GRIDSCAN 5000

TM

POWERED BY H2SCAN

Hydrogen sensors for transformer dissolved


gas monitoring using our proven DGA platform
G RI DSCANTM 5000 sensor techn o l ogy is hydrogen
specific using a proven industrial hardened design
comprised of metal alloys with a proprietary coating
to protect the sensor. This enables the sensor to
measure hydrogen in oil or ga s ph a se of po w er
t ra n sformers a nd ancillary equipment.

This solid-state sensing element is insensitive to


other transformer gases and can be immersed di-
rectly in the transformer oil during normal operation
to measure hydrogen levels continuously.
00
GRID
HY
SCANSE50
DROGEN
NSOR
The GRIDSCAN TM 50 0 0 platform has no consumable
components or any degradation of the sensor, does
not require carrier or calibration gases to maintain ac-
curacy and has a theoretically unlimited useful life.

■ Major OEM partners

■ Installed Worldwide

■ Highest Uptime Availabilty

H2scan Corp., 27215 Turnberry Lane, Unit A Valencia, CA 91355 USA


Tel: 661-775-9575 Fax: 661-775-9515
E-mail: [email protected] www.h2scan.com
GRIDSCAN™ 5000
Hydrogen Sensor Specifications
Parameter Oil Phase Gas Phase
Measurement Range 25 - 5,000 ppm 25 - 5,000 ppm in oil equivalent
Accuracy 1
+/- 20% of reading or +/- 25 ppm†
Repeatability2 +/- 10% of reading or +/- 15 ppm†
Response Time < 60 minutes (location on Xfmr)
Operating Temperature (Ambient) -40°C to +70°C
Storage Temperature -40°C to +85°C
Oil Temperature Range3 -40°C to +105°C n/a
Data Log Storage 1 Year
Cross-sensitivity to H2O, CO2, C2 H2, C2 H4, CO, etc. <2%
Serial Communications 2-Wire RS485, MODBUS RTU and DNP3.0
Power Supply 12-48VDC, 10 Watt
Environment “IP68 (7.62m [25ft] water for 14 days) – Marine Rated (C5M)”
Insulating Liquid Supported Mineral Oil, Silicone, Natural Ester, Synthetic Ester

† whichever is greater
1
Accuracy of the sensor in the FIELD
2
For consecutive measurements to an identical hydrogen concentration
3
Main tank bulk oil temperature

Physical Specifications
Wetted Materials and Internal Sealing: Ratings:
316SS, 40% mineral filled Nylon, polyimide, CE Mark
Viton (fluoropolymer elastomer), hermetic ROHS 2011/65/EU compliant
glass-to-metal feedthrough EMC/RFI and Other Electrical Certification
External Housing and Sealing: • IEC 55022 IFCC Part 15
Hard Anodized 6061 Aluminum, 40% mineral • IEC 55011
filled Nylon, Viton (fluoropolymer elastomer), • IEC 61000-4-2 through 61000-4-4, 61000-4-6, and 61000-4-8
nickel-plated zinc (4-wire connector) • IEC 61010-1 , ANSI/UL 61010-1
• IEC 61326
Humidity and Corrosion Resistance:
• FM 6520:2022
Class C5M Marine rated; salt-water condensing
Vibration: 3-axis Sinusoidal, Wideband and Random
(IEC 60068-2-11 & DIN EN ISO 12944)
[Simulated Long-Life] (IEC 60068-2-6 table C.2,
Ingress Protection: IP68; 25 feet water for 14 days
IEC 60068-2-64 paragraph A.2, category no. 2)
(IEC 60529)
Shock: 30g, shock duration 18ms (IEC 60068-2-27)

H2scan Corp., 27215 Turnberry Lane, Unit A Valencia, CA 91355 USA


Tel: 661-775-9575 Fax: 661-775-9515
E-mail: [email protected] www.h2scan.com