NGR Testing Procedure Overview
NGR Testing Procedure Overview
Name
ame: Neutral Grounding Resistor Test Pro
rocedure :ﻧﺎم ﻣﺪرك
Title: : ﻋﻨﻮان
Neutral Groun
unding Resistor Test Procedur
edure
Revision
ﺗﺎرﯾﺦ
Rev وﯾﺮاﯾﺶ
Date وﯾﺮاﯾﺶ tion:
Descripti :ﺗﻮﺿﯿﺤﺎت Compiled Checked Approved
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :ﻧﺎم ﻣﺪرك
Table of Contents
Scope …….………………………
………………………………………………………
……………….... 03
Reference Documents………… ……………… 03
…………………………………………………………
Nomenclatures……………………
………………………………………………………
……………………... 04
Test Procedure………………………
……………………………………………………….
……...……… 05
1- Visual and Dimensionall Check
C ……………………………………………… ………..……….. 05
2- Tes ………………………………………………
Resistance Measurementt Test …………………. 05
3- istance Test (Megger Test) …………………………
Primary Insulation Resist ………………. 05
4- wer Frequency Withstand Tests …………...……
Rated Short Duration Power …...………………... 06
5- Lifting Secondary Insulattion Resistance Test (Megger Test) ...……………………………… 06
Doc. Name
ame: Neutral Grounding Resistor Test Pro
rocedure :ﻧﺎم ﻣﺪرك
Scope
This document provides the routine test procedure of the Neutral Ground ding resistors
(NGRs). The routine test contains
ontains both electrical and visual check tests.
Reference Document
Nomenclatures:
Frame earth: The overall frame or enclosure which is conn
connected to the
earth.
Tie rods: Individual frame of each resistor blocks.
Megger test: Measurement of insulation resistance of compo
ponents
Power frequency withstand
d A dielectric test in which the voltage is a low
l frequency
test: alternating voltage from an external source applied
ap between
conducting parts and between conducting partts and ground
2- Resistance Measureme
ment Test
2-1- Using a digital ohmm meter check and record the value of DC resistance ance at ambient
temperature and correc
rrect its value to specified temperature. According to the IEEE-32-
1972, Sec 10.1.4, accept
eptance tolerance in the lack of customer request is ±10%.
±10
oltage of the section of which the frame is a part plus 1000V when
Twice the rated vol
2V p
rated 600V or less. Vrmsapplied kV 1000
N
2.25 times the rated value plus 2000V when rated over 600V.
2.25V p
Vrms applied kV 2000
N
5- Secondary Insulation
n Resistance Test (Megger Test)
To ensure that the insulations interval in the section (3) isn’t damaged, again the same test is
applied.