Doc.

Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 1 of 6

Title: : ‫ﻋﻨﻮان‬

Neutral Groun
unding Resistor Test Procedur
edure

 

Revision
‫ﺗﺎرﯾﺦ‬
Rev ‫وﯾﺮاﯾﺶ‬
Date ‫وﯾﺮاﯾﺶ‬ tion:
Descripti :‫ﺗﻮﺿﯿﺤﺎت‬ Compiled Checked Approved
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 2 of 6

Table of Contents

Scope …….………………………
………………………………………………………
……………….... 03
Reference Documents………… ……………… 03
…………………………………………………………
Nomenclatures……………………
………………………………………………………
……………………... 04
Test Procedure………………………
……………………………………………………….
……...……… 05
1- Visual and Dimensionall Check
C ……………………………………………… ………..……….. 05
2- Tes ………………………………………………
Resistance Measurementt Test …………………. 05
3- istance Test (Megger Test) …………………………
Primary Insulation Resist ………………. 05
4- wer Frequency Withstand Tests …………...……
Rated Short Duration Power …...………………... 06
5- Lifting Secondary Insulattion Resistance Test (Megger Test) ...……………………………… 06
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 3 of 6

Scope
This document provides the routine test procedure of the Neutral Ground ding resistors
(NGRs). The routine test contains
ontains both electrical and visual check tests.

Reference Document

 ANSI/IEEE–32, 1972 72, “Requirements, Terminology, and Test Procedure


P for
Neutral Grounding
nding Devices”.
De
 IEC 60071–1, “Insulation
sulation Co-ordination”.
Co
 ANSI/NETA ATA, A, “Standard for Acceptance Testing Specif
Specifications for
Electrical Power Equipm
quipment and Systems”.
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 4 of 6

Nomenclatures:
Frame earth: The overall frame or enclosure which is conn
connected to the
earth.
Tie rods: Individual frame of each resistor blocks.
Megger test: Measurement of insulation resistance of compo
ponents
Power frequency withstand
d A dielectric test in which the voltage is a low
l frequency
test: alternating voltage from an external source applied
ap between
conducting parts and between conducting partts and ground

The overall test procedures are defined


d as follows:

1- Visual and Dimensionall C Check


2- Resistance Value Test
3- Insulation Resistance Tes
est
4- Power Frequency Withstan tand Test
5- Insulation Resistance Tes
est
6- Incoming & Outgoing cabcable connection & integrity of Terminal box connecti
tions

The sufficient explanation of each


ea section is presented in the rest of the document.
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 5 of 6

1- Visual and Dimension


onal Check
1-1- Confirm Overall dim dimension is in accordance with the latest revisionn of applicable
drawing.
1-2- Confirm integrity of all resistor connections.
1-3- Confirm all componponents are correctly installed and connected in accord
cordance with the
latest revision of applica
plicable drawing.
1-4- Confirm paint (or other
oth coverage) of Enclosure has not been damage.
1-5- Confirm accuracy & fixing of name plates and labels.

2- Resistance Measureme
ment Test
2-1- Using a digital ohmm meter check and record the value of DC resistance ance at ambient
temperature and correc
rrect its value to specified temperature. According to the IEEE-32-
1972, Sec 10.1.4, accept
eptance tolerance in the lack of customer request is ±10%.
±10

3- Primary Insulation Resistance


Res Test (Megger Test)
3-1- Using a digital insulatiion test, apply acceptance DC voltage between thee resistor H.V.
connection and individua
idual resistor bank tie rods regarding the ANSI/NETTA ATS Table
100.1. Minimum acceptaptance value is obtained from the Table 100.1.
3-2- Repeat test (3-1) betwee
een H.V. connection and frame earth with acceptance
ance DC voltage
according to the ANS SI/NETA ATS Table 100.1. This test checks the th integrity of
secondary insulation materials.
m Minimum acceptance value is obtained from the Table
100.1.

4- Rated Short Duration


on Power Frequency Withstand Tests (1
1 Minute)
Remove the connecting link bettween the resistor and any base point and/or LV connect
nnection.

4-1- Using a suitable externa


rnal source, apply the specified voltage between terminals and
ground for the completee device extracted from IEC 60071-1 Table 2.
4-2- Using a suitable extern
nal source according to the IEEE-32-1972, Sec. 10.3.2
10 apply the
specified voltage between
een terminals of each unit and its own individual frame.
fram

Note: The voltage applied from


rom the terminals of each assembly to its own framee shall
sha be:
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :‫ﻧﺎم ﻣﺪرك‬

Construction & Engineering Project: :‫ﻧﺎم ﭘﺮوژه‬ Customer: :‫ﻣﺸﺘﺮي‬


‫ﺷﺮﮐﺖ ﻣﻬﻨﺪﺳﯽ و ﺳﺎﺧﺖ ﭘﺎرﺳﺎن‬
(‫)ﻣﺴﺌﻮﻟﯿﺖ ﻣﺤﺪود‬ Date:
Doc. No: IQ – 15 – 0008
Rev.: 00 Page:
P 6 of 6

 oltage of the section of which the frame is a part plus 1000V when
Twice the rated vol
2V p
rated 600V or less. Vrmsapplied  kV    1000
N

 2.25 times the rated value plus 2000V when rated over 600V.
2.25V p
Vrms  applied  kV    2000
N

In the event of a retest the voltage


v shall be 80% of the original test voltage.

5- Secondary Insulation
n Resistance Test (Megger Test)
To ensure that the insulations interval in the section (3) isn’t damaged, again the same test is
applied.

ation test apply acceptance DC voltage between the


5-1- Using a digital insulation he resistor H.V.
connection and individua
idual resistor bank tie rods regarding the ANSI/NET
TA ATS Table
100.1. Minimum accepteptance value is obtained from the Table 100.1.
5-2- Repeat test (3-1) betwee
een H.V. connection and frame earth with acceptance
ance DC voltage
according to the ANS SI/NETA ATS Table 100.1. This test checks the th integrity of
secondary insulation materials.
m Minimum acceptance value is obtained from the Table
100.1.

6- Incoming & Outgoing


ng cable connection & integrity of Terrminal box
connections
6-1- Check dimension,, distance
di and integrity of terminals in relation to final drawings.
d