0% found this document useful (0 votes)
32 views3 pages

New 30701

This software release from TYCO includes updates to the 4100ES/4010ES programmer, executive, and slave files to support new features and fix reported issues. The version 3.07.01 programmer includes support for NXNA horn strobe ceiling mount devices and advanced earth fault diagnostics. Updates are also made to the executive and slave files to enable these new features and resolve other defects. Users are directed to documentation regarding compatibility and installation of the new files.

Uploaded by

Rafael Contreras
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views3 pages

New 30701

This software release from TYCO includes updates to the 4100ES/4010ES programmer, executive, and slave files to support new features and fix reported issues. The version 3.07.01 programmer includes support for NXNA horn strobe ceiling mount devices and advanced earth fault diagnostics. Updates are also made to the executive and slave files to enable these new features and resolve other defects. Users are directed to documentation regarding compatibility and installation of the new files.

Uploaded by

Rafael Contreras
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

TYCO Fire Protection Products Technical Support

May 18, 2017

Software Release

Product: 4100ES, 4010ES


Programmer: ESProgrammer_3.07.01.exe
Executive: ES_3.07.bin
Slaves included: 4010IDNETPLUS_3.12.11
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.02
CPUBoot_2.02.03
EBOOT_1.01.03
EOS_1.01.02
EPS_1.06
ESS_1.06
FUI_1.05
FUIBoot_104
IDNET_3.12.11
IDNET1PLUS_3.12.11
idnet2_1.03.02
IDNETPLUS_3.12.11
lmc_3.01.02
MSS_3.12.11
MSSI_3.12.11
mxdloop_2.01.03
Phone_1.04.01
rps_3.12.11
SecurityZoneRelay_1.02
SPS_204 (for Rev E and earlier boards)
sps_3.12.11
TFXLoop_10103
tic_3.01.02
TIC2_1.01.02
TPS_1.05.05
XALIC_10105
XBC_10604
XPS_3.12.11
XSIG_101

Compatibility See SB11002 (in C:\4100ESINFO)

After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-07-01
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.07.01.exe

1
ES Programmer 3.07.01
DBF Revision = 177

Functional Changes
 This version supports NXNA Horn Strobe Ceiling Mount Devices and Advanced Earth Fault Diagnostic
Feature

Fixed Defects:
788334 Copy and paste of NXNA point broken in Point Editing tab
788282 Unable to perform Remote Download via BNIC using 3.01 and later programmers if mDNS is
disabled or target is on different subnet.
793909 Program memory checksum error occurs with DACT with External IDNAC REPEATER Point
800016 Binary S-Record job file is built incorrectly
803711 Copy/Paste is broken for NXNA point on the ESS

Other Changes:
793160 3000-Point 4100ES support
796016 No warning is shown when you configure a switch to an unassociated VNAC

4100/4010ES Executive 3.07


Functional Changes
 This version supports NXNA Horn Strobe Ceiling Mount Devices and Advanced Earth Fault Diagnostic
Feature

Fixed Defects
793880 Panel may incorrectly report "will alarm" when enabling AMZ device from external node
793879 AMZ points are on the install mode list at the NDU but not at the owning node or TSW
796035 the Heat sensitivity threshold shown on front panel is invalid in centigrade format
793177 Strobe and Relay appliances of an SV do not operate independently

Other Changes
 None

Usage Notes
 Revision 3.07 of the ESSupport tools should be used with this release.
 Requires revision 2.02.02 or greater of CPU Bootloader.
 Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
 Requires EPS revision 1.05.03 or later

2
EPS_1.06.bin
ESS_1.06.bin

Functional Changes
 This is the first version that supports Ceiling Mount Devices and Advanced Earth Fault Diagnostic
Feature.

Fixed Defects
751875 Wrong EPS trouble LEDs indication after removal of earth fault on IDNAC
788332 EPS LED does not display any errors when the earth fault is removed even if missing devices
troubles exist
791715 EPS 1.05.03 when IDNAC Channel is only programmed with MTAA (CM A/V) device, going to
Alarm won't activate these MTAA (CM A/V) devices
793177 Strobe and Relay appliances of an SV do not operate independently

Other Changes
 Should be used with ES programmer/ Master 3.07 or higher to use Ceiling Mount devices and Advanced
Fault Diagnostic Feature.

TIC2_1.01.02.bin

Functional Changes
 None

Fixed Defects
796009 Cannot clear the Primary receive trouble on the DARIC card.

Other Changes
 None