BATTERY SIZING CALCULATION
Customer Name :
Battery Type : 6EL+
UPS Data
UPS RATING (in KVA) 6 kVA
P.F 0.8
Kilowatt 4.8 KW
Watt 4800 W
UPS O/Put Watt 4800 W
Efficiency 0.95
Battery O/Put Watt 5052.63 W
No. of Cells and ECV SYSTEM VOLTAGE
Max. DC Voltage 230.4 V
Max. charging voltage 2.4 V Volt / Battery No. of Battery System Voltage
No. of Cells 96.0 nos. Boost VPC 2.4
Actual No. of Cells required 96 nos. No. of cell / battery 6
Min. DC Voltage 168 V 14.4 16 230.4 MAX
e.c.v. 1.75 V
Max. System Current 30.075 Amp Cut off VPC 1.75
Duration (min.) 30 mins. No. of cell / battery 6
K - factor 1.41 10.5 16 168 MIN
Maximum Section Size 42.406 Ah
Considering Temp. correction factor 1 (Considering 27 deg C)
Considering Design Margin 1.1
Considering Ageing factor 1.25
Estimated Battery Size 58.31
Number of battery (12V) / String ::
Number of string (max) 1
C10 Required of battery 58
Selected Battery 16 no's of 6EL60 of battery banks for 30 min Back up.
K-FACTOR FOR 12 TUBULAR FLOODED
ECV 1 Min. 5 Min. 10 Min. 15 Min. 20 Min. 30 Min. 45 Min. 1 HR 2 HR 3 HR 4 HR 5 HR 6 HR 7 HR 8 HR 9 HR 10 HR
1.7 0.70 0.77 0.90 1.02 1.12 1.24 1.57 1.90 2.88 3.79 4.69 5.45 6.08 6.68 7.46 8.10 9.13
1.75 85.02 0.93 1.07 1.17 1.29 1.41 1.73 1.96 2.94 3.86 4.76 5.54 6.16 6.76 7.55 8.17 9.20
1.8 1.09 1.18 1.31 1.41 1.53 1.67 1.96 2.27 3.23 4.15 5.01 5.80 6.41 7.10 7.84 8.49 9.40
1.85 1.57 1.64 1.72 1.78 1.96 2.12 2.30 2.76 3.77 4.67 5.46 6.32 7.13 7.89 8.47 9.09 9.80
1.9 2.51 2.51 2.63 2.67 2.74 2.94 3.19 3.61 4.60 5.49 6.31 7.17 8.23 8.99 9.39 10.00 10.41
For Exide Industries Limited
Authorised Signatory
BATTERY SIZING CALCULATION
Customer Name :
Battery Type : 6EL+
UPS Data
UPS RATING (in KVA) 10 kVA
P.F 0.8
Kilowatt 8 KW
Watt 8000 W
UPS O/Put Watt 8000 W
Efficiency 0.95
Battery O/Put Watt 8421.05 W
No. of Cells and ECV SYSTEM VOLTAGE
Max. DC Voltage 230.4 V
Max. charging voltage 2.4 V Volt / Battery No. of Battery System Voltage
No. of Cells 96.0 nos. Boost VPC 2.4
Actual No. of Cells required 96 nos. No. of cell / battery 6
Min. DC Voltage 168 V 14.4 16 230.4 MAX
e.c.v. 1.75 V
Max. System Current 50.125 Amp Cut off VPC 1.75
Duration (min.) 60 mins. No. of cell / battery 6
K - factor 1.96 10.5 16 168 MIN
Maximum Section Size 98.246 Ah
Considering Temp. correction factor 1 (Considering 27 deg C)
Considering Design Margin 1.1
Considering Ageing factor 1.25
Estimated Battery Size 135.09
Number of battery (12V) / String ::
Number of string (max) 1
C10 Required of battery 135
Selected Battery 16 no's of 6EL150 of battery banks for 60 min Back up.
K-FACTOR FOR 12 TUBULAR FLOODED
ECV 1 Min. 5 Min. 10 Min. 15 Min. 20 Min. 30 Min. 45 Min. 1 HR 2 HR 3 HR 4 HR 5 HR 6 HR 7 HR 8 HR 9 HR 10 HR
1.7 0.70 0.77 0.90 1.02 1.12 1.24 1.57 1.90 2.88 3.79 4.69 5.45 6.08 6.68 7.46 8.10 9.13
1.75 85.02 0.93 1.07 1.17 1.29 1.41 1.73 1.96 2.94 3.86 4.76 5.54 6.16 6.76 7.55 8.17 9.20
1.8 1.09 1.18 1.31 1.41 1.53 1.67 1.96 2.27 3.23 4.15 5.01 5.80 6.41 7.10 7.84 8.49 9.40
1.85 1.57 1.64 1.72 1.78 1.96 2.12 2.30 2.76 3.77 4.67 5.46 6.32 7.13 7.89 8.47 9.09 9.80
1.9 2.51 2.51 2.63 2.67 2.74 2.94 3.19 3.61 4.60 5.49 6.31 7.17 8.23 8.99 9.39 10.00 10.41
For Exide Industries Limited
Authorised Signatory
BATTERY SIZING CALCULATION
Customer Name :
Battery Type : 6EL+
UPS Data
UPS RATING (in KVA) 40 kVA
P.F 0.8
Kilowatt 32 KW
Watt 32000 W
UPS O/Put Watt 32000 W
Efficiency 0.96
Battery O/Put Watt 33333.33 W
No. of Cells and ECV SYSTEM VOLTAGE
Max. DC Voltage 662.4 V
Max. charging voltage 2.4 V Volt / Battery No. of Battery System Voltage
No. of Cells 276.0 nos. Boost VPC 2.4
Actual No. of Cells required 276 nos. No. of cell / battery 6
Min. DC Voltage 483 V 14.4 46 662.4 MAX
e.c.v. 1.75 V
Max. System Current 69.013 Amp Cut off VPC 1.75
Duration (min.) 120 mins. No. of cell / battery 6
K - factor 2.94 10.5 46 483 MIN
Maximum Section Size 202.899 Ah
Considering Temp. correction factor 1 (Considering 27 deg C)
Considering Design Margin 1.1
Considering Ageing factor 1.25
Estimated Battery Size 278.99
Number of battery (12V) / String ::
Number of string (max) 2
C10 Required of battery 139
Selected Battery 46 no's of 6EL150 of two battery banks for 120 min Back up.
K-FACTOR FOR 12 TUBULAR FLOODED
ECV 1 Min. 5 Min. 10 Min. 15 Min. 20 Min. 30 Min. 45 Min. 1 HR 2 HR 3 HR 4 HR 5 HR 6 HR 7 HR 8 HR 9 HR 10 HR
1.7 0.70 0.77 0.90 1.02 1.12 1.24 1.57 1.90 2.88 3.79 4.69 5.45 6.08 6.68 7.46 8.10 9.13
1.75 85.02 0.93 1.07 1.17 1.29 1.41 1.73 1.96 2.94 3.86 4.76 5.54 6.16 6.76 7.55 8.17 9.20
1.8 1.09 1.18 1.31 1.41 1.53 1.67 1.96 2.27 3.23 4.15 5.01 5.80 6.41 7.10 7.84 8.49 9.40
1.85 1.57 1.64 1.72 1.78 1.96 2.12 2.30 2.76 3.77 4.67 5.46 6.32 7.13 7.89 8.47 9.09 9.80
1.9 2.51 2.51 2.63 2.67 2.74 2.94 3.19 3.61 4.60 5.49 6.31 7.17 8.23 8.99 9.39 10.00 10.41
For Exide Industries Limited
Authorised Signatory
K-FACTOR FOR 12 TUBULAR FLOODED
ECV 1 Min. 5 Min. 10 Min. 15 Min. 20 Min. 30 Min. 45 Min. 1 HR 2 HR 3 HR 4 HR 5 HR 6 HR 7 HR 8 HR 9 HR 10 HR
1.7 0.70 0.77 0.90 1.02 1.12 1.24 1.57 1.90 2.88 3.79 4.69 5.45 6.08 6.68 7.46 8.10 9.13
1.75 85.02 0.93 1.07 1.17 1.29 1.41 1.73 1.96 2.94 3.86 4.76 5.54 6.16 6.76 7.55 8.17 9.20
1.8 1.09 1.18 1.31 1.41 1.53 1.67 1.96 2.27 3.23 4.15 5.01 5.80 6.41 7.10 7.84 8.49 9.40
1.85 1.57 1.64 1.72 1.78 1.96 2.12 2.30 2.76 3.77 4.67 5.46 6.32 7.13 7.89 8.47 9.09 9.80
1.9 2.51 2.51 2.63 2.67 2.74 2.94 3.19 3.61 4.60 5.49 6.31 7.17 8.23 8.99 9.39 10.00 10.41