2170963 DATA SHEET
valid from: ETHERLINE LAN 500 Cat.6A F/UTP LSZH
18.08.2022 4x2x23/1 AWG
Application
Field of use: Installation cable for generic cabling systems acc. to
ISO/IEC 11801 and EN 50173
Performance: Bandwidth up to 500 MHz acc. To IEC 61156-5 Category 6A and
applications up to 10GBase-T
Characteristics: halogen free, flame retardant and largely resistant to acids, alkalis
and certain oils
Applications: PROFINET, EtherCAT, EtherNet/IP, PoE (IEEE 802.3af), PoE+
(IEEE 802.3at) and many other
Design
Certification EN 13501-6 and EN 50575 Classification of fire behaviour
Conductor solid bare copper
23/1 AWG
Insulation Polyethylene
core Ø: ca. 1.09 mm
Core identification code pair 1: white/blue, pair 2: white/orange,
pair 3: white/green, pair 4: white/brown
Stranding 2 cores stranded to pair,
4 pairs stranded to bundle with central separating element
Screen plastic laminated aluminium foil (overlapping) with tinned copper drain wire
Outer sheath LSZH
orange, similar RAL 2003
outer diameter: 7.4 mm (± 0.3 mm)
dlsafjl öjf
Electrical properties at 20 °C
Loop resistance max. 16.0 Ω/100 m
Insulation resistance min. 5 GΩ x km
Mutual capacitance nom. 50 nF/km
Coupling attenuation > 55 dB (30 MHz - 500 MHz)
Characteristic impedance nom. 100 Ω acc. to IEC 61156-5
Velocity of propagation 0.66 c
Signal propagation time ≤ 510 ns/100 m
Delay skew ≤ 40 ns/100 m
Maximum operating voltage 100 V (not for ower purposes)
Test voltage core/core: 1000 V
Creator: KIOS / PDC Document: DB2170963EN
Page 1 of 2
Released: ALTE / PDC Version: 03
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN
2170963 DATA SHEET
valid from: ETHERLINE LAN 500 Cat.6A F/UTP LSZH
18.08.2022 4x2x23/1 AWG
Electrical transmission properties at 20°C
The transmission characteristics meet the requirements of the standards EN 50288-10-1 and IEC 61156-5 for category 6A.
The normative requirements for the transmission properties are shown in the following table:
f [MHz] 4 10 20 62,5 100 200 250 500
(max.) Attenuation [dB/100 m] 3,8 5,9 8,4 15 19,1 27,6 31,1 45,3
(min.) TCL [dB] 34 30 27 22 20 17 16 ---
(min.) EL TCTL [dB/100 m] 23 15 9 --- --- --- --- ---
(min.) NEXT [dB] 66,3 60,3 55,8 48,4 45,3 40,8 39,3 34,8
(min.) PS EL FEXT [dB/100 m] 53 45 39 29,1 25 19 17 11
(min.) ACR-F/EL FEXT [dB/100 m] 56 48 42 32,1 28 22 20 17
(min.) Return Loss [dB] 23 25 25 21,5 20,1 18 17,3 17,3
Mechanical and thermal properties
Minimum bending radius fixed: 4x outer diameter
occasional flexing: 8x outer diameter
Temperature range fixed: -20 °C up to +60 °C
occasional flexing: 0 °C up to +50 °C
Flammability flame retardant acc. to IEC 60332-1-2 resp. EN 60332-1-2
Halogen free acc. to IEC 60754-1 resp. EN 60754-1
Corrosivity of gases acc. to IEC 60754-2 resp. EN 60754-2
Smoke density acc. to IEC 61034 resp. EN 61034
. ..
General requirements This cable is conform to the EU-Directive 2011/65/EU (RoHS, Restriction of the use of certain
hazardous substances) and the LV-Directive 2014/35/EU (Low voltage Directive).
This cable is classified in accordance with the EU-Regulation no. 305/2011 (CPR).
Environmental information These cables meet the substance-specific requirements of the EU Directive 2011/65/EU
(RoHS).
. .
Creator: KIOS / PDC Document: DB2170963EN
Page 2 of 2
Released: ALTE / PDC Version: 03
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN