EMX3 User Manual
EMX3 User Manual
Soft Starter
User Manual
Contents
Section 6 Operation..................................................................................................................................................................................23
6.1 Start, Stop and Reset Commands................................................................................................................................................................... 23
6.2 Soft Start Methods................................................................................................................................................................................................... 23
6.3 Stop Methods ............................................................................................................................................................................................................. 26
6.4 Jog Operation.............................................................................................................................................................................................................. 28
Section 8 Troubleshooting.....................................................................................................................................................................56
8.1 Trip Messages.............................................................................................................................................................................................................. 56
8.2 Protection Responses............................................................................................................................................................................................. 57
8.3 General Faults ............................................................................................................................................................................................................. 58
This symbol is used throughout this manual to draw attention to topics of special importance to the
installation and operation of EMX3 soft starters.
Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of
damage. It is the installer's responsibility to follow all instructions in this manual, to follow good electrical practice and
to seek advice before operating this equipment in a manner other than as described in this manual.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in
this manual is subject to change at any time and without prior notice. In no event will responsibility or liability be
accepted for direct, indirect or consequential damages resulting from the use or application of this equipment.
SHORT CIRCUIT
EMX3 soft starters are not short circuit proof. After severe overload or short circuit, the
operation of the soft starter should be fully tested.
Section 2 Installation
1 Two-wire control
2 Three-wire control
3 Four-wire control
The reset input can be normally open or normally closed. User parameter 6M to select the configuration.
CAUTION
Do not apply voltage to the control input terminals. These are active 24 VDC inputs and must be
controlled with potential free contacts.
Cables to the control inputs must be segregated from mains voltage and motor cabling.
The bus bars on models EMX3-0360C ~ EMX3-1600C can be adjusted for top or bottom input and output as
required. For step-by-step instructions on adjusting the bus bars, contact your supplier.
NOTE
For personnel safety, the power terminals on models up to EMX3-0105B are protected by snap-off tabs.
When using large cables, it may be necessary to break off these tabs.
Models which are internally bypassed do not require an external bypass contactor.
CAUTION
When connecting the EMX3 in inside delta configuration, always install a main contactor or shunt trip
circuit breaker.
3.6 Fuses
Semiconductor fuses can be used with the EMX3 for Type 2 coordination and to reduce the potential for damage to
SCRs from transient overload currents. For fuse information on 690 VAC units contact your local supplier.
Model SCR I2t Bussmann Fuse Bussmann Ferraz Fuse Ferraz Fuse Ferraz Fuse
(A2s) Square Body Fuse British (HSJ) European Style N. American Style
(170M) Style (PSC 690) (PSC 690)
(BS88)
EMX3-0023B 1150 170M1314 63FE HSJ40 ** 6.9URD30D11A0050 A070URD30XXX0063
EMX3-0043B 8000 170M1318 120FEE HSJ60 6.9URD30D11A0125 A070URD30XXX0125
EMX3-0050B 10500 170M1318 200FEE HSJ80 ** 6.9URD30D11A0125 A070URD30XXX0125
EMX3-0053B 15000 170M1318 200FEE HSJ90 ** 6.9URD30D11A0125 A070URD30XXX0125
EMX3-0076B 15000 170M1319 200FEE HSJ110 ** 6.9URD30D11A0200 A070URD30XXX0200
EMX3-0097B 51200 170M1321 280FM HSJ150 6.9URD30D11A0200 A070URD30XXX0200
EMX3-0100B 80000 170M1321 280FM HSJ175 6.9URD30D11A0200 A070URD30XXX0200
EMX3-0105B 125000 170M1321 280FM HSJ225 6.9URD30D11A0315 A070URD30XXX0315
EMX3-0145B 125000 170M2621 280FM HSJ250 6.9URD30D11A0315 A070URD30XXX0315
EMX3-0170B 320000 170M2621 450FMM HSJ300 6.9URD30D11A0315 A070URD30XXX0315
EMX3-0200B 320000 170M2621 450FMM HSJ350 6.9URD31D11A0450 A070URD30XXX0450
EMX3-0220B 320000 170M2621 450FMM HSJ350 6.9URD31D11A0450 A070URD30XXX0450
EMX3-0255C 320000 170M2621 450FMM - 6.9URD31D11A0450 A070URD30XXX0450
EMX3-0360C 238000 170M6010 - HSJ400 ** 6.9URD33D11A0630 A070URD33XXX0630
EMX3-0380C 320000 170M6011 400FMM * - 6.9URD33D11A0800 A070URD33XXX0700
EMX3-0430C 320000 170M6011 400FMM* - 6.9URD33D11A0800 A070URD33XXX0700
EMX3-0620C 1200000 170M6015 630FMM * - 6.9URD33D11A1000 A070URD33XXX1000
EMX3-0650C 1200000 170M6015 630FMM * - 6.9URD33D11A1000 A070URD33XXX1000
EMX3-0790C 2530000 170M6017 - - 6.6URD33D11A1250 A070URD33XXX1250
EMX3-0930C 4500000 170M6019 - - 6.6URD33D11A1400 A070URD33XXX1400
EMX3-1200C 4500000 170M6019 - - 6.9URD233PLAF1800 A065URD33XXX1800
EMX3-1410C 6480000 170M6021 - - 6.9URD233PLAF2200 -
EMX3-1600C 12500000 170M6018 * - - 6URD233PLAF2500 A050URD33XXX1400*
* Two parallel connected fuses required per phase.
** Two series connected fuses required per phase.
XXX Blade Type. Refer to Ferraz catalog for options.
NOTE
Adaptive Acceleration Control (XLR-8) controls the motor's speed profile, within the programmed time
limit. This may result in a higher level of current than traditional control methods.
For applications using Adaptive Acceleration Control to soft stop the motor with stop times greater than 30 seconds,
motor branch protection should be selected as follows:
• standard HRC line fuses: minimum 150% motor full load current
• motor rated line fuses: minimum rating 100/150% motor full load current
• motor control circuit breaker minimum long time setting: 150% motor full load current,
• motor control circuit breaker minimum short time setting: 400% motor full load current for 30 seconds
Non-bypassed models
NOTE
* EMX3-0255C current transformers are located on the output. Bypass terminals are labelled T1B, T2B
and T3B.
The keypad is attached to the body of the soft starter by a DB9 serial connector and two screws. The screws are
concealed behind a snap-on faceplate.
To remove the keypad:
1. On the EMX3-0023B ~ EMX3-0220B
open the EMX3's door, on EMX3-0255C
~ EMX3-1600C remove the EMX3's front
cover.
2. Insert a small screwdriver under the
faceplate, between the air vents in the side
of the starter, and use the screwdriver to
lever the faceplate off the keypad.
3. Lift the faceplate off completely.
When a keypad is connected to an EMX3, it synchronises its parameter settings with the settings in the soft starter.
Every time a different keypad is plugged into the starter, an acknowledgement
is displayed. New Display Detected
The default action is to copy the parameter settings from the keypad to the Copy Parameters
soft starter. To change the action, use the ▲ and ▼ buttons. Press STORE Display to Starter
to proceed. Starter to Display
If any of the settings in the keypad are not valid for the starter, the keypad
loads the default values.
4.2 Displays
The keypad displays a wide range of performance information about the soft starter. The top half of the screen shows
real-time information on current or motor power (as selected in parameter 8D). Use the ▲ and ▼ buttons to select
the information shown on the bottom half of the screen.
• Starter status
• Motor temperature
• Current
• Motor power
• Voltage
• Last start information
• Date and time
NOTE
Screens shown here are with the default settings.
Starter Status
The starter status screen shows details of the starter's operating status and motor current or power.
Ready
M1 000% 0000.0kW
Programmable screen
The EMX3's user-programmable screen can be configured to show the most important information for the particular
application. Use parameters 8E to 8H to select which information to display.
0.0A
Ready
0 hrs --%
Motor Temperature
The temperature screen shows which motor data set is in use, and the temperature of both motors as a percentage of
total thermal capacity. If the EMX3 is configured for use on one motor, the temperature for the secondary motor
(M2) will always show 0%.
0.0A
Primary Motor Set
M1 000% M2 000%
Current
The current screen shows real-time line current on each phase. If the RTD and ground fault protection card is fitted,
the screen will also show ground current.
0.0A
Phase currents
000.0A 000.0A 000.0A
Motor Power
The motor power screen shows motor power (kW, HP and kVA) and power factor.
0.0A
0000.0kW 0000HP
0000kVA -. - - pf
If the voltage measurement card is not installed, the motor power figures are calculated using the Mains Reference
Voltage (parameter 8N).
0.0A
YYYY MMM DD
HH:MM:SS
Performance Graph
The performance graph provides a real-time display of operating performance. Use parameters 8I~8L to select which
information to display.
For internally bypassed models the SCRs are off during run.
Menus
• Commissioning Menu
• Programming Menu
The Programming Menu lets you view and change programmable parameters that control how the EMX3 operates.
To open the Programming Menu, press the MENU button while viewing the monitoring screens.
MENU, STORE or ►: open the menu,
◄ or EXIT: cancel changes or close a menu select a menu item or confirm a change.
item
The Logs Menu provides information on events, trips and starter performance.
To open the Logs Menu, press ALT then F1 (Logs) while viewing the metering screens.
To navigate through the Logs Menu:
• to open a log, press the ► button.
• to scroll through the entries in each log, press the ▲ and ▼ buttons.
• to view details of a log entry, press the ► button.
• to return to the previous level, press the ◄ button.
• to close the Logs Menu, press ◄ repeatedly.
ALT
F2 (Tools)
To navigate through the Commissioning Menu:
• to scroll to the next or previous item, press the ▲ or ▼ button.
• to open an item for viewing, press the ► button.
• to return to the previous level, press the ◄ button.
• to close the Commissioning Menu, press ◄ repeatedly.
Simulation Tools
Software simulation functions let you test the soft starter's operation and control circuits without connecting the soft
starter to mains voltage. The EMX3 has three simulation modes:
• Run simulation: simulates a motor starting, running and stopping to confirm that the soft starter and
associated equipment have been installed correctly.
• Protection simulation: simulates activation of each protection mechanism to confirm that the soft starter and
associated control circuits are responding correctly.
• Output signal simulation: simulates output signalling to confirm that outputs and associated control circuits are
operating correctly.
The simulation tools are accessed via the Commissioning Menu. The simulations are only available when the soft
starter is in Ready state, control voltage is available and the keypad is active.
NOTE
Access to the simulation tools is protected by the security access code.
Default access code is 0000.
• Run Simulation
The run simulation simulates starting, running and stopping the motor. The run simulation is a safe method of
confirming that the soft starter, external switchgear and control equipment have been installed and configured
correctly.
You can end the simulation at any time by pressing EXIT. The keypad will return to the Commissioning Menu.
5. Press ►. The EMX3 simulates its pre-start checks and closes Run Simulation
the main contactor (if installed). The Run LED flashes. Pre-Start Checks
STORE to Continue
6. Press ►. The EMX3 simulates starting. The Run LED flashes. Run Simulation
Starting X:XXs
STORE to Continue
7. Press ►. The EMX3 simulates running. The Run LED stays on Run Simulation
without flashing and the bypass contactors close. Running
Apply Stop Signal
8. Press STOP or activate the stop input. The EMX3 simulates Run Simulation
stopping. The Run LED flashes. Stopping X:XXs
STORE to Continue
The EMX3 can simulate each different protection, in order to confirm that the soft starter is responding correctly and
reporting the situation on the display and across the communication network.
To use the protection simulation:
1. Open the Commissioning Menu.
2. Scroll to Protection Simulation and press ►.
NOTE
If the protection trips the soft starter, reset before simulating another protection. If the protection action
is set to 'Warning or Log', no reset is required.
If the protection is set to 'Warning & Log', the warning message can be viewed only while the
'Menu/Store' button is pressed.
If the protection is set to 'Log only', nothing appears on the screen but will appear in the log.
The keypad allows the user to simulate output signalling in order to confirm that the output relays are operating
correctly.
NOTE
To test operation of the flags (motor temperature and low/high current), set an output relay to the
appropriate function and monitor the relay's behaviour.
To use the signal simulation:
1. Open the Commissioning Menu.
2. Scroll to Output Signalling Simulation and press ►.
4. Use the ▲ and ▼ buttons to turn the signal on and off. Prog Relay A
To confirm correct operation, monitor the state of the output. Off
On
The analog output simulation uses the ▲ and ▼ buttons to change the current at the analog output terminals.
Analog Output A
0%
4.0mA
Attach a current measuring device to the analog output terminals. Use the ▲ or ▼ button to adjust the percentage
value on the display. The current measuring device should indicate the same level of current as shown on the display.
If the input/output expansion card is fitted, the simulation can also be used to test the operation of Relays D, E, F and
Analog Output B.
This screen shows the state of the Motor Thermistors and RTD. Temp Sensors State
If the RTD/Ground Fault expansion card is fitted, this will show the status of Thermistor: X
RTDs 2 ~ 7.
RTDs 1-7:XXXXXXX
S = Shrt H=Hot C=Cld O=Opn
• Digital I/O State
Digital I/O State Digital I/O State
This screen shows the current status of the Digital I/O in order. The screen Inputs: 01100000
shot shows Input C23-24 as open (0) Input C31~32 as closed (1). The
outputs follow a similar pattern. Outputs: 00001000
Trip Log
The trip log stores details of the eight most recent trips, including the date and time the trip happened. Trip 1 is the
most recent and trip 8 is the oldest stored trip.
To open the trip log:
1. Open the Logs Menu.
2. Scroll to trip log and press ►.
3. Use the ▲ and ▼ buttons to select a trip to view, and press ► to display details.
To close the log and return to the main display, press ◄ twice.
Event Log
The event log stores time-stamped details of the starter's 99 most recent events (actions, warnings and trips), including
the date and time of the event. Event 1 is the most recent and event 99 is the oldest stored event.
To open the event log:
1. Open the Logs Menu.
2. Scroll to event log and press ►.
3. Use the ▲ and ▼ buttons to select an event to view, and press ► to display details.
4. To close the log and return to the main display, press ◄ twice.
Performance Counters
The performance counters store statistics on the starter's operation:
• Hours run (lifetime and since counter last reset)
• Number of starts (lifetime and since counter last reset)
• Motor kWh (lifetime and since counter last reset)
• Number of times the thermal model has been reset
The resettable counters (hours run, starts and motor kWh) can only be reset if the Adjustment Lock (parameter 15B)
is set to Read & Write.
Section 6 Operation
NOTE
XLR-8, Brake and Jog functions operate only with in-line connected motors.
To Control Use
Motor Start Current Constant Current
Motor/Load Acceleration or Deceleration XLR-8 Adaptive Acceleration Control
Constant Current
Constant current is the traditional form of soft starting, which raises the current from zero to a specified level and
keeps the current stable at that level until the motor has accelerated.
Constant current starting is ideal for applications where the start current must be kept below a particular level.
Current Ramp
Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3), over an
extended period of time (2).
NOTE
XLR-8 will control the load according to the programmed profile. Start current will vary according to the
selected acceleration profile and start time.
XLR-8 cannot start the motor faster than a direct on-line (DOL) start.
If replacing a motor connected to an EMX3 programmed for XLR-8 starting, or if the starter has been
tested on a different motor prior to actual installation, it will be necessary for the EMX3 to learn the
characteristics of the new motor. To force the EMX3 into learn mode, make an adjustment to parameter
2K Adaptive Control Gain as follows:
Kickstart
Kickstart provides a short boost of extra torque at the beginning of a start, and can be used in conjunction with current
ramp or constant current starting.
Kickstart can be useful to help start loads that require high breakaway torque but then accelerate easily (for example
flywheel loads such as presses).
Coast to Stop
Coast to stop lets the motor slow at its natural rate, with no control from the soft starter. The time required to stop
will depend on the type of load.
Timed voltage ramp stopping can be useful for applications where the stop time needs to be extended, or to avoid
transients on generator set supplies.
1. Select Adaptive Control from the Stop Mode menu (parameter 2H)
2. Set the desired Stop Time (parameter 2I)
3. Select the required Adaptive Stop Profile (parameter 2J)
XLR-8 Adaptive stop profile (parameter 2J):
1. Early deceleration
2. Constant deceleration
3. Late deceleration
4. Stop ramp time (parameter 2B)
NOTE
Pump stopping: The hydraulic characteristics of pump systems vary considerably. This variation means the
ideal deceleration profile and stop time will vary from application to application. The table below
provides guidelines on selecting between XLR-8 deceleration profiles, however trials of the three XLR-8
deceleration profiles will identify the best profile for a given application.
NOTE
XLR-8 will control the load according to the programmed profile. Stopping current will vary according to
the selected deceleration profile and stop time.
XLR-8 cannot stop the motor faster than a coast to stop. Use Brake for shorter stopping times.
If replacing a motor connected to an EMX3 programmed for XLR-8 starting, or if the starter has been
tested on a different motor prior to actual installation, it will be necessary for the EMX3 to learn the
characteristics of the new motor. To force the EMX3 into learn mode, make an adjustment to parameter
2K Adaptive Control Gain as follows:
Brake
Brake reduces the time the motor requires to stop. This is recommended for medium to low inertia loads. For high
inertia loads soft braking is recommended.
• Brake
When brake is selected, the EMX3 uses DC injection to slow the motor.
The EMX3 braking:
• Does not require the use of a DC brake contactor
• Controls all three phases so that the braking currents and associated heating is evenly distributed
through the motor.
NOTE
Brake operation causes motor heating. If you are using brake, enable the motor temperature check
(parameter 4N) or allow sufficient restart delay (parameter 4M).
During braking an increased noise level from the motor may be audible. This is a normal part of motor
braking.
In some applications the available jog torque may not be sufficient to accelerate the motor as required. In these
applications a customised forward jog profile can be programmed using secondary motor setting Start/Stop Modes 2 in
parameter group 10. Please refer to "EMX3 Forward Jog" (Application Note: 710-06355-00).
WARNING
Slow speed running is not intended for continuous operation due to reduced motor cooling.
The simulation tools and counter resets are also protected by the security access code.
The default access code is 0000.
On the display the highlighted values are suggested values and the values indicated by a ► are the loaded values.
Always set parameter 1A Motor FLC to match the motor's nameplate full load current. The suggested value for motor
FLC is the starter's minimum FLC.
▼
8 Display ► 8A Language English
◄ 8B F1 Button Action Auto-Start/Stop Menu
8C F2 Button Action None
8D Display A or kW Current
8E User-Scrn – Top L Starter State
8F User-Scrn – Top R Blank
8G User-Scrn – Btm L Hours Run
8H User-Scrn – Btm R Analog Input
▼
5 Auto-Reset Trips ► 5A Auto-Reset Action Do Not Auto-Reset
◄ 5B Maximum Resets 1
▲ 5C Reset Dly - Grp A & B 00m:05s
5D Reset Dly - Grp C 05 m
▼
6 Inputs ► 6A Input A Function Motor Set Select
◄ 6B Input A Name Input Trip
▲ 6C Input A Trip Always Active
6D Input A Trip Dly 0m:00s
6E Input A Initial Dly 00m:00s
6F Input B Function Input Trip (N/O)
6G Input B Name Input Trip
6H Input B Trip Always Active
6I Input B Trip Dly 0m:00s
6J Input B Initial Dly 00m:00s
6E Input C Function Motor Set Select
6L Input D Function Emergency Stop
6M Remote Reset Logic Normally Closed
6N Analog Input Trip Do Not Trip
6O Analog Input Scale 2-10 V
6P Analog Trip Point 50%
6Q LCL/RMT Button LCL/RMT Anytime
6R Comms in Remote Enable Cntrl in RMT
▼
7 Outputs ► 7A Relay A Function Main Contactor
◄ 7B Relay A On Delay 0m:00s
▲ 7C Relay A Off Delay 0m:00s
7D Relay B Function Run
7E Relay B On Delay 0m:00s
7F Relay B Off Delay 0m:00s
7G Relay C Function Trip
7H Relay C On Delay 0m:00s
7I Relay C Off Delay 0m:00s
7J Relay D Function Off
7K Relay E Function Off
7L Relay F Function Off
7M Low Current Flag 50%
7N High Current Flag 100%
7O Motor Temp Flag 80%
7P Analog Output A Current (% FLC)
7Q Analog A Scale 4-20 mA
7R Analog A Max Adj 100%
7S Analog A Min Adj 000%
7T Analog Output B Current (% FLC)
7U Analog B Scale 4-20 mA
7V Analog B Max Adj 100%
7W Analog B Min Adj 000%
▼
8 Display ► 8A Language English
◄ 8B F1 Button Action Auto-Start/Stop Menu
▲ 8C F2 Button Action None
8D Display A or kW Current
8E User Scrn – Top L Starter State
8F User Scrn – Top R Blank
8G User Scrn – Btm L Hours Run
8H User Scrn – Btm R Analog Input
8I Graph Data Current (% FLC)
8J Graph Timebase 10 seconds
8K Graph Max Adj 400%
8L Graph Min Adj 000%
8M Current Calibrat 100%
8N Mains Ref Volt 400 V
▼
9 Motor Data-2 ► 9A Dual Thrml Model Single
◄ 9B Motor FLC-2 Model Dependent
▲ 9C Lock Rotor Time-2 0m:10s
9D Lock Rotor Crnt-2 600%
9E Mtr Srvc Factor-2 105%
▼
10 Start/Stop Modes-2 ► 10A Start Mode-2 Adaptive Control
◄ 10B Start Ramp-2 0m:10s
▲ 10C Initial Current-2 350%
10D Current Limit-2 350%
10E Adaptv Start Prof-2 Constant Acceleration
10F Kickstart Time-2 0000 ms
10G Kickstart Lvl-2 500%
10H Stop Mode-2 Coast To Stop
10I Stop Time-2 0m:00s
10J Adaptv Stop Prof-2 Constant Deceleration
10K Adaptv Ctrl Gain-2 75%
10L Brake Torque-2 20%
10M Brake Time-2 0m:01s
▼
11 RTD Temperatures ► 11A RTD A Trip Temp 50 °C
◄ 11B RTD B Trip Temp 50 °C
▲ 11C RTD C Trip Temp 50 °C
11D RTD D Trip Temp 50 °C
11E RTD E Trip Temp 50 °C
11F RTD F Trip Temp 50 °C
11G RTD G Trip Temp 50 °C
▼
12 Slip-Ring Motors ► 12A Mtr Data-1 Ramp Single Ramp
◄ 12B Mtr Data-2 Ramp Single Ramp
▲ 12C Changeover Time 150 ms
12D Slip-Ring Retard 50%
▼
15 Advanced ► 15A Access Code 0000
(Requires Access Code. ◄ 15B Adjustment Lock Read & Write
Default: 0000) 15C Emergency Run Disable
▲ 15D Shorted SCR Actn 3-Phase Control Only
▼
16 Protection Action ► 16A Motor Overload Trip Starter
◄ 16B Excess Start Time Trip Starter
▲ 16C Undercurrent Trip Starter
16D Inst Overcurrent Trip Starter
16E Current Imbalance Trip Starter
16F Frequency Trip Starter
16G Input A Trip Trip Starter
16H Input B Trip Trip Starter
16I Motor Thermistor Trip Starter
16J Starter/Comms Trip Starter
16K Network Comms Trip Starter
16L Heatsink Overtemp Trip Starter
16M Battery/Clock Trip Starter
16N Ground Fault Trip Starter
16O RTD A Overtemp Trip Starter
16P RTD B Overtemp Trip Starter
16Q RTD C Overtemp Trip Starter
16R RTD D Overtemp Trip Starter
16S RTD E Overtemp Trip Starter
16T RTD F Overtemp Trip Starter
16U RTD G Overtemp Trip Starter
▼
20 Restricted ► Factory Use Only
◄
7.7 Load/Save Settings
The Load/Save Settings menu requires an access code and allows users to:
• Load the EMX3's parameters with default values
• Reload previously saved parameter settings from an internal file
• Save the current parameter settings to an internal file
NOTE
The saved files and current operating settings are stored in both the keypad and in the soft starter. The
keypad will prompt you to synchronise the settings whenever it is plugged into a new EMX3.
In addition to the factory default values file, the EMX3 can store two user-defined parameter files. These files contain
default values until a user file is saved.
To load or save parameter settings:
1 Motor Data-1
The parameters in Motor Data-1 configure the soft starter to match the connected motor. These parameters describe
the motor's operating characteristics and allow the soft starter to model the motor's temperature.
1A – Motor FLC
Range: Model dependent
Description: Motor Full Load Current matches the starter to the connected motor's full load current.
Set to the full load current (FLC) rating shown on the motor nameplate.
2 Start/Stop Modes-1
2A – Start Mode
Options: Constant Current
Adaptive Control (Default)
Description: Selects the soft start mode.
2C – Initial Current
Range: 100% - 600% FLC (Default: 350%)
Description: Sets the initial start current level for current ramp starting, as a percentage of motor full
load current. Set so that the motor begins to accelerate immediately after a start is
initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
2D – Current Limit
Range: 100% - 600% FLC (Default: 350%)
Description: Sets the current limit for constant current and current ramp soft starting, as a percentage of
motor full load current.
2F, 2G – Kickstart
Parameter 2F – Kickstart Time
Range: 0 – 2000 (milliseconds) (Default: 0000 milliseconds)
Description: Sets the kickstart duration. A setting of 0 disables kickstart.
Parameter 2G – Kickstart Level
Range: 100% - 700% FLC (Default: 500%)
Description: Sets the level of the kickstart current.
NOTE
Kickstart subjects the mechanical equipment to increased torque levels. Ensure
the motor, load and couplings can handle the additional torque before using this
feature.
2H – Stop Mode
Options: Coast To Stop (Default)
TVR Soft Stop
Adaptv Control
Brake
Description: Selects the stop mode.
2I – Stop Time
Range: 0:00 - 4:00 (minutes:seconds) (Default: 0 seconds)
Description: Sets the time for soft stopping the motor using timed voltage ramp or XLR-8 adaptive
acceleration control.
If a main contactor is installed, the contactor must remain closed until the end of the stop
time. Use the run output (terminals 23, 24) to control the main contactor.
2L, 2M – Brake
Brake uses DC injection to actively slow the motor.
Parameter 2L Brake Torque
Range: 20 - 100% (Default: 20%)
Description: Sets the amount of brake torque the EMX3 will use to slow the motor.
Parameter 2M Brake Time
Range: 1 - 30 (seconds) (Default: 1 second)
Description: Sets the duration for DC injection during a braking stop.
NOTE
Parameter 2M is used in conjunction with parameter 2I. Refer to Section 6.3 for details.
3 Auto-Start/Stop
The EMX3 can be programmed to start and stop automatically, after a specified delay or at a specified time of day.
Auto-start and auto-stop can be set separately.
NOTE
This function should not be used in conjunction with Remote and 2 wire control.
The soft starter will still accept start and stop commands from the keypad, remote inputs or serial
communication network. To disable local or remote control, use parameter 6Q.
3A, 3B – Auto-Start
Parameter 3A Auto-Start Type
Options: Off (Default) The soft starter will not auto-start.
Timer The soft starter will auto-start after a delay from the next
stop, as specified in parameter 3B.
Clock The soft starter will auto-start at the time programmed in
parameter 3B.
Description: Selects whether the soft starter will auto-start after a specified delay, or at a time of day.
Parameter 3B Auto-Start Time
Range: 00:01 - 24:00 (Default: 1 minute)
Description: Sets the time for the soft starter to auto-start, in 24 hour clock format.
3C, 3D – Auto-Stop
Parameter 3C Auto-Stop Type
Options: Off (Default) The soft starter will not auto-stop.
Timer The soft starter will auto-stop after a delay from the next
start, as specified in parameter 3D.
Clock The soft starter will auto-stop at the time programmed in
parameter 3D.
Description: Selects whether the soft starter will auto-stop after a specified delay, or at a time of day.
Parameter 3D Auto-Stop Time
Range: 00:01 - 24:00 (Default: 1 minute)
Description: Sets the time for the soft starter to auto-stop, in 24 hour clock format.
4 Protection Settings
These parameters determine when the soft starter's protection mechanisms will activate. The activation point for each
protection mechanism can be set to suit the installation.
The soft starter responds to protection events by tripping, warning, or writing the event to the event log. The
response is determined by the Protection Action settings (parameter group 16). The default response is a trip.
NOTE
The protection settings are vital for safe operation of the soft starter and motor.
Defeating the protection may compromise the installation and should only be done in
the case of emergency.
4C, 4D – Undercurrent
The EMX3 can be configured to trip if the average current of all three phases drops below a specified level
while the motor is running.
Parameter 4C Undercurrent
Range: 0% - 100% (Default: 20%)
Description: Sets the trip point for undercurrent protection, as a percentage of motor full load current.
Set to a level between the motor's normal working range and the motor's magnetising (no
load) current (typically 25% to 35% of full load current). A setting of 0% disables
undercurrent protection.
Parameter 4D Undercurrent Dly
Range: 0:00 - 4:00 (minutes:seconds) (Default: 5 seconds)
Description: Slows the EMX3's response to undercurrent, avoiding trips due to momentary fluctuations.
4G – Phase Sequence
Range: Any sequence (Default)
Positive only
Negative only
Description: Selects which phase sequences the soft starter will allow at a start. During its pre-start
checks, the starter examines the sequence of the phases at its input terminals and trips if
the actual sequence does not match the selected option.
NOTE
Running a motor outside it's specified frequency for long periods can cause damage
and premature failure.
NOTE
If the mains frequency drops below 35 Hz, the starter will trip immediately.
4M – Restart Delay
Range: 00:01 - 60:00 (minutes:seconds) (Default: 10 seconds)
Description: The EMX3 can be configured to force a delay between the end of a stop and the beginning
of the next start. During the restart delay period, the display shows the time remaining
before another start can be attempted.
NOTE
The restart delay is measured from the end of each stop. Changes to the
restart delay setting take effect after the next stop.
NOTE
Ground fault protection is only available if the RTD and ground fault protection card is fitted.
5 Auto-Reset Trips
The EMX3 can be programmed to automatically reset certain trips, which can help minimise operating downtime.
Trips are divided into three categories for auto-reset, depending on the risk to the soft starter:
Group A Current Imbalance
Phase loss
Power loss
Mains frequency
B Undercurrent
Instantaneous overcurrent
Input A trip
Input B trip
C Motor overload
RTD temperature trips
Motor thermistor
Starter overtemperature
Other trips cannot be automatically reset.
5A – Auto-Reset Action
Options: Do Not Auto-Reset (Default)
Reset Group A
Reset Group A & B
Reset Group A, B & C
Description: Selects which trips can be auto-reset.
5B – Maximum Reset
Range: 1 - 5 (Default: 1)
Description: Sets how many times the soft starter will auto-reset, if it continues to trip. The reset
counter increases by one each time the soft starter auto-resets, and decreases by one after
each successful start/stop cycle.
6 Inputs
The EMX3 has two programmable inputs, which allow remote control of the soft starter. If required, two extra inputs
are available on the input/output expansion card.
6A – Input A Function
Options: Motor Set Select (Default) The EMX3 can be configured with two separate sets of
motor data. The primary motor data is programmed using
parameters 1A to 2-M. The secondary motor data is
programmed using parameters 9A to 2-M.
To use the secondary motor data, parameter 6A must be
set to Motor Set Select and C53-C54 must be closed
when a start command is given. The EMX3 checks which
motor data to use at a start, and will use that motor data
for the entire start/stop cycle.
Input Trip (N/O) Input A can be used to trip the soft starter. When
parameter 6A is set to Input Trip (N/O), a closed circuit
across C53-C54 trips the soft starter (refer to parameters
6C, 6D, 6E).
Input Trip (N/C) When parameter 6A is set to Input Trip (N/C), an open
circuit across C53-C54 trips the soft starter (refer to
parameters 6C, 6D, 6E).
Local/Remote Select Input A can be used to select between local and remote
control, instead of using the LCL/RMT button on the
keypad. Selecting this option disables the LCL/RMT button,
and the soft starter will ignore any Local/Remote select
command from the serial communications network.
An open circuit across the input selects local control and a
closed circuit selects remote control.
To use Input A to select between local and remote
control, parameter 6Q must be set to Button Always
Active or Button Active When Off.
Emergency Run In emergency run the soft starter continues to run until
stopped, ignoring all trips and warnings (refer to parameter
15C for details).
Closing the circuit across C53-C54 activates emergency
run.
Opening the circuit ends emergency run and the EMX3
stops the motor.
Emergency Stop The EMX3 can be commanded to emergency stop the
motor, ignoring the soft stop mode set in parameter 2H.
When the circuit across C53-C54 is opened, the soft
starter allows the motor to coast to stop.
Jog Forward Activates jog operation in a forward direction.
Jog Reverse Activates jog operation in reverse direction.
Description: Selects the function of Input A.
6B – Input A Name
Options: Input Trip (Default) No Flow
Low Pressure Emergency Stop
High Pressure Controller
Pump Fault PLC
Low Level Vibration Alarm
High Level
Description: Selects a message for the keypad to display when Input A is active.
6Q – LCL/RMT Button
Options: LCL/RMT Anytime (Default) LCL/RMT button is always enabled.
LCL/RMT When Off LCL/RMT button is enabled when the starter is off.
Local Control Only All remote inputs are disabled.
Remote Control Only Local control buttons (START, RESET, LCL/RMT)
are disabled.
Description: The Local/Remote button selects when the LCL/RMT button can be used to switch
between local and remote control, and enables or disables the local control buttons and
remote control inputs. The STOP button on the keypad is always enabled.
CAUTION
The STOP button on the keypad is always enabled. When using two-wire
remote control, the soft starter will restart immediately if the remote start input
is still active.
6R – Comms in Remote
Options: Disable Ctrl in RMT
Enable Ctrl in RMT (Default)
Description: Selects whether the starter will accept Start, Stop and Reset commands from the serial
communication network when in Remote mode. The Force Comms Trip, Local/Remote
Control and Test Start commands are always enabled.
7 Outputs
The EMX3 has three programmable outputs, which can be used to signal different operating conditions to associated
equipment. Three additional outputs are available on the input/output expansion card.
7A – Relay A Function
Options: Off Relay A is not used.
Main Contactor (Default) The relay closes when the EMX3 receives a
start command, and remains closed as long as
the motor is receiving voltage.
Run The relay closes when the starter changes to
run state.
Trip The relay closes when the starter trips.
Warning The relay closes when the starter issues a
warning.
Low Current Flag The relay closes when the low current flag
activates (refer to parameter 7M Low Current
Flag).
High Current Flag The relay closes when the high current flag
activates (refer to parameter 7N High Current
Flag).
Motor Temp Flag The relay closes when the motor temperature
flag activates (refer to parameter 7O Motor
Temperature Flag).
Input A Trip The relay closes when Input A activates to trip
the soft starter.
Input B Trip The relay closes when Input B activates to trip
the soft starter.
Motor Overload The relay closes when the starter trips on
Motor Overload.
Current Imbalance The relay closes when the starter trips on
Current Imbalance.
Undercurrent The relay closes when the starter trips on
Undercurrent.
Inst Overcurrent The relay closes when the starter trips on
Instantaneous Overcurrent.
Frequency The relay closes when the starter trips on
Frequency.
Ground Fault The relay closes when the starter trips on
Ground Fault.
Heatsink Overtemp The relay closes when the starter trips on
Heatsink Overtemperature.
Phase Loss The relay closes when the starter trips on
Phase Loss.
Motor Thermistor The relay closes when the starter trips on
Motor Thermistor.
Changeover Contactor The relay closes when the high rotor resistance
current ramp has reached full voltage, allowing
use with a slip-ring motor.
Description: Selects the function of Relay A (normally open).
8 Display
These parameters allow the keypad to be tailored to individual users' requirements.
8A – Language
Options: English (Default)
Chinese
Description: Selects which language the keypad will use to display messages and feedback.
8D – Display A or kW
Options: Current (Default)
Motor kW
Description: Selects whether the EMX3 will display current (amperes) or motor kilowatts on the main
monitoring screen.
8M – Current Calibrat
Range: 85% - 115% (Default: 100%)
Description: Motor Current Calibration calibrates the soft starter's current monitoring circuits to match
an external current metering device.
Use the following formula to determine the necessary adjustment:
Current shown on soft starter display
Calibration (%) =
Current measured by external device
66 A
eg 102% =
65 A
9 Motor Data-2
The EMX3 can support two different starting and stopping motor data sets.
• To use the EMX3 with two separate motors (such as a duty-standby configuration), use parameter 9A to
select dual thermal modelling and configure parameters 9B~9E to suit the second motor.
• To use the EMX3 with two different motor data sets for the same motor (for dual speed motors or
applications where starting conditions may vary), use parameter 9A to select a single thermal model, and
configure the starting and stopping profiles as required in parameters 10A~10G. The soft starter will ignore
parameters 9B~9E and will use settings from the primary motor.
To select the secondary motor data set, a programmable input must be configured to parameter set selection
(parameters 6A and 6F) and the input must be active when the soft starter receives a start signal.
NOTE
You can only choose which motor data set to use while the soft starter is stopped.
10 Start/Stop Modes-2
11 RTD Temperatures
The EMX3 has one PT100 RTD input and can be fitted with another six RTD inputs by using the RTD and ground
fault protection card. The inputs can trip the soft starter when the temperature exceeds a specified point, and different
trip temperatures can be set for each input.
The RTD inputs B ~ G are only available if the RTD and ground fault protection card have been installed.
12 Slip-Ring Motors
These parameters allow the soft starter to be configured for use with a slip-ring motor.
15 Advanced
NOTE
Changes to the Adjustment Lock setting take effect only after the Programming Menu has been
closed.
CAUTION
PowerThrough uses a two-phase soft start technology and additional care is required when sizing
circuit breakers and protection. Contact your local supplier for assistance.
PowerThrough operation does not support XLR-8 adaptive acceleration control soft starting or
soft stopping. In PowerThrough, the EMX3 will automatically select constant current soft starting
and timed voltage ramp soft stopping. If PowerThrough is enabled, parameters 2C and 2D must
be set appropriately.
NOTE
PowerThrough only operates with in-line connected motors.
16 Protection Action
These parameters define how the soft starter will respond to different protection events. The soft starter can trip,
issue a warning, or ignore different protection events as required. All protection events are written to the event log.
The default action for all protections is to trip the soft starter. Protections 16-N Ground Fault and 16-P ~ 16-V are
only available if the RTD and ground fault protection card have been installed.
CAUTION
Defeating the protection can compromise the soft starter, motor and installation.
20 Restricted
These parameters are restricted for AuCom internal use and are not available to the user.
Section 8 Troubleshooting
Motor Connection The motor is not connected correctly to the soft starter.
Check each output phase of the soft starter for power circuit continuity.
Related parameters: none
Motor Thermistor The resistance at the thermistor input has exceeded 3.6 kΩ or fallen below 100 Ω for more
than one second.
The motor winding has overheated. Identify the cause of the overheating and allow the
motor to cool before restarting.
If you are not using a thermistor, you must attach a 1.2 kΩ resistor across terminals B4-B5.
Related parameters: 16-I
Network Comms The network master has sent a trip command to the starter, or there may be a network
communication problem.
Check the network for causes of inactivity.
Related parameters: 16K
Phase Sequence The phase sequence on the soft starter's input terminals (L1, L2, L3) is not valid.
Check the phase sequence on L1, L2, L3 and ensure the setting in parameter 4G is suitable
for the installation.
Related parameters: 4G
Power Loss The EMX3 is not receiving mains supply on one or more phases. Check that the mains
supply is connected to L1, L2, L3 and all fuses are healthy.
Check that the main contactor closes when a start command is given, and remains closed
until the end of a soft stop.
Related parameters: 20B
Starter/Comms There is a problem with the connection between the soft starter and the serial
communications module, or the communications module has failed. Remove and reinstall
the module.
Contact your local supplier if the problem persists.
Related parameters: 16J
Undercurrent The motor has experienced a sharp drop in current, caused by loss of load. Causes can
include broken components (shafts, belts or couplings), or a pump running dry.
Related parameters: 4C, 4D, 16C
• The load may be jammed. Check the load for severe overloading or
a locked rotor situation.
Erratic motor operation. • The SCRs in the EMX3 require at least 5 A of current to latch. If you
are testing the soft starter on a motor with full load current less than
5 A, the SCRs may not latch correctly.
Soft stop ends too quickly. • The soft stop settings may not be appropriate for the motor and load.
Review the settings of parameters 2H, 2I, 10H and 10I.
• If the motor is very lightly loaded, soft stop will have limited effect.
Corrupted text shown on keypad • The keypad may not be screwed sown, resulting in an intermittent
display. connection. Screw down the keypad or hold squarely in place.
XLR-8 adaptive acceleration • Check if you have a 6-wire installation. Only operate in 3-wire.
control, DC brake and Jog
functions not working
A reset does not occur after an • The remote 2-wire start signal must be removed and reapplied for a
Auto-Reset, when using a remote re-start.
2-wire control.
Remote start/stop command is • Auto Start/Stop function should only be used in LOCAL mode or in
overriding Auto Start/Stop settings tandem with REMOTE mode, 3 and 4-wire control.
when using remote 2-wire control.
After selecting XLR-8 the motor • The first XLR-8 is current limit so that the starter can learn from the
used an ordinary start and/or the motor characteristics. Subsequent starts use XLR-8.
second start was different to the
first.
Non-resettable THERMISTOR • The Thermistor input is enabled once a link is fitted and short circuit
FAIL trip, when there is a link protection has activated. Place a 1k2 ohm resistor across the
between Thermistor input B4/B5. Thermistor input.
Display is distorted • Check that the keypad has not be screwed down to tight. Loosen
screws off slightly.
Parameter settings cannot be • Make sure you are saving the new value by pressing the STORE
stored. button after adjusting a parameter setting. If you press ◄, the change
will not be saved.
• Check that the adjustment lock (parameter 15B) is turned off. If the
adjustment lock is on, settings can be viewed but not changed. You
need to know the security access code to change the adjustment lock
setting.
• The EEPROM may be faulty on the keypad or the power interface
PCB. A faulty EEPROM will also trip the soft starter, and the keypad
will display the message EEPROM Fail. Contact your local supplier for
advice.
Section 9 Appendix
9.1 Specifications
Model Codes
Contact your local supplier for ratings under operating conditions not covered by the above ratings charts.
A B C D E Weight
Model mm mm mm mm mm kg
(inches) (inches) (inches) (inches) (inches) (lbs)
EMX3-0023B
EMX3-0043B 192.2 3.2
EMX3-0050B (7.57) (7.05)
EMX3-0053B 156.4 124.0 294.6 278.0
EMX3-0076B (6.16) (4.88) (11.60) (10.94) 3.5 (7.22)
EMX3-0097B 222.7
4.8
EMX3-0100B (8.77)
(10.58)
EMX3-0105B
EMX3-0145B
EMX3-0170B 282 250 438 380 250 16
EMX3-0200B (11.10) (9.84) (17.24) (14.96) (9.84) (35.27)
EMX3-0220B
EMX3-0255C 390 (15.35) 320 (12.60) 417 (16.42) 400 (15.75) 281 (11.06) 25 (55.12)
EMX3-0360C
EMX3-0380C
EMX3-0430C
430 320 545 522 299 50.5
EMX3-0620C
(16.93) (12.60) (21.46) (20.55) (11.77) (111.33)
EMX3-0650C
EMX3-0790C
EMX3-0930C
EMX3-1200C
574 500 750 727 361 136
EMX3-1410C (22.60) (19.69) (29.53) (28.62) (14.21) (299.83)
EMX3-1600C
NOTE
For EMX3-0145B ~ EMX3-1600C, dimensions A and C are the unit footprint. Bus bars are not included as
this dimension will vary with bus bar configuration.
Heat Dissipation
During start .................................................................................................................................................................................... 4.5 watts per ampere
During run
EMX3-0023B ~ EMX3-0053B ......................................................................................................................................... ≤ 39 watts approx
EMX3-0076B ~ EMX3-0105B ........................................................................................................................................ ≤ 51 watts approx
EMX3-0145B ~ EMX3-0220B ..................................................................................................................................... ≤ 120 watts approx
During run
EMX3-0255C ~ EMX3-0930C .............................................................................................................. 4.5 watts per ampere approx
EMX3-1200C ~ EMX3-1600C .............................................................................................................. 4.5 watts per ampere approx
Certification
C9 ................................................................................................................................................................................................................ IEC 60947-4-2
UL/ C-UL .................................................................................................................................................................................................... UL 508, UL 347
EMX3-0023B ~ EMX3-0105B ................................................................................................................................Indoor, Enclosed. Type 1
EMX3-0145B ~ EMX3-1600C ..........................................................................................................................................Indoor, Open Type.
CE .................................................................................................................................................................................................................. IEC 60947-4-2
CCC ........................................................................................................................................................................................................................ GB 14048-6
Marine (EMX3-0023B ~ EMX3-0220B only) ................................................................................... Lloyds Marine No 1 Specification
RoHS .................................................................................................................................................... Compliant with EU Directive 2002/95/EC
9.2 Accessories
Communication Modules
EMX3 soft starters support network communication using the Profibus, DeviceNet and Modbus RTU protocols, via an
easy-to-install communications module.
• Input/Output
PC Software
WinMaster PC software provides monitoring, programming and control of up to 99 EMX3 soft starters.
A Modbus communication module is required for each EMX3 to use WinMaster.
6 Inputs
6A Input A Function
6B Input A Name
6C Input A Trip
6D Input A Trip Delay
6E Input A Initial Delay
6F Input B Function
6G Input B Name
6H Input B Trip
6I Input B Trip Delay
6J Input B Initial Delay
6E Input C Function
6L Input D Function
6M Remote Reset Logic
6N Analog Input Trip
6O Analog Input Scale
6P Analog Trip Point
6Q Local/Remote Button
6R Comms Control in Remote Mode
7 Outputs
7A Relay A Function
7B Relay A On Delay
7C Relay A Off Delay
7D Relay B Function
7E Relay B On Delay
7F Relay B Off Delay
7G Relay C Function
7H Relay C On Delay
7I Relay C Off Delay
7J Relay D Function
7K Relay E Function
7L Relay F Function
7M Low Current Flag
7N High Current Flag
7O Motor Temperature Flag
7P Analog Output A Function
7Q Analog Output A Scale
7R Analog A Maximum Adjustment
7S Analog A Minimum Adjustment
7T Analog Output B Function
7U Analog Output B Scale
7V Analog B Maximum Adjustment
7W Analog B Minimum Adjustment
8 Display
8A Language
8B F1 Button Action
8C F2 Button Action
8D Display Current or Kilowatts
8E User-Programmable Screen – Top Left
8F User-Programmable Screen – Top Right
8G User-Programmable Screen – Bottom Left
8H User-Programmable Screen – Bottom Right
8I Graph Data
8J Graph Timebase
8K Graph Maximum Adjustment
8L Graph Minimum Adjustment
8M Current Calibration
8N Mains Reference Voltage
9 Motor Data-2
9A Dual Thermal Model
9B Motor Full Load Current-2
9C Locked Rotor Time-2
9D Locked Rotor Current-2
9E Motor Service Factor-2
10 Start/Stop Modes-2
10A Start Mode-2
10B Start Ramp Time-2
10C Initial Current-2
10D Current Limit-2
10E Adaptive Start Profile-2
10F Kickstart Time-2
10G Kickstart Level-2
10H Stop Mode-2
10I Stop Time-2
10J Adaptive Stop Profile-2
10K Adaptive Control Gain-2
10L Brake Torque-2
10M Brake Time-2
11 RTD Temperatures
11A RTD A Trip Temperature
11B RTD B Trip Temperature
11C RTD C Trip Temperature
11D RTD D Trip Temperature
11E RTD E Trip Temperature
11F RTD F Trip Temperature
11G RTD G Trip Temperature
12 Slip-Ring Motors
12A Motor Data-1 Ramp
12B Motor Data-2 Ramp
12C Changeover Contactor Time
12D Slip-Ring Conduction Retard
15 Advanced
15A Access Code
15B Adjustment Lock
15C Emergency Run
15D Shorted SCR Action
21 Protection Actions
16A Motor Overload
16B Excess Start Time
16C Undercurrent
16D Instantaneous Overcurrent
16E Current Imbalance
16F Frequency
16G Input A Trip
16H Input B Trip
16I Motor Thermistor
16J Starter Communication Timeout
16K Network Communication Trip
16L Heatsink Overtemperature
16M Battery/Clock Failure
16N Ground Fault
16O RTD A Overtemperature
16P RTD B Overtemperature
16Q RTD C Overtemperature
16R RTD D Overtemperature
16S RTD E Overtemperature
16T RTD F Overtemperature
16U RTD G Overtemperature
20 Restricted N/A N/A