Aikon PD ES Manual Overview

The document provides technical specifications and installation instructions for variable frequency drives from Shanghai Pumping Tech International Co. It includes details on parameters, dimensions, terminal arrangements, and the keyboard for their drives. The document contains extensive information on the specifications and usage of the drives.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views20 pages

Aikon PD ES Manual Overview

The document provides technical specifications and installation instructions for variable frequency drives from Shanghai Pumping Tech International Co. It includes details on parameters, dimensions, terminal arrangements, and the keyboard for their drives. The document contains extensive information on the specifications and usage of the drives.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Introduction: Provides an introduction to the high-performance vector AC drive manual, outlining its purpose and the company responsible.
  • Technical Parameters: Details the technical features of the vector AC drive, including power specifications and control types.
  • Installation and Dimensions: Covers the installation requirements and physical dimensions of the drive components.
  • Terminal Arrangement: Provides instructions for the arrangement of main and control circuit terminals for effective setup.
  • Keyboard Control: Describes the keyboard interface and functionalities for controlling the AC drive.
  • Quick Setup: Guides users through the setup process for the drive, including initial configurations and parameter adjustments.
  • VFD Parameters: Details the parameter settings for various functionalities of the Variable Frequency Drive (VFD).
  • Error Diagnosis: Details troubleshooting and error elimination for the drive, including a list of error codes and their resolutions.

PD ES Manual

SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 1 Technical parameters


Table 1.1

Feature name Eigenvalues

Standard size 0.75-900 kw

Power supply, V 220:200~240V;380V:360-460V;660V;1140V

Power frequency 47~63Hz

Analog input/output signal type In: 0~10v/0/0-20 mА; *2

Control method V/F control; Open loop vector control

Starting torque 0.5Hz/100%

Speed range 1:100, adjustment accuracy: ±0.5%

60s for 120% of the rated current; 3s for 150% of the


Overload capability
rated current

Straight-line V/F curve


Multi-point V/F curve
Type of V / F curve
N-power V/F curve (1.2-power, 1.4-power, 1.6-power,
1.8-power, square)

Maximum frequency Vector control: 0-320 Hz; V/F control: 0-3200Hz

1. Operation, 2. I/O terminal, [Link],


Control command source [Link] start; Control channels 1 and 2 main, 3
and 4 additional.

Built-in PID controller For closed loop control with feedback.

Built-in 1 independent RS485 interface+1 eCan


Multi-drive system operation
interface

Maintain a constant output voltage


AVR function
Input oscillation

1
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Table 1.2

Feature name Eigenvalues

Prevent unauthorized changes


Parameter lock
Parameters before and during work

The current and voltage are limited automatically


Over voltage/Over current
during the running process so as to avoid frequent
stall control
tripping due to overvoltage/over current.
It can limit the torque automatically and prevent
Torque limit and control frequent over current tripping during the
running process.
It helps to avoid frequent over current faults of the
Rapid current limit
AC drive.

Control of asynchronous motor is implemented


High performance through the high-performance current vector control
technology.

Motor short-circuit detection at power-on, output


phase loss protection, over-current protection,
Protection mode
over-voltage protection, under voltage protection,
overheat protection and overload protection.

Indoor, avoid direct sunlight, dust, corrosive gas,


Installation location
combustible gas, oil smoke, vapour, drip or salt.

Lower than 1000m (Lower the grades when using


Altitude
higher then 1000m)

-10°C ~40°C (Lower the grades if the ambient


Ambient temperature
temperature is between 40°C and 50°C)

Humidity Less than 95%RH, without condensing

Vibration Less than 5.9 m/s2 (0.6 g)

Storage
-20°C~60°C
temperature

Protection level IP20/ 65

2
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 2 Installation and dimensions


Table 2.1 Dimensions (IP20)

Model Power Input output Dimensions (mm) Installations(mm) Weight


(KW) Current(A)Cuttent A H D W B d (Kg)
(A)

3PH 360V~460V 47PH~63H


01D5K 1.5 5 3.7 118 185 157 106 175 4.5 1.7

02D2K 2.2 5.8 5 1.7

04D0K 3.7 10.5 8.5 1.8

05D5K 5.5 14.6 13 1.8

07D5K 7.5 20.5 18 160 247 177 148 235 5,5 3.2

0011D 11 26 24 3.4

0015D 15 35 30 3.65

0018D 18.5 38.5 37 220 321 198 205 305 5,5 5.65

0022D 22 46.5 46 6.45

0030D 30 62 58 6.5

0037D 37 76 75 220 411 238 160 395 7 12

0045D 45 92 90 12

0055D 55 113 110 255 453 237 190 440 7 16.5

0075D 75 157 150 280 582 295 200 563 9 26.2

0090D 93 180 170 26.2

0110D 110 214 210 300 685 323 200 667 11 41

0132D 132 256 250 40

0160D 160 307 300 360 690 330 260 660 11 46.9

0185D 187 345 340 420 840 334 150*150 815 11 72

0200D 200 385 380 72

0220D 220 430 430 540 934 390 200*200 893 13 106

0250D 250 468 465 106

0280D 280 525 520 106.3

0315D 315 590 585 640 1035 390 250*250 1003 11 140

0350D 350 665 650 140

0400D 400 785 754 860 1200 400 350*350 1164 15 205

0450D 450 870 850 205

0500D 500 965 930 210

0560D 560 1070 1050 210

3
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Table2.2 Display panel for IP20

*Hole diameter of the panel installation box(height*width):122*86mm


*Size of outline box:135*92
Table1.3 IP 65 Type

3.4

0.75~7.5KW

Model Power Input output Dimensions (mm) Installations(mm) Weight


(KW) Current(A)Cuttent (Kg)
W H D A B Φd
(A)

3PH 360V~460V 47PH~63H


0D76K 0.75 3.4 2.5

01D5K 1.5 5 3.7 165 195 130 178 105 4 2.5


02D2K 2.2 5.8 5

04D0K 3.7 10.5 8.5

05D5K 5.5 14.6 13 200 235 151 225 129 4 3.2


07D5K 7.5 20.5 18

4
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 3 Terminal arrangement

Table 3.1 Main circuit terminals

NOTES:

5
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

6
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 4 keyboard

IP20 IP65
4.1 Key description(Table 4.1)

button Description

FUNC/ENTER Enter menu screen function, set parameter confirmation


button.

JOG In Panel start mode, this button acts as a shift function.

Run Controls the start and stop of the frequency converter; it


Stop/RST can be used to reset the fault in the fault state.

PRGM/ESC Set parameters

Up Under the monitoring interface, if it is in constant pressure


mode, the target pressure can be increased. If in menu
Down
mode, this button is used to increase the value.

FWD/REV In Panel start mode, this button acts to change rotation

A/M In menu mode, this button acts as a shift [Link]


genenal mode shift auto and manual:hold press 1.5s

4.2 Indicator description


RUN: When the inverter is running, the indicator light is on, and the indicator is off
when the inverter stops outputting.

STANDBY: When the inverter is in the state of cut off(standby) , the standby
indicator flashes;

Auto: VFD/VSD works in auto mode for constant pressure/temperature

Master:light on Backup maste:twinkle every second Slave :light off

Manul: VFD/VSD works in Manul mode,frequency is setted manully

REV: Reversed rotation

8
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 5 Quick Setup


Below is the procedure to complete the setup:

First step:

Setting Modbus address every VFD/VSD

Then set F26.03 choose the master and F26.04( QTY of pumps(VFD/VSD) in
system)

Set the parameters in master(lead F26.03=0)VFD/VSD

F10.04 = 10.0 (10 bar) Sensor measurement limit --- default

F10.01 = 5 (5 bar)

Parameters will copy to other VFD/VSD( not include the terminal parameters)

Second step: Check the direction of rotation of the engine:

Start the pump briefly and check that the direction of rotation is correct.

The direction of rotation can be changed in the following ways:

Turn off the frequency converter. Make sure the display goes out. Swap

any two wires on the U / V / W pins.

Stop the frequency converter and change the value of function P4.00.

Third step:Detailed setting.

Detailed settings must be made according to the table below

Forth step:Start-up mode setting

The keyboard start-up

Set the parameter F00.01=0, and operate the keyboard Run/Stop to control the start
and stop of the inverter.

The terminal start-up

Set parameter F00.01=1, and short-circuit S1 and DCM on the terminals(F06.00=1),


the inverter will start; disconnect S1 and DCM, the inverter will stop. The shorting
method is shown in Figure 8.2.

Figure 8.2.

9
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

6.2 Operating parameters


Table 6.2
Default
code description Valid values
value
F00.03 Maximum frequency 50.00
Frequency operation

F00.04 Upper limit frequency 50.00


F00.05 Lower limit frequency 20.00
F00.12 Acceleration time Power
F00.13 Deceleration time depends
Acceleration/Deceleratio
F00.14 0: 1s 1: 0.1s 2: 0.01s 1
n time unit

6.3 Terminals
Table 6.3
Default
code description Valid values
value

F06.00 S1 Terminal 1
1:In running
F06.01 S2 Terminal 7:Err reset 51
DI setting

51: Hand mode


F06.02 S3 Terminal 52:Dry running(F26.28=1 Err:E065) 0
53:Pipe bursting(Err:E066)
F06.03 S4 Terminal 53

0:No output 3
F7.02 TA1*TC1 Relay
3:Err
18:Run 42
F7.03 RA*RB*RC Relay
42:Initialization finished, ready for
work 43
DO setting

F7.04 TA2*TC2 Relay


43:Master mode
44:Dry running protection 0
45:Pipe bursting
F7.05 TA3*TC3 Relay 46:Auto mode
47:Manual mode
48:Sensor(Transmitter failure)

11
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

6.4 Cut in/cut off and wheel pumps


Table 6.4

Default
code description Valid values
value
Master cut in pressure Unit:bar,
F09.50 0.5
deviation Cut in pressure=F10.01-F09.50
Master cut in delay
F09.51 1~6500s 3
time
Master Cut off
F09.52 0~F00.03 30.00Hz
frequency
Master Cut off delay
F09.53 1~6500s 3.0
time
the frequency of cut in 48.00Hz
F26.06
slave
The time delay of cut 5.00s
F26.07
Cut in /Cut off

in slave pumps

the frequency of 25.00Hz


F26.08
Cut off slave

The time delay of cut 5.00s


F26.09
off slave

0: off
Cut in/out 2 mode
F26.23 1: on: for master vfd 2
selection
2: on:for all vfd

Cut in/out 2 Pressure


F26.24 0~F10.04 0.5
floating deviation

Cut in/out 2 water


F26.24 1~100s 5
detection interval

Cut in/out 2 frequency


F26.25 2
changing step

0:close(start by modbus address) 1


pumps
Wheel

F26.10 Wheel pump 1:start pump with min working


period

12
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

6.5 alarm signal


Table 6.5

Valid Default Alarm


code description
values value value
F26.18 Overload limit,compare to F02.05 110.0%
Overl
oad

E67
F26.19 Stall detection time 3.00s

0~20mA
feedback
Pressure

F10.26 Pressure sensor lost alarm 3.80mA


0:close
E020E
F10.27 Pressure sensor lost alarm delay 0.0s-20.0s 5

F26.11 High pressure alarm, 0 is off 0~F10.04 8bar


E063
F26.12 High pressure alarm delay 0~100s 3s
Pressure alarm

F26.13 High pressure alarm reset delay 0~600s 60s

F26.14 Low pressure alarm, 0 is off 0~F10.04 0bar


F26.15 Low pressure alarm delay 0~100s 5s
E064
F26.16 Low pressure alarm reset delay 0~600s 600s
F26.17 Low pressure alarm reset QTY 0~20 5

Dry running protection type


0:Close
F26.28
1:Terminal signal (value 52)
2:Inlet pressure (F09.46 F09.47) AI2
Dry Running

F26.28=2
Dry running test pressure, E065
F09.46 bar 0.1bar
F26.28=sensor current/2 ,less than
F09.46,means dry running
F26.28=2
When pressure higher than
F09.47 bar 0.1bar
F09.46+F09.47, Err reset
automatically.
0:close
PTC

F20.20 1:work
Connect PTCP/PTCN terminal

6.6 Motor parameters

13
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Table 6.6

code description Valid values

F02.01 Rated motor power


Motor parameter

F02.02 Rated frequency


F02.03 Rated speed rotation Set by motor
F02.04 Rated voltage
F02.05 Rated current

6.7 Monitoring parameters


Table 6.7

code description Valid values

F08.09 Software version


F08.10 Total Running time unit:h
Monitoring
parameter

F08.13 Total boot time unit:h


F08.14 Total power used unit:kw
F17.13 AI2 V
F17.71 0:normal 1:Lose sensor

14
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Chapter 7 Information on the protection, diagnosis and

elimination of errors in the VFD.


PD ES series controller is equipped with effective protection against under voltage and over
voltage, over current and voltage overheating. If the controller fails, first eliminate the cause of
the problem and then restart it.

Note: The power must be cut off during maintenance.


Table 7.1

Error code Description Cause Elimination

The pressure sensor is broken or Check pressure sensor and


E02E Lost feedback
damaged connection

1:Reconnect communication cable


Initialization
1:Check QTY of VFD in master VFD(F26.04)eCAN
E060 error in HVAC
2 Check the eCan cable 2:Set F26.04 in master VFD, and
mode
F13.00 for all VFD
Initialization
E061 error in HVAC In initialization,find more than 1 master 1:check F26.03 of all VFD
mode
Initialization 1: Started VFD before
E062 error in HVAC 1:Didn’t find any work VFD initialization finished
mode 2:All VFD err.

High pressure Excessive pressure or damage to the pressure 1: Check feedback F26.11
E063
alarm sensor 2: Check pressure sensor

Low pressure Lower pressure or damage to the pressure 1: Check feedback F26.14
E064
alarm sensor 2: Check pressure sensor

1:Check F26.26 and accordingly


E065 Dry running 1:No water in inlet of pump
sensor

E066 Pipe Bursting 1:Water filled the accordingly sensor 1:Check pipe

Set the right parameters or check


E067 Overload Check parameter F26.18 F26.19 F26.15
the pump and motor
Check the motor and PTC terminal( broken or
E068 PTC overheated Maintain the motor or PTC sensor
not)

15
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Table 7.2

Error code Description Cause Elimination

1. instantaneous power failure


2. input voltage of the inverter is [Link] reset
within the specified requirements [Link] to normal voltage
Bus 3. bus voltage is abnormal [Link] technical support
E001
under-voltage 4. rectifier bridge and buffer resistance [Link] technical support
abnormal [Link] technical support
5. drive board is abnormal [Link] technical support
6. main control board is abnormal

1: Abnormal power supply. 1: Check the power supply voltage.


Over voltage 2: Peripheral circuitry is incorrectly set 2: Do not use power supply switch
(switch control on or off, etc.). to control the inverter on or off.
E002 during
3: Inverter fault. 3: Sent for repairing.
acceleration
4:The braking unit and braking resistor 4: Install the braking unit and
are not installed. braking resistor.
1: Increase deceleration time.
1: Decelerate time is too short.
2: Check the power supply voltage.
Over voltage 2: Power supply voltage abnormal.
3: Check braking unit and
E00A during 3: Over load.
resistance.
deceleration 4: Braking resistor incorrectly set.
4: Set Braking resistor over again.
5: Braking parameter is incorrectly set.
5: Correctly set parameter, e.g.
1: Check the power supply voltage.
Over voltage 1: Power supply voltage abnormal.
2: Install braking unit and
E003 during constant 2: Energy feedback load.
resistance.
speed 3: Braking resistor incorrectly set.
3: Affirm resistance setting again.
1: Acceleration time is too short. 1: Increase acceleration time.
Over current
2: V/F curve is not set correctly. 2: Correctly set V/F curve.
E004 during
3: Motor or motor wire have short 3: Check the insulation
acceleration
circuit to the ground. of motor and motor wire.
1: Decelerate time is too short.
Over current 1: Increase deceleration time.
2: Inverter capacity is inappropriately
E005 during 2: Enlarge inverter capacity.
set.
deceleration 3: Solve disturbing resource.
3: Whether there is any disturbing.
1: The insulation of motor and motor 1: Check the insulation of
Over current
wire is motor and motor wire.
E006 during constant
not good. 2: Check load situation and
speed
2: Load fluctuation. Mechanical lubrication.

Table 7.3

16
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Error code Description Cause Elimination

1:Reduce the load and check the


1:The load is too heavy or motor-stalled
motor and the mechanical
occurs on the motor.
E007 Motor overload condition.
2: The AC drive model is of too small
2:Select an AC drive of higher
power class.
power class.

1: The load is too heavy or motor-stalled 1: Reduce the load and check the
AC drive occurs on the motor. motor and mechanical condition.
E008
overload 2: The AC drive model is of too small 2: Select an AC drive of higher
power class. power class.

[Link] three-phase power input is


[Link] external faults.
abnormal.
Power input [Link] technical support
E012 [Link] drive board is faulty.
phase loss [Link] technical support
[Link] lightening board is faulty.
[Link] technical support
[Link] main control board is faulty.

1: The cable connecting the AC drive


and the motor is faulty. 1: Eliminate external faults.
Power output 2: The AC drive’s three-phase output is 2: Check whether the motor
E013
phase loss unbalanced when the motor is running. three-phase winding is normal.
3: The drive board is faulty. 3: Looking for technical support.
4: The module is faulty.

1: The ambient temperature is too 1: Reduce ambient temperature.


temperature. 2: Clean up the air filter.
Module 2: The air filter is blocked. 3: Replace the damaged fan.
E00E
overheat 3: The fan is damaged. 4: Replace the damaged thermally
4: The thermally sensitive resistor of the sensitive resistor.
module is damaged. 5: Replace the inverter module.

1: External fault signal is input via X.


External
E00d 2: External fault signal is input via Reset the operation.
equipment fault
virtual I/O.

17
SHANGHAI PUMPING TECH INTERNATIONAL CO.,LTD Website:[Link]

Table 7.4

Error code Description Cause Elimination

Current 1: The HALL device is faulty. 1, replace the faulty HALL device
E015
detection fault 2: The driver board is faulty. Replace the faulty drive board

1: Set the motor parameters


1: The motor parameters are not set
Motor according to the nameplate properly.
E016 according to the nameplate.
auto-tuning fault 2: Check the cable connecting the
2: The Motor auto-tuning times out.
AC drive and the motor.
EEPROM
E00F EEPROM chip is damaged. Replace the main control board.
read-write fault
Communication
E018 Check communication cable
fault
Short circuit to The Motor is short circuited to the
E023 Replace the cable or motor.
ground fault ground.
Check S1~S4 terminal connnection and
E027 Terminal Err Revise terminal setting
setting
The AC drive running current is lower Check that the load is disconnected
E030 Load lose
than F05.13. or the setting of F05.13
1: The load is too heavy or 1. Reduce the load and check the
Pulse-by-Pulse
locked-rotor occurs on the motor. motor and mechanical conditions.
E032 current limit
2: The AC drive model is of too small 2: Select the AC drive of higher
fault
power class. power class.
AC drive 1: Over voltage exists. 1: Handle based on over voltage.
E033
hardware fault 2: Over current exists. 2: Handle based on over current.
1: The encoder parameters are set
1: set the encoder parameters
Too large speed incorrectly.
E034 properly.
deviation fault 2: the motor auto-tuning is not
2: perform the motor auto-tuning.
performed.
1: The encoder parameters are set
1: Set the encoder parameters
Motor incorrectly.
E035 properly.
over-speed fault 2: The motor auto-tuning is not
2: Perform the motor auto-tuning.
Performed.
[Link] the temperature sensor cabling
[Link] cabling of the temperature sensor
and eliminate the cabling fault.
E036 Motor overheat becomes loose.
[Link] the carrier frequency or adopt
[Link] motor temperature is too high.
other heat radiation measures.
Check that the motor parameters are set
Initial position The motor parameters are not set based on
E037 correctly and whether the setting of
fault the actual situation.
rated current is too small.

18