure.
Check the refrigerant charge level. The receiver liquid level gauge should indicate
between ½ and ¾ full with the refrigerant charge pumped down. Refer to Chapter 2,
Section 1, Paragraph K.4 for refrigerant charging procedure.
s
NOTE:
ne
The refrigeration system is prepared for shipment by isolating the
maximum amount of the refrigerant charge in the receiver tank.
rli
Ai
CAUTION:
an
TO AVOID DAMAGE TO THE COMPRESSOR FROM INADEQUATE
LUBRICATION, ENSURE THAT THE SEPARATOR TANK SHUT
ic
OFF VALVE (V13) IS OPENED PRIOR TO UNIT OPERATION.
er
Open the refrigerant receiver tank rotolock valves (V17, V42) fully once charge level is
Am
established to be good.
Leak check the refrigeration system following the instructions provided in Chapter 3,
Section 4, Paragraph 3. Refer to the leak detection instrument manufacturer’s literature in
Chapter 5 for operating instructions.
ty
This section covers steps that must be taken, prior to placing the unit in service following
op
storage. The steps for placing the unit into service after shipment should be followed after these
before placing the unit into service, see the previous section.
Pr
[Link].a. Preservatives
Preservative oils and compounds not designed to dissipate during unit operation must be
drained or flushed from the unit prior to operation.
[Link] Belts
When belt tension has been relieved to reduce deterioration and stretching during storage,
belts must be retensioned prior to operation. Refer to the engine manufacturer’s
instructions contained in Chapter 5 for re-tensioning the drive belts.
Creation:05-04-2012 1-2-4
[Link]. Preparation for Use at Various Altitudes or in Temperature Extremes
Prepare the unit as described in use after shipment
Fill the engine crankcase with lubricating oil of the recommended SAE viscosity grade for the
expected ambient temperature conditions. Refer to the engine manufacturer’s operation manual
contained in Chapter 5.
Adjust the engine coolant concentration as required to prevent freezing at the lowest expected
temperature. Check the coolant concentration using a commercial temperature corrected
spectrometer calibrated for ethylene-glycol base antifreeze.
If the engine is equipped with optional ether starting aid, ensure that a full dispenser of starting
fluid is installed when operating the unit in low ambient temperatures.
s
ne
When operating the unit at high altitudes (over 3,281 ft. above sea level), it will be necessary to
reduce the injected fuel quantity, reducing engine power. Consult the engine manufacturer’s
instructions for derating the engine whenever operating the unit at altitudes over 3,281 ft. (1,000
rli
m) above sea level.
Ai
2.C. Required Equipment
The following accessory equipment is necessary to permit connection of the unit hose outlet(s) to the
an
aircraft conditioned air inlet(s).
supplied in 30-ft. and 40-ft. lengths. Hose assemblies consist of a male coupler ring with turn
catch latches for attachment to the unit conditioned air outlet; a round or lay flat 12-inch I.D.
retractable duct hose; hose clamps; and quick connect/disconnect hose coupler assembly.
Hoses may be connected using aluminum sleeves in multiple sections for remote air delivery.
of
2.C.i.a. Hose
The air delivery duct hose is constructed of fire resistant non-permeable fabric with scuff
ty
strip, and transition section to 8-inch I.D. cuff. The duct is designed for outdoor use in all
types of weather including damp, salt-laden air for extended periods of time. The hose
er
may be handled in any direction with a minimum crimping of fabric. The internal surface
of the duct is constructed to minimize air friction losses and leakage.
op
Pr
s
ne
rli
Ai
3
an
2
ic
er
1
Am
of
ty
1......Quick-disconnect coupler
er
2......Hose clamp
3......Duct hose
op
4......Male coupler
Pr
Creation:05-04-2012 1-2-6
2.C.i.b. Quick Disconnect Coupler (See Figure 37)
An 8-inch coupler is required to connect the air delivery hose duct to the aircraft
conditioned air inlet. The hose to aircraft coupler clamped to the end of the hose is a
quick connect/disconnect assembly of all stainless steel construction matching the
industry standard specification (MS33562) for aircraft 8-inch conditioned air connectors.
The coupling consists of a stainless steel body and sliding ring, opposed loop handles,
adjustable hook latches, locking levers, and compression springs. The handles aid
pushing the steel coupling hooks into the slots of the aircraft connector ring. The slots are
located 180 degrees apart on 9-1/8 in. centers. The coupler is twisted ¼-turn to engage
the connector ring; then clamped into position tightly using the spring loaded locking
levers. A replaceable neoprene gasket seals the circumference of the connector.
s
The following sizes are offered:
ne
ACE-277-004 8-inch coupler for connection to duct hose, with 12-8 inch transition cuff
ACE-277-804 8-inch coupler for direct connection to 12-inch duct hose.
rli
2.C.i.c. Hose Coupler (See Figure 38)
Ai
Clamped stainless steel sleeves are available for connecting hose lengths of the same
diameter. Male coupler Part No.1003415 and female coupler Part No.1003414 are
available in various sizes. When multiple 12-inch hose lengths are to be joined in series
an
for remote air delivery, a Part No.1003414-6 female coupler and Part No.1003415-6 male
coupler are required for each joint.
ic
er
Am
of
ty
er
op
Pr
1
5
s
ne
6
rli
COUPLER
Ai
P/N 1003414-6
1
an 3
ic
2
er
4
Am
5
of
ty
6
1 ..... Body
er
4 ..... Handles
5 ..... Gasket
6 ..... Latch
Pr
QUICK-DISCONNECT COUPLER
FIGURE 37
Creation:05-04-2012 1-2-8
ACE P/N 1003415
MALE COUPLER
s
ne
rli
Ai
ACE P/N 1003414
an
ic
er
Am
HOSE SIZE
MALE COUPLER FEMALE COUPLER
I.D. IN.
4 1003415-1 1003414-1
of
5 1003415-2 1003414-2
ty
6 1003415-3 1003414-3
8 1003415-4 1003414-4
er
10 1003415-5 1003414-5
op
12 1003415-6 1003414-6
14 1003415-7 1003414-7
Pr
16 1003415-8 1003414-8
18 1003415-9 1003414-9
HOSE COUPLER
FIGURE 38
s
38027 Gauge manifold
ne
40012 Charging hose, ¼ in. I.D.
rli
40084 Charging hose, 3/8 in. I.D.
40085 Adapter, ¾ in. straight pipe X 3/8 in. SAE 45 degree flare
Ai
57355 Adapter, 3/8 in. straight pipe X ¼ in. SAE 45 degree flare
an
40095 Refrigeration ratchet wrench
1008641 Leak detector ic
er
Am
of
ty
er
op
Pr
Creation:05-04-2012 1-2-10
The following basic equipment and instruments are necessary for satisfactory unit maintenance.
s
HI-300 Electric Halogen leak detector (V64615)
ne
rli
2.D. Operation
Ai
2.D.i. A. Pre-start Inspection
an
Perform the following checks prior to each use:
ic
Ensure that the battery pack is adequately charged.
er
Check the parking brake for proper operation. Ensure that the parking brake lever is engaged to
prevent unit movement.
Am
The fuel gauge should indicate at or near full (“F”). Drain accumulated water from the fuel
filter/water separator.
ty
Check engine coolant level. Add coolant to the recovery bottle as required.
op
If the unit is being operated indoors, ensure that exhaust fumes are discharged outdoors to
Pr
prevent accumulation of carbon monoxide gas. Ensure that windows or vents are open to
provide sufficient ventilation for the engine and operating personnel when the unit is being
operated indoors.
NOTE:
Ensure that hearing protection conforms to NIOSH or OSHA
s
standards for personal protective equipment. Earplugs should
ne
be worn in combination with dielectric earmuffs.
rli
[Link] Starting and Operating Procedure
Ai
Before using this unit, refer to Figure 39 for the instrument panel layout. Ensure you are familiar
with the controls and instruments before attempting to operate the unit. The following section
an
describes the layout of the control panel and function of each instrument.
[Link].a. Unit control panel layout and description (see Figure 39)
ic
er
[Link].a.1. Control System Display/Menu
This is the screen the personnel will interact with when using the unit. It will display
the home screen by default at power on.
Am
[Link].a.3. OK Button
Turns on/confirms selection on the menu.
ty
Pressing the button while the engine is running will cause the unit to turn off the
engine after running a cooldown cycle and then turn off the machine.
s
ne
Control System Display/Menu Menu Buttons, UP and DOWN
rli
Engine Information Display
Ai
an
ic
er
Am
of
Emergency Stop
s
[Link].b.3. Heat / Cool
ne
When the aircraft probe is not deployed, the operator can select heating or cooling
mode via a similar process to selecting the aircraft being serviced.
rli
[Link].b.4. Fuel Level
Remaining fuel in the tank is shown on a scale of 100% (Full) to 0% (Empty).
Ai
[Link].b.5. Bias
an
This is a number raging from -10 to 10 and is the only operator input on unit
capacity. When the unit is operating, this is the only adjustment the operator can
make to the unit. If the cabin is too warm, the operator can place a negative (-) bias
ic
on the unit to command a cooler cabin temperature. Likewise, if the cabin is too
cool, the operator can place a positive bias on the unit to command a warmer cabin
er
temperature. This feature is available with and without the aircraft probe in use.
The status of having a probe connected to the unit or not is shown via the graphic.
When the icon is crossed out, the probe is either not connected, or there is a
problem with probe or its connections. When the icon is not crossed out, the probe
is connected correctly and the unit will automatically use it in controlling the
of
Creation:05-04-2012 1-2-14
Unit Model
Probe / No
s
Probe
ne
rli
Aircraft Selection
Ai
Heat/Cool
an
ic
Bias Fuel Level
er
UNIT CONTROL PANEL
Am
FIGURE 40
of
ty
er
op
Pr
Before starting the unit, it is imperative the hose(s) is (are) connected to the aircraft being
serviced. Perform the following:
Inspect the conditioned air coupler on the delivery hose for damaged or missing seal, and
proper operation.
Remove the air delivery duct hose from the unit hose storage compartment, grasp the
coupler, and extend the hose to the aircraft. Couple multiple hose sections if remote
servicing is being conducted.
s
Open air outlet damper fully for each hose connected to the aircraft.
ne
rli
NOTE:
Ai
Inspect hose condition before each use. If torn or punctured,
the duct fabric can be repaired. Deformed stiffener can be
manually restored to its original contour. Replace severely
an
damaged or leaking hose.
ic
[Link] Operation (See Figure 41)
er
1. Press and hold the power on/off button (I/O) for 4 seconds, release the button when the
button illuminates. Allow the onboard controller to boot up.
Am
2. Use the up (↑) and down (↓) keys to move the selection box on the screen to the aircraft
type, and press the OK button (√).
of
3. Use the up (↑) and down (↓) keys to select the aircraft type connected to the unit, and
press the OK button (√).
ty
[Link] not using the unit probe, move the selection box using the up (↑) and down (↓) keys
to the lower right corner selection box. Press the OK button (√) and use the up (↑) and
down (↓) keys to select cooling (↓) or heating (↑) on the screen. Press the OK button (√).
op
[Link] the engine start/stop button, it will blink, and the engine will be cranked
automatically to start. After the engine has started, the start/stop button will continue to
Pr
blink, and the engine will idle in warm-up mode for 2 minutes.
6. The unit will automatically control the engine speed and outlet temperature as needed
to keep the airplane at the correct temperature. If the airplane becomes too cold or too
warm, use the up and down keys while the unit is operating to adjust the temperature bias,
with -10 commanding the unit for a much colder cabin and 10 commanding the unit for a
much warmer cabin. While the unit is operating, verify the engine coolant temperature,
and the system voltage are in normal operating ranges.
Creation:05-04-2012 1-2-16
7. When aircraft servicing is complete, press the engine start/stop button to stop the
engine, or press the power on/off button (I/O) to stop the engine and turn the unit main
power off after the engine stops. The start/stop button will blink and the unit will idle the
engine in a cooldown mode for 2 minutes and shut off automatically.
During the operation of the unit, various sensors and switches are monitored to ensure the
unit is operating correctly. The unit will automatically shut itself down, and set a fault code
if any of the operating parameters exceed safe limits. The fault code will be displayed on
the unit display along with a short description. The fault code chart can be found with the
schematics of the unit. Further diagnosis of fault codes can be found in the
troubleshooting section of Chapter 2 of this manual. Press the OK key to reset a fault
s
code, which will then allow the unit to be restarted.
ne
[Link].f. Emergency Shutdown
rli
In the event of an emergency situation, immediate engine shut down may be
accomplished by pushing in the emergency stop button on the instrument panel.
Ai
The unit control power will remain on, and a fault message will be displayed. The
fault will need to be reset before the unit can be restarted.
an
CAUTION: ic
NEVER USE THE EMERGENCY STOP SWITCH FOR NORMAL
UNIT SHUTDOWN. REDUCED LIFE OF THE ENGINE
er
TURBOCHARGER AND OTHER COMPONENTS WILL OCCUR.
Am
of
ty
er
op
Pr
s
ne
rli
Ai
Stop the Engine
an
7
ic
1 5
er
Turn Power On Start the Engine
Am
of
Automatic –
Uses it only if the
ty
probe is connected.
This is a feedback
er
only.
op
2 3 4
Select Aircraft
Pr
4a Select Heating
or Cooling
UNIT OPERATION
FIGURE 41
Creation:05-04-2012 1-2-18
3. Specifications and Capabilities
3.A. ACU-802-Trailer
Length overall (towbar extended) 224 in.
Width overall .. 94 in.
Height overall 101in.
Weight 14,000 lbs.
3.B. ACU-802-Skid
Length overall 164 in.
s
Width overall 94 in.
Height overall 86 in.
ne
Weight* 12,000 lbs.
*Excluding the curb weight of the truck.
rli
See Figure 46 for more information
Ai
an
ic
er
Am
of
ty
er
op
Pr
ACU-802 DIMENSIONS
FIGURE 46
(1 OF 3)
Creation:05-04-2012 1-3-2
s
ne
rli
Ai
an
ic
er
Am
of
ty
er
op
Pr
ACU-802 DIMENSIONS
FIGURE 46
(2 OF 3)
ACU-802 DIMENSIONS
FIGURE 46
(3 OF 3)
Creation:05-04-2012 1-3-4
4. Shipping
4.A. Domestic Shipment
The instructions provided below for preservation of the unit and packaging of equipment applies to
equipment intended for immediate use after domestic shipment from supply source to first receiving
station. This level of preservation and packaging is designed to protect material from physical damage
and deterioration during favorable conditions of shipment, limited handling, and short-term storage.
4.A.i. Equipment Preparation
4.A.i.a. Engine
1. Drain the engine crankcase, replace the oil filter, and refill the crankcase to the proper
s
level with the recommended viscosity and grade of oil suitable for engine operation in the
ambient temperatures expected at the shipping destination. Refer to the engine
ne
manufacturer’s operation manual in Chapter 5. Operate the engine for two minutes to
allow the fresh oil to circulate in the engine.
rli
2. Clean or replace the engine air filter.
Ai
3. If the engine cooling system will not be drained for shipment, check engine coolant level
and fill as required with 50% ethylene glycol base antifreeze and fresh water solution. If
engine coolant will be drained, position a suitable size container under the drain port
an
located at the front of the engine adjacent to the water pump inlet and open the drain
valve. Remove the cap from the expansion tank to facilitate drainage. Leave the drain
valve open.
ic
er
NOTE:
Am
cap installed to purge air from the system. Install the cap after
coolant level has stabilized at the bottom of the expansion tank
ty
CAUTION:
TO AVOID POSSIBLE PERSONAL INJURY WHEN USING
COMPRESSED AIR, WEAR ADEQUATE EYE PROTECTION. DO
NOT EXCEED 40 PSI (276 kPa) AIR PRESSURE.
s
ne
5. Seal all engine openings using a strong water and vapor proof tape.
rli
CAUTION:
Ai
DO NOT INSTALL CHAINS OR STRAPS OVER FUEL LINES,
ELECTRICAL WIRES, CABLE, OR COMPONENTS.
an
4.A.i.b. Refrigerant
ic
The refrigeration system is prepared for shipment by isolating the maximum amount of the
er
refrigerant charge in the receiver tank. This prevents a large volume of refrigerant from
escaping into the atmosphere in the event that leakage occurs due to rough handling or
Am
Check the compressor oil level in the separator tank. Fill the tank as required with Solest
68 (CPI) compressor oil only. Fill the oil separator tank in accordance with the instructions
provided in Chapter 2
ty
Ensure that the batteries are clean and dry; check the electrolyte level in each cell and fill
as necessary with fresh demineralized water; and ensure that the batteries are fully
op
charged. Battery posts shall be covered with plastic caps or high dielectric strength tape.
Leave the batteries hooked up with the battery switch in the ‘off’ position.
Pr
Creation:05-04-2012 1-4-2
[Link]. Pre Shipment Documentation
Whenever a component or system is deactivated or disabled for shipment, a notice that identifies
the procedure and provides instructions to the end user for reactivation shall be displayed on the
cart instrument panel and a duplicate copy provided to the shipper for attachment to shipping
documents.
[Link]. Shipping
1. Refer to Chapter 1, Section 3, Figure 46 for unit weight and center of gravity. Position the unit
on the transporting vehicle on which it will be shipped.
2. Block up the axles under the springs to remove the load from the tires.
3. Tie axles securely to the shipping vehicle.
s
4. Block up the spring carriers to prevent the unit from shifting.
5. Tie the spring carriers securely to the deck.
ne
6. If the unit is to be shipped on a flat rack or in an open container exposed to salt water spray,
apply a commercial corrosion preventive compound to exposed surfaces and shrink wrap the
unit.
rli
[Link]. Boxed or Palletized Equipment
Ai
[Link].a. Preservation and Packaging
All accessory equipment, component parts, repair parts, tools, and publications shall be
an
preserved and packaged to prevent loss, physical, or mechanical damage due to handling
during shipment, loading, or unloading from pilferage; and from deterioration, including the
corrosive action of water or polluted air and other environmental elements.
ic
Packing
All parts removed by disassembly shall be match-marked or labeled to identify installation
er
location. Installation instructions shall be packed with the removed assemblies to aid
reassembly and reinstallation.
Am
Follow the procedures described in covering preparation of the unit for domestic shipment.
er
If using an open deck or open container shipment: The exposed surfaces of equipment shipped
open deck on cargo vessels shall be protected by a commercial corrosion preventive compound
op
2......Chock, wheel
ty
er
SHIPPING ARRANGEMENT
FIGURE 47
op
Pr
Creation:05-04-2012 1-4-4
4.C. Storage
Accessory equipment shall be adequately protected during storage periods from physical or mechanical
damage due to handling, from pilferage of unit parts or components, and from deterioration, including
the corrosive action of water or polluted air and other environmental elements.
Packing of parts and equipment shall be accomplished using acceptable preservation materials,
containers, and processes based on material composition, surface finish, size, weight, fragility,
configuration, and intended level of protection. Packages and containers shall be uniformly marked to
identify contents and installation location.
NOTE:
s
ne
Consult the manufacturer’s literature contained in Chapter 5 for
further information on component assembly storage.
rli
4.C.i. Short Term Storage
Ai
The instructions provided below for preservation of the unit and packaging of equipment applies
to units intended for storage outdoors for up to 90 days.
an
4.C.i.a. Equipment Preparation
4.C.i.a.1. Engine
ic
1. Drain and flush the cooling system following the engine manufacturer’s
er
instructions. Refill the cooling system with clean, soft water and add an approved
corrosion inhibitor to the cooling system.
Am
2. Operate the engine without the expansion tank pressure cap installed to bleed air
from the system. Then install the cap and operate the engine until normal
temperature is reached (thermostat open) to assure a complete mixing and
thorough distribution of the corrosion inhibitor. Then shut off the engine. Fill the
of
3. Drain the engine crankcase, replace the oil filter, reinstall and tighten the oil drain
ty
plug.
er
4. Fill the crankcase to the proper level with a 30 weight preservative lubricating oil
meeting the requirements of MIL-L-21260C, Grade 2.
op
5. Drain the fuel tank. Refill with enough clean diesel fuel to permit approximately
10 minutes of engine operation.
Pr
6. Drain the fuel system and remove the fuel filters. Fill replacement filters with
clean diesel fuel.
[Link] the engine for five minutes to circulate the clean fuel oil throughout the
engine. Ensure that the engine fuel system is full. Disconnect and plug the fuel
return line and inlet line at the primary filter to retain the fuel in the engine.
s
PRESERVED: DO NOT CRANK.”
ne
4.C.i.a.2. Refrigerant
The refrigeration system is prepared for shipment by isolating the maximum amount
rli
of the refrigerant charge in the receiver tank. This prevents a large volume of
refrigerant from escaping into the atmosphere in the event that leakage occurs due
Ai
to rough handling or accident. Pump down the refrigerant charge following the
procedures described in Chapter 2.
an
4.C.i.a.3. Power Take Off
Ensure that the power take off is properly lubricated. Refer to Chapter 2.
ic
4.C.i.a.4. Batteries
If vehicle storage will be under 90 days, the batteries may be left in place in the unit.
er
Ensure that the batteries are clean and dry; and that the batteries are fully charged.
The battery posts shall be covered with plastic caps or high dielectric strength tape.
Am
Disconnect the main power cables from the positive and negative terminals of the
battery pack.
Ensure that all covers, viewports, portholes, access panels, and doors are in place,
closed, and secure. Lubricate the steering gear and tow bar. Refer to Chapter 2 for
lubricant specifications.
ty
Check tire air pressure and fill to the specified pressure. Ensure that all valve stem
caps are in place and tight. Refer to stencil or sticker near each tire for correct
pressure.
op
All preservatives, packing materials, and containers shall be adequate to provide the
degree of protection required corresponding to the known or anticipated storage
conditions. Stow all loose components in a properly equipped box.
Creation:05-04-2012 1-4-6
[Link] Term Storage
The instructions provided below for preservation of the unit and packaging of equipment applies
to units intended for storage outdoors for over 90 days. Prepare the unit in accordance with the
instructions provided in the previous section in with the following exceptions.
[Link].a. Equipment Preparation
[Link].a.1. Wheels and Tires
If the unit will be stored outdoors for over 90 days, block up the axles under the
springs to remove all load from the tires, and reduce tire pressure to 10 psi.
[Link].a.2. Refrigeration System
Long term storage will necessitate recovery of the refrigerant charge from the unit
s
and system evacuation. Recovery refers to the removal of HFC-134a from the
using equipment and collection in an appropriate external container. Recovery does
ne
not involve processing or analytical testing, although these additional procedures
may be required. Refrigerant HFC-134a may be recovered using permanent on-site
equipment or portable recovery units. At the completion of the recovery cycle, the
rli
system is evacuated to remove vapors.
Ai
NOTE:
an
Ensure that recovery equipment has elastomeric seals and a
compressor compatible with HFC-134a.
ic
CAUTION:
er
WARNING:
ty
NOTE:
Use only new lubricant to replace the amount removed during
the recovery process. A sample of refrigerant shall be taken to
determine the level of moisture and noncondensable particle
contamination. Contaminated refrigerant shall be cleaned using
appropriate recycling equipment.
s
2. Remove the plugs from the inlet and outlet of the fuel lines and reconnect the lines to
their proper mating fittings.
ne
3. Wash the exterior of the engine with the fuel oil to remove the rust preventive coating.
4. Remove the paper strips from between the pulleys and drive belts.
rli
NOTE:
Ai
Check for serviceable drive belts. Install a new drive belt if
required. Adjust belt tension in accordance with the engine
an
manufacturer’s instructions.
5. Fill the crankcase to the proper level with the required grade of lubricating oil. Use a
ic
pressure lubricator to ensure that all bearings and rocker shafts are lubricated.
er
NOTE:
Am
6. Fill the fuel tank with fresh, clean diesel fuel of the recommended grade.
7. Close all drain cocks and fill the engine cooling system through the filler neck at the top
ty
of the expansion tank with a solution of 50% ethylene glycol antifreeze and fresh, soft
water.
er
8. Remove the batteries from storage. Install the batteries and reconnect the cables. Load
test the batteries to check for satisfactory condition. Recharge the batteries if necessary.
9. Remove the covers from the turbocharger air inlet and turbine outlet connections.
op
12. Operate the engine until warm. Monitor the oil pressure and coolant temperature
gauges closely during engine warm up.
Creation:05-04-2012 1-4-8
[Link].b. Wheels and Tires
Remove blocks from the chassis and fill tires to the specified air pressure.
[Link].c. Refrigeration System
1. Recharge the system with fresh or reclaimed R-134a refrigerant if the charge was
removed for long term storage.
2. If the storage period was short term and the refrigerant charge was not recovered, open
the receiver rotolock valves to release stored refrigerant into the system.
3. Leak check the refrigeration system following the instructions provided in Chapter 3.
WARNING:
s
UNDER NO CIRCUMSTANCES SHOULD THE REFRIGERATION
ne
SYSTEM BE PRESSURE TESTED OR LEAK TESTED WITH AIR
AND HFC-134a MIXTURES. NEVER USE COMPRESSED (SHOP)
rli
AIR FOR LEAK DETECTION IN HFC-134a SYSTEMS.
PRESSURIZED CONCENTRATIONS OF HFC-134a REFRIGERANT
Ai
AND AIR GREATER THAN 60% BY VOLUME MAY BE
COMBUSTIBLE.
an
NOTE: ic
Use a compound-specific leak detector sensitive only to R-134a
vapor if possible.
er
Am
CAUTION:
BEFORE USING A DYE TO LEAK CHECK THE SYSTEM,
of
CAUTION:
s
DO NOT OPEN PARTS OR COMPONENTS PACKED IN SEALED
ne
MOISTURE/VAPOR PROOF PACKAGING OR IN
ELECTROSTATICALLY SHIELDED PACKAGING UNTIL READY
FOR INSTALLATION OR USE.
rli
Ai
WARNING:
an
AVOID DIRECT CONTACT WITH VOLATILE CORROSION
INHIBITORS. THE ACTIVE CHEMICAL COMPOUNDS USED IN
THESE INHIBITORS MAY BE SKIN OR EYE IRRITANTS.
ic
er
Am
of
ty
er
op
Pr
Creation:05-04-2012 1-4-10
The compressor serves multiple functions in the refrigeration system. It pressurizes and circulates the refrigerant gas through the system, facilitating heat exchange . The compressor is of the positive displacement rotary screw type and operates with a fixed volume ratio, optimizing efficiency by preventing overcompression. It employs a slide valve for stepless capacity control, allowing it to unload to 25% of full load capacity . This regulation of capacity is crucial to maintain the desired supply air temperature amidst varying ambient conditions . Furthermore, vapor injection helps "supercharge" the compressor by injecting vapor at a higher pressure, enhancing cooling capacity .
The slide valve is integral to managing the compressor’s capacity in the refrigeration cycle. It enables stepless capacity control by adjusting the volume of refrigerant vapor delivered to the rotors. This allows the compressor to adapt to varying load demands, maintaining efficiency by unloading to 25% of full load capacity without shutting down. The hydraulically actuated slide valve is controlled by a solenoid valve, which is regulated by a programmable logic controller (PLC) based on pressure feedback from the system. This precise control mechanism not only optimizes performance but also conserves energy under different operational conditions .
Filters and driers are critical components that enhance the reliability and longevity of a refrigeration system by removing contaminants from the refrigerant before they can cause damage. They trap non-condensable elements and separate or absorb moisture from the refrigerant charge. By preventing the formation of acids through hydrolysis, particularly hydrochloric and hydrofluoric acids that can corrode system components, filters prolong system life and ensure efficient operation . Proper filtration prevents blockages and enhances system performance under varying conditions .
The evaporator plays a critical role in both the heating and cooling modes of a refrigeration cycle by absorbing heat from the surrounding environment. In the cooling mode, the inside coil acts as the evaporator where the liquid refrigerant absorbs heat from the supply air and evaporates at a low temperature . In the heating mode, the outside coil functions as the evaporator, where the liquid refrigerant absorbs heat from the ambient air and evaporates at a low temperature . This absorbed heat is then carried by the refrigerant gas back to the compressor, completing the cycle.
Failure to properly prepare exhaust outlets for indoor operation of refrigerated units can lead to the accumulation of carbon monoxide gas, posing severe health risks and potential for asphyxiation to operating personnel . Proper ventilation is mandatory to discharge exhaust fumes outdoors, which helps prevent dangerous build-up of fumes in confined spaces. Ensuring window or vent openings is essential to provide adequate airflow and protect against toxic exposures in indoor settings . Non-compliance with these guidelines could result in personal safety hazards, legal liabilities, and equipment malfunction.
Compressor capacity control is vital for maintaining desired air temperatures under varying ambient conditions by dynamically adjusting the compressor’s output. This is achieved through a hydraulically actuated slide valve that regulates the volume of refrigerant vapor being compressed and circulated . The capacity control system, guided by a programmable logic controller (PLC), responds to changes in system demand by adjusting the load on the compressor, thus preventing overcooling or inefficiencies. The system’s ability to modulate based on pressure feedback ensures precise temperature regulation, improving energy efficiency and system stability .
The refrigerant receiver tank plays a crucial role in the efficiency and safety of the refrigeration system by storing the refrigerant charge during idle times or service operations, ensuring a steady supply of refrigerant to meet variable heat loads . It is built to withstand high pressures, with a maximum working pressure of 400 psig, and includes features like a liquid level float gauge and safety pressure relief valve to prevent overpressure situations . This reservoir design prevents escape of refrigerant to the environment, minimizing leakage risks and contributing to the system’s reliability .
To prepare a refrigeration unit for long-term storage, several measures are advised: Ensure the refrigerant charge is maximally contained within the receiver tank to prevent leaks . The wheels and tires should be relieved of load by blocking up the axles and reducing tire pressure to approximately 10 psi . All engine openings are sealed, and a corrosion preventive compound is applied to protect the engine. Additionally, the engine cooling system and preservative oil should be drained, and the entire unit should be lubricated, cleaned, and securely boxed if possible .
The thermal expansion valve (TEV) facilitates the vapor injection process by regulating the flow of refrigerant to the vapor injection coil within the evaporator. This valve maintains a specific superheat range of 10°F to 15°F to ensure that no liquid refrigerant enters the compressor, which could cause damage. By "supercharging" the compressor through the introduction of vapor at higher pressure than the suction, the TEV increases the cooling capacity of the system, allowing it to achieve greater efficiency and performance . This process optimizes energy use and extends compressor life by reducing stress during operation.
Ambient temperature and altitude significantly affect the air delivery system of the refrigerated unit. While the volume of air delivered by the fans and blower is not affected by air density changes, both delivery pressure and mass flow rate vary directly with air density . At higher altitudes, the reduced air density results in decreased delivery pressure and mass flow rate, potentially impacting the system’s performance. Moreover, extreme temperatures necessitate adaptations such as cold weather starting kits to maintain optimal operation .