Inspection Report - Earthing

This document summarizes an inspection of earthing work done at a site in Ponpadi, Tamil Nadu. The inspection found that the earthing was done using a chemical earth electrode with a diameter of 17mm and depth of 2 meters, as specified in the drawings. Visual checks found that 5 earth pits were installed, the earth chamber was cast in situ and measured 500x500x400mm, and the earth grid and individual pit resistances were both measured to be 0.68 ohms. Representatives from the contractor and Jio signed off on the inspection.

Uploaded by

vinoth kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
565 views4 pages

Inspection Report - Earthing

This document summarizes an inspection of earthing work done at a site in Ponpadi, Tamil Nadu. The inspection found that the earthing was done using a chemical earth electrode with a diameter of 17mm and depth of 2 meters, as specified in the drawings. Visual checks found that 5 earth pits were installed, the earth chamber was cast in situ and measured 500x500x400mm, and the earth grid and individual pit resistances were both measured to be 0.68 ohms. Representatives from the contractor and Jio signed off on the inspection.

Uploaded by

vinoth kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Earthing

Site Information

Sap Id I-TN-TRTN-ENB-9072

Candidate Id C1

Form No R4G-70-CQM-FMT-PR-010

Site Name Ponpadi

Mr B Baskaran, S/o Mr Balan, Ponpadi Village Post, Thirutani Taluk, Thiruvallur


Site Location
District 631213 Ph:9944461384,,

City --

Latitude 13.227958

Longitude 79.594901

R4G State Tamil Nadu

Contractor METRO ELECTRICALS

Date 24 August 2023

Reliance Jio Infocomm Limited Page 1


Inspection Report- Earthing

[Link]. Description Specifications Observations Remarks

Preliminary Checks

10070-C53-xx-xxx-
1.0 IFC Drawing No of Earthing
xxxx-ENB-0000-007

Chemical,Pipe,Plate
1.1 Type of Earthing used at site chemical

G.I. 80 mm for Pipe,


Cu Bonded 17 mm
1.2.1 Dia. Of Earth Electrode Used 17mm
for Chemical

600 x 600 x 12 CI or
600 x 600 x 6 GI for
1.2.2 Plate Size use for earthing yes as per drawing
Plate Earthing

B Class &
Class and Thickness of Pipe
1.3 80mm,4mm thk 4.5
Electrode Used
100,4.5 mm thk

As per specified
1.4 Check layout of earthing Yes
drawing

Visual and Physical Verification

2.1 No. of Earth Pits 1,2,3,4,5,6 5

Diameter of bore hole for earthing


2.2 300 mm,100 mm 100mm

Depth of bore hole for earthing


2.3 3M,2M,4.5 M 2 2mtr

2.4 Assemble of earth electrode As per drawing Yes

Reliance Jio Infocomm Limited Page 2


Joints of earthing strip with earth
2.5 Tight Connection Yes
electrode

Check for No. of Earth Bus Bars As per Earthing


2.6 3nos
installed & Specification drawing

Check for earthing of all As per Earthing SLD


2.7 Yes
equipments

Min. 50 mm
Check for jointing of two earth overlapping & Zinc
2.8 Yes
strips and coating Rich Metallic Paint
on joints
Earthing Strip dimensions for 50 x 6 mm GI or 25
2.9 interconnections of earth x 3 mm GI,Cu 25 50x6mm GI
electrodes bonded

2.10.1 Earth Chamber Type Pre-casted,Brick 500 cast insitu

2.10.2 Earth Chamber Size ( mm ) (LxWxH) 500*500*400

Check Individual Earth Pit EP1,EP2,EP3,EP4,


2.11 0.68
Resistance EP5,EP6 ( ohms )

2.12 Check Earth Grid Resistance ( ohms ) 0.68

Observations and Comments:

as of new specification earthing done

Reliance Jio Infocomm Limited Page 3


CFQ details

Contractor’s representative Field Engineer QC Engineer

Signature

Name mohan vinoth

Date 25 August 2023 25 August 2023 --