Product Specification
37954

IKD-OUT-16 Unique Features


IKD-OUT-16  16 configurable relay outputs
 plug-n-play connection with Wood-
ward power management controls
 easy integration with PLC
 compact remote I/O with IKD-IN-16
 Shorter lead time

Digital Output Expansion Module  Flexible remote output


module. Works with
DESCRIPTION
 Woodward power
management controls
The IKD-OUT-16 is a smart solution to increase number of digital outputs to Woodward power
management controllers or apply it as a remote output module in your PLC based control system. It  PLC
is possible to connect one or more IKD-OUT-16 modules (see table Related Products below).

The IKD-OUT-16 output relays are controlled over the CAN bus connection from the main control-
 16 relay outputs FORM C
ler. Configuration is performed through the LogicsManager in the main controller and transmitted to
the IKD. It requires no configuration tool as few parameters such as module address and CAN  Requires no
baud rate can be setup by onboard DIP switches. configuration tool

FEATURES  CAN bus communication


 16 configurable FORM C relays with potential free contacts
 CAN bus communication to the higher-level controller
 CE/UKCA marked
 The control unit sends commands via the CAN bus to remotely control the output relays
 The IKD-OUT-16 can be used with other manufacturer's controllers/PLCs. Consult product
manual 37952 for information regarding the CAN bus data telegram  UL/cUL pending
 DIP switches to configure device module number and CAN baud rate.
 Power LED to indicate state of the device (CPU OK)

Ordering Part Number


 8440-2305
Released

SPECIFICATIONS
Power supply .............................................................24 VDC (19 to 35 VDC) CAN Interface .................................................................................... isolated
Intrinsic consumption ................................................................. max. 5 W Insulation voltage (continuous) ....................................................... 2500 V DC
Reverse voltage protection ................................................................. Yes Version ............................................................................................ CAN bus
Internal line termination ....................... no (120 Ohm to be wired externally)
Ambient temperature (operation) .................... -25 to 70 °C / -13 to 158 °F
Ambient temperature (storage) ...................... -30 to 80 °C / -22 to 176 °F Housing DIN-rail mounting .................................................... Plastic housing
Ambient humidity..................................................... 93%, non-condensing Dimensions WxHxD ................................... 161.6 × 89.7 × 60.7 mm
Connection ..................................................... screw-plug-terminals 2.5 mm²
Relay outputs .................................................................................isolated Protection system .................................................................................. IP20
Contact material ........................................................................... AgSnO2 Weight ......................................................................................approx. 600 g
Load (GP)..................................................................................... 7.00A DC Disturbance test (CE) ............ tested according to applicable IEC standards
Pilot duty (PD) ......................................................................... 7A@28V DC Listings .................................................................. CE, UKCA, UL(Pending)

DIMENSIONS
Released

TERMINAL DIAGRAM

RELATED PRODUCTS
 Supported power management controls
Max. # of IKD-OUT-16
easYgen-3000XT (GC-3400XTP1) 2 (1)
easYgen-3400/3500P1 and -3100/3200P2 2
easYgen-3400/3500P2 and -3100/3200P1 1
easYgen-2000 1
easYgen-1500/1700/1800 1
easYgen-800 1
DTSC-200 and -200A 1
 Digital input expansion module IKD-IN-16 (Product spec #37955): P/N 8440-2304
 Digital I/O expansion module IKD 1 (Product spec #37171): P/N: 8440-2116
Released

TYPICAL APPLICATION

CONTACT The control device’s relay manager (LogicsMan-


agerTM) controls the IKD-OUT-16 relays. The control
North & Central America
Tel.: +1 (208) 278 3370 logic for each IKD-OUT-16 relay can be pro-
grammed individually in the control device. Logical
South America
Tel.: +55 19 3708 4800 commands can be configured using internal events
as well as the status of the digital inputs coming
Europe V~
Tel.: +49 711 78954 510 from the IKD-IN-16 or IKD 1or supported 3rd party
Middle East & Africa I~ remote input modules.
Tel.: +971 2 678 4424

Russia
Tel.: +49 711 78954 515
Load

China
Tel.: +86 512 8818 5515

India V~
Tel.: +91 124 4399 500
e.g.
ASEAN & Oceania easYgen-3200XT
Tel.: +49 711 78954 510

V~
SALES SUPPORT
 [Link] PG@[Link] I~

TECHNICAL SUPPORT

G
CAN bus

 [Link]@[Link] V/Q

[Link]
/n/Vbatt/..
Start/Stop
n/f/P
Subject to alterations, errors excepted.

Subject to technical modifications. IKD-OUT-16


#1
This document is distributed for informa-
tional purposes only. It is not to be con- IKD-OUT-16
strued as creating or becoming part of #2
any Woodward Company contractual or
warranty obligation unless expressly
stated in a written sales contract.

We appreciate your comments about the


content of our publications. Please send
comments including the document num-
ber below to
stgt-doc@[Link]
© Woodward
All Rights Reserved

 Product documentation site, [Link]


For more information contact:

37954 - 2022/11/Stuttgart

You might also like