IES Notes 6th Sem
IES Notes 6th Sem
MODULE 1
ANSHUL SHEKHAR
BCE BHAGALPUR
LT system wiring components, Selection of cables, wires,
Two-way Switch – These are used for wiring circuits which are to be
controlled from two points independently such as stair case wiring.
Flush Switch- The flush switches are fixed in flush with the wall and do not
project out. Such types of switches are used where high quality performance
and appearance are desired. Sometimes these switches are called Piano type
switches.
Pull Switch or Ceiling Switches- The pull switches are fixed on the ceiling
and all the alive parts are out off reach of the operator. The switch has a
strong mechanical action and is usually operated with a single pull on the
cord for the on and off position. These switched are used in bath rooms
where water heaters are used, bed rooms and restaurants.
Grid Switch- The grid switches are similar to tumbler switches, except that
they are lighter and are portable type, so that they are quite useful for
the portable machines such as hand-drill, portable grinder etc. They are
manufactured either in single-way or two-way pattern.
Push Button Switches- These switches are used for bell circuit, refrigerator
lighting circuit etc.
Rotary Switches
The rotary switches are much different from that of ordinary tumbler
switch. It consists of an insulated handle to which blades are fixed.
These blades move in steps by the movement of the handle and
make contact with the terminals to which are connected the wires
in the electric circuits.
Such switches are of cast iron and have very robust construction. cork
gasket is fitted between the case and the cover which makes it water-
tight. These are used for outdoor lamp control.
Iron-clad Switch
The knife switch consists of blades hinged at one end and are arranged
to go into forked terminals or jaws at the other end. These are
available as single throw switches or double throw switches.
Lamp Holder
A lamp-holder is used to hold the lamp required for
lighting purposes.
Earlier, brass lamp-holders were quite popular, but now-a-
days these have been superseded by the all insulated
pattern.
A lamp-holder has either moulded or porcelain interior
with a solid or spring plunger and easily wired terminals.
Types of Lamp Holders
Swivel Lamp-holder
Small Bayonet Cap Holder Cord grip type Batten type Screwed pattern
• Swivel Lamp-holder- The swivel lamp holders are designed for
controlled wide angle directional lighting which are used for lighting
of shop windows, show cases etc.
• Fluorescent Lamp holder and starter holder- The fluorescent
holders are either of bi-pin type or of bayonet cap type, but pin
type holders are generally used for ordinary fluorescent tubes.
Ceiling Roses
These are used to provide a tapping to the pendant lamp-holders,
fan or fluorescent tube. According to Indian standard
c) A ceiling rose shall not embody fuse terminal as integral part of it.
Ceiling Roses
Socket Outlet
The socket outlets have all insulated base with moulded or socket base
having 3 terminal sleeves. The two thin terminal sleeves are meant for
making connection to the cable, with the third terminal sleeve, thicker in
cross-section, is used for an earth connection. The cover is again
moulded and has corresponding 3 holes.
15 Amp 5 Amp
Socket Socket
Plugs
For taking power from socket outlets, plugs are used. The thicker
pin is used for an earth connection to the portable appliances. They
are also made for 5 amps and 15amps load.
Terminal Blocks
Terminal blocks used for termination and connection to the other
circuits. A single-way terminal block is used for differentiating the live
line from the neutral when the domestic connection is given and is
called as Connector.
Main Switch
The main switches are used to control the whole supply for a house or
office. These are of following types:
ICDP (Iron Clad Double Pole)- use for single phase supply control (15 A,
30A, 60A, 100A, 250 V)
ICTP (Iron Clad Three Pole)- use for three phase-three wire and three
phase four wire supply control (15A, 30A, 60A, 100A, 150A, 200A, and
500V)
ICDP ICTP
Distribution Box
A distribution board is the main electrical supply system for any
commercial or residential entity. The main cable comes into
the distribution board and then via breakers get distributed in the
secondary circuits such as lights and plugs.
PDB (Power DB) – It is used to distribute electrical power /supply to power loads
such as Geyser, Fridge, AC etc. All these items draw high current. MCBs of current
rating 16A,20A,25A are used.
NDB (Normal DB) – It is used for normal AC supply where load is to be fed from
normal power.
UPS DB – It is used for UPS supply where load is to be fed from UPS power.
(2) Classification of DB according to supply –
SP – Single Pole (only one point isolation contact where one phase is connected). Application –
Switching & protection is done in one phase only.
DP – Double Pole (Two point isolation contacts where Phase & Neutral are
connected). Application – Switching & protection is done in one phase & neutral only.
TP – Triple Pole (Three point isolation contacts where R,Y,B phase are connected). Application –
Switching & protection is done in all 3 phases only.
TPN – Triple Pole with Neutral (Four point isolation contacts). R,Y,B phase & Neutral are
connected but protection is given for 3 phases only, not for neutral.
4P – Four Pole (Four point isolation contacts. R,Y,B & Neutral are isolated & protection is given for
3 phases & neutral)
4/6/8.. Way TPN DB – In this, each phase has 4/6/8/.. MCBs that is why 4 Way TPN DB has 12
outgoing MCBs while 6 Way TPN has 18 MCBs & so on.
Wires
Whenever a circuit is extended or rewired, or when any new circuit is
installed, it is critical that the new wiring is made with wire conductors
that are properly sized for the amperage rating of the circuit, as
determined by the size of the circuit breaker controlling it.
Manufacturers have labeled the outer coating of the wire with types
and size of wire.
Wires are available with different sizes and their current carrying
capacities are also varying according to their size.
Wire Size and Uses
The wires dimensions are defined in terms of [Link]. of cross-section and sizing is
determined based on current-carrying capacity. For house wiring, the sizing is
generally in the range of 1 to 6 [Link] with current-carrying capacity determined
in accordance with IS 3961 (Part V)-1968 as under:
Current carrying
Purpose Size of wire
capacity in Amp.
• Single-Core
• Multi-Core
• Usually, single-core stranded wires are used for house wiring & multi-core wires
are used for connection of an appliance with the plug.
• There is no protective sheathing (or black covering in the image above) available
in single-core stranded wires whereas the same is given in the multi-core cable to
keep all the core together.
• In any case, the copper conductor is covered with PVC insulation to prevent any
current leakage. (Indian Standard: IS 694 for the PVC insulation)
Selection of cables
Important factors that determine the selection of cables
For example: Cables installed deep under the ground will have reduced
current carrying capacity than cables installed in air. This is impacted
due to multiple factors like soil temperature, soil thermal resistivity
etc.
This type of meter is simple in construction and accuracy is somewhat less due to creeping
and other external fields. A major problem with these type of meters is their easy prone to
tempering, leading to a requirement of an electrical energy monitoring system. These are
very common used in domestic and industrial applications.
2. Electronic Energy Meter: It is based on Digital Micro technology (DMT) and uses no
moving parts. So the electronic energy meter is known as Static Energy meter. In
Electronic energy meter the accurate functioning is controlled by a specially designed IC
Called Application specified integrated circuit (ASIC). ASIC is constructed only for specific
applications using embedded system technology. In addition to ASIC, analogue circuits,
voltage transformer, current transformer etc. are also present in Electronic energy meter to
sample current and voltage.
The input data (voltage) is compared with a programmed Reference Data (voltage) and
finally a “voltage rate” will be given to the output. This output is then converted into digital
data by the Analogue-Digital converter (ADC) presented in the ASIC.
Smart metering system uses the advanced metering infrastructure system technology for
better performance. These are capable of communicating in both directions. They can
transmit the data to the utilities like energy consumption, parameter values, alarms, etc.
and also can receive information from utilities such as automatic meter reading system,
reconnected/disconnected instructions, upgrading of meter software’s and other important
message.
These meters reduces the need to visit while taking or
reading monthly bill. Modems are used in these smart
meters to facilitate communication systems such as
telephone, wireless, fiber cable, power line
communications. Another advantage of smart metering
is complete avoidance of tampering of energy meter
where there is scope of using power in an illegal way.
Protective Devices
When a failure occurs on any part of the electrical power system, it must be
quickly detected and disconnected from the system. There are two reason for it.
Firstly, if the fault not cleared quickly , it may cause unnecessary interruption of the
service to the customer. Secondly, rapid disconnection of faulty apparatus limit the
amount of damage to it and prevent the effects of fault from spreading into the
system.
The detection of fault and disconnection of faulty part can be achieved by using
fuses or relays in connection with circuit breakers. A fuse can perform both the
function but for low voltage circuit only. For high voltage circuits, relays and circuit
breakers are employed to serve the desire function for automatic protective gear.
Fuses
A fuse is a short piece of metal, inserted in the circuit, which melts when excessive
current flows through it and thus breaks the circuit.
5. The smaller sizes of fuse element impose a current limiting effect under
short-circuit conditions.
7. The minimum time of operation can be made much shorter than with the
circuit breakers.
Disadvantages
For small currents upto 10 A, tin or an alloy of lead and tin (lead 37%, tin 63%) is
used for making the fuse element. For larger currents, copper or silver is employed.
Important Terms-
(i) Current rating of fuse element: It is the current which the fuse element
can normally carry without overheating or melting. It depends upon the
temperature rise of the contacts of the fuse holder, fuse material and the
surroundings of the fuse.
(ii) Fusing current: It is the minimum current at which the fuse element melts
and thus disconnects the circuit protected by it. Obviously, its value will be
more than the current rating of the fuse element.
For a round wire, the approximate relationship between fusing current ‘I’ and
diameter ‘d’ of the wire is I = k d3/2 where ‘k’ is a constant, called the fuse
constant.
(iii) Fusing factor: It is the ratio of minimum fusing current to the current
rating of the fuse element. Its value is always more than one.
(iv) Cut-off current: It is the maximum value of fault current actually reached
before the fuse melts.
(v) Pre-arcing time: It is the time between the commencement of fault and the
instant when cut off occurs.
2. AUTOMOTIVE FUSES: These fuses are specifically designed for automotive systems that
run up to 32V and occasionally 42V. They come in ‘blade’ form (a transparent plastic envelope
with flat contacts) and are colour coded according to rated current. Some of these types are
also used in other high-power circuits. Each colour of fuse has specific rating.
Resettable Fuses
DC FUSES
4. SEMICONDUCTOR FUSES: The power dissipated by a semiconductor increases
exponentially with current flow, and hence semiconductors are used for ultrafast fuses. These
fuses are usually used to protect semiconductor switching devices that are sensitive to even
small current spikes.
AC FUSES
HIGH VOLTAGE FUSES: These fuses are used in high voltage AC transmission lines where
voltages can exceed several hundreds of kilovolts.
1. HRC (High Rupture Current) fuses: HRC fuses are cartridge type fuses consisting of a
transparent envelope made of magnesium silicate. The fuse is filled with quartz powder (and
in the case of a liquid-filled HRC fuses, a non-conducting liquid like mineral oil) that acts as an
arc extinguishing agent. These fuses are used for very high fault currents.
AC FUSES
2. Expulsion Fuses: These fuses are filled with chemicals like boric acid that produce gases
on heating. These gases extinguish the arc and are expelled from the ends of the fuse. The
fuse element is made of copper, tin or silver.
AC FUSES
LOW VOLTAGE FUSES: Used in the relatively low voltage distribution networks.
1. Cartridge fuses: They are very similar to cartridge type DC fuses. They consist of a
transparent envelope surrounding the fuse element. They can be plugged in (blade type) or
screwed into a fixture (bolt type).
2. Rewireable fuses: They are a simple reusable fuse used in homes and offices. They
consist of a carrier and a socket. When the fuse is blown, the carrier is taken out, rewired
and put back in the socket to resume normal operation. They are somewhat less reliable
than HRC fuses.
Cartridge Fuse
Rewireable Fuse
Miniature Circuit Breaker
ON STATE
Principle of Operation of MCB
During short circuits, a transient current flowing through the solenoid forces the
plunger towards the latch. This action instantaneous releases the mechanical latch
and opens the contacts immediately. When we switch it on, we reset the displaced
operating latch to its previous on position and the MCB is ready for another switch
off or trip operation.
OFF STATE
Types of MCB
MCBs are available with different current ratings of 0.5, 1.2, 2.5, 3, 4, 5, 6, 7.5,
10, 16, 20, 25, 32, 35, 40, 63, 100, 125, 160 A and voltage rating of 240/415 V
AC and up to 220 V DC. Operating time is very short (less than 5 ms). They are
suitable for the protection of important and sophisticated equipment, such as air-
conditioners, refrigerators, computers etc. MCBs are available in single, two,
three and four-pole versions. MCB is also categorized based on trip current, which
is the minimum current at which a MCB will trip instantaneously.
Trip class Trip Current
Above 2 to 3 times the rated current. These types of MCBs are highly
CLASS Z sensitive to short circuit and are used for the protection of highly
sensitive devices such as semiconductor devices.
Fuse Vs MCB
Nowadays miniature circuit breakers (MCBs) are much more commonly used in low voltage
electrical networks instead of fuses. The MCB has many advantages compared to a fuse:
•It automatically switches off the electrical circuit during the abnormal conditions of the network
(both overload and fault conditions). The MCB is much more reliable in the detection of such
conditions because it is more sensitive to change in current.
•As the switch operating knob comes at its off position during tripping, the faulty zone of the
electrical circuit can easily be identified. But in case of a fuse, the fuse wire should be checked
by opening fuse grip or cutout from fuse base, for confirming the blow of fuse wire.
•Quick restoration of supply cannot be possible in case of fuse, as fuses have to be replaced for
restoring the supply. But in the case of an MCB, quick restoration is possible by flipping a
switch.
The only one disadvantage of MCB over fuse is that this system is costlier than a fuse unit
system.
MCCB
A Moulded Case Circuit Breaker (MCCB) is a type of electrical protection device
that is used to protect the electrical circuit from excessive current, which can cause
overload or short circuit.
It is mainly used for high current applications and in a place where adjustable
tripping requires. With a current rating of up to 2500A, MCCBs can be used for a wide
range of voltages and frequencies with adjustable trip settings.
These breakers are used instead of miniature circuit breakers (MCBs) in large scale
systems for system isolation and protection purposes.
The MCCB uses a temperature sensitive device (the thermal element) with a current
sensitive electromagnetic device (the magnetic element) to provide the trip
mechanism for protection and isolation purposes.
MCCB
MCCB has main three functions
They protect in the event of an overload where the current is higher than the
rated value and lasts a longer time than normal.
The on and off function can be used to switch the circuit on or off for repairs and
replacements.
MCCB Icu: Ultimate Short Circuit Breaking
Capacity- If the fault current exceeds
this value, the MCCB will be unable to
trip.
Ics: Operating Short Circuit Breaking
Capacity- This is the highest fault
current value that the MCCB can
handle.
Ue: Rated Working Voltage- It is the
rated voltage for the continuous
operation of MCCB, same as or close
to the system voltage.
Ui: Rated Insulation Voltage -This
value indicates the maximum voltage
which the MCCB can resist in lab
conditions.
Uimp: Rated Impulse Withstand
Voltage- This value is the transient peak
voltage, the circuit breaker can
withstand from switching surges or
lightning strikes.
MCB Vs MCCB
Sl. No MCB MCCB
Its trip characteristics are normally Its trip current may be fixed as well
5 not adjustable since they basically as adjustable for overload and
cater to low circuits. magnetic setting.
Types of MCCB
Type of Operating Operating Surge Installation
Application Suitability
MCCB Current Time Current Location
At incoming/
Trips between 5
0.04-5 Commercial or Inductive load outgoing of
Type C and 10 times Moderate
seconds industrial applications applications Distribution
rated current (In)
Board
Inductive –
capacitive load
Trips between 10 At incoming of
0.04-3 Commercial or applications
Type D and 20 times High Distribution
seconds industrial applications (Pumps, motor,
rated current (In) Board/Panels
large winding
motors etc.)
Inductive and
Trips between8 At incoming of
0.04-5 motor loads
Type K and 12 times Industrial applications High Distribution
seconds with high inrush
rated current (In) Board/Panels
currents.
Earth Leakage Circuit Breaker (ELCB)
If any current leaks from any electrical installation, there must be any insulation
failure in the electrical circuit, it must be properly detected and prevented otherwise
there may be a high chance of electrical shock if anyone touches the installation. An
earth leakage circuit breaker does it efficiently. Means it detects the earth leakage
current and makes the power supply off by opening the associated circuit breaker.
Also, the ELCB is used to protect the circuit from the electrical leakage. When
someone gets an electric shock, then this circuit breaker cuts off the power at the
time of 0.1 sec. for protecting the personal safety and avoiding the gear from the
circuit against short circuit and overload.
ELCB
A current ELCB has a toroidal iron core over which phase and neutral windings are
wound. A sensing coil is also wound on the same iron core which in turn is connected
to the trip coil. Figure below shows the constructional detail of Current ELCB.
Under normal operating condition, the current through the phase winding and neutral
winding are same but both the windings are wound in such a manner to oppose the
mmfs of each other, therefore net mmf in the toroidal iron core will be zero.
Consider a condition where earth leakage current exists in the load side. In this case
the current through the phase and neutral will no longer be equal rather phase
current will be more than the neutral current.
Thus mmf produced by phase winding will be more than the mmf produced by
neutral winding because of which a net mmf will exist in the toroidal iron core.
This net mmf in the core will link with the sensing coil and an emf will be induced
across the terminals of the sensing coil. This emf will in turn drive a current
through the Trip/Sensing Coil which will pull lever to open supply contacts to isolate
the power supply.
Schneider 125 A 4 Pole RCCB Siemens 25 A 2 Pole RCCB
ELCB Vs RCCB
Sl. No RCCB ELCB
RCCB refers to Residual Current ELCB stands for Earth Leakage Circuit
1.
Circuit Breaker. Breaker.
A Motor Protection Circuit Breaker safely disconnect the current in the event of a
short circuit. Main Functions of MPCB are as follows:
a) Protection against electrical faults such as short circuits, L-G faults etc.
The reliability of the MPCB is greater than MCCB or fuse. MPCB > MCCB > Fuse
Construction & Working of MPCB
MPCB contains 6 different parts such as thermal overload release, magnetic trip unit,
main contact, auxiliary switches, arc chute, plunger, and enclosure.
Thermal Overload Release: Used to protect the motor from overload or
high balanced current which is more than a preset value. The thermal overload is
designed along with the current adjuster to limit the current flow to the motor. It is
made up of bimetallic strip (usually steel and copper, or in some cases steel and
brass). It operates when the current flow is higher than the preset value.
Main Contact: The main contacts of the Motor Protection Circuit Breaker are
responsible for the current flowing from the source to the load circuits. It is divided
into two-part fixed contacts and moving contacts.
Both contacts are made up of Copper tungsten and copper tungsten carbide. The
fixed contacts will be stabled at the MPCB enclosure and moving contact will be
fixed with the trip mechanism.
Arc Chute: Arc chute is used to quenching the arc developed at that time of MPCB
circuit is opening. The outer body It is made up of glass sole to withstand high
temperature during the circuit breaker is opening. The arc chute contains copper
plates to cut the continuity of the arc.
Enclosure: An insulative enclosure is used to cover the inner mechanism from the
outside world. It is made up of molded plastic resins. To increase the strength, the
enclosure, fillers such as glass fibers are added to the plastic resin.
Advantages:
The high degree of protection such as Short circuit, Unbalanced, phase loss, and over
current protection are available in one pack.
Easy adjustment
Compact size
Less maintenance
No need for external thermal overload relay
Disadvantage:
High cost
Cannot be repaired (use & through)
Cannot adjust the short circuit current tripping limit
Application:
Induction Motor starting (DOL/Star-delta)
Lighting circuit applications
Direct starting applications
Isolator
The isolator is a switch which isolates a part of the circuit from the system
as per requirement.
Electrical isolators are the separate part of the system that is created for the
safe maintenance. Isolators are generally used before MCB for repair or
replacement work.
Main Supply
M M M
C C C
B B B
Normally
Closed OFF
Push Button
Connection of Contactor
with Single Phase Motor
Relays
Relay is a device that detect the fault and initiate the operation of the circuit
breaker to isolate the faulty element from the rest of the system.
1. Selectivity: It is the ability of the protective system to select correctly that part
of the system in trouble and disconnect the faulty part without disturbing the
rest of the system
2. Speed: The relay system should disconnect the faulty section as fast as possible.
3. Sensitivity: It is the ability of the relay system to operate with low value of
actuating quantity.
4. Reliability: It is the ability of the relay system to operate under the pre-
determined conditions.
2. Solenoid type
3. Electrodynamics type
4. Induction type
5. Thermal type
5. Differential Relay
6. Distance Relay
1. Instantaneous Relay
2. If in any case the inaccuracy in the connection and the failure arises the
updation of the single diagram becomes easy even on the regular basis.
3. The information from one line diagram can be widely used to enhance the
performance of service activities.
Single Phase Wiring
Three Phase Wiring
Tariff
The rate at which electrical energy is supplied to a consumer is known as tariff.
Tariff should include the total cost of producing and supplying electrical energy
plus the profit, yet it cannot be the same for all types of consumers. Therefore, a
tariff should include the following items :
In this type of tariff, the price charged per unit is constant i.e., it does not vary with
increase or decrease in number of units consumed. The consumption of electrical
energy at the consumer’s terminals is recorded by means of an energy meter.
Disadvantages
In this type of tariff, the consumers are grouped into different classes and each class of
consumers is charged at a different uniform rate. For instance, the flat rate per kWh for
lighting load may be 60 paise, whereas it may be slightly less (say 55 paise per kWh) for
power load. The different classes of consumers are made taking into account their diversity
and load factors. The advantage of such a tariff is that it is more fair to different types of
consumers and is quite simple in calculations.
Disadvantages
(i) Since the flat rate tariff varies according to the way the supply is used, separate meters
are required for lighting load, power load etc. This makes the application of such a tariff
expensive and complicated.
(ii) A particular class of consumers is charged at the same rate irrespective of the magnitude
of energy consumed. However, a big consumer should be charged at a lower rate as in his
case the fixed charges per unit are reduced.
3. Block rate tariff: When a given block of energy is charged at a specified rate and the
succeeding blocks of energy are charged at progressively reduced rates, it is called a block
rate tariff.
In block rate tariff, the energy consumption is divided into blocks and the price per unit is
fixed in each block. The price per unit in the first block is the highest and it is progressively
reduced for the succeeding blocks of energy.
For example, the first 30 units may be charged at the rate of 60 paise per unit ; the next 25
units at the rate of 55 paise per unit and the remaining additional units may be charged at the
rate of 30 paise per unit.
The advantage of such a tariff is that the consumer gets an incentive to consume more
electrical energy. This increases the load factor of the system and hence the cost of generation
is reduced. However, the disadvantage is that it lacks a measure of the consumer’s actual
demand. This type of tariff is being used for majority of residential and small commercial
consumers.
4. Two-part tariff: When the rate of electrical energy is charged on the basis of maximum
demand of the consumer and the units consumed, it is called a two-part tariff.
In two-part tariff, the total charge to be made from the consumer is split into two components
viz., fixed charges and running charges. The fixed charges depend upon the maximum
demand of the consumer while the running charges depend upon the number of units
consumed by the consumer. Thus, the consumer is charged at a certain amount per kW of
maximum demand plus a certain amount per kWh of energy consumed i.e.,
where, b = charge per kW of maximum demand c = charge per kWh of energy consumed.
This type of tariff is mostly applicable to industrial consumers who have appreciable maximum
demand.
Two-part tariff
Advantages
(ii) It recovers the fixed charges which depend upon the maximum demand of the consumer
but are independent of the units consumed.
Disadvantages
(i) The consumer has to pay the fixed charges irrespective of the fact whether he has
consumed or not consumed the electrical energy.
(ii) There is always error in assessing the maximum demand of the consumer.
Energy Charge: Rs
5.75 x 59 = Rs 339.25
Fixed/Demand
Charge: Rs 40/kW x
1.72 kW = Rs 68.80
Electricity Duty: 6%
of Rs 339.25
5. Three-part tariff: When the total charge to be made from the consumer is split into three
parts viz., fixed charge, semi-fixed charge and running charge, it is known as a three-part
tariff. i.e.,
where a = fixed charge made during each billing period. It includes interest and depreciation
on the cost of secondary distribution and labour cost of collecting revenues, b = charge per
kW of maximum demand, c = charge per kWh of energy consumed.
It may be seen that by adding fixed charge or consumer’s charge (i.e., a) to two-part tariff, it
becomes three-part tariff. The principal objection of this type of tariff is that the charges are
split into three components. This type of tariff is generally applied to big consumers.
Tariff of HT Consumer having 100 KVA Contract Demand, Supply Voltage (kV) : 11 KV
Maximum Demand
Recorded: 120 KVA
Electricity Duty: 6%
of Rs 246636.98
Electric Shock
An electric shock occurs when a person comes into contact with an electrical
energy source. Electrical energy flows through a portion of the body
causing a shock.
• Duration of contact
d) Muscle, nerve, and tissue destruction from a current passing through the body
e) Death (electrocution)
Accidents and injuries with electricity are caused by one or a combination of the
following:
1. Avoid water at all times when working with electricity. Never touch
or try repairing any electrical equipment or circuits with wet hands. It
increases the conductivity of electric current.
5. Never try repairing energized equipment. Check all the wires, the
outer metallic covering of the service panel and any other hanging
wires with an electrical tester before proceeding with your work.
6. Never use an aluminium or steel ladder if you are working on any
receptacle at height in your home. An electrical surge will ground you
and the whole electric current will pass through your body. Use a
wooden or a fiber glass ladder instead.
11. Always turn off the mains when perform electric work at your home.
12. Never place bare wire of leads in plugs. Fit a plug top.
References
1. Principles of Power System” by [Link], Rohit Mehta, S Chand & Co Ltd, 2005
2. [Link]
INDUSTRIAL ELECTRICAL SYSTEM
MODULE 2
ANSHUL SHEKHAR
BCE BHAGALPUR
Topics to be covered
Types of residential and commercial wiring systems, general
rules and guidelines for installation, load calculation and sizing
of wire, rating of main switch, distribution board and
protection devices, earthing system calculations, requirements
of commercial installation, deciding lighting scheme and
number of lamps, earthing of commercial installation, selection
and sizing of components.
Electrical Wiring
A process of connecting various accessories for
distribution of electrical energy from supplier’s meter
board to home appliances such as lamps, fans and other
domestic appliances is known as Electrical Wiring.
1. Durability
2. Safety
3. Appearance
4. Cost
5. Accessibility
6. Maintenance Cost
System of Internal Wiring
1. Cleat wiring
2. Casing and capping wiring
3. Batten wiring
a) CTS or TRS or PVC sheath wiring
b) Lead sheathed or metal sheathed wiring
4. Conduit wiring
a) Surface or open Conduit type
b) Concealed or underground type Conduit
Cleat Wiring
In this system of wiring, cables are supported and gripped
between porcelain cleats and above the wall or roof.
The casing has usually two (or three) shaped grooves, into
which the VIR or PVC cables are laid in such a way that the
opposite polarity cables are laid in different grooves.
The width of the batten depends upon the number and size of
cables to be carried by it.
11. When the installation has been completed it should be tested before
giving the supply.
13. In case of 3-phse, 4-wire system, at the main board, indication should
be done in Red, Yellow and Blue. Neutral should be indicated in black.
Electrical Installation Rules & Guidelines
Various standards are being followed for low-voltage installations. IS 4648-
1968 “Indian Standard Guide for Electrical Layout in Residential Building”
is one of them.
Electrical Energy Distribution System
(as per electrical connection)
As per the recommendations of IS, each circuit shall not have more than
800 Watt connected load or more than 10 points which is less. In case of
CFL points where load per point may be less, number of points may be
suitably increased.
Hence, in case of more load or more points to be connected to the supply
system, then it is to be done by having more than one circuit through
In the given circuit same circuit contains light, fan and power circuit which
Dividing the wiring into a number of smaller circuit is called sub- circuit.
b) Power Sub-circuit
Determination of number of sub-circuits: It is decided as per number of
In one light & fan circuit the maximum load that can be connected is 800
watts & the maximum number of points which can be wired is 10.
In one power sub-circuit the maximum load that can be connected is 3,000
watts and the number of socket-outlets which can be provided is 2.
current rating of main switch is decided as per total current of the circuit
to be controlled by it.
The number of ways and current rating of the DB is decided as per number
of sub-circuits to be connected to it and current of the sub-circuit having
highest current rating.
Single Phase Wiring
Three Phase Wiring
Load calculation & sizing of wire
Determination of number of points: Number of fan/light points is
determined as per the measure (length, height and width) of room and the
size/rating of fan/light. Higher the size of the fan (900 mm, 1200 mm, 1400
mm) higher will be delivery of air (in m3/minute) and lesser will be number of
fan required. Similarly, higher rating of light causes lesser number of installation
of light (high rating means high illumination). For determination of number of
socket-outlets, IS 4648-1968 shall be referred.
Bed Room 2 to 3 1
Living Room 2 to 3 2
Kitchen 1 2
Dining Room 2 1
Bathroom 1 1
For AC 0 1
For Refrigerator 0 1
Rating of commonly used electrical items are
Kettle 13 3000
Printer <0.5 50
Kitchen 200
Bathroom 100
Entrance 100
Stair 100
Garage 70
Determination of size of wires: The wires dimensions are defined in terms
of [Link]. of cross-section and sizing is determined based on current-
carrying capacity. The conductor used in house wiring (except flexible &
fitting wires) must not be of size less than 1/1.12 mm in copper or 1/1.40
mm (1.5 mm2) in aluminium wire.
Rated Voltage
Voltage Drop
Therefore, use of items for AC load based upon its current is as under:
Switch : 16A - 220V
Socket : 16A – 220V
Plug Top : 16A – 220V
MCB/SPN : 16A – 220V
PVC wires : 2.5 mm2
Protective Devices
When a failure occurs on any part of the electrical power system, it must be
quickly detected and disconnected from the system. There are two reason for it.
Firstly, if the fault not cleared quickly , it may cause unnecessary interruption of the
service to the customer. Secondly, rapid disconnection of faulty apparatus limit the
amount of damage to it and prevent the effects of fault from spreading into the
system.
The detection of fault and disconnection of faulty part can be achieved by using
fuses or relays in connection with circuit breakers. A fuse can perform both the
function but for low voltage circuit only. For high voltage circuits, relays and circuit
breakers are employed to serve the desire function for automatic protective gear.
Other protective devices are MCB, MCCB, MPCB, ELCB, RCCB, Relay, Isolator
General items required as per load
PVC wires: Generally 4.0 mm2, 2.5 mm2, 1.5 mm2, 1.0 mm2, 0.75
DP Isolator, etc.
6A switch is used for all light points, fan points, etc.
6A, 5-pin socket is used for refrigerator, Iron, washing machine, LED TV,
16A/20A switch and 16A/20A 6-pin socket is used for geyser point, high
2way switches are used for stair case light control and entry gate
lights.
All accessories should be of ISI marked, branded bearing good look and as
2. Conductors
4. Reception and distribution of main supply
The consumer’s main switch fuse is connected after the meter and feed a
distribution fuse board. It is important to note that fuses should be connected
only in live wire and never in the neutral wire. Similarly all switches installed
on live wire only and never on the neutral wire.
Simple Diagram of Single Phase Installation
Single Phase Installation with a number of sub-distribution boards
having a common main switch fuse
Single Phase Installation with a number of sub-distribution boards each
connected to the mains through a separate fuse
9. Service Connection
The line bringing electric power from supplier’s low voltage distribution up
to the energy meter installed at the consumer’s premises is called the service
connection.
The electric supply authority supplies power to the consumers through a low
voltage three phase four wire distribution system called the secondary
distribution system.
Large consumers supplied at higher voltages through three-wire high voltage
distribution system called the primary distribution system (6.6, 11, 33 kV)
Service connection may be by mean of underground cables or by mean of
overhead conductors or cables.
Overhead Service Connection
This system is used when the consumer’s premises are more than
45 meter away from the supplier’sdistribution pole.
a) PVC or weather proof cable service line
b) Bare conductor service line
Estimating and Costing of Electrical Installation
• Quantity and specification of material
• Price list
• Labour charges
• Overhead charges
• Contingencies
• Profit purchase system
Electrical Installations for Residential
building: Estimating and Costing of Material
Industrial Substation
At many places in the line of the power system, it may be desirable and necessary to
change some characteristic (e.g. voltage, a.c. to d.c., frequency, p.f. etc.) of electric supply.
This is accomplished by suitable apparatus called substation.
For example, generation voltage (11 kV or 6·6 kV) at the power station is stepped up to
high voltage (say 220 kV or 132 kV) for transmission of electric power. The assembly of
apparatus (e.g. transformer etc.) used for this purpose is the sub-station. Similarly, near
the consumers localities, the voltage may have to be stepped down to utilization level.
This job is again accomplished by a suitable apparatus called substation. At some places
in the line of the power system, it may be desirable to convert large quantities of a.c.
power to d.c. power e.g. for traction, electroplating, *d.c. motors etc. This job is again
performed by suitable apparatus (e.g. ignitron) called sub-station. It is clear that type of
equipment needed in a sub-station will depend upon the service requirement.
The following are the important points which must be kept in view while laying out a
sub-station:
(i) It should be located at a proper site. As far as possible, it should be located at the
centre of gravity of load.
(ii) It should provide safe and reliable arrangement. For safety, consideration must be
given to the maintenance of regulation clearances, facilities for carrying out repairs
and maintenance, abnormal occurrences such as possibility of explosion or fire etc.
(iii) It should be easily operated and maintained.
(iv) It should involve minimum capital cost.
The comparison between outdoor and indoor sub-stations is given below in the tabular
form:
From the above comparison, it is clear that each type has its own advantages and
disadvantages.
2. According to service requirement. A sub-station may be called upon to change
voltage level or improve power factor or convert a.c. power into d.c. power etc.
According to the service requirement, sub-stations may be classified into:
(i) Transformer sub-stations. Those sub-stations which change the voltage level of
electric supply are called transformer sub-stations. These sub-stations receive power at
some voltage and deliver it at some other voltage. Obviously, transformer will be the
main component in such substations. Most of the sub-stations in the power system are
of this type.
(ii) Switching sub-stations. These sub-stations do not change the voltage level i.e.
incoming and outgoing lines have the same voltage. However, they simply perform the
switching operations of power lines.
(iii) Power factor correction sub-stations. Those sub-stations which improve the
power factor of the system are called power factor correction sub-stations. Such sub-
stations are generally located at the receiving end of transmission lines. These sub
stations generally use synchronous condensers as the power factor improvement
equipment.
(iv) Frequency changer sub-stations. Those sub-stations which change the supply
frequency are known as frequency changer sub-stations. Such a frequency change may
be required for industrial utilisation.
(v) Converting sub-stations. Those sub-stations which change a.c. power into d.c.
power are called converting sub-stations. These sub-stations receive a.c. power and
convert it into d.c. power with suitable apparatus (e.g. ignitron) to supply for such
purposes as traction, electroplating, electric welding etc.
(vi) Industrial sub-stations. Those sub-stations which supply power to individual
industrial concerns are known as industrial sub-stations.
Fig. 4.1 shows the block diagram of a typical electric supply system indicating the
position of above types of sub-stations. It may be noted that it is not necessary that all
electric supply schemes include all the stages shown in the figure. For example, in a
certain supply scheme there may not be secondary sub-stations and in another case, the
scheme may be so small that there are only distribution sub-stations.
Symbols for equipment in sub-station:
It is a usual practice to show the various elements (e.g. transformer, circuit breaker,
isolator, instrument transformers etc.) of a sub-station by their graphic symbols in the
connection schemes. Symbols of important equipment in sub-station are given below:
Equipment used in a transformer sub-station:
The equipment required for a transformer sub-station depends upon the type of sub
station, service requirement and the degree of protection desired. However, in general, a
transformer sub-station has the following main equipment:
1. Bus-bars. When a number of lines operating at the same voltage have to be directly
connected electrically, bus-bars are used as the common electrical component. Bus-bars
are copper or aluminum bars (generally of rectangular x-section) and operate at
constant voltage. The incoming and outgoing lines in a sub-station are connected to the
bus-bars. The most commonly used bus-bar arrangements in sub-stations are:
(i) Single bus-bar arrangement
(ii) Single bus-bar system with sectionalisation
(iii) Double bus-bar arrangement
2. Insulators. The insulators serve two purposes. They support the conductors (or bus-
bars) and confine the current to the conductors. The most commonly used material for
the manufacture of insulators is porcelain. There are several types of insulators (e.g. pin
type, suspension type, post insulator etc.) and their use in the sub-station will depend
upon the service requirement. For example, post insulator is used for bus-bars. A post
insulator consists of a porcelain body, cast iron cap and flanged cast iron base. The hole
in the cap is threaded so that bus-bars can be directly bolted to the cap.
3. Isolating switches. In sub-stations, it is often desired to disconnect a part of the
system for general maintenance and repairs. This is accomplished by an isolating switch
or isolator. An isolator is essentially a knife switch and is designed to open a circuit
under no load. In other words, isolator switches are operated only when the lines in
which they are connected carry *no current.
4. Circuit breaker. A circuit breaker is an equipment which can open or close a circuit
under normal as well as fault conditions. It is so designed that it can be operated
manually (or by remote control) under normal conditions and automatically under fault
conditions. For the latter operation, a relay circuit is used with a circuit breaker.
Generally, bulk oil circuit breakers are used for voltages upto 66kV while for high (>66
kV) voltages, low oil circuit breakers are used. For still higher voltages, air-blast, vacuum
or SF6 circuit breakers are used.
5. Power Transformers. A power transformer is used in a sub-station to step-up or
step-down the voltage. Except at the power station, all the subsequent sub-stations use
step-down transformers to gradually reduce the voltage of electric supply and finally
deliver it at utilisation voltage. The modern practice is to use 3-phase transformers in
sub-stations ; although 3 single phase bank of transformers can also be used. The power
transformer is generally installed upon lengths of rails fixed on concrete slabs having
foundations 1 to 1·5 m deep. For ratings upto 10 MVA, naturally cooled, oil immersed
transformers are used. For higher ratings, the transformers are generally air blast
cooled.
6. Instrument transformers. The lines in sub-stations operate at high voltages and
carry current of thousands of amperes. The measuring instruments and protective
devices are designed for low voltages (generally 110 V) and currents (about 5 A).
Therefore, they will not work satisfactorily if mounted directly on the power lines. This
difficulty is overcome by installing instrument transformers on the power lines. The
function of these instrument transformers is to transfer voltages or currents in the
power lines to values which are convenient for the operation of measuring instruments
and relays. There are two types of instrument transformers viz. (i) Current transformer
(C.T.) (ii) Potential transformer (P.T.)
(i) Current transformer (C.T.): A current transformer in essentially a step-up
transformer which steps down the current to a known ratio. The primary of this
transformer consists of one or more turns of thick wire connected in series with the line.
The secondary consists of a large number of turns of fine wire and provides for the
measuring instruments and relays a current which is a constant fraction of the current
in the line. Suppose a current transformer rated at 100/5 A is connected in the line to
measure current. If the current in the line is 100 A, then current in the secondary will be
5A. Similarly, if current in the line is 50A, then secondary of C.T. will have a current of
2·5 A. Thus the C.T. under consideration will step down the line current by a factor of 20.
(ii) Voltage transformer: It is essentially a step down transformer and steps down the
voltage to a known ratio. The primary of this transformer consists of a large number of
turns of fine wire connected across the line. The secondary winding consists of a few
turns and provides for measuring instruments and relays a voltage which is a known
fraction of the line voltage. Suppose a potential transformer rated at 66kV/110V is
connected to a power line. If line voltage is 66kV, then voltage across the secondary will
be 110 V.
7. Metering and Indicating Instruments. There are several metering and indicating
instruments (e.g. ammeters, voltmeters, energy meters etc.) installed in a sub-station to
maintain watch over the circuit quantities. The instrument transformers are invariably
used with them for satisfactory operation.
Key diagram of a typical 66/11 kV sub-station:
(i) There are two 66 kV incoming lines marked ‘incoming 1’ and ‘incoming 2’ connected
to the bus-bars. Such an arrangement of two incoming lines is called a double circuit.
Each incoming line is capable of supplying the rated sub-station load. Both these lines
can be loaded simultaneously to share the sub-station load or any one line can be called
upon to meet the entire load. The double circuit arrangement increases the reliability of
the system. In case there is a breakdown of one incoming line, the continuity of supply
can be maintained by the other line.
(ii) The sub-station has duplicate bus-bar system; one ‘main bus-bar’ and the other
spare busbar. The incoming lines can be connected to either bus-bar with the help of a
bus-coupler which consists of a circuit breaker and isolators. The advantage of double
bus-bar system is that if repair is to be carried on one bus-bar, the supply need not be
interrupted as the entire load can be transferred to the other bus.
(iii) There is an arrangement in the sub-station by which the same 66 kV double circuit
supply is going out i.e. 66 kV double circuit supply is passing through the sub-station.
The outgoing 66 kV double circuit line can be made to act as incoming line.
(iv) There is also an arrangement to step down the incoming 66 kV supply to 11 kV by
two units of 3-phase transformers; each transformer supplying to a separate bus-bar.
Generally, one transformer supplies the entire sub-station load while the other
transformer acts as a standby unit. If need arises, both the transformers can be called
upon to share the sub-station load. The 11 kV outgoing lines feed to the distribution sub-
stations located near consumers localities.
(v) Both incoming and outgoing lines are connected through circuit breakers having
isolators on their either end. Whenever repair is to be carried over the line towers, the
line is first switched off and then earthed.
(vi) The potential transformers (P.T.) and current transformers (C.T.) and suitably
located for supply to metering and indicating instruments and relay circuits (not shown
in the figure). The P.T. is connected right on the point where the line is terminated. The
CTs are connected at the terminals of each circuit breaker.
(vii) The lightning arresters are connected near the transformer terminals (on H.T. side)
to protect them from lightning strokes.
(viii) There are other auxiliary components in the sub-station such as capacitor bank for
power factor improvement, earth connections, local supply connections, d.c. supply
connections etc. However, these have been omitted in the key diagram for the sake of
simplicity.
Selection of Transformer
In order to select the correct three phase transformer we must first determine:
(1) The equipment being installed operates on a three phase supply- If both
single phase and three phase equipment are connected at the load end; the single
phase equipment is connected to only one phase of the transformer.
(2) The Primary Voltage of the transformer- This is the same as the line input
(or source) voltage.
(3) The Secondary Voltage of the transformer- This is the transformer's output
voltage and must be the same as the voltage required by the equipment being
installed (see equipment nameplate).
(4) Frequency- The Frequency of the input (source) voltage must be the same as
the operating frequency of the equipment being supplied. The transformer
selected must operate at the same frequency. Typical operating frequency is 50
Hz.
(5) Rating- The rating of the load is determined by the product of the voltage
supplied across the load and the current passing through it. This is normally
expressed in VA or kVA on the equipment nameplate. The total load is often as
combination of various loads (i.e. lights, heaters, motors). We must calculate
these individual loads and add them together to obtain the total load of the
transformer.
The transformer must have a kVA rating greater than the load
requirement. The three phase transformer must be selected in a way that any
one phase is not overloaded.
Full Load Current Table - 3 Phase Transformer
Different Types of Electrical Loads
Industrial load consists of small, medium, large and heavy scale industries.
The induction motor forms a high proportion of the industrial load. The
industrial load is a function of frequency and voltage and it cover a major part of
the system load.
The three different types of industrial loads under which electric motors are
required to work are as under:
(i) Continuous Load: In such cases, the calculation of motor size is simpler
because the loads like pumps and fans require a constant power input to keep
them operating. However, it is essential to calculate the KW rating of the motor
correctly. If the KW rating of the motor is less than what is required, the motor
will overheat and consequently burn out. If, on the other hand, KW rating is
more than what is needed by the load, the motor will remain cool but will
operate at lower efficiency and power.
(ii) Intermittent Loads: Such loads can be of the following two types:
(a) In this type of load, motor is loaded for a short time and then shut off for a
long time, allowing the motor to cool down to room temperature as shown in
Fig 1. In such cases, a motor with a short time rating is used.
(b) In this type of load, motor is loaded for a short time and then it is shut off for
a short time. The shut off time is so short that the motor cannot cool down to the
room temperature as shown in Fig.2. In such cases, a suitable continuous or
short-time rated motor is chosen which, when operating on a given load cycle,
will not exceed the specified temperature limit.
Fig: 1 Fig: 2
(iii) Variable Loads: In the case of such loads, the most accurate method of
selecting a suitable motor is to draw the heating and cooling curves as per the
load fluctuations for a number of motors. The motor which does not exceed the
permitted temperature rise when operating on the particular load cycle should be
chosen for the purpose.
The selection of a motor depends primarily on the conditions under which it has
to operate and the type of load it has to handle. Main factors for such a selection
are as follows:
In fact, heating is proportional to square of the current but since load can be
expressed in terms of the current drawn, the proportionality can be taken for
load instead of the current.
Starting of Motors:
The induction motor, the most common type of motor utilized in building and
industry processes. Induction motors work by generating rotation power through
electrical conversion. This is with interacting magnetic fields. The back
electromagnetic force (EMF), which is coupled with magnetic field build-up at
the time of motor start, injects transient events that happen in the electrical
system. Such transitory conditions affect all equipment connected to the system
and its electrical supply. Motor starting is carefully studied and inspected in
industrial applications to limit such transient influence and to correctly
accelerate the mechanical load of the motor.
Direct-on-Line
Direct-on-line (DOL) is a straightforward method that is done by connecting the
motor to the supplier directly at a specific voltage. Not every system can use this
method; the most common examples are in well-dimensioned and mechanically
stiff shaft systems. It can also be used for pumps and other equipment that have
a stable supply. Direct-on-line is the most common method particularly since it
is the cheapest and simplest. It also causes the tiniest rise in temperature out of
all the techniques in motor starting. The issue with DOL is that the current can
be as high as eight times or more than its normal load.
Star-delta
Star-delta starting method is used in three-phase motors. It is applied to
minimize the starting current. At the motor start-up, the supply is connected to
the star end for the stator windings to commence. As soon as it achieves running
position, the current supply is reattached to the delta windings. The advantage of
using star-delta is the reduced starting voltage. The current at start-up for this
technique is only a third of the DOL method. This system is applied to high
inertia models wherein loads are initiated at the time full loading speed is
achieved. The setback to using star-delta is that around 33% reduction in
starting torque occurs. The effective changeover is required from star to delta so
that the speed is maintained. If this fails or happens at a low speed, the current
surge rises as much as in DOL, which can be detrimental to the entire system.
Auto-transformer
The auto-transformer starting is perhaps the fanciest of these three methods
since it uses an auto-transformer that is coupled with the induction motor at the
start-up. This technique utilizes dual voltage reductions brought about by
transformers, which also minimizes the voltage (around 50-80% of the full
voltage) using the secondary auto-transformer voltage. This system causes
reduced torque and locked-rotor current. It also causes a concurrent increase in
possible torque per ampere line. The auto-transformer start may also cause a
pulsing current due switching from secondary voltage to the main one.
……………………………………………………………………………………
Assignment: Explain different methods of starting induction motor.
……………………………………………………………………………………
Selection of Cable
Conductors: A cable may have one or more than one core (conductor). The
conductors are made of copper or aluminum and are usually stranded in order to
provide flexibility to the cable.
Insulation: Each core or conductor is provided with a suitable thickness of
insulation, the thickness of layer depending upon the voltage to be withstood by
the cable. The insulating materials used in cables are rubber, vulcanized India
rubber, impregnated paper, varnished cambric and polyvinyl chloride.
Metallic sheath: In order to protect the cable from moisture, gases or other
damaging liquids (acids or alkalies) in the soil and atmosphere, a metallic sheath
of lead or aluminum is provided over the insulation.
Bedding: Over the metallic sheath is applied a layer of bedding which consists
of a fibrous material like jute or hessian tape. The purpose of bedding is to
protect the metallic sheath against corrosion and from mechanical injury due to
armoring.
Armoring: Over the bedding, armoring is provided which consists of one or two
layers of galvanized steel wire or steel tape. Its purpose is to protect the cable
from mechanical injury.
Serving: In order to protect armoring from atmospheric conditions, a layer of
fibrous material (like jute) similar to bedding is provided over the armoring.
This is known as serving.
…………………………………………………………………………………..
The selection and satisfactory operation of a cable depends to a great extent
upon the characteristics of insulation used. The insulating materials used in
cables should have the following properties:
High insulation resistance to avoid leakage current.
High dielectric strength to avoid electrical breakdown of the cable.
High mechanical strength to withstand the mechanical handling of cables.
It should not absorb moisture from air or soil. The moisture tends to
decrease the insulation resistance and hastens the breakdown of the cable.
Non-inflammable
Low cost
Classification of Cables:
(i) Low-tension (L.T.) cables — upto 1000 V
(ii) High-tension (H.T.) cables — upto 11,000 V
(iii) Super-tension (S.T.) cables — from 22 kV to 33 kV
(iv) Extra high-tension (E.H.T.) cables — from 33 kV to 66 kV
(v) Extra super voltage cables — beyond 132 kV
A cable may have one or more than one core depending upon the type of service
for which it is intended. It may be (i) single-core (ii) two-core (iii) three-core
(iv) four-core etc. For a 3-phase service, either 3-single-core cables or three-core
cable can be used depending upon the operating voltage and load demand.
(i) single-core (ii) two-core (iii) three-core (iv) four-core
Selection Parameters:
(i) Voltage Rating: This is the rated voltage of the system, in which the cable
is to be installed & used. It is also important to know the method of system
earthing. The rated voltage of the cable is generally specified as a dual rating
(e.g.) 6.6kV (UE)/11kV (E).
‘UE’ means that the cable can be used for the specified voltage in an unearthed
or in a non-effectively earthed system. ‘E’ means that the cable can be used for
the specified voltage in a solidly earthed system. Thus, a cable whose rated
voltage is specified as 6.6kV (UE)/11kV (E) can be used either in a 6.6kV
unearthed or in a 6.6kV non-effectively earthed system or in an 11kV solidly
earthed system.
(ii) Type of Conductor: The most generally used conductor in a cable is either
Copper or Aluminum. For the same voltage rating, type, insulation, cross
sectional area and method of installation, the continuous current rating, the short
time current rating and the per unit length; cost of a Copper cable is
considerably higher than that of an Aluminum cable.
(iii) Type of Insulation: Most of today’s cables are insulated either with PVC
(Polyvinyl chloride) or with XLPE (Cross-linked polyethylene). Obviously, for
the same conductor material, voltage rating, type, insulation, cross sectional area
and method of installation, the continuous current rating, the short time current
rating and the per unit length; cost of an XLPE insulated cable is considerably
higher than that of a PVC insulated cable.
(iv) Type of Cables: Armored or Unarmored cables are used in indoor
installations and on above ground installations. But armored cables are
mandatory for any underground cable installation.
(v) Continuous Current Rating: The continuous current rating of cables with
Aluminium / Copper conductor is provided by manufacturer but, it should be
noted that the continuous current ratings are given for certain standard
conditions. In practice, it is not possible to get or to maintain these standard
conditions. Thus, certain rating factors are applied to arrive at the practical
continuous current rating.
(vi) Rating Factors: The following are the general rating factors to be
considered:
Rating factor for variation in ground temperature or in duct temperature
Rating factor for variation in ambient temperature
Rating factor for variation in thermal resistivity of soil
Group Rating Factor – Vertical Spacing
Group Rating Factor – Horizontal Spacing
(vii) Voltage Drop: Cables consist of resistance & reactance and hence the
current flowing though such impedance will cause a voltage drop. This drop
should not affect the loads connected by the cable. Actual voltage drops in
cables are given in V/km/A. It is also given in Indian Standard IS 1255. This
voltage drop should not be more than 10%.
(viii) Short Circuit Current Withstand: Any cable’s short time current
withstand capacity can be calculated using the following formula:
S = [(I √t) / K]
Where, I = Short Circuit Current in Amperes, t = Duration of Short Circuit in
seconds, K = Adiabatic Constant (= 115 for PVC /Copper; = 143 for XLPE /
Copper; = 76 for PVC / Aluminum and = 92 for XLPE / Aluminum)
Switchgear selection
The apparatus used for switching, controlling and protecting the electrical
circuits and equipment is known as switchgear. The switchgear equipment is
essentially concerned with switching and interrupting currents either under
normal or abnormal operating conditions.
(i) Complete reliability: With the continued trend of interconnection and the
increasing capacity of generating stations, the need for reliable switchgear has
increased. When fault occurs on any part of the power system, the switchgear
must operate to isolate the faulty section from the rest of the circuit.
(ii) Absolute discrimination: When fault occurs on any section of the power
system, the switchgear must be able to discriminate between the faulty section
and the healthy section. It should isolate the faulty section from the system
without affecting the healthy section. This will ensure continuity of supply.
(iii) Quick operation: When fault occurs on any part of the power system, the
switchgear must operate quickly so that no damage is done to generators,
transformers and other equipment by the short-circuit currents. If fault is not
cleared by switchgear quickly, it is likely to spread into healthy parts, thus
complete shutdown of the system may occur.
(iv) Provision for manual control: Switchgear must have provision for manual
control. In case the electrical (or electronics) control fails, the necessary
operation can be carried out through manual control.
A direct stroke to a phase (line) conductor is the most severe lightning stroke as
it produces the highest overvoltage for a given stroke current. Direct lightning
stroke approximates to a constant current source.
Methods of protection:
(i) Ground wires: The most generally accepted and effective method of
protecting lines against direct strokes is by the use of overhead ground wires
(also called earth wire). This method of protection is known as shielding
method which does not allow an arc path to form between the line conductor
and ground.
(ii) Lightning Arresters or Surge Diverters: They are connected between the
line and ground at the substation and always act in shunt (parallel) with the
equipment to be protected.
The process of connecting the metallic frame (i.e. non-current carrying part) of
electrical equipment or some electrical part of the system (e.g. neutral point in a
star-connected system, one conductor of the secondary of a transformer etc.) to
earth (i.e. soil) is called grounding or earthing.
Equipment grounding deals with earthing the non-current carrying metal parts
of the electrical equipment.
It is a core type transformer having three limbs built in the same fashion as that
of the power transformer. Each limb of the transformer has two identical
windings wound differentially (i.e. directions of current in the two windings on
each limb are opposite to each other) as shown in fig. Under normal operating
conditions, the total flux in each limb is negligibly small. Therefore, the
transformer draws very small magnetizing current.
If we connect a single-phase load between one line and neutral, the load current
I divide into three equal currents in each winding. Because the currents are
equal, the neutral point stays fixed and the line to neutral voltages remain
balanced as they would be on a regular 4-wire system. In practice, the single-
phase loads are distributed as evenly as possible between the three phases and
neutral so that unbalanced load current I is relatively small.
There are different types of earthing system mostly used, which are
Earth pit: Excavate and make an earth pit of size 900 mm x 900 mm x
minimum 3.0 meter deep. Level the bottom surface.
Plate electrode: Use GI plate of minimum size 600 Mm x 600 Mm x 6 mm
thickness. In case of a Copper plate, a minimum thickness of 3.15 mm can
be used.
Earthing connection: Fix two numbers of 50 mm x 6 mm GI strips to GI
plate with GI nuts, bolts and washer with each strip fixed to GI plate at two
locations. Weld the GI strips to GI plate. Join the two strips at the top with a
GI strip of the same size. Any loose earthing connection with the earth plate
will have an adverse effect on the electrode system resistivity.
Make a borehole of 500 mm diameter and 3.5 meters deep or as per the
approved design and drawing.
Lower the Pipe electrode made of a 65 mm diameter GI perforated pipe of
3.0-meter length attached at the top with a funnel covered with wire mesh. A
G.I. strip is fixed to the electrode to act as an earthing connection. For rod
earthing, a copper rod of required diameter is used in place of the pipe.
Fill the annular space between the electrode and borehole walls with
alternating layers of coke or charcoal and common salt.
Inspection chamber: Construct brick chamber of size 450 x 450 x 450 mm
with 100 mm thick brick walls over a P.C.C. layer. Keep 100 mm of the
chamber above ground level. Cover the top with a cast iron (CI) cover.
Follow the approved design and drawing for fixing and laying of earth wires
or GI/copper strips between the earth electrode and the electrical room.
Comparison between pipe and plate earthing:
Reference:
1. “Principles of Power System” by [Link], Rohit Mehta, S Chand & Co Ltd, 2005
2. [Link]
Module 5: Industrial Electrical Systems II
DG System
Components of Micro-Grid:
(1) Distributed Generator: is an electric power source connected directly to the
distribution network or on the customer side of the meter to fulfil the power
demand. This DG may be of any rating/size depending upon various factors. Also
it may be either conventional or non-conventional type of power source. Some of
the examples are Wind Power, Solar PV, Solar Thermal, Natural Gas, Bio Gas, Fuel
Cell, Combined Heat & Power, and Micro Turbine.
(2) Load Centre: the power generated from distributed generator shall be
distributed to the load centre for the utilization.
(3) Electric Power Storage: Microgrid can have storage as backup while operating
in stand-alone mode of operation. When there is renewable source of power,
excess power from renewable (after the load demand is fulfilled), can be stored
in batteries. This can then be used as backup when needed. Therefore, the
electric power storage in microgrid is able to improve the power quality,
flexibility and reliability by providing grid support functions. The electric power
storage system may be classified as Electrochemical: Battery (Lead Acid, Li-ion);
Electromagnetic: Super Capacitor, Super Conductor; Mechanical: Pumped
Hydro, Compressed Air, Flywheel; Chemical: Hydrogen, Synthetic Natural Gas;
and Thermal: Water Tank.
(4) Controller: Control unit is one of major component of microgrid. The flow of
power from generation to the load centers should be monitored, controlled and
managed properly. Even before, the generation of electric power must have
controller to maintain power quality (voltage, frequency and sin wave within
limit).
(5) Point of common coupling: A micro-grid can be connected or disconnected
from the grid to enable it to operate from either disconnected or islanded mode
thus preventing power outage. It may be connected or disconnected from point
of common coupling, which is basically a power electronic interface.
The purpose of DG is to provide Active Power. According to the
definition, a DG is not able to provide only reactive power.
If an energy source generating active power only……..may
only…….. be
considered as DG
If an energy source generating active and reactive power
both……may
may be considered as DG
If an energy source generating reactive power only…………..cannot
only………….. be
considered as DG
DG
1 Watt to 5 kW to 5 5 MW to 50 MW to
5 kW MW 50 MW 300 MW
Classification from electrical point of view: This will help to study their
impact on the electric system. Different classifications can be obtained to
differentiate between DG types according to their electrical applications,
supply duration, generated power types, electric ratings and renewable and
non-renewable technologies. Several types of DG classification are
mentioned below:
(i) Standby: DG can be used as a standby to supply the required power
for sensitive loads, such as process industries and hospitals, during
grid outages.
(ii) Stand alone: Usually, isolated areas use DGs as a power provider
instead of connecting to the grid. These areas have geographical
obstacles, which make it expensive to be connected to the grid.
(iii) Peak load shaving: The electric power cost varies according to the
load demand curves and the corresponding available generation at
the same time. Hence, DGs can be used to supply some loads at peak
periods, which reduce the electricity cost for large industrial
customers who used to pay time-of-use rates (TOU).
(iv) Rural and remote applications: DG can provide the stand-alone
remote applications with the required power. These applications
include lighting, heating, cooling, communication, and small
industrial processes. Even more, DGs can support and regulate the
system voltage at rural applications (sensitive loads) connected to the
grid.
(v) Providing combined heat and power (CHP): DGs providing CHP as a
cogeneration has a high overall energy utilization efficiency. The
produced heat, from converting fuel into electric power process, is
used onsite for a wide range of applications in hospitals, large
commercial areas and process industries.
(vi) Base load: Utility owned-DGs are usually used as a base load to
provide part of the main required power and support the grid by
enhancing the system voltage profile, reducing the power losses and
improving the system power quality.
Non-Fossil
Fossil Fuels
Fuels
Technology
Technology
(iv) Cooling system: The heat released by the burning of fuel in the engine cylinder is
partially converted into work. The remainder part of the heat passes through the
cylinder walls, piston, rings etc. and may cause damage to the system. In order to keep
the temperature of the engine parts within the safe operating limits, cooling is provided.
The cooling system consists of a water source, pump and cooling towers. The pump
circulates water through cylinder and head jacket. The water takes away heat form the
engine and itself becomes hot. The hot water is cooled by cooling towers and is
recirculated for cooling.
(v) Lubricating system: This system minimizes the wear of rubbing surfaces of the
engine. It comprises of lubricating oil tank, pump, filter and oil cooler. The lubricating oil
is drawn from the lubricating oil tank by the pump and is passed through filters to
remove impurities. The clean lubricating oil is delivered to the points which require
lubrication. The oil coolers incorporated in the system keep the temperature of the oil
low.
(vi) Engine starting system: This is an arrangement to rotate the engine initially, while
starting, until firing starts and the unit runs with its own power. Small sets are started
manually by handles but for larger units, compressed air is used for starting. In the
latter case, air at high pressure is admitted to a few of the cylinders, making them to act
as reciprocating air motors to turn over the engine shaft. The fuel is admitted to the
remaining cylinders which makes the engine to start under its own power.
(vii) Alternator: Alternator is salient pole type synchronous generator, self excited and
self regulated by an excitation unit. The excitation unit consists of choke, CT, diodes and
condenser. Voltage is adjustable to within 2.5% of the nominal voltage from no-load to
full load at rated pf. The choke is meant for adjusting the terminal voltage at no load. The
CT is meant for adjusting the terminal voltage at load condition.
Sizing of a DG Set
(a) If the DG set is required for 100% standby, then the entire connected load in HP /
kVA should be added. After finding out the diversity factor, the correct capacity of a DG
set can be found out.
Example :
Connected Load = 650 kW
Diversity Factor = 0.54
(Demand / connected load)
Max. Demand = 650 x 0.54 = 350 kW
% Loading = 70
Set rating = 350/0.7 = 500 kW
At 0.8 PF, rating = 625 kVA
(b) For an existing installation, record the current, voltage and power factors (kWh /
kVAh) reading at the main bus-bar of the system at every half-an-hour interval for a
period of 2–3 days and during this period the factory should be having its normal
operations. The non-essential loads should be switched off to find the realistic current
taken for running essential equipment. This will give a fair idea about the current taken
from which the rating of the set can be calculated.
(c) For a new installation, an approximate method of estimating the capacity of a DG set
is to add full load currents of all the proposed loads to be run in DG set. Then, applying a
diversity factor depending on the industry, process involved and guidelines obtained
from other similar units, correct capacity can be arrived at.
Reference:
1. Distributed generation: a definition, Thomas Ackermann, Goran Andersson,
Lennart Soder, Electric Power Systems Research 57 (2001) 195–204, 05
December 2000
2. “Principles of Power System” by [Link], Rohit Mehta, S Chand & Co Ltd, 2005
3. [Link]
UPS & Battery System
An Uninterruptible Power Supply (UPS) is defined as a piece of electrical
equipment which can be used as an immediate power source to the
connected load when there is any failure in the main input power source.
So, the prime role of UPS is to supply power for a short time when there is
any failure in main power source.
Types of UPS
(i) Standby UPS/Offline UPS
(ii) Hybrid/ Ferroresonant UPS
(iii) Line Interactive UPS
(iv) Online UPS
(i) Standby UPS/Offline UPS: It is the most common type of UPS system used
on a day to day basis for our personal and office computers.
Design: Here, the primary source is the filtered AC mains. The input line
voltage is routed through a surge suppressor, filter, and transfer switch
before finally being routed to the output of the UPS device.
Fig 5: (a) 12V, 18AH, VRLA Gel Type Battery (b) Battery Bank
Most commonly used batteries (at home for UPS) are usually of the sealed
lead acid or gel cell type which prevents spilling of any dangerous and
harmful chemicals from inside the battery into the UPS device itself. If the
acids from inside the battery leaked out into the device cabinet they would
destroy the electronic components inside the system rendering it useless.
Other than the internal make up of the battery they can differ in two other
ways.
The first is the actual physical size of the battery. Most are shaped like
the battery in figure 5 above, but the dimensions of length, width, and
height can be almost any combination.
Another key specification of the battery is its current capacity. This is
usually rated in milliamp-hours/amp-hours. The amp hour rating tells
the amount of current the battery will supply in an hour. Example: If
the current capacity of a battery is 20 amp hour and the load is drawing
0.5 amps then this battery is able to supply its rated voltage to the load
for 40 hours.
Three stages of the battery charging is: (i) Normal or Bulk stage (ii)
Absorption/Equalization stage and (iii) Float stage.
Bulk/ Normal stage: It is the initial portion of a charging cycle performed
at any charge rate and it involves 80 % state of charge, hence called bulk
stage of charging. In this case the charger current is held constant (in a
constant current charger), and voltage increases. The properly sized
charger will give the battery as much current as it will accept up to charger
capacity.
Absorption/Equalization stage: The absorption/equalization has the
charger holding the voltage and decreasing the current until the battery is
charged nearly up to 95-97%. The portion of charging cycle covered in this
stage is called “cool-down” cycle.
Float Stage: The float stage is where the charge voltage is reduced and held
constant, while the current is reduced to less than 1% of battery capacity
(i.e supplying steady current). This mode can be used to maintain a fully
charged battery indefinitely. At that time, the charger will continue to
monitor the battery and apply a charge if it detects any loss.
Battery Discharging
Depth of Discharge (DOD): It is defined as the percentage of capacity that
has been withdrawn from a battery compared to the total fully charged
capacity. OR, Depth of Discharge is defined as the total amount of energy
that is discharged from a battery, divided by the battery nominal capacity.
Depth of discharge is normally expressed as a percentage.
Example: If a 90 Ah battery is discharged for 20 minute at a constant
current of 50 A, then find the value of depth of discharge.
Ans: DoD = (50 amps * (20 mins / 60 mins) / 90Ah
= (50A * 0.33333h)) / 90Ah
= 16.67Ah / 90Ah = 0.18522 can be written as 18.522%
State of Charge (SOC): The state of charge (SOC) is defined as the amount
of energy as a percentage of the energy stored in a fully charged battery.
Discharging a battery results in a decrease in state of charge, while charging
results in an increase in state of charge. Ex: If a battery that has had three
quarters of its capacity removed, or been discharged 75 %, is said to be at
25 % state of charge.
…………………………………………………………………………………………………
PLCs are widely used in a variety of industries because they’re fast, easy to
operate and are considered easy to program. PLCs can be programmed in
several ways, from ladder logic, which is based on electromechanical relays, to
specially adapted programming languages of BASIC and C. Most PLCs today
use one of the following 5 programming languages: Ladder Diagram, Structured
Text, Function Block Diagram, Instruction List, or Sequential Function Charts.
PLC act as the physical interfaces between device on the plant or manufacturing
floor and a SCADA system. PLCs communicate, monitor and control automated
processes like assembly lines, machine functions, or robotic devices.
Programming the PLC is easier than wiring physical components; the only
wiring required is that of connecting the I/O terminals.
The PLC can be reprogrammed using user-friendly programming devices.
Controls must be physically rewired.
PLCs take up much less space.
Installation and maintenance of PLCs is easier, and in present day reliability
is grater compared with solid-state technology.
The PLC can be connected to a distributed plant automation system,
supervised and monitored.
Ability of PLCs to accept digital data in serial, parallel and network modes
imply a drastic reduction in plant sensor and actuator wirings, since single
cable runs to remote terminal I/O units can be made. Wiring only need to be
made locally from that point
Application of PLC:
Logic/Sequence control
PID control and computing
Coordination and communication
Operator control and monitoring
Plant start-up, shut-down
A PLC’s functions are divided into three main categories: inputs, outputs and the CPU. PLCs
capture data from the plant floor by monitoring inputs that machines and devices are
connected to. The input data is then processed by the CPU, which applies logic to the data,
based on the input state. The CPU then executes the user-created program logic and outputs
data or commands to the machines and devices it is connected to.
Central Processing units
The CPUs are generally micro programmed processors sometimes capable of handling
multiple data width of either 8, 16 or 24 bits. In addition sometimes additional circuitry is
provided, since much of the computing involves logical operations involving digital inputs
and auxiliary quantities. Memory with battery backup is also provided for the following:
A. Direct program entry to the program memory (RAM) plugged into the central controller.
For this purpose, the programmer is connected to the processor or to the programmer
interface modules.
B. Programming the EPROM sub modules in the programmer without connecting it to the PC
(off-line). The memory sub modules are then plugged into the central controller.
Other units such as Power Supply Units (mainly 24 V DC), Bus Units etc. can also be
connected to the PLC system.
PLCs operate in cycles. First, the PLC detects the state of all input devices that are connected
to it. The PLC applies the user-created logic, and then executes it based on the input
states. The PLC then outputs commands to any output device connected to the PLC either
turning them on or off. The PLC resumes the cycle each time the process is completed.
Need of programmable logic controller (PLC) in automation:
1. PLCs are similar to industrial computers. PLCs can work as standalone units that can
continuously monitor and automate a process. PLCs can be networked; such a network can
control an entire production line. PLCs can be adapted to monitor and control many sensors
and actuators; they process electrical signals and use them to carry out preprogrammed
commands for almost any application. PLCs are used in industrial automation to increase
reliability, system stability and performance, minimizing the need for human operators and
the chances of human error.
2. PLC is used in the fully automated industries or plants or process, the actual processes
handled and controlled by the controllers which are nothing but the programming logic
controllers that means PLC plays a very important role in automation section.
2. PLCs constantly monitor the state of the systems through input devices and generate the
control actions according to the logic given in the user program.
3. It is a heart of control systems, PLC monitors the state of the system through field input
devices, feedback signals and based on the feedback signal PLC determine the type of action
to be carried out at field output devices.
4. PLC provides easy and economic solution for many automation tasks like
Operates control and monitoring
Co-ordination and communication
PID computing and control
Logic / sequence control
Industrial Automation
Industrial Automation is a process of operating machines and other industrial equipment with
the help of digital logical programming and reducing human intervention in decision making
and manual command process with the help of mechanized equipment. The automation
process typically uses devices such as PLCs, PCs, PACs, etc. and various types of industrial
communication technologies.
Some of the examples of automated industrial processes are:
Packaging and material handling
Quality control and inspection
Metal fabrication; machining, welding, cutting, cladding etc.
Food and beverage processing
Planning and decision making
Industrial Automation Advantages
Reduction in production time – having a machine that is automated definitely speeds
up the production time since no thinking is needed by the machine; there is better
repeatability, and less human error.
Increase in accuracy and repeatability – when an automated machine is programmed
to perform a task over and over again, the accuracy and repeatability compared to an
employee is far greater.
Less human error – no one is perfect, and we are all prone to making mistakes. Which
is why a machine that performs repeated tasks is less likely to make mistakes than an
employee?
Less employee costs – by adding automated machines to an operation, means less
employees are needed to get the job done. It also indicates less safety issues, which
leads to financial savings. With having less employees, there are numerous costs that
are diminished or reduced such as payroll, benefits, sick days, etcetera.
Increased safety – having automated machines means having fewer employees who
perform tasks that can be dangerous and prone to injury, which can make the work
environment safer.
Higher volume production – investing in automated equipment creates a valuable
resource for large production volumes, which in turn, will increase profitability.
Key factors to consider when selecting motors for industrial applications include: 1. **Load Type**: Understanding if the motor will handle continuous, intermittent, or variable loads is crucial. Continuous loads require constant power input, whereas intermittent and variable loads need motors with suitable rating to prevent overheating . 2. **Starting Torque and Speed Control**: Motors should have adequate starting torque to handle the initial power surge demands of the application. For example, a high starting torque is necessary for applications like elevators . Speed control capabilities may also dictate motor choice depending on whether constant or variable speed is required . 3. **Electrical Characteristics**: It's essential to match the motor's electrical characteristics, such as starting and running characteristics, speed control, and braking, with the application's requirements . 4. **Mechanical Considerations**: The type of enclosure, bearings, power transmission method, cooling type, and noise level should align with the working environment's demands . 5. **Size and Rating**: Choosing the correct size and rating of motors based on the required load cycle and overload capacity prevents inefficiency and potential overheating . 6. **Cost**: Both capital and operational costs should be factored into the decision, including potential efficiency losses if the motor's KW rating is higher than needed . 7. **Motor Type**: Depending on the application, specific types of motors, such as DC motors for high starting torque or AC motors for rugged simplicity, might be preferred .
Offline or Standby UPS systems provide power to equipment from a battery only when the main power fails, offering simplicity and efficiency, making them suitable for personal and office computers . Line Interactive UPS continuously keeps the inverter/converter connected, reducing switching time during power failures, benefiting small business servers by providing better transition times than standby systems, although some transition time still occurs . Online UPS systems, also known as "true" UPS, provide continuous, clean power without interruption by using a double conversion process with no switching time delay during power outages, making them ideal for critical equipment requiring constant power quality, though they consume more power and are costlier .
The main advantage of an Online UPS is its ability to provide total isolation between input and output voltages, resulting in zero switching time during a power failure, preventing any interruption to connected devices . This contrasts with other UPS types like Standby and Line Interactive, which have longer switching times and some interruption when switching from main power to battery . However, the Online UPS is generally more expensive due to its continuous operation of double conversion processes, which demand higher quality and more reliable components like the charger, inverter, and battery. This double conversion process also leads to higher power consumption and heat generation, affecting overall efficiency .
A line interactive UPS system incorporates an inverter/converter assembly that is continuously connected to the output, reducing the switching time during power failures compared to a standby UPS. The continuous connection allows for a quicker transition to battery power, whereas a standby UPS relies on a transfer switch that only activates during a power interruption, causing longer switch times .
Fuses are used in electrical protective systems primarily for their simplicity and automatic operation for low-voltage circuits, where they protect by melting and breaking a circuit when excessive current flows. They are cost-effective, require no maintenance, and operate automatically without external control. However, replacing them can be time-consuming as they need to be physically replaced after they blow out . Relays, on the other hand, are used in conjunction with circuit breakers for high-voltage circuits. They detect faults and initiate the tripping of a circuit breaker to isolate faulty elements from the system. This is essential for quick disconnection and system protection without manual intervention, preventing fault effects from spreading and minimizing damage . Unlike fuses, relays are critical for handling higher complexities and rapid response required in more sophisticated and automated systems . In summary, fuses are simpler, self-contained protective devices suited for low-voltage applications, whereas relays are used for precise fault detection and action in high-voltage systems, often in combination with circuit breakers.
Gearless driving machines for elevators offer several benefits over geared machines. Gearless machines are typically used for high-speed applications and do not require a mechanical speed reduction unit, allowing them to operate more efficiently at speeds between 2.5 m/s to 10 m/s, while supporting the direct connection of the drive motor and drive sheave . This design is optimal for high-rise buildings due to its capability of handling higher speeds and smooth operation. In contrast, geared machines include a mechanical speed reduction gear set, making them more suitable for lower speeds between 0.1 m/s and 2.5 m/s and often used in low and mid-rise applications . Additionally, the lack of a gear system in gearless machines reduces maintenance requirements and potential points of mechanical failure, improving reliability and reducing the long-term operational costs of elevators .
A DC series motor is typically chosen over a squirrel cage induction motor in applications requiring high starting torque and variable speed, such as in electric locomotives, steel rolling mills, hoists, lifts, and cranes. Its ability to handle heavy-duty applications with varying speed demands makes it more suitable than a squirrel cage motor, which is better for constant speed applications and lacks the same level of torque flexibility .
Programmable Logic Controllers (PLCs) are integral to industrial automation as they enable the automation of electromechanical processes. PLCs use a programmable memory to implement logic sequences, timing, counting, and arithmetic functions. They monitor input devices and control output devices based on custom programs, thus facilitating the seamless operation of manufacturing plants, industrial machinery, and other automated environments .
A cumulative compound motor is preferred in scenarios requiring both variable speed and high starting torque, such as in driving compressors, variable-head centrifugal pumps, rotary presses, circular saws, shearing machines, elevators, and continuous conveyors. Its capability to provide high starting torque and adapt to different load conditions makes it suitable for applications requiring robust and flexible performance .
Smart meters improve communication and reduce the need for physical visits by automatically sending data on energy consumption to utility companies. This is achieved through a two-way communication system that allows real-time data collection, which eliminates the need for manual meter readings . Additionally, the automated transmission of data enhances accuracy and reduces human error associated with estimating energy usage, thus streamlining the billing process without requiring monthly on-site visits .